Specification Intro Overview
Specification Intro Overview
PART 1 1.01 A.
GENERAL SUMMARY
This section gives general requirements for Process Instrumentation and Control (PIC). The following PIC subsections expand on requirements of this section: 1. Section 40 91 00, Instrumentation and Control Components. 2. Section 40 95 80, Local Area Network (LAN) Communication System.
B.
Major Work Items: Includes but is not limited to engineering, furnishing, calibrating, adjusting, testing, documenting, starting up, and training for complete PIC. 1. Process instrumentation including primary elements, transmitters, control devices, and control panels. 2. Programmable logic controllers. 3. Networks for Human Machine Interface (HMI).
2.10 A.
1. General: a. PLC system shall be Automation Direct Productivity 3000 Series, as specified below. No substitutions allowed. b. Equipment quantities shall be per Drawings. 2. Control Processor: Units shall be Productivity 3000 Model P3-550. 3. Power Supply Module: Units shall be Productivity 3000 Model P3-01AC 4. PLC I/O Chassis: Eight slot chassis shall be Productivity 3000 Model P3-08B. Eleven slot chassis shall be Productivity 3000 Model P3-11B. 5. Digital Input Module: AC Units shall be Productivity 3000 Model P3-16NA with Model P3-RTB I/O Module Terminal Interface. DC Units shall be Productivity 3000 Model P3-64ND3. 6. Digital Output Module: AC Units shall be Productivity 3000 Model P3-16TA with Model P3-RTB I/O Module Terminal Interface. DC Units shall be Productivity 3000 Model P3-16TD2 with Model P3-RTB I/O Module Terminal Interface. 7. Analog Input Module: Units shall be Productivity 3000 Model P3-16AD-1 with Model P3-RTB I/O Module Terminal Interface. Analog Output Module: Units shall be Productivity 3000 Model P3-16DA-1 with Model P3-RTB I/O Module Terminal Interface.
8.