Fan Schedule

This document lists 28 ventilation and exhaust fans with details like location, area served, type, air flow, electrical characteristics, and remarks. It includes fans for areas like the powerhouse, parking, toilets, storage areas, radiology, and more. The fans range in air flow from 25 CFM to over 24,000 CFM and include wall mounted, inline centrifugal, jet, and vane axial fans powered by single and three phase electricity. Remarks note issues like missing CFMs or fans not shown on drawings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views

Fan Schedule

This document lists 28 ventilation and exhaust fans with details like location, area served, type, air flow, electrical characteristics, and remarks. It includes fans for areas like the powerhouse, parking, toilets, storage areas, radiology, and more. The fans range in air flow from 25 CFM to over 24,000 CFM and include wall mounted, inline centrifugal, jet, and vane axial fans powered by single and three phase electricity. Remarks note issues like missing CFMs or fans not shown on drawings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

VENTILATION AND EXHAUST FANS

Sr. # EQUIPMENT TAG QTY. LOCATION AREA SERVED SERVICE TYPE AIR FLOW (CFM) ESP (in w.g) MOTOR (KW) DESIGN MOTOR (RPM) ELECTRICAL CHARACTERISTICS REMARKS Remarks for ESP works

1 EF‐S‐STO 1 POWERHOUSE STORE EXHAUST FAN WALL MOUNTED 25 ‐ 0.04 2900 220/1 PH/50HZ Calculation not required

2 TEF‐S‐01 1 POWERHOUSE TOILET TOILET EXHAUST FAN WALL MOUNTED 50 ‐ 0.04 2900 220/1 PH/50HZ Calculation not required

3 TEF‐S‐02 1 POWERHOUSE STAFF TOILETS TOILET EXHAUST FAN INLI NE DUCTED 100 0.3 0.04 2900 220/1 PH/50HZ M04.00_HVAC Layout For Powerhouse

4 EF‐S‐TR 1 POWERHOUSE TRANSFORMER ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,744 0.5 1.5 1440 380/3 PH/50HZ M04.00_HVAC Layout For Powerhouse

5 EF‐S‐HT 1 POWERHOUSE HT ROOMS EXHAUST FAN INLI NE CENTRIFUGAL FAN 316 0.4 0.08 820 220/1 PH/50HZ M04.00_HVAC Layout For Powerhouse

6 EF‐S‐BR 2 POWERHOUSE STEAM BOI LER ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,060 ‐ 0.85 1350 380/3 PH/50HZ Calculation not required

7 EF‐S‐PR 2 POWERHOUSE PUMP ROOM EXHAUST FAN WALL MOUNTED 4,000 ‐ 0.85 1350 380/3 PH/50HZ Calculation not required

CFMs are missed


8 EF‐LL‐08 1 LOWER GROUND FLOOR NUCLEAR MEDICI NE EXHAUST FAN INLI NE CENTRIFUGAL FAN 10,614 2 5.6 1425 380/3 PH/50HZ ‐
Clouded on DWG
5,304 /
9 I DV LL‐01 7 LOWER GROUND FLOOR PARKI NG PARKING EXHAUST FAN JET FANS ‐ 3.8 1425 380/3 PH/50HZ 2 SPEED FANS ARE REQUI RED Calculation not required
3,182

10 EF‐LL‐04 1 LOWER GROUND FLOOR TOILETS a nd SOILED EXHAUST FAN INLI NE CENTRIFUGAL FAN 721 1 0.3 1425 220V/1 PH/50HZ Rechecked and OK

11 EF‐LL‐05 1 LOWER GROUND FLOOR TOILETS a nd SOILED EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,719 1 0.6 1425 220V/1 PH/50HZ Rechecked and OK

12 EF‐LL‐10 2 LOWER GROUND FLOOR TRANSFORMER ROOM EXHAUST FAN VANE AXIAL 24,964 1.5 11.19 1425 380/3 PH/50HZ ‐ Rechecked and OK

37,125 / 2 SPEED FANS ARE REQUI RED (1


13 PEF LL‐01 2 GROUND FLOOR PARKI NG PARKING EXHAUST FAN VANE AXIAL 1 14.9 1425 380/3 PH/50HZ Drawing not available
22,275 DUTY + 1 STANDBY)
CFMs are missed
14 EF‐WR‐01 1 GROUND FLOOR WOMEN RADI OLODY EXHAUST FAN INLI NE CENTRIFUGAL FAN 8,185 1 5.6 1425 380/3 PH/50HZ ‐
Clouded on DWG

15 EF‐LL‐07 1 GROUND FLOOR NUCLEAR MEDICINE LABS EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,430 2.2 2.24 1425 380/3 PH/50HZ CHARCOAL FILTER IS REQUIRED Fan Not available in the drawing

16 EF‐CT2‐01 1 GROUND FLOOR CT SCAN EXHAUST FAN INLI NE CENTRIFUGAL FAN 719 1 0.3 1425 220V/1 PH/50HZ ‐ Rechecked and OK

17 EF‐MR2‐01 1 GROUND FLOOR MRI + ANGIO + RF EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,860 1 1.5 1425 220V/1 PH/50HZ ‐

18 SEF‐04 1 1ST FLOOR CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,125 0.6 2.2 1425 380/3 PH/50HZ FOR 1ST FLOOR Fan Not available in the drawing

19 EF‐BM‐01 1 FIRST FLOOR BONE MARROW EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,552 1 0.56 1425 220V/1 PH/50HZ ‐ Checked..CFMs Issue

20 EF‐1F‐BB 1 FIRST FLOOR BLOOD BANK EXHAUST FAN INLI NE CENTRIFUGAL FAN 4,053 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK

21 EF‐ST‐01 1 FIRST FLOOR STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,939 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

22 EF‐1F‐ESC 1 FIRST FLOOR ENDOSCOPY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,087 1 0.56 1425 220V/1 PH/50HZ ‐ Rechecked and OK

23 1F‐PCH‐01 1 FIRST FLOOR PEDS CHEMO EXHAUST FAN INLI NE CENTRIFUGAL FAN 880 1 0.37 1425 ‐ Rechecked and OK

24 EF‐2F‐01 1 SECOND FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,910 1 2.24 1425 220V/1 PH/50HZ ‐ Rechecked and OK

25 EF‐2F‐03 1 SECOND FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,612 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK

26 SWPF‐03 1 3rd FLOOR STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 11,448 2 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan not Found on 3rd Floor

27 EF‐3F‐01 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,905 1.5 3.73 1425 380/3 PH/50HZ ‐ Rechecked and OK

28 EF‐IS‐01 1 THIRD FLOOR EMERGENCY I SOLATION EXHAUST FAN INLI NE CENTRIFUGAL FAN 863 1.5 0.37 1425 220V/1 PH/50HZ ‐ Rechecked and OK

29 EF‐2F‐02 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,174 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK

30 EF‐2F‐ANS 1 THIRD FLOOR ANESTHESI A STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 521 0.5 0.3 1550 220V/1 PH/50HZ ‐ Rechecked and OK

31 EF‐2F‐04 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,392 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK

32 EF‐2F‐IC 1 THIRD FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,899 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK

33 HVF‐1F‐LB4 1 THIRD FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,250 1 2.24 1425 380/3 PH/50HZ ‐ Fan available at 3F
35 KVF‐GF‐01 1 THIRD FLOOR FOOD SERVICE HOOD VENTILATION FAN INLI NE CENTRIFUGAL FAN 14,480 1 7.5 1425 380/3 PH/50HZ ‐ Fan available at 3F

36 EF‐2F‐CSSD 1 FOURTH FLOOR CSSD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,824 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK

37 EF‐2F‐SURG. 1 FOURTH FLOOR SURGERY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,601 1 1.49 1425 220V/1 PH/50HZ ‐ Rechecked and OK

38 EF‐2F‐ISO PREP 1 FOURTH FLOOR I SOLATION PREP EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,143 1 0.75 1425 220V/1 PH/50HZ ‐ Rechecked and OK

39 EF‐GF‐PHR1 1 FOURTH FLOOR BIOSAFETY CABINETS EXHAUST FAN INLI NE CENTRIFUGAL FAN 3,200 1.5 1.5 1425 380/3 PH/50HZ ‐ Rechecked and OK

40 EF‐GF‐PHR2 1 FOURTH FLOOR PHARMACY EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,615 1.5 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK

41 HEF‐1F‐TB 1 FOURTH FLOOR TB LAB HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 320 1 0.19 1425 220V/1 PH/50HZ ‐ Rechecked and OK

42 EF‐1F‐TB 1 FOURTH FLOOR TB LAB EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,910 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

43 HEF‐1F‐VIR 1 FOURTH FLOOR VIROLOGY LAB HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 320 1 0.19 1425 220V/1 PH/50HZ ‐ Rechecked and OK

44 EF‐1F‐VIR 1 FOURTH FLOOR VIROLOGY LAB EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,464 1 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK

45 HEF‐1F‐LB1 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

46 HEF‐1F‐LB2 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

47 HEF‐1F‐LB3 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,400 1 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

48 HEF‐1F‐LB4 1 FOURTH FLOOR LAB AREA HOOD EXHAUST FAN INLI NE CENTRIFUGAL FAN 7,500 1 2.24 1425 380/3 PH/50HZ ‐ Rechecked and OK

49 EF‐LL‐06 1 FOURTH FLOOR CYCLOTRONE EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,541 1 0.75 1425 220V/1 PH/50HZ ‐ Rechecked and OK

50 EF‐LL‐11 1 FOURTH FLOOR LAUNDRY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,268 1.5 0.56 1425 380/3 PH/50HZ ‐ Rechecked and OK

51 EF‐6F‐01 1 SIXTH FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 960 0.2 0.2 1425 380/3 PH/50HZ ‐ Rechecked and OK

52 EF‐6F‐02 1 SIXTH FLOOR TOI LETS a nd STORAGE EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,260 0.4 0.56 1425 380/3 PH/50HZ ‐ Rechecked and OK

53 EF‐EMR‐01 1 PENT HOUSE EMERGENCY EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,315 1.5 1.12 1425 380/3 PH/50HZ ‐ Fan is available. Area not clear

54 EF‐LL‐02 1 PENT HOUSE RADI OLOGY WAI TI NG EXHAUST FAN INLI NE CENTRIFUGAL FAN 14,684 1.5 5.6 1425 380/3 PH/50HZ CFMs Not clear

55 EF‐OP‐01 1 PENT HOUSE OP ADULTS AND PEDS EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,881 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

56 EF‐CIR‐01 1 PENT HOUSE CIRCULATION + PHARMACY EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,895 1.5 1.12 1425 220V/1 PH/50HZ ‐ Rechecked and OK

57 EF‐ACH‐01 1 PENT HOUSE ADULT CHEMO + CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,543 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

58 EF‐3F‐ISL 1 PENT HOUSE 3RD FLOOR ISOLATION EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,698 1.5 1.12 1425 380/3 PH/50HZ ‐ Rechecked and OK

59 EF‐LL‐09 1 PENT HOUSE MEDICAL GAS EXHAUST FAN INLI NE CENTRIFUGAL FAN 16,482 2 7.5 1425 380/3 PH/50HZ Rechecked and OK

60 EF‐LL‐12 2 PENT HOUSE COMPRESSOR AND BOI LER EXHAUST FAN VANE AXIAL 24,977 2 11.4 1425 380/3 PH/50HZ Rechecked and OK

61 EF‐LL‐01 1 PENT HOUSE HOT LABS EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,583 1.5 2.24 1425 380/3 PH/50HZ Rechecked and OK

62 EF‐LL‐03 1 PENT HOUSE TOI LETS EXHAUST FAN INLI NE CENTRIFUGAL FAN 1,500 1.5 0.75 1425 380/3 PH/50HZ Rechecked and OK

66 SWPF‐01 2 ROOF STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 12,172 1.5 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan Not available in the drawing

64 SWPF‐02 2 ROOF STAIR CASE VENTILATI ON FAN INLI NE CENTRIFUGAL FAN 11,991 1.5….. 7.5 1425 380/3 PH/50HZ SHALL BE VSD DRI VEN Fan Not available in the drawing

FAN OPERATION SHOULD BE AS


65 SEF‐01 3 ROOF CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,503 2 3.7 1425 380/3 PH/50HZ PER FOLLOWING: BF FLOOR ‐‐‐‐ 3 Fan Not available in the drawing
FAN ON
66 SEF‐02 1 ROOF CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 19,770 2 11.19 1425 380/3 PH/50HZ FOR BF/GF/1F/2F/3F FLOOR Fan Not available in the drawing

67 SEF‐03 1 ROOF CORRIDOR/CIRCULATI ON EXHAUST FAN INLI NE CENTRIFUGAL FAN 5,365 1 2.2 1425 380/3 PH/50HZ FOR 6TH FLOOR Fan Not available in the drawing

68 EF‐R‐01 2 ROOF STORAGE ROOM EXHAUST FAN INLI NE CENTRIFUGAL FAN 2,164 0.5 0.55 1425 220V/1 PH/50HZ Axial fans so need to have calculations

NOTES:
1‐ THE REMOTE / START FACILITY SHALL BE PROVI DED FOR ALL FANS. START / STOP FACILITY AND LOCATION TO BE FINALI ZED AS PER SITE CONDITION & CLI ENT REQUIREMENT'S

2‐ CONTRACTOR TO CALCULATE ACTUAL EXTERNAL STATIC PRESSURE AS PER SI TE CONDI TIONS AND SUBMIT FOR ENGINEER'S APPROVAL

3‐ ALL EXHUAST AI R FANS AND MOTORS SHALL BE 2HR FIRE RATED AND SUI TABLE FOR HIGH TEMPERATURE APPLI CATION (300 oC) & FAN MOTORS SHALL BE MOUNTED AT OUT OF AI R STREAM

4‐ QUANTI TY AND LOCATION OF I NDUCTI ON FANS SHALL BE FINALI ZED AFTER CFD ANALYSIS

5‐ ALL MOTORS SHOULD HAVE A MI NI MUM OF IE3 EFFICIENCY