Ahu-Isolation Room Catalogue

This document provides specifications for an HVAC system for an isolation room, including an air handling unit, outdoor unit, and exhaust fan unit. The air handling unit has features like double wall panels, magnehelic pressure drop monitoring, and evaporator coils. The outdoor unit uses hermetic scroll compression and protection devices. The exhaust fan unit includes HEPA and pre-filters and can achieve over 2500 m3/h of airflow. The system is designed to maintain negative room pressure between -5 to -15Pa and control temperature and humidity for isolation.

Uploaded by

-Tokusatsu Man-
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
85 views2 pages

Ahu-Isolation Room Catalogue

This document provides specifications for an HVAC system for an isolation room, including an air handling unit, outdoor unit, and exhaust fan unit. The air handling unit has features like double wall panels, magnehelic pressure drop monitoring, and evaporator coils. The outdoor unit uses hermetic scroll compression and protection devices. The exhaust fan unit includes HEPA and pre-filters and can achieve over 2500 m3/h of airflow. The system is designed to maintain negative room pressure between -5 to -15Pa and control temperature and humidity for isolation.

Uploaded by

-Tokusatsu Man-
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

STANDARD FEATURE

Panels Air Handling Unit


- 25mm double wall
high density 45 kg/m3 Magnehelic
- Injecting polyurethane - Air Pressure Drop
- Thickness 25mm or 50 mm Monitoring

Casing Flatform
- Frame work
aluminum profiles
- Thermal Break System
- Joint nylon corner

Airfilter
- G4 (Prefilter)
Washable type (Eff.30-35%)
- F8 (Medium Filter)
V Bank (eff.95-97%)
Blower
- Double inlet centrifugal fans Evaporator Coil
- Accordance to AMCA Standard - Aluminum finned
- Inner Grooved
Motor Copper tubes and
- Installed in 3 phase Galvanized casing
with 380 V-50 Hz
- Class F Insulation
and IP 55 Protection

Exhaust Fan unit


Panels
- 25mm double wall high density 45 kg/m3

H VAC S Y S T E M
- Injecting polyurethane
- Thickness 25mm or 50 mm
Casing Flatform
- Frame work
aluminum profiles
- Thermal Break System

f o r I S O L AT I O N RO O M - Joint nylon corner

Blower
- Double inlet centrifugal fans
- Accordance to AMCA Standard
Airfilter
- G4 – Prefilter
Washable type (Eff.30-35%)
Motor
- Installed in 3 phase
with 380 V-50 Hz
- Class F Insulation
Magnehelic and IP 55 Protection
- Air Pressure Airfilter
Drop Monitoring - H13 (Hepa Filter)
(eff.99.99%)

CONTROL
• Fan Speed Control
All the motor using Variable Speed Drive (VSD),
easy balancing between Air Handling Unit and Exhaust Fan,
make room pressure constant.

www.aicoolonline.com
SPESIFICATION DRAWING
AHU SUPPLY
MODEL AHU SUPPLY DFE 01D.PMF.VSD.ISO
Cooling Capacity kW 32.2
Heating Capacity kW 6.8
Backup heater kW 5
Refrigerant R407C
Airflow m3/h 1,800
Eksternal Static Pressure Pa 350
Power Supply V/Ph/Hz 380/3/50
Power Consumption Total kW 6.1
Rated Ampere Total A 10.55
Approx. Weight kg 300
Filter Pre, Medium Filter
Pre Filter G4
Qty pcs 1 OUTDOOR UNIT
Dimension inchi 24x24x2
Medium Filter F8
Qty pcs 1
Dimension inchi 24x24x12
MODEL OU DCU 102
Compressor Type Hermetic Scroll
Phase Protector, Thermal Overload Relay, High & Low
Protection Device
Pressure Control, Internal Temperature Protection
Compressor Quantity unit 1
Power Supply V/Ph/Hz 380/3/50
Power Consumption Total kW 8.82
Rated Ampere Total A 16.23
Approx. Weight kg 190

MODEL EXHAUST FAN UNIT EF 01.PHF.VSD.ISO


Airflow m3/h 2,520
EXHAUST FAN UNIT
Eksternal Static Pressure Pa 300
Power Supply V/Ph/Hz 380/3/50
Design Reference :
Power Consumption Total kW 1.1
Pedoman Teknis Ruang Isolasi, Kemenkes 2015
Rated Ampere Total A 2.55 Design Specification based on :
Approx. Weight kg 250 2
- Room area 20~30m with 3m height and 25x ACH
- Bigger room can use double system or more
Filter Pre, HEPA Filter Operating Condition :
Pre Filter G4 - Pressure Room Design : Negative (-5 to -15Pa)
Qty pcs 1 - Target Room Condition :
o
Temperature : 24 to 26 C
Dimension inchi 24x24x2 Humidity : 40 to 60% RH
HEPA Filter H-13 o
- Ambient Design @35 C/65%RH
Qty pcs 1
Dimension inchi 24x24x12

www.aicoolonline.com