Section 1. General Specifications
Content Unit Specification
Compressor Model — C-SCP270H39A
Type — Hermetic Scroll Compressor
Application — High Back Pressure
Evap. Temp. Range °C (°F) -15~12 (5~54)
Compressor Cooling Type — Natural Cooling
Phase — 3
Power Source Rated Voltage V 380
Rated Frequency Hz 60
Voltage Range V 342~418
Weight (Including Oil) kg (lb) 66.5(146.6)
Refrigerant — R410A
Oil Type — FV68S or Equivalent
Oil Charge ml (fl oz) 2800 (94.7)
3 3
Displacement cm (in ) /rev 89.2(5.44)
Motor Type — 3-PH Induction Motor
Number of Poles — 2
Electrical Insulation Class E
Nominal Revolution min-1 —
Motor
Locked Rotor Ampere A 124
U-V 0.833
Winding Resistance
Ω U-W 0.875
[at 25°C (77°F)]
V-W 0.861
Suction Line (O.D.) mm (in) 25.4 (1.000)
Connection Tube
Discharge Line (O.D.) mm (in) 19.05 (0.750)
Compressor Surface Paint — Black Paint
Notes
1 Voltage range is applied at standard rating conditions.
2 Motor specifications in the table are the average values for your reference.
3 ( ): All units with parentheses are reference values.
Expiration of Specification
Expiration of this specification shall be effected until issuing a notice with indication of the expiration date from the
issued date . In case of improvement or elimination of this specification , it shall be handled by the revision record
based on agreement between both sides.
2
Model: C-SCP270H39A
File No: C-SCP270H39A-00-GGS-0
Section 2. Performance Warranty
2.1 Performance
Hz 60 Remark
Power Source (3PH)
V 380
W 27,600 ±5%
Capacity
(BTU/hr) 94,171 reference
Input Power W 8,800 ±5%
Current A 15.9 ±5%
Standard Rating Conditions
Condensing Temp. °C (°F) 54.4(130)
Evaporating Temp. °C (°F) 7.2( 45 )
Suction Gas Temp. °C (°F) 18.3( 65 )
Liquid Temp. °C (°F) 46.1(111)
Ambient Temp. °C (°F) 35.0( 95 )
MP 427.7
2.2 Sound Level
Hz 60
Power Source (3PH)
V 380
Sound Level dB(A) 74Max.
Notes
1 The operating conditions are the same as 2.1.
2 MIC location is the distance of 1m (3.28feet) from the compressor.
3 Sound Level is an average sound pressure level in four directions.
2.3 Minimum Starting Voltage
Power Source (3PH) Hz 60
Minimum Starting Voltage V 304
Conditions
Compressor Temp. °C (°F) 10~60(50~140)
Ambient Temp. °C (°F) 10~40(50~105)
High Pressure MPa(G)/psig 3.25(471)
Low Pressure MPa(G)/psig 0.9(130.5)
2.4 Others
Content Unit Specification
L.P. S. MPa(G)/psig 2.21(320)
Design Pressure
H. P. S. MPa(G)/psig 4.35(631)
Insulation Resistance MΩ 100 (without refrigerant)
Dielectric Strength V 1900 (1 minute)
Residual Moisture mg 400
Note:
1. The insulation resistance be measured with a DC500V megohm tester.
3
Model: C-SCP270H39A
File No: C-SCP270H39A-00-GGS-0
Section 3. Standard Accessories
3.1 Accessories List
Parts Name Qty Parts code Revision No. Note
Terminal Box Cover 1 A-0101-DSB 0 Installed on Compressor
Terminal Box Clip 1 A-0201-DSB 0 Installed on Compressor
Eyelet Rub Lead Wire 1 A-0301-DSB 0 Installed on Compressor
Mounting Grommet 4 M-0101-DSC 0 Included with Compressor
Mounting Sleeve 4 M-0202-DSC 1 Included with Compressor
3.2 The Drawing for Reference
Parts Name Parts Code Revision No.
Compressor Outline Drawing D-0105-DSC 0
Mounting Parts Listing M-5102-DSC 0
Packing Dimensions D-0201-DSC 0
Wiring Diagram E-0910-DSC 0
3. 3 Inernal Motor Protector (in compressor)
Parts Name Specification
Trip Temprature 160±5℃
Inernal Motor Protector Reset Temprature 70±10℃
Trip Current 180A / 3~10s
4
Model: C-SCP270H39A
File No: C-SCP270H39A-00-GGS-0
Section 4. Compressor Protection
4.1 Protection Required but not Included with compressor
Protection Device Items Specifications
Features To protect the compressor from reverse rotation
Reversal Defensible Relay
Rated Voltage AC380V
Crankcase Heater Rated Power 88 Watts
Mounting Position Located in the well pipe of top shell
Discharge Thermostat Trip Temperature 135±5℃(275 ±10 °F)
Reset Temperature 86±15℃ (187 ± 27 °F)
High Pressure Switch Setting Cut-out seting no higher than 4.15MPa(G)
Low Pressure Switch Setting Cut-out seting no lower than 0.15MPa(G)
4.2 Position of the Protection and Refrigerant Charging
FOR LIQUID
REFRIGERANT
CHARGING
CAPILLARY
LIQUID LINE
SERVICE
OUTDOOR VALVE
INDOOR
HEAT HEAT
EXCHANGER EXCHANGER
GAS LINE
REVERSING SERVICE VALVE
VALVE
DISCHARGE FOR GAS
THERMOSTAT REFRIGERANT
CHARGING
HIGH
PRESSURE ACCUMULATOR
SWITCH
LOW
PRESSURE
SWITCH
COMPRESSOR CRANKCASE
HEATER
5
Section 5. Operating Envelope
Suction Gas Superhea : 11.1K.
Refrigerant : R410A.
70
Transient Operation
60
Condensing Temperature(℃)
50
Normal Operation
40
30
20
10
-30 -25 -20 -15 -10 -5 0 5 10 15 20
Evaporating Temperature(℃)
6
Section 6. Application Standard & Limit
The following requirements apply to vertical type hermetic scroll compressors:
Standard: Applicable to ordinary conditions in Japan JIS B8616 or standards relative to JIS B8616, such as standard rating
conditions, maximum operating conditions, low temperature conditions, etc.
Limit: Applicable to transitional brief period of time, such as start-up and beginning of defrost mode.
No. Item Standard Limit Note
1 Refrigerant R410A
-15~12℃(5~54 °F) -25~15℃(-13~59 °F)
2 Evaporating Temp.
0.38~1.06MPa(G)(55~154psig) 0.23~1.16MPa(G)(33~168psig)
30~60℃(86~140 °F) 67℃(152.6 °F)
3 Condensing Temp.
1.80~3.75MPa(G)(261~544psig) 4.35MPa(G)(631psig)
4 Compression Ratio 2~6 8
5 Winding Temp. 115℃(240 °F) Max. 125℃(257 °F)
90℃(194 °F) Max.
6 Shell Bottom Temp. Evaporating Temp.+12℃(21 °F) Min.
Ambient Temp.+11℃(20 °F) Min.
C-SB:130℃( 266°F) Max.
Discharge Gas
7 115℃(240 °F) Max.
Temp.
C-SC:135℃( 275°F) Max.
It should meet the
requirement of item 5, 6,
8 Suction Gas Temp. Superheat: 5K(10 °F)Min. No excessive noise
7 and 14 within 30cm of
the suction fitting.
Voltage at compressor
9 Running Voltage Within ±10% of the rated voltage
terminals.
Three Phase Models: 85% of the rated voltage min. Voltage at compressor
10 Starting Voltage
Single Phase Models: 90% of the rated voltage min. terminals.
On Period: Until the oil level returns to the center of the lower bearing For at least 7 minutes -
11 On/Off Cycling on/3 minutes-off is
Off Period: Until balance of high and low pressure is obtained recommendable.
Specific gravity of the
12 Refrigerant Charge oil/refrigerant(wt.)≥0.35
Oil:0.94
13 Life Time 200,000 cycle
C-SB: Center of the lower bearing C-SB:Bottom of the lower bearing
14 Minimum Oil Level
C-SC:No less than 70% of the initial oil charge
Abnormal Pressure Pressure Rise: 4.15MPa(G) (602psig) Max. By high pressure switch
15
Rise/Drop Pressure Drop: 0.15MPa(G) (22psig) Min. By low pressure switch
System Moisture
16 200ppm Max.
Level
System 1 Vol.% Max. 24 hrs. after vacuuming:
17 Uncondensable Gas
Residual Oxygen 0.1 Vol.% Max. 1.01kPa Max.
Level
18 Tilt 5。Deg.Max.
Operation beyond the above limits must be approved by Panasonic Appliances Compressor (Dalian) Co., Ltd.
(G): Gauge Pressure
7
Notes
1 Installation should be completed within 15 minutes after removing the rubber plugs.
2 Do not use the compressor to compress air.
3 Do not energize the compressor under vacuumed conditon.
4 Evacuation and Refrigerant charge : Evacuate internal section in the refrigeration system from high and low pressure
sides and charge liquid refrigerant from condenser outlet side. Additional charge shall be done with gas condition from
low side.
5 Do not tilt over the compressor while carrying it.
6 Do not remove the paint.
7 Crankcase heater is required when the oil sump temperature is too low to meet the requirement of item 6 on page7.
8 Voltage fluctuation between compressor terminals, during operation, shall be within 2% of the rated voltage.
9 Do not operate compressor in reverse rotational direction.
10 Suction strainers are recommended for all applications.
11 Copper Piping Stress Start/Shutdown 34.32 N/mm2 Max.
Run 12.26 N/mm2 Max.
8
Section 7. Selection of Electrical Wire
Voltage drop may occur due to the large current draw during compressor starting.
We recommend selecting the wire size from the table below.
7.1 Type of Unit
7.1.1 Window & Commercial Type Unit ① outdoor
power source
③
terminal plate compressor
indoor
7.1.2 Split Type(Separate Type)
outdoor
power ① ② ③
terminal
source indoor plate
compressor
7.2 Size Table of Electrical Wire
Size of electrical wire(mm2)
Starting current Remark③(heat-
(A) Remark ① or Remark ①+②(heat-resistance Temperature: 60°C(140°F) min.) resistance Temperature:
120°C(248°F) min.)
5m max. 10m max. 15m max. 20m max. 30m max. 50m max. 1m max.
20max. 2.0 2.0 2.0 3.5 5.5 8.0 2.0
30max. ↑ ↑ 3.5 5.5 ↑ 14.0 ↑
40max. ↑ 3.5 5.5 ↑ 8.0 ↑ ↑
50max. ↑ ↑ ↑ 8.0 14.0 22.0 ↑
60max. ↑ 5.5 ↑ ↑ ↑ ↑ ↑
70max. 3.5 ↑ 8.0 14.0 ↑ ↑ 3.5
80max. ↑ ↑ ↑ ↑ 22.0 30.0 ↑
90max. ↑ ↑ 14.0 ↑ ↑ ↑ ↑
100max. ↑ 8.0 ↑ ↑ ↑ 38.0 ↑
110max. ↑ ↑ ↑ ↑ ↑ ↑ ↑
120max. 5.5 ↑ ↑ 22.0 30.0 ↑ ↑
140max. ↑ 14.0 ↑ ↑ ↑ 50.0 5.5
160max. ↑ ↑ 22.0 ↑ ↑ ↑ ↑
180max. ↑ ↑ ↑ ↑ 38.0 60.0 8.0
200max. 8.0 ↑ ↑ 30.0 ↑ ↑ ↑
220max. ↑ ↑ ↑ ↑ 50.0 80.0 ↑
240max. ↑ ↑ ↑ ↑ ↑ ↑ 14.0
7.3 Caution of Ground
The internal motor protector does not protect the compressor against all possible conditions.
Please be sure that the system utilizes the ground connection when installed in the field.
9
COMP. CODE A B C D E
809 28* 8*
809 18* 8* 538 284 486 7.9 289
809 29* 8* [21.18] [11.18] [19.13] [0.31] [11.38]
809 19* 8*
809 20* 8*
809 10* 8*
809 22* 8* 553 299 501 9 304
809 12* 8* [21.77] [11.77] [19.21] [0.35] [11.97]
C-SCP270,315,
360,400
77.2
U W
68.2
TAPPING SCREWS M4
TERMINAL
Part Code
D-0105-DSC
Name
Compressor Outline Drawing
10
No. Part QTY Name
1 M-0101-DSC 4 Mounting Grommet
2 M-0202-DSC 4 Mounting Sleeve
11
Part Code
M-5102-DSC
Name
Mounting Parts Listing
`
Compressor Model A
C-SCP270H38*
C-SCP315H38*
697 [27.441]
C-SCP360H38*
C-SCP400H38*
12
Part Code
D-0201-DSC
Name
Packing Dimensions
SWITCH
DISCHARGE GAS
V TEMP. SENSOR
POWER SUPPLY
50Hz 380~415V INTERNAL
PROTECTOR
R
U W
S
T
COMPRESSOR
TERMINAL MAGNETIC SWITCH
13
A 14
B 11
POWER SUPPLY C 12
50Hz 220V
REVERSAL
DEFENSIBLE RELAY
CRANKCASE HEATER
Part Code
E-0910-DSC
Name
Wiring Diagram