0% found this document useful (0 votes)
51 views

Chapter 2

- A transformer is a device that changes alternating current (AC) at one voltage level to AC at another voltage level through electromagnetic induction. It consists of two coils wrapped around a common core. - The primary winding is connected to the power source and the secondary winding is connected to loads. The transformer transfers power from the primary to the secondary winding through magnetic coupling between the coils. - Transformers are used to match impedances between a source and load, isolate circuits, and step up or step down voltages.

Uploaded by

Mekonnen Ayal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views

Chapter 2

- A transformer is a device that changes alternating current (AC) at one voltage level to AC at another voltage level through electromagnetic induction. It consists of two coils wrapped around a common core. - The primary winding is connected to the power source and the secondary winding is connected to loads. The transformer transfers power from the primary to the secondary winding through magnetic coupling between the coils. - Transformers are used to match impedances between a source and load, isolate circuits, and step up or step down voltages.

Uploaded by

Mekonnen Ayal
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 39

Electrical Machines

CHAPTER-2
Transformer
1
 INTRODUCTION
A transformer is a device that changes ac electric power at one voltage level to ac electric power
at another volt age level through the action of a magnetic field.
 It consists of two or more coils of wire wrapped around a common ferromagnetic core.
These coils are (usually) not directly connected.
The only connection between the coils is the common magnetic flux present within the core.
 The transformer winding connected to the power source is called the primary winding or input
winding.
The winding connected to the loads is called the secondary winding or output winding.

2
Function of transformer in difference system.

 Matching the impedance of a source and its load maximum power transfer.
 Isolating one ckt from another ckt.
 Isolating direct current which maintaining ac continuity two ckts.

operation principle of a transformer.

 A transformer is an electronic device which has two or more wdgs coupled by mutual
magnetic flux.

 These wdgs are electrically separated but magnetically coupled (link).

 If one of these wdgs, 1st is connected to an ac voltage source an alternating flux is set up
in the coil.
3
Cont…

 And also link the other wdgs, the 2nd in which it produces mutually induced emf.
 The amplitude of alternating flux depends on
 Primary voltage
 Frequency of applied voltage
 Number of turns.

 The value of induce emf depends on

 Magnitude of mutual flux.

 Number of turns 2nd wdgs.

 The frequency
4
Cont…

 If the 2nd ckts is closed a current flows in it and electric energy is


transferred from 1st coil to 2nd .
 Voltage ration - r/ship of 2nd voltage to 1st voltage.
 Turns ratio - the ratio of No of turns of 2nd to the No of turns in the 1st .
 Current ratio- it is an inverse proportion to the voltage ratio.
 1st volt. > 2nd volt. are step down transformer.
 1st volt. < 2nd volt. are step up transformer.

5
The Equivalent Circuit of a Transformer

 In order to Accurately model of transformer, there are losses to be taken into account.
1. Copper (I2R) losses:- the resistive losses in the 1st and 2nd wdgs.
2. Eddy current losses :- resistive heating losses in the core of the transformer.
 They are proportional to the square of the voltage applied to the transformer.
3.Hysteresis losses:- associated with the rearrangement of the magnetic domains in the core during each
half-cycle, as explained in, They are a complex, nonlinear function of the voltage applied to the
transformer.
4. Leakagef1ux:- the fluxes 1st and 2nd which escape the core and pass through only one of the
transformer windings are leakage fluxes. These escaped fluxes produce a self-inductance in the
primary and secondary coils, and the effects of this inductance must be accounted for.

6
The Exact Equivalent Circuit of a Real Transformer
 Copper losses-modeled by placing a resistor Rp in the primary circuit of the transformer
and a resistor Rs in the secondary circuit.
 the leakage flux in the primary windings produces a voltage given by

 the leakage flux in the secondary windings produces a voltage given by

 Since the flux is directly proportional to current flow.

7
cont…..

8
cont…..

 Therefore, the leakage flux will be modeled by 1st & 2nd reactance of

inductance (Xp & Xs).

 The core excitation can be modeled by a reactance Xm connected across the

1st voltage source.

 The core loss can be modeled by a resistance Rc connected across the 1st

voltage source.

9
cont…..
 Therefore, accurate model of transformer,

10
cont…..
 The equiv. ckt must be referred either to its 1st side or to its 2nd side problem solution.

 The transformer model referred to its primary voltage level:-

11
cont…..
 The transformer model referred to its secondary voltage level:-

12
Approximate Equivalent Circuits of a Transformer
 The excitation branch has(large impedance) so, a very small current
compared to the load current of the transformers.
 In fact, it is so small that under normal circumstances it causes a completely
negligible voltage drop in Rp and Xp.
 As a result, the excitation branch is simply moved to the front of the
transformer, and the primary and secondary impedances are left in series
with each other.
 In some applications, the excitation branch may be neglected entirely
without causing serious error.

13
cont…..

(a) Referred to the primary side;


(b) Referred to the secondary side;
(c) without excitation branch. referred to the primary side;
(d) without excitation branch. referred to the secondary side.
14
cont….
Example :- A 2000/200 V, single-phase, 50 Hz transformer has the following data
Rp =3.5Ω Rs = 0.015Ω
Xp =4.5Ω Xs =0.012Ω
Find
A. The equiv. (approximate) ckt referred to the 1st .
B. The equiv. (approximate) ckt referred to the 2nd .

15
Determining the Values of Components in the Transformer Model

 To d/ne the values of the inductances and resistances in the transformer model.
 We use to test, the open-ckt & short-ckt test.
open-ckt
 a transformer's secondary winding is open circuited, and its primary winding is
connected to a full-rated line voltage.

16
cont…
 all the input current must be flowing through the excitation branch of the transformer.
 The series elements Rp and Xp are too small in comparison to Rc and Xm to cause a
significant voltage drop,
 So essentially all the input voltage is dropped across the excitation branch.
 In this test Full line voltage is applied to the primary of the transformer,
 the i/p voltage, i/p current, and i/p power to the transformer are measured.
 From this information, it is possible to determine the Pf & magnitude & angle of the
excitation impedance.
 The easiest way to calculate the values of Rc and Xm is to look first at the
admittance of the excitation branch.

17
cont…
 The conductance of the core- loss resistor is given by:-

 the susceptance of the magnetizing inductor is given by:-

 Since these two elements are in parallel, their admittances add, and the total excitation
admittance is:-

 The magnitude of the excitation admittance (referred to the primary circuit) can be
found from the open- circuit test voltage and current:-

18
cont…
 The angle of the admittance can be found from ckt PF.
 The open- circuit PF is given by:-

 and the power-factor angle (θ) is given by:-

 The power factor is always lagging for a real transformer.


 So the angle of the current always lags the angle of the voltage by (θ) degrees.
 There fore, the admittance is :-

 Therefore, it is possible to determine the values of Rc and Xm directly from the open-
circuit test data. 19
short-circuit test
 The secondary terminals of the transformer are short circuited, and the primary terminals
are connected to a fairly low-voltage source.

 The input voltage is adjusted until the current in the short circuited windings is equal to
its rated value.
 The i/p voltage, current, and power are again measured.
 Since the input voltage is so low during the short- circuit test, negligible current flows
through the excitation branch. 20
cont…
 If the excitation current is ignored, then all the voltage drop in the transformer can be
attributed to the series elements in the circuit.
 The magnitude of the series impedances referred to the primary side of the transformer
is:-

 The PF of the current is given by:-

 The current angle is thus -ve, and the overall impedance angle (θ)is positive:-

21
cont…
 Therefore,

 It is possible to determine the total series impedance referred to the primary


side by using this technique.
 But there is no easy way to split the series impedance into primary and secondary
components.
 Fortunately, such separation is not necessary to solve normal problems.
 These same tests may also be performed on the secondary side of the transformer.

22
cont…
 Example:- The equivalent circuit impedances of a 20-kVA, 800/240- V, 50-Hz
transformer are to be determined. The open-circuit test and the short-circuit test were
performed on the primary side of the transformer, and the following data were taken:

Find the impedances of the approximate equivalent circuit referred to the primary side, and
sketch that circuit.

23
Transformer Voltage Regulation
 A real transformer has series impedances within it, the output voltage of
a transformer varies with the load even if the input voltage remains constant.
 Voltage regulation (VR). Full-load voltage regulation is a quantity that compares the
output voltage of the transformer at no load with the output voltage at full load.
 It is defined by the equation:-

 Since at no load, Vs = Vp /a, the voltage regulation can also be expressed as

24
cont…
 it is a good practice to have as small a voltage regulation as possible.
 For an ideal transformer, VR = 0 percent.
 high-impedance and high-voltage regulation transformers are deliberately used to reduce
the fault currents in a circuit.
 How can the voltage regulation of a transformer be determined?

25
The Transformer Phasor Diagram
 To determine the voltage regulation of a transformer, we must understand the voltage
drops within it.
 The effects of the excitation branch on transformer voltage regulation can be ignored.
 Because its impedance is high the i/p voltage is almost equal to the voltage drop in it.
 So only the series impedances need be considered.
 To d/ne the effect of the impedances and the current phase angles on the transformer
voltage regulation is to examine a phasor diagram, a sketch of the phasor voltages and
currents in the transformer

26
cont…
 Assume that the reference phasor is the 2nd voltage (Vs).
 Therefore, the reference phasor will be 0 degree interims of angle.
 And all other voltage & current are compared to that reference.
 By applying Kirchhoff's voltage law to the equivalent circuit, the primary voltage can be
found as

 From this equation the phasor diagram can be drawn as

27
cont…
 operating @ a lagging PF.
 that Vp/a > Vs for lagging loads.
 VR with lagging loads must be > zero.

 operating @ unity PF.


 Vp/a > Vs & VR > 0

 Leading PF.
 Vs > Vp/a &
 The transformer has –ve VR 28
cont…
 Derivation of the approximate for Vp/a

29
Transformer Efficiency
 Transformers are also compared and judged on their efficiencies & given by [these
equations apply to motors and generators as well as to transformers.]

 losses present in transformers:


1. Copper (I2R) losses. accounted for series resistance in the equiv. ckt.
2. Hysteresis losses. accounted for by resistor Rc.
3. Eddy current losses. accounted for by resistor Re.

30
cont…
 To calculate the efficiency of a transformer at a given load, just add the losses
 Since the output power is given by:-

 the efficiency of the transformer can be expressed by

31
cont…
Example:- A 15KVA, 2300/230 V transformer is to be tested and its series impedances are
Req,s = 0.0445 Ω & Xeq,s = 0.0645 Ω. Calculate the full load VR at 0.8 lagging pf, 1.0
pf & 0.8 pf leading. Also what is the efficiency of the transformer at full load with at 0.8
pf lagging? (Rc/a2=1050 Ω).

32
Parallel operation of transformer
 Parallel operation of transformer is performed the load to be supplied is in excess of the
rating of a single.
 Also it is advantageous to several smaller units sharing a common load rather than a
single big unit.
 In practice, smaller units of equal rating are used to facilitate interchangeability of spare
parts & maintain inventory.
Necessary conditions for parallel operation
 Single phase transformers:-
 The rating of primary voltage must be the same.
 Since primary wdgs of all transformer are connected common supply bus-bars.

33
Cont…..
 The transformation ratio, therefore, voltage ration must be equal.
 Since all secondary wdgs are connected to common load bus bar.
 They must have the same polarity (absolutely necessary).
 If the parallel with dissimilar polarity, it will result in dead sc.
 They must have the same voltage regulation, even if the impedance are not equal in
magnitude.
 When transformer of d/t KVA rating are to be paralleled it is desirable that their equiv.
impedances should be inversely proportional to their rating.
 They must have equal %age impedances, X/R ratio must be the same.
 If X/R ration are not the same they operate at d/t pf which leads to unequal sharing of
common load. 34
Cont…..
 For satisfactory parallel operation all above conditions must be satisfied.
 If the voltage ratio slightly unequal, // operation is possible but there would be a
circulating current even if the absence of load.
 And when loaded there is a possibility of one of the unit getting overloaded and
overheating due to improper sharing of load.
 When 3-phase transformer are to be // in addition to the above condition the following
condition are also need to be fulfilled.
 The phase sequence must be same
 The phase displacement b/n the 1st and 2nd voltage must be same
 All three phase transformer in the 3-phase transformer bank will be the same
construction either core or shall. 35
Cont…..
Example-1:- Two 1-ᶲ transformer with equal turns have impedance of (0.5+j3)Ω & (0.6+j10)
Ω wrt the 2nd if they operate in //, d/ne how they will share a total load of 100 KW at pf
0.8 lagging.
Example-2 :- A transformer of 500 KVA with 1% resistance & 5% reactance is connected in
// with a 250 KVA transformer with 1.5% resistance & 4% reactance. The 2nd volt. of
each transformer on no-load is 400 V. find how they share a load of 750 KVA at pf of
0.8 lagging.
Example-3 :- Two transf. A & B are connected in // to a load of (1+j0.75) Ω. Their
impedance in 2nd terms is ZA= (0.075 + j0.25) Ω & ZB = (0.05+ j0.3) Ω. Their no load
terminal voltages are EA = 217 @ 0 degree. & EB =215 @ 0 degree V. find the KVA
rating of each transformer. 36
Instrument transformer
 In DC ckts when large current are to be measured, it is used to use low range ammeter
with suitable shunts.
 For measuring high voltage, low range voltmeter with high resistance in series are used.
 But it is not convenient to use for measuring AC current & voltage.
 Instrument transformer in conjunction with standard low range AC instrument are used
 Instrument transformer are two types :-
1. current transformer (CT)
2. potential transformer (VT)

37
current transformer (CT)
 Are used with low range ammeter to measure high AC currents
 Will have one or few turns of 1st wdgs & large No of turns in the 2nd
 With regard to volt. it is step-up type & current will step-dawn.
 If the 1st & 2nd current ratio is 100:5 then it step up the voltage by 20 time & step-dawn
the current to 1/20.
 Actual current = Ammeter reading*CTR, CTR = current transformer ratio.
 Most commonly used current transformer is clamp on meter.
 Since Ammeter resistance is low, CT is normally works on SC.
 By any reason ammeter is taken out, 2nd wdg must be sckted with the help of switch (S).

38
Cont……..
 If not shorted due to absence of counter amper-turns in the 2nd unopposed 1st mmf will
set up high flux which produce excessive core loss & heating (also high voltage across
2nd terminal)
Potential transformer
 Are used in conjn. With standard low range voltmeter (usually 110v) to measure high ac
voltage.
 Their operation is not much d/t from ordinary two wdg transformer.
 They are very accurate step-dawn transformer.
 1st contains large No of turns & 2nd consists few turn.
 For safety purpose 2nd wdg should be grounded (high volt. may damage the voltmeter)
 To measure power in ac ckts both CT & PT in conjn. With wattmeter is used 39

You might also like