AC VOLTAGE RELAY
LVM SERIES
Introduction
Prok dvs make AC Digital Microcontroller Based Definite-Time Under Voltage (UV)
and Over Voltage (OV)/ Line Voltage Monitor (LVM) is a microcontroller based
voltage monitoring and supervision relay for poly-phase system. It can monitor
b o t h under voltage (UV) and over voltage (OV) conditions in the system. Both
under voltage (UV) & over voltage (OV) conditions are associated with definite
time tripping characteristics. It has wide setting range of operating time on the
occurrence of fault condition.
DIGITAL MICROCONTROLLER BASED DEFINITE TIME UNDER VOLTAGE
(UV) AND OVER VOLTAGE RELAY/ LINE VOLTAGE MONITOR(LVM)
provides wide range of time delay for healthy resumption of the operating
voltage.
FEATURES
APPLICATION
Monitoring & Supervision of Under and Over Voltage in power generating plants &
distribution system
To protect Generator & AMF switchboards
For protection of synchronous & induction motors
For transformer feeder panel
Protection for capacitor control panels
WORKING PRINCIPLE
All the line voltages are monitored and sensed simultaneously using three independent scale
down potential transducer. This low level ac signal is subjected to signal conditioning, which
includes surge suppressors and harmonic filter. The filtered signal is fed to the ADC of the
industrial grade microprocessor. When the sensing voltage exceeds the user set value for
under or over voltage, the relay given an output signal in the form of relay changeover for
tripping/alarming.
Step1: Connect the suitable auxiliary supply in the range of 85 -275V AC/DC voltage
to the P (+) & N (-) Terminals Refer wiring diagram LVM 01/02/03 2C/O
Display shows for a while
After selecting the Rated Voltage Un, press key to save the value
Display shows - Set Under voltage [70-99.0%] – Mode 1.
In mode 1- Select the suitable under voltage in the range of 70% to 99% of selected
Un (220 to 250) P-N by using or key
After selecting the suitable % of Under voltage of Un, Press key to save the value.
Display Shows – Set UV Trip time [0 -30 secs] DEFT selection – Mode 2
In mode 2- Select the suitable UV Trip Time in the range of 00.0- 30.0S in steps of 0.1S by
using or key
After selecting the UV Trip Time press key to save the value.
Display Shows- Set Over Voltage [101-120%] - mode 3
In mode 3- Select the suitable over voltage in the range of 101% to 120% of Selected Un
After selecting the suitable % of over voltage of Un, Press key to save the value.
Display Shows – Set OV Trip time [0 -30 secs] DEFT selection – Mode 4
In mode 4- Select the suitable OV Trip Time in the range of 00.0- 30.0S in steps of 0.1S
After selecting the OV Trip Time, press key to save the value.
Display Shows – Set ON Delay [0 -30 secs] UV&OV DEFT selection – Mode 5
In mode 5- Select the suitable ON Delay in the range of 00.0- 30.0S in steps of 0.1S by
using or key
In mode 6- Select the suitable Reset gap in the range of 1%- 5% of Un in steps of 1% by
using or key
After selecting the Reset Gap, press SET key to save the value.
Note: % Reset gap is common for both UV & OV settings
% Reset gap (UN) is the voltage above or below the set UV/OV corresponding to reset
from fault to healthy state.
If the sensing input voltages are given to R, Y, B, N Terminals refer wiring diagram
Display shows
Rn-220V Yn- 220V
Bn-220V 3P4W /220
NOTE: During setting mode, If none of the key was pressed within 15 sec display returns to
normal working condition retaining the previous settings.
MODELS:1) LVM11- Both Under & Over Voltage -3P4W
2) LVM02- Only Under Voltage -3P4W
3) LVM11- Only Over Voltage - 3P4W
Wiring Diagram:
Technical Specification