K68i / K68 Relay Tester Instruction Manual
K68i / K68 Relay Tester Instruction Manual
Instruction Manual
Version: 1.3
e . c o m . c n
@k ing s i n
ro ge r
e . c o m . c n
@k ing s i n
ro ge r
Note:
This manual is applicable for KINGSINE K68i and K68 Relay Tester but it is compiled to use K68i
as example. The corresponding updated software and functions instruction will be released on our
website (www.kingsine.com.cn), when updating the software and increasing the contents. In order
to obtain the latest and first-hand information, please pay more attention to the latest news on our
website. The functions and pictures mentioned in this manual will be as reference only and the
released real product is the sole standard.
1
Catalogue
c n
3.5 Distance/ Zero-sequence Relays Testing .............................................................................26
n e . c o m .
3.6 Harmonic Output Testing.....................................................................................................37
i
k ing s
3.7 Frequency Protections Testing .............................................................................................41
r @
ro ge
3.8 Aux DC ................................................................................................................................48
Chapter 4 System Calibration, Settings & Update.............................................................................49
4.1 System Calibration...............................................................................................................49
4.2 IP Setting..............................................................................................................................55
4.3 Software Upgrade and Report Upload .................................................................................57
-2-
K68 Series Protection Relay Test Set
Chapter 1 Overview
K68 Series Relay Tester is new All-in-One protections testing systems developed
independently by KINGSINE on the basis of Windows CE system, which adopts the
embedded system, the latest high-speed DSP processor and ultra-large-scale field
programmable logic devices FPGA.
It have high-precision signal and high-efficiency and high-stability power amplifier with
the advanced level in the world by the developed digital phrase lock patented algorithm and
SPWM technology based on the advanced SOC design concept, to provide customers with
comprehensive and easy-to-use testing solutions with complete functions.
It is widely applied to power industry, metallurgy industry, petrochemical industry, railway
and scientific research institution as well as industrial and mining enterprises and power
equipment factories that on a large scale.
e . c o m . c n
Characteristics:
@k ing s i n
ro ge r
1. High power: 3 x 0…35A with a power of 450VA for Medium/Low Voltage test.
2. Phase, frequency and amplitude are independently and continuously adjustable.
3. The maximum output of DC voltage for every phase:300V
4. High Precision: 0.14% reading+0.06% range guaranteed at 0-35A & 0.14% reading+0.06%
range guaranteed at 0-300V.
5. Auto/Manual Test on all its five modules: DC Test, AC Test, Distance Test, Harmonic Test,
Frequency protection.
6. 3-Years Warranty for free repair.
7. Reliability: Self-protection by stop output plus with light flashing/sound alarming in case
of wrong-wiring, open/short-circuit, overheat & overload.
8. On-site Testing Convenience: the equipment can be put vertically or horizontally when
on-site testing.
9. The tester could upgrade by USB and can make speed data communication between
computer On 100M-T Network-card.
10. Internal design is of architectural style framework and of shock & impact resistance
external box made of high intensity aluminum alloy enables the equipment subject to rigid
vibration.
3
K68 Series Protection Relay Test Set
Model
K68 K68i
Factor
AC Current I 3*35A 3*35A
AC Voltage U 4*130V 4*300V
DC Current I 3*20A 3*20A
DC Voltage U 1*150V 1*150V
DC Voltage Ubc 1*300V 1*300V
Aux. DC
0~300V 0~300V
(DC Module Setting)
Aux. DC
0~260V 0~300V
(Interface Setting)
Binary Input 8 pairs ● ●
Binary Output 4 pairs ● ●
e . c o m . c n
1.2 Technical Parameters
@k ing s i n
ro ge r
Voltage generators (overload and short protection)
Setting 4-phase AC (L-N) 4x 0 ... 300 V
Range 2-phase AC (L-L) 2 x 0 ...600 V
Resolution 1mV
4
K68 Series Protection Relay Test Set
Rise/down time <50µs
Resolution 1mA
Generators, general
Voltage and Current Synchronism ≤10μS
Resolution 0.001Hz
Resolution 0.01°
e . c o m . c n
0 ... 300V/180VA
Current ranges
ro ge r
<0.14% reading + 0.06% range guaranteed at 0…20A;
Accuracy
<0.05% reading + 0.02% range typical at 0…20A;
Resolution 1mA; 1 mV
Aux DC supply
Ranges 0~300V/0.5A
Accuracy Error<0.5%
Binary inputs
Number 8 pairs (extendible to 64channel)
Resolution 0.1ms
Binary outputs
Number 4 Pairs
Ranges DC-250V/3,AC-250V/3A
Power supply
Nominal input voltage 220V±10% VAC, 1-phase
Power 1000VA/Max.15A
5
K68 Series Protection Relay Test Set
Nominal frequency 50/60±10% Hz
Environmental conditions
Working temperature -5°C... 55 °C
Weight 24KG
e . c o m . c n
@k ing s i n
ro ge r
6
K68 Series Protection Relay Test Set
Current generator and voltage generator have no current booster and no voltage booster, but direct
coupling mode is adopted by them, which enables the power supply’s frequency output range to be
from 0Hz to 1000Hz, outputting DC and all AC voltage or AC current in all frequency. Such as
square waveform, varying waveform in proportion with the exponential function as well as mixed
Reclosing waveform. Basically it meets the transient testing requirements of the protection device,
thereby achieving the simple simulating test on various protection devices.
Power amplifier circuit has the perfect protective function against over-current, over-voltage and
over-temperature so that keep the high-power components of the set from damage in the test. When
the power amplifier is charged, the internal circuits of protection relay will real-time monitor/detect
the output current value from the voltage circuit and determine whether the detected current values
are overload. When there is overload or short-circuit in the circuit voltage, the power of the power
amplifier will shut down automatically and the test will stop, giving out the warning signal.
. c n
1.4 Package list
s i n e . c o m
k ing
Relay-Tester mainframe 1set
ro ge r @ Operation software
Twisted-pair
Special testing cables
1set
2pc
1kit
Power cord 1pc
Instruction Manual 2pcs
Aluminum alloy packaging box 1pc
The Host will have free maintenance for three years. While the 3-year guarantee for free repair shall
be subject to the condition that the ‘products’ shall not be modified or improperly used within three
years after being sold. In order to improve continually on the reliability and performances of the
hardware and software of the test device, welcome all customers to bring forward valuable
comments and suggestions on this product. We will be happy to work with you and explore and
strive to meet your requirements.
7
K68 Series Protection Relay Test Set
1.6 Attention:
z There are good Grounding picture in the right bottom of each interface menu.
n
affecting the testing results.
z
e . c o m . c
In case that there is overload or short-circuit in the voltage generator, the Relay Tester will
i n
k ing s
automatically shut down the power of the amplifier power and give out warning signal.
r @
ro ge
Maximum current load in each phase is up to 0.55A for the voltage generator.
z In case that the large current has been output for a long time, and as a result, the power
amplifier’s temperature is at high degrees, the Relay Tester will automatically shut down the
power of the amplifier power and give out warning signal, User shall stop test right until the
amplifier power gets cool.
z Binary Input’s potential is directional. So better to use idle contact as usual.
z Negative terminals A, B, C of Binary input are all connected together, but not connected with
the public terminal ‘N’ of voltage / current output terminal and the ground wire (such as panel,
machine box) that is the suspending ground. Binary Input’s terminal is compatible with the idle
contact and the potential (10-250V). However, Binary Input’s terminal has directionality for the
input of the charged contact, as shown in the Figure below, A, B, C and R are connected with
the high potential (+),the negative terminal are connected with the lower potential (-) of the
charged contact, and then the computer can detect the overturn of the contact state. If the
connections are in reverse, what will always be detected will be the closed state.
z If there is emergency in the process of the test, the Power Amplifier button must exit rapidly
and then to shut down the power of the host of Relay Tester.
8
K68 Series Protection Relay Test Set
e . c o m . c n
(3)
ing s i n
Power amplifier button: Press the button to start amplifier, while amplifier stop
@k
ro ge r
working the moment the button revert.
UB and UC are applied for programmable DC output of DC module. UN terminal is
(4)
electrically connected.
Both AC current and DC current can be output from Current output terminals. IN
(5)
terminal is electrically connected.
Functional keyboard: the numeric keys from 0 to 9 are worked for changing the
data of the testing menu. When inputting the data, user should firstly point to the
(6) data position which to be modified with the mouse, and then click the confirm
button. Previous data get cleared and then input new data. After the input please
click confirm button.
Rotary encoder: clockwise move cursor to left and anticlockwise move cursor to left
(7) and pressing down or Fn Key for enter. It can be substituted for the button
▲, , , , on the function keyboard.
Binary Input contact:
1) Public terminal TN corresponds to binary Input contact A, B, C, and TN is electrically
(8)
connected.
2) Binary contact are compatible with idle contact and charged contact, Potential +
9
K68 Series Protection Relay Test Set
terminal of charged contact is supposed to connect to public terminal TN (HN).
e . c o m . c n
@k ing s i n
ro ge r
10
K68 Series Relay Tester
. c n
5 VGA interface, is meant to be external connective to various VGA display
6
i n e . c o m
PS/2 mouse or keyboard, is meant to be external connective to PS/2 mouse or
s
k ing
keyboard at one time
7
8
ro ge r @
RJ45 interface, is meant to have data transmission between network and computer;
COM4
11
K68 Series Relay Tester
The main interface of user Operation is shown as below after set software start running:
e . c o m . c n
@k ing s i n
ro ge r Fig 3.1-1 Main menu
Users may choose to enter the function modules required with the Rotary encoder or mouse and can
also switch to choose the function modules with the first shortcut key or the direction key on the left
of the external keyboard and then press ‘Enter’ to enter.
12
K68 Series Relay Tester
company name, website and telephone of the current system. The reference of the first edition of
K68i Instruction such as software upgrade or content supplement. The real function should refer to
the set latest version as software upgrading.
(1) Run
Click ‘Run’ button and begin to this test.
(2) +
Click ‘+’ manual increase button and the chosen variable are increased gradually in
accordance with the set step length.
(3) -
Click ‘-’ Manual decrease button, and the chosen variable is decreased gradually in
accordance with the set step length.
(4) PgDn
. c n
Click ‘PgDn’ button, and switch to another Parameter Setup interface.
(5) Save
s i n e . c o m
e r @k ing
Click ‘Saver’ button, spring out ‘Save parameter’ interface. In the interface of ‘Save
g
ro
parameter’, save the tested parameters or import the tested parameters previously saved
and delete parameters.
(6) Report
When springing out ‘Report processing’ interfaces, save, View or delete a report.
(7) Bin. Input
Binary Input: the potential of the electric volume of the input switch has directionality,
under the normal circumstance, you had better use the dead contact. A, B, C negative
terminals of Binary Input terminals are all connected together, and not connected with
the public terminal ‘N’ of voltage and current output terminal and the ground wire (such
as panel, machine box) that is the suspending ground. Binary Input terminal is
compatible with the dead contact and the potential (10-250V). However, the input with
electric contact has directionality (refer to the attentions in 1.6 above for the detail).
(8) Bin. Output
Binary Output: the impulse signal can be triggered from the Relay Tester, to start some
functions of the protection device and reach synchronous or delay timing.
(9)Load
13
K68 Series Relay Tester
Switch the light load and heavy load of the Relay Tester. Under the normal
circumstances, the Relay Tester outputs light load; when the impedance value is greater
with load or the greater current is output in the Relay Tester; it is proposed to switch the
state of the heavy load before testing.
(10)Exit
Exit this module and Return to the Main menu of the system.
(11)Fn
Press ‘Fn’ function key can jump the Cursor to the bottom function control key and step
to next key.
e . c o m . c n
@k ing s i n
ro ge r
14
K68 Series Protection Relay Test Set
Click‘DC Test’ module of the Main menu and enter Direct Current interface, This Module test
manually and automatically action value and return time of AC current/Voltage relay as shown in
Fig. 3.3-1:
e . c o m . c n
@k ing s i n
ro ge r Fig. 3.3-1 DC Relays Testing
① Left upper area of the interface: You can set the starting value, the final value and step size for
each variable value of the tested AC and DC voltage and current. There are a 4 voltage
channels and 3 current channels in the area, including DC 0-150V voltage output from
UA, UB, UC port and DC 0-300V voltage output from Ub (+) and Uc (-) port. And
0-20A DC current is output from IA, IB, and IC. Click ‘√’of the option box of
‘variable’ with the mouse, as indicates the variables will the variable tested.
② On the left upper area of the interface: The setup area for testing parameters:
③ On the lower area of the interface: It displays the open or close state of Binary Input or Binary
Output and it is the display column of tested results.
15
K68 Series Protection Relay Test Set
c n
3.3.2 Parameter setup of the set:
i n e . c o m .
r @k ing s
Variable : including Amplitude Value, phase and frequency, one of which can be chosen as a
ro ge
variable and eight channels(five-way voltage and three-way current)of which can also
be chosen as variable output.
Test mode: including Automatic test and manual testing mode.
Auto: Control Action value, Return Value and Return Coefficient of the testing variables through
setting variable mode, automatic test time and variable step size. When testing, the
variable will increase or decrease by degrees from the starting value to the final value in
accordance with automatic time and step size; when doing an excessive test, set step
size to the positive and the starting value set must be less than the final value; when
doing an inadequate test, set step size to the negative and the starting value set must be
more than the final value. Note: Click ‘Stop’ button to stop the test and then amend the
parameters to retest if a new test is required by changing the parameters in the
automatic test.
Manual : Control the test manually by variable step size of ‘+’ Manual increase or‘-’ Manual
decrease. When testing, the change of the variable will not be controlled by the change
time and not be limited by the final value, step size will not be set to the negative, and
the test of increase or decrease by degrees can be done by +Manual increase and
-Manual decrease; when Binary Input receives the action signal and then the test stops,
16
K68 Series Protection Relay Test Set
meanwhile, action time and action value are recorded. After testing, the setup
parameters will be changed to re-test without clicking‘Stop’ button to stop the test, for
the parameter can be changed directly.
Mode : Only adapt to Automatic test, including ‘Action stops’ and ‘Action returns’ mode.
Pick-up: Variables change to strop from the starting value to the final value in accordance with step
size or receive the protection signal to stop the testing process in the process of the
change. Action time and Action value will be automatically recorded and action value
or Return Value of the variable can be tested.
Drop-off : Voltage or current variables change from the starting value to the final value in
accordance with step size, when the protection action signal is received, the variable
will begin to return to the starting value until return signal is received, when Action
stops, action time, action value, return value and return coefficient will be recorded.
Action value, return value and return coefficient will be automatically tested.
Steps(s): when automatically testing, the time of step size changes once for the variable, the
automatic time generally set should be more than Action time and Return Time of the
m . c n
relay, Maximum Automatic testing time is set to 1000s. When manually testing, users
e . c o
ing s i n
can grasp the changing time.
e r @k
Deglitch(s): JitterBuffer time, Deglitch(s) generally can be set to 15ms, it functions when the tested
ro g
result is affected due to the jitter of the protection access point in the process of testing
during automatic test, only after the lasting period when the access point is closed or
disconnected meets the set time, the located state is authorized.
Click ‘DC Test’ module with the mouse and enter the interface shown in Fig. 3.3-3:
17
K68 Series Protection Relay Test Set
. c n
Connect the testing terminals of the relay or the protection device to be tested with the
s i n e . c o m
corresponding output port of the current or voltage by wire and connect the contact of the
ge r @k ing
relay or the output contact of the protection device with Binary Input port of the Relay Tester
ro
by wire. (Note: DC voltage is output from Ub (+) and Uc (-) port and DC current is output
from IA and In).
2) Parameter setup
A. Set testing mode, including Manual test and Automatic test.
B. Set variables and the starting value and the final value of variables.
C. Set Binary Input (Digital input) and time mode.
D. Set ‘Light load’ or ‘Heavy load’ according to the testing load bulk of the Relay Tester.
E. Save Parameters.
F. Run.
G. Report processing and choose whether to save the report.
3) Testing process
Click on ‘Run’ button to begin the test and click ‘stop’ key if pausing the test in
Operation. In the process of manual test, the parameters of the variable can be changed. If it is
the automatic test, the parameters cannot be changed. Manually press ‘+’ and ‘-’ to make the
relay operate if it is the manual test, when action value and action time are recorded. When
clicking ‘stop’, the test ends and Save Report dialog box is automatically sprung out. Press
18
K68 Series Protection Relay Test Set
‘Save’ to save results and ‘View’ to preview the selected testing report.
e . c o m . c n
@k ing s i n
ro ge r
19
K68 Series Protection Relay Test Set
3.4 AC Relays Testing
Click ‘AC Test’ module on the Main menu with the mouse and enter Alternating Current
interface, as shown in Fig. 3.4-1:
e . c o m . c n
@k ing s i n
ro ge r Fig. 3.4-1 AC Test
The AC test as AC Current and Voltage Source can output 4-channel Voltage and 3-phase Current
for various manual and automatically test.
This module is mainly Calibrate the action and return value and time of AC/DC Current/Voltage
Relay, it can also verify the protective Action value and time of over current, zero-sequence,
overloading.
In manual test, press ‘+’ or ‘-’ to add/subtract each steps of amplitude, phase and Frequency, the
action value from motionless/act to act/motionless of relay are recorded.
Automatic test can set ‘ mode’,‘Auto time’ and ‘Variable step’ to control Action value, Return
Value and Return Coefficient of the testing variable. When testing, variables will decrease or
increase by degrees from the starting value to the final value in accordance with automatic time and
step size, when doing the excessive test, step size is set to the positive and the starting value must be
set less than the final value; when doing the inadequate test, step size is set to the negative and the
starting value must be set to more than the final value.
Click ‘√’of the option box of ‘variable’ with the mouse, as indicates the variables will the variable
tested.
20
K68 Series Protection Relay Test Set
3.4.1 Interface Introduction to the set:
. c n
Parameter Setup ①
s i n e . c o m
k ing
Variable : including Amplitude Value, phase and frequency, any one of which can be chosen as
ro ge r @
the variable and 7 channels can be simultaneously(4-way voltage and 3-way
current)as the output variable.
Testing mode: including automatic testing and manual testing mode.
Auto : can set ‘change mode’, ‘Automatic testing time’ and ‘Variable step size’ to control
Action value, Return Value and Return Coefficient of the testing variable. When testing,
variables will decrease or increase by degrees from the starting value to the final value
in accordance with automatic time and step size, when doing the excessive test, step
size is set to the positive and the starting value must be set less than the final value;
when doing the inadequate test, step size is set to the negative and the starting value
must be set to more than the final value. Note: the parameters will not be changed in the
process of automatic testing, or else the test must be stopped at first and then the
parameters can be corrected to test again.
Manual: Change Step Test to manually control the test through ‘+Manual increase’ or ‘-Manual
decrease ‘. When testing, the variable changes will not be controlled by the changes in
time and not be limited by the final value, step size is not set to the negative and can be
increased or decreased by degrees through +Manual increase and -Manual decrease.
After Binary Input receives the action signal, the test stops, meanwhile, Action time
21
K68 Series Protection Relay Test Set
and Action value automatically are recorded. After testing, it needs to change the
parameters set and test again without stopping the button to stop the test, directly
changing the parameters.
Mode : Only for Automatic test, including ‘Action stops’ and ‘Action returns’ modes.
Pick-up: Variable change to stop from the starting value to the final value or receive the protecting
action signal in the process of change to stop the test. Action time and Action value are
automatically recorded, and Action value or Return Value can be tested.
Drop-off: When voltage or current variable is changing step by step from the starting value to the
final value in accordance with step size, it will receive the protecting action signal and
begin to return to the starting value. Action will not stop until Return signal is received.
Action time, Action value, Return Value and Return Coefficient are automatically
recorded.
Steps(s): when automatically testing, the time of step size changes once for the variable, the
automatic time generally set should be more than Action time and Return Time of the
relay, Maximum Automatic testing time is set to 1000s. When manually testing, users
m . c n
can grasp the changing time.
s i n e . c o
ing
Ux : Including being continuously adjustable, +3U0, -3U0, + 3 *3U0 and - 3 *3U0 five setups,
ro ge r @k
when setting to 3U0, its value conforms to 3U0 value of the phase-sequence diagram;
when Ux is set to be continuously adjustable, its amplitude value, phase and frequency
can be set up arbitrarily, when Ux phase refers to UA.
22
K68 Series Protection Relay Test Set
. c n
1) Testing Connection
s i n e . c o m
Connect the terminal of the relay or the protection device to be tested with the output port of
@k ing
the corresponding current or voltage by wire and connect the Action contact of the relay or the
ge r
ro
output contact of the protection device with Binary Input port of the Relay Tester by wire.
2) Parameter Setup
A. Set Testing mode and choose Manual test or Automatic test.
B. Choose the variable and set the starting value and the final value.
C. Set Binary Input and timing mode.
D. Set ‘Load’ fore ‘Light load’ or ‘Heavy load’ chooses according to the load size of the
Relay Tester.
E. Save Parameters.
F. Run.
G. Process the report and choose whether to save the report.
3) Testing Process
Click on ‘Run’ button to begin the test and click ‘Stop’ key if pausing the test in Operation.
In the process of manual test, the parameters of the variable can be changed. If it is the
automatic test, the parameters cannot be changed. Manually press ‘+’ and ‘-’ to make the relay
operate if it is the manual test, when action value and action time are recorded. When clicking
‘Stop’, the test ends and Save Report dialog box is automatically sprung out. If it is the
manual test, the test ends after Binary Input receives the signal of the closed Action contact of
23
K68 Series Protection Relay Test Set
the relay, Save Report dialog box is automatically sprung out from the system.
n
Zero-sequence over current three-step time limit: 1.00S
i n e . c o
Zero-sequence over current four-step direction input/exit:
m . c Exit
k ing s
Zero-sequence over current four-step fixed value:
r @
1.00A
ro ge
Zero-sequence over current four-step time limit: 1.50S
Testing Steps:
1)Testing Connection: connect A-phase current circuit of the protection device with IA and IN
of the current output terminal and connect the Action contact of the protection output with
terminal A of Binary Input of the Relay Tester, as shown in Fig. 3.4-3 below.
24
K68 Series Protection Relay Test Set
2) Parameter Setup:
Variable type: A phase current amplitude value Frequency: 50Hz
Starting current value: 5.00A
Change step size: 0.50A
Testing mode: manual mode
3) Test: Click ‘Run’ key to begin the test and record automatically Action value, Return Value
and Return Coefficient.
4) Save the report according to the reminder of the system and click ‘View’ button to consult
the report, as shown in Fig. 3.4-4:
e . c o m . c n
@k ing s i n
ro ge r
Fig. 3.4-4 AC Relays Testing Report
25
K68 Series Relay Tester
Click ‘Distance’ module on the Main menu and enter the interface. The Testing Module is mainly
applied for Distance Test of circuit protection, such as the distance and zero-sequence; Be able to
simulate various single-phase grounding, two-phase grounding, inter-phase and three-phase
short-circuit fault in the power system, including instantaneous/transient, permanent and
transitional/switch faults. The verifying functions of the module include fixed impedance value
verifying and fixed value verifying of impedance weight/hefts of working frequency variable, as
shown in Fig. 3.5-1 below.
e . c o m . c n
@k ing s i n
ro ge r
26
K68 Series Relay Tester
e . c o m . c n
3.5.1 Interface Introduction to the Set
@k ing s i n
ro ge r
There are 3 areas in the interface and Press ‘PgDn’ to the next page interfaces
① it is the area to control parameter setup.
② it is the setup area for computation model option and fault startup mode, etc.
③ it display open and close of Binary Input and Binary Output contact and it is the display column
of tested result.
Parameter Setup ①
Options of testing items
Testing Item Option is including the checkout of fixed impedance value and the fixed value of
variable impedance component of power frequency.
Checkout of impedance fixed value:
Computation formula of short-circuit voltage
Positive direction single-phase grounding short-circuit: V=(1+KL)kIZset
Positive direction short-circuits between phases: V=2kIZset
27
K68 Series Relay Tester
n
entering the fault, no matter how the tested result will be; the test device will close the test
e . c o m . c
automatically when the hour that tests are over comes. For example: if the action time at I
i n
k ing s
step is 0.5S, the test period must be more than 0.5s when checking the fixed value at I step, as
r @
ro ge
can be set to 1.5S.
Deglitch(s): JitterBuffer Time. Generally, it can be set to 15ms and it is the set time parameter to
prevent the protection contact from jittering to affect the tested result in the process of testing
when it is the automatic test, and the located stated will be authorized only when the closed
contact or the lasting disconnection meets the set time.
Fault setting
Fault Type: Click [Fault Type] with the mouse. There are nine kinds of fault states in the drop menu,
such as ‘A phase grounding, B phase grounding, C phase grounding, short-circuit between
A and B phase, short-circuit between B and C phase, short-circuit between C and A phase,
AB phase grounding, BC phase grounding, CA phase grounding, three-phase short-circuit’.
Direction: including two directions: 1.Forward 2. Reversed
Fault character: permanent fault and instantaneous fault. When choosing the instantaneous fault,
after Reclosing, the fault will not occur. Whereas, the fault will continue to occur. For the
permanent fault, the Reclosing fault phase is related to whether fault switch will arise.
PT: Simulate that the mutual inductor of voltage is installed either on the bus (At busbar) or on the
circuitry (At line). When PT is installed on the bus, after disconnecting the fault phase, the
28
K68 Series Relay Tester
phase current is zero, and voltage comes back to the normal phase voltage(V=Vnom); When
PT is installed in the circuit, after disconnecting the fault phase, the phase current and voltage
are zero.
Z : there are two expression methods for the impedance value of the circuit or the load when there
is fault: (Z∠θ°) or (R+jX). For changeable fault, it can be set to short-circuit impedance
value that is completely different from the setting impedance. Setting different impedance
values can test the latter speedup of the protection.
Multiple : Short-circuit impedance=0.95 times of setting impedance denotes that impedance value is
0.95 times of setting impedance when fault is simulated, in principle: when the impedance
value tested by the protection is less than or equals 0.95 times of the setting impedance, it
will surely operate reliably at the step; when the impedance value tested by the protection is
more than or equals 1.05 times of the setting impedance, it will not surely operate reliably at
the step; the action time will be tested when the impedance value tested by the protection
equals 0.7 times of the setting impedance.
Test mode
e . c o m . c n
@k ing s i n
Calculation: including ‘KL’ and ‘Re/Rl and Xe/Xl’ two modes. When the fixed value of the
ro ge r
protection is K, ‘KL’ computation method can be chosen and the values of Re, Im can
be set. When the fixed values of the protection are KR and KX, ‘RE/RL and XE/XL’
can be chosen and the values of KR and KX can be set.
Computing Impedance contains the impedance and short-circuits impedance in the
system. The setup value of impedance Zs in the system must be more than or equal 0,
the range of Ph (Zs) is from -90 to +90 degrees. The setup value of short-circuit
impedance Zl may be more than 0 or less than 0. When Zl is negative, it means the
short-circuit impedance when there is the fault in reverse direction of the installation
position of the protection. The range of Ph (Zl) is from -90 to +90 degrees. If Ph (Zl)>0,
it is the inductance in the circuit, if Ph (Zl) <0, short-circuit impedance has
capacitance.
29
K68 Series Relay Tester
sequence, Kso is a real number and its void. Its imaginary part is zero.
Test mode: including constant short-circuit current, constant short-circuit voltage and constant
power(system)impedance three kinds of computation models.
1. I=Constant
e . c o m . c n
@k ing s i n
There is an ideal current source in the fault circuit assumed by the model. Compute
ge r
short-circuit voltage by short-circuit current and short-circuit impedance.
ro
2. U=Constant
There is an ideal voltage source in the fault circuit assumed by the model. Compute
short-circuit current by short-circuit voltage and short-circuit impedance.
3. Z=Constant
There is a power impedance in series with the ideal voltage source, connecting with the fault
circuit. The model is adjacent to the actual grid.
The short-circuit voltage and short-circuit current will change as the short-circuit impedance
changes. When reducing short-circuit impedance, the short-circuit current will increase and fault
residual voltage will be decreased. Whereas, short-circuit current and short-circuit voltage will
decrease and increase as the short-circuit impedance increases.
For the computation model of the constant current, the short-circuit voltage Vf computed by current
and impedance will not more than Vnom(Rated Voltage). If V>Vnom, short-circuit current will
automatically decrease when computing in order to meet the conditions of VF<Vnom.
For the computation model of the constant voltage, when the fault current If computed by voltage
and impedance is over big, that is If>Imax (30 A), the program will produce the alarm. The solution
is to reduce the short-circuit voltage set.
30
K68 Series Relay Tester
For the computation model of the constant power(system)impedance, when the amount of
short-circuit impedance and the power impedance is near or equals zero, the computed short-circuit
current will be over big, that is If>Imax. When the reminder of current beyond the limit is on the
bottom of the screen. The solution is to increase the power impedance to remove the existing
number beyond the limit.
Parameter Setup ②
Mode : including ‘Time startup’,‘ Key startup’ and ‘overturn startup of h contact’ and‘ GPS
startup’, ‘Time startup’ is chosen after the test begins, and the test is carried out
automatically according to time before fault and fault time that have already been set.
Key startup works after the test begins. Choose manually whether to enter fault sate.
GPS startup is used to test the Property of the whole set of HF protection by
synchronous fault output of GPS on the tow terminals in the circuit.
Binary setup: to set the time before fault and to set the Binary Output when starting fault. Time
n
before fault is the time to be set before entering the fault. The default Binary Output
e . c o m . c
setup is output, once entering the fault state. Relay Tester can give out a signal by Binary
i n
k ing s
Output after prolonging one-step time according to the setup; Binary Output delay is
r @
ro ge
used to match Binary Output setup. Binary Output hold is the Hold of the signal sent by
Binary Output.
Binary Input: A, B and C three couples of Binary Input can be defined as protection Trip A, Trip B
and Trip C or three-jump signal, respectively, where necessary, and can also be closed.
The state change of Binary Input contact will not be checked any longer when testing.
Binary Input H is generally re-switching Binary Input signal, and there are other four
Binary Input contacts a, b, c and h for the device.
Ux : voltage Ux Output options include random value, +3U0, -3U0, + 3 *3U0 and - 3 *3U0,
Non-V A、Non-V B、Non-V C、Non-V AB、Non-V BC、Non-V CA
Note: Take ‘ there is no voltage A when checking’ as an example, the output process of Ux is from
before fault to after re-switch, and Ux outputs A phase voltage Ua if that there is no
voltage when checking is chosen for Ux setup.
Binary Output: The test device can output Binary Output by‘1’,‘2’,‘3’ and‘4’ four couples Binary
Output contacts on the side panel, Binary Output is output by empty contact. The test device
can be off or closed to output the relaying contact and empty contact signal according to the
requirement before fault or instantly when testing, and the main use is to start other
equipments.
31
K68 Series Relay Tester
. c n
protection screen to be tested with the test wire.(Note: here the current is output by
i n e . c o m
three-phase, IA terminal connection is as A phase current and IB terminal connection is
s
k ing
as B phase current, IC terminal connection is as C phase current, each phase current has
ro ge r @
the output range of 0-35A)
C. Connect the Trip And closed output contact of the protected and integrated re-switch
device to Binary Input ports A, B, C, COM and H, COM of the test device. The trip and
the closed contact can be either the empty standby contact of the protection or re-switch
or the contact with electricity to be connected with the Trip and closed coil of the
breaker.
Note: when using the contact with electricity, the public terminal COM must be connected with+
terminal of DC power, which is +KM of the control source, and only any one terminal of it
is connected. The allowed voltage of DC power is 0~250V.
D. Operate the computer and enter the testing unit of the whole set to set the testing
parameters, such as short-circuit impedance, fault type, fault characteristic and closed
angle and to set whether PT lies at the bus or at the circuit according to the actually
installation position of PT. The test of the whole set begins after all parameters have been
set according to the requirements.
E. The whole set’s action time measurement, to measure the time of re-switch action and
32
K68 Series Relay Tester
action time from beginning to simulate fault to the circuit action of the breaker trip.
When testing of protecting the failure of the breaker matching linkage, the breaker’s
performance should be simulated to test under the Operation of the positive and negative
auxiliary bus and under the failure of starting the breaker in the protection circuit,
respectively. Connect the action contact of failure protection to ‘a’ Binary Input terminal
of Relay Tester. The fault current should be more than the current setting value of the
failed protection when testing and the maximum fault time of simulating fault should be
more than the action time of the failed protection.
◆ Testing of circuit protection whole-set transmission breaker
All preparations and Operation steps are the same as above. Before the formal transmission
breaker is tested, the following step should be:
A. Exit Trip and close the export press board, and take a simulation test without transmission
switch at first.
B. After simulating the test correctly, input the Trip, closed export press board and take a
simulation test with transmission switch.
◆ Allowed or closed HF protecting commissioning:
e . c o m . c n
@k ing s i n
When the allowed or closed directional high-frequency protection or high-frequency Distance
ro ge r
Protection is adopted to test, Binary Output terminal on the panel of the test device is the
contact of the protection device to send signal. When simulating the internal fault in the
positive direction, the contact is conducted instantaneously; the protection receives the allowed
signal and can instantaneously trip. When simulating the external fault, shut off the connection
between Binary Output contact of the host and the contact of protection device to receive
signal. The protection will not trip if it has no allowed signal, or only when simulating the
closed directional high-frequency protection or high-frequency Distance Protection, the output
terminals can be used as the closed contact of the protection to receive signal. When simulating
the external fault, the contact is conducted. The protection receives the closed signals and will
not trip or delay the trip, during the fault simulation, as long as the terminal is disconnected,
the protection can instantaneously trip without receiving the closed signals.
When simulating the closed high-frequency protection, this terminal can be used as the input
terminal of the fault signal in the channel. When simulating the fault in the positive directional
area, the contact is conducted, the protection receives the fault signal in the channel because
the protection has no allowed signal at the same time, making high-frequency trip circuit open
in a short time, as can instantaneously trip. The terminal is relieved, and the protection can not
instantaneously trip.
33
K68 Series Relay Tester
1)Testing Connection
A.Connect the output terminal of voltage and current of the test device with the
corresponding input terminal of current or voltage by test wire.
B. Connect the trip export contact of the protection device with Binary Input contact A of
the Relay Tester and connect the Action contact of re-switch with Binary Input
contact H of the Relay Tester.
2)Parameter Setup
A. Choose fault type, fault direction and types.
B. Choose the control mode of the test.
C. Set impedance fixed value and testing time (for automatically start control mode) mode.
D. Set the definitions of Binary Input and Binary Output.
E. Run.
F. Process the report and choose whether to save the report.
c n
3.5.5 Testing Example
i n e . c o m .
Protection Device: The whole-set protection device for ISA—311 model Microcomputer line
k ing s
Testing Task: the whole set simulation test of two-step grounding Distance Protection
r @
ro ge
Bill of Fixed value:
Zero-sequence Impedance Compensation Coefficient:
One-step input/exit for grounding spacing:
0.67
Exit
One-step fixed impedance value for grounding spacing: 0.250 Ω
Two-step input/exit for grounding spacing: Input
Two-step fixed impedance value for grounding spacing: 1 Ω
Two-step time limit for grounding spacing: 0.50S
Three-step input/exit for grounding spacing: Exit
Three-step fixed impedance value for grounding spacing: 5.00 Ω
Three-step time limit for grounding spacing: 1.00S
Fixed angle value for grounding spacing displacement: 0°
Positive sequence fixed impedance angle value in the circuit: 75 °
Zero-sequence fixed impedance angle value in the circuit: 75 °
Power frequency variable Distance Protection input/exit: Exit
Protection start re-switch input/exit: Input
Re-switch time limit: 1.50S
34
K68 Series Relay Tester
Testing Connection:
A.Connect the output terminal of voltage and current of the test device with the
corresponding input terminal of the current or voltage by test wire.
B. Connect the trip export contact of the protection device with Binary Input contact A of
the Relay Tester and connect the Action contact of re-switch with Binary Input
contact H of the Relay Tester,
Parameter Setup:
The process for the test is: before fault → fault → Reclosing
Parameter Setup ①:
Testing Item: fixed impedance value here is chosen to check.
Basic Setting:
Fault time:2.50S Fault mode: Transient
Un:57.74V; Trip Delay:0S
e . c o m . c n
fn(Hz):50.00Hz;
@k ing s i n
Deglitch: 15ms
ro ge r
Fault Setting:
Fault Type: L1-E Direction: Forward
Z(Ω):1 Ω θ(°): 80 °
R:Calculated automatically by program. X:Calculated automatically by program.
Multiple :0.95
Computation Model:
Computation Model: I= constant
Zero-sequence Compensation Coefficient: here is KL
Coefficient KL(Re):0.67; Coefficient KL(Im): 0
I(fault): generally ,it is 5.0A(if fixed impedance value is small, such as about 0.1 Ω , the
corresponding short-circuit current should be increase in order to decrease the
error of current and voltage of protecting measurement, whereas, the
short-circuit current should be decreased).
Parameter Setup ②
Fault startup mode: here is Time startup.
Time before fault: choose 20s.
35
K68 Series Relay Tester
e . c o m . c n
@k ing s i n
ro ge r
36
K68 Series Relay Tester
Click the icon of ‘Harmonic’ on the Main menu and enter the Operation Interface of Harmonic.
The Testing Module can control Test instrument and output AC and DC and harmonic to test
automatically and manually, and oscillogram is used for real-time monitor of every output channel.
If the grounding protection tests of the stator winding of the dynamotor and harmonic constraint
differential relay test can be done by the module to test Action value and Action time of the
harmonic relay, with operation interface shown in Fig. 3.6-1:
e . c o m . c n
@k ing s i n
ro ge r
37
K68 Series Relay Tester
Harmonic setup: amplitude value and phase of fundamental and 12th harmonic of every channel can
be set in the left upper area on the interface. For instance, click ‘UA’ and ‘IB’ button
and switch the output channel to set the parameter or View.
Testing mode: including Manual test and Automatic test.
e . c o m . c n
testing when it is the automatic test, and the located stated will be accepted only when
ing s i n
the closed contact or the lasting disconnection meets the set time .
e r @k
Step(s): it is the Hold of output and is only applicable to the automatic testing mode.
ro g
3.6.3 Test Flow
1)Testing Connection
A. Connect the output terminals of voltage or current of the test instrument with the
corresponding input terminals of the voltage and current of the protection device by
test wire.
B.Connect the closed trip export contact of the protection device with Binary-Input
contact A of the test instrument.
2)Parameter Setup
A. Choose Harmonic phase, such as one of UA, UB, UC, IA, IB, IC as the Harmonic
phase.
B. Choose the expression mode of harmonic.
C. Choose testing mode.
D. Choose harmonic number of the variable.
E. Choose amplitude value or phase the variable.
F. Start.
38
K68 Series Relay Tester
Protection Device: Shenzhen NARI ISA-387F Digital transmitter Differential Protection Device
Testing Item: Fixed detection harmonic constraint characteristic (HV A-phase)
Bill of Fixed value:
Transformer Connection Mode Y/Y/D-11
CT ratio regulating coefficient is separately 1:0.5:1 at the first, second and third side.
Differential current quick-break protection input/exit Input
Differential current quick-break protection fixed value 5A
Compound ratio differential protection input/exit Input
Compound ratio fixed differential current threshold value 1A
Compound ratio fixed differential ratio value 0.2
CT break-line closed ratio differential input/exit Exit
n
Testing Connection as Fig3.6-2
e . c o m . c
Test instrument IA→ High-voltage side of protection IHA, Test instrument In→
i n
r @k ing
High-voltage side of protection IHA,
s
ro ge
Testing Setup:
IA harmonic setup:
1st :5.0A 1st phase:0°
2nd:1.8A 2nd phase:0°
39
K68 Series Relay Tester
e . c o m . c n
s i n
Click ‘process the report’ and spring out the dialog box of ‘process the report’, choose
ge r @k ing
the file name of the testing report to be saved or input the new file name of the testing
ro
report again and click ‘Save’, to save the report.
40
K68 Series Relay Tester
Click the icon of ‘Frequency’ on the main menu with the mouse and enter its interface. The Testing
Module of Frequency protection including LF/LV/LI deloading and test the Action value, Action
time, df/dt Action value, the closed value of voltage and the lockout value of current of various
frequency relays and Low Frequency Decrease Load automatic device, as shown in Fig. 3.7-1
e . c o m . c n
@k ing s i n
ro ge r
Fig. 3.7-1 Frequency protection Testing
41
K68 Series Relay Tester
e . c o m . c n
Fig 3.7-2 Frequency protection
@k ing s i n
ge r
3-Phase Output:Set the 3-phase output V / I
ro
Low-frequency:
From :Set the starting change point of frequency.
To :Set the final change point of frequency
Auto slip:Set the change rat of frequency.
Step :Set the change step size of frequency. Generally, the proper step size will be chosen
according to the testing requirement, and step size is the less, the tested precision of
Action value is the higher.
Time At :According to the direction of frequency change, when frequency changes to the timing
frequency value, the timer start to work, and the timer will not stop until the relay
moves and feedbacks to Relay Tester.(it is available when testing Action time.)
Interval :Protect the return time, to ensure the protection returns reliably before each step changes.
Hold :Set the hold output time for each state, generally, Hold set should be more than Action time
of the device.
Pre-time:It is the time before frequency changes, and it is the frequency output time, when voltage
and current are output according to the setup.
42
K68 Series Relay Tester
‘Frequency protection’ can test movment frequency, Action time, slip lockout value, low-voltage
lockout value and low-current lockout of various frequency relays and automatic devices of Low
Frequency Decrease Load, the testing method is as below:
n
Testing Item: Action frequency
e . c o m . c
A. Set the scope of frequency change and slip: generally, the starting value is the rated
i n
k ing s
frequency of the device(50Hz), and the final value is the frequency with which the
r @
ro ge
protection can move reliably. The change step size is the value that meets the testing
precision, generally it is 0.1Hz and slip df/dt is less than ‘df/dt lockout’ of the
protection.
B. Set voltage and current values under which the device can work normally.
C. Input the fixed value of the device and input the allowed error.
D. Description of Test Flow
In ‘Testing setup’, set ‘Pre-time’ 2.000S; ‘Interval’ 0.5S; ‘Hold’0.3S; ‘auto slip’
1Hz/S; ‘Step’ 0.1Hz. Test instrument firstly outputs 50Hz frequency for 2.000S(Change
Time), making the device work normally. After the Pre-time, the output frequency of the
test instrument changes from 50Hz at 1Hz/S to 49.9Hz and holding 0.3S, if the protection
moves, the test instrument will stop testing; if the protection does not move, test
instrument will stop to output and will output 50Hz again after 0.5S, holding 2S, and then
it will slip to49.8Hz at 1Hz/S, by this analogy, taking the same way, it changes to 49.7Hz,
49.6Hz… until the Action frequency of the protection will be measured.
Testing Item: Action time
A. Set voltage and current value under the working conditions of the device.
B. Input timing triggering frequency.
43
K68 Series Relay Tester
C. Input the starting value of change and the final value (should be consistent to the triggering
frequency) and df/dt(less than df/dt lockout value)in the column of the frequency change
scope and the change rate.
D. Description of Test Flow
In ‘Testing setup’, set ‘Pre-time’ 2.000S; ‘Interval’ 0.5S; ‘Hold’0.3S; ‘auto slip’
0.5Hz/S; ‘Step’ 1Hz; Test instrument firstly outputs 50Hz frequency for 2.000S(Pre-time),
making the device work normally. And then it will change from 50Hz to the final value at
0.500Hz/S, until the timer starts at 49.000Hz, and it will not continue to change the
frequency until the device moves and the test instrument stops timing and measures the
Action time.
1)Wire Connection
A. Connect the output terminal of voltage and current of the test device with the
corresponding input terminal of current or voltage of the protection device by test
wire.
. c n
B. Connect the trip export contact of the protection device with Binary-Input contact A of
the test instrument.
s i n e . c o m
k ing
2)Parameter Setup
ro ge r @
A. Set testing items.
B. Set three-phase current value and voltage value that ensure the protection device works
normally.
C. Set the control time.
D. Set the step size of the corresponding variable according to testing items.
E. Start.
F. Process the report and choose whether to save the report.
Protection Device Shenzhen NARI ISA-351F type decentralized Microcomputer Protection Test
and Control Device.
Testing Task: Action Frequency Testing
Bill of Fixed value:
Δ f/ Δ t lockout Low Frequency Decrease Load input: Input
Δ f/ Δ t lockout low-cycle fixed frequency value: 49.00Hz
Δ f/ Δ t lockout Low Frequency Decrease Load time limit: 2.00S
44
K68 Series Relay Tester
Testing Connection
e . c o m . c n
@k ing s i n
A. Connect the output terminal of voltage and current of the test device with the
ge r
corresponding input terminal of current or voltage of the protection device by test
ro wire.
B. Connect the trip export contact of the protection device with Binary-Input contact A of
the test instrument, as shown in Fig. 3.7-3.
45
K68 Series Relay Tester
m . c n
Run: Go on the test in accordance with ‘Run’ and go on the test according to testing items for test
e . c o
instrument.
@k ing s i n
e r
Save Report: Click ‘report’ and spring out the dialogue box of ‘process report’, choose the file
ro g
name of the testing report to be saved or input the new file name of the testing report again and
click ‘Save’, to save the report.
Note: Three-phase voltage and current setups must be ensured that the device work normally,
without closing when there is low-voltage or low-current, and the time should ensure that the
protection can return reliably before changing, Hold should be more than Action time of low-cycle.
46
K68 Series Relay Tester
e . c o m . c n
@k ing s i n
ro ge r
47
K68 Series Relay Tester
3.8 Aux DC
Relay Tester Model K68i can provide relay protection device with independent Aux. DC power
supply. The Aux DC output can be set according to the demand on the Aux DC switch of main
interface, and the range is 0V~300V.
e . c o m . c n
@k ing s i n
ro ge r
48
K68 Series Protection Relay Test Set
Click on Calibrate icon to enter the interface of System Calibration, and calibrating password is
required Please ensure that each item of standard instruments accord to the demand precision
and is better to the set when entering as Fig. 4.1-1 shows (Note: Calibration coefficient will
directly influence system output, so non-professional people is prohibited to enter)
e . c o m . c n
@k ing s i n
ro ge r
Fig. 4.1-1 System Calibration
System provides five types of calibration:
1. Zero offset
2. AC Amplitude calibrate
3. DC Amplitude calibrate
4. AC frequency character
49
K68 Series Protection Relay Test Set
Calibration methods:
4.1.1 AC Zero-offset Calibration
Application:Is applied to calibrate DC content of AC current and of AC voltage
Note: When AC offset, Meter’s anode and cathode corresponds to these of relay tester.
Two calibration channel in interface:Calibrate all, calibrate partial; to select ‘calibrate all’ to
calibrate all the items; And as for calibrate partial, it can make calibration for fixed point
1. Voltage Calibration
System provides two voltage shifts’ calibration: 10V and 60V, the following are taken UA
offset as example to calibrate its voltage’s offset, shown as Fig. 4.1-2
①.Select UA offset
e . c o m . c n
@k ing s i n
ro ge r
50
K68 Series Protection Relay Test Set
m . c n
③Input actual offset, i.e. DC content of 10V, and to click Ok button
e . c o
@k ing s i n
④After calibration of 10V, System will output 60V, and to input actual offset, click OK
ge r
⑤Click Save button to save the calibrated coefficient.
ro
2. Current calibration
Three phase current calibration
System provides two current shifts’ calibration: 5A and 8A, and each shift can be divided
into light load and heavy load two kinds. The following are taken IA as example to calibrate its
current’s offset
① Select IA offset,
② Click calibrate, system will firstly output 5 A at the status of light load
③ Input actual offset, i.e. DC content of 5 A, and to click Ok button
④ System outputs 5 A at the status of heavy load, Input actual offset, and to click Ok
button
⑤ After calibration for 5A, system outputs 8A at the status of light load; Input actual
offset, and to click Ok button
⑥ System outputs 8 A at the status of heavy load,Input actual offset, and to click Ok
button
⑦ Click Save button to save the calibrated coefficient.
51
K68 Series Protection Relay Test Set
4.1.3 AC Phase
No need for calibration because of hardware installed in relay tester. And the phase
discrepancy is from 0.1 to 0.2 digress.
m . c n
meter; and vice versa.
s i n e . c o
ge r @k
4.1.5 AC Frequency Character
ing
ro
Application:Is applied to calibrate the range value of AC voltage/ current under different
frequency, shown as Fig. 4.1-4
52
K68 Series Protection Relay Test Set
e . c o m . c n
@k ing s i n
ro ge r
Fig. 4.1-5 Voltage frequency range calibration
② Click ‘Run’, system will firstly output 100Hz, 10V; Input actual AC range, and to
click Ok button, shown as Fig. 4.1-6
③After calibration for 100Hz, 10V,system outputs 100Hz, 60V,Input actual AC range,
and to click Ok button,
④ Click ‘Save’ button to save the calibrated coefficient.
53
K68 Series Protection Relay Test Set
e . c o m . c n
s i n
(2).Three phase current calibration
e r @k ing
The current for calibrating corresponds to one of frequency, and the current has two shifts
g
ro
for output: 5A and 8A. The following are taken IA as example to calibrate its range value less
than 100Hz.
① Select IA Range on the interface, frequency options select100Hz,
② Click calibrate, system will firstly output 100Hz, 5A; Input actual AC range, and to
click Ok button,
③ After calibration for current of 100Hz/5A,system outputs 100Hz, 8A,Inputs actual AC
range, and to click Ok button
④ Click Save button to save the calibrated coefficient.
54
K68 Series Relay Tester
4.2 IP Setting
Click ‘IP Setting’ module on the Main menu and enter the following interface, as shown in
Fig. 4. 2-1:
e . c o m . c n
@k ing s i n
ro ge r
Fig.4. 2-1 IP Setting
The module is used to set IP address and system time.
IP is for internet/LAN PC-linking upgrading and report uploading, which need IP of set is in
the same network section as the PC for data PC-linking and please restart the set after IP setting.
Time setting is for the local date and time and saving.
55
K68 Series Relay Tester
e . c o m . c n
@k ing s i n
ro ge r
56
K68 Series Relay Tester
Before System Upgrade(at the local)and report upload, at first set IP address of the Test set
and ensure it under the same subnet,
1. IP ADDRESS SETUP for the linking computer
Operate the program of the upper computer and click ‘IP Setting’ under ‘System
Setting’ column as shown in Fig.4.3-1.
e . c o m . c n
@k ing s i n
ro ge r
Fig.4.3-1 PC-link Setting
57
K68 Series Relay Tester
e . c o m . c n
@k ing s i n
ro ge
(1)Local Upgrade r Fig. 4.3-3 System Upgrade
Download the latest upgrade packet of set to the local computer manually from KINGSINE
website and transmit the upgrade file to the Test set by the computer, the test set has been online
correctly before upgrading as shown in Fig. 4.3-4:
58
K68 Series Relay Tester
. c o m . c n
(1)Click the Test set ‘System Upgrade’ and enter ‘Local Upgrade’ menu, the present software
e
k ing s i n
version number is displayed on the interface of the system and click ‘Next’ to prepare online
@
upgrade.
ro ge r
(2)Operate the program of the upper computer and click ‘Upgrade’ module, as shown in
Fig.4.3-5
59
K68 Series Relay Tester
e . c o m . c n
@k ing s i n
ro ge r
60
K68 Series Relay Tester
e . c o m . c n
Fig. 4.3-7 Online Upload Report
ing s i n
(2) Choose the report to be uploaded in ‘System Report’ column and click ‘Next’ and list the
ge r @k
reports in ‘ the report to be uploaded’ column as shown in Fig. 4.3-8:
ro
61
K68 Series Relay Tester
Choose the file path to be saved and click ‘Enter’ and upload the repot.
(2) Upload report by U disk
Upload the report to U disk with USB interface of the Test set and copy the report to a computer by
U disk to print it.
Click ‘Upgrade’ and enter ‘Upgrade by U disk’ menu as shown in Fig.4.9-9
e . c o m . c n
@k ing s i n
ro ge r
62
e . c o m . c n
@k ing s i n
ro ge r
Address: 6/F, Block 4-CD, TianAn Cyber Park, Shenzhen 518048, China
Tel: +86-755-83418941
Fax: +86-755-88352611
Email: [email protected]
Website: www.kingsine.com.cn