[SmartX Controller] SmartStruxure solution

I/O Module UI-16


16 channel universal input

As counter inputs they are commonly used in


energy metering applications. As supervised inputs
they are used for security applications where it is
critical to know whether or not a wire has been cut
or shorted. These events provide a separate
indication of alarms and trouble conditions to the
system.

Function
Modular and scalable system
The modules are part of a modular system that
delivers power and communications on a common
bus. Connecting modules is a one-step process:
just slide the modules together using the built-in
connectors.

Patented two-piece design


Each module can be separated from its terminal
base to allow the site to be wired prior to the
installation of the electronics. The patented locking
mechanism serves as handles for removing the
module from its base. All critical components have
a protective cover that permits convection cooling
Introduction to occur.
The UI-16 is a universal input, 16 channel I/O
module.

The universal inputs are ideal for any mix of


temperature, pressure, flow, status points, and
similar point types in a building control system.

The universal inputs can be configured to read


several different types of inputs:

• Digital
• Counter
• Supervised
© 2016 Schneider Electric. All rights reserved.

• Voltage
• Current
• Temperature
• Resistive Figure: Two-piece design

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-16006-02-en June 2016
[SmartX Controller] SmartStruxure solution
2

Hot-connect and Hot-swap Operation WorkStation software can generate


Because critical applications require 24-hour custom as-built labels for each module. Pre-
operation, Schneider Electric designed the I/O perforated letter and A4 size label sheets are
modules for hot-connection of terminal bases and available as an accessory.
hot-swapping of the modules to their bases. This
design ensures continuous power and Accommodates multiple row panel installations
communication during service operations. The SmartStruxure devices use built-in connectors
for single row connectivity, side by side. If a panel
Auto-addressing size requires multiple rows, extension cords are
The auto-addressing feature eliminates the need for available.
setting DIP switches or pressing commission
buttons. Each module automatically knows its order LED status indicators
in the chain and assigns itself accordingly – The I/O module has a status indicator that denotes
significantly reducing engineering and maintenance the health and status of the module.
time.
Each input channel has a dedicated two color
Simple DIN-rail installation status LED. The LED can be configured to display
Fasteners easily snap into a locked position for either red or green for each input state.
panel installation. The fastener has a quick-release
feature for easy DIN-rail removal. Protection
Protection components on the inputs protect
Efficient terminal management against high-voltage short-duration transient
The I/O module terminals are clearly labeled and events.
protected by transparent covers. The input and
output terminals are at the top and bottom of each The current inputs are protected against over
module and are accessible for maintenance without current.
removing the module. The StruxureWare Building

Specifications
Input channels .........................................................................................................................................16
DC input supply power .......................................................................................................................1.8 W
DC input supply voltage ...................................................................................................................24 VDC
Environment
Ambient temperature, operating .............................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage .........................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity...............................................................................................95 % RH non-condensing
Material
Plastic rating................................................................................................................................UL94-5VB
Enclosure .......................................................................................................................................PC/ABS
Enclosure rating...................................................................................................................................IP 20
© 2016 Schneider Electric. All rights reserved.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-16006-02-en June 2016
[SmartX Controller] SmartStruxure solution
3

Mechanical
Dimensions including terminal base ..............................90 W x 114 H x 64 D mm (3.6 W x 4.5 H x 2.5 D in.)

Weight including terminal base..........................................................................................0.269 kg (0.59 lb)


Weight excluding terminal base.........................................................................................0.146 kg (0.32 lb)
Terminal base ..............................................................................................................................TB-IO-W1
Agency compliances
Emission ................................................................RCM; EN 61000-6-3; FCC Part 15, Sub-part B, Class B
Immunity ...............................................................................................................................EN 61000-6-2
Safety.................................................................................................EN 61010-1; UL 916 C-UL US Listed
Product ....................................................................................................................................EN 61326-1
Smoke control product safety...........................................................................................................UL 864
Part numbers
UI-16, I/O module
16 universal inputs ..........................................................................................................SXWUI16XX10001
TB-IO-W1, terminal base for I/O module
(Required for each I/O module)......................................................................................SXWTBIOW110001
Accessory part numbers
DIN-RAIL-CLIP, DIN-rail end clip
package of 25 pieces ....................................................................................................SXWDINEND10001
PRINTOUT-A4-W1, printout sheets for terminal labels
A4 sheet size, 100 sheets, 18 labels per sheet...............................................................SXWTERLBL10011
PRINTOUT-LTR-W1, printout sheets for terminal labels
Letter sheet size, 100 sheets, 16 labels per sheet ..........................................................SXWTERLBL10012
S-CABLE-L, S-cable extension cord for the I/O bus, L shaped connectors
© 2016 Schneider Electric. All rights reserved.

1.5 m............................................................................................................................SXWSCABLE10002
S-CABLE-L, S-cable extension cord for the I/O bus, L shaped connectors
0.75 m..........................................................................................................................SXWSCABLE10003

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-16006-02-en June 2016
[SmartX Controller] SmartStruxure solution
4

Universal inputs

Absolute maximum ratings .................................................................................................-0.5 to +24 VDC


A/D converter resolution ....................................................................................................................12 bits
Digital
Range .........................................Dry contact switch closure or open collector/open drain, 24 VDC, 2.4 mA
Minimum pulse width .......................................................................................................................120 ms
LED polarity ...................................Software selectable, if the LED is activated when the input is high or low
LED color .................................................................................................Red or green, software selectable
Counter
Range .........................................Dry contact switch closure or open collector/open drain, 24 VDC, 2.4 mA
Minimum pulse width .........................................................................................................................20 ms
Maximum frequency ...........................................................................................................................25 Hz
LED polarity ...................................Software selectable, if the LED is activated when the input is high or low
LED color .................................................................................................Red or green, software selectable
Supervised
5 V circuit, 1 or 2 resistors
Monitored switch combinations...........................................Series only, parallel only, and series and parallel
Resistor range .........................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor is assumed to have the same value +/- 5 %
Voltage
Range.......................................................................................................................................0 to 10 VDC
Accuracy .........................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution ........................................................................................................................................2.7 mV
Impedance...................................................................................................................................100 kohm
© 2016 Schneider Electric. All rights reserved.

Reliability check .....................................................................................................................................Yes


Current
Range.........................................................................................................................................0 to 20 mA
Accuracy ....................................................................................................+/-(0.03 mA + 0.4 % of reading)
Resolution .........................................................................................................................................5.6 μA
Impedance ......................................................................................................................................47 ohm
Reliability check .....................................................................................................................................Yes

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-16006-02-en June 2016
[SmartX Controller] SmartStruxure solution
5

Resistive
10 ohm to 10 kohm accuracy .................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy ...............................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Reliability check .....................................................................................................................................Yes
Temperature
Range .........................................................................................................-50 to +150 °C (-58 to +302 °F)
Reliability check .....................................................................................................................................Yes
Supported thermistors
Honeywell ......................................................................................................................................20 kohm
Type I (Continuum) .........................................................................................................................10 kohm
Type II (I/NET).................................................................................................................................10 kohm
Type III (Satchwell)..........................................................................................................................10 kohm
Type IV (FD)................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt)...............................................................................................Linearized 10 kohm
Satchwell D?T ...............................................................................................................Linearized 10 kohm
Johnson Controls..........................................................................................................................2.2 kohm
Xenta ............................................................................................................................................1.8 kohm
Balco ...............................................................................................................................................1 kohm
Thermistor accuracy
20 kohm, 10 kohm, 2.2 kohm, and 1.8 kohm....................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
...........................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
............................................................................................. 0 to 50 °C: +/-0.2 °C (32 to 122 °F: +/-0.4 °F)
....................................................................................... 50 to 100 °C: +/-0.5 °C (122 to 212 °F: +/-0.9 °F)
..................................................................................... 100 to 150 °C: +/-1.5 °C (212 to 302 °F: +/-2.7 °F)
Linearized 10 kohm ..........................................................-50 to -30 °C: +/-3.0 °C (-58 to -22 °F: +/-5.4 °F)
...........................................................................................-30 to 0 °C: +/-1.0 °C (-22 to +32 °F: +/-1.8 °F)
............................................................................................. 0 to 50 °C: +/-0.3 °C (32 to 122 °F: +/-0.5 °F)
....................................................................................... 50 to 100 °C: +/-0.5 °C (122 to 212 °F: +/-0.9 °F)
..................................................................................... 100 to 150 °C: +/-2.0 °C (212 to 302 °F: +/-3.6 °F)
1 kohm .......................................................................-50 to +150 °C: +/-1.5 °C (-58 to +302° F: +/-2.7 °F)

For protection from excess current that could be • Individual 24 VDC power sources to the field
produced by field wiring, follow these instructions: must be current limited to maximum of 4
amps for UL compliant installations, and no
• Connect one RET terminal on each of the I/O more than 6 amps in other areas.
© 2016 Schneider Electric. All rights reserved.

modules to a common chassis/power ground


• For more information on wiring, see
rail in the control panel using a size 16 AWG,
Hardware Reference Guide.
1.3 mm, or larger wire.

Schneider Electric | Building Business www.schneider-electric.com/buildings


Trademarks and registered trademarks are the property of their respective owners.
03-16006-02-en June 2016
[SmartX Controller] SmartStruxure solution
6

Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
two conditions: (1) This device may not cause harmful interference. (2) This device must This equipment complies with the rules, of the Official Journal of the European Union, for
accept any interference received, including interference that may cause undesired governing the Self Declaration of the CE Marking for the European Union as specified in
operation. the above directive(s) per the provisions of the following standards: EN 61326-1 Product
Standard, EN 61010-1 Safety Standard.
Industry Canada
This Class B digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. WEEE - Directive of the European Union (EU)
This equipment and its packaging carry the waste of electrical and electronic equipment
Regulatory Compliance Mark (RCM) - Australian Communications and Media (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing
Authority (ACMA) the disposal and recycling of electrical and electronic equipment in the European
This equipment complies with the requirements of the relevant ACMA standards made community.
under the Radiocommunications Act 1992 and the Telecommunications Act 1997. These
standards are referenced in notices made under section 182 of the Radiocommunications
Act and 407 of the Telecommunications Act. UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.

th
UL 864 Listed products for the United States. 10 Edition Smoke Control
System. UL file S5527.