Attachment 1:
Settings List
V1.04
Project: Reppie Waste to Energy Project
Bay: 132kV line 1&2
Relay Type: PCS-902
Document No.: RWEP-CNEEC-SC-01A
NR Electric Co., Ltd.
2018-06-26
NOTES:
1) The setting list is calculated according to the parameters provided by users.
本定值依据用户提供的参数进行整定。
2) The setting list is only suitable for current system operation mode, it should be rechecked if the
system operation mode changes in the future.
本定值清单只适应于现有的运行方式,如果将来运行方式改变,相应定值需要重新核实。
3) The setting list only lists the setting that need to be set according to the designer or actual
conditions. For other settings that not listed in this section, please set them according to the
actual condition on site. If a protection function is not used, the corresponding over-value
protection setting can be set as its maximum value, the corresponding under-value protection
setting can be set as its minimum value, and the corresponding protection function
enabling/disabling logic setting can be set as “disabled”.
本定值清单只提供了保护装置根据设计或实际情况需要整定的定值项,未列出的保护定值项,请
根据实际情况设置。如果保护功能未使用,过量保护定值整定为最大值,欠量保护定值整定为最
小值,保护功能控制字整定为退出。
4) Due to the concrete settings item and sequence will change when the concrete protection
configuration changes, so it is not considered whether the settings are in a different order.
由于定值内容和顺序会根据站内保护配置而发生变化,所以可以不考虑定值顺序不同的影响。
5) In order to make sure the settings are consistent with the actual conditions, please check the
bay name, CT ratio, VT ratio, and tripping output matrix etc. parameters during the setting
configuring process.
定值设定过程中,请核实间隔名称,CT,VT,出口矩阵等参数,与实际相对应。
6) Any doubt please contact us (Relays setting calculation group of NR).
任何疑问请联系南瑞继保定值小组。
Reppie Waste to Energy Project
PCS-902 Name of Substation:
2018-06-26 Name of Bay: 132kV line 1(to mekanisa)
Note:
1) The setting is only suitable for current system wiring mode, it should be rechecked if the system wiring mode changes in the
future.
2) For other settings that not listed in this section, please set them according to the actual condition on site.
System Settings
No. Item Value Unit Remark
1 Active_Grp 1 Active setting group
2 Opt_SysFreq 50 Hz System frequency
3 PrimaryEquip_Name The name of primary equipment
4 U1n 132 Kv Primary rated value of VT (phase to phase)
5 U2n 100 V Secondary rated value of VT (phase to phase)
6 CB1.I1n 400 A Primary rated value of CT corresponding to circuit breaker No.1
Primary calculation base rated current of CT, and generally set as
7 I1n_Base 400 A same as [CB1.I1n]
8 I2n_Base 1 A Secondary calculation base rated current of CT
Frequency upper limit setting The device will issue an alarm
9 f_High_FreqAlm 53 Hz [Alm_Freq], when system frequency is higher than the setting.
Frequency lower limit setting The device will issue an alarm
10 f_Low_FreqAlm 47 Hz [Alm_Freq], when system frequency is lower than the setting.
Line parameters Settings
No. Item Value Unit Remark
1 X1L 0.887 Ω Positive-sequence reactance of the whole line (secondary value)
2 R1L 0.5394 Ω Positive-sequence resistance of the whole line (secondary value)
3 X0L 3.1163 Ω Zero-sequence reactance of the whole line (secondary value)
4 R0L 1.0727 Ω Zero-sequence resistance of the whole line (secondary value)
5 X0M 0 Ω Zero-sequence mutual reactance (secondary value)
6 R0M 0 Ω
Zero-sequence mutual resistance of the whole line (secondary value)
7 LineLength 7.11 km Total length of the whole line
Fault detector Settings
No. Item Value Unit Remark
1 FD.DPFC.I_Set 0.3 A Current setting of DPFC current fault detector element
2 FD.ROC.3I0_Set 0.15 A Current setting of residual current fault detector element
3 FD.NOC.I2_Set 0.15 A Current setting of negative-sequence current fault detector element
Enabling/disabling negative-sequence current fault detector element
4 FD.NOC.En 0 0: disable, 1: enable
DPFC distance protection Settings
No. Item Value Unit Remark
1 21D.Z_Set 0.6 Ω Impedance setting of DPFC distance protection
Enabling/disabling DPFC distance protection
2 21D.En 0
0: disable, 1: enable
Load encroachment Settings
No. Item Value Unit Remark
Angle setting of load trapezoid characteristic, it should be set
1 LoadEnch.phi 36.8 deg according to the maximum load area angle (φLoad_Max), φ
Load_Max+5°is recommended.
Resistance setting of load trapezoid characteristic, it should be set
2 LoadEnch.R_Set 21 Ω according to the minimum load resistance, 70%~90% minimum load
resistance is recommended.
Enabling/disabling load trapezoid characteristic
3 LoadEnch.En 1 0: disable, 1: enable
Distance protection (Mho) Settings
No. Item Value Unit Remark
Direction option for zone x of distance protection (x=2, 3, 4, 5)
1 21-1.DirMode 0 0: Forward
1: Reverse
4 NR Electric Co., Ltd.
Real component of zero-sequence compensation coefficient for zone
2 21-1.Real_K0 0.7432 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
3 21-1.Imag_K0 0.2526 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
4 21-1.phi1_Reach 58.7 deg 5)
5 21M1.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
6 21M1.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
7 21M1.ZG.Z_Set 0.83 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
8 21M1.ZG.t_Op 0 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
9 21M1.ZG.t_ShortDly 0 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
10 21M1.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
11 21M1.ZG.En_BlkAR 0 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
12 21M1.ZP.Z_Set 0.83 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
13 21M1.ZP.t_Op 0 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
14 21M1.ZP.t_ShortDly 0 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
15 21M1.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
16 21M1.ZP.En_BlkAR 0 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
17 21M1.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
18 21-2.DirMode 0 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
19 21-2.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
20 21-2.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
21 21-2.phi1_Reach 58.7 deg 5)
22 21M2.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
23 21M2.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
24 21M2.ZG.Z_Set 1.45 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
25 21M2.ZG.t_Op 0.3 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
26 21M2.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
NR Electric Co., Ltd. 5
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
27 21M2.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
28 21M2.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
29 21M2.ZP.Z_Set 1.45 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
30 21M2.ZP.t_Op 0.3 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
31 21M2.ZP.t_ShortDly 10 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
32 21M2.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
33 21M2.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
34 21M2.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
35 21-3.DirMode 0 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
36 21-3.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
37 21-3.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
38 21-3.phi1_Reach 58.7 deg 5)
39 21M3.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
40 21M3.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
41 21M3.ZG.Z_Set 4 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
42 21M3.ZG.t_Op 1.5 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
43 21M3.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
44 21M3.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
45 21M3.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
46 21M3.ZP.Z_Set 4 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
47 21M3.ZP.t_Op 1.5 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
48 21M3.ZP.t_ShortDly 10 s 3, 4, 5)
6 NR Electric Co., Ltd.
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
49 21M3.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
50 21M3.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
51 21M3.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
52 21-4.DirMode 1 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
53 21-4.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
54 21-4.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
55 21-4.phi1_Reach 58.7 deg 5)
56 21M4.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
57 21M4.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
58 21M4.ZG.Z_Set 0.1 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
59 21M4.ZG.t_Op 1.5 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
60 21M4.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
61 21M4.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
62 21M4.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
63 21M4.ZP.Z_Set 0.1 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
64 21M4.ZP.t_Op 1.5 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
65 21M4.ZP.t_ShortDly 10 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
66 21M4.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
67 21M4.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
68 21M4.En_ShortDly 0 0: disable
1: enable
Pilot distance zone Settings
No. Item Value Unit Remark
Real component of zero-sequence compensation coefficient for pilot
1 21.Pilot.Real_K0 0.7014 distance protection
NR Electric Co., Ltd. 7
Imaginary component of zero-sequence compensation coefficient for
2 21.Pilot.Imag_K0 0.2258 pilot distance protection
Phase angle of positive-sequence impedance for pilot distance
3 21.Pilot.phi1_Reach 58.7 deg protection
4 21M.Pilot.Z_Set 2.08 Ω Impedance setting of pilot distance protection (Mho characteristic)
5 21Q.Pilot.Z_Set 0 Ω Impedance setting of pilot distance protection (Quad characteristic)
Impedance setting of pilot distance protection in reverse direction
6 21M.Pilot.Z_Rev 0.78 Ω (Mho characteristic)
Impedance setting of pilot distance protection in reverse direction
7 21Q.Pilot.Z_Rev 0 Ω (Quad characteristic)
Resistence setting of pilot distance protection (Quad characteristic
8 21Q.Pilot.R_Set 0 Ω only)
Resistence setting of pilot distance protection in reverse direction
9 21Q.Pilot.R_Rev 0 Ω (Quad characteristic only)
Power Swing Blocking Releasing (PSDR) Settings
No. Item Value Unit Remark
Enabling/disabling zone 1 of distance protection controlled by PSBR
1 21M1.En_PSBR 1 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 2 of distance protection controlled by PSBR
2 21M2.En_PSBR 1 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 3 of distance protection controlled by PSBR
3 21M3.En_PSBR 0 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 4 of distance protection controlled by PSBR
4 21M4.En_PSBR 0 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling pilot distance zone controlled by PSBR (Quad
5 21M.Pilot.En_PSBR 1 characteristic)
0: disable, 1: enable
6 21M.I_PSBR 1.1 A Current setting for power swing blocking (Quad characteristic)
Distance SOTF protection Settings
No. Item Value Unit Remark
Enabling/disabling distance SOTF protection
1 21SOTF.En 1 0: disable, 1: enable
Enabling/disabling zone 2 of distance SOTF protection for manual
2 21SOTF.Z2.En_ManCls 1 closing
1: enable, 0: disable
Enabling/disabling zone 3 of distance SOTF protection for manual
3 21SOTF.Z3.En_ManCls 0 closing
1: enable, 0: disable
Enabling/disabling zone 4 of distance SOTF protection for manual
4 21SOTF.Z4.En_ManCls 0 closing
1: enable, 0: disable
Enabling/disabling zone 2 of distance SOTF protection for 3-pole
5 21SOTF.Z2.En_3PAR 1 reclosing
1: enable, 0: disable
Enabling/disabling zone 3 of distance SOTF protection for 3-pole
6 21SOTF.Z3.En_3PAR 0 reclosing
1: enable, 0: disable
Enabling/disabling zone 4 of distance SOTF protection for 3-pole
7 21SOTF.Z4.En_3PAR 0 reclosing
1: enable, 0: disable
Enabling/disabling zone 2 controlled by PSB of distance SOTF
8 21SOTF.Z2.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
Enabling/disabling zone 3 controlled by PSB of distance SOTF
9 21SOTF.Z3.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
8 NR Electric Co., Ltd.
Enabling/disabling zone 4 controlled by PSB of distance SOTF
10 21SOTF.Z4.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
Enabling/disabling distance SOTF protection under pole discrepancy
11 21SOTF.En_PDF 1 conditions
1: enable, 0: disable
Time delay of distance protection operating under pole discrepancy
12 21SOTF.t_PDF 0.12 s conditions
13 SOTF.U_Ddl 30 v Undervoltage setting of deadline detection
14 SOTF.t_Ddl 15 s Time delay of deadline detection
Option of manual SOTF mode
ManClsBI: initiated by input signal of manual closing
CBPos: initiated by CB position
15 SOTF.Opt_Mode_ManCls All
ManClsBI/CBPos: initiated by either input signal of manual closing or
CB position AutoInit: initiated by no voltage detection
All: initiated by both binary input and no voltage detection
Pilot distance protection Settings
No. Item Value Unit Remark
1 85.Opt_PilotMode POTT Option of pilot scheme
Option of phase-segregated signal scheme or three-phase signal
2 85.Opt_Ch_PhSeg 0 scheme
0: three-phase signal scheme, 1: phase-segregated signal scheme
Enabling/disabling weak infeed scheme
3 85.En_WI 0 0: disable, 1: enable
4 85.U_UV_WI 40 V Undervoltage setting of weak infeed logic
Enabling/disabling pilot distance protection
5 85.Z.En 0 0: disable, 1: enable
Enabling/disabling unblocking scheme
6 85.En_Unblocking1 0 0: disable, 1: enable
7 85.t_DPU_Blocking1 0.1 s Time delay for blocking scheme of pilot distance protection operation
8 85.t_DDO_CR1 0.025 s Time delay dropoff for current reversal logic
9 85.t_DPU_CR1 0.03 s Time delay pickup for current reversal logic
Enabling/disabling zone extension protection
10 85.ZX.En 0 0: disable, 1: enable
11 85.t_DPU_ZX 0.1 s Pickup time delay for zone extension protection operation
Pilot directional earth-fault protection Settings
No. Item Value Unit Remark
Enabling/disabling pilot directional earth-fault protection
1 85.DEF.En 0 0: disable, 1: enable
Enabling/disabling pilot directional earth-fault protection operate to
2 85.DEF.En_BlkAR 0 block AR
0: selective phase tripping and not blocking AR
1: three-phase tripping and blocking AR
Enabling/disabling independent channel for pilot directional earth-fault
protection
3 85.DEF.En_IndepCh 1 0: pilot directional earth-fault protection sharing same channel with
pilot distance protection
1: pilot directional earth-fault adopting independent pilot channel
Enabling/disabling unblocking scheme for pilot DEF via pilot channel 2
4 85.En_Unblocking2 0
0: disable, 1: enable
5 85.DEF.3I0_Set 0.8 A Current setting of pilot directional earth-fault protection
6 85.DEF.t_DPU 0.1 s Time delay of pilot directional earth-fault protection
Time delay pickup for current reversal logic when pilot directional
7 85.t_DPU_CR2 0.025 s earth-fault protection adopts independent pilot channel 2
Time delay dropoff for current reversal logic when pilot directional
8 85.t_DDO_CR2 0.03 s earth-fault protection adopts independent pilot channel 2
Phase overcurrent protection Settings
No. Item Value Unit Remark
NR Electric Co., Ltd. 9
Setting of second harmonic component for blocking phase overcurrent
1 50/51P.K_Hm2 0.2 elements
2 50/51P1.I_Set 20.76 A Current setting for stage 1 of phase overcurrent protection
3 50/51P1.t_Op 0.2 s Time delay for stage 1 of phase overcurrent protection
Enabling/disabling stage 1 of phase overcurrent protection
4 50/51P1.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 1 of phase
5 50/51P1.En_BlkAR 0 overcurrent protection operates
0: disable, 1: enable
Enabling/Disabling stage 1 of phase overcurrent protection is blocked
6 50/51P1.En_VTS_Blk 0 by VT circuit failure
0: disable, 1: enable
7 50/51P1.Opt_Dir Non-directional Direction option for stage 1 of phase overcurrent protection
Enabling/disabling second harmonic blocking for stage 1 of phase
8 50/51P1.En_Hm2_Blk 1 overcurrent protection
0: disable, 1: enable
Option of characteristic curve for stage 1 of phase overcurrent
9 50/51P1.Opt_Curve Definite
protection
Time multiplier setting for stage 1 of inverse-time phase overcurrent
10 50/51P1.TMS 200 protection
Minimum operating time for stage 1 of inverse-time phase overcurrent
11 50/51P1.tmin 20 s protection
Constant “Χ” for stage 1 of customized inverse-time characteristic
12 50/51P1.Alpha 0.02 phase overcurrent protection
Constant “C” for stage 1 of customized inverse-time characteristic
13 50/51P1.C 0 phase overcurrent protection
Constant “K” for stage 1 of customized inverse-time characteristic
14 50/51P1.K 0.14 phase overcurrent protection
15 50/51P2.I_Set 1.2 A Current setting for stage 2 of phase overcurrent protection
16 50/51P2.t_Op 0.5 s Time delay for stage 2 of phase overcurrent protection
Enabling/disabling stage 2 of phase overcurrent protection
17 50/51P2.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 2 of phase
18 50/51P2.En_BlkAR 1 overcurrent protection operates
0: disable, 1: enable
Enabling/Disabling stage 2 of phase overcurrent protection is blocked
19 50/51P2.En_VTS_Blk 0 by VT circuit failure
0: disable, 1: enable
20 50/51P2.Opt_Dir Forward Direction option for stage 2 of phase overcurrent protection
Enabling/disabling second harmonic blocking for stage 2 of phase
21 50/51P2.En_Hm2_Blk 0 overcurrent protection
0: disable, 1: enable
Option of characteristic curve for stage 2 of phase overcurrent
22 50/51P2.Opt_Curve IECN
protection
Time multiplier setting for stage 2 of inverse-time phase overcurrent
23 50/51P2.TMS 0.2 protection
Minimum operating time for stage 2 of inverse-time phase overcurrent
24 50/51P2.tmin 0.5 s protection
Constant “Χ” for stage 2 of customized inverse-time characteristic
25 50/51P2.Alpha 0.02 phase overcurrent protection
Constant “C” for stage 2 of customized inverse-time characteristic
26 50/51P2.C 0 phase overcurrent protection
Constant “K” for stage 2 of customized inverse-time characteristic
27 50/51P2.K 0.14 phase overcurrent protection
Earth fault protection Settings
No. Item Value Unit Remark
Setting of second harmonic component for blocking earth fault
1 50/51G.K_Hm2 0.2 elements
2 50/51G1.3I0_Set 10.47 A Current setting for stage 1 of earth fault protection
3 50/51G1.t_Op 0.2 s Time delay for stage 1 of earth fault protection
10 NR Electric Co., Ltd.
Enabling/disabling stage 1 of earth fault protection
4 50/51G1.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 1 of earth fault
5 50/51G1.En_BlkAR 0 protection operates
0: disable, 1: enable
6 50/51G1.Opt_Dir Non-directional Direction option for stage 1 of earth fault protection
Enabling/disabling second harmonic blocking for stage 1 of earth fault
7 50/51G1.En_Hm2_Blk 1 protection
0: disable, 1: enable
Enabling/disabling blocking for stage 1 of earth fault protection under
8 50/51G1.En_Abnor_Blk 0 abnormal conditions
0: disable, 1: enable
Enabling/disabling blocking for stage 1 of earth fault protection under
9 50/51G1.En_CTS_Blk 0 CT failure conditions
0: disable, 1: enable
10 50/51G1.Opt_Curve DefTime Option of characteristic curve for stage 1 of earth fault protection
Time multiplier setting for stage 1 of inverse-time earth fault protection
11 50/51G1.TMS 100
Minimum operating time for stage 1 of inverse-time earth fault
12 50/51G1.tmin 10 s protection
Constant “Χ” for stage 1 of customized inverse-time characteristic
13 50/51G1.Alpha 0.02 earth fault protection
Constant “C” for stage 1 of customized inverse-time characteristic
14 50/51G1.C 0 earth fault protection
Constant “K” for stage 1 of customized inverse-time characteristic
15 50/51G1.K 0.14 earth fault protection
16 50/51G2.3I0_Set 0.12 A Current setting for stage 2 of earth fault protection
17 50/51G2.t_Op 0.5 s Time delay for stage 2 of earth fault protection
18 50/51G2.t_ShortDly 10 s Short time delay for stage 2 of earth fault protection
Enabling/disabling stage 2 of earth fault protection
19 50/51G2.En 1 0: disable, 1: enable
Enabling/disabling short time delay for stage 2 of earth fault protection
20 50/51G2.En_ShortDly 0 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 2 of earth fault
21 50/51G2.En_BlkAR 1 protection operates
0: disable, 1: enable
22 50/51G2.Opt_Dir Forward Direction option for stage 2 of earth fault protection
Enabling/disabling second harmonic blocking for stage 2 of earth fault
23 50/51G2.En_Hm2_Blk 0 protection
0: disable, 1: enable
Enabling/disabling blocking for stage 2 of earth fault protection under
24 50/51G2.En_Abnor_Blk 1 abnormal conditions
0: disable, 1: enable
Enabling/disabling blocking for stage 2 of earth fault protection under
25 50/51G2.En_CTS_Blk 1 CT failure conditions
0: disable, 1: enable
26 50/51G2.Opt_Curve IECN Option of characteristic curve for stage 2 of earth fault protection
Time multiplier setting for stage 2 of inverse-time earth fault protection
27 50/51G2.TMS 0.32
Minimum operating time for stage 2 of inverse-time earth fault
28 50/51G2.tmin 0.5 s protection
29 50/51G3.3I0_Set default A Current setting for stage 3 of earth fault protection
30 50/51G3.t_Op default s Time delay for stage 3 of earth fault protection
31 50/51G3.t_ShortDly default s Short time delay for stage 3 of earth fault protection
Enabling/disabling stage 3 of earth fault protection
32 50/51G3.En 0 0: disable
1: enable
NR Electric Co., Ltd. 11
Enabling/disabling short time delay for stage 3 of earth fault protection
0: disable
33 50/51G3.En_ShortDly default 1: enable
Enabling/Disabling auto-reclosing blocked when stage 3 of earth fault
protection operates
34 50/51G3.En_BlkAR default 0: disable
1: enable
35 50/51G3.Opt_Dir default Direction option for stage 3 of earth fault protection
Enabling/disabling second harmonic blocking for stage 3 of earth fault
protection
36 50/51G3.En_Hm2_Blk default 0: disable
1: enable
Enabling/disabling blocking for stage 3 of earth fault protection under
abnormal conditions
37 50/51G3.En_Abnor_Blk default 0: disable
1: enable
Enabling/disabling blocking for stage 3 of earth fault protection under
CT failure conditions
38 50/51G3.En_CTS_Blk default 0: disable
1: enable
39 50/51G3.Opt_Curve default Option of characteristic curve for stage 3 of earth fault protection
Time multiplier setting for stage 3 of inverse-time earth fault protection
40 50/51G3.TMS default
Minimum operating time for stage 3 of inverse-time earth fault
41 50/51G3.tmin default s protection
Overcurrent protection for VT circuit failure Settings
No. Item Value Unit Remark
1 50PVT.I_Set 1.2 A Current setting of phase overcurrent protection when VT circuit failure
2 50PVT.t_Op 0.6 s Time delay of phase overcurrent protection when VT circuit failure
Enabling/disabling phase overcurrent protection when VT circuit
3 50PVT.En 1 failure
0: disable, 1: enable
4 50GVT.3I0_Set 0.15 A Current setting of ground overcurrent protection when VT circuit failure
5 50GVT.t_Op 0.6 s Time delay of ground overcurrent protection when VT circuit failure
Enabling/disabling ground overcurrent protection when VT circuit
6 50GVT.En 1 failure
0: disable, 1: enable
Residual current SOTF protection Settings
No. Item Value Unit Remark
1 50GSOTF.3I0_Set 0.12 A Current setting of residual current SOTF protection
Enabling/disabling residual current SOTF protection
2 50GSOTF.En 1 0: disable, 1: enable
Synchrocheck settings
No. Item Value Unit Remark
0(according to Voltage selecting mode of line 1.
1 CB1.25.Opt_Source_UL1 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of bus 1.
2 CB1.25.Opt_Source_UB1 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of line 2.
3 CB1.25.Opt_Source_UL2 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of bus 2.
4 CB1.25.Opt_Source_UB2 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
12 NR Electric Co., Ltd.
Option of circuit breaker configuration, and it should be set as “
NoVoltSel” if no voltage selection is adopted.
5 CB1.CBConfigMode NoVoltSel DblBusOneCB: one circuit breaker for double busbar
3/2BusCB: bus side circuit breaker for one and a half breakers
3/2TieCB: line side circuit breaker for one and a half breakers
6 CB1.25.U_Dd 30 V Voltage threshold of dead check
7 CB1.25.U_Lv 40 V Voltage threshold of live check
8 CB1.25.K_Usyn 1 Compensation coefficient for synchronism voltage
9 CB1.25.phi_Diff 15 deg Phase difference limit of synchronism check for AR
Compensation for phase difference between two synchronism
10 CB1.25.phi_Comp 0 deg voltages
11 CB1.25.f_Diff 0.2 Hz Frequency difference limit of synchronism check for AR
12 CB1.25.U_Diff 12 Voltage difference limit of synchronism check for AR
13 CB1.25.t_DdChk 0.05 Time delay to confirm dead check condition
14 CB1.25.t_SynChk 0.05 Time delay to confirm synchronism check condition
Enabling/disabling frequency difference check
15 CB1.25.En_fDiffChk 1 0: disable, 1: enable
Synchrocheck mode selection
16 CB1.25.SetOpt 1 0: determined by external signal, 1: determined by the setting
Enabling/disabling synchronism check
17 CB1.25.En_SynChk 1 0: disable, 1: enable
Enabling/disabling dead line and dead bus (DLDB) check
18 CB1.25.En_DdL_DdB 0 0: disable, 1: enable
Enabling/disabling dead line and live bus (DLLB) check
19 CB1.25.En_DdL_LvB 1 0: disable, 1: enable
Enabling/disabling live line and dead bus (LLDB) check
20 CB1.25.En_LvL_DdB 0 0: disable, 1: enable
Enabling/disabling AR without any check
21 CB1.25.En_NoChk 0 0: disable, 1: enable
Enabling/disabling live three-phase check of line
22 CB1.25.En_3PLvChk 1
0: disable, 1: enable
Auto-reclosing settings
No. Item Value Unit Remark
1 CB1.79.N_Rcls 1 Maximum number of reclosing attempts
2 CB1.79.t_Dd_1PS1 0.8 s Dead time of first shot 1-pole reclosing
3 CB1.79.t_Dd_3PS1 1 s Dead time of first shot 3-pole reclosing
4 CB1.79.t_Dd_3PS2 600 s Dead time of second shot 3-pole reclosing
5 CB1.79.t_Dd_3PS3 600 s Dead time of third shot 3-pole reclosing
6 CB1.79.t_Dd_3PS4 600 s Dead time of fourth shot 3-pole reclosing
7 CB1.79.t_CBClsd 15 s Time delay of circuit breaker in closed position before reclosing
Time delay to wait for CB healthy, and begin to timing when the input
8 CB1.79.t_CBReady 0.4 s signal [79.CB_Healthy] is de-energized and if it is not energized within
this time delay, AR will be blocked.
9 CB1.79.t_Wait_Chk 10 s Maximum wait time for synchronism check
Time delay allow for CB status change to conform reclosing
10 CB1.79.t_Fail 0.3 s successful
11 CB1.79.t_PW_AR 0.12 s Pulse width of AR closing signal
12 CB1.79.t_Reclaim 15 s Reclaim time of AR
13 CB1.79.t_PersistTrp 0.2 s Time delay of excessive trip signal to block auto-reclosing
Drop-off time delay of blocking AR, when blocking signal for AR
14 CB1.79.t_DDO_BlkAR 15 s disappears, AR blocking condition drops off after this time delay
15 CB1.79.t_AddDly 0.5 s Additional time delay for auto-reclosing
16 CB1.79.t_WaitMaster 10 s Maximum wait time for reclosing permissive signal from master AR
Time delay of discriminating another fault, and begin to times after 1-
pole AR initiated, 3-pole AR will be initiated if another fault happens
17 CB1.79.t_SecFault 0.3 s
during this time delay. AR will be blocked if another fault happens
after that.
NR Electric Co., Ltd. 13
Enabling/disabling auto-reclosing blocked when a fault occurs under
18 CB1.79.En_PDF_Blk 1 pole disagreement condition
0: disable, 1: enable
Enabling/disabling auto-reclosing with an additional dead time delay
19 CB1.79.En_AddDly 0 0: disable, 1: enable
Enabling/disabling adjust the length of reclosing pulse
20 CB1.79.En_CutPulse 1 0: disable, 1: enable
Enabling/disabling confirm whether AR is successful by checking CB
21 CB1.79.En_FailCheck 0 state
0: disable, 1: enable
Enabling/disabling auto-reclosing
22 CB1.79.En 1 0: disable, 1: enable
Enabling/disabling AR by external input signal besides logic setting
23 CB1.79.En_ExtCtrl 1 [79.En]
0: only logic setting, 1: logic setting and external input signal
Enabling/disabling AR be initiated by open state of circuit breaker
24 CB1.79.En_CBInit 0 0: disable, 1: enable
Option of AR priority
None: single-breaker arrangement
25 CB1.79.Opt_Priority None High: master AR of multi-breaker arrangement
Low: slave AR of multi-breaker arrangement
Control option of AR mode
26 CB1.79.SetOpt 0 1: select AR mode by internal logic settings
0: select AR mode by external input signals
Enabling/disabling 1-pole AR mode
27 CB1.79.En_1PAR 1 0: disable, 1: enable
Enabling/disabling 3-pole AR mode
28 CB1.79.En_3PAR 0 0: disable, 1: enable
Enabling/disabling 1/3-pole AR
29 CB1.79.En_1P/3PAR 0 mode
0: disable, 1: enable
Transfer trip Settings
No. Item Value Unit Remark
1 TT.t_Op 0.02 s Time delay of transfer trip
Transfer trip controlled by local fault detector element
2 TT.En_FD_Ctrl 1 0: not controlled by local fault detector element
1: controlled by local fault detector element
Trip logic Settings
No. Item Value Unit Remark
Enabling/disabling auto-reclosing blocked when multi-phase fault
1 En_MPF_Blk_AR 1 happens
0: disable, 1: enable
Enabling/disabling auto-reclosing blocked when three-phase fault
2 En_3PF_Blk_AR 1 happens
0: disable, 1: enable
Enabling/disabling auto-reclosing blocked when faulty phase selection
3 En_PhSF_Blk_AR 1 fails
0: disable, 1: enable
Enabling/disabling three-phase tripping mode for any fault conditions
4 CB1.En_Trp3P 0 0: disable, 1: enable
The dwell time of tripping command, empirical value is 0.04 The
5 t_Dwell_Trp 0.04 s tripping contact shall drop off under conditions of no current or
protection tripping element drop-off.
VTS settings
No. Item Value Unit Remark
1 VTS.t_DPU 1.25 s Pickup time delay of VT circuit supervision
2 VTS.t_DDO 10 s Dropoff time delay of VT circuit supervision
14 NR Electric Co., Ltd.
No voltage used for protection calculation
1: enable, 0: disable
3 VTS.En_Out_VT 0 In general, when VT is not connected to the device, this logic setting
should be set as “1”
Voltage selection for protection calculation from busbar VT or line VT
4 VTS.En_LineVT 1 1: line VT, 0: busbar VT
Alarm function of VT circuit supervision
5 VTS.En 1 1: enable, 0: disable
NR Electric Co., Ltd. 15
Reppie Waste to Energy Project
PCS-902 Name of Substation:
2018-06-26 Name of Bay: 132kV line 1(to sebeta)
Note:
1) The setting is only suitable for current system wiring mode, it should be rechecked if the system wiring mode changes in the
future.
2) For other settings that not listed in this section, please set them according to the actual condition on site.
System Settings
No. Item Value Unit Remark
1 Active_Grp 1 Active setting group
2 Opt_SysFreq 50 Hz System frequency
3 PrimaryEquip_Name The name of primary equipment
4 U1n 132 Kv Primary rated value of VT (phase to phase)
5 U2n 100 V Secondary rated value of VT (phase to phase)
6 CB1.I1n 400 A Primary rated value of CT corresponding to circuit breaker No.1
Primary calculation base rated current of CT, and generally set as
7 I1n_Base 400 A same as [CB1.I1n]
8 I2n_Base 1 A Secondary calculation base rated current of CT
Frequency upper limit setting The device will issue an alarm
9 f_High_FreqAlm 53 Hz [Alm_Freq], when system frequency is higher than the setting.
Frequency lower limit setting The device will issue an alarm
10 f_Low_FreqAlm 47 Hz [Alm_Freq], when system frequency is lower than the setting.
Line parameters Settings
No. Item Value Unit Remark
1 X1L 0.8861 Ω Positive-sequence reactance of the whole line (secondary value)
2 R1L 0.5388 Ω Positive-sequence resistance of the whole line (secondary value)
3 X0L 3.1155 Ω Zero-sequence reactance of the whole line (secondary value)
4 R0L 1.0721 Ω Zero-sequence resistance of the whole line (secondary value)
5 X0M 0 Ω Zero-sequence mutual reactance (secondary value)
6 R0M 0 Ω
Zero-sequence mutual resistance of the whole line (secondary value)
7 LineLength 7.09 km Total length of the whole line
Fault detector Settings
No. Item Value Unit Remark
1 FD.DPFC.I_Set 0.3 A Current setting of DPFC current fault detector element
2 FD.ROC.3I0_Set 0.15 A Current setting of residual current fault detector element
3 FD.NOC.I2_Set 0.15 A Current setting of negative-sequence current fault detector element
Enabling/disabling negative-sequence current fault detector element
4 FD.NOC.En 0 0: disable, 1: enable
DPFC distance protection Settings
No. Item Value Unit Remark
1 21D.Z_Set 0.6 Ω Impedance setting of DPFC distance protection
Enabling/disabling DPFC distance protection
2 21D.En 0
0: disable, 1: enable
Load encroachment Settings
No. Item Value Unit Remark
Angle setting of load trapezoid characteristic, it should be set
1 LoadEnch.phi 36.8 deg according to the maximum load area angle (φLoad_Max), φ
Load_Max+5°is recommended.
Resistance setting of load trapezoid characteristic, it should be set
2 LoadEnch.R_Set 21 Ω according to the minimum load resistance, 70%~90% minimum load
resistance is recommended.
Enabling/disabling load trapezoid characteristic
3 LoadEnch.En 1 0: disable, 1: enable
Distance protection (Mho) Settings
No. Item Value Unit Remark
Direction option for zone x of distance protection (x=2, 3, 4, 5)
1 21-1.DirMode 0 0: Forward
1: Reverse
16 NR Electric Co., Ltd.
Real component of zero-sequence compensation coefficient for zone
2 21-1.Real_K0 0.7432 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
3 21-1.Imag_K0 0.2526 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
4 21-1.phi1_Reach 58.7 deg 5)
5 21M1.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
6 21M1.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
7 21M1.ZG.Z_Set 0.83 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
8 21M1.ZG.t_Op 0 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
9 21M1.ZG.t_ShortDly 0 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
10 21M1.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
11 21M1.ZG.En_BlkAR 0 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
12 21M1.ZP.Z_Set 0.83 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
13 21M1.ZP.t_Op 0 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
14 21M1.ZP.t_ShortDly 0 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
15 21M1.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
16 21M1.ZP.En_BlkAR 0 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
17 21M1.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
18 21-2.DirMode 0 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
19 21-2.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
20 21-2.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
21 21-2.phi1_Reach 58.7 deg 5)
22 21M2.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
23 21M2.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
24 21M2.ZG.Z_Set 1.45 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
25 21M2.ZG.t_Op 0.3 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
26 21M2.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
NR Electric Co., Ltd. 17
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
27 21M2.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
28 21M2.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
29 21M2.ZP.Z_Set 1.45 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
30 21M2.ZP.t_Op 0.3 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
31 21M2.ZP.t_ShortDly 10 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
32 21M2.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
33 21M2.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
34 21M2.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
35 21-3.DirMode 0 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
36 21-3.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
37 21-3.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
38 21-3.phi1_Reach 58.7 deg 5)
39 21M3.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
40 21M3.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
41 21M3.ZG.Z_Set 4 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
42 21M3.ZG.t_Op 1.5 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
43 21M3.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
44 21M3.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
45 21M3.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
46 21M3.ZP.Z_Set 4 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
47 21M3.ZP.t_Op 1.5 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
48 21M3.ZP.t_ShortDly 10 s 3, 4, 5)
18 NR Electric Co., Ltd.
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
49 21M3.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
50 21M3.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
51 21M3.En_ShortDly 0 0: disable
1: enable
Direction option for zone x of distance protection (x=2, 3, 4, 5)
52 21-4.DirMode 1 0: Forward
1: Reverse
Real component of zero-sequence compensation coefficient for zone
53 21-4.Real_K0 0.7022 x (x=1, 2, 3, 4, 5)
Imaginary component of zero-sequence compensation coefficient for
54 21-4.Imag_K0 0.2271 zone x (x=1, 2, 3, 4, 5)
Phase angle of positive-sequence impedance for zone x (x=1, 2, 3, 4,
55 21-4.phi1_Reach 58.7 deg 5)
56 21M4.ZG.phi_Shift 30 Phase shift of phase-to-ground distance protection for zone x (x=1, 2)
57 21M4.ZP.phi_Shift 15 Phase shift of phase-to-phase distance protection for zone x (x=1, 2)
Impedance setting of zone x of phase-to-ground distance protection
58 21M4.ZG.Z_Set 0.1 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-ground distance protection (x=1, 2,
59 21M4.ZG.t_Op 1.5 s 3, 4, 5)
s Short time delay of zone x of phase-to-ground distance protection
60 21M4.ZG.t_ShortDly 10 (x=2, 3, 4, 5)
Enabling/disabling zone x of phase-to-ground distance protection
(x=1, 2, 3, 4, 5)
61 21M4.ZG.En 1 0: disable
1: enable
Enabling/disabling phase-to-ground zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
62 21M4.ZG.En_BlkAR 1 0: disable
1: enable
Impedance setting of zone x of phase-to-phase distance protection
63 21M4.ZP.Z_Set 0.1 Ω (x=1, 2, 3, 4, 5)
Time delay of zone x of phase-to-phase distance protection (x=1, 2, 3,
64 21M4.ZP.t_Op 1.5 s 4, 5)
Short time delay of zone x of phase-to-phase distance protection (x=2,
65 21M4.ZP.t_ShortDly 10 s 3, 4, 5)
Enabling/disabling zone x of phase-to-phase distance protection (x=1,
2, 3, 4, 5)
66 21M4.ZP.En 1 0: disable
1: enable
Enabling/disabling phase-to-phase zone x of distance protection
operation to block AR (x=1, 2, 3, 4, 5)
67 21M4.ZP.En_BlkAR 1 0: disable
1: enable
Enabling/disabling fixed accelerate zone x of distance protection (x=2,
3, 4, 5)
68 21M4.En_ShortDly 0 0: disable
1: enable
Pilot distance zone Settings
No. Item Value Unit Remark
Real component of zero-sequence compensation coefficient for pilot
1 21.Pilot.Real_K0 0.7014 distance protection
NR Electric Co., Ltd. 19
Imaginary component of zero-sequence compensation coefficient for
2 21.Pilot.Imag_K0 0.2258 pilot distance protection
Phase angle of positive-sequence impedance for pilot distance
3 21.Pilot.phi1_Reach 58.7 deg protection
4 21M.Pilot.Z_Set 2.08 Ω Impedance setting of pilot distance protection (Mho characteristic)
5 21Q.Pilot.Z_Set 0 Ω Impedance setting of pilot distance protection (Quad characteristic)
Impedance setting of pilot distance protection in reverse direction
6 21M.Pilot.Z_Rev 0.78 Ω (Mho characteristic)
Impedance setting of pilot distance protection in reverse direction
7 21Q.Pilot.Z_Rev 0 Ω (Quad characteristic)
Resistence setting of pilot distance protection (Quad characteristic
8 21Q.Pilot.R_Set 0 Ω only)
Resistence setting of pilot distance protection in reverse direction
9 21Q.Pilot.R_Rev 0 Ω (Quad characteristic only)
Power Swing Blocking Releasing (PSDR) Settings
No. Item Value Unit Remark
Enabling/disabling zone 1 of distance protection controlled by PSBR
1 21M1.En_PSBR 1 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 2 of distance protection controlled by PSBR
2 21M2.En_PSBR 1 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 3 of distance protection controlled by PSBR
3 21M3.En_PSBR 0 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling zone 4 of distance protection controlled by PSBR
4 21M4.En_PSBR 0 (Quad characteristic)
0: disable, 1: enable
Enabling/disabling pilot distance zone controlled by PSBR (Quad
5 21M.Pilot.En_PSBR 1 characteristic)
0: disable, 1: enable
6 21M.I_PSBR 1.1 A Current setting for power swing blocking (Quad characteristic)
Distance SOTF protection Settings
No. Item Value Unit Remark
Enabling/disabling distance SOTF protection
1 21SOTF.En 1 0: disable, 1: enable
Enabling/disabling zone 2 of distance SOTF protection for manual
2 21SOTF.Z2.En_ManCls 1 closing
1: enable, 0: disable
Enabling/disabling zone 3 of distance SOTF protection for manual
3 21SOTF.Z3.En_ManCls 0 closing
1: enable, 0: disable
Enabling/disabling zone 4 of distance SOTF protection for manual
4 21SOTF.Z4.En_ManCls 0 closing
1: enable, 0: disable
Enabling/disabling zone 2 of distance SOTF protection for 3-pole
5 21SOTF.Z2.En_3PAR 1 reclosing
1: enable, 0: disable
Enabling/disabling zone 3 of distance SOTF protection for 3-pole
6 21SOTF.Z3.En_3PAR 0 reclosing
1: enable, 0: disable
Enabling/disabling zone 4 of distance SOTF protection for 3-pole
7 21SOTF.Z4.En_3PAR 0 reclosing
1: enable, 0: disable
Enabling/disabling zone 2 controlled by PSB of distance SOTF
8 21SOTF.Z2.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
Enabling/disabling zone 3 controlled by PSB of distance SOTF
9 21SOTF.Z3.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
20 NR Electric Co., Ltd.
Enabling/disabling zone 4 controlled by PSB of distance SOTF
10 21SOTF.Z4.En_PSBR 0 protection for 3-pole reclosing
1: enable, 0: disable
Enabling/disabling distance SOTF protection under pole discrepancy
11 21SOTF.En_PDF 1 conditions
1: enable, 0: disable
Time delay of distance protection operating under pole discrepancy
12 21SOTF.t_PDF 0.12 s conditions
13 SOTF.U_Ddl 30 v Undervoltage setting of deadline detection
14 SOTF.t_Ddl 15 s Time delay of deadline detection
Option of manual SOTF mode
ManClsBI: initiated by input signal of manual closing
CBPos: initiated by CB position
15 SOTF.Opt_Mode_ManCls All
ManClsBI/CBPos: initiated by either input signal of manual closing or
CB position AutoInit: initiated by no voltage detection
All: initiated by both binary input and no voltage detection
Pilot distance protection Settings
No. Item Value Unit Remark
1 85.Opt_PilotMode POTT Option of pilot scheme
Option of phase-segregated signal scheme or three-phase signal
2 85.Opt_Ch_PhSeg 0 scheme
0: three-phase signal scheme, 1: phase-segregated signal scheme
Enabling/disabling weak infeed scheme
3 85.En_WI 0 0: disable, 1: enable
4 85.U_UV_WI 40 V Undervoltage setting of weak infeed logic
Enabling/disabling pilot distance protection
5 85.Z.En 0 0: disable, 1: enable
Enabling/disabling unblocking scheme
6 85.En_Unblocking1 0 0: disable, 1: enable
7 85.t_DPU_Blocking1 0.1 s Time delay for blocking scheme of pilot distance protection operation
8 85.t_DDO_CR1 0.025 s Time delay dropoff for current reversal logic
9 85.t_DPU_CR1 0.03 s Time delay pickup for current reversal logic
Enabling/disabling zone extension protection
10 85.ZX.En 0 0: disable, 1: enable
11 85.t_DPU_ZX 0.1 s Pickup time delay for zone extension protection operation
Pilot directional earth-fault protection Settings
No. Item Value Unit Remark
Enabling/disabling pilot directional earth-fault protection
1 85.DEF.En 0 0: disable, 1: enable
Enabling/disabling pilot directional earth-fault protection operate to
2 85.DEF.En_BlkAR 0 block AR
0: selective phase tripping and not blocking AR
1: three-phase tripping and blocking AR
Enabling/disabling independent channel for pilot directional earth-fault
protection
3 85.DEF.En_IndepCh 0 0: pilot directional earth-fault protection sharing same channel with
pilot distance protection
1: pilot directional earth-fault adopting independent pilot channel
Enabling/disabling unblocking scheme for pilot DEF via pilot channel 2
4 85.En_Unblocking2 0
0: disable, 1: enable
5 85.DEF.3I0_Set 1.07 A Current setting of pilot directional earth-fault protection
6 85.DEF.t_DPU 0.1 s Time delay of pilot directional earth-fault protection
Time delay pickup for current reversal logic when pilot directional
7 85.t_DPU_CR2 0.025 s earth-fault protection adopts independent pilot channel 2
Time delay dropoff for current reversal logic when pilot directional
8 85.t_DDO_CR2 0.03 s earth-fault protection adopts independent pilot channel 2
Phase overcurrent protection Settings
No. Item Value Unit Remark
NR Electric Co., Ltd. 21
Setting of second harmonic component for blocking phase overcurrent
1 50/51P.K_Hm2 0.2 elements
2 50/51P1.I_Set 19.83 A Current setting for stage 1 of phase overcurrent protection
3 50/51P1.t_Op 0.2 s Time delay for stage 1 of phase overcurrent protection
Enabling/disabling stage 1 of phase overcurrent protection
4 50/51P1.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 1 of phase
5 50/51P1.En_BlkAR 0 overcurrent protection operates
0: disable, 1: enable
Enabling/Disabling stage 1 of phase overcurrent protection is blocked
6 50/51P1.En_VTS_Blk 0 by VT circuit failure
0: disable, 1: enable
7 50/51P1.Opt_Dir Non-directional Direction option for stage 1 of phase overcurrent protection
Enabling/disabling second harmonic blocking for stage 1 of phase
8 50/51P1.En_Hm2_Blk 1 overcurrent protection
0: disable, 1: enable
Option of characteristic curve for stage 1 of phase overcurrent
9 50/51P1.Opt_Curve Definite
protection
Time multiplier setting for stage 1 of inverse-time phase overcurrent
10 50/51P1.TMS 200 protection
Minimum operating time for stage 1 of inverse-time phase overcurrent
11 50/51P1.tmin 20 s protection
Constant “Χ” for stage 1 of customized inverse-time characteristic
12 50/51P1.Alpha 0.02 phase overcurrent protection
Constant “C” for stage 1 of customized inverse-time characteristic
13 50/51P1.C 0 phase overcurrent protection
Constant “K” for stage 1 of customized inverse-time characteristic
14 50/51P1.K 0.14 phase overcurrent protection
15 50/51P2.I_Set 1.2 A Current setting for stage 2 of phase overcurrent protection
16 50/51P2.t_Op 0.5 s Time delay for stage 2 of phase overcurrent protection
Enabling/disabling stage 2 of phase overcurrent protection
17 50/51P2.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 2 of phase
18 50/51P2.En_BlkAR 1 overcurrent protection operates
0: disable, 1: enable
Enabling/Disabling stage 2 of phase overcurrent protection is blocked
19 50/51P2.En_VTS_Blk 0 by VT circuit failure
0: disable, 1: enable
20 50/51P2.Opt_Dir Forward Direction option for stage 2 of phase overcurrent protection
Enabling/disabling second harmonic blocking for stage 2 of phase
21 50/51P2.En_Hm2_Blk 0 overcurrent protection
0: disable, 1: enable
Option of characteristic curve for stage 2 of phase overcurrent
22 50/51P2.Opt_Curve IECN
protection
Time multiplier setting for stage 2 of inverse-time phase overcurrent
23 50/51P2.TMS 0.2 protection
Minimum operating time for stage 2 of inverse-time phase overcurrent
24 50/51P2.tmin 0.5 s protection
Constant “Χ” for stage 2 of customized inverse-time characteristic
25 50/51P2.Alpha 0.02 phase overcurrent protection
Constant “C” for stage 2 of customized inverse-time characteristic
26 50/51P2.C 0 phase overcurrent protection
Constant “K” for stage 2 of customized inverse-time characteristic
27 50/51P2.K 0.14 phase overcurrent protection
Earth fault protection Settings
No. Item Value Unit Remark
Setting of second harmonic component for blocking earth fault
1 50/51G.K_Hm2 0.2 elements
2 50/51G1.3I0_Set 11.5 A Current setting for stage 1 of earth fault protection
3 50/51G1.t_Op 0.2 s Time delay for stage 1 of earth fault protection
22 NR Electric Co., Ltd.
Enabling/disabling stage 1 of earth fault protection
4 50/51G1.En 1 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 1 of earth fault
5 50/51G1.En_BlkAR 0 protection operates
0: disable, 1: enable
6 50/51G1.Opt_Dir Non-directional Direction option for stage 1 of earth fault protection
Enabling/disabling second harmonic blocking for stage 1 of earth fault
7 50/51G1.En_Hm2_Blk 1 protection
0: disable, 1: enable
Enabling/disabling blocking for stage 1 of earth fault protection under
8 50/51G1.En_Abnor_Blk 0 abnormal conditions
0: disable, 1: enable
Enabling/disabling blocking for stage 1 of earth fault protection under
9 50/51G1.En_CTS_Blk 0 CT failure conditions
0: disable, 1: enable
10 50/51G1.Opt_Curve DefTime Option of characteristic curve for stage 1 of earth fault protection
Time multiplier setting for stage 1 of inverse-time earth fault protection
11 50/51G1.TMS 100
Minimum operating time for stage 1 of inverse-time earth fault
12 50/51G1.tmin 10 s protection
Constant “Χ” for stage 1 of customized inverse-time characteristic
13 50/51G1.Alpha 0.02 earth fault protection
Constant “C” for stage 1 of customized inverse-time characteristic
14 50/51G1.C 0 earth fault protection
Constant “K” for stage 1 of customized inverse-time characteristic
15 50/51G1.K 0.14 earth fault protection
16 50/51G2.3I0_Set 0.12 A Current setting for stage 2 of earth fault protection
17 50/51G2.t_Op 0.5 s Time delay for stage 2 of earth fault protection
18 50/51G2.t_ShortDly 10 s Short time delay for stage 2 of earth fault protection
Enabling/disabling stage 2 of earth fault protection
19 50/51G2.En 1 0: disable, 1: enable
Enabling/disabling short time delay for stage 2 of earth fault protection
20 50/51G2.En_ShortDly 0 0: disable, 1: enable
Enabling/Disabling auto-reclosing blocked when stage 2 of earth fault
21 50/51G2.En_BlkAR 1 protection operates
0: disable, 1: enable
22 50/51G2.Opt_Dir Forward Direction option for stage 2 of earth fault protection
Enabling/disabling second harmonic blocking for stage 2 of earth fault
23 50/51G2.En_Hm2_Blk 0 protection
0: disable, 1: enable
Enabling/disabling blocking for stage 2 of earth fault protection under
24 50/51G2.En_Abnor_Blk 1 abnormal conditions
0: disable, 1: enable
Enabling/disabling blocking for stage 2 of earth fault protection under
25 50/51G2.En_CTS_Blk 1 CT failure conditions
0: disable, 1: enable
26 50/51G2.Opt_Curve IECN Option of characteristic curve for stage 2 of earth fault protection
Time multiplier setting for stage 2 of inverse-time earth fault protection
27 50/51G2.TMS 0.33
Minimum operating time for stage 2 of inverse-time earth fault
28 50/51G2.tmin 0.5 s protection
29 50/51G3.3I0_Set default A Current setting for stage 3 of earth fault protection
30 50/51G3.t_Op default s Time delay for stage 3 of earth fault protection
31 50/51G3.t_ShortDly default s Short time delay for stage 3 of earth fault protection
Enabling/disabling stage 3 of earth fault protection
32 50/51G3.En 0 0: disable
1: enable
NR Electric Co., Ltd. 23
Enabling/disabling short time delay for stage 3 of earth fault protection
0: disable
33 50/51G3.En_ShortDly default 1: enable
Enabling/Disabling auto-reclosing blocked when stage 3 of earth fault
protection operates
34 50/51G3.En_BlkAR default 0: disable
1: enable
35 50/51G3.Opt_Dir default Direction option for stage 3 of earth fault protection
Enabling/disabling second harmonic blocking for stage 3 of earth fault
protection
36 50/51G3.En_Hm2_Blk default 0: disable
1: enable
Enabling/disabling blocking for stage 3 of earth fault protection under
abnormal conditions
37 50/51G3.En_Abnor_Blk default 0: disable
1: enable
Enabling/disabling blocking for stage 3 of earth fault protection under
CT failure conditions
38 50/51G3.En_CTS_Blk default 0: disable
1: enable
39 50/51G3.Opt_Curve default Option of characteristic curve for stage 3 of earth fault protection
Time multiplier setting for stage 3 of inverse-time earth fault protection
40 50/51G3.TMS default
Minimum operating time for stage 3 of inverse-time earth fault
41 50/51G3.tmin default s protection
Overcurrent protection for VT circuit failure Settings
No. Item Value Unit Remark
1 50PVT.I_Set 1.2 A Current setting of phase overcurrent protection when VT circuit failure
2 50PVT.t_Op 0.6 s Time delay of phase overcurrent protection when VT circuit failure
Enabling/disabling phase overcurrent protection when VT circuit
3 50PVT.En 1 failure
0: disable, 1: enable
4 50GVT.3I0_Set 0.15 A Current setting of ground overcurrent protection when VT circuit failure
5 50GVT.t_Op 0.6 s Time delay of ground overcurrent protection when VT circuit failure
Enabling/disabling ground overcurrent protection when VT circuit
6 50GVT.En 1 failure
0: disable, 1: enable
Residual current SOTF protection Settings
No. Item Value Unit Remark
1 50GSOTF.3I0_Set 0.12 A Current setting of residual current SOTF protection
Enabling/disabling residual current SOTF protection
2 50GSOTF.En 1 0: disable, 1: enable
Synchrocheck settings
No. Item Value Unit Remark
0(according to Voltage selecting mode of line 1.
1 CB1.25.Opt_Source_UL1 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of bus 1.
2 CB1.25.Opt_Source_UB1 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of line 2.
3 CB1.25.Opt_Source_UL2 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
0(according to Voltage selecting mode of bus 2.
4 CB1.25.Opt_Source_UB2 practical 0: A-phase voltage, 1: B-phase voltage, 2: C-phase voltage
situation) 3: AB-phase voltage, 4: BC-phase voltage, 5: CA-phase voltage
24 NR Electric Co., Ltd.
Option of circuit breaker configuration, and it should be set as “
NoVoltSel” if no voltage selection is adopted.
5 CB1.CBConfigMode NoVoltSel DblBusOneCB: one circuit breaker for double busbar
3/2BusCB: bus side circuit breaker for one and a half breakers
3/2TieCB: line side circuit breaker for one and a half breakers
6 CB1.25.U_Dd 30 V Voltage threshold of dead check
7 CB1.25.U_Lv 40 V Voltage threshold of live check
8 CB1.25.K_Usyn 1 Compensation coefficient for synchronism voltage
9 CB1.25.phi_Diff 15 deg Phase difference limit of synchronism check for AR
Compensation for phase difference between two synchronism
10 CB1.25.phi_Comp 0 deg voltages
11 CB1.25.f_Diff 0.2 Hz Frequency difference limit of synchronism check for AR
12 CB1.25.U_Diff 12 Voltage difference limit of synchronism check for AR
13 CB1.25.t_DdChk 0.05 Time delay to confirm dead check condition
14 CB1.25.t_SynChk 0.05 Time delay to confirm synchronism check condition
Enabling/disabling frequency difference check
15 CB1.25.En_fDiffChk 1 0: disable, 1: enable
Synchrocheck mode selection
16 CB1.25.SetOpt 1 0: determined by external signal, 1: determined by the setting
Enabling/disabling synchronism check
17 CB1.25.En_SynChk 1 0: disable, 1: enable
Enabling/disabling dead line and dead bus (DLDB) check
18 CB1.25.En_DdL_DdB 0 0: disable, 1: enable
Enabling/disabling dead line and live bus (DLLB) check
19 CB1.25.En_DdL_LvB 1 0: disable, 1: enable
Enabling/disabling live line and dead bus (LLDB) check
20 CB1.25.En_LvL_DdB 0 0: disable, 1: enable
Enabling/disabling AR without any check
21 CB1.25.En_NoChk 0 0: disable, 1: enable
Enabling/disabling live three-phase check of line
22 CB1.25.En_3PLvChk 1
0: disable, 1: enable
Auto-reclosing settings
No. Item Value Unit Remark
1 CB1.79.N_Rcls 1 Maximum number of reclosing attempts
2 CB1.79.t_Dd_1PS1 0.8 s Dead time of first shot 1-pole reclosing
3 CB1.79.t_Dd_3PS1 1 s Dead time of first shot 3-pole reclosing
4 CB1.79.t_Dd_3PS2 600 s Dead time of second shot 3-pole reclosing
5 CB1.79.t_Dd_3PS3 600 s Dead time of third shot 3-pole reclosing
6 CB1.79.t_Dd_3PS4 600 s Dead time of fourth shot 3-pole reclosing
7 CB1.79.t_CBClsd 15 s Time delay of circuit breaker in closed position before reclosing
Time delay to wait for CB healthy, and begin to timing when the input
8 CB1.79.t_CBReady 0.4 s signal [79.CB_Healthy] is de-energized and if it is not energized within
this time delay, AR will be blocked.
9 CB1.79.t_Wait_Chk 10 s Maximum wait time for synchronism check
Time delay allow for CB status change to conform reclosing
10 CB1.79.t_Fail 0.3 s successful
11 CB1.79.t_PW_AR 0.12 s Pulse width of AR closing signal
12 CB1.79.t_Reclaim 15 s Reclaim time of AR
13 CB1.79.t_PersistTrp 0.2 s Time delay of excessive trip signal to block auto-reclosing
Drop-off time delay of blocking AR, when blocking signal for AR
14 CB1.79.t_DDO_BlkAR 15 s disappears, AR blocking condition drops off after this time delay
15 CB1.79.t_AddDly 0.5 s Additional time delay for auto-reclosing
16 CB1.79.t_WaitMaster 10 s Maximum wait time for reclosing permissive signal from master AR
Time delay of discriminating another fault, and begin to times after 1-
pole AR initiated, 3-pole AR will be initiated if another fault happens
17 CB1.79.t_SecFault 0.3 s
during this time delay. AR will be blocked if another fault happens
after that.
NR Electric Co., Ltd. 25
Enabling/disabling auto-reclosing blocked when a fault occurs under
18 CB1.79.En_PDF_Blk 1 pole disagreement condition
0: disable, 1: enable
Enabling/disabling auto-reclosing with an additional dead time delay
19 CB1.79.En_AddDly 0 0: disable, 1: enable
Enabling/disabling adjust the length of reclosing pulse
20 CB1.79.En_CutPulse 1 0: disable, 1: enable
Enabling/disabling confirm whether AR is successful by checking CB
21 CB1.79.En_FailCheck 0 state
0: disable, 1: enable
Enabling/disabling auto-reclosing
22 CB1.79.En 1 0: disable, 1: enable
Enabling/disabling AR by external input signal besides logic setting
23 CB1.79.En_ExtCtrl 1 [79.En]
0: only logic setting, 1: logic setting and external input signal
Enabling/disabling AR be initiated by open state of circuit breaker
24 CB1.79.En_CBInit 0 0: disable, 1: enable
Option of AR priority
None: single-breaker arrangement
25 CB1.79.Opt_Priority None High: master AR of multi-breaker arrangement
Low: slave AR of multi-breaker arrangement
Control option of AR mode
26 CB1.79.SetOpt 0 1: select AR mode by internal logic settings
0: select AR mode by external input signals
Enabling/disabling 1-pole AR mode
27 CB1.79.En_1PAR 1 0: disable, 1: enable
Enabling/disabling 3-pole AR mode
28 CB1.79.En_3PAR 0 0: disable, 1: enable
Enabling/disabling 1/3-pole AR
29 CB1.79.En_1P/3PAR 0 mode
0: disable, 1: enable
Transfer trip Settings
No. Item Value Unit Remark
1 TT.t_Op 0.02 s Time delay of transfer trip
Transfer trip controlled by local fault detector element
2 TT.En_FD_Ctrl 1 0: not controlled by local fault detector element
1: controlled by local fault detector element
Trip logic Settings
No. Item Value Unit Remark
Enabling/disabling auto-reclosing blocked when multi-phase fault
1 En_MPF_Blk_AR 1 happens
0: disable, 1: enable
Enabling/disabling auto-reclosing blocked when three-phase fault
2 En_3PF_Blk_AR 1 happens
0: disable, 1: enable
Enabling/disabling auto-reclosing blocked when faulty phase selection
3 En_PhSF_Blk_AR 1 fails
0: disable, 1: enable
Enabling/disabling three-phase tripping mode for any fault conditions
4 CB1.En_Trp3P 0 0: disable, 1: enable
The dwell time of tripping command, empirical value is 0.04 The
5 t_Dwell_Trp 0.04 s tripping contact shall drop off under conditions of no current or
protection tripping element drop-off.
VTS settings
No. Item Value Unit Remark
1 VTS.t_DPU 1.25 s Pickup time delay of VT circuit supervision
2 VTS.t_DDO 10 s Dropoff time delay of VT circuit supervision
26 NR Electric Co., Ltd.
No voltage used for protection calculation
1: enable, 0: disable
3 VTS.En_Out_VT 0 In general, when VT is not connected to the device, this logic setting
should be set as “1”
Voltage selection for protection calculation from busbar VT or line VT
4 VTS.En_LineVT 1 1: line VT, 0: busbar VT
Alarm function of VT circuit supervision
5 VTS.En 1 1: enable, 0: disable
NR Electric Co., Ltd. 27