HITACHI
HITACHI
Compatible PLCs
Family Model
HITACHI EH-150, Micro-EH, H20, H40, H64, H200, H250, H252, H300, H302, H700, H702,
H series H1000, H1002, H2000, H4010
HITACHI Web site: http://www.vanet.hitachi.co.jp/public/Div/iced/english/products/
HMI Setting:
Parameters Recommend Option Notes
PLC type HITACHI
Com port RS232 RS232, RS485 Must match the PLC’s port setting.
Baud rate 19200 9600, 19200, 38400 Must match the PLC’s port setting.
Parity bit Even Even Must match the PLC’s port setting.
Data Bits 7 7 Must match the PLC’s port setting.
Stop Bits 1 1 Must match the PLC’s port setting.
HMI Station No. 0 0-255 Does not apply to this protocol.
PLC Station No. 0 0-255 Does not apply to this protocol.
Online Simulator OK
Direct Online Simulator OK
Extend address mode Does not Support
PLC Setting:
Communication mode 19200,E,7,1(default)
Select
Device address :
Device
Bit/Word Format Range Memo
Type
B X hhh(h) hhh: 0~FFFF (h):0~F External Input-bit(X)
B Y hhh(h) hhh: 0~FFFF (h):0~F External Output-bit(Y)
B M hhh(h) hhh: 0~FFFF (h):0~F Data area-bit(M)
B T hhh(h) hhh: 0~FFFF (h):0~F Timer(T)
B R hhh(h) hhh: 0~FFFF (h):0~F Internal Output(R)
B L hhh(h) hhh: 0~FFFF (h):0~F Link area-bit(L)
W TC hhh hhh: 0~FF Timer/Counter current value
W WX hhh hhh: 0~270F External Input-word(X)
W WY hhh hhh: 0~270F External Output-word(Y)
W WR hhh hhh: 0~270F Internal Output-word(R)
W WL hhh hhh: 0~270F Link area-word(L)
W WM hhh hhh: 0~270F Data area-word(M)
Wiring diagram :
WARNING: If your communications cable is not wired exactly as shown in our cable assembly
instructions, damage to the MT500 or loss of communications can result.
Switch Number
1 OFF Normal mode
2 OFF TRNS0 operation
3, 4 3 4 Port1 transmission speed
ON ON 4,800 bps Doesn’t support
OFF ON 9,600 bps
ON OFF 19,200 bps Default
OFF OFF 38,400 bps
5 ON Dedicated port
6 6 PHL Port2 transmission speed
Toggle-Switch
ON Low 9,600 bps
PHL
ON High 38,400 bps
Low
OFF Low 4,800 bps Doesn’t support
OFF High 19,200 bps Default
PHL
7 OFF (System mode) Do not turn on. High
8 OFF (System mode) Do not turn on.
MT500 PLC[232]
9P D-SUB Male
7 CTS
8 RTS
EH-150 RS-485 connect must short the PLC[232] port pin 7,8.
MT500 PLC[232]
9P D-SUB Male
7 CTS
8 RTS
EH-150 RS-485 connect must short the PLC[232] port pin 7,8.