External Prestressing in Bridges - 201-468
External Prestressing in Bridges - 201-468
0
3Li0 -2R. JR. dy.1 dw(x, t 0 )
H.(t ) E A - -d- d dx -
10 ii OX X
a
+ c3tx a + [ l.p(x)dx] dx-
+ c4t ss-
- ( :~ - 1) J[J~ (x , t 0
) dx] dx (20)
2
b) for Kt < 0
w*(x,t) =C~tShKtx+C~tChKtx +
and using conditions ( 17) , where the lower chord does not pos-
sess the property of creep.
For vertical load only, when K~0 =K~, the solution of the
stress strain state is reduced to the integration of equations (16)
and (22), in order to define w(x,t 0 ) and w(x,t} with considerably
simplified "length" conditions ( 17) and (18) .
1 H (t ) 2 4 3 3
wg(t 0 )= 24 R [ g - 8 7 f2 J[x -2xR.+xR. J. (23)
1
The length conditions, for t=t 0 , that is, at=bt=1, using
expression ( 17) , are:
3L -2R. 3L -2R.
H (t )[ 1o + 2o J -
g o E1~1 E2A2
(26)
Order Theory. The comparison of the H~1 )(t 0 ) and H~2 )(t0 )
values shows whether the solution accoratng to the First Order
Theory Is sufficiently accurate.
1 3 8 2 R1
atg I5 f2£ - (at- bt) Hg(to) [ 15 f2 £ + E A C1 J
H(l) (t) 1 1 (29)
g 8 2 R1 R1
bt [ 15 f2 £ +EA C1J +EA c2
1 1 2 2
section of the box girder is constant along the whole span, having
4. 00 m external width and 2. 80 m external height. The upper slab
is 35 em thick, the side walls are 25 em and the thickness of the
bottom slab is 20 em. The percentage of the mild reinforcement in
the box girder along the whole span is about one percent.
The analysis has shown that, due to the creep and shrin-
kage of concrete, forces in such systems change very little with
time. This explains why the loss of prestressing force with time,
due to the time-dependent deformations of concrete,is incomparably
lower than in classically prestressed concrete girder with tendons
inside the cross-section.
CONCLUSIONS
REFERENCES
P,{x)
lm:;w;IJI
~ -....
<
~
~
()
§
0...
~
::::!.
....
a>
()
~ ~~ ~ 18.~ ~ l
i 25.90
m
B
50.40 25.90
Fig. 4--The general plan of the new prestressed concrete hangar at the Belgrade International
Airport in Yugoslavia
Prestressing 205
AriD
AL~--------------------,~j7·~~--------------------T
¢ :-1
l!l25~5
I
Cl
Fig. 5--The view and characteristic cross-sections of the main girder
Fig. 7--Lifting of the main girders: first two girders are already
lifted while the third one is half-way up
207
208 Klaiber, Dunker, and Sanders, Jr.
F. Wayne Klaiber, FACI, is Professor of Civil and Construction
Engineering and Manager of the Bridge Engineering Center at Iowa
State University, Ames, Iowa. He is a member of ACI Committee
215, Fatigue of Concrete and ACI Educational Committee, E801.
INTRODUCTION
For the past eight years, the authors have been investigating
the use of external post-tensioning for strengthening existing
bridges. Although this work involves numerous projects, for
discussion purposes it will be presented here as follows:
Span and Anchorage Location: Span length was found to be the most
significant variable in the moment fractions; exterior beams were
found to retain less moment as the span length was increased.
When the span length was held constant and anchorages were moved
toward the supports, more moment was distributed away from the
exterior beams. The distribution is thus dependent on the length
of the beam subjected to post-tensioning (i.e., distance between
anchorages).
PROJECT 2
SUMMARY
ACKNOWLEDGMENTS
REFERENCES
14'- 8"
4'- 3"
TOTAL: 60.SOkips
.
0
FIXED ;_N~---""'
:I:
u
~
0::
w -80
\
//
/
/
/
..' ' .....................
'
"-
II\
w
:I:
u
~
0
0::
~
:::!:
z
<
0::
1-
II\
e FIELD MEASUREMENT
BM1 8M2
. .
~~IMPlE ~PA?
u
:I:
~ //
/ ''
0:: -80 / ''
w
"-
/
/
'
II\
w
:I:
u
• •
z
0
0::
~ SIMPLE SPAN
:::!:
z
<
0::
1-
II\
e FIELD MEASUREMENT
-320
BM1 MB2 8M3 BM4
500,.....
4. ~~
0
-500 • •
•
L-
a. Beam 4
,.....
500
u
:I:
z 0
,. tt
cc
1.1.1
Q.. • • •
""
1.1.1
:I:
-500 '--
b. Beam 3
u
z
0
cc ,.....
~ 500
:::!:
z 0 ...
<(
cc • •
....
"" -500 L-
c. Beam 2
500,.....
0 • • •
d. Beam 1
-500 .__
20.20kips 19.71kips 19.92kips
~I I I l
Beam and Load Key
:I:
u
~
a:
UJ
0..
Ill
UJ
:I:
u
~
0
a:
u
:E
EXTERIOR BEAM
e EXPERIMENTAL STRAIN
:I:
u
~
a:
UJ
25~[
•
0..
Ill
UJ
:I:
-250 ---- INTERIOR BEAM
u
~
500
I
0
a: I
u
:E 0
z"
<
a:
-500
1-
Ill -1000
1- 1- MIDSPA~
1I· I-MIDSPAN
I
5PAN1 =12'-8" ~
MIDSPAN
A•I•
SPAN 2 I= 16' -...:.4'_'_ _r._ .:.S:. .:PA.:.N.:. .3:._~. .:.1.:. .2'_·.:.8'_'_:A-.!I
-·
[I[]
117 [TIE
143 cru
123
lliiJ
115 [ill]
167 [;]
105
ffiB
102 [ill]
176 [I[]
114
[ili]
122 [ill]
148 illf]
112
ABSTRACT
229
230 Osborn and Preston
INTRODUCTION
Background of Problem
Two fabrication practices used before 1955 have led to the present
state of deterioration of this bridge type. First, calcium
chloride was often added to the concrete mix to accelerate curing
in cold weather. Calcium chloride, in the presence of air and
water, causes corrosion of steel items embedded in concrete. The
corrosion causes pitting of the prestressing strand and loss of
cross-sectional area. The corrosion product, rust, exerts
bursting forces on the surrounding concrete leading to cracking
and spalling.
The diaphragm core (see Figure 3 for location) was for the full
depth of the member. Chloride ion contents and concrete
compressive strengths were measured from the core. Chloride ion
contents ranged from 6. 5 lbs to 11.2 lbs per cubic yard of
concrete. These levels are 5 to 8 times those needed to support
corrosion of embedded steel. Compressive strengths measured on
two samples were 7700 psi and 8900 psi. Based on the compressive
strengths, it is estimated that the flexural tensile strength is
over 800 psi and the modulus of elasticity is about 4,700,000 psi.
Concrete of this strength is relatively impermeable. Two layers
of strands were found at the bottom of the core. No corrosion was
visible.
The final design of the post- tensioned repair called for the
placement of four .5 inch diameter strands, each tensioned to a
load of 18 kips. A lesser number of strands would have been
possible, except that a symmetric pattern would have been
difficult to place. A simple welded plate assembly (Figures 4 and
5) was designed as an end anchorage for the strands. Each
assembly was to be bolted to the beam soffit with six Hilti HAS
Super 78-10 polymer grouted anchor bolts. Uncertainties in the
shear strength of these embedments dictated a conservative design.
Also, the anchorage design was predicated on preventing the
anchorage from being the weak link in the system. A schematic of
the anchorage is presented in Figure 4.
Midspan Bottom
Ultimate Flexural Stress under Dead
Capacity at Midspan and Live Loads
(foot kips) io.ill*
Original Beam
(As designed) 1444 -82**
Prestressing 235
Midspan Bottom
Ultimate Flexural Stress under Dead
Capacity at Midspan and Live Loads
(foot kips) ..lo.ill*
Deteriorated Beam
(Assumed) 757 -763**
Repaired Beam
(Assumed) 1122 - 307**
Deteriorated Beam
(Actual) 1295 +24***
Repaired Beam
(Actual) 1718 +266***
Code Requirements
Required Ultimate Required Midspan
Flexural Strength Bottom Fiber Stress
(foot kips) ..lo.ill
AASHT0-1949
Specification 1056 0
AASHT0-1983
Specification 777 -424
* + - compressive stress
- - tensile stress
stress calculation based on AASHT0-1949 truck load
distribution
stress calculation based on measured truck load distribution
simular to AASHT0-1983
Construction of Repair
3. "L" shaped anchors were set into drilled holes. These were
used to hold up the mesh reinforcement and help provide
composite action between the original beam and the gunite.
Strands used were .6 inch diameter since wedge anchors for epoxy
coated, .5 inch diameter strands were not available. The post-
tensioning loads, however, remained the same as designated for .5
inch strands.
The wedges were set and slack was removed by first tensioning each
strand to 1.8 kips. Then each strand was tensioned to 18 kips.
Prestressing 237
The repairs for a single beam took about one week. They would
have been done sooner except that the contractor had much
difficulty in drilling holes for the anchor frame bolts. The
holes were wider than the spacing between prestressing strands in
the original beam. It was found that the percussion type masonry
bits used by the contractor were inappropriate. The strands were
very hard, which caused the drill bit to become dull. A water
lubricated diamond core bit would have been superior, if one of
the proper diameter was available.
Another potential problem was in the use of the "L" anchors. The
standard form of these anchors have lead expansion bushings. The
combination of lead, steel, zinc coating and dissimilar concretes
can create a galvanic cell which will corrode the anchors. Other
inert anchor materials should be considered for future projects.
A crack developed between the gunite and the original beam soffit.
However, it did not appear to affect the composite behavior of the
repair. Before attempting an actual construction project, other
methods of applying the gunite should be explored. Cores should
be taken through the finished work to verify proper bond.
Cost of Repair
The primary purpose of the tests was to verify that the gunite
encased external reinforcement was acting compositely with the
original beam under service loads. The tests were also designed
to yield information about the lateral distribution of loads
across the bridge, the distribution of strain through the cross-
section of a beam, and the distribution of strain along the length
of a beam.
The strain and dial gage readings were taken with the truck(s) in
each position and under zero live load, between each position,
with the truck(s) off the bridge. Strains were converted to
stress by multiplying by the estimated modulus of elasticity,
4, 700,000 psi.
Results are presented for just two load positions: one with the
truck(s) along an edge beam and one with the truck(s) centered on
the bridge. Results for the remaining positions can be found in
Reference 18.
through the cross section of the repaired beam under single and
double truck loading. The strain distribution is nearly linear
which indicates that the reinforcement within the gunite is acting
compositely.
One of the most enlightening results of the test program was the
measured lateral distribution of loads to beams adjacent to the
loaded beam. In spite of the poor condition of the shear keys,
lateral distribution was nearly equal to the distribution
designated in current AASHTO specifications and that determined
from analysis. This means that even bridges which appear to be
severely distressed may have substantial reserve capacity since
they were designed using conservative assumptions with respect to
lateral load distribution and allowable tensile stresses. The
242 Osborn and Preston
ACKNOWLEDGEMENTS
The authors wish to thank PADOT for their support of the research
project which is the basis of this paper. Many individuals at
Wiss, Janney, Elstner Associates participated in the research.
However, the authors wish particularly to thank Carol Roach for
her substantial efforts on this project.
REFERENCES
2. Roesli, A.; A. Smislova; E.G. Ekberg, Sr.; and W.J. Eney, all
of Lehigh University, Field Tests on Prestressed Concrete
Mul tibeam Bridge, Highway Research Board Proceedings, Vol. 36,
1956.
10. Koretzky, H.P., What Has Been Learned from the First
Prestressed Concrete Bridges Repair of such Bridges.
Transportation Research Record 664, Bridge Engineering, V. 1,
Transportation Research Board.
11. Rabbat, B.G., Kaar, P.H., Russell, H.G. and Bruce, R.N., Jr.,
Fatigue Tests of Pretensioned Girders with Blanketed and
Draped Strands. PCI Journal, V. 24 No. 4, July-August 1979.
12. Overman, T.R., Breen, J.E. and Frank, K.H., Fatigue Behavior
of Pre tensioned Concrete Girders, Research Report 300-2F.
Center for Transportation Research, University of Texas at
Austin No. 1984.
BE.AM
NUMII[RS I0!0Jc5J@j0j0!0!0!&TI::~:
I e" 3 • -o" • 27' -o" 1 DESIGN WIOTH l ' .J
I NOTE· MEASURED WIDTH
v
BRIDGE CROSS· SECTION WAS 27'-4" DUE TO
GAPS BETWEEN SOX
(LOOKING NORTH) BEAMS
•'
•' •'
"
.. ,.
·• ..
•'
' ct>
~ ~
51'-o" o/c IRGS A 51'-o" 51'-o"
l~~
52'• 5" 52'-9" 52'- 5"
BRIDGE PLAN
1' s"
4- •s BARS FULL
I LENGTH 1/2'' ( AVG. MEAS.)
• ..... ......
..
•• (I)
,.,~
,o ..
'V
.. '<t
....
"'<t
-.- .l.::-:-:-:-:-:-
~
.................... ····· ............ . ..
........................ . ~:.
-~
-
l 40 -1/4"2) STRAND PER ROW
APPROX 314" C. TO C.
I JL "
112'' AVERAGE
MEASURED GAP
I,.
<B:> vv..•
eli:> 1/'!&"
ul
.
--- '
ec.o.Le
• •
(~T)
· CuiOleA~
',(
~~t~~~====!~~!:~t!J,1z"auNNJrE
WWF2 • xz•
"12fiAI.kiE
a. ~EIIH CROSS·SECTION
SHOWIN6 POST· TENSION£0 REPIIIRS
lll
L DISTANCE FROM FACE Of PIER IN FEET AND i OF lOX BEAM UNLESS NOTED OTHERWISE
~POSITION RELATIVE TO GAGE AT CENTER Of BEAM
£-EAST, W- WEST, N-NORTH (NEAR PIER) 0CfJ
-· - - S·SOFFIT, B-REINFORCING BAR, G-GUNNITE, T-TOP
---- - B£ AM NUMB£ R
0"'
0
IHVAR WIRE
~~··· ...PlATE
STEEl
. ... ~
\:
;: ~
: o
~=!=!~
: : o 1
A
' I
~
::
r==1
I o :
~
F3: : : ~%~
n
~ I ~~ :===1 ~
o o
~~~EKD c~-'
: : : :
:.. .. 1
! :: :
~,._ __.: !.... •• J
:
'-··J
! :
L-J
: : :
l _ _ _,
! : !L.~:
._ __ J
13K
t 't
18K 18K
D l,,.tc ___g-
~
c ----'!.
5'1" ~ Je'o"
•1=2,. c.
10"
11 1 11 1 11
1
13 -4 4'-3" e'-3 1/2" 4 -3 13 -4
t• I 'I I I
19K 19K
·I
13 K
13 K 20K 20K
c 0
[-~ ~
D c c D
&-o ~ 10" 7"
a __g__
c
c
c
.rt1t
c ~~1!1' 11t0
-t1""
PATTERN
IW
4W
.. '-
0.15
0 0 0 CD 0 80 ® ®
....;
0.12
.......c"
0.01
u
......." 0.01
~
"
0.05
0.04
0.03
0.02
0.01
....... __./ n ---
........_
0.00
(a)
...____
~I v
/ r--..
-
~
(b)
...
...c01 ..."" .
.....
c orn.tcnoN
.," STRAIN
~
....c 1-c ,..
" 8
..." ......u
00
"u" ........."
1-
"'" &
(c)
TWO TRUCKS
ONE TRUCK
TOP OF BEAMJ
ill] ill (
0 0 0 0 00 0 0 0
0.00
-0.01
-O.Ol
v - f.--.>
~r
....~ -o.oJ
-0.0-4
...."
..0
-o.oe
u -0.07
......." -o.oa
..
v ~
-o.oe
= -0.10
-0.11
-0.12
-0.1.l
-0.1S
I
Fig. lla
II
\ I
I
.. \ ~
,. 1\_1--.-
t---.-_
i
~
r--
Fig. llb
I
I
.. ...
I'll
0
1-<
.. I
l
....0 "'...0
~011
....... ........
.. g 20llli ~
I
u
"... .......
u
.. ..
"' =
Fig.
:\ m- m ;
0.00
0 0 0 000 0 00
-0.01
....,;
-0.02
-o.u ....... /
v v
c
-0.0<1
-o.oa
~ ...............
..
.,..0 -0.01
~
.........
u -0.07
-o.oa
-0.01
"
1'1 -0.10
-0.11
-0.12
-G. I>
-0.14
-G.IO
Fig. 12a
••
..••
.,..c
.."'.... ..
..
0 .. II r--- "'- 1--
.. -
....)1:u J--.... !'---
20
r--.--..
Fig. 12b
...'"' "'..
..
0 0
....:0 .,....g ,
".. ......."
u
u
....,; -o.o•
-o.o2
-o...
......."
0 -o...
u -o.oe
....
~
....
-o.OI
-o.07
~ -o.oo
-o.o•
-o.10
-G. II
...0.12
-0.1~
-o.,.
-o.u
..
..
..
...."
...... ..
"...0
....u ..
lC
.
..
80
10
60
face of
pier ~ of bea• 2_
50
40
30 -
I
20
"
I'" 10
~~
"'
'''
·-20 ----,--r- -.---~-~-~--,----,--·..--,.--·1---,--
o 4 8 12 16 20 24
257
258 Beaupre et al
ACI member Richard J. Beaupre is a Design Engineer for Greiner Engineering, Inc.
in Tampa, Florida. He received a BS in Civil Engineering from the University of Florida
in 1984, and a MS in Civil Engineering from The University of Texas at Austin in August
1988.
ACI member Lisa Carter Powell is a Senior Bridge Designer for Figg and Muller
Engineers, Inc. in Austin, Texas. She received a BS degree in Civil Engineering from the
Georgia Institute of Technology in 1984, and a MS degree in Civil Engineering from The
University of Texas at Austin in August 1987.
John E. Breen, FACI, holds the Nasser I. Al-Rashid Chair in Civil Engineering at The
University of Texas at Austin. He is the past Chairman of ACI Committee 318, Stan-
dard Building Code, and is a former chairman of ACI-ASCE Committee 441, Reinforced
Concrete Columns, and of ACI's Technical Activities Committee
ACI member Michael E. Kreger is an Assistant Professor of Civil Engineering at The
University of Texas at Austin. He received BS, MS and Ph.D. (1983) degrees from the
University of Illinois at Urbana-Champaign. He is a member of ACI Committee 318-C,
Analysis, Serviceability and Safety, ACI-ASCE Committee 352, Joints and Connections,
and ACI Committee 215, Fatigue of Concrete. He has conducted research in the areas of
repair and strengthening of concrete structures, behavior of reinforced concrete buildings
subjected to seismic loads, and behavior of prestressed concrete bridge structures.
INTRODUCTION
One of the latest and most dramatic developments in segmental technology has
been the use of external tendons which are defined as tendons in ducts not encased in the
concrete of the webs or flanges of the box girder bridge and attached to the concrete boxes at
only a few discrete points (see Fig. 1). This innovative type of construction has been shown
to provide substantial economic savings, as well as savings in construction time. External
post-tensioning differs from internal post-tensioning because the tendons are removed from
the webs and flanges and placed in the cell-void. The tendon deviators maintain the draped
profile of the external tendons and provide the only positive attachment of the tendons to
the structure other than at the anchorage zones. This makes the deviator a key element of
this bridge system.
Three basic kinds of tendon deviators have been utilized in externally post-
tensioned segmental box girder bridges; the diaphragm (Fig. 2a), the rib or stiffener
(Fig. 2b), and the saddle or block (Fig. 2c). The deviators are usually monolithically
cast in the bridge segments to accommodate the required tendon duct configurations. The
diaphragm and rib or stiffener are usually full web-height deviators. The diaphragms usu-
ally extend the entire width of the box section and are provided with an access opening for
passage along the span. The rib or stiffener extends out only a small distance from the web
wall. The advantage of using th~ diaphragm or rib type deviators is that compressive strut
action in the concrete may be utilized to resist the tendon deviation forces. Compression
struts can develop from immediately above the tendon duct to the top flange which provides
these deviator types with greater inherent resistance than the saddle or block. However,
Prestressing 259
many disadvantages also exist with these types. They create added dead load, sometimes
offsetting the savings from the efficient web thickness. Other disadvantages are construc-
tion related. The formwork for the diaphragm and rib and the geometry for the tendon
pass-throughs becomes very complicated, especially for a curved span because the bridge is
curving while the tendons remain on straight paths. In contrast, the block or saddle is usu-
ally a relatively small block of concrete located at the intersection of the web and bottom
flange. Advantages of utilizing this type of deviator in a bridge are that there is relatively
insignificant additional weightfoJ:.J.~ structure, the formwork is less complicated than
that r~quired for a diaphragm or a rib, and g~metry complications are minimized because
non-deviated tendon pass-throughs are generally not required. However, the disadvantage
is that the deviator capacity may be greatly reduced as compared to the diaphragm or rib
because there is no major direct compression strut formed after cracking. Therefore, the
deviator force must be tied back into the box by reinforcement. This may require greater
attention to detailing and may lead to more congestion of reinforcing for a saddle-type
deviator than for a diaphragm or rib.
RESEARCH SIGNIFICANCE
Uncertainties exist concerning the behavior and proper design criteria for the ten-
don deviator details. In order to provide careful verification of behavior and develop efficient
details, the study documented herein encompassed an experimental investigation 1 •2 •3 •4 of
the tendon deviator details and suggested a design methodology for the deviators.
which was bent to required deviation angles using a hydraulic pipe bender. Multiple 3/8-
inch diameter strands were used for tendons in loading the specimens.
Specimens lA and lB modeled a typical prototype deviation saddle detail used in a
straight-span bridge (see Fig. 3). The reinforcement scheme consisted of primary link bars
supplemented with two types of stirrups (designated as open stirrup and closed stirrup).
For specimen lA, three tendons were deviated which represented a tendon configuraton of
a deviation saddle located closest to the center of a span. The corner tendon had both a
vertical deviation and a slight horizontal deviation directed away from the web, while the
other tendon had only horizontal deviation directed towards the web. The specimen lB
reinforcement scheme was identical to that of specimen lA. However, the tendon configu-
ration was different. This deviation saddle only deviated two tendons which represented a
tendon configuration typical of a deviation saddle located somewhat closer to the piers. The
corner tendon had both a vertical deviation and a horizontal deviation directed away from
the web, while the other tendon had only a slight horizontal deviation directed away from
the web. The objective for specimens 2A and 28 was to isolate the behavior of the indi-
vidual reinforcement patterns of specimens lA and lB. These specimens were not intended
to be properly detailed deviation saddles, and they were expected to have an abnormally
low factor of safety at ultimate. Reinforcement details for specimen 2A provided the link
bar alone. Specimen 28 reinforcement details provided the two types of stirrups (open and
closed stirrups) without the link bars. The tendon pattern for specimens 2A and 28 was
identical to specimen lB. The objective of specimens 3A and 38 was to determine if the
frequently used epoxy coated reinforcement has any effect on the behavior and strength of
a deviation saddle. Specimens 3A and 38 were companion specimens to specimens lA and
lB. The only planned difference between these specimens was that the reinforcement was
to be epoxy coated, but some very minor differences in the bar chairs and strain gage lead
wires developed that were not discovered until after fabrication 2 • In spite of this, it was
felt possible to make direct comparisons between the epoxy coated specimens (3A and 38)
and the uncoated specimens (lA and lB).
The objective of specimens 4A and 48 was to evaluate the modified reinforcement
scheme and deviation saddle geometry shown in Fig. 4. This was an attempt to simplify
and standardize reinforcement patterns and deviation saddle geometry for typcal deviation
saddle details. Because of reinforcement congestion, the link bars previously anchored at
the intersection of the web and flange centerlines were replaced by loops anchored into
the expanded nodes and outer stirrups tying the nodes to the web and flange. The actual
reinforcement patterns utilized were based on small rectangular closed loops which enclosed
each tendon, and outer closed stirrups which enclosed the entire deviation saddle. These
bars were anchored under the top mat of reinforcement of the bottom flange. The deviation
saddle geometry was changed to a horizontal top surface with vertical sides. The tendon
configuration for specimen 4A was representative of a deviation saddle on the outside of
a small radius curve. The tendon configuration for specimen 48 was representative of a
deviation saddle on the inside of a small radius curve. Both specimens had two tendons
which had both vertical and horizontal deviations. The objective of specimens 5A and 58
was to further evaluate the effect of epoxy coated reinforcement. Specimens 5A and 58
were companion specimens to specimens 4A and 48 with the only difference being that the
reinforcement was epoxy coated.
Prestressing 261
TESTING PROCEDURE
A specially designed testing apparatus shown in Fig. 5 applied load to the deviator
just as it would be loaded in a bridge. This load was applied incrementally. The generalized
test setup could accommodate a variety of specimen si:.;es, tendon layouts and loading
schemes. Specimens were usually loaded in two cycles. The first load cycle generally
continued until yield of the reinforcement, and the second load cycle continued to failure
of the specimen. Strain gages were placed internally on the reinforcement of the deviation
saddle to determine contributions of individual reinforcement bars.
TEST RESULTS
Physical behavior of each specimen was observed and noted for the full range of
loadin@J. This included general observation of the deviation saddle, their cracking pattern,
reinforcement fracture locations, and strain data. Detailed results for each test are provided
in References 2 and 4. Typical test results and photographs before and after failure are
shown in Figs. 6-11.
The symbol D and e respectively correspond to the magnitude and direction of
the deviation force on the deviator. The positive horizontal axis is directed towards the
center of the box, and the vector direction is measured clockwise from this axis. The symbol
Do is the nominal design jacketing force for the specimen (0.8~uAp,) based on the total
allowable force of the prototype tendons. The symbol e. is the nominal design jacking
load vector force direction. Since external tendons are basically an unbonded type of post-
tensioned construction, it is likely that the maximum jacking force is the highest tendon
load that would be exerted on the deviators. The ratio of D/Do is equal to the deviation
saddle factor of safety. The strain gage plots typically indicated that at early load stages
the maximum strains occurred in reinforcement located directly above the tendon with the
highest deviation force, while at later load stages after a considerable amount of cracking,
the highest strains were in the link bar or loop bar reinforcement legs which were acting
in direct tension. The fracture locations in the legs of the reinforcement acting in direct
tension confirm this (see Fig. 10). For the modified specimens (4A, 4B, 5A, and 5B), it is
significant to note that all the strain gages indicated yield of reinforcement which revealed
efficent use of the reinforcement. Final failures were generally explosive and dramatic with
many of the deviator bars fracturing and splices opening (see Figs. 10 and 11).
For making strength comparisons, the critical load stages were denoted as microc-
racking, visible cracking, first yield of the reinforcement, and ultimate. Microcracking was
asumed to be indicated by the first apparent jump in strain indicated by the strain gages
(see Fig. 8). Visible cracking was noted when the first surface crack appeared. Yield of the
reinforcement was noted when any of the strain gages reached the yield strain, and ultimate
load stage was apparent due to the explosive nature of the failure. Magnitudes of these
critical load stages and the nominal design load D. are given in Table 3. All specim!'ns
which were intended to be properly detailed deviation saddles (all specimens except 2A
and 2B) had an acceptable factor of safety for ultimate load (values ranged from 2.24 to
3.16). The factor of safety was adequate for the yield load stage for the properly detailed
deviation saddles 1A, lB, 3A, 3B, 4B, and 5B (values range from 1.6 to 2.08). However,
for tests 4A and 5A, the factor of safety at the yield load stage was unacceptably low,
1.33 and 1.06 respectively. The factor of safety against visible cracking was adequate for
specimens 1A, 1B, 3B, 4B, and 5B (1.3 to 2.03). However, it was marginal for specimens
3A, 4A, and 5A (0.78 to 1.03).
262 Beaupre et al
ANALYSIS METHODS
Two separate analysis methods were investigated for each test. The first method
utilized simplified analysis models (direct tension model, shear friction model, and beam
model), and the second method utilized strut-tie analysis models (tie model for direct
tension reinforcement, and strut-tie model for top surface reinforcement). These analyses
models were formulated based on the physical behavior of the specimens. The ¢> factor used
in comparisons with test results for both analyses had a value of one since the material
strengths and specimen dimensions were known accurately. The analysis of the direct
tension reinforcement was the same for both methods.
In the simplified analysis method illustrated in Fig. 14, the direct tension model 1 is
used for the analysis of the direct tension reinforcement in the deviation saddle. The shear
friction model 2 explains the actions of the shear friction reinforcement which transfers
the shear across a crack interface which may form below the tendon ducts. The beam
model3 explains the action of the top surface reinforcement which provides added strength
to the deviation saddle to resist pull-out forces. This reinforcement is stressed like tensile
reinforcement in a beam, and it also distributes surface cracks.
For the second method referred to, two separate strut- tie models, shown in Fig. 15,
were developed. One models the contribution of the primary direct tension reinforcement
and the other the contributions of the top surface reinforcement. The strut-tie model is
based on the premise that reinforced concrete structures carry load through a set of com-
pressive struts which are distributed and interconnected by tensile ties. The reinforcing
bars utilized in direct tension in the deviation saddles are simply tension ties linking the
deviation force to the box reinforcement. The strut-tie model for the top surface reinforce-
ment resistance is a combination of compressive struts branching from the average location
of the tendon duct to the tension tie which is the top surface reinforcement. Complete
details and results of the analyses are presented in Ref. 4. Comparisons of test results with
analytical predictions are included in Table 3. The values shown are at ultimate and the
analytical results are based on the measured ultimate strength of the reinforcement in or-
der to show the accuracy of the analysis method. Design would be based on reinforcement
yield points and introduce further conservatism.
Prestressing 263
CONCLUSIONS
The following conclusions can be drawn based on the ten deviation saddle tests of
this investigation.
1) The safety of deviation saddles has been verified in this investigation. Properly
detailed deviation saddles will perform adequately under service load conditions
and have a sufficient factor of safety at ultimate.
2) Excluding the purposefully misdesigned specimens 2A and 28, all specimens except
specimens 18 and 38 exhibited adequate ductility and thus gave sufficient warning
of the impending explosive failure. The specimens which resisted the pull-out force
mainly by direct tension reinforcement (specimens 4A, 48, 5A, and 58) always
displayed adequate ductility because the reinforcement had to strain substantially
to fail.
3) The epoxy coated reinforcement had adverse effects on the behavior of the devia-
tion saddle at microcracking and visible cracking stages. However, at the critical
strength stage of yielding, coated reinforcement has little effect on the behavior.
The well anchored coated reinforcement favorably affected the behavior of the
deviation saddle at the ultimate load stage.
4) From the cracking patterns and the strain data, three behavioral mechanisms
were evident in the deviation saddle. They were the pull-out resistance of the
direct tension reinforcement, the flexural beam type resistance of the top surface
reinforcement, and the shear friction resistance of the specimens across the critical
cracked plane which was observed to be directly below the tendon ducts. The
pull-out resistance of the direct tension reinforcement and the effective bending
of the top surface reinforcement are additive. Some uncertainty exists concerning
the effectiveness of this top surface reinforcement at the yield load stage of the
deviation saddle. The top surface reinforcement is beneficial in controlling and
distributing cracks on the top surface of the deviation saddle.
5) All final failures (except with special specimen 28) were the result of the fracture
of the direct tension reinforcement. Test observations and analysis indicated that
in all of these tests shear friction did not appear to be critical to the failure of the
deviation saddle.
6) The capacity of the specimens could be determined by either the simplified anal-
ysis models or the strut-tie analysis models. Both analysis methods appear to
produce reasonable agreement with the test results, although both methods rely
on subjective assumptions for the analysis of the top surface reinforcement.
7) In comparing the two types of reinforcement which are utilized to resist pull-out
force in this study (direct tension reinforcement and top surface reinforcement), it
is obvious that the direct tension reinforcement (the link bar in specimens 1A, 18,
2A, 3A, 38 and the loop bar in specimens 4A, 48, 5A, 58) is significantly more
efficient than the top surface reinforcement in resisting the deviated force.
8) The critical force which acts on the deviation saddle is the deviation force con-
tributed by the tendon with the maximum deviation component. In this test
series, this is the force that was closely confined by the direct tension reinforce-
ment. In the early configuration (specimens 1A, 18, 3A, and 38), this was the
264 Beaupre et al
deviated force of the corner tendon which had both vertical deviation and horizon-
tal deviation. The other tendons of the early specimens did not greatly influence
thP deviator capacity of the specimens because they were not enclosed within the
critical reinforcement (direct tension reinforcement). In the revised configuration
(specimens 4A, 4B, 5A, and 5B), both tendons were enclosed in separate direct
tension reinforcement, but the corner tendon was more critical since it had greater
vertical deviation than the other tendon. The basic direct tension reinforcement
around the critical tendon should be proportioned for this maximum tendon devi-
ation force. The other tendons could be provided with the same reinforcement to
simplify detailing, or some lesser amount determined by a similar analysis based
on the individual tendon deviated force.
RECOMMENDATIONS
The following recommendations are made based on the ten deviation saddle tests
of this investigation. Recommendations are focused on the deviation saddle since it is the
weakest of the three basic types of tendon deviators. However, these recommendations can
be conservatively applied to the diaphragm and rib or stiffener since these type of deviators
generally have added strength contribution from the concrete.
1) Total service load design forces for the deviator should be the sum of the vertical
and horizontal components of the deviated force from each tendon. These can be
calculated as the maximum allowable initial jacking force multiplied by the size
of the angle change for the vertical and horizontal planes of the tendon. Under
AASHTO Specification5 , the maximum allowable initial jacking force is limited to
80% of the ultimate strength of the tendon (0.8(fpu)(Ap,)).
2) At service load levels, reinforcement stresses should be limited to the specified
allowable stresses in AASHTO Sec. 8.15.2.
3) For load factor design, neither AASHT0 5 nor ACI 1 1 clearly specify an appropriate
load factor for the prestress tendon force. In view of the explosive nature of
failure, and in order to guarantee a reasonable factor of safety commensurate with
other load and resistance factor combinations, it is suggested that for this specific
application the load factor on prestress force should be at least 1.7. Conventional
reinforcement should be assumed at the yield point. The t/J factor that should
be used in the design of the direct tension reinforcement should be 0.90 since the
primary acting force is tension. The t/J factor for the shear friction calculation
should be 0.85.
4) The recommended design detail is very similar to the modified deviation saddle
detail (specimens 4A, 4B, 5A, and 5B) of the test series shown in Fig. 4. The
general approach to the design of the deviation saddle should be to rely only
on the very efficiently utilized direct tension reinforcement for the pull-out force
resistance of the deviation saddle. Any contribution to the pull-out resistance from
the concrete is ignored as is any additional resistance from any beam type element
above the tendon ducts.
For the direct tension reinforcement, utilize small closed rectangular stirrups (la-
beled as loop bars) along the entire deviator tendon axis which loop around each
individual tendon duct of the deviation saddle and are well anchored in the box-
deviator corner node under the top mat of reinforcement of the bottom flange.
Additionally, provide closed tie reinforcement which encircles the entire corner
Prestressing 265
node, ties the node into the web and flange, and provides reinforcement along the
deviator top surface for controlling and distributing surface cracks (this reinforce-
ment should be neglected in the calculation of the pull-out capacity). An amount
of closed stirrups of the same area and spacing as the loop bar reinforcement should
produce very satisfactory results.
Each individual loop bar group should be designed with the specified load factors
and tjJ factors to resist the full pull-out force of the tendon with the largest vertical
deviation. It will be more economical and will minimize fabrication errors to
provide the other tendons with the same reinforcement regardless of their tendon
deviation forces. The dimensions of the loop bars and the outer closed stirrup
must be based on the tendon duct curvatures and outer diameters, reinforcement
clearances, and development lengths. For the loop bars, the minimum clearance
at the highest point of the tendon duct should be approximately 1". The vertical
inside dimension of the outer closed stirrup should be at least 2" larger than the
loop bars. The maximum bar size utilized for the loop bars should be limited to
a deformed #5 size so as to be able to fully develop the 90° hook.
5) Deviation saddle geometry utilized should be a horizontal top surface with vertical
sides. This makes fabrication of the segments easier and provides the lowest height
deviation saddle possible, which is critical in shallow highway bridge structures for
clearance of deviated tendons from adjacent deviation saddles.
The concrete dimensions of the deviation saddle are controlled by the requirements
of the tendon duct curvatures and outer diameter, reinforcement clearances, and
cover requirements. The lowest point of the tendon duct above the top of the
bottom flange should be based on required clearance (1" to 2") for constructability
(protective sheathing placed on extension of tendon duct is generally used for
external post-tensioning). The transverse location of the ducts should be as close
as possible to the web wall since it is desirable to have as small of an eccentricity to
the web as possible to minimize bending moments in the bottom flange. The width
of the deviation saddle in the longitudinal direction of the bridge is dependent on
the spacing and amount of reinforcement (4" to 6" center to center reinforcement
spacing is recommended to allow constructability). Also, it is dependent on the
minimum radius that the tendon duct can be bent.
6) Provide a full bottom flange width deviation saddle as shown in Fig. 16 for curved
spans with small radii when all the tendons in a deviation saddle have large hori-
zontal deviations. For straight spans, when the horizontal tendon angles are small
(less than 3°) and the horizontal components are directed either into the web or
away from the web, it should only be necessary to use a deviation saddle which
is similar to those tested. It may also be a advisable to provide the full bottom
flange width deviation saddle no matter what the tendon deviations are when
epoxy coated reinforcement is being utilized because it was observed in this test
series that the specimens with epoxy coating reinforcement cracked at a much
lower load than that of the conventionally reinforced specimens (averaged 24%
lower). Since the reinforcement is being epoxy coated because of severe corrosion
conditions, it would be advantageous to go one step further and provide the full
bottom flange width deviation saddle which will substantially increase the factor
of safety against visible cracking.
266 Beaupre et al
A reduction in concrete volume for the full bottom flange width deviation saddle
could be made by reducing the longitudinal dimension of the deviation saddle by
one-half in the center of the bottom flange at a certain distance from the tendon
ducts. Near the webs the deviation saddle would be the same as the models tested,
but would be joined to the opposite deviation saddle by a concrete strut half the
dimension of the deviation saddle.
7) In cases where a full bottom flange width deviation saddle is not provided, a
shear friction calculation should be made. In most cases, extra shear friction
reinforcement will not have to be provided since there is usually an excess of direct
tension reinforcement at the critical shear plane. Also, the outer closed stirrups
contribute to the shear friction reinforcement. The shear friction equation that
should be used for this check is Equation 8-10 of AASHTO Sec. 8.15.4.3. Any net
tension across the shear plane is taken into account by subtracting it from the total
capacity of the reinforcement crossing the shear plane. The maximum allowable
shear strength provided by this equation is the lesser ofthe two values, 0.09~Acv or
360Acv where Acv is the area of concrete section resisting shear transfer. This area
is assumed to be the area below the tendon ducts from the centerline of tendon
closest to the web wall to the front face of the deviation saddle. The mu factor is
taken as 1.4 since the deviation saddle is monolithically cast.
DESIGN EXAMPLES
Two design examples are presented to help clarify the recommendations discussed
above. The first one is shown in Fig. 17a and b for a deviation saddle from a straight span.
Since the horizontal deviations are less than 3°, a deviation saddle similar to those tested
is assumed. The second design example is shown in Fig. 18a and b for a deviation saddle
from a curved span. A full bottom flange width deviation saddle is assumed because the
horizontal angles are quite significant.
ACKNOWLEDGEMENTS
REFERENCES
4. Beaupre, R.J., Powell, L.C., Breen, J.E., and Kreger, M.E., "Deviation Saddle Be-
havior and Design for Externally Post-Tensioned Bridges," Center for Transporta-
tion Research Report No. 365-2, The University of Texas at Austin, June 1988.
Yield Ultimate
Size Strength Strength Yield Strain
(ksi) (ksi) (micro in.fin.)
#1.25 36 51 1240
#1.5 45 63 1550
#2 45 63 1550
Compressive
Specimen Strength (psi)
Thst lA 5650
Test 1B 5650
Test 2A 5700
Test2B 5750
Test 3A 6000
Test 3B 5800
Test 4A 5700
Test4B 5700
Test5A 5400
Test5B 5400
~
Diaphragm Anchorage .J ~
[fJ
~
[fJ
.. .
[fJ
~
Cfq
t-.:1
Figure 1. External Post-Tensioning in Long Key Bridge (From Ref. 1)
$
270 Beaupre et al
a) Diaphragm
b) Rib
c) Saddle
Figure 2. Deviator Types
Prestressing 271
(#1.5 bar)
(4 req'd)
(10 roq'd)
·[0
l7.:'f
(5roq'd)
,. I
t::F~
• 2.25" ..
20
en
Cl..
::;::: 15
.........
w
~ 10
0
u..
5
0
..,
... ... ..,~ ~ 0
"'
ot) ot)
-..., w w
w
N
w
N
w
N
~
~
CL
2
~
~
0
i= lJ""""
~55
0::::
Ci
50
w
ot)
~
-... ~
ot)
~
~ ~
0
N
w
ot)
N
w
"'
N
~ ~ ~
"'~ "-0
~
C)
~
~ ~
(/) V>
0
(/)
N
V>
~
~
~
~
~ 2
~
D.
D.
:' , . ! LS 12.
13 t.·(-~
.· .· - 7
LS . ,.,,.......•' .'''....
,,,.,,
2 '.' '.
$ .1 }
., .D ..
.
1
.
...,.·.;,.
···::;:..: :·:: .. ',.. i'{>> LS 23
LS 7-FIRST CRACK
_...__ PHASEI
--.....__PHASE/I
~
(/J
......
,..,
~
(/J
TOP FACE (/J
s·
(fq
25
I -H-
--9--
"8" GAGE
"C" GAGE
en
~
.:
'ij
0+-----~--~------~--~----.----.-----.----.-----,
0
0
0
0
8 80 8 80 8 8 0 80
~ ~
ll) ll) ll) I()
I N P"l '<!"
::::15
(.)
- - - "G" GAGE
-m- "H" GAGE
0:::: -+- "I" GAGE
0
lL. 10 _ _.OF
,~~~~"'
"A" "0" "G"
5
\ ·slc·Q·E··F·Q·w
closed stirrup "I" loop bars
~
rJl
0+----+----~---,--~~----r----r----~---T----, .......
0 g g g ~
8 8 0
~
~ ~
80 0
~
8 rJl
I
0
""
~
""
~
n
0
-.:t
s·
rJl
crq
STRAIN (MICRO lN./IN.)
Figure 9. Test 4A Reinforcement Strain Data - Phase 2 t...:l
-.)
-.)
278 Beaupre et al
"A" Side
EBFracture location
\
EB
I fi [J AIII"P' tailed
\
EB
I 0 0
\e I 0 0
\
EB
I 0 0
0 0
Tendon 2
0 Tendon 1
3.------------------------------------------------, §
'i:l
~
~ AVERAGE ('!I
.......
2 ·+---- e.
0
0
',,
0
0
C) C)
_,
0 w
z z w ~
.:::.c ~ ~
u u >-
~ ~ ~
::::::>
u u
0
a:::
u
_,
w
m
::;'E Vi
5
Figure 12. Average Factor of Safety for Critical Stages
COMPARISON OF REINFORCEMENT TYPES
RATIO D/Do FOR PROPERLY DETAILED DEVIATION SADDLES
3 1.18*
~ AVG. UNCOATED 2.78
()
0 ~ 0 w
z z _J
~
sz
u
<{
~
u
w
>= ~
i=
~
C/l
f1:_ _J .......
0:::
u u ~ ~
*Ratio of epoxy coated reinforcement specimen strength to C/l
0 C/l
w
u
0::: _J
m
the uncoated reinforcement specimen strength s·
crq
:::;?; in
>
1:-.:)
Figure 13. Comparison of Factors of Safety for Reinforcement Types
co
......
282 Beaupre et al
Closed Stirrup
Open Stirrup
a) Early configuration
\
\J
~F
c~~ r "'
Link
fR
};ill
-~
/ '-../
bar ' •I L [5 \.
Compression Struts
Tension Tie
t::l:l
Cb
~
"t:l
~
Elevation Cb
.....
e..
Strut half the width of deviation saddle
Plan View
Fi,gure 16. Plan and Elevation of Full Bottom Flange Deviation Saddle
Prestressing 285
Tendon 2-19..0.5•0 270 ksi strands Aps-2.91 sq. ln. (closest to web waD)
Tendon 1-12-0.5·0 270 ksl strands Aps-1.84 sq. ln.
fc-6000 psi Grade 60 reinforcement
Load Factor-1.7
0-0.9 (Tension)
0-0.85 (Shear)
I of loops-2.83 sq. inJ(2(0.20 sq. in.))-7.1 use 7-#4 loops each tendon
use 7-14 closed outer stirrups
Shear frictjon check,
Vu-(0Asfy-Nu)~ AASHTO Sec. 8.15.4.3
Area equal to two legs of 7 loops for each tendon and one leg of 7
outer closed stirrups
~~a~:~
Development-90" hook
lhb =1200(db )/(f'c)112 =7./
ACI12.5.3.2 Factor=0.7(1oops only) 25"
I dh =7./(0.7)=5.4" uses· O.K.
Provide fun bottom flange width deviation saddle since sman radius
curved span
Tendon 2-19-0.6•0 270 ksi strands Aps-4.09 sq. in. (closest to web wall)
Tendon 1-19-0.6.0 270 ksi strands Aps-4.09 sq. in.
rc-6000 psi Grade 60 reinforcement
Load Factor-1 .7
0-0.9 (Tension)
0-0.85 (Shear)
Oesjgn tendon loops based on 122 9 k
Fu-0(As)(fy)
~~
38"
LCJ
115 closed outer stirrup
I (lap- B"ll
~
Development-90' hook
lhb =1200(db )/(f'c)112 =9.7" 29"
ACI12.5.3.2 Factor=0.7 (loops only
ldh =9.7"(0.7)=6.a" use a· O.K.
289
290 Menn and Gauvreau
2. Dynamic Behaviour
4. Fatigue Behaviour
FUTURE PROSPECTS
REFERENCES
M
3. 33 3... 3.. . 3... 3.3. 3.. .
p;Aj · ~ · ~~
s=
~
::l
::l
~
::l
0...
CJ
~
SECTION .:
<
~
~
~~~~-,r,,----=---=..--,rr
I' 'I
--==.=;;- t'J -~---=--,.,.---==
I' ,
---,'11_.=-....=-_--,~,1
"
II
'I
.,L-=---=--=
'"
nl
' 'I IL•
hi
II
II
_jUL-==---=- _jLJL_-=_Jj --:-;
l_l=---=-=- _juL__==--_jUL_-=---=-
~ LJI
nl
IIL•I
lnl I'
_jr
1
PLAN
r-
0
q ,.,,
I<
,.,,.,
,,-i$& z
~
"'en
p.
,.._
i_ II
II
-
l
l
<(
a..
~
•rl
~
0
;
<D (/) -rl
,.,C7l z
'-'
u
QJ
0 en
0 f--- ~- --- - ~ I-
-i z ~
,.._
,.,
C7l
0 "'
u
·rl
<D
• •••••••
II i= p.
:>,
II u '-'
L&J
(/) ~
..
•••••• ,....- QJ
,.,,., ., ~ .....
'"Cl
s
0
QJ
~
"'u
U)
I
r: I
0 <')
q
- , ., ()()
·ri
""'
[>
L
-
302 Menn and Gauvreau
100 ·•
--
0
Q.
98
96 \
\
-en
~
0 94
92
\._
.,.,
en
w 90
............1'--.
a:
1-
en
88
~.- ..._._1--·- ........ 1-o
86 •
84
0 10 20 30 40 50 60 70 80 90
TIME (Days)
Fig. 5--External tendon stresses under permanent load
-
2.5
E
- ;·
E 2.0 •~·...... ·-· ~ ........
.,
,................
z 1.5 • ~ .......
0
........\
1-
(.) 1.0 1/
I!
w
...J
~
u. 0.5
w
c
0.0 .•
0 10 20 30 40 50 60 70 80 90
TIME (Days)
Fig. 6--Slab deflections at midspan under permanent load
304 Menn and Gauvreau
12
-
--
10
>-
c.. ~
~ 8 ~~~
0
~'\)~
().'\) (S
en 6 -:.
en ~c
w 4
a: 0 '((12
1-
en ooo ~~'((\
2 - '\':>
~c-
-E
-zE -5
-20
305
306 Rabbat and Sowlat
where
fsu* = average stress in prestressing steel at ultimate
load, psi and
fse =effective steel prestress after losses, psi.
Based on this equation, the flexural strength for the
Unbonded Tendon Girder was calculated at 4380 kip-in. (495
kN m) assuming six effective strands. Therefore the Unbonded
Tendon Girder exceeded the calculated strength during the first
loading cycle by 29 percent.
CONCLUSIONS
REFERENCES
1. Sowlat. Koz and Rabbat, Basile G., "Testing of Segmental
Concrete Girders With External Tendons," Journal of the
Prestressed Concrete Institute, V. 32, No. 2, March-April
1987, pp. 86-107.
2. Virlogeux, M., "External Prestressing," IABSE Proceedings,
International Association for Bridge and Structural
Engineering, P-62/82, Zurich, Switzerland, 1982, pp.
101-108.
3. Standard Specifications for Highway Bridges, American
Association of State Highway and Transportation Officials,
Thirteenth Edition, Washington, D.C., 1983.
First Second
Loading Cycle Loading Cycle
Maximum Residual Maximum
Maximum Deflec- Deflec- Maximum Deflec-
Test Girder Moment* tion tion+ Moment* tion
(kip-in.) (in. ) (in. ) (kip-in.) (in. )
A-,s-,A-,
II
2 4
·- I Ill I II II II II
. ..
+0041 s041 A.-I
12'-o'j Nine Segments at 3'- o"
31'- o"
I
.·-
12'-0"
:
4'-o" 4'-o"
I
11fl
2'-4''
I
I
I
14 1'-4"
Section A-A
.I I.
Section B·B
Bonded Tendon Girder
LeQend
e 0.6-1n.01a Strand
• 0.5-in 01o Strand
15'-6"
8
Cycle 2 Bonded Tendon
J.'\.-,r-Unbonded Tendon
Applied 5
Moment, -v.A.!:-")J
1000 kip -in.
4
II
3 )1
2 /-/' Metric Equivalents:
// 1000 kip-in.= 113 kN.m
/ / lin.= 25.4mm
/~·
/•
Deflection , in.
315
316 MacGregor, Kreger, and Breen
ACI member Robert J.G. MacGregor is a Senior Engineer for Arvid Grant and
Associates in Olympia, Washington. He received BS and MS degrees from the University
of Alberta in Edmonton, Alberta, Canada and a Ph.D. degree in Civil Engineering from
The University of Texas at Austin in 1989.
ACI member Michael E. Kreger is an Assistant Professor of Civil Engineering at The
University of Texas at Austin. He received BS, MS and Ph.D. (1983) degrees from the
University of Illinois at Urbana-Champaign. He is a member of ACI Committee 318-C,
Analysis, Serviceability and Safety, ACI-ASCE Committee 352, Joints and Connections,
and ACI Committee 215, Fatigue of Concrete. He has conducted research in the areas of
repair and strengthening of concrete structures, behavior of reinforced concrete buildings
subjected to seismic loads, and behavior of prestressed concrete bridge structures.
John E. Breen, FACI, holds the Nasser I. Al-Rashid Chair in Civil Engineering at The
University of Texas at Austin. He is the past Chairman of ACI Committee 318, Stan-
dard Building Code, and is a former chairman of ACI-ASCE Committee 441, Reinforced
Concrete Columns, and of ACI's Technical Activities Committee
INTRODUCTION
A significant number of precast segmental box girder bridges with external pre-
stressing tendons have been constructed in the United States and Europe. Substantial
economic savings have been indicated for this type of construction. However, questions
have been raised as to how these bridges will beha,ve when subjected to loads greater than
service-level loads. It is not known to what degree the behavior of these bridges will re-
semble the behavior of monolithic, fully bonded or unbonded prestressed concrete girders.
In addition, segmental box- girder bridges have been constructed with epoxy between the
match-cast segments (epoxied joints) and also without any type of joinery material in the
joints (dry joints). It is not known whether epoxied or dry joints have any influence on the
stiffness, strength, or ductility of the structure.
A one-quarter scale three-span externally post-tensioned box girder bridge model
was constructed in the Ferguson Structural Engineering Laboratory at The University of
Texas at Austin. The model was load- tested to determine the level of strength and
ductility that may be expected for precast segmental bridges with external tendons, current
tendon anchorage and deviation details, and alternate joinery details. A description of the
experimental program, evaluation of selected test results, and conclusions follow.
TEST PROGRAM
The model bridge, shown in Fig. 1, was a three-span segmental box girder with
geometric symmetry about the center of the bridge. Figure 2 shows a plan view and
elevation of the structure. Each span contained ten typical segments, and over each support
was a pier segment containing the anchorages for the prestressing tendons. Because the
typical segments were match cast separately from the pier segments, a cast-in-place closure
Prestressing 317
strip was provided between the typical segments and the pier segments at the ends of each
span. Joints between typical segments were either epoxy filled or dry (no epoxy). Both
the south and center spans contained epoxied joints.
Cross sections for typical segments and pier segments are presented in Fig. 3.
The typical segment shape was chosen to give a span-to-depth ratio (18.75) and efficiency
rating (0.60) typical of contemporary construction. A modified box section was developed
for use in the model structure to provide access to the external tendons. Webs were shifted
towards the center of the box to facilitate moving the draped external tendons outside the
box. At midlength of each typical segment was a full-height diaphragm through which
external tendons passed freely or were deviated as required.
Shear keys were used on segment faces to transfer shear across segment joints
and to provide an interlock between match-cast segments. Keys were also provided in the
flange regions, with their primary purpose being to assist in aligning the segments during
erection. Details for the shear keys are shown in Fig. 4.
Concrete strength for typical segments was nominally 6000 psi at 28 days. In
order to adequately resist anchorage forces in the pier segments, a concrete mix design
with a minimum 28-day compressive strength of 10,000 psi was used.
A schematic of the post-tensioning tendons is shown in Fig. 5. Tendons were
draped downward from high over the supports to just above the bottom flange near
midspan. Theoretical tendon locatio11.s are shown for sections at the exterior support,
midspan, and interior support. The structure was erected on traveling falsework using
the span-by-span method of construction. Single-span tendons (1A, 1B, 2, 4A, and 4B)
which contained 5-3/8" diameter strands on each side of the box, were used during erection
of individual spans. Additional multi-span tendons (3 and 5) containing 2-3/8" diameter
strands on each side of the box, were added after erecting span 2 and span 3. External
tendons were pressure grouted in their plastic and metal pipe sheaths at deviation points.
In addition to the external tendons, internal tendons were provided in the top
corners of the box and at the ends of the thin top flange. The additional tendons were
provided to augment flexural and torsional capacity, and to control shear lag. All internal
tendons had a straight profile and were anchored at the extreme ends of the structure.
Each internal tendon consisted of two 3/8" diameter strands. All prestressing strand used
in the model structure was Grade 270 low-relaxation strand.
Instrwnentation
Strains were measured in each tendon in the inclined portions near the supports and also
in the horizontal region at midspan.
Distortions along the height of critical joints were measured using displacement
transducers and mechanical crack-width gages. Displacement transducers were attached
to the tension flange of the box, and spanned across the joint. The crack monitors placed
across bottom-opening joints were located at the top and bottom of the vertical portion of
one of the webs and on one end of the bottom flange. For top-opening joints, the inclined
tendons did not allow access to the web regions, so a single crack monitor was attached to
the top flange.
Load Tests
A series of weights to compensate for model effects were applied during construc-
tion to bring the model to the correct dead load configuration.
The three-span model was then loaded to examine the complete range of flexural
behavior for the dry and epoxy-jointed exterior spans. The model was also subjected to
very low-level torsional loads and to loadings that were intended to mobilize the shear
strength of the dry and epoxy-jointed spans. The test program consisted of three distinct
load phases:
• structural characterization
• factored loads
• ultimate strength
The first phase of testing involved loading the structure to the design service live
loads and then increasing loads to higher levels to establish the cracking loads at critical
locations, or the decompression loads at critical joints or existing flexural cracks throughout
the structure. In the second phase of testing, factored design loads were applied to the
structure. In the final phase, the structure was loaded until the ultimate strength was
attained. Failure of both the north and south span (dry vs. epoxy joints) was dominated
by flexural behavior. Exploratory tests were then carried out on the damaged structure to
investigate shear behavior at opening joints.
Each possible load configuration was analyzed using a limit analysis to determine
the location of critical joints. The flexural and shear- test load locations were chosen so
that the same joints were critical for both tests. If two different joints were critical for
the flexure and shear tests, the desired critical shear mechanism may not have developed
properly in the cracked epoxy-jointed span.
So that comparisons could be made with the AASHTO HS-20 truck load, it was
necessary to determine the quantity of applied load that was equivalent to the reduced-
scale service live loads. Because the tests were dominated by flexural behavior, moments
at joint locations were used to convert between service loads and test loads. The applied
"equivalent live load with impact" (LL+I) was chosen to provide the same moment at the
critical joint as the maximum service-load moment calculated at any location. Maximum
service-load moments were determined using influence diagrams developed for each joint.
A schematic illustrating the positions of loads during flexure and shear tests on
exterior spans is shown in Fig. 6.
Prestressing 319
TEST RESULTS
A primary purpose for using epoxy at segment joints is to provide reserve capacity
against joint opening for over-load conditions. In the epoxy jointed exterior span of the
model, cracking occurred through the concrete adjacent to a midspan match-cast joint at
an applied load of 5.4 multiples of live load including impact (5.4*(11+I)). For subsequent
applied load cycles, the load required to decompress the flexural tension fiber, and cause
the crack adjacent to the epoxy joint to begin to open, was measured at an applied load of
2.6*(11+I). This measured decompression load for the cracked south span was somewhat
higher than the measured decompression load of 1.9*(11+I) for the dry jointed north
span. However, this was affected more by difference in effective prestress than joint type.
If zero tension is used as the limit for service behavior, then the epoxy joints provided
a potential factor of safety against joint opening of approximately 2.0. Similar behavior
was also noticed in the epoxy jointed interior span. In setting design criteria, however, it
should be realized that the true factor of safety might be less than this because of traffic
overloads, calculation inaccuracies, actual insitu epoxy behavior, and fatigue behavior of the
concrete/epoxy joint. It would therefore be prudent to specify a small residual compressive
stress in the extreme flexural tension fiber for epoxy-jointed segments without bonded
reinforcerr.ent crossing the joint. In dry joints, without bonded reinforcement crossing the
joint, the beneficial tensile capacity offered by the epoxy is not present, so higher design
residual compressive stresses are recommended.
320 MacGregor, Kreger, and Breen
Factored Loads
After completing the service load tests the three-span structure was loaded with
additional weight to simulate the factored dead load condition of 1.3*DL. Each of the
exterior spans of the structure was then individually loaded with the factored design live
load with impact, 2.86*(LL+I). Factored load tests were not conducted on the interior
span. The structure behaved linearly throughout the load cycle with a slight reduction in
stiffness when the midspan joint decompressed. At these higher load levels the measured
maximum factored live load deflections, as determined in different load cycles, were L/1764
for the dry jointed exterior span and L/2310 for the epoxy jointed exterior span. In this
case the deflections in the dry jointed span are approximately 25 percent more than in
the epoxy-jointed exterior span, with the difference caused by the reduced effective cross-
section in the dry joints and the tensile capacity in the uncracked regions of the epoxied
joints.
The factored-load tendon stress increases in the midspan region of the loaded
span were measured to be less than 5 ksi in all spans. The tendons did not appear to slip
at the deviators for any of the factored load cycles.
Mechanism Behavior
The applied load is plotted against the resultant midspan deflection for the ulti-
mate load test of the dry jointed north span, in Fig. 9. The deflections represent the net
deflection of the structure, at the location shown on the schematic, after adjustment for
support deflections. The deflections increase linearly with applied load up to the decom-
pression load, Pd. As the midspan joints begin to open, stiffness reduces, and deflections
increase at an escalating rate. The stiffness continues to decrease until the support joint
opens and a mechanism forms. For load levels higher than the "mechanism load", Pm,
the stiffness remains relatively constant with slight decreases as the ultimate strength is
approached.
The measured deflected shapes of the three-span structure with factored dead
load (1.3*DL) and increasing levels of applied load are shown in Fig. 10. At the applied
service live load, l.O*(LL+I), and the applied factored design load, 2.9*(LL+I), the deflec-
tions are small and the deflected shape appears as a smooth curve. The deflected shape
remains smooth until the midspan joints open widely at 3.0*(LL+I). Beyond this load,
"hinging" occurs at the midspan joints, and the midspan deflections increase considerably.
When the support joint opens at 4.8*(LL+I) the mechanism forms and deflections begin to
increase very rapidly. Due to reduced flexural requirements, the center span has less post-
tensioning than the exterior spans. The support joint therefore opened on the interior side
of the interior pier segment. The final deflected shape of the structure clearly illustrates
the mechanism behavior of the structure at ultimate load levels.
Because the external tendons are bonded to the concrete section only at discrete
locations along the span, large concentrated rotations must occur at opening joints to
develop the large tendon elongations required for increased tendon stresses. These rotations
allow the internal forces to redistribute to stiffer uncracked regions. This is apparent from
the reaction and joint-moment data for the flexural test of the north span, shown in Fig. 11.
If no redistribution had taken place, these plots would be linear. The changes in slope
indicate redistribution of moments and the related reaction is occurring. The initial slopes
reflect the expected behavior from an elastic analysis. As the midspan joints begin to
open at the decompression load, the resultant loss in stiffness causes a larger portion of
Prestressing 321
the additional load to be carried at the interior support. As loading is further increased,
the support joint opens causing a reduction in stiffness at the support as reflected by the
increased reaction rate. The internal forces then redistribute back towards the midspan
region with the ultimate distribution of internal forces being controlled by the relative
stiffness of the support and midspan regions.
This redistribution of internal forces, caused by "hinging" at the critical joint
locations, will also cause redistribution of the secondary prestress forces near ultimate
load levels. The secondary prestress forces are caused by geometric constraints on the
entire structure when the tendons are initially stressed (2). To develop the required tensile
forces with external tendons, large rotations must occur at the segment joints. As the
joints "hinge" and the mechanism forms, the forces from the initial geometric constraints
dissipate. If the segments are detailed to allow large rotations to occur at the segment
joints, then the geometric constraints will no longer be valid. The geometric constraints,
and the corresponding secondary forces therefore affect the service load behavior, with the
ultimate condition approaching the plastic mechanism behavior.
As loads are increased beyond service levels, the tendon stresses exhibit several
stages of behavior, shown in Fig. 12a. The concrete stress profile at the critical opening joint
is shown in Fig. 12b for important stages of tendon stress development. Initially, before
the joints begin to opep., the tendon-stress increases are linear with the applied load. The
tendon stresses remain linear until the neutral axis at the opening joint reaches the level
of the tendon, Point B, at an applied load that is slightly greater than the decompression
load, Pd. Beyond this load, the tendon stresses increase slowly at first as the increased
moments are resisted primarily by an increased internal-force lever arm. When the resultant
concrete compressive stresses are concentrated in the top flange of the section, Point C,
then additional moments must be resisted by increased tendon forces. To develop the
required tensile forces with external tendons, large rotations must occur at opening joints
resulting in increased deflections and joint openings.
The applied-load stresses for a typical tendon during the flexural strength load
cycle are shown in Fig. 13. Tendon strain measurements were made at the exterior and in-
terior ends of the span, joints (1,2) and (9,10) respectively, and at midspan, joint (5,6). The
midspan tendon stresses remained linear with applied load up to approximately 1.8*(11+1)
when the concrete section had decompressed to the level of the external tendons. This load
is slightly higher than the measured decompression load of 1.4*(11+1). The tendon stresses
increased slowly at first until the midspan joints opened at 3.0*(11+1). At this load level
the resultant compressive stress had concentrated in the top flange and additional mo-
ments were resisted by a direct increase in tendon stress. Subsequently, as the support
joint opened, at approximately 4.8*(11+1), midspan moments increased and the rate of
tendon stress development also increased.
At an applied load of 5.0*(11+1) the tendon began to slip from the interior end
towards the midspan region. Slip also occurred from the exterior end at approximately
6.2*(11+1). The tendon slipped through the deviator when the change in tendon force
exceeded the maximum friction capacity. Substantial tendon slip was noticed in all tendons
at all locations for ultimate load levels.
The increase in midspan tendon stresses corresponding with flexural strength
ranged from 35 to 60 ksi in the midspan region and from 15 to 20 ksi at the critical
support joint. The ACl formula for unbonded post-tensioning tendons (3) was used to
predict the ultimate tendon stresses at midspan and at the critical support joint. The
322 MacGregor, Kreger, and Breen
average measured tendon stress increases in the midspan regions were accurately predicted
by the ACI formula with measured-to-predicted ratios of 0.98 in the north dry span and
1.03 in the south epoxied span. This result is reasonable if it is remembered that the
tests used to develop the ACI formula {5) were conducted on specimens with short span
lengths approximately equal to that used in the model bridge. The AASHTO formula
{4) for unbonded tendons predicts lower stress increases, but implicitly assumes much
longer spans. The slightly higher stress increases in the epoxied span may be due to
the concentration of rotation at a single joint causing larger induced deformations in the
tendon.
The average measured tendon stress increase at the critical support joint was
overestimated by the ACI formula with measured to predicted ratios of 0.61 at the north
interior support and 0.69 at the south interior support. At these locations the effective
depth of the external tendons is reduced because of the drape from the support. An increase
in the ratio of the free length of tendon segments to the effective depth of tendons leads to
reduced stress development under applied loads.
The maximum midspan stress that was achieved in the model tendons was af-
fected by the load level at which slip began. If tendon slip began at a low load level then
the ultimate midspan tendon stress was low. Conversely, if slip did not occur until higher
load levels then the ultimate midspan tendon stress was increased. Therefore, before proto-
type extrapolation can be made, additional information is required to determine the force
transfer mechanism at deviators.
A final comment can be made about the overall performance of the structural
system. The maximum applied-load moment at the center of the north span, for an applied-
load equal to the design service live load (DL+(LL+I)), was approximately 50 ft-kips.
When the ultimate flexural strength was reached in the north span, at an applied load
of 1.3*DL+6.8*{LL+I), the maximum applied-load moment at the same midspan location
was approximately 250ft-kips. With the additional factored dead load, 0.3*{DL), causing a
midspan moment of approximately 30 ft- kips, the overall factor of safety above the service
load condition, with respect to the midspan moment, is approximately (250+30)/50 or 5.6.
Joint Behavior
The local behavior of the segments near an opening joint was affected by the
amount of shear that was being transferred across the joints. In the flexural tests, with the
load applied as a series of forces along the longitudinal axis of the structure, small shears
were transferred across the critical opening joints. In this case the concentrated rotations
occurred either at the joints in the dry span or at a crack adjacent to the precast joint in
the epoxied spans. At ultimate load levels the joint/crack had opened into the top flange
of the girder in both the dry-jointed and epoxy-jointed spans.
The local force transfer mechanism in the segments adjacent to the opening joints
when the flexural strength was reached is shown schematically in Fig. 14a. The joint/crack
had opened into the top flange causing the load to arch across the segment joint. The small
shears that are transferred across the open joints at this stage are carried by the vertical
component of the "arch force" at t!Je joint. The segment reinforcement transfers the shears
from the load point to the edge of the segment, and then the arch action transfers the force
across the joint.
In the shear tests, a concentrated force was applied to the structure so that
significant shear would be transferred across opening joints. In this case, after the joint
Prestressing 323
had opened up through the bottom flange, an inclined crack formed from the load point
to the bottom of the web at the edge of the segment, as shown in Fig. 14b. As load
was increased to ultimate levels, the concentrated rotations occurred at the inclined crack
leaving the joint region in firm contact. This was true for both the dry-jointed and the
epoxy-jointed spans.
The local force transfer mechanism in the segments adjacent to the opening joints
when capacity was reached is shown schematically in Fig. 14b. A compressive strut formed
from the load point to the lower corner of the segment. The segment web reinforcement
transmitted this force across the inclined crack to the top of the segment. The shear force
was then transferred across the joint utilizing much of the depth of the webs.
The reinforcement for the concrete segments near opening joints must be properly
detailed to allow the large rotations required for tendon stress increases. Local truss mech-
anisms, such as shown in Fig. 14, should be developed for the critical segments to ensure
that force transfer can be made across the joints. The bottom longitudinal reinforcement
must be anchored close to the opening joint and must resist the horizontal component from
the transient shears (Fig. 14c) plus an inclined strut running from the load point to the
bottom corner of the segment. The web reinforcement must be able to resist the transient
shear from global loads plus the vertical component of the inclined strut. The web rein-
forcement must be anchored under the bottom longitudinal reinforcement and high in the
section so that anchorage is maintained when the neutral axis shifts to the top flange of
the segment.
CONCLUSIONS
Several important observations have been made concerning the full range of be-
havior of segmental box-girder bridges with external post- tensioning tendons.
1. The structure was extremely stiff for service load conditions, with live-load de-
flections of about L/6000 in the exterior spans and L/7500 for the interior span.
Tendon slip was not noticed during service load cycles. Additional information
is required to assess the problem of fretting fatigue at the deviators of external
tendons.
2. The cracking load in the epox:, joints was approximately twice the load required
to decompress the flexural tension fiber and begin to open a previously cracked
joint. Cracking occurred through the concrete adjacent to the epoxied joint.
3. The structure exhibited linear behavior to load levels higher than the factored
design ultimate load.
4. The maximum applied-load moment in the north span, when flexural capacity
was reached, was approximately 5.6 times the maximum applied service-load
moment in the north span. This indicates that the applied midspan moment has
an overall factor of safety above the service load condition of approximately 5.6.
5. Large concentrated rotations are required at opening joints to cause tendon
stresses to increase with the applied load. These rotations allow the internal
forces to redistribute to stiffer regions. The secondary prestress forces also redis-
tribute as ultimate load levels are reached.
6. The applied-load tendon stresses at midspan of the loaded span, corresponding to
the flexural capacity of the girder, were accurately predicted by the ACI formula
324 MacGregor, Kreger, and Breen
for unhanded prestressing tendons. The AASHTO formula for unhanded ten-
dons underestimated the ultimate tendon stresses at midspan. The applied-load
tendon stresses at the critical support joint, corresponding to the flexural capac-
ity of the girder, were overestimated by the ACI formula and underestimated
by the AASHTO formula. Additional information is necessary, however, before
extrapolations can be made to the prototype structure.
7. Tendon slip was noticed at the deviators in all the tendons at all locations during
the ultimate strength cycles. The tendons also slipped during cracking and joint-
opening cycles.
8. The local transfer of forces across opening joints depended on the level of shear
being transmitted across the joint. For opening joints with small shear transfer,
the joint/crack opened in a flexural mode into the top flange of the structure
with the concentrated rotations occurring at the joint. For opening joints with
large shear transfer, an inclined crack formed from the load point to the lower
corner of the segment adjacent to the joint. The concentrated rotations occurred
at the inclined crack.
A more complete discussion of the test setup, procedures, observations, and con-
clusions are available in Reference 6.
ACKNOWLEDGEMENTS
REFERENCES
± I
~
(:6
7'-0" TOP FLANGE I
(Jq
('!I
4'-0" BOTTOM FLANGE
PLAN VIEW ~""!
I
§
r16" I 0...
~
(:6
('!I
::I
3" 3"
10
77'-0"
ELEVATION
7'-0"
7'-0"
.................. ... ~
~
II"[
__ c,.cocc,. ...
\
16-1"_ _
•
3.5___
~0
c,.,.",."'c.-.c"",.,..l\."'..,"'..,"'~
:.:.>>:.:.:.:
•••••••
• ••• •. •. •. •. •. •
&0
EXTERNAL
TENDONS
............................ "" ......... ,. ...
.-o. I· ANCHORAGE
I
·
4
REGION
b. PIER SEGMENT
1-;--1'
"!
M '<t
M
l_s_
0
2~2 "
" •
"
5"
r~
m~il:IDmBmrt!B§=JJ§E![fTI:§:gmrmmm~tflL ~-PITit:t=
IE 6 I 7 I a I I I 1 o I HI 11 I 12 I 13 I 14 I u I 11 111 111 I 11 I 20 II Sli 2112 2 I 2 3 I 24 I 2 s I 211 27 I 211 21 I 30 I se
NORTH ""---SEGMENT HUMBER SOUTH
PLAN VIEW
ELEVATION
3 1
; : } AT NOIITH UT. a'-"'POftf IUCTION AI )
5,S,Ie.l,1A AT NOftTH ..r. SUPf'OfU {SECnoH Cl)
~
'-.!·}
.,~,, ..
AT SOUTH llfT. IUP'I"'RT (SE:CTIOH A2)
~-;·:,.·;
rJl
......
"1
('!I
rJl
SECTION A SECTION 8 SECTION C rJl
s·
O'Cl
'w
CfJ
--
I t)
N
-
I t)
N
CfJ
CfJ
rn t-
c. t-
w CfJ
..:.::
~
,...
N --
I t)
t-
..J
c(
a:
rn
c.
..:.::
--
It)
w
t-
a:
c(
c
<t
0
..J
-+
N N
II ::;)
~ w I
1-
><
w ,...
0 :I: C/)
w
..J
..J
""":"
..J
LL
-II
+
..J
1-
co
-
..J (!)
u:::
a.
a. a.
N
--
I t)
N
DEFLECTION PROFILE
Service Load Tests of North Span - Live Load Cycles
.03~----------------------~----~------~--~
.01
_..
CD
Q)
.r:. -.01
0
c
~
c
0
:;:o -.OJ
0
Q)
;;:
p p
Q)
0 f_11_,~tt_f !!l. 2P:EQU.(LL+I):12.4 kips
-.05 ~~~~~~~r1-r 1 1 ~ 1 1 1 1 r 1 r 1 1 ft r 1 1 1 1 1 1 1 1 A
-~511 I 2511 I 2511 i i
[Jl
.......
~
-.07~--------------~--------------~--------------~
[Jl
[Jl
0 25 50 75 s·
(J'q
Location (ft from N.E.)
FIG.7 - TYPICAL SERVICE LOAD DEFLECTIONS w
w
.......
332 MacGregor, Kreger, and Breen
Q_ 51. SL
~
........ 25tt 1 25tt
0...
<( 1.3* DL (/)
......
~
(/)
-1 +---------~---------r--------~--------~~--------T---------,---------~--------~--------~ (/)
............ :;:::
01 -.4 (:6
CD (Jq
.s::. 1. 3*DL+3.0*(LL+I) ('II
(J ~..,
c:
!;j
0
-.8
1.3*DL+4.8*{LL+I)
I ::l
0...
ttl
(J (:6
CD -1.2 SUPPORT JOINT OPENS ('II
;;: ::l
CD
Cl
I
-1.6 .f v ""'- 1.3*DL+6.8*{LL+I)
FLEXURAL STRENGTH
-2
I I
0 2S so 7S
Location (ft from N.E.)
..
......
:X
a. 50
......
..
c
0
NE
!fl0 25
•
a:: SE
0 ---
-25+----+----~---,----~--~r---~----r----r--~
-1 1.31>0L 2 3 4 5 7
• a
Applied Load - Equivalent (Ll+l)
(4,5)
200
...... 100
~
I
s...
e
c
0
-100
:2 -200 (NI,11)
-300
-400+----+----~--~----~--~----~--~----~--~
-1 1.3• DL 2 3 4 5
•
Applied Load - Equivalent (LL+I)
7
•
{ il t [.I
~
A B
c ~
rse 1 e ....., 0
(:6
O'Cl
0
~'"!
A INITIAL Pd- DECOMPRESSION
CONDITION LOI\11 ~
(:6
~
Pd Pm
APPLIED LOAD
D
tz:.r t k .r
B. TENDON STRESS
BECOMES NON-LINEAR
C. COMPRESS! VE STRESSES
CONCENTRATE IN TOP Fl ANGE
~
~'"~
~
=
Q...
t;l:j
(:6
Cb
=
t I .1 t I .1
L>.P
c
A B
Pd Pm Pu
Pm- MECHANISM LOAD DULTIMATE
APPLIED LOAD CONDITION
50
~
[fJ
.....
@
-10+---~~--~-+--n-----r----,----+r----~---,.---~ [fJ
[fJ
-1 1.3* DL 1 2 J 4 S 8 7 8 s·
~
Applied Load (Equivalent Model Uve Loads)
p
V 1 > V2
V1+V2=P
EXTERNAL _ __.
a. FLEXURAL TEST TENDON
2P V1 = V2
V 1+V2=2P
b. SHEAR TEST
c. GENERAL
339
340 Naaman
INTRODUCTION
problem to the case of bonded tendons through the use of a strain reduction
coefficient n. It can be shown that the coefficient n depends only on the
steel profile _and txee of lol:l.ding, and needs to be detE;~rmined.o!lly once.Jor
comfif6iiloading-ancftendon
-~-
configurations.
----"-· ·--------·· ______, _____
~-
( 2)
where fps is the stress in the prestressing steel at any loading state, fpe
is the effective stress in the prestressing steel, Fe is the effective
prestressing force, and Aps is the cross sectional area of the steel.
!o--,, J
For a moment larger than the dead load moment and smaller that
the cracking moment, the following equation can be written (Fig. 3):
( 3)
where ~Eps represent the strain change in the prestressing steel in the
section considered due to an increment in bending moment ~M = (M-Mo).
It is also equal to the strain change in the concrete at the level of the steel
afthe section considered, that is:
(~Eps)bonded = (~Ecps)bonded ( 5)
Prestressing 343
nC =
nlcr
-
lg
+ -2 (1 - ~
1
lc r
lg I
Jic/2 M(x) e 0 (x) dx
( 9)
0
Mmax (eo)max
where Mmax and (e 0 )max represent the applied external moment and the
eccentricity of the tendons at the section of maximum moment (here the
midspan section).
( 1 0)
CONCWDING REMARKS
ACKNOWLEDGEMENTS
REFERENCES
3. Nowak, A.S. and Absi, E., Editors Proceedings of the first US-
Eurpoean Workshop on "Bridge Evaluation, Repair and
Rehabilitation," Paris, June 1987, University of Michigan, 705
pages.
11. Burns, Ned H., Charney, F.A., and Vines, W.R., "Tests of One-Way
Post-Tensioned Slabs With Unbonded Tendons", PCI Journal,
September-October 1978, pp. 66-83.
13. Elzanaty, A., and Nilson, A., "Flexural Behavior of Unbonded Post-
Tensioned Partially Prestressed Concrete Beams", Research Report
No. 82-15, Cornell University, November 1982.
14. Mattock, A. H., Yamazaki, J., and Kattula, B.T., "Comparative Study
of Prestressed Concrete Beams With and Without Bond", AQ.L
Journal, Vol. 68, No.2, February 1971, pp. 116-125.
17. Tam, A., and Pannell, F.N., "The Ultimate Moment of Resistance of
Unbonded Partially Prestressed Reinforced Concrete Beams",
Magazine of Concrete Research, Vol. 28, No. 97, 1976, pp. 203-
208.
\
348 Naaman
APPENDIX I
The solution equations for the cracked section, assuming linear elastic behavior, are given below. For a given
moment M, the following equations lead to the stresses in the component materials.
(21)
(22)
fs ~
Ec fct (~)
c (23)
'ps
h
~ (25)
's
2
Eg (26)
f' s - E's
Ec fct (£..:.£)
c (27)
c' s !.i
E's (28)
TABLE 1
Expressions for the Strain Reduction
Coefficient n for the Uncracked State
---------------------------.-------------------------------
Loading Type and Strain Reduction Coefficient:
Tendon Profile Uncracked State
TABLE 2
Solution Equations for the Uncracked State
fps • fpe 11
(Fe+ Mo) 12
13
n (M-Mo) eo
fps = fpe+ S 14
I Eps + Aps (r2 + e~)n
(F + M)
f.p1Aps [
1 +
eo ( d s - y 1) 1 M ( d s - y 1)
15
fes - r-c r2 ] - I
Mo<M<Mcr
~
fs = Ec fes 16
fet • ~[
Ac 1 - e...!LJ
kb + ~
I 17
TABLE 3
Expressions for the Strain Reduction
Coefficient Oc for the Cracked State
M
E
0
F
t Ultimate
Cracked
Elastic Cracked
A Elastic Uncracked
I
I
~
Figure 1
Schematic moment deflection curve of
an externally prestressed beam
l I
w
* **** * ***
1
t t
I
t t
I
~p
8 -l:F-~-4
5
2
I
t t
I t t
~a1.ff31=}
3
1t I N-RABOLIC ---1
I t t t
Figure 2
Typical loadings and tendon profiles
considered in the computation of the strain
reduction coefficients n and nc
Prestressing 353
~ Compression
e>v; 'j
reference state
Fe + MD
I I
:.. ..:I bonded
~€ :
ps :
I
Figure 3
Strain differential between bonded and
Unbonded tendons in bending - Uncracked state
~ I
Figure 4
Typical representation of elastic uncracked,
elastic cracked, and idealized elastic cracked beam
354 Naaman
0.50.---------------------.,
UNIFORM LOADING- SINGLE DRAPING POINT PROFILE
c
w
~
~ 0.30
a:
0
c:(
CJ 0.20
w
lett lg. 0.2
-11:1-
0== ......
lcr/lg = 0.4
0.10 -a- lcti lg .. 0.6
...
+ let/ lg. 0.8
leti lg • 1.0
0.00 +--..----,---r--r---r---r---.,.---r--.---1
0.0 0.2 0.4 0.6 0.8 1.0
lc/L
Figure 5
Typical illustration of the variation of nc
~ Compression
- --------~-r--- F + M
(M >Mer)
dps
,___- reference state
e Fe+ MD
.._I_ _..... :I
ce £
pe
H
I I
:.....r---...i bonded
I
I
A £ I
Ll. ps:
I
~unbonded
I
I
I
Figure 6
Strain diagrams from the uncracked to
the cracked state
SP 120-17
355
356 Muller and Gauthier
l.Scope
The concept of precast segmental construction with
external tendons has been developed extensively since
1978, starting with the construction of the Long Key
bridge.
Since the experience of the four segmental bridges in
the Florida Keys, representing a deck area of
2,200,000 SF, many other structures have been
designed and successfully built using the same
method.
The following list of structures also includes
projects still under construction :
Prestressing 357
Wiscasset, ME 122,000 SF
Dauphin Island, AL 165,000 SF
Sunshine Skyway Bridge, FL 735,000 SF
Escatawpa River,MS 240,000 SF
Albemarle Sound, NC 620,000 SF
I-110 in Biloxi, MS 615,000 SF
I-170 in Glenwood Canyon,CO 75,000 SF
Wando River, sc 740,000 SF
James River, VA 540,000 SF
Neches River, TX 528,000 SF
San Antonio Y, TX 1,300,000 SF
FIG 1.
Crack pattern in segmental bridge
dw
FIG 2
NOTATION AT JOINTS
The deformability of a typical segment can be
obtained by means of a finite element analysis in
order to account for the shape of the section, the
length of the precast segments and the height of the
section in compression at the joints.
The segment is divided into volume elements as shown
in Fig 3.:
FIG 3
FINITE ELEMENT MODEL
Nl
I Fig 4
·-·-r·cr••••d
.mal Aala
. C.O.G.
s ... ,•• Principle of computation
step 2
..
~
u
II
.I .
;.
~ N
,.;
i.
u
~
FIG 6
Example of P/T steel stress-strain diagram
0.100.1
..
0
0
..J
...
0
00
.
..J
Q.
Q. 50
0
DEFLECTION OF EXTERNAL TENDON GIRDER c.E.I.T.P. TEST
0 ~------~------~--------~------~--------~----~--~
0 0.25 0.50 0.7!1 1.00 1.25
1.4T 1.14
DEFLECTION ( ln.J
C.E.B.T.P. TEST
FIG 7
364 Muller and Gauthier
r
Tendons" by K. sowlat and B.G. Rabbat).
The following conclusions may be drawn from the test
results :
- Beyond the design stage, the unbonded beam is more
flexible than the bonded one.
- A complete elastic recovery was experienced after
loading the beams up to 1.7 times the design load in
spite of the substantial joint opening of the
critical joints (0.14 in).
Q Applied
. ood (Kips) ' " 1
Deflecticfr1 (Inches)
~----·
.
k~~
_.-
/.·'
_£:
'
r
lj --Ol:FUCTION OF' UT!NW..
.. _._.f... ,_Tto ""' ~~
~N
~
GR21:1t • TEJT
"'' ·~
I l!!!l!l:lltl
...
~
[!I s.e--• ,._....
e~= s'::.~h:.
T....... I. 2 K!
J """' •.••
C.T.L TEST
FIG 8
366 Muller and Gauthier
AREA ~ 56.25.,
/8 = 48J.5H
c ~ 2.478"
CP ~ 5.522"
0 • 73.512"
_,_ = 6.58"
0
TYPICAL CROSS SECTION
SPAN I
P.T. LAYOUT
SPAN 2
P.T. LAYOUT
SPAN I-JOINT 6
MAX. ULTIMA T£ LOAD /pill' ASSHTOI
1.3 OL • 2./7 (LL •II
13!5' 135'
SPAN I - JOINT 6
MAX. ULTIMA T£ LOAD /pill' ASSHTOJ
1.3DL •0.5GRAD•2.17(LL.[J
-...
!!!
~ 13!5' 13!5'
'i' 'i' :::u SPAN 1- JOINT 6
MAX. ULTIMATE: CAPACITY
1.3 DL+3.49 (LL +II
SPAN /-JOINT 6
MAX. Ul.. TIMA T£ LOAD O>er ASSHTOI
!3 DL • 2.17 ( LL f/)
NO BOND IN DEVIATION 8...0CKS
He • height in comprflsston
PRESSURE LIN£
7.17'../J ..
~ ~ 8. ~ .
~ l! 8;g 8
.,~ .iii"' ~
i
!:! !!
i l i i :l 1" 1
SPAN 1 PRESSURE UNE AT ULTIMATE LOAD !PER AASHTO!
PRESSURE LIN£
Il ~
~
~
l
~
i
i1
SPAN 1 PRESSURE UNE.AT ULTIMATE CAPACITY
r::s
" I I I
30
jllllilfH±t
~ I
~
-
100' Soon s.,.. I
0
100'
-"'
.."'
0
0
-'
25 !'Oj P£YIAT!JN ILOCK 1PA. AS P!:DEVIATION a.oc!( SPa. AT 5'
20
I
19 JOINTS OPEN1NG
OEFLECTIC'N (Ft.)
...
Fig 13
Comparison of several prestressing methods
Prestressing 373
Loll of Eccentricity
8. Conclusion
Prestressing with external tendons has proved to be a
very practical and efficient tool in the field of
concrete bridge particularly with precast segmental
construction. It is not i:t11::~!1.Qed ±o....r.epl.ace internal
pre_f:!ltressing in all st,rl,lct_l,!res, bu!- rather complement
the more conventional prestressing methods with
bo1'lded · tendons .
In term of structural behaviour and design methods,
the experience gained during a period of now more
than ten years has proven the method of external
prestressing to be essentially equivalent to the
method of internal prestressing. Design tools are now
available to analyze and predict the behaviour of
structures pretressed with external tendons at all
loading stages from serviceability limit state up to
ultimate limit state and even actual ultimate
capacity.
It is anticipated that external prestressing will be
used more extensively in the future in concrete
construction, but also in steel or composite concrete
and steel structures.
SP 120-18
375
376 Eibl
1. INTRODUCTION
2. DESIGN ASPECTS
Fig. 1
378 Eibl
Section 8-8
@ @
Section A-A
8 8 8 8
.1._ __ 1 .t. _ __ j
II
CD
Fig. 2
Prestressing 379
L L
J[cc(s)- c.,] ds = 0
0
€11 =~ J
0
cc(s) ds
( 1)
au A = '7•[e,( S) - e,j ds
11=0
Bridge
Fig . 3
Prestressing Prestressing
Wires Wires
Fig. 4
Prestressing 381
3. EXPERIMENTAL RESULTS
? ~ /
Fig. 5
4. APPLICATIONS
11 1 1'111 :v-
I I
7 X 44,50 35.50
509,50m
Fi g. 6
Cable -Layout
Fig. 7
1. 44.aam .1
I. 44.00m .I
Fig. 8
In the case of the railway bridges, for the first time, after a
thorough investigation decompression already under half of the
live load was allowed. Until now full prestress was always been
demanded by the German Railways.
Fig . 9
REFERENCES
Synopsis: A nonlinear finite element analysis was conducted to examine the full range
of behavior of segmentally precast box-girder construction with external post-tensioning
tendons. A primary objective of the study was to examine the effect of dry joints (without
epoxy) on the strength and ductility of box girder construction. A secondary consideration
was the influence of supplemental bonded internal tendons on the behavior of t he structure.
389
390 Kreger, Fenves, and El-Habr
INTRODUCTION
Since the completion of segmental bridges in the 1950's and 1960's in Europe, and
in the 1970's in the United States, segmental prestressed concrete box-girder bridges have
become a predominant form of medium and long- span bridge construction (100 to 650
foot spans) that has been characterized by rapid evolution. Economic factors have contin-
ually suggested refinements in construction practices to increase productivity and minimize
construction time. Each of these developments in construction methods has required in-
novative design procedures. Principal among these are the relocation of tendon anchorage
zones, the use of multiple shear keys, the omission of epoxy from the joints, and the use of
tendons external to the webs and flanges.
A significant number of segmental prestressed concrete box girder bridges with ex-
ternal tendons and dry joints have already been constructed. Substantial economic and
construction time savings have been indicated for this type of construction. However,
relatively little analytical investigation has been undertaken to evaluate the behavior of
segmental bridges, incorporating the new developments, for all ranges of loads. The ana-
lytical evaluation of their behavior is desirable before additional construction proceeds.
A segmental girder with external tendons is modeled with three types of finite el-
ements: a one-dimensional beam element for the segments, a tendon element connected
to the segments by rigid diaphragms, and a joint element that transmits forces between
two segments. Figure 1 illustrates a simple-span girder of two segments modeled with four
beam elements, three tendon elements, and one joint element.
Prestressing 391
Beam Element
(1)
where Ll£ is the increment of strain from the current strain state, £ 0 , and all strains (and
stresses) are positive in compression. Neglecting shear deformations, the assumption of
plane sections gives
(2)
where Ll£a and Ll¢ are increments of axial strain and curvature, respectively. In the finite
element approximations these increments are expressed as
{~;} = (3)
where Ll_y = < Llu 1 , ...Llu 6 > T are the increments of nodal displacements and .!1. contains
derivatives of !f_, the standard linear and cubic shape functions for a beam element [5].
The force-incremental displacement relationship can be expressed as:
(4)
where the following summations over the fibers in the cross-section replace the integrals of
stress:
Po ~O'o;A;, Mo = ~O'o;A;y;
In the summations, E;, A;, y;, and u o; are the tangent modulus, area, distance from the
reference axis, and current stress of fiber i, respectively.
Upon use of Eqs. (3) and (4), the principle of virtual displacements gives the equi-
librium equations
where
Kt = J liT ll.fl.dz (5b)
392 Kreger, Fenves, and El-Habr
in which ill!. is the load increment from the current load l!.o· The quantity (Eo - Eo)
represents the unbalanced forces from previous load iucrcwcnts; it is zero if each load
increment is brought to equilibrium.
After solution for A!!., the strain in each fiber is computed from Eqs. (1) through
(3), the stresses are computed from the constitutive relationships, and summed to give P 0
and M •. Equation (5e) then gives the current internal resisting forces.
Neglecting slippage at the attachment points, the tendons are modeled by axial
elements connected through rigid links to the girder segments. The rigid links represent
the points of tendon attachment at diaphragms (or deviators) and anchorages, which, in
this analytical procedure, are assumed much stiffer than the box girder. Figure 2 shows
the geometry of the tendon element.
As with the beam element, the strain in the tendon can be represented by Eq. (1).
Assuming small displacements, the increment in strain is
(6)
where fl. = t p
< -1 1 > and A'Ji = < Au 1' Au 2' > in the local coordinates of the
tendon, and Lp is the length of the tendon. the force displacement relationship is obtained
by the principle of virtual displacements:
(7)
t _
-
[c
0
s -f31
0 0
o o oJ
c s -{32
(8)
(9)
The current strain in the tendon is given by A£ = fl. tAl!. and Eq. (1), which can be used
to evaluate the axial force in the tendon.
Prestressing 393
Joint Element
Externally post-tensioned bridges have been constructed with no epoxy in joints
betwen precast segments. Under load, the joints may open, causing a redistribution of
internal resisting forces in the girders. The joint opening is modeled by assuming that
deflections are small, sections remain plane, and there is no slippage between segments
across the joint.
The element is shown in Fig. 3. The element has two rotational degrees and two
horizontal translational degrees of freedom to represent the opening of the joint. The ends
of adjacent beam elements (segments) are connected by a distributed spring that only
resists closing of the joint (Fig. 4a). The assumed kinematic relationship at the joint is
shown in Fig. 4b, where the gap is given by
g = .!l.!!. (10)
where .!l = < 1 - y - 1 y >, !!. = < u 1 , ••• u 4 > T, and negative g indicates opening of
the joint. The location, Yc, of the gap opening is defined by g = 0, or
(11)
The value of Yc, when compared to the values of g at the top and bottom, determines the
four states of the joint: fully closed, open at top, open at bottom, and fully open.
The force in the joint spring is I = kg over the depth of contact, s ~ Yc ~ r, where
s and r depend on the state of the joint opening, and I = 0 over the open portion of the
joint. Representing the force in the spring as I =
I:::. I + I 0 and the gap as g=l:::.g + g0 ,
the principle of virtual displacements gives the following force displacement relationship:
I
where P. = < Pl, ···P4 > T, l:::.y = < l:::.u1, ... l:::.u4 > T
and
Using the definition of .!land lo, closed-form expressions for lit and /_ 0 can be formed
in terms of the current state of opening of the joint (7]. The state of the joint and internal
resisting forces can be updated after solution for t::.y.
The joint stiffness, k, used in the model was 100,000 ksi. This was large in comparison
to the axial stiffness of the girder, but was not so large as to result in an ill-conditioned
stiffness matrix or oscillatory solution as determined from a parameter study. Additional
details on the formulation of the model and solution procedure can be found in Ref. 6 and
7.
394 Kreger, Fenves, and El-Habr
APPLICATION OF MODEL
The nonlinear finite element model described in the previous section was used to
analyze a three-span, post-tensioned segmental box-girder bridge with external tendons.
Comparisons are made between computed behavior of a girder with dry joints between
precast segments and behavior of a similar monolithic structure. In addition, behavior of
the segmental box girder with additional bonded internal tendons is examined.
During development of the finite element model and the course of this investigation a
reduced-scale, three-span, post-tensioned segmental box-girder bridge model with external
tendons was designed and fabricated at The University of Texas at Austin. As a matter of
convenience the basic details of the experimental model were used as input for the finite
element model. A plan view and elevation of the model are presented in Fig. 5, and the fiber
models for typical segments and pier segments are shown in Fig. 6. In the finite element
model each segment is divided into two elements, and closure strips at the end of each
span are considered as separate elements with the same cross section as typical segments,
but without reinforcement. The area of each fiber, distance from the fiber centroid to
the reference axis, and material types are given in Tables la and lb. Dead load for the
box-girder model is 1.80 kips/ft, and is applied as concentrated forces at nodes in the finite
element model.
Material behavior is idealized by a second-degree nonlinear stress-strain relationship
for concrete [4], and a bilinear curve for each type of reinforcing steel.
Table 2 lists the properties for the different material types. The external tendons
are divided into elements that span between anchorage locations and deviation points at
the diaphragms, and have a bilinear stress-strain relationship (Fig. 7).
I
The external tendon geometry and prestressing forces used in the finite element
analyses are presented in Fig. 8. Data for the tendons are tabulated below each span. Two
lines of data are presented for each tendon. Each entry of data in the top line corresponds
with the vertical distance of the tendon below the reference axis (Fig. 6) at deviator
locations. Data in the second line correspond with the tendon forces between deviators.
Tendon force is constant between deviator locations because tendons are not attached to
the girder between adjacent deviator locations or between anchorage and deviator locations.
Failure at a joint-opening location corresponds with crushing of concrete in the
compression flange. Concrete crushing is assumed to occur when an average stress of
0.85!' c acting over a rectangular area defined by the width of the compression flange and
a depth equal to fJ1c (as defined in ACI 318-83 [8]) is needed to satisfy equilibrium at a
joint.
However, the monolithic girder first forms a hinge at midspan when the corresponding
prestressed and non-prestressed reinforcement yields. Then, a mechanism develops when
two more hinges form at the closure strips of the interior span because concrete reaches its
limiting strength at the bottom fibers of the girder.
The applied load versus displacement response, and response of one of the tendons
at interior midspan for both girders are plotted in Fig. 9 and 10. The maximum load
capacity, deflection, and tendon stress are 56 kips, 0.67 in., and 194 ksi, respectively for
the segmental girder. In contrast, the maximum load capacity, deflection, and tendon stress
for the monolithic girder are 108 kips, 2.8 in., and 245 ksi.
The low strength and ductility of the externally prestressed segmental girder can be
attributed to the unbonded tendons and dry joints. Because the tendons between deviation
points are unbonded, the strain in the tendon is constant along its length, and the strain at
the critical section is less than what it would be for internally bonded tendons under similar
conditions. Hence, the stress in the tendons increases very little so that when the crushing
strain has been reached in the concrete, stress in the prestressing steel is far below its
ultimate strength (Fig. 10). Also, the existence of joints tends to concentrate compressive
stresses in the concrete at the joints, resulting in "premature" failure.
In the monolithic girder, multiple cracks form in the interior midspan. The absence
of the joints eliminates the problem of concentrated compressive stresses because the cracks
1
are not as deep as the joint openings in the segmental girder. Also, the increased size of
the compression zone allows stress in the tendons to increase to yield at an applied load
of 100 kips. Furthermore, the improved section behavior afforded by distributed cracking
also results in a large increase in ductility.
The degree of ductility reduction indicated for the segmental girder should be viewed
with some amount of caution because of potential errors associated with the assumptions
incorporated in the analysis of the opening joint near ultimate loads. When the joint-
opening width becomes large, it is unlikely that the joint section can be considered plane
any loanger. Also, any overestimation of joint stiffness increases the fraction of the joint
that opens at a given load, and results in a concentration of compressive stresses in the
flange that leads to joint failure at a reduced load.
The segmental girder is considered here with bonded internal tendons in the top
and bottom flanges of the segments. These tendons are composed of the same material
as the external tendons, with a total cross-sectional area of 0.68 sq. in. in the top flange
and 0.34 sq. in. in the bottom flange. The tendons are located at 1.3 in. from the
top and bottom of the section, and are stressed to 185 ksi (before elastic shortening). In
the analysis, the internal tendons are approximated by end forces and two additional steel
fibers in each segment. The response of the girder with internal tendons is compared to the
response of the segmental girder in Fig. 11 and 12. The addition of bonded internal tendons
results in an increase in capacity (from 56 to 65 kips), and a slight reduction in maximum
midspan deflection. The internal tendons increased the compression stress acting over the
entire girder cross section which slightly reduced the initial stress in external tendons at
midspan, and substantially reduced internal tendon stresses at ultimate (See Fig. 12). The
added internal tendons also reduced the width of opened joints.
396 Kreger, Fenves, and El-Habr
CONCLUSIONS
ACKNOWLEDGEMENTS
This paper is based on research sponsored by the Texas State Department of High-
ways and Public Transportation and the Federal Highway Administration. All opinions
and conclusions expressed are those of the writers and do not necessarily represent the
views of the sponsors.
Prestressing 397
REFERENCES
1. Kaba, S.A., and Mahin, S.A., "Refined Modelling of Reinforced Concrete Columns
for Seismic Analysis," Report No. UCB/EERC- 84/03, Earthquake Engineer-
ing Research Center, University of California, Betkeley, April, 1984.
2. Kang, Y.-J., and Scordelis, A.C., "Nonlinear Analysis of Prestressed Concrete
Frames," Journal of Structural Engineering, American Society of Civil En-
gineers, Vol. 106, No. ST2, Feb. 1980, pp. 445-462.
3. Mahasuverachai, M., and Powell, G.H., "Inelastic Analysis of Piping and Tubular
Structures," Report No. UCB/EERC- 82/27Earthquake Engineering Research
Center, University of California, Berkeley, Nov., 1982.
4. Hognestad, E., "A Study of Combined Bending and Axial Load in Reinforced Con-
crete Members," Bulletin No. 399, Engineering Experiment Station, University
of Illinois, Urbana, Nov., 1951.
5. Zienkiewicz, O.C., The Finite Element Method, 3rd Ed., McGraw-Hill, 1977.
6. Fenves, G.L., "Nonlinear Analysis of External Prestressed Bridges," Proceedings,
Ninth Conference on Electronic Computation, American Society of Civil Engineers,
Birmingham, Alabama, Feb. 1986, pp. 192-201.
7. El-Habr, Kamal C., "Finite Element Analysis of Externally Prestressed Segmental
Construction," unpublished M.S. Thesis, The University of Texas at Austin, May
1988.
8. American Concrete Institute Committee 318, "Building Code Requirements for Re-
inforced Concrete (ACI 318-83), American Concrete Institute, Detroit, Michigan.
398 Kreger, Fenves, and El-Habr
0 Beam Element
0 Joint Element
D Tendon Element
I Rigid Link
Tendon
e Lp
e2
Rigid
t u5
e1
tu2
"• (j. • u,
Links
"•( ~l
L
.I \
u4
-
.. u1 _t Reference
Axis
f(Y)
Compression
Compression
y
Reference Axis
Tension g (Y)
------ - ---- ------- ------ ------- ----·-- ------ ------- ------ ------ .................. ------- ------ ------ ------- ------· ~
:I I! ! I I: :I I, I I! I[ I: II J.lhlilli 1: i_l 11 Ji ! I I: ::s
~
Jl "
(Jl
ll:l
4'-0" BOTTOM FLANGE ::s
PLAN VIEW Q...
M
,_.
I
::I:
ll:l
0""
'"I
ELEVATION
I
L 1
2,3
l 4
5
6.5"
8
r-- I
9
y r-
10
r-
........... 11
L
___..,r 12
L 13
14,15
l 16
I
4
6.5" ~
j 7
Reference Axis I 8
10
y
"'
11
12
~~
15
16
17
300
ftu
fty
--------------------
I
I
I
200 I
I
I
I
I
I
I
100 I
I
I
I
.00838 = f:ty 1.0623 = etu
rn
Figure 7. Stress-strain relationship for external tendons
*
Span B
~ lllllllllllllllllllllllllllllll
:;& ;:JJ;;
Tendon B: 10-3/8" dia, A ps =0.85 in.2
...,.
~
y (in.) co
-.82 5.75 6.33 6.33 5.75 -.82 ~
Span C
~ lilllllllillillllllllllllllllll ;:y; I
Jh7
Tendon C1 : 10-3/8" dia., A ps =0.85 in~
..... It)
y (in.) ~ -.77 5.75 6.33 6.33 5.75 3.99<'i
p (kips) 138 144 149 153 157 161 161
-
Tendon C2 ·10 3/8" dia., A ps=
0
y(in.) ~ -1.48 5.75 6.04 6.04 5.75 -.87 ~
~ 0
y(in.) ~-1.91 5.75 5.75 -1.15 ~
120
100
0 Monolithic
0.
;g. 80
i
.3 60
j
a.
0. 40
<(
20
0
0 1 2 3
Displacement (in.}
260
240
--
·u;
.::J!
220
0
0
e
us 200
c:
0
"0
1:: 180
~
160
140
0 20 40 60 80 100 120
Applied Load (kips}
Figure 10. Applied load versus interior midspan stress of tendon B
Prestressing 407
190 .---------------------------~r-----------~
180
"iii
e. Without Internal
If)
If) Tendons
~
Ci5 170
c:
0
"0
c:
Cl) W~h Internal
1- Tendons
160
150 +-----r---~-----r----~----~--~-----r--~
0 20 40 60 80
80
Displacement (in.)
Figure 12. Comparison of tendon stress-applied load response for seg-
mental girders with and without internal tendons
SP 120-20
409
410 Nagele, Das, and Bakeer
INTRODUCTION
CONCLUSIONS
ACKNOWLEDGMENT
REFERENCES
Parameter Value
Pressure (ksf)
Divisions Region(s)
Radial Colatitude Azimuth
4 18 -11.36 6.9 1. 06
Pressure (ksf)
Divisions Region(s)
Radial Colatitude Azimuth
12 38 -6.69 2.36 1. 22
47 -11.12 5.66 1. 21
CENTER UNE
SPRING UNE
'lc 'b
21 Tenttnn,.
e- n/2
21 Tendons
e- n/4
e- = 0
E
(a)
~
"' c
l..
+'
(/)
2f
.
' '===~--:
... a
Center Line
(b)
¢
)
....
.....
B = 0 e- = TI/2
¢ = TI/2 ¢ = TI/2
~0
~
'\ l\ ~~
80 1\
~
\\
1\ \
70
60
1\~\
50
\;~ o
LEGEND
REGION 11
A REGION 36
D REGION 50
o REGION 75
e REGION 107
40
0.40
I~
+'
c
0.30 1
Ill
u
<;::
""
Ill
0
u
o.eo
c
0
.p
u
I
u..
0.10
LEGEND
II 0 REGION 11
A REGION 36
D REGION 50
0 REGION 75
2 3 4 5678910 20 30 40 50 60 80 100
3000
2!100
ll
"Ill0. 1/
~ Ill
.<: 2000
+'
jl
/
0)
c:
Ill
1..
+'
V)
a, 1500
;I .L
+'
E
d
v/;~/
.;:;
:5
1000
/I; 'i'l/
LEGEND
0 REGION II
A REGION 36
D REGION :50
0 REGION 75
e REGION 107
Pressure (-l)liE(ksf)
80
70
Ul
c 60
0
""0
c
QJ
I-
'+- 50
If ~11
v~~
0
!..
QJ
.Q
E 40 j
:::l
z
30
I; I/
vI/ I/
v f LEGEND
0 REGION II
vII
A REGION 36
~p{jl
0 REGION 50
o REGION 75
e REGION 107
20
2 3 4 5 6 7 8 910 20 30 40 50 60 80 100
425
426 Woelfel
The Eurocodes
Eurocode 7 - Foundations;
For the moment, the author can only give his per-
sonal view on how to proceed with the design of struc-
tures with external tendons on the basis of the Prin-
ciples of EC 2. As a matter of the fact, some propo-
sals will be amended during the ongoing discussion,
Prestressing 427
lp • S = R (fs/ls' fc/lc)
The partial safety factors lp and 1M are derived
from statistical considerations and are influenced
from:
The set of safety factors for the SLS and the ULS
is given in tables 1 and 2. The values taken from re-
liability studies [4] are shown in brackets for demon-
stration. When comparing the safety factors for pre-
stressing in ULS, one has to take into account that
the reference value in EC 2 is the mean value whereas
the author uses the 17 %-fractile as reference value.
The factors ~F (for self weight and live load) and lM
contain a partial coefficient taking account of the
uncertainty of the calculation which (in ULS) is
chosen as 1.05.
tendon length 80 m
Prestressing 431
Literature
Notation A area
L span
p tendon-force
R resistance (bearing capacity)
s action effect
f strength
p fractiles
s standard deviation
v variation coefficient
X
x }mean value of x
mean
0 safety-factor
E strain
fJ. E strain-variation
G stress
Indices: c concrete
cr creep
k characteristic
1 lower characteristic value
o zero (eg time = 0)
p prestressing, prestressing steel
rel relaxation
s steel
sh shrinkage
t time
u upper characteristic value
x abscissa (length of the element)
y yield point
F force
M material
Q due to load
J..L friction
434 Woelfel
s L s u L s
acting un- favorable un- favorable
favorable favorable
A Ep s 1) A Ep s 1)
Friction
~p.~ • {1-exp[-~(atkx)]} Epo,max 1.02·10-3 0.35·Afp,~ 0.41·10-3 0.20·Afp,~
-
I
{0.2 roos
with ~ a • 35" k- 0
0.1 I
i
Shrinkage
AEp,s • i';;,s 0.30·10-3 0.35·Afp,s 0.30·10-3 0.35·Afp,s
~
Relaxation
fEp,r - 0.04 £p,x • 0.04(£po,max - ~~) 0.23·10-3 0.30·A£p,r 0.26·10-3 0.30·Afp,r lfl
fi
2.25·10-3 0.1B·Afp 2) 1. 57 .}0"3 O.l25·Afp 2) lfl
lfl
--- - ---
s·
(1q
fyk ----------------------
fyk 'Ys
ULS 6pku
{
Gpkl
Gpku
SLS
{
Gpkl
prestressing x =0
t =0
Ql
1/)
5l
....
u
c:
c:
0
....
Iii due to deformation
of the section regarded
437
438 Nowak, Naaman, and Ting
INTRODUCTION
STRUCTURAL RELIABILITY
ory is available for predicting the expected life, expected failure rate, or
expected time between breakdown of elements (systems), given some test
or failure data for the system and/or its components. In structural engi-
neering the probabilistic analysis have been developed mostly in the last
20 years. It has been applied to safety evaluation of structural members
in buildings and bridges. Little has been done, however, for the analysis
of whole structural systems. The available methodology is presented in
several recent publications, e.g. (4 ).
A structure fails when it cannot perform its function any longer, oth-
erwise it is safe. Limit states are the boundaries between safety and
failure. In bridge structures failure is defined as inability to carry traffic.
Bridges can fail in many ways, or modes of failure, by cracking, corrosion,
excessive deformations (non catastrophic failure), by exceeding carrying
capacity for shear or bending moment (collapse, catastrophic failure), by
local or overall buckling, and so on. Some members fail in brittle manner,
some are more ductile. In the traditional approach each mode of failure
is considered separately. Safety is provided by specifying the design ca-
pacity much larger than the expected loads. Probabilistic methods allow
for quantification of the safety reserve.
There are two types of limit states. Ultimate limit states (ULS)
are mostly related to the bending capacity, shear capacity and stabil-
ity. Serviceability limit states (SLS) are related to gradual deterioration,
user's comfort or maintenance costs. The serviceability limit states such
as cracking, fatigue, deflection or vibration, often govern the bridge de-
sign. The main concern is accumulation of damage caused by repeated
applications of load (trucks). Therefore, the model must include the load
magnitude and frequency of occurrence, rather than just load magnitude
as is the case in the ultimate limit states (3).
A traditional notion of the safety limit is associated with the ultimate
limit states. For example, a beam fails if the moment due to loads exceeds
the moment carrying capacity. Let R represent the resistance (moment
carrying capacity) and Q represent the load effect (total moment applied
to the considered beam). Then the corresponding limit state function, g,
can be written,
g=R-Q (1)
If g > 0 the structure is safe, otherwise it fails.
The limit state function and the associated probability of failure are
clearly defined in case of the ultimate limit states.
In general, due to uncertainties in material properties, dimensions,
workmanship, truck weights and occurrence rate, both R and Q are ran-
dom variables. Therefore, the probability of failure, Pp, is equal to,
BRIDGE LOADS
The major load components of highway bridges are dead load, live load
with impact, environmental loads, earth pressure, and abnormal loads.
Each load group includes several subcomponents. The statistical models
for the various bridge loads are based on available data and on results
from special studies.
Further studies are required to establish the site-specific live load
model, distribution of truck weight, multiple presence in one lane and
in adjacent lanes, and transverse position of truck on the bridge. An ad-
ditional area in need of further research is dynamic load. Further field
442 Nowak, Naaman, and Ting
RESISTANCE MODELS
tion of the analytical model may be very expensive because of the large
size of bridge members. Therefore, the available data about resistance is
still incomplete.
Typical stress-strain curves for concrete, reinforcing steel and pre-
stressing steel are shown in Figs. 2, 3 and 4, respectively.
The ultimate flexural capacity of prestressed concrete bridge girders
can be derived using a nonlinear model of performance. A computer pro-
gram has been developed (7). The statistical data is taken from (8) and
(9). Two phases of the performance are considered: uncracked section and
cracked section. The strains are assumed to be linearly distributed. The
section is divided into a number of horizontal strips of small depth. For
given strains, stresses are calculated using material stress-strain curves.
The bending moment is calculated as the resultant of the internal stresses.
The moment-curvature is obtained by incremental increases in load (bend-
ing moment).
The moment changes under cyclic loading (trucks). If the total bend-
ing moment, Mq, exceeds the cracking moment, Mer, the section cracks
and the tensile strength of concrete is reduced to zero. The crack stays
open any time Mq exceeds the decompression moment, Md (if Mq < Md,
then all concrete is compressed, if Mq > Md then the crack opens).
Moment-curvature relationships have been derived for typical
AASHTO sections, strengths of concrete and levels of prestress. The
results show that the mean-to-nominal ratio of the ultimate moment is
1.04 and the coefficient of variation is about 0.035. The coefficient of
variation is very small because all sections are under-reinforced and the
ultimate moment is controlled by the prestressing tendons.
The strands were 1/2 inch (12.7 mm) in diameter and had a specified ul-
timate strength of 270 ksi (1862 MPa). The computed effective stress in
the steel after losses was 144 ksi (993 MPa). Details of the strand layout
for the midspan and the support sections are given in Fig. 6. The steel
profile is selected to have two draping points each at 30ft (9.14 m) from
the support. Twelve strands are draped and sixteen strands are straight.
Various limit states and conditions were considered: ultimate moment,
cracking, maximal crack width, fatigue in concrete, fatigue in steel and
live load deflection. Reliability indices were calculated using Eq. 4, with
definition of R given in Table 1, and Q defined as applied moment (dead
load, live load and impact).
The moment-curvature relationship for the composite girder was de-
rived using the available statistical data on dimensions and material prop-
erties as reported in Table 2. The resulting average curve is shown in Fig. 7
as a solid line while the dashed lines correspond to the average plus or mi-
nus one standard deviation. The girder midspan moments were calculated
for dead load, Mv, superimposed dead load, and live load plus impact
ML+l· Observed nominal and mean values with bias, standard deviation,
and coefficient of variation are reported in Table 2. Corresponding values
of the reliability index (3 for ultimate strength and various serviceability
limit states are reported in Table 3. Note that the probability of failure or
survival with respect to one limit state can be estimated from the values
of the reliability index. Typical examples are given in Table 4. It can
be observed for instance that, at time of completion, the probability of
girder failure by fatigue of concrete under normal loading conditions is
less than three in ten millions. It is noted that the nominal moment car-
rying capacity of the girder is 5180 k-ft (7 023 kN-m) and the safety factor
representing the ratio of nominal resistance in bending to the maximum
service moment was calculated as 2.00.
In this example it is assumed that due to some severe environmental
exposure to corrosion, 8 straight strands from the layer of reinforcement
closest to the bottom fiber were damaged, and snapped off. The analysis
of the bridge in this damaged condition indicated that: 1) the dead load
moment exceeded slightly the cracking moment, 2) the girder would crack
under live load, 3) the cracks will open at each application of the loading,
4) the stress range in the prestressing strands due to the full application
of live loads is high enough to raise concern about fatigue.
The safety factor given by the ratio of the nominal moment resistance
of the damaged girder to the maximum service moment is 1.59. Clearly
however, due to the cracking condition and the possible fatigue in the rein-
forcement the bridge needed repair. Application of the reliability analysis
to the damaged girder led to the moment curvature relationship shown in
Fig. 8. The analysis also led to a mean resistance of 3830 k-ft (5193 kN-
m) and a corresponding reliability index for the ultimate strength limit
Prestressing 445
CONCLUDING REMARKS
The reliability analysis of a structure being new, old, or damaged, for var-
ious strength and serviceability limit states provides not only convenient
446 Nowak, Naaman, and Ting
ACKNOWLEDGEMENT
REFERENCES
1 Ghosn, M. and Moses, F., 1984, "Bridge Load Modeling and Reliabil-
ity Analysis," Report No. R 84-1, Department of Civil Engineering,
Case Western Reserve University.
2 Nowak, A. S. and Zhou, J. H., 1985, "Reliability Models for Bridge
Analysis," Report No. UMCE85-9, University of Michigan, March.
3 Nowak, A. S. and Grouni, H. N., 1988, "Serviceability Considerations
for Guideways and Bridges," Canadian Journal of Civil Engineering,
Vol. 15, No. 4, August, pp. 534-538.
4 Thoft-Christensen, P. and Baker, M. J., 1982, Structural Reliability
Theory and It3 Applications, Springer-Verlag, p. 267.
5 AASHTO, 1983, "Manual for Maintenance Inspection of Bridges,"
American Association of State Highway and Transportation Officials,
Washington, D. C.
6 AASHTO, 1983, "Standard Specifications for Highway Bridges,"
American Association of State Highway and Transportation Officials,
Washington, D. C., p. 394.
7 Nowak, A. S. et al., 1988, "Risk Analysis for Evaluation of Bridges,"
Report UMCE 88-7, Department of Civil Engineering, University of
Michigan, Ann Arbor, November.
8 Ellingwood B. et al., 1980, "Development of a Probability Based Load
Criterion for American National Standard A58," National Bureau of
Standards, NBS Special Publication 577, Washington.
9 Siriaksorn, A. and Naaman, A. E., 1980, "Reliability of Partially Pre-
stressed Beams at Serviceability Limit States," Report No. 80-1, Uni-
versity of Illinois at Chicago Circle, Chicago, June.
Prestressing 44 7
limit state R
8 in. strand effective depth, inch 49.43 .996 49.25 .011 0.52
9 ex. tendon effective depth, inch 37.00 .995 36.82 .014 0.52
10 slab thickness, inch 8.00 1.004 8.03 .059 0.47
448 Nowak, Naaman, and Ting
100
80
60
]
vr
"'
~
""
20
0
0.00 0.01 0.02 0.03 0.04 0.05
Strain
300
prestressing strand
200
]
vi
"' prestressing bar
~
100
L~--------------32'-----------------~
[r3'--+•·-----12'-----+-----12'-------t-3' ,.
1-------6'9''----------1 1 - - - - - - 6'9"---------11
6.------------------------------------------,
__________
,-.-_:-::.:-::.;.-_-
~~ ,..-
'1'/
-----------
Mean Value
~82!:!.Y.aJ!:!.e.:!:.g>:
~2!:!.Y.aJ!:!.~g>:
6,------------------------------------------,
a Original
181Damaged
A Repaired
o~~~~~~~~~~~~~~~~~~~~~~
0 100 200 300 400 500 600 700 800
Curvature rp, 10-a/inch
0.8
1 M 0 -orlglnal (slab)
0.7
2 t.f. -original {girder)
0.6
3 M.-damaged {slab)
]
~
0.5 4 M • -damaged {girder)
j
Ill
0..4
5 t.f•-repaired {slab)
6 M. -repaired (girder)
Ill 0.3
~ 0.2
0.1
0.0
0 0.2 0..4 0.6 0.8
Bending Moment, (M - M0 )/ML+t
30
25
1 M,.. -original
] 2 t.f,..-damaged
20
"EG> 3 M,..-repaired {In)
j Ill
15
4 t.f,..-repaired (ex)
Ill
~
10
---6'9"-------l•l
~-----,-
---r-
8"
Anchor
Blocks and
External
Tendons
54"
6@2" = 12"
RC t= 8"
Length
Area
square inch ................... square centimeter (cm 2) • • • • • • • • • • • • • • • • • • • 6.451
square foot ..................... square meter (m') .................... . 0.0929
square yard ..................... square meter (m 2 ) • • • • • • • • • • • • • • • • • • • • • 0.8361
Volume (capacity)
Force
kilogram-force ..................... newton (N)........................ 9.807
kip-force .......................... newton (N) ........................ 4448
pound-force ....................... newton (N)........................ 4.448
Mass
ounce-mass (avoirdupois) ............. gram (g) ........................ . 28.34
pound-mass (avoirdupois) ........... kilogram (kg) ............. ·......... . 0.4536
ton (metric) ....................... megagram (Mg) ..................... . I.OOOE
ton (short. 2000 Ibm) .............. megagram (Mg) ..................... . 0.9072
Temperature§
deg Fahrenheit (F) ................. deg Celsius (C) ................ tc = (IF - 32), 1.8
deg Celsius (C) .................. deg Fahrenheit (F) ................. tF = 1.8tc "'" 32
*This selected list gives practical conversion factors of units found in concrete tech-
nology. The reference source for information on SJ units and more exact conversion
factors is "Standard for Metric Practice.. ASTM E 380. Symbols of metric units are
given in parentheses.
+E Indicates that the factor given is exact.
t One liter (cubic decimeter) equals 0.001 m" or 1000 em".
~ These equations convert one temperature reading to another and include the neces-
sary scale corrections. To conver: a difference in temperature from Fahrenheit degrees
to Celsius degrees. divide by 1.8 only. i.e .. a change from 70 to 88 F represents a change
of 18 For 18/1.8 = 10 C deg.
457
INDEX