Inteligen 200 1.9.0 New Features List
Inteligen 200 1.9.0 New Features List
SW version 1.9.0
2 Changes in the version 1.9.0 3
3 Changes in the version 1.8.1 5
4 Changes in the version 1.8.0 6
5 Changes in the version 1.7.1 7
6 Changes in the version 1.7.0 8
7 Changes in the version 1.6.0 9
8 Changes in the version 1.5.0 16
9 Changes in the version 1.4.0 20
10 Changes in the version 1.3.1 22
11 Changes in the version 1.3.0 24
12 Changes in the version 1.2.0 28
13 Changes in the version 1.1.2 30
IMPORTANT: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
WARNING: This type of paragraph highlights a procedure, adjustment etc., which can cause a
damage or improper function of the equipment if not performed correctly and may not be clear at
first sight.
Example: This type of paragraph contains information that is used to illustrate how a specific function
works.
Max ROCOF
Comm object Related applications MINT, SPtM
Description
Max ROCOF is value of highest Rate of Change of Frequency since the protection was
activated.
LBO STOP FAIL is active when there is not active but unconfirmed alarm Wrn Stop Fail.
Stop Fail
Comm object Related applications MINT, SPtM
Description
This LBO is active when there is not active but unconfirmed alarm Wrn Stop Fail.
Password reset code was not valid when controller was restarted between sending PRRC code and
receiving PRAC code.
3.2 Bugfixing
USB host repairs and optimization
Update fluency improvements
Total fuel consumption
Fixed issue with US unit formats
Tristate and binary analog sensors
Fixed issue with state evaluation on certain input levels
Autodetect nominal current
Fixed issue with displayed decimal point place in values when using Autodetect nominal-current
5.2 Repairs
Priority switching in power management
Priority switching was repaired for RunHourEql option
Prestart Bypass
Description
This binary input is used for bypassing prestart time. If this LBI is activated before the engine starts, the
controller skips the prestart during starting phase. If the controller is already in a prestart phase, it will carry
on with the next phase immediately after this input becomes active.
6.2 Repairs
Controllers with CAN addresses between 9 and 16 are visible on CAN line
Repair of aftertreatment function for Doosan ECU
New setpoint Open Param Governor Speed Adjust for speed governor adjustment for Cummins engines
ECU analogue values added into MIB table
Number of displayed ECU values has been increased in InteliConfig. It can display up to 20 values now.
Doosan ECU support added
Modification of accelerator pedal position
Pedal position is set to 0 when idle speed is send to ECU
Hatz engines support
Added new Connection type SplPhL1L2 and renamed former SplitPhase to SplPhL1L3
Single parallel to mains application. The controller controls two breakers – a mains
SPTM
breaker and a generator breaker. Feedback from both breakers is required.
Multiple island-parallel application without mains and multiple parallel application with
mains. The controller controls one breaker only, the generator breaker. Feedback from
MINT
the generator breaker is required. For parallel to mains operation also mains breaker
feedback is required.
Application mode selection is done with LBI SPTM/MINT MODE SELECT, change of the
External
LBI state is accepted in the OFF mode only
Ready/AUTO
Description
This LBO is available in a configuration as standard LBO. It is active when controller in Ready state and in
AUTO mode simultaneously.
D+ Thershold
Setpoint group Engine Settings Range [units] 0..100%
Default value 80% Step 1%
Config level Standard Related applications MINT, SPTM
Description
This setpoint adjusts threshold level for D+ function.
D+ Delay
Setpoint group Engine Settings Range [units] 1 ..225 s
Default value 1s Step 1s
Config level Standard Related applications MINT, SPTM
Description
This setpoint adjusts delay for D+ function. This delay is used for:
Alarm Charging Alternator Fail.
For engine running condition - disengagement of starter
D+ Alarm type
Setpoint group Engine Settings Range [units] No Protec/Wrn/Sd
Default value Wrn Step NA
Config level Standard Related applications MINT, SPTM
Description
This setpoint adjusts type of alarm Charging Alternator Fail.
AL Battery Overvoltage
Description
This output is active when the Wrn Battery Overvoltage alarm is present in the alarmlist.
AL Battery Undervoltage
Description
This output is active when the Wrn Battery Undervoltage alarm is present in the alarmlist.
7.2 Repairs
Issue when controller is sending event emails with too long text was fixed
Improvement of controller stability during active calls (SMS/email) sending
Rename of setpoint RunHoursSource to Run Hours Source
Setpoint Generator <> Frequency BOC Delay renamed to Generator <> Frequency Delay
Vector shift value is now measured with high accuracy
Controller message "Unsupported config. table version. Please contact helpdesk!!!" was changed to the
message "Waiting for programming of compatible configuration table.”
Alterned configuration number now visible with any language not just English
Modbus (over TCP) no longer returns invalid data for binary objects for bits 16 and higher
Reading fuel consumption value from any ECU was fixed.
LBI: Battery Charge has been renamed to BATTERY CHARGER. The same has been done with Battery
Charger Fail Delay setpoint and history record
Options of setpoint SNMP Trap were made shorter in order to fit them on controller screen
It is now possible to change setpoint Web Interface over Modbus
Inconsistency in counting of running hours
When RunHoursSource setpoint was set to internal value, sometimes running hours from ECU were
used instead of running hours from internal counter
AL Excitation Loss
Description
This output is active when the BOC Excitation Loss alarm is present in the alarmlist.
AL Reverse Power
Description
This output is active when the BOC Reverse Power alarm is present in the alarmlist.
AL Synchronisation Fail
Description
This output is active when the STP Synchronization Fail alarm is present in the alarmlist.
Bus Heathy
Description
This output is active when the bus voltage and frequency are within limits. The limits for under /
overvoltage and under / overfrequency are the same as for generator voltage / frequency and can be
found in the Generator Settings setpoint group.
It works only with Application Mode Select = MINT, the output is always inactive with Application Mode
Select = SPTM.
Engines Swapped
Description
When the master controller (controller with the lowest Controller Address) swaps priority of two Gen-sets,
it generates 100ms pulse with the output. The output works with the #Priority Auto Swap option
RunHourEql.
Forward Synchronization
Description
the output is active during forward synchronization and is opened when GCB is closed or forward
synchronisation is interrupted.
Idle/Nominal Pulse
Description
200ms pulse is generated when transition from the Starting to the Running state is done. It means that the
pulse is generated when the LBO IDLE/NOMINAL is activated.
kWh Pulse
Description
This output generates a 100ms pulse whenever the internal kWh counter is incremented.
Nominal/Idle
Description
This function generates a pulse when transition to the Cooling or Stop state is done.
Cooling Speed = Idle
200ms pulse is generated when transition from the Running to the Cooling state is done.
Cooling Speed = Nominal
200ms pulse is generated when transition from the Cooling to the Stop state is done.
It means that the pulse is generated when the LBO IDLE/NOMINAL is deactivated.
Reverse Synchronization
Description
the output is active during reverse synchronization and is opened when MCB is closed or reverse
synchronisation is interrupted.
Synchronizing
Description
The output is active during synchronization. output is active when GCB is closed or synchronization is
interrupted.
System Ready
Description
The output is active, if the Actual Reserve is higher than the Start Reserve or system is able to increase
the Actual Reserve by starting another Gen-set, which is available with power management. It means that
the output can be active even with the Actual Reserve lower than the Start Reserve. The output is inactive,
if the group of Gen-sets does not have enough capacity to cover the Start Reserve.
Unloading
Description
The output is active when generator is unloaded – controller is in the Soft unld state.
CT Ratio
Setpoint group Basic Settings Range [units] 1 .. 10 000 [A/5A]
Default value 2000 A/5A Step 1 A/5 A
Config level Standard Related applications SPtM, MINT
Description
Generator current transformers ratio.
8.2 Repairs
CAN communication improvement
On-board RS485 communication improvement
Timeout for MODBUS ethernet client inactivity
Timeout is 45 s
ATT HEST Lamp
Alarm Type Alarm indication
Alarmlist message ATT HEST Lamp
Alarm evaluated All the time
Related applications MINT, SPtM
Description This alarm occurs when ATT HEST Lamp is active.
9.2 Repairs
DM1 single frame handling
DM1 message shorter than 8 bytes can create fictitious fault codes
CU HMI optimization
Note: Permanent blocking cannot occur accidentally, just by user mistake. It can be practically triggered only
by a focused activity.
10.2 Repairs
RTC initialization improvement
Note: The alarm is activated after 20 s. However, the GCB (own) closing is blocked immediately for
safety reasons.
Maintenance Timer 4
Setpoint group Engine Settings Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Step 1 day
Config level Standard Related applications SPtM, MINT
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 4
appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
Maintenance Timer 5
Setpoint group Engine Settings Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Step 1 day
Config level Standard Related applications SPtM, MINT
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 5
appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
Maintenance Timer 6
Setpoint group Engine Settings Range [units] [DD/MM/YYYY]
Default value 01/01/2015 Step 1 day
Config level Standard Related applications SPtM, MINT
Description
This maintenance timer is based on date. At the midnight of the last day the alarm Wrn Maintenance 6
appears in alarmlist.
IMPORTANT: To disable this maintenance timer, set date to 01/01/2015.
AL Maintenance 4
Description
This output is active when the Alarm Wrn Maintenance 4 is present in the alarmlist.
AL Maintenance 5
Description
This output is active when the Alarm Wrn Maintenance 5 is present in the alarmlist.
AL Maintenance 6
Description
This output is active when the Alarm Wrn Maintenance 6 is present in the alarmlist.
Idle RPM
Setpoint group Engine Settings Range [units] 100 .. 4000 [RPM]
Default value 900 Step 1 RPM
Config level Standard Related applications SPtM, MINT
Description
This setpoint adjusts idle speed.
12.2 Repairs
Binary Output Regen Needed
This binary output is connected to DPF lamp
Tier IV screen hiding
Screen is visible only for ECUs with SPN 3695 or SPN 3696
Connection type Autodetect
Autodetect didn't hold detected connection type after Engine stop
Now, connection type detected by Autodetect is used also after engine stop
15.2 Repairs
Synchronisation in WebSupervisor
WebSupervisor did not display information that controller performs synchronisation. It has been fixed.
Coils reading with Modbus
Reading of some Modbus coils (function code 1) did not work. It has been fixed.
Archives (*.aig3)
For InteliGen 200
InteliGen200-GC-1.9.0.1
16.2 Available HW
InteliGen 200
Binary Inputs 8
Binary Outputs 8
Analog Inputs 4
Analog Outputs 0
Communications USB, RS232-485, 4G, GPRS, Ethernet