This document contains a duct pressure drop calculation form for a medical gas room and compressor room project. It includes tables with duct section details like flow rate, size, velocity, friction rate, and fitting quantities. Pressure drops are calculated for each section and totaled to determine the overall expected pressure drop of 1.01 inches of water column for the medical gas room system and 0.018 inches for the compressor room system. Notes provide additional information on how the calculations were performed.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
87 views

ESP

This document contains a duct pressure drop calculation form for a medical gas room and compressor room project. It includes tables with duct section details like flow rate, size, velocity, friction rate, and fitting quantities. Pressure drops are calculated for each section and totaled to determine the overall expected pressure drop of 1.01 inches of water column for the medical gas room system and 0.018 inches for the compressor room system. Notes provide additional information on how the calculations were performed.
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

DUCT PRESSURE DROP CALCULATION FORM

PROJECT SKCMS Design CFM 16482 Unit location Pent house


DESCRIPTION Medical Gas Room Design ESP 2.0" of WC Area Lower level

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)

DUCT DUCT PRESSUR DUCT TOTAL


SECTION NO. SCALED FITTING LOSS COEFFICIENTS QTY. OF FITTINGS
FLOW SIZE SIZE VELOCITY E DROP IN PRESSURE PRESSURE
FRICTION RATE VELOCITY LENGTH
S. No. RATE PRESSURE FITTINGS DROP DROP
(L)
ELBOW (8)×(9)x(10) (5)×(6)/100 (10)+(11)
W H TEE Plenum Collar ELBOW TEE Plenum Collar
FROM TO 90°
CFM Inch Inch Inch WC/100ft FPM Inch WC Inch WC Inch WC Inch WC Inch WC Inch WC
1 A B 3296 22 18 0.09 1199 10 0.09 0.21 0.3 1.43 0.1 0 2 0 0 0.054 0.009 0.062
2 B C 4944 26 22 0.07 1245 4 0.10 0.21 0.3 1.43 0.1 0 1 0 0 0.029 0.003 0.032
3 C D 8240 30 24 0.11 1648 8 0.17 0.21 0.3 1.43 0.1 0 2 0 0 0.102 0.009 0.110
4 D E 11536 36 30 0.08 1538 4 0.15 0.21 0.3 1.43 0.1 0 2 0 0 0.088 0.003 0.091
5 E F 16480 40 34 0.08 1745 272 0.19 0.21 0.3 1.43 0.1 3 3 0 0 0.290 0.226 0.516
0.21 0.3 1.43 0.1
0.21 0.3 1.43 0.1
12 SUB-TOTAL 0.56 0.25 0.81
HEPA FILTER 0
VCD 0.10
GRILL 0.10
Sound Attenuator
0.00
(Supply & Return)
TOTAL 1.01
S.F 15% 0.2
SUB-TOTAL 1.16

PREPARED CHECKED APPROVED

NOTE:
1. Elbow 90 degree Is from chart attached
2. Rest for all other fittings, Values ranges as per the ASHRAE design so for easier of Calculation the above values are considered.
3. Equivalent Rectangular lengths are considered where there was given round ducts
DUCT PRESSURE DROP CALCULATION FORM

PROJECT SKCMS Design CFM 24977 x 2 Unit location Pent house


DESCRIPTION Compressor Room Design ESP 2.0" of WC Area Lower level

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)

DUCT DUCT PRESSURE DUCT TOTAL


SECTION NO. SCALED FITTING LOSS COEFFICIENTS QTY. OF FITTINGS
FLOW SIZE SIZE VELOCITY DROP IN PRESSURE PRESSURE
FRICTION RATE VELOCITY LENGTH
S. No. RATE PRESSURE FITTINGS DROP DROP
(L)
ELBOW (8)×(9)x(10) (5)×(6)/100 (10)+(11)
W H TEE Plenum Collar ELBOW TEE Plenum Collar
FROM TO 90°
CFM Inch Inch Inch WC/100ft FPM ft Inch WC Inch WC Inch WC Inch WC Inch WC Inch WC
1 A B 2490 20 16 0.02 1121 9 0.08 0.21 0.3 1.43 0.1 1 0 0 0 0.016 0.002 0.018
2 B C 4980 26 22 0.08 1254 9 0.10 0.21 0.3 1.43 0.1 0 1 0 0 0.029 0.007 0.036
3 C D 7470 30 18 0.19 1992 17 0.25 0.21 0.3 1.43 0.1 0 1 0 0 0.074 0.032 0.106
4 D E 9960 34 28 0.08 1507 10 0.14 0.21 0.3 1.43 0.1 0 1 0 0 0.042 0.008 0.050
5 E F 24900 48 40 0.08 1868 24 0.22 0.21 0.3 1.43 0.1 0 4 0 0 0.261 0.018 0.279
6 F G 44820 54 44 0.14 2716 41 0.46 0.21 0.3 1.43 0.1 2 4 0 0 0.745 0.057 0.803
7 G H 49980 56 46 0.14 2794 185 0.49 0.21 0.3 1.43 0.1 2 1 0 0 0.350 0.261 0.611
12 SUB-TOTAL 1.52 0.38 1.90
HEPA FILTER 0
VCD 0.10
GRILL 0.10
Sound Attenuator
0.00
(Supply & Return)
TOTAL 2.10
S.F 15% 0.3
SUB-TOTAL 2.42

PREPARED CHECKED APPROVED

NOTE:
1. Elbow 90 degree Is from chart attached
2. Rest for all other fittings, Values ranges as per the ASHRAE design so for easier of Calculation the above values are considered.
3. Equivalent Rectangular lengths are considered where there was given round ducts
DUCT PRESSURE DROP CALCULATION FORM

PROJECT SKCMS Design CFM 5583 Unit location Pent house


DESCRIPTION Hot lab Design ESP 1.5" of WC Area Lower level

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12)

DUCT DUCT PRESSURE DUCT TOTAL


SECTION NO. SCALED FITTING LOSS COEFFICIENTS QTY. OF FITTINGS
FLOW SIZE SIZE VELOCITY DROP IN PRESSURE PRESSURE
FRICTION RATE VELOCITY LENGTH
S. No. RATE PRESSURE FITTINGS DROP DROP
(L)
ELBOW (8)×(9)x(10) (5)×(6)/100 (10)+(11)
W H TEE Plenum Collar ELBOW TEE Plenum Collar
FROM TO 90°
CFM Inch Inch Inch WC/100ft FPM ft Inch WC Inch WC Inch WC Inch WC Inch WC Inch WC
1 A 970 22 8 0.07 794 7 0.04 0.21 0.3 1.43 0.1 1 0 0 0 0.008 0.005 0.013
2 A B 2910 30 12 0.09 1164 82 0.08 0.21 0.3 1.43 0.1 0 2 0 0 0.051 0.071 0.121
3 B C 5820 32 22 0.06 1190 203 0.09 0.21 0.3 1.43 0.1 5 2 0 0 0.146 0.120 0.266
0.21 0.3 1.43 0.1
0.21 0.3 1.43 0.1
0.21 0.3 1.43 0.1
0.21 0.3 1.43 0.1
12 SUB-TOTAL 0.20 0.19 0.40
HEPA FILTER 0
VCD 0.10
GRILL 0.10
Sound Attenuator
0.00
(Supply & Return)
TOTAL 0.60
S.F 15% 0.1
SUB-TOTAL 0.69

PREPARED CHECKED APPROVED

NOTE:
1. Elbow 90 degree Is from chart attached
2. Rest for all other fittings, Values ranges as per the ASHRAE design so for easier of Calculation the above values are considered.
3. Equivalent Rectangular lengths are considered where there was given round ducts