NP2 3-12 English

The NP-Series - Valve Regulated Lead Acid Battery NP2.3-12 has a nominal voltage of 12V, a 20-hour rate capacity of 2.3Ah, and dimensions of 178mm x 34mm x 64mm. It has a float charge voltage of 2.275V per cell and can operate in temperatures between -20°C to +60°C. The battery has a design life of up to 5 years and contains safety features such as pressure release valves and handles that should not be used for suspension.

Uploaded by

Jonathan Bryant
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views1 page

NP2 3-12 English

The NP-Series - Valve Regulated Lead Acid Battery NP2.3-12 has a nominal voltage of 12V, a 20-hour rate capacity of 2.3Ah, and dimensions of 178mm x 34mm x 64mm. It has a float charge voltage of 2.275V per cell and can operate in temperatures between -20°C to +60°C. The battery has a design life of up to 5 years and contains safety features such as pressure release valves and handles that should not be used for suspension.

Uploaded by

Jonathan Bryant
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

NP-Series - Valve Regulated Lead Acid Battery

NP2.3-12
SPECIFICATIONS
Nominal voltage 12 V
20-hr rate Capacity to 1.75VPC at 20°C 2.3 Ah
10-hr rate Capacity to 1.75VPC at 20°C 2.1 Ah
DIMENSIONS
Length 178 (±1) mm
Width 34 (±1) mm
Height mm
(height over terminals) 64 (±2) mm
Mass (typical) 0.95 kg
TERMINAL TYPE
FASTON (Quickfit / release) 4.75 mm
OPERATING TEMPERATURE RANGE
Storage -20°C to +60°C
Charge -15°C to +50°C
Discharge -20°C to +60°C LAYOUT
STORAGE
Capacity loss per month at 20°C (approx) 3 %
CASE MATERIAL
Standard Option ABS (UL.94:HB)
Flame retardant option (FR) ABS (UL94:V0)
CHARGE VOLTAGE
13.65 (±1%) V
Float charge voltage at 20°C
2.275 (±1%) V/cell
Float Charge voltage temperature correction factor
-3 mV/cell/°C
(for variations from the standard 20°C)
14.5 (±3%) V
Cyclic (or Boost) charge at 20°C
2.42 (±3%) V/cell
Cyclic Charge voltage temperature correction factor
-4 mV/cell/°C
(for variations from the standard 20°C)
CHARGE CURRENT
Float charge current limit No limit A
Cyclic (or Boost) charge current limit 0.575 A
MAXIMUM DISCHARGE CURRENT
1 second 69 A
1 minute 23 A
SHORT-CIRCUIT CURRENT & INTERNAL RESISTANCE
(according to EN IEC 60896-21) 3RD PARTY CERTIFICATIONS
Internal resistance N/A mΩ ISO 9001 - Quality Management Systems
Short-Circuit current N/A A ISO 14001 - Environmental Management Systems
IMPEDANCE EN 18001 - OHSAS Management Systems
Measured at 1 kHz 90 mΩ UNDERWRITERS LABORATORIES Inc.
PERFORMANCE & CHARACTERISTICS VdS (Germany) - VdS No: G101139
Refer to the technical manual NP
DESIGN LIFE STANDARDS
EUROBAT Classification: Standard Commercial 3 to 5 years IEC61056
Yuasa design life @ 20°C up to 5 years
SAFETY
Installation
Can be installed and operated in any orientation except permanently inverted
Handles
Batteries must not be suspended by their handles (where fitted)
Vent valves ALL DATA IS SUBJECT TO CHANGE WITHOUT NOTICE

Each cell is fitted with a low pressure release valve to allow gasses to escape and then reseal. Issue No.: V.2 / Issue Date: Mar 2011

Gas Release
VRLA Batteries release hydrogen gas which can form explosive mixtures in air. Do not place inside a sealed
container
Recycling
YUASA's VRLA batteries must be recycled at the end of life in accordance with local and national laws and
regulations