Specifications

ECB-VAVS
BACnet B-ASC 9-Point Overview
Programmable Controllers
The ECB-VAVS controllers are microprocessor-based programmable
variable air volume (VAV) controllers designed to control cooling only
and cooling with reheat single duct variable air volume boxes.
®
Each controller uses the BACnet MS/TP LAN communication proto-
®
col and is BTL -Listed as BACnet Application Specific Controllers (B-
ASC).

Features & Benefits


= Internal power supply uses power factor correction (PFC) to opti-
mize power usage when multiple controllers are connected at the
same power transformer
= Flexible inputs and outputs support all industry-standard VAV uni-
tary applications
= Rugged hardware inputs and outputs eliminate the need for exter-
nal protection equipment
= Polarity free, on-board airflow sensor for precise airflow monitor-
ing and control at low and high airflow rates
= Built-in actuator with an integrated position feedback system for
worry-free operation
= Factory pre-loaded applications allow for out-of-the-box, energy
efficient operation of standard VAV equipment
= Optimized air balancing through myDC AirBalancing saving time
during the commissioning process
= Supports EC-gfxProgram, making Building Automation System
programming effortless
= Open-to-Wireless™ ready, supporting a wide variety of wireless
sensors and switches and helping to reduce installation costs
= Supports the Allure™ Series Communicating Sensors, providing
intelligent sensing and environmental zone control
Model Selection
Example: ECB-VAVS (SI)
Series Model Units
(SI) : Preloaded Apps in SI (Metric) units
ECB- VAVS : 9 points, flow sensor, damper actuator, 3 UI, 3 DO, 1 UO
(IMP) : Preloaded Apps in Imperial (US) units
Accessories
Terminal cover designed to conceal the controller’s wire terminals. Required to
Terminal covers
meet local safety regulations in certain jurisdictions.

Recommended Applications
Model ECB-VAVS
Cooling Only VAV Boxes
Cooling with Reheat VAV Boxes
Room Pressurization

BACnet Objects List


BACnet Objects Commandable Objects
Calendar Objects 1 BV Objects 10
Special events per calendar 25 MSV Objects 10
Schedule Objects 2 AV Objects 25
Special events per schedule 5
Non-Commandable Objects
PID Loop Objects 8 BV Objects 40
MSV Objects 40
AV Objects 75

Product Specifications
Power Supply Input Subnetwork
Voltage Range1 24VAC/DC; ±15%; Class 2 Communication RS-485
Frequency Range 50/60Hz Cable Cat 5e, 8 conductor twisted pair
Overcurrent Protection Field replaceable fuse Connector RJ-45
Fuse Type 3.0A Connection Topology Daisy-chain
1
Power Consumption 4 VA typical plus all external Maximum number of room 4
2
loads , 75 VA max (including devices supported per
powered triac outputs). controller combined
1. 24VDC does not support DO (triac outputs). 1. A controller can support a maximum of 2 Allure sensor models equipped with a
2. External loads must include the power consumption of any connected modules CO2 sensor. Any remaining connected sensors must be without a CO2 sensor.
such as an Allure Series Communicating Sensor. Refer to the respective module’s
datasheet for related power consumption information. Hardware
Communications Processor STM32 (ARM Cortex™ M3)
Communication Bus BACnet MS/TP MCU, 32 bit
1 CPU Speed 68 MHz
BACnet Profile B-ASC
Applications Memory 384 kB Non-volatile Flash
EOL Resistor Built-in, selectable
Storage Memory 1 MB Non-volatile Flash
Baud Rates 9600, 19 200, 38 400, or 76 800
bps Memory (RAM) 64 kB RAM
Addressing Dip switch or with an Allure EC- Real Time Clock (RTC) Built-in Real Time Clock without
Smart-Vue Series battery
Communicating Sensor Network time synchronization is
1. Refer to Distech Controls’ Protocol Implementation Conformity Statement for required at each power-up cycle
BACnet. before the RTC become
available
Green LEDs Power status & LAN Tx
Orange LEDs Controller status & LAN Rx

2/5 ECB-VAVS
Wireless Receiver
1
Communication Protocol EnOcean wireless standard
On-Board Air-Flow Sensor
Number of Wireless Inputs2 18
Differential Pressure Range ±2.0 in. W.C. (±500 Pa)
Supported Wireless Receivers Refer to the Open-to-Wireless Polarity-free high-low sensor
Application Guide connection
Cable Telephone cord Input Resolution 0.00007 in. W.C. (0.0167 Pa)
Connector 4P4C modular jack Air Flow Accuracy ±4.0% @ > 0.05 in. W.C. (12.5
Length (maximum) 6.5ft (2m) Pa)
±1.5% once calibrated through
air flow balancing @ > 0.05 in.
W.C. (12.5 Pa)
1. Available when an optional external Wireless Receiver module is connected to the Pressure Sensor Accuracy ±(0.2 Pa +3% of reading)
controller. Refer to the Open-to-Wireless Application Guide for a list of supported
EnOcean wireless modules.
2. Some wireless modules may use more than one wireless input from the controller.

Integrated Damper Actuator


Universal Inputs (UI)
Motor Belimo brushless DC motor General
Torque 45 in-lb, 5 Nm Input Type Universal; software configurable
Degrees of Rotation 95º adjustable Input Resolution 12-Bit analog / digital converter
Shaft Diameter 5/16 to 3/4”; 8.5 to 18.2mm
Contact
Acoustic Noise Level < 35 dB (A) @ 95º rotation in 95 Type Dry contact
seconds
Counter
Mechanical Type Dry contact
Dimensions (H × W × D) 7.90 × 5.51 × 3.70"
(200.61 × 139.93 × 94.04 mm) Maximum Frequency 1Hz maximum
Dimensions with terminal block 7.90 × 10.84 × 3.70" Minimum Duty Cycle 500ms On / 500ms Off
covers (H × W × D) (200.61 × 275.26 × 94.04 mm) 0 to 10VDC
Shipping Weight 1.35lbs (0.61 kg) Range 0 to 10VDC
(Controller) (40kΩ input impedance)
Shipping Weight 0.30lbs (0.14 kg)
Terminal Cover (one side, bulk
0 to 20mA
packaged) Range 0 to 20mA
1
165Ω external resistor wired in
Enclosure Material FR/ABS parallel
Enclosure Rating Plastic housing, UL94-5VB
flammability rating Resistance/Thermistor
Plenum rating per UL1995 Range 0 to 350 KΩ
1. All materials and manufacturing processes comply with the RoHS directive and are Thermistor 10KΩ Type 2, 3 (10KΩ @ 77ºF;
marked according to the Waste Electrical and Electronic Equipment (WEEE) 25ºC)
directive

Environmental
Operating Temperature 32°F to 122°F Universal Outputs (UO)
(0°C to 50°C)
General
Storage Temperature -4°F to 122°F
Output Type Universal; software configurable
(-20°C to 50°C)
Output Resolution 10-bit digital to analog converter
Relative Humidity 0 to 90% Non-condensing
Output Protection Built-in snubbing diode to
Standards and Regulation protect against back-EMF, for
CE Emission EN61000-6-3: 2007; example when used with a
A1:2011 12VDC relay
CE Immunity EN61000-6-1: 2007 Output is internally protected
against short circuits
FCC Compliance with FCC
rules part 15, subpart B, Load Resistance Minimum 600 Ω for 0-10VDC
class B and 0-12VDC outputs
UL Listed (CDN & US) UL916 Energy Auto-reset fuse Provides 24VAC over voltage
management equipment protection
CEC Appliance Appliance Efficiency
1
0 or 12VDC (On/Off)
Database Program Range 0 or 12VDC
Source Current Maximum 10 mA at 12VDC or
20 mA at 11VDC
1. California Energy Commission’s Appliance Efficiency Program: The manufacturer
has certified this product to the California Energy Commission in accordance with PWM
California law. Range Adjustable period from 2 to 65
seconds
Thermal Actuator Management Adjustable warm up and cool
down time

ECB-VAVS 3/5
Floating
Minimum Pulse On/Off Time 500 milliseconds
Digital Outputs (DO)
Drive Time Period Adjustable

0 to 10VDC General
Output Type 24VAC Triac; software
Range 0 to 10VDC
configurable
Source Current Maximum 20 mA at 10VDC
Maximum Current per Output 0.5A continuous
(minimum load resistance
1A @ 15% duty cycle for a 10-
600Ω)
minute period
Sink Current Maximum 2.5mA at 1 VDC
Power Source Internal power supply
(minimum load resistance 4KΩ)
0 or 24VAC (On/Off)
Range 0 or 24VAC

PWM
Range Adjustable period from 2 to 65
seconds
Floating
Minimum Pulse On/Off Time 500 milliseconds
Drive Time Period Adjustable
Power Source Internal power supply

Dimensions
5.51 [139.93]
2.75 [69.96] 3.70 [94.04]

2.27 [57.62] 2.27 [57.62] 1.25 [31.75]

0.40 [10.05]

0.86 [21.95]

6.09 [154.76]

7.90 [200.61]

Front Profile
±0.20
[± 5]
0.55 [13.85]
Sliding Grommet Inches [Millimeters]

Figure 1: ECB-VAVS Controller Dimensions

4/5 ECB-VAVS
10.84 [275.26] 3.70 [94.04]
5.42 [137.63] 1.25 [31.75]

0.40 [10.05]

0.86 [21.95]

6.09 [154.76]
½-inch
7.90 [200.61] knockout: Ø 0.875 (7/8)
[Ø 22.23]
4 Positions

Front Profile
±0.20
[± 5]
0.55 [13.85]
Sliding Grommet Inches [Millimeters]

Figure 2: ECB-VAVS Controller with Terminal Covers Dimensions

Specifications subject to change without notice.


Distech Controls, the Distech Controls logo, Innovative Solutions for Greener Buildings, EC-Net, ECO-Vue, Allure, and Open-To-Wireless are trademarks of Distech Controls Inc.; Lon-
Works, LON, and LNS are registered trademarks of Echelon Corporation; BACnet is a registered trademark of ASHRAE; BTL is a registered trademark of the BACnet Manufacturers
AX
Association; Niagara Framework is a registered trademark of Tridium, Inc.; EnOcean is a registered trademark of EnOcean GmbH. All other trademarks are property of their respective
owners.
©, Distech Controls Inc., 2017 - 2022. All rights reserved.
Global Head Office - 4205 place de Java, Brossard, QC, Canada, J4Y 0C4 - EU Head Office - ZAC de Sacuny, 558 avenue Marcel Mérieux, 69530 Brignais, France

5/5 ECB-VAVS_SP_15_EN