POWERCOMMAND®
GTEC TRANSFER SWITCH
POWERCOMMAND® 40-02 CONTROL | OPEN TRANSITION | 40 A – 2000 A
AUTOMATIC TRANSFER SWITCH (IEC)
DESCRIPTION
GTEC transfer switches combine reliability
and flexibility in a small, economic package.
The GTEC series transfer switch provides the basic
features typically required for primary source and
generator set monitoring, generator set starting and
load transfer functions for emergency standby power
applications. The are suitable for use in emergency,
legally required, and optional standby circuits in
commercial and light industrial applications. The GTEC
transfer switch features the new PowerCommand®
40-02 control with a comprehensive feature list to suite
a wide variety of ATS applications.
FEATURES
PowerCommand® 40-02 control – A sophisticated, Advanced transfer switch mechanism – True transfer
fully featured microprocessor-based control with switch mechanism with break-before-make action.
LCD digital display and tactile-feel soft-switches
for easy operation and screen navigation. Control Manual operation – Standard removable handle
highlights include Modbus communication, front panel can be used to manually operate the switch after the
PC software configuration. Advanced features include, power source has been completely disconnected.
three phase sensing on both sources, manual restore
to S1, synch check, and event logging capability. Multi-voltage rating – The multiple selectable
Please see the PowerCommand® 40-02 control speci- voltage setting is adjustable. So GTEC can be
fication sheet S-6561 for the full description, benefits applied to voltages from 110 V to 277 V
and features. without external transformers.
Programmed transition – Open transition timing Positive interlocking – Mechanical and electrical
can be adjusted to completely disconnect the load interlocking prevent source-to-source connection
from both sources for a programmed time period. through the power or control wiring.
Recommended for inductive loads to prevent
nuisance tripping.
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
Main contacts – Silver alloy contacts with multi-leaf A mechanical interlock prevents simultaneous
arc chutes are rated for 100% load interruption. They closing of normal and emergency contacts.
require no routine contact maintenance and provide Electrical interlocks prevent simultaneous closing
100% Continuous current ratings. signals to normal and emergency contacts and
interconnection of normal and emergency sources
Ease of service and access – Single-plug harness through the control wiring.
connection and compatible terminal markings simplify High-pressure silver alloy contacts resist burning
servicing. Access space is ample. Door-mounted and pitting. Separate arcing surfaces further protect
controls are field-programmable; no special tools the main contacts. Contacts are mechanically held
are required. in both normal and emergency positions for reliable,
quiet operation.
Complete product line – Cummins is a single
Contact wear is reduced by multiple leaf arc chutes
source supplier with a wide range of equipment,
that cool and quench the arcs. Barriers separate
accessories and services to suit virtually any
the phases to prevent interphase flashover.
backup power application.
Protective covers for lugs are available.
Warranty and service - Products are backed by
a comprehensive warranty and a worldwide network
of distributors with factory-trained service technicians.
TRANSFER SWITCH MECHANISM
A powerful, economical AC solenoid operates
GTEC transfer switches.
Independent break-before-make action is used
for 2-pole, 3-pole and 4-pole switches. On 4-pole/
switched neutral switches, this action prevents the
objectionable ground currents and nuisance ground
fault tripping that can result from overlapping designs.
SPECIFICATIONS
Voltage rating Up to 480 V AC, 50 or 60 Hz.
Arc interruption Multiple leaf arc chutes provide dependable arc interruption.
Neutral bar A full current-rated neutral bar is standard on enclosed 3-pole transfer switches.
Two isolated contacts (one for each source) indicating switch position are provided for customer
use. Contacts are normally open, and close to indicate connection to the source. Wired
Auxiliary contacts
to terminal block for easy access. Rated at 5 amps Continuous at 100 V AC or 2.5 amps
Continuous at 200 V AC.
Operating temperature -22 ˚F (-30 ˚C) to 140 ˚F (60 ˚C)
Storage temperature -40 ˚F (-40 ˚C) to 140 ˚F (60 ˚C)
Humidity Up to 95 % at 20 ˚C
Altitude Up to 6,561 ft (2,000 m) without derating
Total transfer time Will not exceed 100msec with normal voltage applied to the actuator and without programmed
(source-to-source) transition enabled.
Transfer switches are equipped with a removable operating handle which allows operation
Manual operation*
during servicing to facilitate troubleshooting with sources of power
*See Operator Manual for further details.
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
TRANSITION MODES ‘Return to programmed transition’ function is active in
Open delayed transition – In this transition mode which case after 2 minutes it performs a programmed
the time required for the transfer switch to transfer delayed transfer.
between sources is adjustable so that the load-
generated voltages decay to a safe level before ACCESSORIES
connecting to an energized source. Recommended Elevator signal relay (M032) – Provides relay output
by NEMA MG-1 to prevent nuisance tripping breakers contacts for sending a load-disconnect warning signal
and load damage. Adjustable 0.5 secs - 10 minutes, to the elevator control. Transfer/re-transfer delay time
and default 0.5 seconds. is selectable for 0, 1, 2, 3, 5, 30, 120 or 300 seconds.
Open in-phase translation – Initiates open transition ELECTRICAL PERFORMANCE
transfer when in-phase monitor senses both sources The transfer switches listed below must be protected
are in phase (voltage, phase and frequency). Operates by circuit breakers or fuses. The following WCR
in a break-before-make sequence. Includes ability ratings are available when protecting the transfer
to enable programmed transition as a backup. The switch with a circuit breaker or fuse. Short circuit
module waits indefinitely for synchronization unless the ratings are stated in symmetrical RMS ampere.
FUSE PROTECTION
Frame Amperage rating (A) WCR rating (kA) Fuse size and type
A 40, 63 26 RT16NT-00 63 A IEC NH Fuse type
B 100, 125 26 RT16NT-00 125 A IEC NH Fuse type
C 160, 200, 225, 250 38 RT16NT-2 250 A IEC NH Fuse type
D 350, 400, 500 50 RT16NT-3 500 A IEC NH Fuse type
E 630, 800 55 RT16NT-4 800 A IEC NH Fuse type
F 1000, 1250 65 RT16NT-4 1250 A IEC NH Fuse type
G 1600, 2000 120 KRP-C 3000 A Class L Fuse type
*All WCR values are at 480 V max with current limiting fuse
CIRCUIT BREAKER PROTECTION
Amperage Max breaker
Frame Specified circuit breaker protection manufacturer, model and type
rating (A) rating (A)
Schneider: NSX160FTM, EZD100, NSD100F, NSD100K Siemens: 3VU,
A 40, 63 63
3RV1, 3VT1 ABB: Isomax S1, S2X80, Sim100
Schneider: NSX160FTM, NSD160K Siemens: 3VL, 3VT1 ABB: Isomax S2,
B 100, 125 125
Isomax S3, S3X, Sim250
Schneider: NSX250NTM, NSD250K Siemens: 3VL, 3VT2 ABB: Isomax S3,
C 160, 200, 225, 250 250
S4X, Sim250
Schneider: NSX630NTM, NSD630K Siemens: 3VL,3VT3 ABB: Isomax S4,
D 350, 400, 500 500
S6X, Sim500
Schneider: MT08, MT10, NW08 Siemens: 3VL, 3WT, 3VT4 ABB: Isomax S6,
E 630, 800 800
E1B, E1N, E1S
F 1000, 1250 1250 Schneider: MT12, NW16 Siemens: 3VL, 3WT, 3VT5 ABB: Isomax S7, E2B, E2L
Schneider: MT20, MT25, NW20, NW25 Siemens: 3WT ABB: E1N, E2N,
G 1600, 2000 2000
E2S, E3S
*All WCR values are at 480 V max with current limiting fuse
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
ENCLOSURE
The transfer switch and control are mounted in a key-operated locked enclosure. Enclosures meet IEC 60947- 6-1
standard. Standard enclosure is grey.
DIMENSIONS – TRANSFER SWITCH IN IP32 AND 1P54 ENCLOSURES
Frame Amperage (A) Height Width Depth Weight Outline drawing
in mm in mm in mm lb kg
A 40, 63
27 680 22.4 570 9.1 231 106 48 A065V089
B 100, 125
C 160, 200, 225, 250
37.4 950 25.6 650 9.1 231 139 63 A065V174
D 350, 400, 500
E 630, 800
54 1370 30 750 24.8 630 415 188 A065V183
F 1000, 1250
G 1600, 2000 81.3 2065 39.4 1000 45.4 1154 893 405 A065V102
ENCLOSURE ACCESS FOR CABLE INSTALLATION AND MAINTENANCE
All frames allow for top, side, and bottom cable entry. NEC Requires Minimum 36” Front Access. Additional front
clearance is needed to remove the mechanism. Refer to the outline drawing.
MODEL NAMING STRUCTURE
The model number is made up of code segments that designate various features or options.
VOLTAGE
POLES CODE FREQUENCY
GT 4 0040 U N 7 2
GTEC AMPERAGE CONTROL ENCLOSURE
TYPE
Poles Frequency
3 Poles (solid neutral) 50/60 Hz
4 Poles (switched neutral)
Enclosure
Amperage 2 = IP32
40, 63, 100, 125, 160, 200, 225, 250, 350, 400, 3 = IP54
500, 630, 800, 1000, 1250, 1600, 2000 A
Warranty
Voltage code 1 year comprehensive
U = Multi-voltage 110/190 – 277/480 V
Y = 220/380 V, 230/400 V, 240/416 V Shipping
Packing - export box
Control type
N = 12 VDC, Powered Line-to-Neutral Sensing Control
Q = 24 VDC, Powered Line-to-Neutral Sensing Control
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
PRODUCT NUMBER MODEL NUMBER DESCRIPTION CONFIGURATION
A067K470 GT30040UN72 40A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A067K472 GT30040UN73 40A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A065W780 GT40040UN73 40A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A065W776 GT40040UN72 40A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A065Z132 GT30063UN72 63A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A012 GT30063UN73 63A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A016 GT40063UN72 63A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A017 GT40063UN73 63A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A018 GT30100UN72 100A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A067K473 GT30100UN73 100A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A026 GT40100UN72 100A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A043 GT40100UN73 100A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A045 GT30125UN72 125A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A067K475 GT30125UN73 125A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A324 GT40125UN72 125A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A067K476 GT40125UN72 125A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard+Option
A066A326 GT40125UN73 125A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A327 GT30160UN72 160A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A067K477 GT30160UN73 160A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A331 GT40160UN72 160A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A334 GT40160UN73 160A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A341 GT30250UN72 250A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A489 GT30250UN73 250A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A491 GT40250UN72 250A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A577 GT40250UN73 250A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A067K482 GT30350UN73 350A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A604 GT30350UN72 350A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A610 GT40350UN72 350A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A612 GT40350UN73 350A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A613 GT30400UN72 400A, 3P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A614 GT30400UN73 400A, 3P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A616 GT40400UN72 400A, 4P, 110-277Vac, 12Vdc, L-N, IP32 Standard
A066A624 GT40400UN73 400A, 4P, 110-277Vac, 12Vdc, L-N, IP54 Standard
A066A628 GT30500UQ72 500A, 3P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A631 GT30500UQ73 500A, 3P, 110-277Vac, 24Vdc, L-N, IP54, Standard
A066A632 GT40500UQ72 500A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A633 GT40500UQ73 500A, 4P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066A642 GT30630UQ72 630A, 3P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A646 GT30630UQ73 630A, 3P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066A756 GT40630UQ72 630A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A757 GT40630UQ73 630A, 4P, 110-277Vac, 24Vdc, L-N, IP54 Standard
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
PRODUCT NUMBER MODEL NUMBER DESCRIPTION CONFIGURATION
A066A758 GT30800UQ72 800A, 3P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A759 GT30800UQ73 800A, 3P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066A776 GT40800UQ72 800A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066A781 GT40800UQ73 800A, 4P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066C215 GT31000UQ73 1000A, 3P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066C039 GT31000UQ72 1000A, 3P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066C216 GT41000UQ72 1000A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066C555 GT41000UQ73 1000A, 4P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066C558 GT31250UQ72 1250A, 3P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066C559 GT31250UQ73 1250A, 3P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066C560 GT41250UQ72 1250A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard
A066C563 GT41250UQ72 1250A, 4P, 110-277Vac, 24Vdc, L-N, IP32 Standard+Option
A066C561 GT41250UQ73 1250A, 4P, 110-277Vac, 24Vdc, L-N, IP54 Standard
A066C580 GT31600YQ72 1600A, 3P, 220-240Vac, 24Vdc, L-N, IP32 Standard
A066C781 GT31600YQ73 1600A, 3P, 220-240Vac, 24Vdc, L-N, IP54 Standard
A066C595 GT41600YQ72 1600A, 4P, 220-240Vac, 24Vdc, L-N, IP32 Standard
A066C784 GT41600YQ73 1600A, 4P, 220-240Vac, 24Vdc, L-N, IP54 Standard
A066C593 GT32000YQ72 2000A, 3P, 220-240Vac, 24Vdc, L-N, IP32 Standard
A067K485 GT32000YQ73 2000A, 3P, 220-240Vac, 24Vdc, L-N, IP54 Standard
A066C596 GT42000YQ72 2000A, 4P, 220-240Vac, 24Vdc, L-N, IP32 Standard
A066C779 GT42000YQ73 2000A, 4P, 220-240Vac, 24Vdc, L-N, IP54 Standard
A067K088 GT40063UN73 Australia, 63A, 4P, 110-277Vac, 12Vdc, IP54 Australia
A067K090 GT40100UN73 Australia, 100A, 4P, 110-277Vac, 12Vdc, IP54 Australia
A067K092 GT40160UN73 Australia, 160A, 4P, 110-277Vac, 12Vdc, IP54 Australia
A067K091 GT40250UN73 Australia, 250A, 4P, 110-277Vac, 12Vdc, IP54 Australia
A067K103 GT40350UN73 Australia, 350A, 4P, 110-277Vac, 12Vdc, IP54 Australia
A067K098 GT40500UQ73 Australia, 500A, 4P, 110-277Vac, 24Vdc, IP54 Australia
A067K114 GT40630UQ73 Australia, 630A, 4P, 110-277Vac, 24Vdc, IP54 Australia
A067K116 GT40800UQ73 Australia, 800A, 4P, 110-277Vac, 24Vdc, IP54 Australia
A067K117 GT41000UQ73 Australia, 1000A, 4P, 110-277Vac, 24Vdc, IP54 Australia
A067K120 GT41250UQ73 Australia, 1250A, 4P, 110-277Vac, 24Vdc, IP54 Australia
A067K122 GT40125UN72 Brazil, 125A, 4P, 110-277Vac, 12Vdc, IP32 Brazil
A067K124 GT40250UN72 Brazil, 250A, 4P, 110-277Vac, 12Vdc, IP32 Brazil
A067K138 GT40500UN72 Brazil, 500A, 4P, 110-277Vac, 12Vdc, IP32 Brazil
A067K127 GT40500UQ72 Brazil, 500A, 4P, 110-277Vac, 24Vdc, IP32 Brazil
A067K149 GT40800UN72 Brazil, 800A, 4P, 110-277Vac, 12Vdc, IP32 Brazil
A067K147 GT40800UQ72 Brazil, 800A, 4P, 110-277Vac, 24Vdc, IP32 Brazil
A067K152 GT41250UQ72 Brazil, 1250A, 4P, 110-277Vac, 24Vdc,IP32 Brazil
POWERCOMMAND® GTEC TRANSFER SWITCH SPEC SHEET
CODES AND STANDARDS
Display controllers meet the following
Electromagnetic Compatibility (EMC) standards:
0-2000 A switches are third-party certified
4 EN 61000-6-2 Generic Immunity Standard
IEC as meeting IEC 60947-6-1 AC31A. EMC for the Industrial Environment.
EN 61000-6-4 Generic Emission Standard
for the Industrial Environment.
All switches bear the CE mark. All switches bear the EAC mark.
All switches are designed and manufactured
ISO® in facilities certified to ISO 9001: 2015
All switches bear the UKCA mark.
For more information, please contact your local Cummins distributor or visit cummins.com
Our energy working for you.™
All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc.
Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
Cummins Inc.
Box 3005
Columbus, IN 47202-3005
U.S.A.
1-800-CUMMINS™ (1-800-286-6467)
cummins.com
NAS-6542-EN PD00000511 Produced in U.S.A. Rev. 03/22