BL-06-EMCD-01-026-Installation of Fire Detection and Alarm System Devices V2
BL-06-EMCD-01-026-Installation of Fire Detection and Alarm System Devices V2
Responsible:
1. Construction Management, Project-in-charge, Electro-Mechanical & Commissioning Division
2. Electro-Mechanical Consultants
I. Implementation:
• Designated personnel listed above are responsible for the full implementation of these guidelines
II. Objective:
• To comply with the code provisions for fire detection and alarm system devices:
To enforce the code require- NFPA 72 (2016), Chapter 17.6 Heat-Sensing Fire Detectors
ments for the correct spacing
A.17.6.3.1.1 The use of a detector with a listed spacing of 9.1 m x 9.1 m should
of HEAT DETECTORS
be considered.
To enforce the code require- NFPA 72 (2016), Chapter 17.7.3.7 Projected Beam-Type Smoke Detectors
ments for the correct location
17.7.3.7.1 Projected beam-type smoke detectors shall be located in accor-
and spacing of PROJECTED
dance with the manufacturer's published instructions.
-BEAM TYPE SMOKE DE-
A.17.7.3.7 On smooth ceilings, a spacing of not more than 18.3 m between pro-
TECTORS.
jected beams and not more than one-half that spacing between a projected
beam and a sidewall (wall parallel to the beam travel) should be used as a
guide.
A.17.7.1.10 See Figure A.17.7.1.10 Smoke Detector Layout Accounting for
Stratification
B.3.2.3.1 A detector ordinarily operates sooner if it is nearer to the fire. Where
ceiling heights exceed 4.9 m (16 ft), ceiling height is the dominant factor in the
detection system response.