Digital Indicator T904

1. The T904 meter measures AC/DC current, voltage, frequency, and analog signals with various output options including indicator, relay, 4-20mA current loop, and RS485 communication. 2. It has a 7-segment LED display, high/low scaling functions, maximum and minimum value monitoring, and power supply options of 12-24VDC or 100-240VAC. 3. Setup and programming is done through front panel buttons to configure parameters such as output type and measurement range according to the application.

Uploaded by

jovcls
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views5 pages

Digital Indicator T904

1. The T904 meter measures AC/DC current, voltage, frequency, and analog signals with various output options including indicator, relay, 4-20mA current loop, and RS485 communication. 2. It has a 7-segment LED display, high/low scaling functions, maximum and minimum value monitoring, and power supply options of 12-24VDC or 100-240VAC. 3. Setup and programming is done through front panel buttons to configure parameters such as output type and measurement range according to the application.

Uploaded by

jovcls
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

■ Measuning input and range

MANUAL Table 1
Type Measuning input and range
T904 Intelligent Ampere,voltage and Process Meter 0.000-5.000A
0.000-1.000A
AC Ampere
0.0-200.0mA
0.00-20.00mA
0.0-500.0V

■ Features 0.0-200.0V
AC Voltage
Super version of panel meter. 0.00-20.00V
Various output options(Default : Indicator) 0.000-2.000V
RS485 Communication output, Current(4-20mA), NPN/PNP open collector output, AC frequency 1-9999Hz/0.1-999.9Hz/0.10-99.99Hz/0.100-9.999Hz
Relay output. 0.000-5.000A
Max. measuring input specification: 500VDC, 500VAC, 5ADC, 5ACA.
0.000-1.000A
Max. display range : -1999 t0 9999. DC Ampere
0.0-200.0mA
High/Low scale function.
AC frequency measurement function : 0.1 t0 9999Hz. 0.000-2.000mA
Various functions : Monitoring function for max. and min. display value function, display 0.0-500.0V
cycle delay function,Zero function, High display correction function,Current output scale 0.0-200.0V
function. DC Voltage
0.00-20.00V
Wide range of power supply : 12-24VDC, 100-240VAC 50/60Hz.
0.000-2.000V
! Please read "Caution for your safety" in operation manual before using. Analog signal 0-20mA/4-20mA/ 0-10V/2-10V/0-5V/1-5V/0-1V/0-500mV/0-200mV/
(Process Meter) 0-100mV
■ ordering information

T904
■ Specifications
1 2 3 4
23℃+5℃ - DC Type: F.S. +0.1% rdg+2digit /AC Type: F.S. +0.3% rdg+3digit
Display accuracy DC/AC Type F.S +0.3% rdg +3digit max. only for 5A terminal.
1 2 3 -10℃ t0 50℃ - DC/AC Type: F.S.+0.5% rdg+3digit
Dimensions Code Signal input type Code OUTPUT Power supply 100-240VAC 50/60Hz(Allowable voltage range: 90 t0 110%)
Code (width X height)
AA AC Ampere N indication type(no output Power consumption ≤5VA
G 48X48mm function)
AV AC Voltage Display method 7Segment LED display(red)
F 48X96mm 0 relay contact output
Hz AC frequency Measurement input AC Ampere/AC Voltage/AC frequency/DC Ampere/DC Voltage/Analog signal
1 transmission output(4-20mA)
4 DA DC Ampere Max. allowable input 110% F.S for each measured input range
2 RS485 communication output
DV DC Voltage A/D conversion Practical oversampling using successive approximation ADC
Code measuning 3 relay+ 4-20mA method
method for AC Analog signal
SVA 4 relay+RS485 Sampling cycle DC type: 50ms, AC type: 16.6ms
average: (Process Meter)
None avg/root Max. indication range -1999 t0 9999(4digit)
*measuring input range 5 relay+ 4-20mA +RS485
mean square: as shown in Table 1 Relay output - Contact capacity: 250VAC 3A, 30VDC 3A/ Contact composition: N.O(1a)
R Preset output
rms NPN/PNP Open collector output - 12-24VDC +2V 50mA Max. (Resistive load)

[1] [2]
Rs485 communication output - Baud rate: 1200/2400/4800/9600, ■ Parameter setting
Sub output Communication method: 2-wire half duplex, MODE
(Transmission Synchronous method: Asynchronous method, Protocol: Modbus type
MODE 3sec
output)
DC4-20mA output - Resolution: 12,000 division(Load resistance max. 600Ω) PA0 RUN PA2
The first
AC measuring function Selectable RMS or AVG parameter
3sec MODE MODE 3sec
Frequency Measurement range : 0.100 t0 9999Hz(Variable by decimal point position)
measurement function MODE

Hold function Includes(External hold function) PA2 MODE

The first
Auxiliary output voltage DC24V 50mA.Max parameter The next
MODE parameter
Insulation resistance Min. 100MΩ(at 500VDC megger) between external terminal and case

...
Dielectric stength 2,000VAC for lminute between external terminal and case MODE
The last
parameter
Noise stength ±2kV the square wave noise(pulse width : 1µs) by the noise simulator MODE
The next MODE

ambient temperature -10 t0 50℃, storage: -20 t0 60℃ MODE parameter

...
ambient humidity 35 t0 85 % RH storage: 35 t0 85%RH MODE
Set the
The last
‫٭‬AC measuring function, and frequency measuring function are only for AC measuring parameter LOC = 900,
input type. then press MODE
key
‫ ٭‬Environment resistance is rated at no freezing or condensation.

■ DimenSionS (Unit:mm) ‫ ٭‬Press MODE key in RUN status, it will advance to [PA0](Parameter 0) group.
‫ ٭‬Press MODE key for 2 sec. in RUN mode, [PA1] is displayed.
T904-F(48X96mm) ‫ ٭‬set LOC=900 then press the mode key,in [PA1](Parameter 1),[PA2] is displayed.
‫ ٭‬Press MODE key for 3 sec., it is returned to RUN at any position.
Panel cut-out: ‫ ٭‬If any key is not touched for 60 sec. in each parameter, it returns to RUN mode.
HI

GO
‫ ٭‬Press the MODE key in the parameter group can switch the display the next parameter.
LO
48 +0.6
45.5 -0
‫ ٭‬It cannot advance to[PA0] when preset output operation mode of [PA1] is [OFF] .
HOLD

MODE ■ [PA0](Parameter 0) group


T900
99 +0.6
91.5 -0
96 9.5 RUN
T904-G(48X48mm) Press MODE key
Panel cut-out: Set preset High-Iimit value.(Set with , , key)
‫ ٭‬It is displayed when set the preset only.
+0.6 When set in mode if parameter 1 group, the
48 45 -0 parameter is not displayed.
HI GO LO HOLD

MODE

Set preset Low-Iimit value.( Set with , , key)


TMCON T900 86
+0.6
45 -0
‫ ٭‬It is displayed when set the preset only.
48 6 When set in mode if parameter 1 group, the
parameter is not displayed.
■ Front panel identification
It shows High-Iimit monitoring value while it is in RUN mode
lamp Explain Key Explain It will be reset by pressing key.

HI HI : High output indication of preset MODE Mode Key,enters parameter mode.


GO GO : GO output indication of preset Moves digit
LO LO : Low output indication of preset changes Sv,up key It shows Low-Iimit monitoring value while it is in RUN mode
It will be reset by pressing key.
HOLD HOLD input signal indication changes Sv,down KEY ‫ ٭‬lf "00" is set in mode of PA-2, and modes
(T904-F Without this key)
will not be displayed.
[3] [4]
■ [PA1](Parameter 1) group ■ [PA2](Parameter 2) group
Set preset hysteresis. Within 10% of F.S.
RUN But, it is not displayed when mode is .
Press key for 3sec.

Display of factory Select measuring input specification by . It corrects a gradient of High-Iimit display value against
default for Refer to “ ‫ ٭‬Specification of measuring input and range”. max. input.
measunng input The settng range is 0.100 t0 5.000(%).

It corrects deviation of Low-Iimit display value against Min. input


Setting range is -99 t0 99 (Refer to zero point function)
Select the display method of measuring input.
Select
Average Processing( Setting range :OFF-2-4-8-16-32-64-128).
The value of will determine the ability of filtering noise.
When a large value is set, the measurement input is stabilized but
When is the response speed is slow. Generally, it can be set to 2 to 8.

Max. display Decimal point Select decimal point Set monitoring delay time.
value position position Setting range : 00 t0 30sec.

Select zero function with operation at front.


It shows Max. display Max. display Set display value against When + Key key are pressed for 3 sec to set , it will be
value of standard value max. measuring input. zero function and the deviation value is saved automatically at
specification. (Set with , , key) mode.
Display value is fixed. Zero-limit Function.
The zero-limit function changes any value below the set value to
Min. display Set display value against zero.( Setting range : 00~99.)
value min. measuring input.
(Set with , , key) Select input with 6, 7(T904-F) terminal or zero function for
extemal signal.
:Holding display value, : Zero function using Hold/Zero
Select Preset output mode. Selectable: terminal.

Transmission output selection.(0-20mA/4-20mA)

LOC=0-1000,PA1 PA2 parameter group Allows the modification.


LOC=1001-9999,PA1 PA2 parameter group Cannot modify. Set the high limit value, output point of current output 20mA.
(When changing measuring input and prescale mode, it is
Set LOC=900 then press the key,will enter the PA2 parameter. changed automatically as maximum value ofinput range )

Set the low limit value, output point of current output 4mA.
‫ ٭‬Measuring input chart by model. (When changing measuring input and prescale mode, it is
ltem Range of measuring input changed automatically as minimum value ofinput range )

T904-□AA (5A) (1A) (200mA) (20mA) Set the address of RS485 communication output.
Setting range : 01~ 99
T904-□AV (500V) (200V) (20V) (2V)

T904-□DA (5A) (1A) (200mA) (2mA) Select Baud rate of RS485 communication output.
T904-□DV (500V) (200V) (20V) (2V)

T904-□SVA
(0-20mA) (4-20mA) (0-10V) (2-10V) (0-5V) (1-5V) (0-1V) (0-500mV) (0-200mV) (0-100mV)
‫ ٭‬After setting each mode, press key for 3 sec. to return to RUN mode.
[5] [6]
■ Functions • Zero adjustment function(Deviation correction function of low limit display value)
It adjusts the display value of the optional configured input value as zero by force, zero point error
• Display scale function[PA1 group: / ]
can be adjusted with 3 ways as below. When zero point adjustment with front key and Hold terminal is
This function is to display setting(-1999 t0 9999) of particular High/Low-Iimit value in order to display
finished normally, zero point of measurement terminal is displayed and the adjusted value at saved
High/Low-limit value of measured input. If measured inputs are “a ” and “b ” and particular values are
in automatically.
“A ” and “B ”, it will display a=A,b=B as below graphs.
Operation Input correction value Front panel key External input signal
B B B B a A
b b
Display Display Display Display PA1: Direct input Press both , keys Short-circuit external Hold terminal
value value
A
value value
A
A Description correction value for 3 sec. at the No.6, 7(T904-F)]over min. 50ms.
Display Display
A *It is enable to use in option mode.
value value method at mode. measuring mode.
a b a b b a b B B
A
Input value Input value Input value Input value Input value Input value
‫ ٭‬Refer to “ • Error correction function”, “ • Error display function ” and “ ■Parameter 2 ” for function
and error.
• Gradient correction function[PA2 group: ]
It corrects the gradient of prescale value and display value (Picture 1) Display value Y can be used as • Current output(DC4-20mA) scale function[PA2 group: / ]
a, ß times against X input value by correction function[ ] and used as correction function of max. It sets current output for the display value at the output current DC 4-20mA.
display value( ) . Adjustment range is 0 100 t0 5 000 and multiply current gradient. It sets display value for 4mA at and 20mA at and the range between and
Ex)input:200mVDC, Display:3.000 for T904-FDV type should be 10%
OutPut
①Select 0-1VDC(1V) for measured input in Parameter 1 ‫ ٭‬When min. set interval between and is set as under 20mA

②Standard specification in input: 0-1VDC and 1.000 therefore it has to be 15.000( ) for 1VDC 10% F.S., it changed as over 10% F.S. automatically.
Min.

(input) in order to display 3.000 for DC200mV(input). ‫ ٭‬Preset display value is fixed to output as 4mA at under 4mA setting range
Display value
But it is unable due to setting range is 9.999 and 20mA at over .
③in this case, please check below chart. • Monitoring max./min. display value function[PA 0: / ,PA2: ]
15.000
Please set as x =15.000

Display value
12.000 It monitors Max. /Min. display value based on the current displays value and then displays the data at
Display value

aY
a time 9.000
, of parameter 0. Set the delay time(0 t0 30sec. ) at of parameter 2 in order to
setting note
H.SC L.SC Inb.H
method Y ß time Display prevent malfunction caused by initial over current or over voltage, when monitoring the peak value.
ßY 6.000 value for
1 unavailable 0 1.000
measuring Delay time is 0 t0 30sec. and it starts to monitor the peak value after the set time. When pressing any
2 7500 0 2.000 3.000 input
In this case, any Input one of key at , of parameter 0, the monitored data is initialized.
1.000
3 5000 0 3.000 setting methods 0 X value Input
4 3750 0 4.000 display the same 0.2 0.4 0.6 0.8 1V value ‫ ٭‬Monitoring function is not displayed when the delay time is set as “ ” at of parameter 2.
display value
5 3000 0 5.000 (Picture 1) (Example of gradient correction)
• Zero-limit Function [PA2 : ]
Display
The zero-limit function changes any value below the set value to zero.
• Error correction function[PA2 : / ]
This is useful when you want to change negative values to zero rather
It corrects display value error of measured input. Zero-limit
than display them, or when you want to make the display in the
: +99(Adjust deviation of low value) setting value
smallest part of the input range zero.
: 5.000 to 0.100(Correct gradient(%) of high value) Input

Diplay value=(Measured value x )+ •Error display function


When the measured range is 0 to 500V, and the display range is 0 to 500.0. if the low display value is Display Description
“ ” to 0V input, set -12 as the value to display “ ”by adjusting the offset of the low value.
Flashes when measurement input is exceeded the max allowable input (110%)
The display value to the 500V measured input varies by adjusting the offset of the low value. if this
Flashes when measuremnet input is exceeded the min allowable input (-10%)
display value is “ ”,calculate 500.0/501.0(the deslred dlsplay value/the display value), and set
Flashes when display input is exceeded set value
the 0.998 correction value as the to display “ ” by adjusting the gradient of the high value.
-1 Flashes when display input is exceeded set value
‫ ٭‬The offset correction range of is within -99 to for D -0 , D mdigit regardless of dicimal point.
Flashes when input frequency is exceeded the max. display value of measured range
• Average Processing [PA2 : ] Flashes when it exceeds zero range (+ 99)
Average processing stabilizes displayed values to minimize flicker by averaging the fluctuating input
signals. Average processing can be performed for the measurement values in either of eight steps • Initialization function
(OFF, 2 times, 4 times, 8 times,16 times,32 times,64 times, or 128 times). It initializes as the factory default status. If press , , keys together for 2sec. in RUN mode,
This is useful for ignoring rapid fluctuations, e.g., eliminating spike noise. mode and the setting value( ) is displayed every 0.5 sec. and it will be initialized as the factory
default when press key after change
[7] [8]
•AC frequency measurement function • User manual for communication
It measures input signal frequency when it is AC input. It uses fixed decimal point[PA1: ], measured To support the MODBUS RTU communication protocol.
Visit our website (www.china-tmcon.com) download or contact us directly.
range can be changed by setting and measured range of decimal point position is as below chart. It is
available to adjust the upper gradient at [PA 2: ]and [PA 2 : ]. In order to measure ■ Terminal connection
frequency normally, input signal, over 10% F.S. of the measured range, should be supplied.
Please select the proper point of T903-F(48X96mm)
① Measuring range T904-FAA/T904-FAV/T904-FHZ/T904-FDA/T904-FDV T904-FSVA

Decimal point position 0.000 00.00 000.0 0000 GO GO


Measurement range 0.100~9.999HZ 0.10~99.99HZ 0.1~999.9HZ 1~9999HZ HI LO HI LO
R485 4-20mA R485 4-20mA
‫ ٭‬Accuracy of frequency measurement : A B + A B +
Below 1kHz, F.S. ±0.3rdg ± 2digit. 10 11 12 13 14 15 16 17 18 10 11 12 13 14 15 16 17 18
From 1kHz t0 10kHz, F.S. ± 0.3rdg ± 2digit.
② : 0.100 to 9.999 [Gradient adjustment of high value]
-2 1
③ : 10 , 10 -1 , 10 0 , 10 [lndex adjustment of ] OV
1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9
+ + + + + + +
2V
•Preset output mode[PA 1: ] mA
20V POWER V 24VDC POWER
EVIN EVIN
Mode Output operation Operation 200V input
HOLD/ZERO HOLD/ZERO
500V input:
Voltage input mA:DC0-20mA/4-20mA.
H.SEt
HY V:DC0-10V/2-10V/0-5V/
*
2mA/
L.SEt HY: Hysterisis 20mA 1-5V/0-1V/0-500mV/
200mA 0-200mV/0-100mV.
1A
No output 5A

If is equal or lower than Low setting value, * No.4, 5 terminal AA for 20mA, DA for 2mA
GO LO output is ON.
LO HY if it is higher than Low setting value, T904-G(48X48mm)
GO output is ON.
T904-GAA/T904-GAV/T904-GHZ/T904-GDA/T904-GDV T904-GSVA
If it is equal or higher than High Setting value,
HI HY Hl output is ON.
5A
GO If it is equal or lower than High Setting value, Ampere input input:
GO output is ON. 1A
200mA * No.4, 5 terminal mA:DC0-20mA/4-20mA.
LO output is ON when it is equal or lower than AA for 20mA, V:DC0-10V/2-10V/0-5V/
20mA
Low setting Value. /2mA DA for 2mA
HI HY 1-5V/0-1V/0-500mV/
HI output is ON when it is equal or higher than * 0-200mV/0-100mV.
GO High setting value. 500V
LO HY GO output is ON when it is higher than Low 200V Voltage input input
setting value, and lower than High setting value. 20V V mA 24VDC
2V
LO output is ON when it is equal or higher than + + +
HI HY Low setting value. 6 7 8 9 10 6 7 8 9 10
HI output is ON when it is equal or higher than OV
GO High setting value.
LO HY GO output is ON when it is lower than Low/High 12 12

4-20mA

4-20mA
+

+
A

A
R485

R485
setting value.
11 11
LO output is ON when it is lower than Low

B
13 13
HI HY setting value. * Can only * Can only
Hl output is ON when it is equal or lower than choose one choose one
GO High Settlng value. 1 2 3 4 5 1 2 3 4 5
LO HY GO output is ON when it is higher than Low/High
setting value.
POWER POWER
HI HI
It is operated same with but LO output does
not operated under initial Low setting value, and LO LO
GO
it is ON from under next Low setting value.
LO HY If this is higher than Low setting value,
GO output is ON ALLSENTECH CO., LTD. Phone:02-102-5314 Hotline:089-206-2445
768/192 Pattanakarn road, Suanluang, Suanluang, http://www.allsentech.com E-mail:[email protected]
‫٭‬ i s displayed according to the Setting of output operation mode,when user sets “ ”, Bangkok, Thailand 10250
/ are not displayed.
[9] [10]