Levelcontrol Basic 2
Levelcontrol Basic 2
LevelControl Basic 2
Signalling Module
Current Measuring Module
Supplementary Operating
Manual
All rights reserved. The contents provided herein must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor otherwise transmitted, published or made available to a
third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
Contents
1 General.................................................................................................................................................... 4
2 Safety ...................................................................................................................................................... 5
2.1 General.............................................................................................................................................................. 5
3 Transport/Temporary Storage/Disposal............................................................................................... 6
3.1 Condition upon delivery .................................................................................................................................. 6
3.2 Transport........................................................................................................................................................... 6
3.3 Storage .............................................................................................................................................................. 6
4 Description ............................................................................................................................................. 7
4.1 Compatibility .................................................................................................................................................... 7
4.2 General description .......................................................................................................................................... 7
4.3 Technical data................................................................................................................................................... 9
5 Installation at Site ................................................................................................................................ 11
5.1 Connecting the signalling module ................................................................................................................ 11
5.2 Connecting the current measuring module.................................................................................................. 13
6 Commissioning/Start-up/Shutdown................................................................................................... 15
6.1 Commissioning/start-up ................................................................................................................................. 15
6.2 Shutdown........................................................................................................................................................ 15
7 Operation.............................................................................................................................................. 17
7.1 Extensions with signalling/current measuring module ................................................................................ 17
7.1.1 Menu extension ................................................................................................................................. 17
7.1.2 Additional functions .......................................................................................................................... 17
8 Servicing/Maintenance ........................................................................................................................ 28
8.1 Maintenance/inspection measures ................................................................................................................ 28
9 Trouble-shooting.................................................................................................................................. 29
10 Related Documents .............................................................................................................................. 30
10.1 Wiring diagram/terminal diagram ................................................................................................................ 30
10.1.1 Individual signals - control board display (example) ....................................................................... 30
10.1.2 Analog output.................................................................................................................................... 30
10.1.3 Three-phase current measurement................................................................................................... 31
10.1.4 Single-phase current measurement .................................................................................................. 32
10.1.5 Field bus connection .......................................................................................................................... 32
10.1.6 Redundant pneumatic level measurement ...................................................................................... 33
10.1.7 Partially redundant bubbler system.................................................................................................. 35
Index ..................................................................................................................................................... 37
LevelControl Basic 2 3 of 40
1 General
This supplementary operating manual accompanies the installation/operating
manual. All information contained in the installation/operating manual must be
observed.
4 of 40 LevelControl Basic 2
2 Safety
2.1 General
This supplementary operating manual contains additional applicable information.
General installation, operating and maintenance instructions that must be observed
to ensure safe operation and prevent personal injury and damage to property are
given in the installation/operating manual.
The safety information in all sections of this supplementary operating manual and in
the relevant installation/operating manual must be complied with.
The supplementary operating manual must be read and completely understood by
the responsible specialist personnel/operators.
The contents of this supplementary operating manual must be available to the
specialist personnel at the site at all times.
The operator is responsible for ensuring compliance with all local regulations which
are not taken into account in this supplementary operating manual.
LevelControl Basic 2 5 of 40
3 Transport/Temporary Storage/Disposal
NOTE
Prior to shipping, the accessories were tested to ensure full compliance with the
specifications. They should, therefore, be in perfect electrical and mechanical
condition upon arrival.
It is recommended that the accessories be inspected for in-transit damage
immediately upon receipt. If there are any complaints or objections, the recipient
and carrier must jointly draw up a damage report.
3.2 Transport
CAUTION
Improper transport
Damage to the accessories!
▷ Always transport the accessories properly and in their original packaging.
▷ During transport, observe the transport instructions on the original packaging.
3.3 Storage
If the ambient conditions for storage are met, the accessories will give reliable service
even after a prolonged period of storage.
6 of 40 LevelControl Basic 2
4 Description
4.1 Compatibility
NOTE
The KSB Service Tool can be downloaded free-of-charge from the KSB web site. The
web site also contains further information on how to order the additional
parameterisation cable required.
Signalling module and current measuring module can be used with device firmware
version 1.2 or higher. Devices with earlier firmware versions must be updated using
the KSB Service Tool.
Signalling module
The signalling module is an extension module for LevelControl Basic 2.
It features:
▪ Six volt-free signals:
– Fault at pump 1
– Fault at pump 2
– High water
– Sensor fault
– Pump 1 in operation (not available for lifting units with single-phase motor
and cutter)
– Pump 2 in operation (not available for lifting units with single-phase motor
and cutter)
▪ Analog output (level-proportional current signal, type 4–20 mA)
▪ ModBus RTU interface (direct connection or field bus module connection)
▪ System bus interface (currently no function)
▪ Connection option for one current measuring module per pump
▪ Depending on the version, the device is fitted with a pressure sensor for
redundant pneumatic level measurement (without compressor) or for setting up
a partially redundant bubbler system
NOTE
The assignment of the volt-free signals and the measured values provided via the
analog output can be modified using the ServiceTool.
LevelControl Basic 2 7 of 40
8 of 40 LevelControl Basic 2
NOTE
The current measuring module measures the currents in phases L2 and L3 (three-
phase motor) or L (single-phase motor) of the connected pumps.
(ð Section 10.1, Page 30)
Signalling module
LevelControl Basic 2 9 of 40
Characteristic Value
Design variants Signalling module
Signalling module with pressure sensor,
3 mlc
Signalling module with pressure sensor,
10 mlc
Weight 0.3 kg
NOTE
The signalling module can be used with device firmware version 1.2 or higher.
NOTE
LevelControl Basic 2 is only fitted with current measuring module(s) ex works.
Current measuring modules cannot be retrofitted!
The current measuring modules are connected to LevelControl Basic 2 via the
signalling module.
This means that the current measuring module can be used only in combination with
the signalling module!
NOTE
The current measuring module can be used with device firmware version 1.2 or
higher.
NOTE
One current measuring module is required for each pump. For dual-pump control,
the signalling module offers connection options for two current measuring
modules.
10 of 40 LevelControl Basic 2
5 Installation at Site
DANGER
Exposed live parts
Danger of death from electric shock!
▷ Separate the control unit from the power supply before installing the signalling
module.
CAUTION
Improper handling of the control unit and its built-in components
Defective control unit!
▷ Handle the control unit and its built-in components carefully.
CAUTION
Incorrect handling of the rechargeable battery
Electrical damage to the control unit!
▷ If the battery installation option is used, disconnect one of the battery's
connectors before connecting the signalling module. This ensures that the
control unit is completely de-energised.
▷ Do not re-connect the battery connector until the connection has been made.
BC version
LevelControl Basic 2 11 of 40
(The connector has a pin that has to engage in the hole in the PCB next to the
PCB-side connector.)
5. Snap the signalling module for the BC version onto the spacers and check that it
is firmly seated.
6. Close the control unit again properly.
7. Reconnect the power supply.
When the device is switched on, the green status LED on the signalling module lights
up continuously. This means that the signalling module is functioning correctly.
If the green status LED on the signalling module does not illuminate, the correct
seating of the cable connecting the signalling module and the LevelControl Basic 2
PCB must be checked again.
If the green status LED on the signalling module flashes, the signalling module has
not been detected by LevelControl Basic 2. In this case, check the firmware version of
the control unit, which is displayed at parameter 4-1-1. Firmware version 1.2 or
higher is required.
NOTE
To set up a redundant pneumatic level measurement system, observe
(ð Section 10.1.6, Page 33) .
To set up a partially redundant bubbler system, observe
(ð Section 10.1.7, Page 35) .
12 of 40 LevelControl Basic 2
BS version
NOTE
To set up a redundant pneumatic level measurement system, observe
(ð Section 10.1.6, Page 33) .
To set up a partially redundant bubbler system, observe
(ð Section 10.1.7, Page 35) .
NOTE
LevelControl Basic 2 is only fitted with current measuring module(s) ex works.
Current measuring modules cannot be retrofitted!
LevelControl Basic 2 13 of 40
Connect the current measuring module in accordance with the wiring diagram.
(ð Section 10.1.3, Page 31) / (ð Section 10.1.4, Page 32)
14 of 40 LevelControl Basic 2
6 Commissioning/Start-up/Shutdown
6.1 Commissioning/start-up
ü The supplementary operating manual and the installation/operating manual
have been read.
ü The device variant conforms to the requirements.
ü The control unit has been assembled as per operating instructions and connected
to the power supply in accordance with the wiring diagram.
ü The signalling module has been installed as per operating instructions
(ð Section 5.1, Page 11) and connected in accordance with the terminal diagram.
ü The current measuring module has been installed as per operating instructions
and connected in accordance with the terminal diagram.
1. Re-tighten the connection terminals (individual signals, analog output, field bus
connection and current measuring modules).
2. Connect the power cable.
3. Connect the sensors.
4. Insert the motor protection device and fuses.
5. Set the manual-0-automatic switches for both pumps to "0".
6. Switch on the power supply.
7. Check that the green status LED is continuously ON.
8. Check that the parameters are set as required and adapt if necessary.
9. Carry out test run for several start/stop cycles.
10. Check alarm devices, including the individual signals, for proper function.
11. Set the manual-0-automatic switches for both pumps to "Automatic".
ð Both pumps can now be started/stopped by the control unit as required.
12. Provide support and/or training for operating personnel.
13. File a copy of the supplementary operating manual with the installation/
operating manual.
6.2 Shutdown
Short-term shutdown
1. Set the manual-0-automatic switches for both pumps to "0".
ð Both pumps are switched off.
ð The control unit remains operational.
Long-term shutdown
1. Set the manual-0-automatic switches for both pumps to "0".
2. Switch off the power supply.
LevelControl Basic 2 15 of 40
16 of 40 LevelControl Basic 2
7 Operation
NOTE
Additional parameters available are documented on the enclosed parameter label.
If signalling module and, where applicable, current measuring module are installed,
additional parameters appear in the display. These can be selected as usual using the
arrow keys.
The selectable parameters depend on the operating mode and measurement
method. Only parameters that are relevant to the current operating mode and
measurement method are displayed.
LevelControl Basic 2 17 of 40
The signal relays are energised in the good or idle state and de-energise in the event
of a signal.
NOTE
In the case of lifting units with single-phase motor and cutter, signal relays 5 and 6
are used to control the start capacitors required for operation and are not available
for volt-free signals.
NOTE
For single-pump systems, the signal relays normally assigned with signals for pump
2 do not carry any standard settings. These can be assigned using the ServiceTool.
The signal relays can be assigned with the following functions using the ServiceTool:
18 of 40 LevelControl Basic 2
NOTE
For current measurement > 10 (15) A, please note the following transformer
factors:
10–20 (40) A: 4 mA ➔ 0 A, 20 mA ➔ 40 A
20–40 (60) A: 4 mA ➔ 0 A, 20 mA ➔ 60 A
40–75 (110) A: 4 mA ➔ 0 A, 20 mA ➔110 A
LevelControl Basic 2 19 of 40
Table 12: Allocation of switching states for level measurement with float switches or digital sensors
Display Level Analog signal Switching state
When draining When filling
Sensor fault 0 mA - -
Medium 10 mA - -
20 of 40 LevelControl Basic 2
NOTE
If sensor fault and high water are present at the same time, the high water level is
output in accordance with the priority of the pending faults.
LevelControl Basic 2 21 of 40
If a control unit with pressure sensor for up to 3 metres of water is used, the fill level
in the range of 0–4 mlc is converted into a signal of 4 to 20 mA.
22 of 40 LevelControl Basic 2
NOTE
To set up a redundant pneumatic level measurement system or a partially
redundant bubbler system, a signalling module with pressure sensor is required.
NOTE
Redundant arrangement of the sensors enables redundant minimum level
monitoring as stipulated by the Atex directives.
NOTE
If the power supply fails and the unit is operated on battery power, level
measurement will be non-redundant. The redundant pressure sensor is deactivated
during battery operation.
NOTE
To set up a redundant pneumatic level measurement system or a redundant
bubbler system, observe the wiring diagram/terminal diagram.
(ð Section 10.1, Page 30)
The signalling module provides the option of setting up a redundant pneumatic level
measurement system or partially redundant bubbler system.
If a redundant level measurement system is used, the mean value of the two
measured values is used for level measurement and pump control.
In the event of a fault in one of the two level measurement systems,
▪ for non-Atex applications (3-6-1 Atex-Mode = "0", deactivated), the higher of the
measured values is used for controlling the pumps
▪ for Atex applications (3-6-1 Atex-Mode = "1", activated), the higher of the
measured values is used as long as at least one of the two level measurement
systems ensures sufficient submergence of the pump.
If a pump that represents a potential ignition source in a potentially explosive
atmosphere can no longer be guaranteed to be sufficiently submerged, all running
pumps will be stopped.
In the event of a fault, message "A11 – Sensor fault" is output.
LevelControl Basic 2 23 of 40
24 of 40 LevelControl Basic 2
LevelControl Basic 2 25 of 40
7.1.2.3.3 Functions
Various device functions of LevelControl Basic 2 can be executed via field bus. They
can be accessed using function code 05 (Write Single Coil). Function code, coil and
value are shown as hexadecimals and can be transferred directly to the Modbus-RTU
protocol in this format.
7.1.2.3.4 Termination
NOTE
The terminating resistors for ModBus RTU and field bus connection are set at the
factory. If the signalling module is not the end device, remove the terminating
resistors.
If LevelControl Basic 2 is operated as the end device in the field bus system or if a
point-to-point connection with a field bus gateway is made, the terminating resistors
must be set on the PCB in order to guarantee correct operation. This can be achieved
easily via DIL switch S1.
26 of 40 LevelControl Basic 2
LevelControl Basic 2 27 of 40
8 Servicing/Maintenance
28 of 40 LevelControl Basic 2
9 Trouble-shooting
Table 20: Trouble-shooting
Faults Causes Remedy
Control unit showing fault A fault has occurred at the signalling ▪ Check signalling module connection
-A17- module ▪ Switch power supply off and then
back on again
▪ Replace signalling module
Green status LED on signalling Signalling module is not correctly ▪ Check signalling module connection
module not lit connected to the PCB or is defective ▪ Replace signalling module
Green status LED on signalling Signalling module not detected ▪ Check firmware version of the
module flashes control unit and update if necessary
Individual signals are not output Setting and/or connection fault ▪ Check control unit setting
as required ▪ Check signalling module terminal
connection
Analog output delivering a Setting and/or connection fault ▪ Check control unit setting
faulty signal ▪ Check signalling module terminal
connection
Analog output delivering no Setting and/or connection fault ▪ Check control unit setting
signal Level measurement faulty (message ▪ Check signalling module terminal
-A11-) connection
▪ Check level measurement
Faulty behaviour during Setting and/or connection fault ▪ Check control unit setting
pneumatic measurement or Tubing is leaking ▪ Check tubing connections
bubbler control
▪ Check tubing for leakage
Parameters 1-2-3, Current Signalling or current measuring module ▪ Check connections of signalling and
Pump 1, and/or 1-3-3, Current connection fault current measuring module
Pump 2, are not shown or are Current measuring module connections
shown interchanged in the to signalling module interchanged
display
Communication via ModBus RTU Connection fault ▪ Check connection
faulty Communication fault ▪ Check settings
Communication interrupted
▪ Switch power supply off and then
back on again
▪ Reset control unit
Communication with field bus Connection fault ▪ Check connection
system faulty Communication fault ▪ Check settings
Communication interrupted
▪ Switch power supply off and then
back on again
▪ Reset control unit
Incorrect parameter settings Undocumented parameters can also be ▪ Restore parameter settings
after field bus access changed via field bus ▪ Check script for field bus access and
correct
LevelControl Basic 2 29 of 40
10 Related Documents
NOTE
The assignment of the signal relays can be altered using the service tool.
NOTE
The analog output provides a level-proportional 4–20 mA signal. The assignment
can be altered using the service tool.
30 of 40 LevelControl Basic 2
LevelControl Basic 2 31 of 40
32 of 40 LevelControl Basic 2
NOTE
The use of a redundant pneumatic system (without compressor) offers redundant
level measurement and also, when ATEX mode is activated, redundant minimum
level monitoring.
LevelControl Basic 2 33 of 40
Table 21: Parameter
Parameter Designation
3-4-4-1 Level of bell 1
3-4-5-1 Level of bell 2
NOTE
To relieve the strain on the plug-type connectors in the control unit, run the tubes
of both closed or open measuring bells through cable glands and tighten firmly.
NOTE
To ensure the control unit is functioning correctly, the air supply tubes of both
closed or open measuring bells must be routed with a continuously falling slope to
prevent the formation of water pockets as a result of condensation. Tubes which
are too long must be cut to length during installation.
34 of 40 LevelControl Basic 2
NOTE
If the compressor fails due to a fault, both level measurement systems continue to
operate as redundant pneumatic level measurement systems (without compressor).
LevelControl Basic 2 35 of 40
Table 22: Parameter
Parameter Designation
3-4-4-1 Level of bell 1
3-4-5-1 Level of bell 2
NOTE
To relieve the strain on the plug-type connectors in the control unit, run the tubes
of both closed or open measuring bells through cable glands and tighten firmly.
NOTE
To ensure the control unit is functioning correctly, the air supply tubes of both
closed or open measuring bells must be routed with a continuously falling slope to
prevent the formation of water pockets as a result of condensation. Tubes which
are too long must be cut to length during installation.
36 of 40 LevelControl Basic 2
Index
A
Analog output 19
C
Commissioning/start-up 15
F
Faults 29
Field bus connection 24
I
Individual signals 9
Inspection 28
Installation 11
M
Maintenance 28
Measured values menu 17
Menu extension 17
ModBus 24
R
Redundant level measurement 23, 33
S
Settings menu 17
Shutdown 15
Storage 6
T
Transport 6
LevelControl Basic 2 37 of 40