0% found this document useful (0 votes)
108 views8 pages

Cba 2000 en

The CBA 2000 is a circuit breaker analyzer and microohmmeter that can completely test high voltage circuit breakers. It has capabilities such as measuring contact resistance, timing circuit breaker operations, controlling trip and close coils, and analyzing circuit breaker motion. The CBA 2000 has a large display, internal memory, and software for analyzing test results and managing data. It provides safe and reliable testing of electric power equipment in substations.

Uploaded by

Abhishek Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
108 views8 pages

Cba 2000 en

The CBA 2000 is a circuit breaker analyzer and microohmmeter that can completely test high voltage circuit breakers. It has capabilities such as measuring contact resistance, timing circuit breaker operations, controlling trip and close coils, and analyzing circuit breaker motion. The CBA 2000 has a large display, internal memory, and software for analyzing test results and managing data. It provides safe and reliable testing of electric power equipment in substations.

Uploaded by

Abhishek Rajput
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

CBA 2000

High Voltage Circuit


Breaker Analyzer
and Microohmmeter
CBA 2000
2

HV Circuit Breaker Analyzer and Microohmmeter

• Built-in 200 A microhmmeter • Three phase first trip test

• Up to 18 main and 18 resistive contact inputs • Stand alone functionality - no PC connection is


required
• 12 auxiliary timing inputs
• Large graphical high brightness sunlight display
• Up to 4 trip/close coils control
• Analysis and result evaluation directly on the
• Motion and speed analyzer display

• Static and dynamic contact resistance • Internal memory for up to 500 test results and 64
measurement pre-defined test plans

• Digital transducer for motion analysis • Possibility to synchronize up to four CBA 2000

• Minimum trip coil test • TDMS - Test & Data Management Software

Application Characteristics
The CBA 2000 is a unique test set for the complete test of all Coil operation
circuit breakers. It is a powerful timing and motion analyzer
equipment with built-in 200 A pure DC microhmmeter for static . Number of circuits: 2 (1 Open and 1 Close coils); optional 4
and dynamic contact resistance tests. (3 Open and 1 Close coils)
The CBA2000 measures CB operation times according with . Type of driver: electronic; it ensures superior timing control
international standards: Open (O), Close (C), Open-Close (O-C), . Driver characteristic: 300 V DC max; 30 A DC max
Close-Open (C-O), Open-Close-Open (O-C-O) free open. It is also . Operating time accuracy: 0.025% of delay ± 50 µs
possible to set up customized operation sequences. In this way . Measurement of the coil current: one per channel;
is possible to get the circuit breaker spread. In the same time you the wave form is displayed on the dedicated channels
can measuring the coils currents. . Coil current ranges: 2.5; 10; 25 A full scale, user selectable
CBA 2000 is a stand alone unit with a large graphical display. The . The 4 coils option allows the selection of single or multiple
unit is supplied with TDMS analysis software. TDMS performs test phase opening
results analysis and creates test reports; it allows also to pre-define . Coil current measurement accuracy: 0.5% of the reading
test plans. TDMS is also a powerful Test and Data Management ± 0.1% of the selected range
software compatible with all ISA Test Sets. All CBA 2000 . Output are galvanically isolated betwen them
circuits have been designed to ensure safe and reliable
operations in the noisy environment of EHV and HV substations. Main contact inputs
. Number of contact inputs: 6 + 6 resistor contacts (2 breaks per
phase), divided in 3 groups of 2 each. In option: 12 or 18,
divided in 3 groups of 4 or 6 resistor and main contacts
. Resistor contact ranges: from 20 Ohm to 10 kOhm
. Contact test voltage: 24 V. Main contact test current: 50 mA
. Each input group is isolated with respect to the others

CBA2000 with tearproof connectors for 2, 4 or 6 breaks for phase


HV Circuit Breaker Analyzer and Microohmmeter
3

Event inputs Microhmmeter - static and dynamic


. Number of auxiliary event inputs: 4, divided in 2 groups of 2 each resistance measurement module
. Optionally: 8 or 12 divided in 4 or 6 groups of 2 each (option)
. Capability of testing dry or wet contacts: 24 V; 20 to 300 V.
. DC Test current: 200 A, 100 A, 25 A
Test current: 2 mA.
. Contact resistance range: 200 µOhm; 1.000 mOhm; 10.00
Sample rates mOhm;
100.0 mOhm; user selectable
20kHz - 10kHz - 5 kHz - 2kHz - 1kHz - 500Hz - 200Hz - 100Hz, 50 Hz
and 20 Hz user selectable. . Resolution: 1µOhm
. Resistance measurement accuracy (range 100 mOhm): ± 1%
Timing accuracy of the reading ± 0.2% of the range
50 µs ± 0.025% of the time reading at 20 kHz.
Minimum trip voltage test (Option)
Maximum record length
The minimum trip voltage test allows the user to verify the
1000 s.
minimum trip voltage threshold and the voltage drop off of a
trip coil
. Two options: 250 V - 4 A; 70 V - 10 A
. Maximum voltage adjustement: up to 50% of nominal DC
Voltage

Digital transducer
CBA 2000 can perform the motion analysis of the circuit
breaker using digital transducers
The characteristics are:
. Up to three digital transducer inputs
. Input type: RS 422 - Single ended for incremental encoders with
quadrature signal
Test result display . Max input frequency : 50 kHz
. Power supply: 5 V and 12 V supplied by the CBA2000.
Analog inputs Possibility to use an external power supply up to 24 V
. Number of analog inputs: 8 (10 Optional) . Connections: 3 multiple connectors on the CBA 2000 front panel
. 2 (4 optional) dedicated to Open and Close coil currents
. 1 dedicated to Dynamic and Static Resistance Measurement First trip test (with optional clamps)
. 3 for travel transducers or analog signals Besides the standard off-line timing mode, the CBA 2000 also
. Input voltage range: ± 10 V features an optional three-phase first trip test. In this mode,
. 2 general purpose analog input the CBA 2000 registers the breaker’s operation (open or close
. Input voltage range: ± 5 V; ± 50 V; ± 500 V user selectable time, open/close coil current and DC auxiliary voltage) while
. The analog inputs are isolated with respect to all other circuits the breaker is in service. Three AC current to voltage clamps
. Analog input measurement resolution: 16 bit record the secondary currents as the CB opens: the current
Programmable sequences waveform timing can be mesured on the waveforms. It is also
possible to record the open current profile with a DC clamp, and
The user can select the following Open and Close sequences: also to monitor the auxiliary contacts. The first time detection
Open; Close; Open-Close; Close-Open; Open-Close-Open. is important because, if the CB has been in service for a long
period in close position, the (first) trip time can be considerably
slow because of friction.
In the normal test conduction, the CB is opened before
connecting to the poles; so, the first movement friction is lost.

Test set control


The control is local, via graphical display, keypad and pushbutton
for menu selection: no PC control is necessary. It is available the
local interface in several languages: English, Spanish, French,
Italian, Turkish.

Display
Large graphical high brightness sunlight display (viewing area
122 x 92 mm). Test results are displayed graphically and in table
format. Zoom functions and cursors for test data analysis are
directly available on the CBA 2000 display.
Microhmmeter display
CBA 2000
4

Interfaces to PC
2 available interface: USB and RS232.

Flash drive interface


It allows to download test results and settings to a commercial
flash drive memory - USB 2.0 compliant.

Memory size
256 Mbytes: 500 results.

Mains supply
CBA 2000 can operate both from mains (AC or DC) and from Test result analysis
internal rechargeable battery: Optional accesories
. Mains supply: The following options are available upon request:
From 85 to 265 V AC; 50-60 Hz Test cable kit
From 100 to 350 V DC The connection cables set includes:
. Internal battery. Battery characteristics: Type: NiMh . Two cables with four conductors each for the connection to the
Circuit Breaker coils. Cable length: 10 m; section 1.5 mm2
Case . Three (6 or 9 in option) cables with silicon insulator each for the
Aluminium case, with hinged removable cover and handle. connection to the main contacts, each with three conductors
for tearproof connector interface on the CBA2000: Cable length:
Weight and dimensions 18 m, section 1 mm2
Weight: 13 kg basic unit; 15 kg with Microhmmeter module. . Two cables (4 or 6 in option) with silicon insulators for the
Dimensions: 485(W) x 365(D) x 240(H) mm. connection to the auxiliary inputs, with three conductors each.
Cable length: 6 m; section 1 mm2.
Accessories supplied with the unit . One shielded cable for the low voltage measurement, with two
The following accessories are always supplied with the unit: conductors. Cable lenght: 10 m; section 0.5 mm2
. Mains cable . One crocodile clips set (16 clips), with different colors, for
. Hardware and software user manuals the connection to the auxiliary contacts and to the 500 V input
. Serial cable measurement
. USB cable . One set of 12 cables, 2 m long, in different colors, for the
. Spare fuses connection to other inputs
. TDMS software . One set of 20 adaptors with banana on one side and terminator
on the other side, in different colors, for the connection to the
TDMS software event contacts and to the coil inputs
. Optional cables 18 m long or 38 m long
TDMS is a powerful software package providing data
. Three short cables to connect the coils mains
management for commissioning and maintenance testing
. One cable for the minimum trip voltage test option
activities. Circuit breaker data and test results are saved in TDMS . Three cables for the connection to the analog transducers
database for historical results analysis. . Three adaptors for the connection to the analog transducers
TDMS software has the following main features. . Three cables with 10 poles for the connection to the digital
. Full control of CBA 2000 functions from PC transducers
. Download of test Plans If microhmmeter option is included, the following cables are
. Download of test results supplied:
. Test plans and test results can be viewed, edited in . Two high current cables, with a conductor. Cable lenght: 10 m;
the missing descriptions, saved, printed, exported section 25 mm2
. Possibility of viewing and overlaying multiple . Transport plastic case, with handles IP65.. Dimensions: 45 x 55 x
results for easy test result comparison 22 cm.
. Possibility to pre-set test plans and to download
them into the test set
Additional 2 open driving coils module
. Two cursors select measurement points and intervals This module increases to 3 the number of Open Coils.
. Zoom in and out feature Microhmmeter - built-in 200 A static /
. Enhanced measurement features for movement - speed - dynamic resistance module
acceleration control With 10 m long test cables, cross section 25 mm2, terminated
ISA software updating policy allows all the users to update their with high current clamps.
software from ISA web site http://www.altanova-group.com/ at
Minimum trip voltage test
no additional cost. This option allows the user to verify the minimum trip voltage
threshold and the voltage drop off of a trip coil.
HV Circuit Breaker Analyzer and Microohmmeter
5

Internal thermal printer Adapter transducer mounting kit for


CBA 2000 can be supplied with a built-in thermal printer, 58 mm wide. analog and digital mounting kit.
External thermal printer Seiko DPV- 414.
Heavy duty transport case with wheels
Plastic soft bag
Digital transducer, model Hegstler RS - 58 - 0 / 5000
AS.41RB, supplied with connection cable 1 m long, terminated with
multiple connectors. Other models are available upon request.
Transducers
Linear transducer TLH 150 - 150 mm length (IP40)
Linear transducer LWG 150 - 150 mm length
Linear transducer TLH 225 - 225 mm length (IP40)
Linear transducer LWG 225 - 225 mm length Applicable standard
Linear transducer TLH 300 - 300 mm length (IP40) The test set conforms to the EEC directives regarding Electromagnetic
Linear transducer TLH 500 - 500 mm length (IP40) Compatibility and Low Voltage instruments.
Linear transducer LWG 500 - 500 mm length A) Electromagnetic Compatibility: Directive 2004/108/EC (CE
Linear transducer LWG750 - 750 mm lenght conform). Applicable standard: EN 61326:2006. IEC61000-6-5
B) Low Voltage: Directive 2006/95/EC (CE conform).
Rotary transducer IP 6501 - 355° rotation angle
. Applicable standards, for a class I instrument, pollution degree 2,
Pressure transducer PA-21 Y 40 BAR Installation category II: CEI EN 61010-1. In particular:
Universal Transducer mounting kit for TLH, . Inputs/outputs protection: IP 2X - CEI EN 60529
LWG and IP trav transducers . Operating temperature: -10°C to 55°C; storage: -20°C to 70°C
. Relative humidity: 5 - 95% without condensing
DC current clamp for coil or motor current measurement
AC current clamp three of them allow the three phase
first trip test

Ordering Information
CODE MODULE CODE MODULE
46169 CBA 2000 - BASIC UNIT 47266 CBA 2000 - BASIC UNIT with tearproof
2 breaks per phase - 4 auxiliary inputs - connectors
3 transducer inputs - TDMS software 4 breaks per phase - 8 auxiliary inputs -
47169 CBA 2000 - BASIC UNIT 3 transducer inputs - TDMS software
4 breaks per phase - 8 auxiliary inputs - 48266 CBA 2000 - BASIC UNIT with tearproof
3 transducer inputs - TDMS software connectors
48169 CBA 2000 - BASIC UNIT 6 breaks per phase - 12 auxiliary inputs -
6 breaks per phase - 12 auxiliary inputs - 3 transducer inputs - TDMS software
3 transducer inputs - TDMS software 15169 Test cables kit with case for CBA 2000 ( 2
15169 Test cables kit with case for CBA 2000 breaks per phase ) with tearproof connectors
( 2 breaks per phase ) 55169 Test cables kit with case for CBA 2000 (4
55169 Test cables kit with case for CBA 2000 breaks per phase ) with tearproof connectors
(4 breaks per phase ) 65169 Test cables kit with case for CBA 2000 (6
65169 Test cables kit with case for CBA 2000 breaks per phase ) with tearproof connectors
(6 breaks per phase ) 13169 Pressure transducer PA-21 Y 40 BAR
92169 Additional 2 Open Coils Module* 16166 Universal Analog Transducer mounting kit
90169 Additional 2 Breaks per phase expansion kit 17169 Universal Digital Transducer mounting kit
91169 Additional 4 Breaks per phase expansion kit 29166 DC Current Clamp
95169 Microhmmeter - 200 A Static / Dynamic 86169 AC current clamp 1 A / 0.1 V
Resistance Module (with test cables 10 m 44166 Flexible Coupling Shaft
terminated with clamps) * 13188 Adapter transducer mounting kit
93169 MTC - Minimum Trip Voltage test module *; ** 81169 Long connection cable for banana plugs (38 m)
94169 Internal Thermal Printer *; ** 45266 Long connection cable for tearproof connectors
14102 External Thermal Printer (38 m)
18169 Heavy Duty Plastic Transport Case Options with * must be specified at order.
19169 Soft carry bag Options with ** are exclusive each other: code 94169 Internal
46266 CBA 2000 - BASIC UNIT with tearproof thermal printer cannot be ordered together.
connectors
2 breaks per phase - 4 auxiliary inputs -
3 transducer inputs - TDMS software
CBA 2000
6

CBA 2000 - Heavy duty plastic transport case CBA 2000 - Soft bag

Transducer case Transducer mounting kit TLH linear transducer LWG linear transducer

Digital rotary transducer Analog rotary transducer Pressure transducer Current clamp
HV Circuit Breaker Analyzer and Microohmmeter
7

Test cable kit with transport case for CBA 2000 2 breaks for phase, microohmmeter and tearproof connectors for main contacts
www.altanova-group.com
DS CBA2000 EN - REV. 09/2021

TECHIMP - ALTANOVA GROUP ISA - ALTANOVA GROUP IntelliSAW - ALTANOVA GROUP


Via Toscana 11, Via Prati Bassi 22, 100 Burtt Rd
40069 Zola Predosa (Bo) - ITALY 21020 Taino (Va) - ITALY Andover, MA 01810 (USA)
Phone +39 051 199 86 050 Phone +39 0331 95 60 81 Phone +1 978-409-1534
Email [email protected] Email [email protected] Email [email protected]

The product and the information contained herein may be changed at any time without prior notification. This document nor any parts thereof may not be reproduced or transmitted in any form