Liebert NXL Ups Installation Manual 500 750kva
Liebert NXL Ups Installation Manual 500 750kva
NXL™ UPS
Installation Manual
500 kVA – 750 kVA, 0.9 PF, 60 Hz, Three-phase, Single-module and Mulit-module
The information contained in this document is subject to change
without notice and may not be suitable for all applications. While
every precaution has been taken to ensure the accuracy and
completeness of this document, Vertiv assumes no responsibility
and disclaims all liability for damages resulting from use of this
information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods,
tools, and materials to be used in performing procedures not
specifically described in this document.
If you encounter any installation or operational issues with your product, check the pertinent
section of this manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.VertivCo.com/en-us/support/ for additional assistance.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.0 MECHANICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Environmental Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.1 UPS Room . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3.2 Storing the UPS and Batteries for Delayed Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4 Positioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.4.1 Moving the Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.2 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.3 Raised-Floor Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.4 Kick Plate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4.5 Special Considerations for 1+N Parallel Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.5 System Composition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.6 Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.0 UPS ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1 External Protective Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.2 Power Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.3 Sizing the Input Breaker feeding a Liebert® NXL™ UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3.1 Power Cable Connection Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.4 Control Cable and Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4.1 Dry Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.2 Multi-Module Communication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.3 Remote Input Breaker (RIB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.4.4 Inverter Output Breaker (IOB) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
2.5 Digital LBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
2.6 Configuring Neutral and Ground Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6.1 Four-Wire Input connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6.2 Three-Wire Input connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.6.3 Preferred Grounding Configuration, Battery Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6.4 Multi-Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.6.5 High Resistance Ground Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.7 Grounding Diagrams, Single- and Multi-Module Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
3.0 OPTIONAL EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.1 Single-Module System Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
3.1.1 Matching Maintenance Bypass Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.2 Battery Temperature Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.3 Matching Liebert® NXL™ Battery Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.4 Matching Module Battery Disconnect—MBD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.5 Load Bus Synch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.1.6 Remote Alarm Status Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
FIGURES
Figure 1 Cabinet arrangement—Liebert NXL, battery cabinets, maintenance bypass cabinet.
6
Figure 2 Cabinet EMI plates - 625kVA and 750kVA only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 3 Kick plate and filter locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 4 Low-voltage cable installation—top entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Figure 5 External Interface Board connections layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 6 Inter-Module Communication Board wiring diagram—Multi-modules . . . . . . . . . . . . . . 12
Figure 7 Remote Input Breaker diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 8 Remote Output Breaker diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 9 Inter-Module Communication Board wiring diagram—Digital LBS. . . . . . . . . . . . . . . . . . 16
Figure 10 Grounding diagram, three-wire single-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 11 Grounding diagram, four-wire single-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 12 Grounding diagram, three-wire multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 13 Grounding diagram, four-wire multi-module system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 14 Control wiring, Programmable Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Figure 15 Programmable relay board dialog box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Figure 16 Input contact isolator dialog box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Figure 17 Optional Input Contact Isolator Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
Figure 18 Main components, 500kVA Liebert NXL SMS and 1+N multi-module unit with static
bypass26
Figure 19 Outline drawing, Liebert NXL 500kVA UPS SMS and 1+N multi-module unit with stat-
ic
bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 20 Input terminal details, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit with
static
bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Figure 21 Output terminal details, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit
with
static bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Figure 22 Base drawing, Liebert NXL 500kVA UPS, SMS and 1+N multi-module unit with static
bypass. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Figure 23 Field connections, shipping split 500kVA Liebert NXL, multi-module or SMS with
static
bypass, Page 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 24 Field connections, shipping split 500kVA Liebert NXL, multi-module or SMS with
static
bypass, Page 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
TABLES
Table 1 UPS input dry contacts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Table 2 UPS control contacts with global maintenance bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 3 UPS control contacts to remote status panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 4 UPS control contacts with battery cabinet or module battery disconnect . . . . . . . . . . 11
Table 5 Parallel from UPS module Inter-Module Communication Board to other Inter-Module
Communication Board in system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 6 RIB UV coil, aux. contacts from UPS RIB CB interface board to remote CB1 . . . . . . . . . 14
Table 7 Remote IOB contacts from remote breaker to UPS IOB CB interface board . . . . . . . . . 15
WARNING
Risk of electrical shock. Can cause personal injury or death.
This UPS has several circuits that are energized with high DC as well as AC voltages. Check
for voltage with both AC and DC voltmeters before working within the UPS. Check for
voltage with both AC and DC voltmeters before making contact.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should be involved in installing the UPS or preparing the UPS for
installation. When performing maintenance with any part of the equipment under power,
service personnel and test equipment should be standing on rubber mats.
In case of fire involving electrical equipment, use only carbon dioxide fire extinguishers or
those approved for use in fighting electrical fires.
Extreme caution is required when performing installation and maintenance.
Special safety precautions are required for procedures involving handling, installation and
maintenance of the UPS system. Observe all safety precautions in this manual before
handling or installing the UPS system. Observe all precautions in the Operation and
Maintenance Manual, SL-25425, before as well as during performance of all maintenance
procedures. Observe all DC safety precautions before working on or near the DC system.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or
death.
Exercise extreme care when handling UPS cabinets to avoid equipment damage or injury
to personnel. The UPS module weight is up to 13,800lb. (6260kg).
Locate center of gravity symbols and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from
vertical at all times.
Slots at the base of the module cabinets are intended for forklift use. Base slots will support
the unit only if the forks are completely beneath the unit.
Read all of the following instructions before attempting to move, lift, or remove packaging
from unit, or prepare unit for installation.
NOTE
Materials sold hereunder cannot be used in the patient vicinity (e.g., use where UL, cUL or
IEC 60601-1 is required). Medical applications such as invasive procedures and electrical life
support equipment are subject to additional terms and conditions.
NOTICE
This unit complies with the limits for a Class A digital device, pursuant to Part 15 Subpart J of the FCC
rules. These limits provide reasonable protection against harmful interference in a commercial
environment. This unit generates, uses and radiates radio frequency energy and, if not installed and used
in accordance with this instruction manual, may cause harmful interference to radio communications.
Operation of this unit in a residential area may cause harmful interference that the user must correct at
his own expense.
WARNING
Risk of electrical shock. Can cause injury or death.
Special care must be taken when working with the batteries associated with this
equipment. When they are connected together, the battery terminal voltage will exceed
400VDC and is potentially lethal.
NOTE
All equipment not referred to in this manual is shipped with details of its own mechanical and
electrical installation.
NOTICE
Three-phase input supply required.
The standard Liebert® NXL™ UPS is suitable for connection to three-phase, four-wire (+ Earth) TN-C, TN-
S, IT-G or IT-IG, or three-phase, three-wire plus ground IT-UG.
If the unit is used with an IT power system, a 4-pole disconnect device must be included as part of
building installation.
NOTICE
Do not apply electrical power to the UPS equipment before the arrival of the commissioning engineer.
1.4 Positioning
The cabinet is structurally designed to handle lifting from the base.
Access to the power terminals, auxiliary terminal blocks and power switches is from the front.
The door can be opened to give access to the power connection bars, auxiliary terminal blocks
and power isolators. Front door can be opened at 180 degrees, and interior doors can be removed
for more flexibility in installations.
NOTE
The UPS must be placed a solid surface. There must be no openings in the surface except those
required for conduit landing areas. All provided kick plates must be installed.
WARNING
Risk of heavy unit falling over. Improper handling can cause equipment damage, injury or
death.
Because the weight distribution in the cabinet is uneven, use extreme care while handling
and transporting. Take extreme care when handling UPS cabinets to avoid equipment
damage or injury to personnel.
The UPS module weight is up to 13,800lb. (6260kg).
Locate center of gravity symbols and determine unit weight before handling each
cabinet. Test lift and balance the cabinets before transporting. Maintain minimum tilt from
vertical at all times.
1.4.2 Clearances
The Liebert® NXL™ has no ventilation grilles at either side or at the rear of the UPS. Clearance
around the front of the equipment should be sufficient to enable free passage of personnel with
the doors fully opened. It is important to leave a distance of 24in (610mm) between the top of the
UPS and any overhead obstacles to permit adequate circulation of air coming out of the unit.
1.4.3 Raised-Floor Installations
If the equipment is to be located on a raised floor, it should be mounted on a pedestal suitably
designed to accept the equipment point loading. Refer to the base view to design this pedestal.
The top of the pedestal must be solid.
NOTE
The UPS must be placed on a solid surface. There must be no openings in the surface except
those required for conduit landing areas. All provided kick plates must be installed.
Liebert® Maintenance
Bypass
NXL™ Cabinet
UPS (Matching)
Additional
Battery Liebert® Maintenance
Battery Bypass
Cabinet(s)
Cabinet NXL™ Cabinet
(Matching)
(Matching) UPS (Matching)
Additional
Battery Liebert® Liebert® Battery
Additional
Battery Battery
Cabinet(s)
Cabinet NXL™ NXL™ Cabinet
Cabinet(s)
(Matching) (Matching)
(Matching) UPS UPS (Matching)
WARNING
Risk of electrical shock. Can cause injury or death.
The UPS contains high DC as well as AC voltages. Check for voltage with both AC and DC
voltmeters before working within the UPS.
Only properly trained and qualified personnel wearing appropriate safety headgear, gloves,
shoes and glasses should be involved in installing the UPS or preparing the UPS for
installation.
WARNING
Risk of electrical shock. Can cause injury or death.
Before cabling the UPS, ensure that you are aware of the location and operation of the
external isolators that connect the UPS input/bypass supply to the power distribution
panel.
Check that these supplies are electrically isolated, and post any necessary warning signs to
prevent their inadvertent operation.
When sizing battery cables, a maximum volt drop of 2VDC is permissible at the current ratings
given in Table 17.
WARNING
Risk of electrical shock. Can cause injury or death.
If the load equipment will not be ready to accept power on the arrival of the commissioning
engineer, ensure that the system output cables are safely isolated at their termination.
WARNING
Risk of electrical shock. Can cause injury or death.
When connecting the cables between the battery extremities to the circuit breaker, always
connect the circuit breaker end of the cable first.
5. For control connection details, see 2.4 - Control Cable and Communication.
NOTE
If fault bracing brackets were removed during installation, they MUST be replaced.
6. Close and secure the interior and exterior doors.
7. Attach the cabinet EMI plates to the top of the UPS at each shipping split (625kVA or 750kVA only). See
Figure 2.
8. Attach the kick plates and filters to the bottom of the unit. See Figure 3.
Figure 2 Cabinet EMI plates - 625kVA and 750kVA only
Note location
of larger cutouts.
Orient ground plate
as shown.
Mounting
Hardware
(Supplied)
Installed at Each Shipping Split Detail A
Kickplate
G
Kickplate
D REAR
FRONT
Kickplate
Kickplate
E
F
Install Factory-Supplied
Install Factory-Supplied Install Factory-Supplied
Install Factory-Supplied Bolt, Lockwasher and
Bolt, Lockwasher and Bolt, Lockwasher and
DETAIL D Bolt, Lockwasher and Washer, 4 Places,
DETAIL E Washer, 2 Places DETAIL G Washer, 2 Places,
Washer, 4 Places, Rear Side
Each Side Each Side
Front Side
NOTE
Kick plates must be installed. If the unit is to be installed in a position that does not permit access
to rear kick plates, then the kick plates must be installed before the unit is placed in its final
position.
P0831 P0832
P0801
P66C P99C AUX SPARE
BATT GND
TEMP
FLT
EXTERNAL TB0815
CAN MOB
TB0811 TB0830
MIB ACT FILT
STATUS
TB0810 TB0816
RIB ON GEN
P0808
TB0823 TB0829 TB1154B TB1154A
EPO TB0813 TB0819
STATUS OPT EXTERNAL INT BATT EXT BATT
PS CAN CAN CAN MBB BYP CNTL
Table 2 UPS control contacts with battery cabinet or module battery disconnect
Termin
al Pi Connects to Wire Size/
Item Block n (Description of External Item) Max Length
1 Battery Interface Board TB1154-1
2 Battery Interface Board TB1154-2 18 AWG
CAN Bus and TB1154
1000ft.
24V Power Supply A 3 Battery Interface Board TB1154-3 (300m)
4 Battery Interface Board TB1154-4
A
To Customer
B Input
Terminals
C
RIB
1
120-240VAC
2 (supplied by
swichgear vendor)
Circuit Breaker
RCB1 TB1102
Electrical RIB
Interface Board
Operator 5_MTR_OP_CLOSE 02-806711-01
Close
2_MTR_OP_ENABLE
120-240VAC
TB1101
5 CB1_COIL
RIB
UVR Coil 4 CB1_COIL_RTN
(48VDC) 3_CB1_NO (CB CLOSED )
Fuses should be 10A class CC or J type time delay Electrical operator power provided by switchgear
1 2
fuse vendor and shall be powered from line side of RIB
A
To UPS
B Output Customer
Connections
C
IOB
1
1 5A 5A 5A TB2
2
TB1101
5 CB2_COIL
IOB UVR
Coil
4 CB2_COIL_RTN
(48VDC)
3_CB2_NO (CB CLOSED )
Fuses should be 5A class CC or J type time delay fuse Electrical operator power provided by switchgear vendor
1 2 and shall be powered from UPS side of IOB
CAUTION
The UPS ground lug must be solidly connected to the service entrance ground by an
appropriately sized wire conductor per NEC Article 250. Each conduit or raceway
containing phase conductors must also contain a ground wire, both for UPS input and
output, which are solidly connected to the ground terminal at each termination point.
Conduit-based grounding systems tend to degrade over time. Therefore, using conduit as a
grounding conductor for UPS applications may degrade UPS performance and cause
improper UPS operation.
2.6.1 Four-Wire Input connections
The UPS module bypass input is connected to a solidly grounded source. In this configuration,
the UPS module is not considered a separately derived source. The UPS module output neutral is
solidly connected to the bypass source neutral, which is bonded to the grounding conductor at
the source equipment.
2.6.2 Three-Wire Input connections
This configuration must NOT be used when single-phase loads are directly connected to the
UPS. The UPS output is considered a separately derived source. The UPS module neutral is
bonded to the UPS ground and connected to a local grounding electrode in accordance with NEC
250-26. Please note that whenever the UPS module transfers to or from bypass, two AC sources
(UPS output and bypass) are briefly connected together and circulating current must flow. In this
configuration, the current flows through the ground path, possibly tripping ground fault
interrupters (GFI’s) and distorting the output voltage waveform. Proper adjustment of ground
fault interrupters is necessary to avoid unwanted tripping. The time delay should be set to at least
0.2 seconds to prevent tripping when the UPS performs a transfer or retransfer.
NOTICE
Risk of improperly set ground fault interrupters. Can cause equipment damage.
Failure to set the ground fault interrupters properly could cause loss of power to the critical load.
BPSS
N To connect equipment
N
G G
Source UPS
BPSS
To connect equipment
N
N
G G
To connect equipment
UPS #1
Source G
UPS #2
G
UPS #3
N N
Grounding for 1+N
systems is wired G G
BPSS Switchgear
To connect equipment
N
Source G
UPS #2
N
BPSS
G
UPS #3
BPSS
N N
G G
NOTE
To deselect an event, click on the event.
Programming Relay 1 2 3 4 5 6 7 8
Relay 1 Assignment
BFB Open
BPSS Unable
Save Cancel
NOTE
Up to two ICI’s can be installed in a Liebert® NXL™.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box,
which is accessed from the Internal Option Settings under Config dialog box on the HMI
touchscreen display. The Input Contact Isolator dialog box contains eight choices to match the
eight channel input board. You can label each button to identify the event associated with the
contact. When the dialog box is accessed, each button flashes to display the Input Contact
Isolator number and the user entered label. This label also appears in the Display Panel when an
event related to an Input Isolator Connector is triggered.
The Input Contact Isolator dialog box allows you to:
• Label the input contact assignments for your setup.
• Set the delay for an external event triggering an alarm.
• Review the isolator contact assignments, once the labels are entered.
The delay allows setting the number of seconds that a condition must exist before it will trigger
an alarm. To configure the Input Contact Isolator relays:
1. Press Internal Option Settings from the Config menu.
2. Press which Input Contact Isolator is to be configured. The Input Contact Isolator dialog box is displayed.
Figure 17 Input contact isolator dialog box
Save Cancel
Keylock or EMO
Button (Optional)
Back Feed Circuit
External Interface Breaker (BFB)
Board
Main Input Module Output
Circuit Breaker Circuit Breaker
(CB1) (CB2)
Option Box
(6 Slots)
DC (+)
Input
DC (-) Output
Input Ground
Input
Busbars
Bypass
Input
Busbars
Ground
Output
Busbars
U40-5C-2000
Rev. 2
DOORS AND INNER SKINS REMOVED
Rectifier / DC
Cable Entry
25.8"
15.6" [654mm]
[396mm] 10.6
[269mm]
69.8"
Cable [1773mm]
Entry
TOP VIEW Bypass/Output
Cable Entry/Exit SECTION A-A
BOTTOM VIEW
39.6"
111.6" [2835mm]
[1005mm]
Rectifier Inverter
Center Center
of Gravity of Gravity
76.8"
[1950mm]
32.3" 35.7"
[820mm] [906mm]
A A
Bolt Busbar
29.5"
(749mm) DUAL LUG
CONNECTION DETAIL
GROUND BUS
DC INPUT
CB1-3
CB1-3
2.56 (44) (60)
2.56 (65) 8.7 TYP TYP Do not double-stack lugs (two lugs
(65) TYP (220) 13.8 on same side of busbar).
TYP (350) 2.36 This is to prevent the cables from
(60)
TYP
coming into contact with other busbars.
DUAL LUG
59.2 Output CONNECTION DETAIL
(1504) Ground
FRONT
44.7 Bypass &
(1135) Neutral
A B C N Bypass
Phases &
31.1 Output & Neutral
(790) Neutral Bus
A B C N Output
Phases &
Neutral
Bus
.0
( 0)
RIGHT FRONT (PART B) RIGHT SIDE (PART B)
NOTES:
1.All dimensions are in inches (mm).
2. Unless otherwise noted, use copper or aluminum conductors suitable for at least 75°C.
3. All wiring is to be in accordance with national and local electrical codes.
REAR
SEE
A
2.4 21.0 21.0 12.1 13.9 13.9 12.1 2.2 33.3
[61] [535] [535] [307] [354] [354] [307] [56] [845]
1.7 4.8 1.7 1.7 1.7 RIGHT SIDE
[42] [122] [42] [42] [42]
FRONT VIEW
BRACKET MOUNTING LOCATIONS
(M10 HEXSERTS)
.75
[19]
RECTIFIER SECTION INVERTER SECTION TYP.
(PART A) (PART B)
DETAIL A
FRONT
36.7 37.2
[931] [945]
Foot PILLAR
Spacing SPACING 8.0 [202]
NOTES:
1. All dimensions are in inches (mm).
2. Unit bottom is structurally adequate for
forklift handling.
8.0 [202]
BOTTOM OUTPUT
(PART B)
604325G1
604309G1
604309G2
02-806704-PHASE C
604309G3 02-806704-PHASE B
02-806704-PHASE A
(+)DC BUSBAR
M10 NUT HEX
M10 RIBBED WASHER(x2)
(-)DC BUSBAR
M10 FLAT WASHER
M10 HEX HEAD BOLT DETAIL A
START FINISH
WH P/N (Part B- Inverter Cabinet) (Part A- Rectifier Cabinet) Label
604309G To: 02-806701
02-806704 Inverter Gate Drive A UPSC
1 ID: P0400A
604309G To: 02-806701
02-806704 Inverter Gate Drive B UPSC
2 ID: P0400B
604309G To: 02-806701
02-806704 Inverter Gate Drive C UPSC
3 ID: P0400C
02-806708 To: 02-806708
604325G1 DCFAN_2 & DCFAP_1 DC Fuse Block
External Interface Board ID: P0814
DETAIL B
604308G1
604313G1
604313G2
604307G1
604348G1
604348G1
604349G1
604348G1
604348G1
604352G1
604348G1
(-) DC BUSBAR
M10 HEX HEAD BOLT
Liebert®
IntelliSlot™
Housings
Main Input
Circuit Breaker
(CB1)
DC Input Output
Busbars
External
Interface
Board (EIB)
Input
Busbars
Neutral
Input
Ground
Output
Ground
CB1/RIB Circuit
Breaker Board
DOORS AND INNER SKINS NOT SHOWN
Liebert
IntelliSlot
Housings
Inter-Module
Communication Module Output
Board (Located Circuit Breaker
Behind HMI Screen) (CB2)
HMI Screen
Keylock or
EMO Button
(Optional)
Back Feed
Main Input Circuit Breaker
Circuit Breaker (BFB)
(CB1)
FRONT DOORS NOT SHOWN
CB2/IOB
Circuit Breaker
Option Box Interface Board
(6 Slots)
Output
Busbars
DC Input
Bypass
External Busbars
Interface
Board (EIB)
Input
Busbars
Input
Ground
CB1/RIB
Circuit Breaker
Interface Board
DOORS AND INNER SKINS
Rectifier Inverter
Center of Center of
Gravity Gravity 76.8
[1950]
31.5 31.5
[800] [800]
.0
(0)
DETAIL B
31.5 34.1
[800] [866]
42
Figure 30 Base detail drawing, 625/750kVA Liebert® NXL™, N+1 multi-module unit without static bypass
Front
Front View
Shipping Split
10.9 9.0 9.0 10.9 10.9 9.0
Front 24.6 [276] [229] [229] [276] [276] [229]
[625]
Of Unit
37.2
[945]
8.0 (203.2)
6.0 (152.4)
DETAIL A
61.8 77.3 FRONT
3.900 OF UNIT
[1570] [1963]
FORKLIFT OPENINGS FORKLIFT OPENINGS
36.7 37.2
[931] [945]
FOOT PILLAR
SPACING SPACING
6.0 (152.4)
6.0 (152.4)
44
Figure 32 Input terminal detail, 625/750kVA Liebert® NXL™, N+1 multi-module unit without static bypass
O .56 2.00 O .56
(14) ( 51) (14) 2.0 (51) O .56
1.26 (32)
Typ.) TYP Typ.) Typ.) (14)
Typ.)
Typ.)
76.8
(1950)
DC (-)
Input
DC (+)
Input
51.3 (1303)
A 40.0 (1016)
Input B 36.2 (920)
Phases
C 32.4
3.5 (824)
(90)
3.5
(90) 23.5 (598)
Input
Ground
0
LEFT SIDE (INPUT) LEFT FRONT
Notes Lugs
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run
in separate conduits. Bolt Busbar
3. Unless otherwise noted, use copper or aluminum
conductors suitable for at least 75°C.
CB1-3
CB1-3
DC (-)
INPUT
DC (+)
INPUT
51.3
(1303)
40.0
A (1016)
INPUT B 36.2 (920)
PHASES C 32.4
3.5 [90] (824)
3.5 [90]
23.5
(598)
INPUT
GROUND
.0
LEFT SIDE (PART A) LEFT FRONT (PART A)
LUGS
BUSBAR
BOLT
CB1-3
CB1-3
1.75
A B C (44) Typ.
53.2 (Top Entry)
(1352)
1.38 x .5
Slot 5 O .56 (14)
Output Places Each Typ. 5
39.4 Phases Busbar Places
(1002)
32.0 1.75 (44)
(813) Typ. (Bottom
OUTPUT Entry)
Neutral
PHASES
Output
Ground
0
RIGHT FRONT RIGHT SIDE (OUTPUT)
O .56 (14) O .56 (14)
Typ. 20
1.38 X .56 Slot Typ. 5 1.57 (40) Typ.
Places
1.75 (44) 10 Places Places
Typ. (Top
Entry)
NOTES:
1. All dimensions are in inches (mm)
CB1-3
CB1-3
DO NOT DOUBLE-STACK LUGS 2. Control wiring and power wiring must be run in separate conduits.
3. Unless otherwise noted, use copper or aluminum conductors suitable
for at least 75°C.
4. All wiring is to be in accordance with national and local electrical
codes.
NOTES
1. All dimensions are in inches (mm).
2. Control wiring and power wiring must be run in separate conduits.
1.75
3. Unless otherwise noted, use copper or aluminum conductors suitable for
(44)
at least 75°C.
TYP
4. All wiring is to be in accordance with national and local electrical codes.
76.8
(1950)
.56 DIA.
1.38 X .56 SLOT OUTPUT
(14)
6 PLACES GROUND
TYP
EACH BUSBAR (TOP ENTRY)
C B A N C B A
1.75
(44) 56.4 OUTPUT
(1432) NEUTRAL
TYP
BYPASS
BYPASS / OUTPUT PHASES PHASES,
OUTPUT APPROX.
1.75
PHASES, 3.0" SPACING
(44) BETWEEN
TYP APPROX.
3.0" SPACING BUSBARS
OUTPUT 1.49
33.9 BETWEEN
NEUTRAL (37.7) (860) BYPASS
BUSBARS
BUS TYP 30.4 NEUTRAL
(772)
531985G1
531983G1
532061G1
531985G3
531985G2
531988G2
A 531985GI
531988G2
531983G1
Power Supply
02-806704-
Phase A 02-806707-
531985G2
START
Part A (Rectifier) - Wire Starting Point Part B (Inverter) - Wire Finishing Point
02-806707- Load VI
02-806707 - Load VI
ID: P0701
Loosen hardware to allow
ID: P0700
ID: P0400B
ID: P0400C
busbar to move to join
ID: P0400A
to Part B Busbar.
To: 02-806707-
To: 02-806707-
Retighten and torque
LABEL
To: 02-806716-__
to 27 N-m (240 in-lb)
WH P/N: 532061G1
Connection ID: P1305
To: 02-806704-Phase C
To: 02-806704- Phase B
To: 02-806704- Phase A
49
Figure 37 Shipping split 625/750kVA Liebert® NXL™ without static bypass (continued)
Use wire label as guide for "to" component, connection ID and wire part number.
Low Voltage Wire Connections Between Part B and Part A
Tie wires away from sharp edges, busbar and electronic components.
532049G1
532063G1
02-806710-
532065G1
532065G1
02-806708-
START FINISH
WH P/N (Part B - Inverter Cabinet) (Part A - Rectifier Cabinet) LABEL
To: 02-806710-__
532049G1 02-806716- AC Distribution Board 02-806710- Fan Interface Board 1 Connection ID: P1011
WH P/N: 532049G1
To: 02-806710-__
532065G1 02-806710- Fan Interface Board 2 02-806710- Fan Interface Board 1 Connection ID: P66
WH P/N: 532065G1
To: 02-806708-__
532063G1 DC Fuse 02-806708- External Interface Board Connection ID: P0814
WH P/N: 532063G1
TO: 02-806708-__
532065G1 02-806710- Fan Interface Board 3 02-806708- External Interface Board Connection ID: P99B
WH P/N: 532065G1
02-806704- 02-806707-
PHASE A
531985G2
02-806705-
02-806704-
PHASE B
02-806716-
531985G3
531984G1
531988G1 F42 & F43
532061G1
532062G1
02-806704-
PHASE C
51
START FINISH
WH P/N (Part A - Rectifier Cabinet) (Part B - Inverter Cabinet) LABEL
531985G1 UPSC (Control Door) 02-806704-Inverter Gate Drive A To: 02-806704- Phase A ID: P0400A
531988G2 UPSC (Control Door) 02-806707-Load Vi To: 02-806707-ID: P0700
531983G1 UPSC (Control Door) 02-806707-Load Vi To: 02-806707- ID: P0701
531985G2 UPSC (Control Door) 02-806704-inverter Gate Drive B To: 02-806704-Phase B ID: P0400B
531985G3 UPSC (Control Door) 02-806704-Inverter Gate Drive C To: 02-806704-Phase C ID: P0400C
531984G1 UPSC (Control Door) 02-806705-Bypass Control Board To: 02-806705-ID: P0500
531988G1 UPSC (Control Door) 02-806705-Bypass Control Board To: 02-806705-ID: P0501
To: 02-806716-__
532061G1 Power Supply 02-806716-AC Distribution Board Connection ID: P1305
WH P/N: 532061G1
To: 02-806705-__
532062G1 Power Supply 02-806705- Bypass Control Board Connection ID: P44
WH P/N: 532062G1
To: F42-2 and F43-2
532062G1 Power Supply F42-2 & F43-2 Bypass PS Fuse Block
WH P/N: 532062G1
532049G1
532065G1
02-806710-
532063G1
02-806708-532065G1
53
Start Finish
WH P/N (Part B - Inverter Cabinet) (Part A - Rectifier Cabinet) Label
To: 02-806710-__
532049G1 02-806716-AC Distribution Board 02-806710- Fan Interface Board 1 Connection ID: P1011
WH P/N: 532049G1
To: 02-806710-__
532065G1 02-806710-Fan Interface Board 2 02-806710- Fan Interface Board 1 Connection ID: P66
WH P/N: 532065G1
To: 02-806708-__
532063G1 DC Fuse 02-806708- External Interface Board Connection ID: P0814
WH P/N: 532063G1
To: 02-806708-__
532065G1 02-806710-Fan Interface Board 3 02-806708- External Interface Board Connection ID: P99B
WH P/N: 532065G1
Reference of Rectifier
Corner Post
See Detail A
inet
Cab
ec tifier
of R
Side
m Left abinet
Fr o eC
nels e of Wir
e Pa id
o v e Sid n Left S
Rem stall o
In
and
Reference of
Wire Cabinet
Corner Post
See Detail A
n)
ow
Sh
nts
ne
po
C om
All
ot
(N
fi er
cti
Re
M10 Hardware
Provided in
Shipped-Loose
B Bag Inside
e t Wire Cabinet
bin
Ca
re
Wi
Kickplate is provided as a
shipped-loose item
inside the Wire Cabinet
on inverter-side the UPS
DETAIL A
1 Ground Plate Cabinet-to-Cabinet
Connection Hardware
This hardware provided
on Rectifer Cabinet.
Reuse hardware
to mount ground plate
Bolt and Washer
Bolt
DETAIL B and
COMPLETE ASSEMBLY
M6 hardware for Ground Plate Washer
provided in shipped-loose bag
inside Wire Cabinet
Bolt and Washer
Phase C Busbar
Phase B Busbar
Phase A Busbar
See Detail A
for Torque
Specifications
Glastic to
Bus Torque
240 in-lb,
Typical
Bolt-Nut to
Bus Torque
240 in-lb, Typical
DETAIL A
Torque Specifications
Phase A and Phase B busbars can be removed to ease bottom cable entry on the Liebert® NXL™
500kVA. The cables can be pulled and lugged.
1. Install Phase C cables.
2. Install Phase B busbar as shown in Figure 41.
3. Install Phase B cables.
4. Install Phase A busbar as shown in Figure 41.
5. Install Phase A cables.
6. Verify that all busbar bolt connections are torque properly.
0.5
1
2
4
Time, seconds
6
10
15
25
40
Load, Percent
60
159 100
250
394
600
937
1363
3748
5000
Continuous
Time, seconds
4500
4000
Figure 44 Bypass overload data
3500
3000
3000
2500
2000
Time, Seconds
1500
1000
600
500 394
250
159 100 60 40 25 15 1
10 6 4 2 0.5
0
100 110 120 130 140 150 160 170 180 190 200
Load, Percent
110% Load - 15,000 Seconds Time, Seconds
65
Table 19 Recommended lug sizes
T&B Copper T&B Copper T&B Aluminum T&B Aluminum
Cable Size One Hole Two Hole One Hole Two Hole
#8 AWG 54930BE 54850BE 60104-TB —
#6 AWG 54905BE 256-30695-868 60109-TB —
#4 AWG 54906BE 256-30695-733 60114-TB —
#2-3 AWG 54942BE 54811BE 60120 —
#1 AWG 54947BE 54857BE 60126 —
#1/0 AWG 54950BE 256-30695-593 60132 —
#2/0 AWG 54951BE 54862BE 60138 60238
#3/0 AWG 54965BE 54864BE 60144 60244
#4/0 AWG 54970BE 54866BE 60150 60250
250kcmil 54913BE 54868BE 60156 60256
300kcmil 54914BE 54870BE 60162 60262
350kcmil 54915BE 54872BE 60165 60267
400kcmil 54916BE 54874BE 60168 60269
500kcmil 54918BE 54876BE 60171 60273
600kcmil 54920BE 54878BE 60176 60275
750kcmil 54922BE 54880BE 60178 60277
© 2018 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to
are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and
completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or
omissions. Specifications are subject to change without notice. SL-25434_REV17_8-18/590-1963-501A