Alarm & Monitoring System NSS-MD-2001-N3500
Alarm & Monitoring System NSS-MD-2001-N3500
N3500
Alarm & Monitoring System
User Manual
Version 1.02
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Document name
List of Changes
Page 2 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Table of Contents
Abbreviations ........................................................................................................................................... 4
Symbols Used In This Document ............................................................................................................ 4
1 Overview .......................................................................................................................................... 5
1.1. Functions 5
2. System Configurations ..................................................................................................................... 6
2.1. Master Station (Industrial computer) .................................................................................... 6
2.2. I/O Module ............................................................................................................................ 7
2.2.1. Gateway .......................................................................................................................... 8
2.2.2. Stm7-SAFT ..................................................................................................................... 9
2.2.3. Stm7-In32 ........................................................................................................................ 9
2.2.4. Stm7-InOut ...................................................................................................................... 9
2.2.5. Stm7-I/V1 ...................................................................................................................... 10
2.2.6. Stm7-PT100 .................................................................................................................. 11
2.2.7. Stm7-MV1 ..................................................................................................................... 11
2.2.8. Stm7-Ainout .................................................................................................................. 11
2.2.9. D/A2 .............................................................................................................................. 12
2.2.10. N3510 .......................................................................................................................... 12
2.2.11. N3520 .......................................................................................................................... 13
2.3. Failure monitor .................................................................................................................... 15
2.3.1. Communication Status .................................................................................................. 15
2.3.2. Module Communication & Status .................................................................................. 16
Technical Data................................................................................................................................ 17
Page 3 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Abbreviations
AMS Alarm and monitoring system
IAMCS Integrated Alarm Monitoring and Control System
Important notes are following.
NOTICE
Page 4 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
1 Overview
The N3500 alarm & monitoring system is a modular system and can be used as data
acquisition system, monitoring system, control system or as a measuring, monitoring and
control system.
The N3500 architecture consists of various system modules, which can be combined in a
great variety of ways. It can be used as a single system (e.g. data acquisition, alarm system
or safety system) or multi-systems (e.g. Central monitoring system). Other types of integrated
systems such as IAMCS (Integrated Alarm Monitoring and Control System) are also possible.
1.1. Functions
Color mimic display (The pictures can be designed according to customer requirements)
Display simulating gauges
Display bar graphics
Display measuring parameters list
Display measuring parameters list defined by customer
Display actual alarm list
Display alarm history of the day
Display complete alarm history (within the storage information)
Display trend tables
Print measuring parameters list defined by customer
Print measuring parameters list at certain time
Print certain part of parameters list
Print actual alarm list
Print alarm history of the day
Print complete alarm history (within the storage information)
Alarm history can be stored in hard disk automatically everyday;
No matter what contents displayed on monitor, the fast-display window wills pop-up
when new alarm triggered.
According to a specify setting conditional points, the current state of all monitoring points
will be stored in hard disk when this specify conditional point is in alarm condition
The current state of monitoring points can be stored in hard disk by manual
The contents of intraday trend can be stored in hard disk automatically
Page 5 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
2. System Configurations
The system is makes up of modular structures which can be configured differently to meet
various requirements of customers.
Page 6 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
computers basically calculate the data received from the I/O modules and display the
information accordingly.
The Master and Slave computers basically work as a redundancy for each other. In the even
if the Master computer fails, the Slave computer will automatic become the Master and take
over it responsibility.
All the signals acquisition is finished in the modules and exchanges the data with the
computer(s) through the gateways. It makes the signal wiring and maintenance convenience
by this manner. Moreover data communication via cable transmission and the sensor cable
can connect near to the slave, which can greatly short the cable length.
Page 7 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
A maximum of 8 main and 8 backup gateways can be connected within a system. The main
and backup gateways are independent of each other as the connection to the CANBUS is
separated. The main gateway will be connected to the CANBUS 1 while backup gateway will
be connected to the CANBUS 2 of the I/O modules. This redundancy connection improves
the reliability of the system.
Page 8 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Figure 3: Gateway
2.2.2. Stm7-SAFT
The Stm7-SAFT module comprises of 20 binary inputs channels and 20 binary outputs
channels. The first 16 binary inputs channels come with wire-break detection function while
the remaining 4 binary inputs channels are without. For these binary inputs with wire-break
function the input signals must be volt-free normally opened contact (closed to alarm) as the
monitoring & alarm system will provide the power supply to it. A 3kΩ resistor must be
connected across the contact to monitor the wire-break.
2.2.3. Stm7-In32
The Stm7-In32 binary input module is makes up of 32 binary inputs channels. Each input
channel is isolated by optocoupler. The input signal should be passive contact type (dry
contact) in general requirement. The monitoring system will provide the power supply of
signal acquisition.
On the other hand, there are also two input channels for speed measurement (accept pulse
signal only). By using these two input channels, it allows the monitoring of speed discrepancy.
Note: If the input signal is an active contact type (wet contact), it should advice accordingly. A
maximum of 8 Stm7-In32 modules can be connected within a loop.
2.2.4. Stm7-InOut
Page 9 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
The Stm7-InOut module comprises of 13 binary inputs, 2 analogue inputs and 16 binary
outputs channels. The 2 analogue inputs can be configured as either current or voltage.
2.2.5. Stm7-I/V1
The Stm7-I/V1 is an analogue input module for either current or voltage and can accept up to
12 inputs. When used as current inputs signal (4~20mA), it is based on two wires system
with the power supply (DC24V) provided from the module itself to power up the transmitter
(active type).
When the module used as voltage input, it can accept either 0~10V, 2~10V, 0~5V or 1~5V.
The connection method and power supply to the transmitter should be discussed before the
design.
_
NOTICE If the current input signals are different (e.g. 4-
wires system or passive type), it should be
advice accordingly.
Page 10 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
2.2.6. Stm7-PT100
The Stm7-PT100 module comprises of 12 PT100, thermal resistance, input channels. The
PT100 sensor can be connected either as 2 wires, 3 wires or 4 wires system. In general a 3
wires system connection is used as it can reduce the measurement error caused by the
cables resistance. Each channel can define the sensor range accordingly.
2.2.7. Stm7-MV1
The Stm7-MV1 module comprises of 12 thermocouple input channels and can accept
different thermocouple type. Each channel can define the thermocouple type and range
accordingly.
2.2.8. Stm7-Ainout
Page 11 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
The Stm7-Ainout module comprises of 10 binary inputs, 6 binary outputs, 4 analogue inputs
and 2 analogue outputs.
2.2.9. D/A
The D/A module comprise of 16 analogue output channels. Each analogue output can only
be configured as 4~20mA.
2.2.10. N3510
The N3510 is an extension alarm panel from the computers and mainly installed at
accommodation, public areas or Bridge. It has independent functions including signal
acquisition, display and alarm function. The main component of N3510 alarm & display unit is
a 5.7 inches monochrome LCD, which has a resolution of 320x240.
The N3510 alarm & display unit include DC/DC power supply, microcomputer, CAN
communication interface, RS485 communication interface and LAN interface.
The display mode of the unit includes the general list, the alarm list, new alarm list etc. The
unit can show the status of all measuring points within the system.
Page 12 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
2.2.11. N3520
The N3520 is an integrated alarm panel from the computers and mainly installed at
accommodation, public areas and Bridge. It has independent functions including signal
acquisition, display and alarm function. The display component of unit is a 7 inches color
LCD, which has a resolution of 800x480.
The N3520 Integrated alarm & display unit include DC/DC power supply, microcomputer,
CAN communication interface, RS485 communication interface and LAN interface.
The display mode of unit includes mimic graphics, general list, the alarm list, new alarm list
etc. The unit can show the status of all measuring points within the system.
The brightness of the LCD display, LED (except for alarm indicating LED) and buttons on the
unit can be adjusted through the dimmer setting of the screen.
Page 13 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Page 14 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
It’s easy for user to check the communication status. In NoriVisu 3500, click the menu by
following step <Check> - < CAN Comm. Status Check > to access the CAN Communicaton
Status window.
Loop1 and Loop2 means 1st and 2nd gateway loop respectively.
Bin0~7 means Stm7-In32 (max. 8 modules)
Ain0~15 means analogue I/O modules (e.g. Stm7-PT100, Stm7-I/V and Stm7-MV)
BI/O0~3 means Stm7-InOut
Page 15 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Status
OK Database set correct and can receive the data from the module
Unused Module not used and no setting in database
Fail Module failure (e.g. disconnect, communication failure, power failure, etc.)
Un-Ack Module has setting in database but no data receive from the set address
For ‘WORK’ and ‘STA’ indicator, the LEDs must be on (red) when the system is running. For
the remaining LEDs (TX1, RX1, TX2 and RX2), it must be flashing continuous to indicate the
communications are ok.
Page 16 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Gateway
Type: Gateway
Operating voltage 18 … 36 V DC
Power consumption < 5W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1
kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port LAN port x1, CAN_BUS port x2, RS485 port x4
Protection class IP23
Installation position Preferably vertical or inclined from vertical
Mounting In cabinet or plate rail
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.32 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 17 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-SAFT
Type: Stm7-SAFT
Operating voltage 18 … 36 V DC
Power consumption < 5W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Binary input port x10, for line break check
Binary input port x7, 12~36 V DC
Binary output port x8, outputs I < 0.15 A @ 36 V DC
Protection class IP23
Installation position Preferably vertical or inclined from vertical
Mounting In cabinet or plate rail
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.3 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 18 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-In32
Type: Stm7-In32
Operating voltage 18 … 36 V DC
Power consumption < 5W (Not included input signal power)
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1
kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Binary input port x32, 12~36 V DC
Frequency input port x2, 12~36 V DC, 0~50 kHz
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 19 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-InOut
Type: Stm7-InOut
Operating voltage 18 … 36 V DC
Power consumption < 5W (Not included input signal power)
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz… 2000 MHz 80% AM@1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Binary output port x16, outputs I < 0.15 A @ 36 V DC
Binary input port x16, 12~36 V DC (include 3xpor frequency input)
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 20 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-I/V1
Type: Stm7-I/V1
Operating voltage 18 … 36 V DC
Power consumption < 8W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Analog input port x12, current or voltage (signal type and rang to be determined)
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 21 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-PT100
Type: Stm7-PT100
Operating voltage 18 … 36 V DC
Power consumption < 8W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Analog input port x12, Thermal resistance (signal type and rang to be determined)
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 22 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-MV1
Type: Stm7-MV1
Operating voltage 18 … 36 V DC
Power consumption < 5W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Analog input port x12, thermocouple (signal type and rang to be determined)
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 23 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
SAFT
Type: SAFT
Operating voltage 18 … 36 V DC
Power consumption < 5W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1 kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Analog input port x13 digital input with wire bread monitor. Port x 26 digital output
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 221 mm, W: 92 mm
Depth D: 51mm
Weight Approx. 0.35 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 24 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
Stm7-D/A
Type: D/A
Operating voltage 18 … 36 V DC
Power consumption < 10W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1
kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port CAN_BUS port x2
Analog output port x16, 4~20mA,for meter display
Protection class IP23
Installation position In cabinet or plate rail
Mounting In wall / switchgear cabinet cut-out with self-locking clips
Dimensions Front face L: 255 mm, W: 72 mm
Depth D: 51mm
Weight Approx. 0.3 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 25 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
N3510
Type: N3510
Operating voltage 18 … 36 V DC
Power consumption < 8W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1
kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Binary output port x1 outputs I < 0.2 A @ 36 V DC
Communication port LAN port x1, RS485x2
Protection class IP44
Installation position Preferably vertical or inclined from vertical
Mounting 4 stud bolts M4 x 16 mm
Dimensions Front face L: 270 mm, W: 140 mm
Depth D: 64mm
Weight Approx. 0.6 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 26 / 27
NSS-MD-2001-EN N3500
Version 1.02 Alarm & Monitoring System
16/11/2017 - XSQ User Manual
Technical Data
N3520
Type: N3520
Operating voltage 18 … 36 V DC
Power consumption < 5W
Operating temperature as per IEC60068-2-2 and IEC60068-2-1Ad -25 °C … +70 °C
range
Storage temperature range as per IEC60068-2 5°C … +70°C
Relative humidity as per IEC60068-2-3 0 Db ≤ 96 % @ 55 °C
Vibration resistance as per IEC60068-2-6 Fc ±1.0mm @ 2…13 Hz, 0.7g @ 13…100 Hz
Shock resistance (impact) as per IEC60068
ESD as per IEC61000-4-2 8 kV air, 6 kV contact
Electromagnetic field as per IEC61000-4-3 10 V/m f = 80 MHz … 2000 MHz 80% AM @ 1
kHz
10 V/m f = 900 ±5 MHz 50% AM @ 200 Hz
10 V/m f = 1800 ±5 MHz 50% AM @ 200 Hz
Burst as per IEC61000-4-4 ±2 kV operating voltage
±1 kV sensor lines
Surge as per IEC61000-4-5 sym. ± 0.5 kV (Ri=2Ω); asym. ± 1 kV (Ri=12Ω)
Conducted RF interference as per IEC61000-4-6 10 Vrms f = 0.01 …100 MHz 80% AM @ 1 kHz
Conducted AF interference as per IEC60553 10 Vrms f = 0.05 …10 kHz
Interference-field strength as per CISPR 16-1– EMC1
Connections Spring terminals up to core Ø ≤ 2.5 mm²
Communication port LAN port x1, CAN_BUS port x1, RS485 port x1, CAN_BUS port or RS485 port
x1
Binary output port x1 outputs I < 0.2 A @ 36 V DC
Protection class IP23
Installation position Preferably vertical or inclined from vertical
Mounting 4 stud bolts M4 x 16 mm
Dimensions Front face L: 210 mm, W: 165 mm
Depth D: 85mm (Including terminals)
Weight Approx. 0.66 kg
Applicable standards IEC61000-6-2; IEC61000-6-4; IACS Req. 1993/Corr.1, 2003, Section E10
Page 27 / 27