LRF-3 Transformer Comparision (SMS-1)

This document compares the technical offers from Raychem RPG and Transformer Rectifier (I) Ltd for a 4000 KVA, 11KV/109-197V oil filled ladle refining duty transformer. Both offers meet the specifications in IS 2026 and IS 12977. Raychem RPG's offer is for a 4000 KVA transformer, while Transformer Rectifier (I) Ltd's offer is for a 4 MVA transformer. Key differences between the offers include Transformer Rectifier (I) Ltd providing an on-load tap changer for voltage variation from 109V to 197V in 8 steps, along with more accessories and fittings listed in their technical specifications.

Uploaded by

SOUMEN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
204 views

LRF-3 Transformer Comparision (SMS-1)

This document compares the technical offers from Raychem RPG and Transformer Rectifier (I) Ltd for a 4000 KVA, 11KV/109-197V oil filled ladle refining duty transformer. Both offers meet the specifications in IS 2026 and IS 12977. Raychem RPG's offer is for a 4000 KVA transformer, while Transformer Rectifier (I) Ltd's offer is for a 4 MVA transformer. Key differences between the offers include Transformer Rectifier (I) Ltd providing an on-load tap changer for voltage variation from 109V to 197V in 8 steps, along with more accessories and fittings listed in their technical specifications.

Uploaded by

SOUMEN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

COMPARISION OF TECHNICAL OFFERS FOR LADLE FURNECE TRANSFORMERS AGAINST SPEC NO :

1223/RMLC/LRF-3/SMS-1/ELE-001(LRF-3, SMS-1, CHALIYAMA.


ITEMS RAYCHEM RPG TRANSFORMER RECTIFIER (I) LTD

4000 KVA, 11KV/ 109-197 V Oil Filled Ladle


4 MVA, 11 kV/109-184-197V, 3- PHASE LRF
Type of Transformer Refining Duty Transformer
TRANSFORMER

Service Indoor NOT FURNISHED


Quantity One No One No
Standard (Overaload shall be as per IS-
IS 2026, IS-12977 IS: 2026, IS:12977
12977, IS-2026)
Temparature rise over an ambient of 50°c
50°C 50°C
Oil by Thermometer
55°C 55°C
Winding by Resistance
Connection -HV Winding/LV Winding Delta / Open Delta D/III
4 MVA, 11 kV/109-
4000KVA 11/ 109-197 V
Rating 184-197 V
ON Load Tap Changer (Easun
Tapping Details ON LOAD TAP CHANGER (LV variation from 109V
MR)
to 197V in 8 steps)
Terminal Arrangement Bare Bushing
Bare Bushings on Cover
HV side (Bushing-Porcelain Type 36 KV,630A)
RISER ( 2 START + 2 FINISH / PHASE)
LV side BUSBAR RISER (2+2) / PHASE
Type of Cooling OFWF OFWF

4000KVA
4 MVA, 11 kV/109-184-197V, 3- PHASE LRF
Transformer Specification 3 Phase, 11KV/ 109-197 V
TRANSFORMER
HV:Ex Delta, LV: Open Delta

2 X 120%
Transformer is with 100% standby heat 1 WORKING + 1 STAND BY Double tybe type Heat
1 x 100% Run+ 1 x 100% Standby
exchanger double wall type exchangers
Make : Positron

Guaranteed Technical particulars (GTP)

1 Bare Bushing for HV & Bus Riser on Top for LV.


2 On Load Tap Changer Switch (Easun MR)
3 Conservator with oil level gauge and filling hole
with cap.
4 Under carriage with bidirectional flange rollers.
5 1 No filter, drain, sampling valve with plug.
6 02 Nos. Earthing terminals.
7 Air release device / Pressure Relief valve.
8 Rating and diagram plate.
9 Top filter valve
10 Haulage Lugs
11 Inspection Covers
12 Jacking Pads
13 Prismatic Oil Level Gauge
14 Lifting lugs for lid.
15 Silica gel breathers.
16 Thermometer pocket.
17 Oil Temperature Indicator with alarm & trip
contacts
List of Fittings and Accessories NOT FURNISHED
18 Winding Temperature Indicator with alarm &
trip contacts
19 Marshaling Box
20 Buchholz Relay with shut off valve.
21 Magnetic Oil Level Gauge with alarm & trip
contacts
22 Oil Flow indicator
23 Water Flow Indicator
24 Temperature Gauge
25 Pressure Gauge
26 Heat exchangers (1 running & 1 no. standby
with 120% coolers) Double
Tube Type (POSITRON MAKE)
27 Oil pump for oil circulation (one 100% running
and one 100% standby).
28 Oil Surge Relay for OLTC
29 R-C Network (C-R Surge suppressor)
30 Lightning Arrestor (LA)
31 Safety Ladder

Overall Dimension (L X W X H) mm Not Furnished Not Furnished


Approximate Weight
a)Core& Winding 8500Kg 7300Kg
b)Tank & Fitting 5500Kg 6800Kg
COMPARISIONb)Tank
OF TECHNICAL
& Fitting OFFERS FOR5500Kg
LADLE FURNECE TRANSFORMERS 6800Kg
AGAINST SPEC NO :
c)Oil 5000 Kg 6500Kg
d)Total Weight Total 19000 Kg Total 20600Kg
Loss Figures a)No Load Loss at rated voltage on
a)At no Load Principal tapping and at rated frequency No load loss: 4.5 KW ( Sub to IS Tolerance )
b)At Full Load 4.5KW @ 197 Volts Load loss:35.0 KW( Sub to IS Tolerance )
b)Load Loss at rated current at principal AUXILIARY LOSSES:2.0 KW (Sub to IS Tolerance)
tapping, at rated frequency at 75 °C 28KW @ Total loss:41.5KW (Sub to IS Tolerance)
197 Volts
Impedance Voltage @ principle tap 8 % @ 197 Volts 8% (Sub to IS tol @ 4 MVA,11/0.197 kV)
Core Material CRGO Material, M4 NOT FURNISHED
Efficiency @ 75 def
a) At 100% Load
b)At 75% Load NOT FURNISHED Not indicated
c) At 50% Load
d) At 25% Load
Flux Density 1.6 Tesla at rated voltage and frequency 1.7 TESLA @ Rated Voltage & Frequancy
3.5 A/sq mm at rated voltage and frequency 3.5 A/Sq. mm @ Max.LV Voltage Tap
Current Density

Insulation Level Separate source: HV-38KV rms, LV-8KV rms. HV-95/38 (kVp/KVrms) LV- / 8 (kVp/KVrms)

1. Tentative dimension and service type shall


1. List of fittings and accessories are not
have to furnish before placement of order.
indicated.
Service should be indoor type.
Observation 2.Efficiency figure not found.
2. Efficiency not found.
3.Check the voltage table which is not
3.Check the voltage table which is not matched
similar with our specification.
with our specification.