EE251 Notes3 - Short Circuit Studies
EE251 Notes3 - Short Circuit Studies
EE 251
Fault Studies
Notes No. 3
Short Circuit Studies
1
Fault Current at Different Times
Clearing Time
of Molded
Breakers Clearing Time
of High Voltage
Breakers
2
Fault Current at Different Times
1.5 to 4 Cycles Fault Current
Interrupting (breaking) duties of HV circuit
breakers
Interrupting magnitude and time of HV breakers
for coordination
3
Characteristic of
Short Circuit Currents
R L
di
Ri L E sin t
E sin (t+) dt
R2 X 2 R2 X 2
Characteristic of
Short Circuit Currents
E sin t E sin( ) R t
i e X
2 2 2 2
R X R X
4
ANSI/IEEE and IEC Standards
5
ANSI/IEEE Calculation Method
1.5-4 Cycle Network: the network used to
calculate interrupting short-circuit current and
protective device duties 1.5-4 cycles after the
fault.
Type of Device Duty
Fuse N/A
6
ANSI/IEEE Calculation Method
30 Cycle Network: also known as the steady-
state network
X/R Ratio
Vf
For the 3-phase fault: Ia
Z1 Z f
Let Z eq Z 1 Z f Req jX eq
X X eq
Cooper:
R Req
X X1 X f
ANSI/IEEE:
R R1 Rf
7
X/R Ratio
3Vf
For the single line-to-ground fault: I a
Z 1 Z 2 Z 0 3Z f
Z 1 Z 2 Z 0 3Z f
Let Z eq
3
X X eq
Cooper:
R Req
X X 1 X 2 X 0 3X f
ANSI/IEEE:
R R1 R 2 R 0 3Rf
X/R Ratio
Vf
For the line-to-line fault: I b ,Ic j 3
Z1 Z 2 Z f
Z1 Z 2 Z f
Let Z eq
j 3
X X eq
Cooper:
R Req
ANSI/IEEE: X X1 X 2 X f
R R1 R 2 Rf
using separate R and X networks
8
X/R Ratio
For the double line-to-ground fault:
Vf Z 0T aZ 2T
Ib j 3
Z 1T Z 2T Z 1T Z 0T Z 2T Z 0T
Ic j 3
Vf Z 0T a 2Z 2T
Z 1T Z 2T Z 1T Z 0T Z 2T Z 0T
Let
Z 1T Z 2T Z 1T Z 0T Z 2T Z 0T
Z eq (b )
j 3Z 0T aZ 2T
Z 1T Z 2T Z 1T Z 0T Z 2T Z 0T
Z eq (c )
j 3 Z 0T a 2Z 2T
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 17
X/R Ratio
where Z 0T Z 0 Z f 3Z g
Z 1T Z 1 Z f
Z 2T Z 2 Z f
Cooper: X X eq
R Req
ANSI/IEEE:
X X 1T X 2T X 1T X 0T X 2T X 0T R 0T aR 2T
R X 0T aX 2T R1T R 2T R1T R 0T R 2T R 0T
X X 1T X 2T X 1T X 0T X 2T X 0T R 0T a 2R 2T
R X 0T a 2 X 2T R1T R 2T R1T R 0T R 2T R 0T
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 18
9
X/R Ratio
X/R Ratio
(0.070)(0.030 0.300)
X0 0.0578
0.070 0.030 0.300
(0.0015)(0.0010 0.0300)
R0 0.00143
0.0015 0.0010 0.0300 IEEE C37.010:1999
10
X/R Ratio
For 3-phase fault,
X X 1 0.0856
33.57
R R1 0.00255
For single line-to-ground fault,
X X1 X 2 X 0 2 0.0856 0.0578
35.1
R R1 R 2 R 0 2 0.00255 0.00143
11
ANSI/IEEE Calculation Method
Momentary (1/2 Cycle) Short-Circuit Current
Peak Momentary Short-Circuit Current
Vpre fault
Imom,rms, symm
3Zeq
Imom,rms, asymm MFm Imom, rms, symm
2
MFm 1 2e X R
12
ANSI/IEEE Calculation Method
High Voltage Circuit Breaker Interrupting Duty
(1.5-4 Cycle)
Adjusted RMS value of Interrupting Short-Circuit
Current (for total current basis CBs)
Vpre fault
Iint,rms, symm
3Zeq
I remote
NACD
I total
• Total short circuit current Itotal = Iremote + Ilocal
• NACD = 0 if all contributions are local
• NACD = 1 if all contributions are remote
13
ANSI/IEEE Calculation Method
High Voltage Circuit Breaker Interrupting Duty
(1.5-4 Cycle)
4
t
MFr 1 2e X R
IEEE C37.010:1999
14
ANSI/IEEE Calculation Method
High Voltage Circuit Breaker Interrupting Duty
(1.5-4 Cycle)
IEEE C37.010:1999
15
ANSI/IEEE Calculation Method
Low Voltage Circuit Breaker Interrupting Duty
(1/2 Cycle) Calculation
Adjusted asymmetrical RMS value of Interrupting
Short-Circuit Current
Vpre fault
Iint,rms, symm
3Zeq
2(1 e X R
)
MF
Unfused power
breakers
( X R)test
2(1 e )
1 2e X R
MF Fused power
breakers &
Molded Case
( X R)test
1 2e
Note: If calculated MF < 1.0, set MF = 1.0
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 32
16
ANSI/IEEE Calculation Method
Low Voltage Circuit Breaker Interrupting Duty
(1/2 Cycle) Calculation
Circuit Breaker Type (X/R)test
Power Breaker (Unfused) 6.59
Power Breaker (Fused) 4.90
Molded Case (> 20 kA) 4.90
Molded Case (10.001 – 20 kA) 3.18
Molded Case (10 kA) 1.73
Fuse Interrupting Short-Circuit Current
Calculation
- same procedure as Circuit Breaker Interrupting
Duty calculation.
X1=0.120 X1=0.200
R1(ac)=0.0120 R1(ac)=0.0040
X0=0.300 X0=0.200
R0=0.30 R0=0.004
Xd”=0.150
R1(ac)=0.0017
IEEE C37.010:1999
17
IEC Calculation Method
Near-to-Generator Short-Circuit
Short-circuit condition to which at least one synchronous
machine contributes a prospective initial short-circuit current
which is more than twice the generator’s rated current, or a
short-circuit condition to which synchronous and
asynchronous motors contribute more than 5% of the initial
symmetrical short-circuit current (I”k) without motors.
Far-from-Generator Short-Circuit
Short-circuit condition to which the magnitude of the
symmetrical ac component of the available short-circuit
current remains essentially constant
*IEC 60909:1988
18
IEC Calculation Method
Time-course of far-from-generator short-circuit current:
*IEC 60909:1988
19
IEC Calculation Method
Short-circuit current calculation according to IEC 60909-0 is
carried out based on the method of ‘equivalent voltage source
at the short-circuit location’.
Assumptions:
Symmetrical short-circuits are represented by the positive-
sequence component; unsymmetrical (unbalanced) short-
circuits are represented by connection of positive-, negative-
and zero-sequence component.
Capacitances and parallel admittances of non-rotating load
of the positive- (and negative-) sequence component are
neglected. Capacitances and parallel admittances of the
zero-sequence component shall be neglected, except in
systems with isolated neutral or with resonance earthing
(systems with Petersen coil) as they have an influence on
fault currents in power.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 39
20
IEC Calculation Method
Example for short-circuit current calculation with an
equivalent voltage source at s.-c. location
(a) Three-phase a.c. system with three-phase short-circuit:
*Schlabbach, 2005
*Schlabbach, 2005
21
IEC Calculation Method
(c) equivalent circuit diagram in 012-system with equivalent
voltage source:
*Schlabbach, 2005
22
IEC Calculation Method
Initial Symmetrical Short-Circuit Current Ik”
The initial symmetrical short-circuit current Ik” is calculated
for balanced and unbalanced short-circuits based on the
equivalent voltage source at the short-circuit location and
the short-circuit impedance seen from the short-circuit
location, which has to be determined with the system of
symmetrical components.
The results obtained for the short-circuit currents (and the
voltages of the non-faulted phases, if required) in the 012-
system have to be transferred back into the RYB-system.
Let
c = voltage factor
Un = nominal system voltage
Z1, Z2, Z0 = short-circuit impedance in the positive-,
negative- and zero-sequence component.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 45
*Schlabbach, 2005
23
IEC Calculation Method
Short Circuit Type Equation Remarks
Three-phase cUn
Ik" 3
3 Z1
Double-phase cUn
without earth Ik" 2
2Z1
connection
Ik" 2EB
jcUn Z0 a2 Z2 Current of
Z1Z2 Z1Z0 Z2 Z0 phase B
cUn Z0 Z1 a2 Current of
Ik" 2EB phase B
Z1 2Z0
Line-to-earth 3cUn
single-phase Ik" 1
(General)
Z1 Z2 Z0
Line-to-earth 3cUn
single-phase
Ik" 1
2Z1 Z0
(Far-from-generator, Z1 = Z2)
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 48
24
IEC Calculation Method
System Feeder
2
c UnQ
Z1Q
"
SkQ
c UnQ
Z1Q
3 Ik" 3Q
Z1Q
X1Q
1 R1Q X1Q 2
Ik" 3Q
Z0Q 3 Z1Q 2 Z1Q
Ik" 1Q
*Schlabbach, 2005
25
IEC Calculation Method
2
ukr UrT
Two-winding Transformer Z KT
T
100% SrT
2
uRr UrT P
RT KT krT KT
100% SrT 2
3 IrT
XT ZT2 RT2
UnQ
KT
Ub max
cmax
1 xT Ib max T IrT sin bT
cmax
0.95
1 0.6 xT
*Schlabbach, 2005
26
IEC Calculation Method
• Transformer with high rated power: XT ≈ ZT
• Correction factor (KT) for positive-, negative- and zero-
sequence component.
• Impedances as per this table are related to HV-side.
• The impedance in the zero-sequence component can either
be given as a ratio of the impedance in the positive-
sequence component or can be calculated from the
impedance voltage and the losses in the zero-sequence
component.
• The impedance in the zero-sequence component depends
on the handling of transformer neutral.
*Schlabbach, 2005
27
IEC Calculation Method
cmax voltage factor
pG voltage control range: UrG = const pG = 0
SrG rated apparent power
UrG rated phase-phase voltage
xd” subtransient reactance
rG phase angle between UrG/3 and rated current IrG
28
IEC Calculation Method
Power-station Unit (PSU)
ZKW ZG trT2 Z
THV K KWi
With tap - changer : K KWi is
2
UnQ 2
UrTLV
K KWs
UrG 1 pG 2 2
UrTHV
cmax
"
1 xd xT sin rG
29
IEC Calculation Method
Asynchronous Motor
2
IrM UrM
ZM
IanM SrM
ZM
XM
1 RM X M 2
PrM
SrM
rM cos rM
*Schlabbach, 2005
30
IEC Calculation
Method
Short-Circuits Inside
Power Plant
*Schlabbach, 2005
kT
3 KGs ZG 2 Z
ZTLV 1 trT Q min
31
IEC Calculation Method
When the unit transformer is not equipped with tap-changer,
the short-circuit current is given as
kT
3 KGo ZG 2 Z
ZTLV 1 trT Q min
32
IEC Calculation Method
If the unit transformer is installed without tap-changer the
impedance correction factors are given for the generator
1 cmax
KGo
"
1 pG 1 x sin
d rG
and for the unit transformer
1 cmax
KTo
1 pG 1 xT sin rG
which shall be used instead of correction factors K Gs and KTs.
The impedance Zrsl including the correction factors is called
the coupling impedance:
1 1
Zrsl
KGs ZG 2 Z
KTs ZTLV 1 trT Q min
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 65
33
IEC Calculation Method
Peak Short-Circuit Current ip
Depending on the feeding source of the short-circuit
different considerations have to be taken to calculate the
peak short-circuit current.
Single-fed
short circuit
*Schlabbach, 2005
34
IEC Calculation Method
The peak short-circuit current, which is a peak value, can be
calculated for the different types of short-circuits based on the
initial short-circuit current (r.m.s. value) by
i p3 2Ik" 3
i p2 2Ik" 2
i p1 2Ik" 1
3R X
The factor κ can be calculated by 1.02 0.98 e
where Ik3”; Ik2”; Ik1” are the initial symmetrical short-circuit
currents for three-phase, double-phase and line-to-earth
short-circuit and R;X are the resistance and reactance of the
short-circuit impedance.
Short-circuit
fed from
non-meshed
sources:
The peak
short-circuit
current is
calculated by
superposing
the contributions
of different
sources.
*Schlabbach, 2005
35
IEC Calculation Method
The peak short-circuit currents ip3T1 and ip3T2 of each
branch, fed through the transformers T1 and T2, are
calculated separately as well as the factors κ1 and κ2.
i p3T 1 1 2 Ik" 3T 1
i p3T 2 2 2 Ik" 3T 2
The total peak short-circuit current ip3 is given by
i p3 i p3T 1 i p3T 2
*Schlabbach, 2005
36
IEC Calculation Method
Uniform (smallest) ratio R/X. The factor κ is calculated
based on the smallest ratio R/X of all branches of the
network. Only those branches need to be taken into account
which contribute to the short-circuit current in the power
system corresponding to the short-circuit location,
respectively those branches connected through transformers
to the short-circuit location. The results are always on the
safe side, however the accuracy is low.
37
IEC Calculation Method
Equivalent frequency fc. Initially, the magnitude of network
reactances are scaled from their power frequency f values to
a reduced frequency fc, then the Thevenin’s impedance at
the fault point is calculated. If the positive and negative
sequence impedances at fc at the fault point are Z1c =
R1c+jX1c and Z0c = R0c+jX0c, the factor κ is calculated
based on the ratio R/X:
R R1c fc
3-phase short-circuit
X X1c f
R 2 X1c X0c 1-phase short-circuit to earth
X 2R1c R0c
where f is nominal system frequency (50 or 60 Hz) and fc/f
=0.4 (fc =20 or 24 Hz). Equal Z1c and Z2c are assumed.
Similar equations can be derived for other fault types.
Electrical & Electronics Engineering Institute EE 251 – Fault Studies
University of the Philippines Diliman 75
38
IEC Calculation Method
where IkG” is the initial symmetrical short-circuit current of
the generator, IrG is the rated current of the generator and
tmin is the minimal time delay of the protection, switchgear
and auxiliaries, that is, minimal time for switching the short-
circuit current off.
The factor μ is valid for high-voltage synchronous
generators, excited by rotating machines of rectifiers. If the
excitation system is not known the factor shall be set to μ =
1.
39
IEC Calculation Method
Contribution of Motors
Initial Symmetrical Short-Circuit Current
Three-phase Double-phase Line-to-earth
cUn 3 " c 3Un
Ik" 3M Ik" 2M Ik 3M Ik" 1M
3ZM 2 Z1M Z2M Z0M
MV-motors:
κM = 1.65 (RM/XM = 0.15) for active power per pole-pair <1 MW
κM = 1.75 (RM/XM = 0.10) for active power per pole-pair ≥1 MW
40
IEC Calculation Method
Symmetrical Short-Circuit Breaking Current
Three-phase Double-phase Line-to-earth
" 3 "
Ib3M qIk 3M Ib2M Ik 3M Ib1M Ik" 1M
2
41
IEC Calculation Method
Example:
ip = 19.43 kA
*Schlabbach, 2005
42
IEC Calculation Method
4 f t min
I b ,asymm I b ,symm 1 2 exp
X /R
2f t min
I dc I b ,symm 2 exp
X /R
f = system frequency
tmin = minimum delay time
Ib,symm = symmetrical AC breaking current = Ib
X/R = calculated based on testing PF of 7% at 50 Hz
4 f t min
I b ,asymm I b ,symm 1 2 exp
X /R
f = system frequency
tmin = minimum delay time
Ib,symm = symmetrical AC breaking current = Ib
X/R = calculated based on testing PF given by IEC
43
IEC Calculation Method
4 f t min
I b ,asymm I b ,symm 1 2 exp
X /R
f = system frequency
tmin = assumed to be a half cycle
Ib,symm = symmetrical AC breaking current = Ib
X/R = calculated based on testing PF of 15%
44