Elmeasure Branch Circuit Monitor Catalog
Elmeasure Branch Circuit Monitor Catalog
Note: Additional error of 0.1% of full scale, for meter input current below 500mA for 5A setting
Schematic Diagram
elmeasure.com
Product Selection:
PN 8700M ET 5030 ET 5730 ET 5720
ACCURACY OPTION Graphical LCD No Display With Display DS With Display
CLASS 1.0
Class 0.5S / Class0.2S
BASIC PARAMETERS
V12, V23, V31 * * *
V, V1, V2, V3 *
A, A1 ,A2, A3 *
Hz *
Angle V & A, RPM
Unbalance V & A
POWER PARAMETERS
W, W1, W2, W3 *
VA, VA1,VA2,VA3 * * *
PF, PF1,PF2,PF3 *
VAR, VAR1,VAR2,VAR3
POWER QUALITY PARAMETERS
THD - Voltage and Current upto 63rd * 15th 15th 15th
Individual Harmonics upto 63rd
K Factor, Crest Factor
High Low - Instantaneous
High Low - Last Minute *
Voltage Sag, Swell & Interruptions
Power cycles
TEHD and TOHD
Power THD and TDD
INTEGRATED PARAMETERS
Wh *
Vah * * *
VARh -Ind
VARh-Cap
Load Hours * * *
Phase Energy and Load hours * * * *
RD(IE)
Wh- Total and Net
VAh- Total and Net
VARh - Total and Net
ON hours
CO2 Emission
Bar graph ( % Load)
Volt squared hours
Amp squared hours
TOD PARAMETERS
TOD Demand - Import
TOD Energy - Import and Export
DEMAND PARAMETERS
Rising Demand (Sliding/Block - Programmable)
Forecast demand
Maximum demand
Demand Profile 4High & 4 Low *
ADDITIONAL FEATURES
12am & 31st day snap shot *
Data Logger - 1MB *
Load Efficiency *
Energy Trends *
Dynamic communication *
Dual Source *
COMMUNICATION
RS485 (MODBUS)
* *
Note: Default - Optional -
Default Optional
in communication only in communication only
elmeasure.com
Technical Specification:
PN8700M EL-Tag
GENERAL CHARACTERISTICS
Display type LCD 4 row, 7/8 Parameter
Instantaneous Digits
Integrated Digits 4 5 / no display
Sensing / Measurement True RMS, 1 Sec update time, 4 Quadrant Power & Energy True RMS, 1 Sec update time.
2 Quadrant Power & Energy.
Rated voltage 50-600 VLL
Rated current 10mA - 6A 10mA-6A, 50mA – 32A, 100mA – 63A
Frequency 45 - 65Hz
Poles description 1P + N, 3P, 3P + N 3 phase 3 channel
Sampling rate 512 samples / cycle 64 samples / cycle
Measured Accuracy Class Class 1 as per IEC 62053-21 / Class 0.5 / Class 1: IEC 62053-21 (Default)
Class 0.2S as per IEC 62053-22 (Optional). Class 0.5: IEC 62053-22 (Optional).
Programmable Setting 110 or 415V LL Nominal & Primary Programmable up to 999 kV. Burden: 0.2VA Max. per phase
Permissible overload 120%, Burden: 0.2VA per phase
External Fuse Rating 200mA No fuse
CT PT Ratio Max 2000MVA Programmable
Auxiliary supply 80-300V AC / DC Self Powered
Power consumption 4VA nominal
Data update rate 1 Sec.
COMMUNICATION
Device ID & Parity 1 to 247 & Odd, Even, None (Preferred Even)
Protocol & Interface Modbus. RTU, RS 485, TCPIP (Optional Wifi) RS 485 for stand alone
Baud rate 9600 bps to 38400 bps (Preferred 9600 bps)
Isolation 2000 volts AC isolation for 1 minute between communication & other circuits
ENVIRONMENTAL CHARACTERISTICS
Operating temperature -10°C to + 55°C (14°F - 131°F)
Storage temperature -25°C to +70°C (-13°F - 158°F)
Humidity 5% to 95% non-condensing
Altitude Below 2000mts
Measurement Category CAT III
Pollution degree 2 (As per IEC 61010)
PROTECTION CLASS
Ingress protection IP 51 ( IP 54 front facia optional ) & Double Insulation ( As per IEC 61010-1)
ELECTROMAGNETIC COMPATIBILITY
Electrostatic discharge IEC 61000-4-2
Immunity to Electromagnetic IEC 61000-4-3
RF Fields
Conducted Immunity IEC 61000-4-6
Immunity to Magnetic Fields IEC 61000-4-8
Immunity to voltage dips and IEC 61000-4-11
interruptions
Fast transient IEC 61000-4-4
Immunity to surge waves IEC 61000-4-5
Conducted and Radiated CISPR- 22
emissions
MECHANICAL CHARACTERISTICS
Weight Unpacked 350 gms. Packed 450 gms. (It may vary based on optional features) 200 gms
Torque 1 N-m (For 5A) 0.4 N-m
Wire gauge 11 AWG (For 5A) 26 - 10AWG (4.0mm2) – Voltage and
Communication
Mechanical Specification: Current Transformers:
90-0+2
96
90
46 25
90-0+2
Hang on CT-
5A or 50A or 100A or 200A Up to 100A, 16mm ID 1A - 1000A (ID: 800MM)
90
96 193
35
57
Clip on
CT-5A | 50A | 100A | 250A Split Core CT-100A | 400A | 1000A 5A - 3000A (ID: 400MM)
elmeasure.com
BM
BRANCH CIRCUIT
MONITOR
Multi Channel Load Manager | Power Distribution Unit/System
MODBUS
Current Transformers :
Mechanical Specification
Clip on CT-5A | 50A | 100A | 250A Split Core CT-100A | 400A | 1000A
67
72
90
45
49 elmeasure.com