SNA-360 analogue addressable smoke/heat detector
EN 54-5, EN 54-7, Smoke/heat detector for addressable 2-wire system applications
Description
SNA-360 analogue addressable photoelectric smoke/heat
detectors are microprocessor controlled state-of-the-art detectors
compatible with popular control and indicating equipment loop
protocols. Up to 125 detectors can be connected to each alarm
zone loop.
Advanced electronics in conjunction with a photoelectric smoke
sensing chamber and an electronic thermistor provide early
detection of fire and high immunity against unwanted alarms. The
heat sensor provides sensitive rate-of-rise operation or fixed-
temperature operation when the response threshold value is
exceeded.
The SNA-360 analogue addressable detector range provides fire
detection and alarm system designers with a premium smoke/heat
detector for life safety and property protection applications.
SNA-360 analogue addressable smoke/heat detector
Features
Dual photoelectric smoke and heat sensors to detect either
smoke, heat or a combination of the phenomena
Ideal for both fast-flaming and slow smouldering fires
Advanced algorithms provide analogue detection
discrimination Specifications
Surface-mount device (SMD) circuit board design
SNA-360-C2 SNA-360-CL
High immunity against unwanted alarms Operating voltage DC (17 ~ 28) V
Stable smoke sensing chamber. No adjustment or Start-up current ≤ 400 µA
replacement required
Start-up time ≤ 30 s
Durable heat sensor. No adjustment or replacement required
Quiescent current ≤ 260 µA
Sleek low-profile housing design
Sampling time ≤2s
Dual LEDs for 360° visibility
Alarm response threshold
DC 24 V operation (0.08 ~ 0.15) dB/m
(smoke)
Convenient 2-wire connection to many popular loop Alarm response threshold (heat) 59 °C static, and rate-of-rise a
protocols
Alarm current (max) 2 mA 5 mA
Easy installation with simple address setting DIP switches
Alarm indicator Dual red LEDs
Available with 125 usable detector address settings per loop
Remote LED output current (max) — 2 mA
when connected to Numens control and indicating equipment
Reset voltage ≤3V
Optional remote LED output
Reset time ≤ 30 s
Low maintenance
Usable addresses per alarm loop 125
Compliance Operating temperature (-10 ~ +55) °C
Operating humidity (0 ~ 95) % RH, non-condensing
SNA-360 smoke/heat detectors have the following compliance.
Storage temperature (-25 ~ +80) °C
EN 54-5a EN 54-7b CE
Storage humidity (0 ~ 98) % RH, non-condensing
SNA-360-C2
Dimensions (excluding contacts) Φ 102 mm × 45 mm
SNA-360-CL
Ingress protection rating IP-42
aEN 54-5 Fire detection and fire alarm systems. Heat detectors. Point detectors
a Detectorsare factory-configured for 30 K/min and comply with EN 54-5 class A1
bEN 54-7 Fire detection and fire alarm systems. Smoke detectors. Point detectors
and class A2.
using scattered light, transmitted light or ionization
Accessories Ordering Information
The following accessories are compatible with SNA-360 Remote Indicator a
smoke/heat detectors. SNA-360-C2 —
Description Part number Datasheet SNA-360-CL
a Requires 8-terminal base if remote indicator is installed.
4-terminal 102 mm low profile base CN302A 31-0036
8-terminal 102 mm low profile base CN304A 31-0038
Remote indicator a 681-001 31-0027
a Requires
View the complete range of products at
8-terminal base.
www.numens.com
1 31-0042-r03_2017-04
Numens
9 Xizhao Road, Innovative Industrial Area, Dong Qian Lake, Ningbo, Zhejiang, China 315121
© 2015 ~ 2017 Ambest Electronics (Ningbo) Co Ltd. All rights reserved. All specifications and other information shown were current at the date of