0% found this document useful (0 votes)
68 views7 pages

Serial Device Server Rs 485 To Ethernet

The RS 485 To Ethernet gateway allows serial devices to connect to Ethernet networks. It has one serial port and one Ethernet port, supports TCP/IP, and can centrally manage scattered serial devices via the network. The gateway has a wall mounting design, supports wide temperature operation, and can be configured via a Windows-based management tool or web interface to network serial devices simply.

Uploaded by

Deni Denden
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views7 pages

Serial Device Server Rs 485 To Ethernet

The RS 485 To Ethernet gateway allows serial devices to connect to Ethernet networks. It has one serial port and one Ethernet port, supports TCP/IP, and can centrally manage scattered serial devices via the network. The gateway has a wall mounting design, supports wide temperature operation, and can be configured via a Windows-based management tool or web interface to network serial devices simply.

Uploaded by

Deni Denden
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

User Manual for RS 485 To Standard TCP/IP OR MODBUS

Gateway

RS 485 To Ethernet

Wall Mounting
RS-485 Serial Device Server
• Support 1 serial port to 1 10/100 Base-T(X) self-adaptive Ethernet interface.
• Support TCP Client.
• Support 5VDC only.
• Support -40~75℃ wide temperature operation

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 1
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
RS 485 To Ethernet is the serial device server that can make serial device be
equipped with networking capability instantly and centrally manage the scattered
serial devices and hosts via network. The product supports RS-485 to 1-100M
Ethernet port. It adopts wall mounting to meet the requirements of different
application scenes.

Serial device server supports network TCP protocol. It also possesses complete
management functions, including Access Control, Rapid Configuration and so on.
Furthermore, supplied management configuration tool based on Windows
platform can guide the user to manage and configure the device, achieving
immediate networking of serial device via simple settings. It can provide users
with good experience with friendly design of network management system
interface, simple and convenient operation.

Hardware adopts fanless, low power consumption, wide temperature and voltage
design and has passed rigorous industrial standard tests, which can suit for the
industrial scene environment with harsh requirements for EMC. It can be widely
used in PLC control and management, Building Automation System, Health Care
Automation System, measuring instrument and environmental forces monitoring
system.

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 2
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
Features:

 Adopts 32 bits ARM processor.


 Support 10/100Base-T(X) self-adaptive Ethernet interface.
 Support 1200 bps – 115200 bps line speed and non-blocking
communication.Support low power consumption mode and high
performance mode.
 Support, TCP Client.
 Support AT command, Via TCP/IP to remotely Configure the Serial port
settings.
 Support across gateway and routing communication.
 Flexible serial port data framing setting, which can satisfy user’s various
demands for data packets segmentation.
 Support standard TCP/IP SOCKET application access the serial device
simultaneously.
 Support configuration tool, WEB ,Ethernet and other configuration forms.

Mechanical Dimensions:
Measurements in mm

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 3
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
Specifications:

Standard: 10Base-T, 100Base-TX


Protocol: TCP, UDP, ARP, HTTP, ICMP,
DHCP, DNS
Rate: 10/100M automatic flow control,
MDI/MDI-X auto tunning
ETHERNET Interface quantity: 1
Interface form: RJ45
Duplex mode: full/half duplex mode self-
adaption
Operating mode: support TCP Client.

Standard: RS-485
Quantity of serial port: 1 RS-485
Serial port RS-485 signal: D+, D-, GND

Baud rate: 1200-115200bps Data bit: 5bit,


6bit, 7bit, 8bit
Parity bit: None, Even, Odd.
Stop bit: 1bit, 2bit
Interface form: RS-232, adopt DB9 male;
Serial Port RS-485/422, adopt 5 pins 5.08mm pitch
terminal blocks
Directional control:
RS-485 direction adopts data, flow
automatic
control.
Load capacity: RS-485/422 end supports
32 points polling (customizable 128
points)
Pull high/low resistor for RS-485:
4.7kΩ(optional).

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 4
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
WEB configuration management,Ethernet
Configuration
(AT Command) for UART.

Power supply indicator, Ethernet port


Indicator
indicator, serial port indicator

Power 5 VDC only


Requirement
No-load: 0.80W@5VDC Full-load:
Power
0.84W@5VDC
Consumption

Physical Operating temperature range: -40~75℃


Characteristics Storage temperature range: -40~85℃
Relative humidity: 5%~95%(no condensation)

Warranty

485 baud rate configuration using Ethernet port(TCP/IP)

Example:

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 5
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
Configuration on Web Server:

Factory Default Setting:

Please type the below IP Address to access the configuration utility on your web browser:

192.168.127.254:4001 (Default)

IP ADDRESS:PORT NUMBER <CR>

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 6
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com
NOTE : If User has changed the IP address and port number using web configuration page. It will be
stored in permanent(Non-Volatile) internal memory of device.

So for next time if user wants to open the configuration page, user has to enter last saved IP address and
port number.

If user has forgotten the ip address and port number, then user can reset the internal memory to default
value by below method.

STEP1: Power off the device

Step2:Press and hold the default push switch and power on the device .

Step 3: RX/TX and ACT led will start blinking simultaneuosly.

Step4: Release the default push switch.

Step 5: RX/TX and ACT led will Stop blinking .

Step6: Now the default Setting of the device is restored:

Default Setting of the device:

IP ADDRES:192.168.127.254

Baudrate: 9600

Data bits:8.

Parity: None

Add: 2
nd
Floor, Span House, Opp. Arogya Diagnostic Clinic, Near Moze College, Balewadi, Pune-411045 7
Tel:09665703661/2/3, Mob:919881196976; @:[email protected]
Web:www.rubixtechno.com