Honeywell - RC500 - Software Installation User Guide
Honeywell - RC500 - Software Installation User Guide
Honeywell RC500
Software Installation User's Guide
RC-DCX210
R200
November 2011
Release 200
Honeywell
Notices and Trademarks
Copyright 2011 by Honeywell International Sárl.
Release 200 November 2011
While this information is presented in good faith and believed to be accurate, Honeywell disclaims
the implied warranties of merchantability and fitness for a particular purpose and makes no
express warranties except as may be stated in its written agreement with and for its customers.
In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The
information and specifications in this document are subject to change without notice.
Honeywell, PlantScape, Experion PKS, and TotalPlant are registered trademarks of Honeywell
International Inc.
Release Information
Document Name Document ID Release Publication
Number Date
References
The following list identifies all documents that may be sources of reference for material discussed
in this publication.
Document Title
Pacific
Contact: Honeywell Global TAC – Pacific
Phone: 1300-364-822 (toll free within Australia)
+61-8-9362-9559 (outside Australia)
Fascimile: +61-8-9362-9564
Mail: Honeywell Limited Australia
5 Kitchener Way
Burswood 6100, Western Australia
Email: [email protected]
India
Contact: Honeywell Global TAC – India
Phone: +91-20- 6603-9400
Fascimile: +91-20- 6603-9800
Mail: Honeywell Automation India Ltd
56 and 57, Hadapsar Industrial Estate
Hadapsar, Pune –411 013, India
Email: [email protected]
Korea
Contact: Honeywell Global TAC – Korea
Phone: +82-80-782-2255 (toll free within Korea)
Fascimile: +82-2-792-9015
Mail: Honeywell Co., Ltd
4F, Sangam IT Tower
1590, DMC Sangam-dong, Mapo-gu
Seoul, 121-835, Korea
Email: [email protected]
Singapore
Contact: Honeywell Global TAC – South East Asia
Phone: +65-6580-3500
Fascimile: +65-6580-3501
+65-6445-3033
Mail: Honeywell Private Limited
Honeywell Building
17, Changi Business Park Central 1
Singapore 486073
Email: [email protected]
Taiwan
Contact: Honeywell Global TAC – Taiwan
Phone: +886-7-536-2567
Fascimile: +886-7-536-2039
Mail: Honeywell Taiwan Ltd.
17F-1, No. 260, Jhongshan 2nd Road.
Cianjhen District
Kaohsiung, Taiwan, ROC
Email: [email protected]
Japan
Contact: Honeywell Global TAC – Japan
Phone: +81-3-6730-7160
Fascimile: +81-3-6730-7228
Mail: Honeywell Japan Inc.
New Pier Takeshiba, South Tower Building,
20th Floor, 1-16-1 Kaigan, Minato-ku,
Tokyo 105-0022, Japan
Email: [email protected]
Elsewhere
Call your nearest Honeywell office.
http://www.honeywell.com/ps
Training Classes
Honeywell Automation College:
http://www.automationcollege.com
Symbol Definitions
The following table lists those symbols used in this document to denote certain conditions.
Symbol Definition
Symbol Definition
5.2 Taking backup of Honeywell RC500 I/O Tool Kit project ..........................33
5.3 Modifying Honeywell RC500 I/O Tool Kit components .............................34
5.4 Repairing Honeywell RC500 I/O Tool Kit components .............................35
5.5 Removing Honeywell RC500 I/O Tool Kit ...................................................36
5.6 Taking backup of ISaGRAF project.............................................................37
5.7 Removing ISaGRAF ......................................................................................38
5.8 Removing ISaGRAF Open license manager ..............................................39
RC500 components
• Remote Terminal Unit (RTU)
− RC-SCONTRL
− RC-MVACONTRL
− RC-MVBCONTRL
• I/O module
− Ethernet I/O-2
• Honeywell RC500 I/O Tool Kit
• ISaGRAF Open
ISaGRAF Open
ISAGRAF programming for RC500 provides IEC 61131 standard programming
languages such as, Sequential Function Chart (SFC), Ladder Diagram, Structured Text
(ST), Instruction List (IL), Function Block Diagram, and Flow Charting.
Graphical Programming: ISaGRAF combines ladder logic with powerful function
blocks to provide you the simplicity of a PLC, and the performance of a high-end process
controller.
Text Programming: IEC 61131 statement language uses simple text that is easy to learn
and maintain.
Multi-Tasking Organization: SFC organizes the programs into tasks or sequential steps.
Each SFC block may be a Ladder Diagram, Structured Text or Instruction list.
On-Line Program Changes: This helps to improve processes without waiting for
shutdowns. The ISaGRAF Workbench lets you make changes in program at any time.
Program Simulation: ISaGRAF has a program simulator that displays how your
program works before the actual startup. You can develop and debug your programs
quickly and easily, and then load them to a RC500 programmable node.
Direct RC500 tag references: The tag names from the Honeywell RC500 I/O Tool Kit
configuration appear automatically in ISaGRAF using Export option. These names are
reflected automatically in program logic and save significant programming time.
ATTENTION
Ensure to restart your antivirus services after you completed the installation.
Step Action
1 Choose Start > All Programs > McAfee > VirusScan Console.
2 In the VirusScan Console window, choose Task > Properties.
Step Action
1 Right-click the McAfee icon on the taskbar.
2 Click VirusScan Enterprise and VirusScan Console.
If the VirusScan console is not available in the notification area, then browse
to C:\Program Files\McAfee\VirusScan Enterprise\shcfg32.exe.
3 In the User Account Control dialog box, click Yes.
4 Double-click On-Access Scanner, and click the ScriptScan tab.
5 Clear Enable ScriptScan check box and click Apply.
6 Click All Processes in the left pane, and click the Detection tab.
7 Click Exclusions.
8 Click Add.
9 Click Browse and browse to the C:\Program Files\Honeywell directory, and
click OK.
10 Select Also exclude subfolders check box, and click OK to close the dialog
boxes.
Step Action
1 Insert the RC500 R200.1 CD into the CD-ROM drive.
2 Browse to the folder containing the Honeywell RC500 I/O Tool Kit and
double-click the HoneywellIOTools.exe.
The Welcome to the Honeywell I/O Tool Kit Setup Wizard page appears.
3 Click Next.
If you want to change the default destination folder, click Browse to specify a
different destination folder.
6 Click Install.
After installation is complete, the Completing the Honeywell I/O Tool Kit
Setup Wizard page appears.
7 Click Finish.
Step Action
1 Insert the RC500 R200.1 CD into the CD-ROM drive.
2 Browse to the folder containing the ISaGRAF Open and double-click
isaopen.exe.
Step Action
or
ATTENTION
It is recommended to restart the computer after ISaGRAF
installation.
9 Click Finish.
Step Action
1 Insert the RC500 R200.1 CD into the CD-ROM drive.
2 Copy “RTU_Display” folder to “C:\ProgramData\Honeywell\Experion
PKS\Client\Abstract.”
ATTENTION
Contents in RTU_Display folder are:
• Folder “Styles”
To register the Honeywell RC500 I/O Tool Kit license using the CD-ROM drive,
perform the following steps.
Step Action
1 Insert the RC500 R200.1 CD into the CD-ROM drive.
ATTENTION
If you do not have the Honeywell RC500 R200.1 CD, refer to
Registering Honeywell RC500 I/O Tool Kit license manually.
2 Choose Start > All Programs > Honeywell Tools > Honeywell RC500 I/O
Tool Kit .
Step Action
5 Browse for the Honeywell.6rg file in the RC500 R200.1 CD and import it.
To register the Honeywell RC500 I/O Tool Kit license manually, perform the following
steps.
Step Action
1 Choose Start > All Programs > Honeywell Tools > Honeywell RC500 I/O
Tool Kit.
Note:
4 Click Next.
Step Action
5 Select the following features.
• Basic setup and maintenance of hardware modules
Step Action
8 Click Enter Registration Number.
A dialog box appears informing you to type the Registration number and
Number of stations authorized.
12 Enter information in the Registration number and Number of stations
authorized boxes and click OK.
ATTENTION
To edit the registration number, double-click it for the respective
Product Name.
13 In the Add-on Registration dialog box, click OK.
14 Close the Registration Status dialog box.
Step Action
1 Connect the USB Dongle to the system where ISaGRAF is installed.
2 Choose Start > All Programs > Honeywell Tools > Honeywell RC500 I/O
Tool Kit.
For example, if you type the part number RC-OW-1131-32 that is available
with the USB Dongle, 32 indicates the number of tags that can be exported.
Step Action
ATTENTION
Following are the part numbers for ISaGRAF that are available with
the respective registration numbers.
RC-OW-1131-256 02P2-D9EC-317
RC-OW-1131-1000 02P3-8E0A-0C6
RC-OW-1131-BIG 02P4-C4BE-AB7
6 Enter version number and registration number for ISaGRAF. These details
are available in the document that is shipped along with the RC500 R200.1
CD.
7 Click OK.
Step Action
1 Insert the RC500 R200.1 CD into the CD-ROM drive.
2 Browse to the folder containing the Switch Utility and double-click the
SwitchUtility.exe.
If you want to change the default destination folder, click Browse to specify a
different destination folder.
Step Action
ATTENTION
You must install Java runtime for Switch Utility to run, and load. If
Java runtime, was installed in your computer. A confirmation
message appears.
You can perform any one of the following:
• Click Yes to reinstall.
Or
• Click No to ignore.
8 Click Close after installing Java runtime.
Step Action
1 Start the Honeywell RC500 I/O Tool Kit application.
2 On the menu bar, click File > Save Project As.
Step Action
1 a) Choose Start > Control Panel > Add or Remove Programs.
or
a) Insert the RC500 R200.1 CD into the CD-ROM drive.
b) Browse to the folder containing the Honeywell RC500 I/O Tool Kit and
double-click the HoneywellIOTools.exe.
c) Click Run.
or
• If you want to add a component, select the component.
4 Click Next.
The Honeywell RC500 I/O Tool Kit is modified with the required components.
ATTENTION
Repair option is currently not supported through Add/remove
programs.
2 Browse to the folder containing the Honeywell RC500 I/O Tool Kit and
double-click HoneywellIOTools.exe.
or
a) Insert the RC500 R200.1 CD into the CD-ROM drive.
b) Browse to the folder containing the Honeywell RC500 I/O Tool Kit and
double-click the HoneywellIOTools.exe.
c) Click Run.
4 Select Don’t display this message again and then click Yes.
Step Action
1 Browse for the folder that contains the ISaGRAF project at the following
location C:\Program Files\ISaGRAF Open\Projects\ISaGRAF \Prj.
2 Select the project folder that you want to take backup and zip it.
3 Browse to any location and save the zip file.
or
a) Insert the RC500 R200.1 CD into the CD-ROM drive.
b) Browse to the folder containing the ISaGRAF Open and double-click the
isaopen.exe.
c) Click Run.
or
ATTENTION
It is recommended to restart the computer after you remove
ISaGRAF.
4 Click Finish.
Step Action
1 Choose Start > Control Panel > Add or Remove Programs.