Dunham-Bush ACHDX-55 - 245TR-50Hz-Screw

This document provides specifications for Air Cooled Horizontal Rotary Screw Chillers. Key details include: - The chillers come in sizes from 55 to 245 tons and use refrigerant R407C. - Standard features include rotary screw compressors, electronic controllers, and direct drive condenser fans. - Evaporators use advanced inner-fin tube technology and meet ASME pressure vessel codes. - Air-cooled condensers have copper tubing with aluminum fins and are tested to 450 psig.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (1 vote)
877 views16 pages

Dunham-Bush ACHDX-55 - 245TR-50Hz-Screw

This document provides specifications for Air Cooled Horizontal Rotary Screw Chillers. Key details include: - The chillers come in sizes from 55 to 245 tons and use refrigerant R407C. - Standard features include rotary screw compressors, electronic controllers, and direct drive condenser fans. - Evaporators use advanced inner-fin tube technology and meet ASME pressure vessel codes. - Air-cooled condensers have copper tubing with aluminum fins and are tested to 450 psig.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

R

Form No: MS0443A


Products That Perform...By People Who Care

Air Cooled Horizontal


Rotary Screw Chillers
ACHDX Series

R407C 55 to 245 Tons

50Hz
TABLE OF CONTENTS

Page No. Page No.


Nomenclature ...................................................................... 2 Application Data ....................................................................6
Standard Features............................................................... 2 Performance Data..................................................................7
Unit Features: Evaporators............................................... 3 Physical Specifications ........................................................8
Unit Features: Advanced Controller ................................. 4 Dimensional Data .................................................................9
Unit Options......................................................................... 5 Evaporator Water Pressure Drop.......................................12
Unit Accessories ................................................................. 6 Typical Wiring Schematic ...................................................13

NOMENCLATURE

AC H DX 55 S 5 S P

Air Cooled Blank – R22


P – R407c

Horizontal Screw S- Standard


Compressor Q- Special

5 - 50Hz
DX Packaged Chiller 6 - 60Hz

S – Single Circuit
Nominal Tons D – Dual Circuit

STANDARD FEATURES
Size Range œ450 psig test pressure for condenser coils.
œ Standard unit fans - direct drive at 960 RPM
œ 12 models from 55 to 245 tons.
œ All fan motors are designed for outdoor
œStandard version available.
œRated with HFC 407c. installations.
œ Fan cycling is standard for all units. Fan speed
Compressor control is an option for low ambient application.
œCopper, hydrophilic and electro-tined coil are
œ Semi-hermetic rotary screw type at 2950 RPM. available options.
œInfinite variable slide valve unloading for precise
load matching. Electrical/Control
œCompressor cycling for maximum efficiency. œReliable Multi-function programmable electronic
controller is standard for all models.
Evaporator œ3 digits LED display with decimal point and
œ Vessels constructed in accordance to ASME sign.
CODES Sections Vlll Division I for unfired œCompressor loading/ staging based on leaving
pressure vessels. fluid temperature.
œDunham-Bush high efficiency inner-fin tubes œHigh and low pressure protection.
design for compactness and weight reduction. œCooler fluid freeze protection.
œ300 psig on refrigerant side design pressure. œStaggered starting compressors.
œ200 psig on water side design pressure. œAnti recycle timing.
œApproval Stamp available from JKKP œFan cycling.
(Malaysia), UDT (Poland), BPA, China State
œAccept remote and stop signal.
Bureau of Quality and Technical Supervision of
œCooler leaving fluid temperature.
the People’s Republic of China and ASME.
œ1” thick PE foam closed cell insulation. œDischarge and suction pressure gauges for all
circuits.
Air Side Condenser œ115V control circuit transformer standard for all
models.
œ Inner ridged copper tubes with aluminum fins.

-2-
UNIT FEATURES: EVAPORATORS

The evaporators incorporate the most advanced The CH evaporators incorporate 1/2 inch (12.7
vessel technology available today, including the mm) copper tubes brazed into tube-sheets. The
patented Inner-Finned construction of the CH and vessel is supplied with welded heads.
EX evaporators. Vessels are designed and The EX evaporators incorporate 5/8 inch
constructed to meet the requirements of the (15.9mm) copper tubes and removable heads for
ASME Code, Section Vlll, Division 1 for unfired ease of tube maintenance.
pressure vessels and are approved and certified
Vent and drain connections are included on all
by the JKKP (the Malaysian DOSH), as well as
vessels.
the Polish and the Chinese authorities.

Typical For 2 Circuit Evaporators


FLUID IN FLUID OUT

RETURN WATER FREEZE STAT “SEE PHYSICAL SPEC’S


BULB WELL BULB WELL FOR CONNECTION SIZE

INTERNAL WATER BAFFLES

REFRIGERANT REFRIGERANT
OUT IN

REMOVABLE WATER FLOW PATH


HEADS BOTH VENT AND DRAIN
ENDS

PATENTED INNER-FIN
CONSTRUCTION

Table 1 : Vessel Design Pressure


Shell & Tube Water Side Refrigerant Side
Heat Exchanger
(Evaporator) Design Pressure Test Pressure (Psig)(Kpa) Design Pressure Test Pressure (Psig)(Kpa)
(Psig)(Kpa) (Psig)(Kpa)

CH, EX 200 (1379) 260 (1793) 300 (2069) 330 (2275)

Air Side Condenser and nipples are all copper, sized for minimum
pressure drop, brazed with inert gas in the tubes
All units have direct driven propeller fans and and tested after fabrication to 450 psig.
motors. Close blade tip clearance with the fan
venturi ensures smooth, quiet operation. Partitions separate each fan section to eliminate
possible back spin. The microcomputer Vision
All air-cooled condensers are constructed with 3/8 2020i fan cycling control is able to decrease the
inch (9.5 mm) diameter copper tubes minimum ambient temperature at which the
mechanically expanded into aluminum fins for package equipment will effectively start and
maximum efficiency of heat transfer between the operate.
circulating refrigerant and air. The fins have full-
spacing collars which completely cover each tube. All unit casing is constructed with heavy-gauge
The staggered tube design improves the thermal galvanized steel sheets. Powder-coat painting is
efficiency of the coil and eliminates bypassing of applied for maximum protection and appearance.
air around the tubes. The return bends, headers

-3-
UNIT FEATURES: ADVANCED CONTROLLER

message to the next. All of these messages are


spelled out in English language on the display
terminal.
There are 15 dedicated buttons enable user to
access information, base on the security level of
the password. For more detail operation of the
DBG1 Display Terminal, please refer to the Unit
Operation Manual.
œEasily accessible measurements include:
œLeaving chilled water temperature
œLeaving chiller water temperature derivative
œEvaporator Pressure
œCondenser Pressure
œCompressor amp draw of each compressor
œCompressor elapsed run time of each
compressor
œCompressor starts status
Vision2020i a flexible and advance programmable
electronic controller designed specifically for the œOil level sensor status
applications and precise control of Dunham-Bush œWater temperature reset value
Rotary Screw compressor chillers. œWater flow switch status
The controller board is provided with a set of œExternal start/stop command status
terminals that connected to various devices such Optional entering chilled water temperature,
as temperature sensors, pressure and current leaving and entering condenser water
transducers, solenoid valves, compressors and temperature are available. With this option the
fans contactors, control relays and etc. Three operator can quickly and accurately read all
sizes of controller boards are provided to handle significant water temperatures and eliminate the
different number of input and output need for often-inaccurate thermometers. Voltage
requirements: DB*-S small board, DB*-M medium readout is also offered as an optional feature.
board and DB*-L large board.
The unit algorithm program and operating Capacity Control
parameters are stored in FLASH-MEMORY that Leaving chilled water temperature control is
does not require a back-up battery. The program accomplished by entering the water temperature
can be loaded through PC or programming key. setpoint and placing the controller in automatic
Vision2020i controller is equipped with a user control. The unit will monitor all control functions
friendly terminal with a semi-graphic display and and move the slide valve to the required operating
dedicated keys that provides easy access to the position. The compressor ramp (loading) cycle is
unit operating conditions, control set points and programmable and may be set for specific
alarm history. building requirements. Remote adjustment of the
Each unit’s controller can be programmed and leaving chilled water setpoint is accomplished
connected to the local DBLAN network that allows through either direct connection of other Dunham-
multiple units sequencing control without Bush control packages to the controller through
additional hardware. The DBLAN is local area either the RS485 long distance differential
network made up of several chillers’ controller. communications port, via terminal or modem
Note: DB* represents DB1, DB2 or DB3. connected to the RS232 communication port, or
from an external Building Automation System
Display and User Terminal supplying a simple 4 to 20mA signal. Remote
Vision2020i controller is design to work with a reset of compressor current limit may be
user friendly back-lit 132 by 64 pixels DBG1 semi- accomplished in a similar fashion.
graphic Display panel connected with controller
through telephone cable. The terminal allows System Control
carrying out all program operations. The user The unit may be started or stopped manually, or
terminal allows displaying the unit working through the use of an external signal from a
conditions, compressor run times, alarm history Building Automation System. In addition, the
and modifying the parameters. The display also controller may be programmed with seven-day
has an automatically self-test of the controller on operating cycle or other Dunham-Bush control
system start-up. Multiple messages will be packages may start and stop the system through
displayed by automatically scrolling from each inter-connecting wiring.

-4-
UNIT FEATURES: ADVANCED CONTROLLER

System Protection Remote Monitoring


The following system protection controls will The controller is complete with an optional RS485
automatically act to insure system reliability: communications card and NETVISOR software
necessary for remote monitoring and controlled
œLow suction pressure
from a PC terminal and optional phone modem.
œHigh discharge pressure
œFreeze protection With various optional add-on cards the
Vision2020i controller can also be interfaced
œLow differential pressure directly to the BMS with the standard
œLow oil level communication protocols using MODBUS,
œCompressor run error LONWORKS, BACNET MSTP as well as over IP.
œPower loss This sophisticated feature makes servicing easier
œChilled water flow loss and more convenient to the system. The
œSensor error controller as standard is additionally equipped
œCompressor over current with history files which may be used to take logs
œCompressor Anti-recycle which may be retrieved via the phone modem or
The controller will retain the latest up to 99 alarm internet connection periodically. Now owners of
multiple buildings have a simple and inexpensive
conditions complete with time of failure together
method of investigating potential problems quickly
data stamping on critical sensor readings in an and in a highly cost effective manner. Dunham-
alarm history. This tool will aid service technicians Bush has various open protocols on its controller
in troubleshooting tasks enabling downtime and to allow direct interface with Building
nuisance trip-outs to be minimized. Management Systems.

UNIT OPTIONS
Options Installed At The Factory - Protects against low or high incoming voltage
conditions as well as phase loss, phase
œ Controller (Vision 2020i) - A standard feature reversal and phase imbalance by opening the
for all models. control circuit. It is an automatic reset device.
œController monitoring of return chilled water and œ Electronic Expansion Valves - For more precise
leaving chilled water temperature. control over a wider range of operation. Ideal
œ Heat reclaim condensers (desuperheaters) are for low ambient and wide operating ambient
available for special applications. temperature range applications.
œ Unit mounted disconnect for each compressor œ Gauges - Includes suction and discharge
and control circuit with fuses and fuse block for pressure gauges for all unit models. These are
400 to 575 volt applications. not necessary with the controller.
œ Copper Condenser Fins- Copper fins offer œ Low Ambient Controls (LAC option) [Kindly
maximum corrosion protection for severe refer to Low Ambient Operation/ Freeze
conditions. In more corrosive environments, Protection].
hydrophilic or electro-tinned fins would be more œ Compressor Start Counter - One start counter
appropriate. provided for each compressor, located inside
œ Indicator Light Set - Provides indicator lights for the control panel.
control power, motor overload, high motor œ Compressor Elapsed Time Meter - One elapsed
temperature and alarm status. time meter to register run hours per
œ Hot Gas Bypass - Consists of hot gas bypass compressor, located inside the control panel.
regulator(s) and solenoid valve(s) for each œ Three Phase Ammeter - Single analog ammeter
circuit for applications with a minimum load with a 3 phase selector switch for indication,
which may dip below the unit’s minimum located inside the control panel.
unloaded capacity.
œ Three Phase Voltmeter - Single analog
œ Control Circuit Transformer - appropriate KVA voltmeter installed with a 3 phase selector
rating to power the 115/1/50 control circuit and switch for indication, located inside the control
compressor oil heaters off the service voltage. panel.
œ Chiller Heater Transformer - Appropriate KVA œ Entering Fluid Temperature Sensor -
rating to power the 115/1/50 evaporator vessel Temperature sensor and bulb installed in
heater tape. evaporator inlet connection to supplement the
œ 115V Convenience Outlet - Duplex outlet standard leaving (outlet) fluid temperature
located inside the control panel and protected sensor.
by a 15 amp fuse. œ Condenser coil guard protects the condenser
œ Over/Undervoltage and Phase Protection Relay coils from harsh environments.
-5-
UNIT ACCESSORIES

Accessories shipped unmounted of installation, these rubber, one-piece, molded


œ Water Flow Switch - Paddle type field isolators are applicable for most installations.
adjustable flow switch available for all units, œ Spring Isolators - These housed spring
installed into the unit safety circuit so that the assemblies have a neoprene friction pad at the
package will remain off until there is water flow. bottom to prevent the passage of noise, and a
Helps to prevent evaporator from freezing. spring locking levering bolt at the top. Neoprene
Vapor-proof enclosure, for use on water or inserts prevent contact between the steel upper
glycol systems. The flow switch is to be shipped and lower housings. Suitable for more critical
loose and installed at site. applications as compared to rubber-in-shear
œ Rubber-in-shear Isolators - Designed for ease isolators.

APPLICATION DATA
Low Ambient Operation / Freeze minimum ambient temperature. Use only glycol
solutions approved for the particular heat
Protection exchanger duty. The use of automotive anti-
The heater strip must be wrapped around the freeze is not recommended because they have
evaporator shell as well as the water piping. If the short-lived inhibitors and fouling of the vessels will
unit is required to operate at an ambient occur. If the equipment is exposed to freezing
temperature below 55°F (12.8°C), solenoid valves temperatures and not in used, the vessels and
would have to be installed along the coil headers piping should be drained.
with the exception of the last running coil. If the If the equipment is being used for operating
unit is required to operate below 32°F (0°C). Both conditions below 42°F (5.5°C) with standard
the solenoid coil control and VFD would have to vessels or below 40°F (4.4°C) with optional 40°F
be incorporated. An additional liquid receiver, (4.4°C) vessels, glycol should be used to prevent
wrapped with the heater strip, would have to be damage due to freezing. The freeze protection
added for each refrigerant circuit if the required level should be 20°F (11°C) lower than the
operating ambient temperature ranges between leaving brine temperature. The use of glycol
0°F (-17.8°C) and 20°F (-6.7°C). In addition to the penalizes the causes a performance as shown in
accessories mentioned, an additional electronic Table 4 for ethylene glycol and Table 5 for
expansion valve is required for each refrigerant propylene glycol and needs to be considered in
circuit if the operating ambient goes below 0°F the unit selection procedure.
(-17.8°C). Condenser pressure regulators would
have to be incorporated as well to regulate the Table 4 : Ethylene Glycol
head pressure. The minimum operating ambient
temperature is -20°F (-28.9°F). For low ambient % E. G. Freeze C1 K1 G1 P1
By Point Capacity kW Flow P.D.
applications, kindly consult factory as the unit Weight Factor Rate Factor Factor
°F °C
would have to be redesigned to suit the
10 26.2 -3.2 0.995 0.998 1.019 1.050
customer’s specific needs.
15 22.4 -5.3 0.991 0.997 1.030 1.083
20 17.8 -7.9 0.988 0.996 1.044 1.121
Desuperheaters 25 12.6 -10.8 0.984 0.995 1.060 1.170
A hot gas desuperheater can be factory supplied 30 6.7 -14.1 0.981 0.994 1.077 1.219
35 0.0 -17.8 0.977 0.992 1.097 1.275
for field installation. Tees in refrigerant lines with
40 -8.0 -25.8 0.973 0.991 1.116 1.331
shut off valves can be supplied. Kindly consult
45 -17.5 -27.5 0.968 0.990 1.138 1.398
factory for further details. 50 -28.9 -33.8 0.964 0.989 1.161 1.466

Water Circuit Table 5 : Propylene Glycol


Constant water flow required with a minimum of 3 % P. G. Freeze C2 K2 G2 P2
gallons per ton ( 3.3 liters / kWo ) increasing to 10 By Point Capacity kW Flow P.D.
Weight Factor Rate Factor Factor
gallons (11 liters) for process, low load °F °C
applications with small temperature range and/or 10 26.1 -3.3 0.988 0.994 1.005 1.019
vastly fluctuating load conditions. 15 22.8 -5.1 0.984 0.992 1.008 1.031
20 19.1 -7.2 0.978 0.990 1.010 1.051
25 14.5 -9.7 0.970 0.988 1.015 1.081
Glycol Freeze Protection 30 8.9 -12.8 0.962 0.986 1.021 1.120
If the chiller or fluid piping may be exposed to 35 2.1 -16.6 0.952 0.981 1.033 1.163
temperatures below freezing temperature, then 40 -6.4 -21.3 0.943 0.978 1.043 1.213
glycol protection is recommended. The re- 45 -16.6 -27.0 0.933 0.975 1.057 1.269
commended protection is 15°F (8.3°C) below the 50 -28.9 -33.8 0.924 0.972 1.073 1.326

-6-
PERFORMANCE DATA R407c

CHILLER AMBIENT AIR TEMPERATURE °F


LWT MODEL 85.00 95.00 105.00 115.00
°F ACHDX TONS KWO KWI TONS KWO KWI TONS KWO KWI TONS KWO KWI
55S-5SP 55.6 195.7 62.8 49.9 175.3 72.4 43.5 153.2 84.0 37.2 131.0 95.6
70S-5SP 71.7 252.1 75.6 64.2 225.9 87.0 56.1 197.4 100.6 48.0 168.8 114.3
90S-5SP 90.7 318.9 97.3 81.3 285.8 112.1 71.0 249.7 129.8 60.7 213.6 147.4
105S-5SP 106.2 373.6 111.4 95.2 334.8 128.2 83.2 292.5 148.3 71.1 250.2 168.4
120S-5SP 124.1 436.5 131.6 111.2 391.1 151.5 97.2 341.7 175.3 83.1 292.3 199.1
75D-5SP 72.8 255.9 82.7 65.2 229.3 95.5 57.0 200.3 110.5 48.7 171.3 125.6
40.00 85D-5SP 84.5 297.3 93.7 75.7 266.4 107.8 66.2 232.7 125.0 56.6 199.0 142.3
115D-5SP 111.3 391.3 125.6 99.7 350.7 144.8 87.1 306.3 168.0 74.5 261.9 191.1
140D-5SP 143.4 504.2 151.1 128.5 451.9 174.0 112.2 394.8 201.3 96.0 337.6 228.5
180D-5SP 181.4 637.9 194.6 162.5 571.7 224.2 142.0 499.4 259.5 121.5 427.1 294.8
210D-5SP 212.5 747.2 222.9 190.4 669.7 256.4 166.3 585.0 296.5 142.3 500.3 336.7
245D-5SP 248.2 872.9 263.2 222.4 782.3 303.0 194.3 683.4 350.6 166.2 584.6 398.3
55S-5SP 58.2 204.8 63.1 52.3 184.0 72.7 45.9 161.3 84.1 39.4 138.7 95.5
70S-5SP 75.0 263.9 76.0 67.4 237.1 87.3 59.1 207.9 100.9 50.8 178.7 114.6
90S-5SP 94.9 333.8 97.8 85.3 299.9 112.4 74.8 263.0 130.0 64.3 226.1 147.7
105S-5SP 111.2 391.1 111.9 99.9 351.4 128.7 87.6 308.1 148.7 75.3 264.8 168.7
120S-5SP 129.9 456.8 132.2 116.7 410.5 152.0 102.3 359.9 175.7 88.0 309.3 199.4
75D-5SP 76.2 267.9 83.1 68.4 240.7 95.6 60.0 211.0 110.7 51.6 181.4 125.8
42.00 85D-5SP 88.5 311.1 94.1 79.5 279.5 108.2 69.7 245.1 125.2 59.9 210.7 142.3
115D-5SP 116.4 409.5 126.2 104.6 368.0 145.4 91.8 322.7 168.2 78.9 277.4 190.9
140D-5SP 150.0 527.7 151.9 134.8 474.2 174.6 118.2 415.8 201.9 101.6 357.3 229.1
180D-5SP 189.8 667.6 195.6 170.6 599.8 224.8 149.6 526.0 260.1 128.6 452.1 295.4
210D-5SP 222.4 782.1 223.8 199.8 702.7 257.3 175.2 616.2 297.3 150.6 529.7 337.3
245D-5SP 259.8 913.7 264.4 233.4 820.9 304.0 204.7 719.8 351.4 175.9 618.7 398.9
55S-5SP 60.9 214.2 63.4 54.9 192.9 72.9 48.3 169.7 84.3 41.7 146.6 95.6
70S-5SP 78.5 276.0 76.4 70.7 248.6 87.6 62.2 218.7 101.1 53.7 188.9 114.7
90S-5SP 99.3 349.2 98.3 89.4 314.5 112.9 78.7 276.7 130.3 67.9 239.0 147.8
105S-5SP 116.3 409.0 112.7 104.8 368.4 129.2 92.2 324.2 149.1 79.6 279.9 169.0
120S-5SP 135.9 477.8 133.0 124.4 437.4 154.4 107.7 378.7 176.1 93.0 327.0 199.6
75D-5SP 79.7 280.2 83.5 73.1 257.0 96.6 63.1 222.1 110.9 54.5 191.8 125.8
44.00 85D-5SP 92.5 325.5 94.5 85.1 299.3 109.8 73.3 257.9 125.6 63.3 222.7 142.7
115D-5SP 121.8 428.4 126.8 112.3 394.8 145.9 96.5 339.5 168.6 83.4 293.2 191.3
140D-5SP 157.0 552.0 152.9 141.4 497.2 175.2 124.4 437.5 202.3 107.4 377.8 229.3
180D-5SP 198.6 698.3 196.6 178.8 629.0 225.8 157.4 553.4 260.7 135.9 477.9 295.6
210D-5SP 232.6 818.1 225.4 209.5 736.8 258.3 184.3 648.3 298.1 159.2 559.8 337.9
245D-5SP 271.7 955.6 266.0 244.7 860.7 305.2 215.3 757.3 352.2 185.9 653.9 399.3
55S-5SP 63.7 223.9 63.8 57.5 202.1 73.2 50.7 178.4 84.5 44.0 154.7 95.7
70S-5SP 82.0 288.5 77.0 74.1 260.5 88.0 65.4 229.9 101.4 56.7 199.4 114.9
90S-5SP 103.8 365.0 99.0 93.7 329.5 113.3 82.7 290.8 130.6 71.7 252.2 148.0
105S-5SP 121.6 427.6 113.6 109.8 386.0 129.7 96.9 340.8 149.5 84.0 295.5 169.2
120S-5SP 142.0 499.5 134.1 128.2 450.9 153.2 113.2 398.0 176.6 98.1 345.1 200.0
75D-5SP 83.3 292.9 83.9 75.2 264.4 96.4 66.4 233.4 111.3 57.5 202.4 126.2
46.00 85D-5SP 96.7 340.2 95.1 87.3 307.1 109.0 77.1 271.1 125.8 66.9 235.1 142.7
115D-5SP 127.3 447.8 127.6 114.9 404.2 146.4 101.5 356.9 169.0 88.0 309.5 191.5
140D-5SP 164.1 577.1 154.1 148.1 520.9 176.0 130.7 459.8 202.9 113.4 398.7 229.7
180D-5SP 207.6 730.0 198.0 187.4 659.0 226.6 165.4 581.7 261.3 143.4 504.4 296.0
210D-5SP 243.2 855.3 227.2 219.5 772.1 259.3 193.8 681.5 298.9 168.0 591.0 338.5
245D-5SP 284.1 999.0 268.1 256.4 901.9 306.3 226.3 796.1 353.2 196.3 690.3 400.0
55S-5SP 66.5 233.9 64.1 60.2 211.6 73.5 53.3 187.4 84.8 46.4 163.1 96.0
70S-5SP 85.7 301.5 77.6 77.5 272.7 88.4 68.7 241.5 101.7 59.8 210.2 115.1
90S-5SP 108.4 381.3 99.8 98.1 345.0 113.8 86.8 305.4 131.1 75.6 265.9 148.5
105S-5SP 127.0 446.8 114.6 114.9 404.2 130.2 101.7 357.8 149.9 88.6 311.5 169.6
120S-5SP 148.4 521.9 135.1 134.2 472.1 153.9 118.9 418.0 177.2 103.5 363.9 200.5
75D-5SP 87.0 306.0 84.5 78.7 276.8 96.8 69.7 245.1 111.5 60.7 213.3 126.2
48.00 85D-5SP 101.1 355.4 95.6 91.4 321.5 109.6 81.0 284.7 126.2 70.5 247.9 142.9
115D-5SP 133.0 467.9 128.2 120.3 423.3 147.0 106.6 374.8 169.5 92.8 326.3 192.1
140D-5SP 171.4 602.9 155.2 155.1 545.4 176.8 137.3 482.9 203.4 119.5 420.4 230.1
180D-5SP 216.9 762.7 199.5 196.2 689.9 227.6 173.7 610.9 262.2 151.2 531.8 296.9
210D-5SP 254.1 893.5 229.1 229.8 808.3 260.5 203.5 715.7 299.9 177.2 623.0 339.3
245D-5SP 296.8 1,043.8 270.3 268.5 944.2 307.7 237.7 836.0 354.4 206.9 727.8 401.0
55S-5SP 69.5 244.3 64.6 63.0 221.4 73.9 55.9 196.6 85.1 48.9 171.8 96.2
70S-5SP 89.5 314.8 78.3 81.1 285.3 88.8 72.0 253.3 102.1 62.9 221.3 115.4
90S-5SP 113.2 398.2 100.6 102.6 360.9 114.4 91.1 320.5 131.5 79.6 280.0 148.7
105S-5SP 132.7 466.5 115.4 120.2 422.9 130.9 106.8 375.5 150.4 93.3 328.0 169.9
120S-5SP 155.0 545.0 136.2 140.5 494.0 154.6 124.7 438.6 177.8 109.0 383.2 200.9
75D-5SP 90.9 319.6 85.1 82.4 289.6 97.2 73.1 257.1 111.9 63.9 224.6 126.6
50.00 85D-5SP 105.5 371.2 96.4 95.7 336.4 110.0 84.9 298.8 126.6 74.2 261.1 143.3
115D-5SP 138.9 488.6 129.2 125.9 442.8 147.8 111.8 393.2 170.1 97.7 343.6 192.5
140D-5SP 179.0 629.6 156.6 162.3 570.7 177.6 144.1 506.7 204.2 125.9 442.6 230.9
180D-5SP 226.5 796.5 201.3 205.3 721.9 228.7 182.2 641.0 263.0 159.2 560.0 297.3
210D-5SP 265.3 933.1 230.9 240.5 845.8 261.9 213.5 750.9 300.9 186.6 656.1 339.9
245D-5SP 309.9 1,089.9 272.4 280.9 988.0 309.3 249.4 877.2 355.5 217.9 766.4 401.8
LEGEND:
LWT : Leaving Chilled Water Temperature KWI : Compressor Power Input In kW TON : Cooling Capacity In Ton. KWO: Cooling Capacity In KW

-7-
PHYSICAL SPECIFICATIONS R407c

MODEL ACHDX 55S-5SP 70S-5SP 90S-5SP 105S-5SP 125S-5SP

COMPRESSOR
MODEL (QTY) HSC 1509 x 1 HSC 1512 x 1 HSC 1709 x 1 HSC 1711 x 1 HSC 1811 x 1
RPM 2950 2950 2950 2950 2950
MIN. % UNIT CAPACITY REDUCTION 25% 25% 25% 25% 25%
EVAPORATOR
MODEL (QTY) HDJ04d(1) HDL04c(1) XDM09e(1) XDN09e(1) XDN10e(1)
WATER CONNECTOR INCH [MM] 4 [101.6] 4 [101.6] 5 [127] 5 [127] 6 [152.4]
NOM. WATER FLOW / P D GPM/ FT IN WG 127.7/19.5 160.4/8.7 204.9/12.5 236.1/22.1 298.8/17.8
MIN/ MAX WATER FLOW GPM 68.5/205 100.7/301.5 140.3/420 119.7/358 174.5/522.6
MIN/ MAX WATER PD FT IN WG 6.4/45.5 3.8/26.9 6.35/44.8 6.6/46.4 6.8/48.3
CONDENSER
COIL ROWS DEEP/ TOTAL FA (SQ.FT) 3/81.3 4/81.3 3/121.9 4/121.9 3/162.6
NO. OF FAN 4 4 6 6 8
FAN DIA. MM 800 800 800 800 800
MOTOR HP (QTY) 1.5(4) 1.5(4) 1.5(6) 1.5(6) 1.5(8)
FLA, AMP (QTY) 3.2(4) 3.2(4) 3.2(6) 3.2(6) 3.2(8)
TOTAL CFM 40480 42400 69600 65400 91440
MIN. AMBIENT TEMP. (F) AT MIN. LOAD 55 55 55 55 55
ELECTRICAL
NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
UNIT RLA A 130 156 204 232 272
UNIT MAX. INRUSH A 304 408 443 576 661
GENERAL
UNIT LENGTH INCH[MM] 98 [2489] 98 [2489] 139.5 [3543] 139.5 [3543] 181.5 [4610]
UNIT WIDTH INCH[MM] 88 [2235] 88 [2235] 88 [2235] 88 [2235] 88 [2235]
UNIT HEIGHT INCH[MM] 85 [2159] 85 [2159] 88.5 [2248] 88.5 [2248] 88.5 [2248]
SHIPPING WEIGHT KG[LBS] 2590 [5710] 2923 [6444] 4135 [9117] 4343 [9575] 5001 [11025]
OPERATING WEIGHT KG[LBS] 2607 [5748] 2967 [6541] 4290 [9457] 4497 [9915] 5211 [11489]
OPERATING CHARGE R407C KG[LBS] 55 [121] 70 [154] 90 [198] 105 [231] 125 [275]

MODEL ACHDX 75D-5SP 85D-5SP 115D-5SP 140D-5SP 180D-5SP 210D-5SP 245D-5SP

COMPRESSOR
MODEL (QTY) HSC 1309 (2) HSC 1311 (2) HSC 1509 (2) HSC 1512 (2) HSC 1709 (2) HSC 1711 (2) HSC 1811 (2)
RPM 2950 2950 2950 2950 2950 2950 2950
MIN. % UNIT CAPACITY REDUCTION 12.5% 12.5% 12.5% 12.5% 12.5% 12.5% 12.5%
EVAPORATOR
MODEL (QTY) XDK09f(1) XDM09e(1) XDM12e(1) XDN12e(1) XDP12e(1) XFQ10d(1) XFQ12e(1)
WATER CONNECTOR INCH/ [MM] 4/[101.6] 5/[127] 5/[127] 6/[152.4] 8/[203.2] 10/[254] 10/[254]
NOM. WATER FLOW/ P D GPM / FT IN WG 167.2/14.4 194.7/11.4 269.7/16.8 323.1/18.7 407.4/15.9 477.2/11.21 555.5/20.5
MIN/ MAX WATER FLOW GPM 108.8/325.8 140.3/420 168.9/506.5 190.8/570.6 213.1/637.9 273.4/819.3 240.3/720.8
MIN/ MAX WATER PD FT IN WG 6.71/47 6.35/44.8 7.3/51.8 7.3/51.6 5.1/35.3 4.2/29.3 4.7/32.6
CONDENSER
COIL ROWS DEEP/ TOTAL FA (SQ.FT) 3/121.9 3/121.9 3/162.6 4/162.6 4/203.2 3/282.3 3/329.4
NO. OF FAN 6 6 8 8 10 12 14
FAN DIA. MM 800 800 800 800 800 800 800
MOTOR HP (QTY) 1.5(6) 1.5(6) 1.5(8) 1.5(8) 1.5(10) 1.5(12) 1.5(14)
FLA, AMP (QTY) 3.2(6) 3.2(6) 3.2(8) 3.2(8) 3.2(10) 3.2(12) 3.2(14)
TOTAL CFM 62880 60720 92800 84800 106000 142200 165900
MIN. AMBIENT TEMP. (F) AT MIN. LOAD 55 55 55 55 55 55 55
ELECTRICAL
NOM. VOLTAGE 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
UNIT RLA A 173 194 259 319 405 459 543
UNIT MAX. INRUSH A 290 361 433 565 642 807 929
GENERAL
UNIT LENGTH INCH[MM] 139.5 [3543] 139.5 [3543] 181.5 [4610] 181.5 [4610] 223.5 [5677] 265.5 [6744] 307.5 [7811]
UNIT WIDTH INCH[MM] 88 [2235] 88 [2235] 88 [2235] 88 [2235] 88 [2235] 88 [2235] 88 [2235]
UNIT HEIGHT INCH[MM] 88.5 [2248] 88.5 [2248] 88.5 [2248] 88.5 [2248] 88.5/[2248] 96 .5 [2451] 96 .5 [2451]
SHIPPING WEIGHT KG[LBS] 4000 [8818] 4126 [9095] 4659.6 [10273] 5627 [12405] 6725 [14825] 8062 [17774] 9073 [20002]
OPERATING WEIGHT KG[LBS] 4095 [9027] 4263 [9399] 4791.3 [10563] 5851 [12910] 6997 [15425] 8334 [18373] 9369 [20654]
OPERATING CHARGE R407C KG[LBS] 75 [165] 85 [187] 115 [254] 140 [309] 180 [397] 210 [463] 245 [540]
Notes: 1.) LRA is across-the-line (IXL) starting amps.
2.) Minimum Circuit Ampacity (MCA) based on 125% of the largest compressor RLA plus 100% of the other compressor RLA and fan circuit amps.
3.) Maximum Fuse Size (MFS) based on 225% of the largest compressor RLA plus 100% of the other compressor RLA and fan circuit amps.
4.) Voltage range: 414V minimum to 506V maximum.

-8-
DIMENSIONAL DATA

ACHDX 55S-5SP, 70S-5SP

ACHDX 90S-5SP, 105S-5SP

ACHDX 125S-5SP

Note All dimensions are in inches[mm].

-9-
DIMENSIONAL DATA

ACHDX 75D-5SP, 85D-5SP

ACHDX 115D-5SP, 140D-5SP

ACHDX 180D-5SP

Note All dimensions are in inches[mm].

- 10 -
DIMENSIONAL DATA

ACHDX 210D-5SP

ACHDX 245D-5SP

Note All dimensions are inches[mm].

- 11 -
EVAPORATOR WATER PRESSURE DROP

SINGLE CIRCUIT
100

ACHDX 55S-5SP
ACHDX 70S-5SP
ACHDX 90S-5SP
.

ACHDX 105S-5SP
ACHDX 125S-5SP
PRESSURE DROP - FT IN WG

10

1
10 100 1000
CHILLED WATER FLOW RATE - GPM

DUAL CIRCUIT
100

ACHDX 75D-5SP
ACHDX 85D-5SP
ACHDX 115D-5SP
.

ACHDX 140D-5SP
ACHDX 180D-5SP
PRESSURE DROP - FT IN WG

ACHDX 210D-5SP
ACHDX 245D-5SP

10

1
100 1000
CHILLED WATER FLOW RATE - GPM

- 12 -
TYPICAL WIRING SCHEMATIC (2 Compressors)

- 13 -
TYPICAL WIRING SCHEMATIC (2 Compressors)

- 14 -
TYPICAL WIRING SCHEMATIC (2 Compressors)

- 15 -
TYPICAL WIRING SCHEMATIC (2 Compressors)

07-06