This document provides information about a digital AC voltage relay called the LVM series made by Prok Dvs. It can monitor both under voltage and over voltage conditions in poly-phase systems. The relay uses a microcontroller to continuously display the measured voltage and provide accurate readings for balanced and unbalanced loads. It has independent contacts for under and over voltage conditions. Settings like trip time, voltage thresholds, and reset gap can be configured through an LCD display and keypad interface. The LVM series is suitable for applications like generator protection, motor protection, and monitoring voltage in power plants and distribution systems. It provides definite time protection for under voltage and over voltage faults.

Uploaded by

BALAJI U
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
890 views

LVM PDF

This document provides information about a digital AC voltage relay called the LVM series made by Prok Dvs. It can monitor both under voltage and over voltage conditions in poly-phase systems. The relay uses a microcontroller to continuously display the measured voltage and provide accurate readings for balanced and unbalanced loads. It has independent contacts for under and over voltage conditions. Settings like trip time, voltage thresholds, and reset gap can be configured through an LCD display and keypad interface. The LVM series is suitable for applications like generator protection, motor protection, and monitoring voltage in power plants and distribution systems. It provides definite time protection for under voltage and over voltage faults.

Uploaded by

BALAJI U
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

PROK DEVICES PRIVATE LIMITED

nd
B-80, 2 & 3rd Floor, KSSIDC Industrial estate, 4th Main Road,
6th Block, Rajaji Nagar, Bengaluru -560010
Ph no: 080-41480777, 080-41157700, Email: [email protected],
www.prokdvs.com, www.prokdvs.in
AC VOLTAGE RELAY
LVM SERIES
Introduction
Prok dvs make AC Digital Microcontroller Based Definite-Time Under Voltage (UV)
and Over Voltage (OV)/ Line Voltage Monitor (LVM) is a microcontroller based
voltage monitoring and supervision relay for poly-phase system. It can monitor
b o t h under voltage (UV) and over voltage (OV) conditions in the system. Both
under voltage (UV) & over voltage (OV) conditions are associated with definite
time tripping characteristics. It has wide setting range of operating time on the
occurrence of fault condition.
DIGITAL MICROCONTROLLER BASED DEFINITE TIME UNDER VOLTAGE
(UV) AND OVER VOLTAGE RELAY/ LINE VOLTAGE MONITOR(LVM)
provides wide range of time delay for healthy resumption of the operating
voltage.
FEATURES

 Site selectable system voltage


 Continuous display of measured voltage parameter
 6 character 2 line LCD display with back-lit
 Accurate reading for balanced and unbalanced load.
 Wide range of auxiliary input for both AC & DC
 Independent contacts for Under & Over voltage
 Self reset & site selectable reset gap
 Built in fixed instantaneous Under & Over voltage
 User friendly setting modes using keypads
 Low power consumption
 Tropicalized design using microcontroller & ideal for industrial environment

APPLICATION
 Monitoring & Supervision of Under and Over Voltage in power generating plants &
distribution system
 To protect Generator & AMF switchboards
 For protection of synchronous & induction motors
 For transformer feeder panel
 Protection for capacitor control panels

WORKING PRINCIPLE
All the line voltages are monitored and sensed simultaneously using three independent scale
down potential transducer. This low level ac signal is subjected to signal conditioning, which
includes surge suppressors and harmonic filter. The filtered signal is fed to the ADC of the
industrial grade microprocessor. When the sensing voltage exceeds the user set value for
under or over voltage, the relay given an output signal in the form of relay changeover for
tripping/alarming.

Setting Procedure for AC Voltage Relay (LVM Series) 3P 4W

Step1: Connect the suitable auxiliary supply in the range of 85 -275V AC/DC voltage
to the P (+) & N (-) Terminals Refer wiring diagram LVM 01/02/03 2C/O
Display shows for a while

Then display shows (if sensing 3ph voltages


Are not given)

Step2: Press key to enter the setting mode


Setting mode consists of Mode 0 to mode 6 depending upon the models (LVM11, LVM02,
LVM03) Modes will vary
In mode 0 - Display Shows Rated voltage (Un) selection
Select suitable rated voltage

1) 380V L-L corresponds to 220V P-N


2) 400V L-L corresponds to 230V P-N
3) 415V L-L corresponds to 240V P-N
4) 433V L –L corresponds to 250VP-N

After selecting the Rated Voltage Un, press key to save the value
Display shows - Set Under voltage [70-99.0%] – Mode 1.

In mode 1- Select the suitable under voltage in the range of 70% to 99% of selected
Un (220 to 250) P-N by using or key

After selecting the suitable % of Under voltage of Un, Press key to save the value.
Display Shows – Set UV Trip time [0 -30 secs] DEFT selection – Mode 2

In mode 2- Select the suitable UV Trip Time in the range of 00.0- 30.0S in steps of 0.1S by

using or key

After selecting the UV Trip Time press key to save the value.
Display Shows- Set Over Voltage [101-120%] - mode 3

In mode 3- Select the suitable over voltage in the range of 101% to 120% of Selected Un

(220 to 250) P-N by using or key

After selecting the suitable % of over voltage of Un, Press key to save the value.
Display Shows – Set OV Trip time [0 -30 secs] DEFT selection – Mode 4

In mode 4- Select the suitable OV Trip Time in the range of 00.0- 30.0S in steps of 0.1S

After selecting the OV Trip Time, press key to save the value.
Display Shows – Set ON Delay [0 -30 secs] UV&OV DEFT selection – Mode 5

In mode 5- Select the suitable ON Delay in the range of 00.0- 30.0S in steps of 0.1S by

using or key

After selecting the ON Delay, press key to save the value.


Note: ON Delay is common for both UV & OV settings
ON Delay is the Delay from fault to healthy state
Display Shows – Set Reset Gap [1% -5%] UV&OV selection – Mode 6

In mode 6- Select the suitable Reset gap in the range of 1%- 5% of Un in steps of 1% by

using or key
After selecting the Reset Gap, press SET key to save the value.
Note: % Reset gap is common for both UV & OV settings
% Reset gap (UN) is the voltage above or below the set UV/OV corresponding to reset
from fault to healthy state.
If the sensing input voltages are given to R, Y, B, N Terminals refer wiring diagram
Display shows
Rn-220V Yn- 220V
Bn-220V 3P4W /220

NOTE: During setting mode, If none of the key was pressed within 15 sec display returns to
normal working condition retaining the previous settings.
MODELS:1) LVM11- Both Under & Over Voltage -3P4W
2) LVM02- Only Under Voltage -3P4W
3) LVM11- Only Over Voltage - 3P4W
Wiring Diagram:
Technical Specification