Fan Schedule
Fan Schedule
Sr. # EQUIPMENT TAG QTY. LOCATION AREA SERVED SERVICE TYPE AIR FLOW (CFM) ESP (in w.g) MOTOR (KW) DESIGN MOTOR (RPM) ELECTRICAL CHARACTERISTICS REMARKS Remarks for ESP works
1 EF‐S‐STO 1 POWERHOUSE STORE EXHAUST FAN WALL MOUNTED 25 ‐ 0.04 2900 220/1 PH/50HZ Calculation not required
2 TEF‐S‐01 1 POWERHOUSE TOILET TOILET EXHAUST FAN WALL MOUNTED 50 ‐ 0.04 2900 220/1 PH/50HZ Calculation not required
3 TEF‐S‐02 1 POWERHOUSE STAFF TOILETS TOILET EXHAUST FAN INLI NE DUCTED 100 0.3 0.04 2900 220/1 PH/50HZ M04.00_HVAC Layout For Powerhouse
4 EF‐S‐TR 1 POWERHOUSE TRANSFORMER ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,744 0.5 1.5 1440 380/3 PH/50HZ M04.00_HVAC Layout For Powerhouse
5 EF‐S‐HT 1 POWERHOUSE HT ROOMS EXHAUST FAN INLI NE CENTRIFUGAL FAN 316 0.4 0.08 820 220/1 PH/50HZ M04.00_HVAC Layout For Powerhouse
6 EF‐S‐BR 2 POWERHOUSE STEAM BOI LER ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,060 ‐ 0.85 1350 380/3 PH/50HZ Calculation not required
7 EF‐S‐PR 2 POWERHOUSE PUMP ROOM EXHAUST FAN WALL MOUNTED 4,000 ‐ 0.85 1350 380/3 PH/50HZ Calculation not required
10 EF‐LL‐04 1 LOWER GROUND FLOOR TOILETS a nd SOILED EXHAUST FAN INLI NE CENTRIFUGAL FAN 721 1 0.3 1425 220V/1 PH/50HZ Rechecked and OK
11 EF‐LL‐05 1 LOWER GROUND FLOOR TOILETS a nd SOILED EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,719 1 0.6 1425 220V/1 PH/50HZ Rechecked and OK
12 EF‐LL‐10 2 LOWER GROUND FLOOR TRANSFORMER ROOM EXHAUST FAN VANE AXIAL 24,964 1.5 11.19 1425 380/3 PH/50HZ ‐ Rechecked and OK
15 EF‐LL‐07 1 GROUND FLOOR NUCLEAR MEDICINE LABS EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,430 2.2 2.24 1425 380/3 PH/50HZ CHARCOAL FILTER IS REQUIRED Fan Not available in the drawing
16 EF‐CT2‐01 1 GROUND FLOOR CT SCAN EXHAUST FAN INLI NE CENTRIFUGAL FAN 719 1 0.3 1425 220V/1 PH/50HZ ‐ Rechecked and OK
17 EF‐MR2‐01 1 GROUND FLOOR MRI + ANGIO + RF EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,860 1 1.5 1425 220V/1 PH/50HZ ‐
18 SEF‐04 1 1ST FLOOR CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,125 0.6 2.2 1425 380/3 PH/50HZ FOR 1ST FLOOR Fan Not available in the drawing
19 EF‐BM‐01 1 FIRST FLOOR BONE MARROW EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,552 1 0.56 1425 220V/1 PH/50HZ ‐ Checked..CFMs Issue
20 EF‐1F‐BB 1 FIRST FLOOR BLOOD BANK EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,053 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK
21 EF‐ST‐01 1 FIRST FLOOR STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,939 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
22 EF‐1F‐ESC 1 FIRST FLOOR ENDOSCOPY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,087 1 0.56 1425 220V/1 PH/50HZ ‐ Rechecked and OK
23 1F‐PCH‐01 1 FIRST FLOOR PEDS CHEMO EXHAUST FAN INLI NE CENTRIFUGAL FAN 880 1 0.37 1425 ‐ Rechecked and OK
24 EF‐2F‐01 1 SECOND FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,910 1 2.24 1425 220V/1 PH/50HZ ‐ Rechecked and OK
25 EF‐2F‐03 1 SECOND FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,612 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK
26 SWPF‐03 1 3rd FLOOR STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 11,448 2 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan not Found on 3rd Floor
27 EF‐3F‐01 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,905 1.5 3.73 1425 380/3 PH/50HZ ‐ Rechecked and OK
28 EF‐IS‐01 1 THIRD FLOOR EMERGENCY I SOLATION EXHAUST FAN INLI NE CENTRIFUGAL FAN 863 1.5 0.37 1425 220V/1 PH/50HZ ‐ Rechecked and OK
29 EF‐2F‐02 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,174 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK
30 EF‐2F‐ANS 1 THIRD FLOOR ANESTHESI A STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 521 0.5 0.3 1550 220V/1 PH/50HZ ‐ Rechecked and OK
31 EF‐2F‐04 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,392 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK
32 EF‐2F‐IC 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,899 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK
33 HVF‐1F‐LB4 1 THIRD FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,250 1 2.24 1425 380/3 PH/50HZ ‐ Fan available at 3F
35 KVF‐GF‐01 1 THIRD FLOOR FOOD SERVICE HOOD VENTILATION FAN INLI NE CENTRIFUGAL FAN 14,480 1 7.5 1425 380/3 PH/50HZ ‐ Fan available at 3F
36 EF‐2F‐CSSD 1 FOURTH FLOOR CSSD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,824 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK
37 EF‐2F‐SURG. 1 FOURTH FLOOR SURGERY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,601 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK
38 EF‐2F‐ISO PREP 1 FOURTH FLOOR I SOLATION PREP EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,143 1 0.75 1425 220V/1 PH/50HZ ‐ Rechecked and OK
39 EF‐GF‐PHR1 1 FOURTH FLOOR BIOSAFETY CABINETS EXHAUST FAN INLI NE CENTRIFUGAL FAN 3,200 1.5 1.5 1425 380/3 PH/50HZ ‐ Rechecked and OK
40 EF‐GF‐PHR2 1 FOURTH FLOOR PHARMACY EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,615 1.5 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK
41 HEF‐1F‐TB 1 FOURTH FLOOR TB LAB HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 320 1 0.19 1425 220V/1 PH/50HZ ‐ Rechecked and OK
42 EF‐1F‐TB 1 FOURTH FLOOR TB LAB EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,910 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
43 HEF‐1F‐VIR 1 FOURTH FLOOR VIROLOGY LAB HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 320 1 0.19 1425 220V/1 PH/50HZ ‐ Rechecked and OK
44 EF‐1F‐VIR 1 FOURTH FLOOR VIROLOGY LAB EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,464 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK
45 HEF‐1F‐LB1 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
46 HEF‐1F‐LB2 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
47 HEF‐1F‐LB3 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
48 HEF‐1F‐LB4 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 7,500 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK
49 EF‐LL‐06 1 FOURTH FLOOR CYCLOTRONE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,541 1 0.75 1425 220V/1 PH/50HZ ‐ Rechecked and OK
50 EF‐LL‐11 1 FOURTH FLOOR LAUNDRY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,268 1.5 0.56 1425 380/3 PH/50HZ ‐ Rechecked and OK
51 EF‐6F‐01 1 SIXTH FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 960 0.2 0.2 1425 380/3 PH/50HZ ‐ Rechecked and OK
52 EF‐6F‐02 1 SIXTH FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,260 0.4 0.56 1425 380/3 PH/50HZ ‐ Rechecked and OK
53 EF‐EMR‐01 1 PENT HOUSE EMERGENCY EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,315 1.5 1.12 1425 380/3 PH/50HZ ‐ Fan is available. Area not clear
54 EF‐LL‐02 1 PENT HOUSE RADI OLOGY WAI TI NG EXHAUST FAN INLI NE CENTRIFUGAL FAN 14,684 1.5 5.6 1425 380/3 PH/50HZ CFMs Not clear
55 EF‐OP‐01 1 PENT HOUSE OP ADULTS AND PEDS EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,881 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
56 EF‐CIR‐01 1 PENT HOUSE CIRCULATION + PHARMACY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,895 1.5 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK
57 EF‐ACH‐01 1 PENT HOUSE ADULT CHEMO + CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,543 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
58 EF‐3F‐ISL 1 PENT HOUSE 3RD FLOOR ISOLATION EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,698 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK
59 EF‐LL‐09 1 PENT HOUSE MEDICAL GAS EXHAUST FAN INLI NE CENTRIFUGAL FAN 16,482 2 7.5 1425 380/3 PH/50HZ Rechecked and OK
60 EF‐LL‐12 2 PENT HOUSE COMPRESSOR AND BOI LER EXHAUST FAN VANE AXIAL 24,977 2 11.4 1425 380/3 PH/50HZ Rechecked and OK
61 EF‐LL‐01 1 PENT HOUSE HOT LABS EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,583 1.5 2.24 1425 380/3 PH/50HZ Rechecked and OK
62 EF‐LL‐03 1 PENT HOUSE TOI LETS EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,500 1.5 0.75 1425 380/3 PH/50HZ Rechecked and OK
66 SWPF‐01 2 ROOF STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 12,172 1.5 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan Not available in the drawing
64 SWPF‐02 2 ROOF STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 11,991 1.5….. 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan Not available in the drawing
67 SEF‐03 1 ROOF CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,365 1 2.2 1425 380/3 PH/50HZ FOR 6TH FLOOR Fan Not available in the drawing
68 EF‐R‐01 2 ROOF STORAGE ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,164 0.5 0.55 1425 220V/1 PH/50HZ Axial fans so need to have calculations
NOTES:
1‐ THE REMOTE / START FACILITY SHALL BE PROVI DED FOR ALL FANS. START / STOP FACILITY AND LOCATION TO BE FINALI ZED AS PER SITE CONDITION & CLI ENT REQUIREMENT'S
2‐ CONTRACTOR TO CALCULATE ACTUAL EXTERNAL STATIC PRESSURE AS PER SI TE CONDI TIONS AND SUBMIT FOR ENGINEER'S APPROVAL
3‐ ALL EXHUAST AI R FANS AND MOTORS SHALL BE 2HR FIRE RATED AND SUI TABLE FOR HIGH TEMPERATURE APPLI CATION (300 oC) & FAN MOTORS SHALL BE MOUNTED AT OUT OF AI R STREAM
4‐ QUANTI TY AND LOCATION OF I NDUCTI ON FANS SHALL BE FINALI ZED AFTER CFD ANALYSIS