Digital Indicator T904
Digital Indicator T904
MANUAL Table 1
Type Measuning input and range
T904 Intelligent Ampere,voltage and Process Meter 0.000-5.000A
0.000-1.000A
AC Ampere
0.0-200.0mA
0.00-20.00mA
0.0-500.0V
■ Features 0.0-200.0V
AC Voltage
Super version of panel meter. 0.00-20.00V
Various output options(Default : Indicator) 0.000-2.000V
RS485 Communication output, Current(4-20mA), NPN/PNP open collector output, AC frequency 1-9999Hz/0.1-999.9Hz/0.10-99.99Hz/0.100-9.999Hz
Relay output. 0.000-5.000A
Max. measuring input specification: 500VDC, 500VAC, 5ADC, 5ACA.
0.000-1.000A
Max. display range : -1999 t0 9999. DC Ampere
0.0-200.0mA
High/Low scale function.
AC frequency measurement function : 0.1 t0 9999Hz. 0.000-2.000mA
Various functions : Monitoring function for max. and min. display value function, display 0.0-500.0V
cycle delay function,Zero function, High display correction function,Current output scale 0.0-200.0V
function. DC Voltage
0.00-20.00V
Wide range of power supply : 12-24VDC, 100-240VAC 50/60Hz.
0.000-2.000V
! Please read "Caution for your safety" in operation manual before using. Analog signal 0-20mA/4-20mA/ 0-10V/2-10V/0-5V/1-5V/0-1V/0-500mV/0-200mV/
(Process Meter) 0-100mV
■ ordering information
T904
■ Specifications
1 2 3 4
23℃+5℃ - DC Type: F.S. +0.1% rdg+2digit /AC Type: F.S. +0.3% rdg+3digit
Display accuracy DC/AC Type F.S +0.3% rdg +3digit max. only for 5A terminal.
1 2 3 -10℃ t0 50℃ - DC/AC Type: F.S.+0.5% rdg+3digit
Dimensions Code Signal input type Code OUTPUT Power supply 100-240VAC 50/60Hz(Allowable voltage range: 90 t0 110%)
Code (width X height)
AA AC Ampere N indication type(no output Power consumption ≤5VA
G 48X48mm function)
AV AC Voltage Display method 7Segment LED display(red)
F 48X96mm 0 relay contact output
Hz AC frequency Measurement input AC Ampere/AC Voltage/AC frequency/DC Ampere/DC Voltage/Analog signal
1 transmission output(4-20mA)
4 DA DC Ampere Max. allowable input 110% F.S for each measured input range
2 RS485 communication output
DV DC Voltage A/D conversion Practical oversampling using successive approximation ADC
Code measuning 3 relay+ 4-20mA method
method for AC Analog signal
SVA 4 relay+RS485 Sampling cycle DC type: 50ms, AC type: 16.6ms
average: (Process Meter)
None avg/root Max. indication range -1999 t0 9999(4digit)
*measuring input range 5 relay+ 4-20mA +RS485
mean square: as shown in Table 1 Relay output - Contact capacity: 250VAC 3A, 30VDC 3A/ Contact composition: N.O(1a)
R Preset output
rms NPN/PNP Open collector output - 12-24VDC +2V 50mA Max. (Resistive load)
[1] [2]
Rs485 communication output - Baud rate: 1200/2400/4800/9600, ■ Parameter setting
Sub output Communication method: 2-wire half duplex, MODE
(Transmission Synchronous method: Asynchronous method, Protocol: Modbus type
MODE 3sec
output)
DC4-20mA output - Resolution: 12,000 division(Load resistance max. 600Ω) PA0 RUN PA2
The first
AC measuring function Selectable RMS or AVG parameter
3sec MODE MODE 3sec
Frequency Measurement range : 0.100 t0 9999Hz(Variable by decimal point position)
measurement function MODE
The first
Auxiliary output voltage DC24V 50mA.Max parameter The next
MODE parameter
Insulation resistance Min. 100MΩ(at 500VDC megger) between external terminal and case
...
Dielectric stength 2,000VAC for lminute between external terminal and case MODE
The last
parameter
Noise stength ±2kV the square wave noise(pulse width : 1µs) by the noise simulator MODE
The next MODE
...
ambient humidity 35 t0 85 % RH storage: 35 t0 85%RH MODE
Set the
The last
٭AC measuring function, and frequency measuring function are only for AC measuring parameter LOC = 900,
input type. then press MODE
key
٭Environment resistance is rated at no freezing or condensation.
■ DimenSionS (Unit:mm) ٭Press MODE key in RUN status, it will advance to [PA0](Parameter 0) group.
٭Press MODE key for 2 sec. in RUN mode, [PA1] is displayed.
T904-F(48X96mm) ٭set LOC=900 then press the mode key,in [PA1](Parameter 1),[PA2] is displayed.
٭Press MODE key for 3 sec., it is returned to RUN at any position.
Panel cut-out: ٭If any key is not touched for 60 sec. in each parameter, it returns to RUN mode.
HI
GO
٭Press the MODE key in the parameter group can switch the display the next parameter.
LO
48 +0.6
45.5 -0
٭It cannot advance to[PA0] when preset output operation mode of [PA1] is [OFF] .
HOLD
MODE
Display of factory Select measuring input specification by . It corrects a gradient of High-Iimit display value against
default for Refer to “ ٭Specification of measuring input and range”. max. input.
measunng input The settng range is 0.100 t0 5.000(%).
Max. display Decimal point Select decimal point Set monitoring delay time.
value position position Setting range : 00 t0 30sec.
Set the low limit value, output point of current output 4mA.
٭Measuring input chart by model. (When changing measuring input and prescale mode, it is
ltem Range of measuring input changed automatically as minimum value ofinput range )
T904-□AA (5A) (1A) (200mA) (20mA) Set the address of RS485 communication output.
Setting range : 01~ 99
T904-□AV (500V) (200V) (20V) (2V)
T904-□DA (5A) (1A) (200mA) (2mA) Select Baud rate of RS485 communication output.
T904-□DV (500V) (200V) (20V) (2V)
T904-□SVA
(0-20mA) (4-20mA) (0-10V) (2-10V) (0-5V) (1-5V) (0-1V) (0-500mV) (0-200mV) (0-100mV)
٭After setting each mode, press key for 3 sec. to return to RUN mode.
[5] [6]
■ Functions • Zero adjustment function(Deviation correction function of low limit display value)
It adjusts the display value of the optional configured input value as zero by force, zero point error
• Display scale function[PA1 group: / ]
can be adjusted with 3 ways as below. When zero point adjustment with front key and Hold terminal is
This function is to display setting(-1999 t0 9999) of particular High/Low-Iimit value in order to display
finished normally, zero point of measurement terminal is displayed and the adjusted value at saved
High/Low-limit value of measured input. If measured inputs are “a ” and “b ” and particular values are
in automatically.
“A ” and “B ”, it will display a=A,b=B as below graphs.
Operation Input correction value Front panel key External input signal
B B B B a A
b b
Display Display Display Display PA1: Direct input Press both , keys Short-circuit external Hold terminal
value value
A
value value
A
A Description correction value for 3 sec. at the No.6, 7(T904-F)]over min. 50ms.
Display Display
A *It is enable to use in option mode.
value value method at mode. measuring mode.
a b a b b a b B B
A
Input value Input value Input value Input value Input value Input value
٭Refer to “ • Error correction function”, “ • Error display function ” and “ ■Parameter 2 ” for function
and error.
• Gradient correction function[PA2 group: ]
It corrects the gradient of prescale value and display value (Picture 1) Display value Y can be used as • Current output(DC4-20mA) scale function[PA2 group: / ]
a, ß times against X input value by correction function[ ] and used as correction function of max. It sets current output for the display value at the output current DC 4-20mA.
display value( ) . Adjustment range is 0 100 t0 5 000 and multiply current gradient. It sets display value for 4mA at and 20mA at and the range between and
Ex)input:200mVDC, Display:3.000 for T904-FDV type should be 10%
OutPut
①Select 0-1VDC(1V) for measured input in Parameter 1 ٭When min. set interval between and is set as under 20mA
②Standard specification in input: 0-1VDC and 1.000 therefore it has to be 15.000( ) for 1VDC 10% F.S., it changed as over 10% F.S. automatically.
Min.
(input) in order to display 3.000 for DC200mV(input). ٭Preset display value is fixed to output as 4mA at under 4mA setting range
Display value
But it is unable due to setting range is 9.999 and 20mA at over .
③in this case, please check below chart. • Monitoring max./min. display value function[PA 0: / ,PA2: ]
15.000
Please set as x =15.000
Display value
12.000 It monitors Max. /Min. display value based on the current displays value and then displays the data at
Display value
aY
a time 9.000
, of parameter 0. Set the delay time(0 t0 30sec. ) at of parameter 2 in order to
setting note
H.SC L.SC Inb.H
method Y ß time Display prevent malfunction caused by initial over current or over voltage, when monitoring the peak value.
ßY 6.000 value for
1 unavailable 0 1.000
measuring Delay time is 0 t0 30sec. and it starts to monitor the peak value after the set time. When pressing any
2 7500 0 2.000 3.000 input
In this case, any Input one of key at , of parameter 0, the monitored data is initialized.
1.000
3 5000 0 3.000 setting methods 0 X value Input
4 3750 0 4.000 display the same 0.2 0.4 0.6 0.8 1V value ٭Monitoring function is not displayed when the delay time is set as “ ” at of parameter 2.
display value
5 3000 0 5.000 (Picture 1) (Example of gradient correction)
• Zero-limit Function [PA2 : ]
Display
The zero-limit function changes any value below the set value to zero.
• Error correction function[PA2 : / ]
This is useful when you want to change negative values to zero rather
It corrects display value error of measured input. Zero-limit
than display them, or when you want to make the display in the
: +99(Adjust deviation of low value) setting value
smallest part of the input range zero.
: 5.000 to 0.100(Correct gradient(%) of high value) Input
If is equal or lower than Low setting value, * No.4, 5 terminal AA for 20mA, DA for 2mA
GO LO output is ON.
LO HY if it is higher than Low setting value, T904-G(48X48mm)
GO output is ON.
T904-GAA/T904-GAV/T904-GHZ/T904-GDA/T904-GDV T904-GSVA
If it is equal or higher than High Setting value,
HI HY Hl output is ON.
5A
GO If it is equal or lower than High Setting value, Ampere input input:
GO output is ON. 1A
200mA * No.4, 5 terminal mA:DC0-20mA/4-20mA.
LO output is ON when it is equal or lower than AA for 20mA, V:DC0-10V/2-10V/0-5V/
20mA
Low setting Value. /2mA DA for 2mA
HI HY 1-5V/0-1V/0-500mV/
HI output is ON when it is equal or higher than * 0-200mV/0-100mV.
GO High setting value. 500V
LO HY GO output is ON when it is higher than Low 200V Voltage input input
setting value, and lower than High setting value. 20V V mA 24VDC
2V
LO output is ON when it is equal or higher than + + +
HI HY Low setting value. 6 7 8 9 10 6 7 8 9 10
HI output is ON when it is equal or higher than OV
GO High setting value.
LO HY GO output is ON when it is lower than Low/High 12 12
4-20mA
4-20mA
+
+
A
A
R485
R485
setting value.
11 11
LO output is ON when it is lower than Low
B
13 13
HI HY setting value. * Can only * Can only
Hl output is ON when it is equal or lower than choose one choose one
GO High Settlng value. 1 2 3 4 5 1 2 3 4 5
LO HY GO output is ON when it is higher than Low/High
setting value.
POWER POWER
HI HI
It is operated same with but LO output does
not operated under initial Low setting value, and LO LO
GO
it is ON from under next Low setting value.
LO HY If this is higher than Low setting value,
GO output is ON ALLSENTECH CO., LTD. Phone:02-102-5314 Hotline:089-206-2445