TSM SG UL Series 10 500kVA S0-1-2 v3.9
TSM SG UL Series 10 500kVA S0-1-2 v3.9
Introduction
COPYRIGHT © 2003 by GE
The information contained in this document is intended solely for the purposes indicated.
The present documentation and any other publication supplied with the UPS system shall not be
reproduced, neither in part nor complete, without prior written consent of GE.
The illustrations and diagrams describing the equipment are intended as general reference only and
are not necessarily complete in every detail.
The content of this publication may be subject to modification without prior notice.
Summary of SG Series features:
This new family of UPS's, although in many ways similar to the currently manufactured SitePro
have some new concepts, in particular the access to all components, for maintenance and
repair, from the front of the UPS.
Below a summary of some of the more important differences valid for the total range 10 -
500kvA:
Output power range with date of February 2003: 10, 20, 30, 40, 50, 80, 100, 120, 150, 225,
300, 400 and 500kVA
Same cabinet size and architecture have: 10, 20, 30 and 40kVA, 50 and 80kVA, 100, 120
and 150kVA, 225 and 300kVA, 400 and 500kVA.
All cabinets have the same height and depth, but differ in width.
All components with the exception of power inductors and transformer are accessible from
the front for maintenance and repair. This allows placing of the UPS against a wall.
Rectifier input circuit breaker Q4 was replaced with a contactor K4.
The static switch has an additional contactor K8, which wraps around K6 and the SSM. The
SSM is therefore used only for the fast switching and is then short-circuited by K8. For this
reason it's not mounted anymore on a heat sink.
3 LEM's are placed in the Bypass connection. No LEM's at the Inverter output like on the A
version. Inverter current is measured with the LEM's of the load measurement. See UPS
Blockdiagram.
All UPS's are equipped with a Battery contactor K3, with the exception of the 400 and
500kVA units, which have fixed Battery fuses.
The function of the ventilators is controlled and an alarm given in case of failure. No control
of the ventilator speed.
The Load OFF button on the panel has changed to a Total OFF, since not only the output
contactors are opened, but Rectifier and Inverter shutdown, also K3 and K4 are opened.
DC floating voltage 540V for 240 Battery cells. (No other values!)
Utility input: 277V Phase / Neutral, 480V Phase / Phase.
Inverter output voltage: 277V Phase - Neutral, 480V Phase / Phase.
LEM replaced the current transformers for the load current measurement.
Space is provided for the integration of a 5th harmonic filter.
The 400/500kVA units have additional space for an optional 11th harmonic filter.
Units 225 - 500kVA can be equipped with an optional 3-wire kit, which allows to run the
UPS without Neutral (3-wires) at the input.
This however allows only to supply loads connected phase-phase.
See also the page "Variation" for a summary of various components, like
PC Boards and assemblies. Many of them different, depending from output power.
Copyright
2.3 27.10.2003
Back to Homepage
PMAD
Power Blockdiagram
Various
10 - 120kVA: All AC Neutral - Phase, except K3 with 24V
150kVA: All AC Neutral - Phase, except K3 and K7 with 24V
225 - 300kVA: All Phase - Phase, except K3 with 24V
Contactor supply
400 - 500kVA: All Phase - Phase, except K4 with 24V
Initial page
IS -Max
The output currents of the Inverter bridge and thus the current in the primary windings of the
transformer, we call series current .
To protect the IGBT's of the Inverter bridge, the bridge currents on two phases (L1 and L2) of
the output of the bridge are measured with 2 LEMs on phase L1 and phase L2.
The maximum allowable series current, which is power depending, we call IS - Max.
The level of IS - Max must be hardware installed with resistor
R 302 on the Main control board IM 0007.
A lower resistor value increases the IS-Max threshold value, a higher resistor value increases
the sensibility i.e results in a lower IS-Max level.
Resistor values vary, depending on the type of A/D Converter and UPS output power.
For description and values see the table in IM 0007_1 Layout.
Two Parameters (136, 137) define the strategy when a IS-MAX condition is detected, and this,
independent from whether mains bypass voltage is available or not, while a third Parameter 76
defines the automatic start of the Inverter.
Initial page
Layout IM 0051 C
This board replaces the version B and is mandatory for the UPSs SG-CE Series 1, but fully compatible also
for the SG-UL Units. Introduction 22.01.2007 with ECN 983.
After some cases of fan failure alarms (4522) without actual fan failure, a new version of firmware, dated
04.12.2007 was introduced, with IC2 version 5.3 on the board IM 0051C. (ECN 1099)
Remember, this Alarm has no effect on the UPS function, but should alert customer or service of a
possible problem or damage of one or more ventilators.
One board can control up to 10 Ventilators of varies types. In case of more Ventilators per UPS, 2 boards
can be connected in series, as this is the case for the 250 and 300kVA units.
The control is based on the measurement of the current drawn from each Ventilator.
Power supply for this board and the Ventilators is taken from the UPS output (IM 0046)
Connect, in Service mode, Bypass or Inverter to the UPS output, in order to have board supply.
Led 1 (green) must be lit.
After another 10 seconds LED 2 flashes for the number of Ventilators found.
LED 2 will flash now every 10 seconds indicating thus a new acquisition.
Disconnect UPS output voltage (Bypass or Inverter) and thus board supply.
Remove Jumper on J8 pin 4+5, in order to avoid that after every shutdown a new acquisition will
start, since the values of the previous acquisition are stored in the Flash Eprom.
In case the IM 0051C detects a bad Ventilator, Alarm 4522 (Fan failure) will be issued. This Alarm has no
influence on the function of the UPS, but is only a notification. Also, the involved Ventilator(s) cannot be
identified from this Alarm.
Cabinet size: 2050 x 850 x 1950 mm (width, depth, height)
Component Reference
F5, F6, F7 Bypass input fuses. (Only certain units) See above note.
F8, F9 Battery fuses (instead of K3)
F16, F17, F18 Bypass reference L1, L2, L3
F19, F20, F21 Inverter reference L1, L2, L3
F22 U - Inverter L1 for K50,. 5th filter
F23, F24, F25 Load reference L1, L2, L3
F11, F12 Transformer TR2 for AC Power supply
F13, F14, F15 Rectifier reference L1, L2, L3
F26, F27 DC - Voltage reference - / +
F28, F29 DC - Voltage for Power supply
F31, F32, F33, F34, F35, F36 Surge suppressors Utility inputs
F40 L2 Inverter for Phase-Phase contacter supply
The 400 and 500kVA units are available with optional input filters for the 5th and 11th harmonics.
5th Harmonic filter with Choke L50, Contactor K50 and Capacitors C50.
11th Harmonic filter with Choke L110, Contactor K110 and Capacitors C110.
Another option is the so called 3 wire kit, which allows input voltages (3 phases) without Neutral
connection. In this case however, also the load has to be Phase - Phase.
The 3 wire kit consist basically of the Choke L4, Capacitors C40 and Fuses 37 - 39.
Since 400 and 500kVA units have no K3 but fuses F8, F9 instead, an optional external K3 is available.
This however requires additional components and wiring, as shown in the schematic below.
Some units, with different order number, are equipped with Bypass fuses F5, F6, F7.
Attention: This fuses are not monitored !!!
Modifications
Changes:
Introduction of Firmware versions 3.30 for U2 & U3 and 10.0 for U36 of
1348 01.12.2009 the control board IM 0007. See the pages Upgrade instructions,
Firmware description and PMAD.
Problems with high temperature on the Resistors on the PC Board
IM0046. A short term solution will be, to solder the Resistors on the
solder side of the PCB and fix it then with 4 25mm spacers. A redesign
1419 19.02.2010 of the Board Layout will solve the problem.
Initial page
Parameters
Parameter Info
1st Level Parameters
2nd Level Parameters
Listing of Parameters 3rd Level
DSP Parameters
Power Depending Parameters
Initial page
Firmware upgrade 3.30 / 10.0
Firmware upgrade can be done for following reasons:
Installation and upgrade for DC Power supply failure detection. Described in ECN 1334.
Important: During Firmware update, the Load cannot be supplied from Inverter. In case Load supply
must continue, then it must be through Maintenance circuit breaker Q2. Only Logic Power on the UPS !!
Upgrade Procedure:
Before changing the Firmware, set Parameter 000 to the number corresponding to the UPS Series i.e.
00000 or 00001.
Turn OFF the Logic power and replace U2 & U3 with new version (3.30) and U36 (10.0)
Turn On the Logic power and verify the value of the following Parameters. If different set to values
shown below:
Turn Off the Logic power, wait 10 seconds, then turn Logic power ON again.
No Alarm should be present.
The Load can now be switched back to Inverter.
To update the unit to the FW 3.34-10.6 follow the procedure SP_03_2011 at this link
Initial page
Layout IM 0049 / IM 0075
Power Interface IM 0049
X1 UDC: pin1 + / pin2 -
X2 Utility Rectifier: pin1 L1 / pin2 L2 / pin 3 L3
Utility Bypass: pin1 L1 / pin2 L2 / pin 3 L3.
X3 Disconnect this plug for voltage free electronics, with Load supplied from maintenance Bypass
Q2.
X4 Inverter voltage: pin1 L1 / pin2 L2 / pin 3 L3 / pin4 Neutral
X5 Load voltage: pin1 L1 / pin2 L2 / pin 3 L3
X6 Command K6 and K8
X7 Command K7 and Auxiliary contact Q1 / Q2
X8 L1 / N Inverter and command K50
J1 LEM Rectifier current measurement
J2 LEM Battery current measurement
J3 Command K3 and auxiliary contact K3
J4 Flat cable to IM 0007 (Main control board)
J5 Flat cable to IM 0007 (Main control board)
J6 Fan error signal from IM 0051
J9 To bus extension board IM 0047 (K4, K8, K50
J10 Battery temperature
J11 Inverter transformer temperature
J12 Rectifier transformer temperature
J17 24VR from power supply Im 0002 for K3 and K4
J18,J19,J20 Lem Bypass L1, L2, L3
UDC TP1 + TP2 -
Utility Rectifier TP3 L1 TP5 L2 Tp4 L3
Utility Bypass TP6 L1 TP7 L2 TP8 L3
Load voltage TP9 L1 TP10 L2 TP11 L3 TP12 Neutral
Inverter voltage TP13 L1 TP14 L2 TP15 L3
LED 1 2 3 4 5 6 7 8 9 10 11
K7 K50 K6 K3 K8 K4 LEM Batt. Rectifier LEM Bypass
Initial page
Alphabetical list of pages
Blockdiagrams
Calibration Measurements
Commissioning
Frontview 10 - 20kVA
Frontview 30 - 40kVA
Frontview 50 - 80kVA
Modifications ECN
Software Versions
Initial page
UPS Front views
Click below to access a frontview of the units of various output powers and their principal
components
10 and 20kVA
30 and 40kVA
50 and 80kVA
100, 120 and 150kVA
225 and 300kVA
400 and 500kVA
Initial page
UPS Panel
Some "Hotspots" on the Panel lead you to detailed information
Events are the Alarms plus the Messages stored in the events memory, which can be visualized on the
display on the UPS by pressing the key "alarms", or clicking in Daisy onto "Events" . Totally 256 events
can be stored.
Alarms indicate a dangerous operational situation or a failure in the UPS, and are, apart from their
storage in the events memory, indicated by a yellow LED on the control panel and the sound of the
Buzzer, which can be silenced with a reset button. Examples: High DC - Voltage, Fuse failure, IS - Max.
Messages store information which in particular concern the function and operation of the UPS. Examples:
Rectifier ON, Load on Mains, Q1 closed.
Events are stored with date and time of the occurrence, in order to facilitate troubleshooting.
Go to the page Alarms or to the page Messages for a listing and a brief explanation of their signification.
In Parameters 77, 78, 79 it is possible to transform an alarm into a message, see the page "Alarm
suppression" for details.
In Parameter 411 some special configuration settings are possible, e.g. the shutdown of only the Module
in a Parallel system where the Load OFF (Total OFF) button was pressed.
Initial page
UPS Operation
Initial page
Commissioning
Before starting a unit some basic rules should be respected, in order to avoid injury or damage.
After placing the UPS(s) at it's final destination and having it unpacked, remove the side- and
protection panels.
With access to all parts, a thorough mechanical inspection should ensure the unit(s) has no damage
or loose bolts, screws, nuts or cables.
Remove transit bracket. Insure that the transit bracket and bolts on the transformer has been
removed. These bracket and bolts are painted in bright yellow.
Connect then all Input / Output cables according to the instructions in the Installation manual.
Note: If any problems with this installation are found that pose a threat to persons or equipment, do not
proceed until the problem has been corrected
Make sure breakers Q1 and Q2 are open. Then connect Mains voltage to the UPS (both if separate,
for Rectifier and Bypass)
Warning: Main Input Feed CB is closed and thus supplying LETHAL voltages to the system.
Caution: It is recommended that the load supplied by the UPS remains OFF until commissioning has been
completed.
Power supply starts and the display shows a self test, at the end of which, should result "Self test
ok" and the display changes to the Main page.
Press "Lamp test" on the panel. All LED's on the panel must blink and buzzer sounds.
Press keys "measuring", "alarms" and "parameters" to verify the function of the display.
Verify in Parameters for correct Date and Time. If incorrect adjust in User Parameters.
Verify in the Service Alarms for the presence of the code 9D04, which indicates the correct function
of important parts of the control board IM 0007. In case you find codes 9D00, 9D01, instead, a
malfunction on the control board is present. Change the control board !! The presence of code 9D02
could indicate a wrong setting of Parameter 292. (00020 instead of 00040), depending on wether
the fast AD-Converters are of 12 or 14-bit type. See more details of possible 9Dxx Error codes,
caused possibly from defective measurement components on the Power Interface or LEMs. See listing
of 9Dxx codes.
Verify LED's on Main control board IM 0007: D19 (supply voltage ok) and D27 (Master unit) must be
ON, D28 OFF, while D29, 30, 32 must be blinking.
Verify on Power interface IM 0049: B1 lit (correct phase rotation), LED's 1,2,3,4,5,6 OFF (Contactors
indication) and LED's 7,8,9,10,11 ON (Power supply LEM ok)
Measure and record all Power supply voltages on test points of Power supply board IM 0061. All
green LED's ON, red LED for AC supply ON (Exception for 400 and 500kVA, red Led always OFF) and
yellow LED for DC supply must be OFF.
Verify red LED's on LEM protectors for load current measurement, which connect directly to main
control board IM 0007. Must be ON.
Verify on Inverter drivers IM 0054 of phase L1 and phase L2: LED1 must be ON
(LEM for IS control)
Verify for correct values of following Parameters related to the Battery and the number of Battery
cells:
Parameter Function
84 Battery charge current limitation.
85 Battery capacity in A/h
Floating voltage. Normally 545 Volt for 240
88
Battery cells.
89 Number of Battery cells. (Normally 240)
103 Battery Backup (Autonomy) time
Verify during commissioning for correct voltages and currents in the measurements of the display of
the UPS. In case these should be different to what is measured with your precise instrument,
calibration is necessary. Refer to the page Calibration for procedure descriptions.
Verify correct Power wiring. In a parallel system the outputs of all units must be connected.
(Customers load not yet connected)
Close Q2 on 1st Unit.
Measure on 1st Unit with Voltmeter Phase L1 Utility - Phase L1 Load connection, followed by the
phases L2 and L3. Measure the same on all other units in case of a parallel system. Should you
measure voltage, you may have a miss wired output.
Open Q2.
Proceed now to startup the single UPS(s), following the description in the chapter "Low voltage
startup".
Run the UPS now in service mode, i.e. with Q1 open, and verify for the correct function of each
module. (Rectifier, Inverter, Bypass)
Once all unit's have been checked as single, you can proceed, in case of a parallel system, with the
paralleling. Go to page "Parallel startup".
To shutdown simply press the "Total OFF" button. Start then the Inverter for discharge of DC - Link
Capacitors. Stop Inverter when the DC voltage has reached ca. 20 Volt.
N.B. K3 will open when the Battery voltage reaches 388 Volt (1.62 Volt/cell), while Power supply shuts
down at 250 Volt.
Yes Not
Subject Description þ þ
General Documents and Database
Verify and eventually correct database and files with Customer information and reference
Check availability of PIOR and schematics
UPS and battery room: check environments and
temperature
UPS room Temp: ° Battery room Temp: °
Inform Customer about maintenance, UPS shutdown and risk of power outage
Check for Connectivity Solution, either on Intelligent Communication or Contacts (AS400). Inform user about disconnection
System configuration
Relevant options
12 Pulses rectifier
DCU
Yes Not
Subject Description
þ þ
General Check with UPS module running on LOAD (Q1 closed)
Check all FANS: rotation, noise and air outlet
Check mimic (front) panel and keyboard: LCD panel readable, clean, key function and LAMP TEST
Connect Service Application and read Alarms Memory. UP-LOAD parameters. Check measure readings.
INPUT SECTION
ñ Rectifier Input Current on each phase OK Not OK Check value and waveform of Neutral current (Typical. Freq. 150Hz)
L3 –
Rectifier Input Voltages: L1 – L2: V L2 - L3: V L1:
V
Phase
Input currents Phase 1: A Phase 2: A 3:
A
OUTPUT SECTION
cos
L1 LOAD voltage, current and cos j V: A: j:
cos
L2 LOAD voltage, current and cos j V: A: j:
cos
L3 LOAD voltage, current and cos j V: A: j:
L3:
Voltage Harmonic Distortion in % of the fundamental L1: L2:
L3:
Load current crest factor values (OK if lower than 3:1) L1: L2:
Alarm List Analysis. Notes about relevant events
Yes Not
Subject Description
þ þ
Switch Load on Maintenance Bypass (Q2) and Power Down the UPS
PCB: Perform a complete optical and mechanical check of the UPS module, connections and screws.
Mod: Ver: Look for indication of critical temperature on cables and components. Check with thermometer.
PCB: Verify on PCB’s modifications number and eventually update. Check Firmware version and eventually update.
Mod: Ver: Clean the UPS module.
Replacement of parts
Parts replaced: Fans Parts to be replaced: Fans (20000 hrs)
DC Capacitors (50000
DC Capacitors
hrs)
AC Capacitors (50000
AC Capacitors
hrs)
Lithium Battery (50000
Lithium Battery
hrs)
Batteries Batteries
Power Supply Check
Check correct LED (except 24V) are ON. Measure voltages on test points.
+5V +12V +18V +24VDR -12V +12VDR +24V
Rectifier section
Check Rectifier soft start and Battery contactor closure (command or indication)
Without temperature compensation, check and eventually correct UDC floating voltage UDC: V
Connect, if available, battery temperature probe. Check correct temperature indication on display and compensation
Remarks:
Yes Not
Subject Description
þ þ
Inverter section
Check Inverter soft start and measure inverter voltages. Eventually correct.
Nominal voltage: RMS values Þ L1: V L2: V L3: V
Measure Inverter and filter current. Verify waveform RMS and peak values with PIOR
L1 L2 L3
RMS values Þ A A A
Peak values Þ A A A
I CP values Þ A A A
Remarks:
Bypass section
Check and eventually correct phase shift INVERTER-MAINS
Command LOAD ON MAINS. Check output voltages
Check correct Inverter Voltage adaptation and LOAD ON INVERTER sequence
Disable BYPASS. Check INVERTER frequency during FREE-RUNNING. Note min and max value Þ Hz: to
With BYPASS disabled, disconnect INVERTER temperature probe. Check OVERTEMP and STOP OPERATION
Final Settings and Load on UPS
Check free potential contacts
Battery test. See separate sheet.
Erase alarm memory and reset statistic. Check UPS date and time.
Transfer load from maintenance bypass to inverter
Execute a Manual Battery test. Duration according to Backup time and previous battery test results. See separate sheet.
Check Battery charging current limitation (Max 20% of Capacity) Nominal: Measured:
Re-connect any previously connected device.
Further Action Required:
Signature:
Initial page
ID - Number (UPS serial number)
Through the ID - Number or serial number, a particular UPS can be exactly identified.
In the past , a number of 2 digits was used for the identification of the UPS-Type.
Example: 70 for Sitepro single, 71 for Sitepro parallel, 49 for D31) followed by a number of 5 digits.
From 1st October 1999 this identification number has changed on the new produced UPS's, due to the
introduction of a new Software for the order processing.
This new type of ID - Number is composed as follows:
Consecutive
UPS Type Series Output power Week of test Year of test
number
A = Sitepro single
B = Sitepro parallel
C = Sitepro US, single
D = Sitepro US, parallel
E = image
Examples:
F = Delta UPS series Week of final
Year of final test:
G = Lanpro 31 single number test:
8kVA=008 00001 - ....
H = Lanpro 31 parallel 1, 2, 3, 4, 5, 6,
20kVA=020 99, 01, 02...
I = 090 single 7, 8, 9 01 - 52
400kVA=400
J = 090 parallel
L = Lanpro 33 single
M = Lanpro 33 parallel
N = Lanpro 31 GE look, SW 1.8
P= SG Series, single and parallel
Initial page
PCB listing
IM 0004 Back plane for customer Interface P6
IM 0005 Customer Interface P4
IM 0006 RPA Board (Parallel board) P13
IM 0007 Control board, 10-500kVA P3
IM 0017 Panel board P5
IM 0025 SNMP card (optional) P30
IM 0023 LEM Protector P15, 16, 17
IM 0046 Minimum load for Bypass P12
IM 0047 Bus extension P14
IM 0048 Parallel communication connector (RJ_T) P18
IM 0049/75 Power Interface P1
IM 0050 Driver Inverter 50 and 80 kVA P8
Fan control 10-500kVA (225-500kVA 2pc.) IC2 version
IM 0051 B or C P19
5.3
IM 0054 Driver Inverter 100, 120, 150, 225 and 300 kVA P8, 9, 10
IM 0060 Driver Inverter + Rectifier 10, 20, 30 and 40 kVA P7
IM 0061 Power supply P2
IM 0064 SSM Driver (400 and 500kVA) P11
IM 0067 Power board Inverter, Rectifier 10-20kVA P24
IM 0070 Contactor control , 225-500kVA P25
IM 0075 Power Interface , 225-500kVA (compact. for all) P1
IM 0076 Power supply, should replace IM 8845
IM 0080 Inverter driver 400 and 500kVA P8, 9, 10
IM 6342 Driver SSM (10 - 300kVA) P11
IM 6343 Driver Rectifier (50 - 150kVA) P7
IM 6386 Filter for power supply (UDC) P20
IM 8821 Driver Rectifier 225 - 500kVA P7
Initial page
Software
Like the Sitepro also the SG Series are using the same control board IM 0007. On this board
we find the firmware for the UPS control, flash Eprom's U2 and U3 and the flash Eprom U36 for
the DSP control.
It's these 3 Eproms, due to their complex function, which are more frequently subject to
updates.
Below a chronological listing with description of changes and version.
The first UPS's have left Riazzino with following versions of Software:
Adaptation to the blown fuse detection without u-switch on the units of 10 and 20 kVA.
Corrections:
With load on Inverter, the alarm "K8 opening failure" was inhibited.
Alarm "K7 closing failure" was issued twice.
During stop operation, on a single UPS, the Inverter could not be shutdown with the key Inverter
OFF on the panel with Utility present.
(Transfer to Utility)
New Parameters:
Same function as the versions 5.0 and 5.1 for the Sitepros. Instead of having 2 versions however,
depending on A/D converters, only 1 version exists.
The setting of Jumper J23 defines now, whether the A/D converters are
12 or 14 Bit. See Layout IM 0007.
Jumper J23 on pin 7-8 ON = 14 Bit, no Jumper = 12 Bit
Reading of the Bypass currents (Parameters 338, 339, 340)
Changes 6.1:
Corrections:
With Parameter 76 (3 x IS Max in this window will block automatic Inverter start) different from
zero, an Alarm will always be generated, in case if IS Max.
K50 for the 5th harmonic filter can only close at the end of Inverter soft start.
It was not possible to modify the UPS name through the protocol.
In case of the opening of a Klixon for the Inverter bridge temperature control, the Inverter was
shut down immediately, without performing stop operation
New Parameters:
The word length for the UPS name was increased from 7 to 9 characters.
The Filter (Delay) for each signal of the output channels, can now be programmed also in the
numbered Parameters. (3rd level)
Example 30027: 300 Delay time in sec. / 27 Code number for function.
Pannel was changed to Panel.
Initial page
Adjustments
Adjustments are used to determine the configuration, functioning mode, tolerance settings,
measurement and calibration values and programming of functions.
Apart from some hardware configurations, mainly resistor values or settings of jumpers, which can be
found in the PIOR or the board layouts, Parameters allow an easy adjustment and adaptation of the UPS
to various operating conditions. See chapter Parameters for details.
Rectifier adjustments
Battery adjustments
Inverter adjustments
Bypass adjustments
Various adjustments
Initial page
Calibration
Calibration means, to make a measurement displayed on the UPS Panel or Graphic Display (Voltages,
Currents) the same, as the value of the same Voltage or Current measured with a precise instrument.
(Minimum resolution 10 times better than the display !!)
Calibration could be necessary after replacing the control board IM0007 or the Power Interface, and is
part of the commissioning procedure.
Calibration Parameters are listed in "Parameters", from 160 to 213.
Do not calibrate, i.e. change calibration Parameters with Rectifier and Inverter running. Where possible,
measurements and calibration shall be done with the UPS in Service Mode (Q1 open). Exception: Load
current.
Measure Load current with Load supplied from Bypass. Calibrate, without Load, and verify after for
correct measured values.
Calibration procedure for all measurement values, with the exception of UDC-Voltage, Inverter output
Voltages and Phase Error calibration Inverter - Mains
Measure with an adequate instrument the voltage or current of interest. (Remember, that for some
calibrations you might need load, in particular for the current calibrations)
Read the value of the corresponding voltage or current on the display or with Daisy.
If they are different, adjust the corresponding parameter until you obtain the same value on the UPS
display and on your reference instrument.
For calibration Parameters see the listing of Parameters, for factory installed values see the PIOR.
Calibration procedure for the Voltages UDC, and the 3 phases of the Inverter output Voltage are different
from the calibration of all other values. Below the description of how to proceed for this calibration.
UDC calibration (DC-Link Voltage)
If different, change the value of Parameter 168 until you obtain the same reading on the voltmeter
and the display.
(Increase value of Parameter to obtain lower Rectifier voltage.)
Adjust then, if necessary, with parameter 88, for correct floating voltage.
Attention: In addition to the above calibration, the UDC calibration for the DSP measurement is
necessary. After having done the above calibration, read the value in Parameter 183. Should the
reading be different to the measured value, change Parameter 182 to obtain the same reading.
(Example of Parameter 183: 4095, means 409,5 V)
Connect a voltmeter to the phase you want to calibrate and compare with the value displayed on the
UPS.
If different (more then +/- 1V), change the value of the corresponding parameter, until the Inverter
voltage is the same as the reading on the display.
Parameters are: Phase L1: 184, Phase L2: 186, Phase L3: 188.
(Increase value of parameter to obtain lower Inverter voltage.)
Adjust in Parameter 112 for the desired nominal Inverter output voltage for all 3 phases.
Measure with Q1 open and the Inverter running, with a voltmeter the voltage difference Inverter -
Mains, e.g. L1 Inverter - L1 Mains.
Initial page
Connectivity box
Go to the page Customer Interface for connections to this board.
In many occasions it might be useful to test the function of Rectifier and Inverter with a voltage low
enough to avoid damage in case of malfunction, in particular to the power modules, before running the
UPS in nominal voltage. Find below a description of this procedure:
Important:
At the end of Low voltage startup, the UPS must be shutdown completely, including power supply, in
order to reset some Parameters to their original values.
Important: In case of problems, the UPS can be, at any time, completely shut down by pressing the "total
off" button !!!
Initial status: The UPS is shutdown completely, Battery and Utility disconnected, Q1 and Q2 open.
Important: At the end of the procedure you must either shut down the UPS completely, including power
supply, or make a reset with PB2 on the main control board IM 0007, with DC - Capacitors discharged !!!!!!
Once the Rectifier is running with floating voltage, switch Inverter off and change Parameter 112 for the
Inverter output voltage, back to it's nominal value.
U
Parameter 217 UDC: Inverter OFF UDC: Inverter ON
Inverter
12 - Puls
17300 57V 35V 5V
17000 73V 50V 8V
16500 105V 74V 22V
16000 143V 100V 38V
15500 170 128 49V
04000 (Default) U - floating U - floating 50V
The values shown in this table are indicative, in particular the values in Parameter 217 should be chosen
on dependence of an actual existing problem !!!
The customer Interface IM 0005, inserted in the Connectivity Box, offers the following facilities:
6 programmable Output channels and 2 programmable Input channels on terminals or sub D plug,
see picture below.
Up to 3 Interfaces can be paralleled to increase the number of channels, but the connectivity box has
only space for either 2 customer interfaces, or 1 customer interface plus 1 SNMP card plus 1
environmental card.
Attention: Do not pull out the customer Interface with the UPS running, as an "Emergency Power OFF"
(EPO) would result !!
In case of paralleled Interfaces (up to 3) the Emergency OFF (EPO) contact is connected to one Interface
only, but the bridge on X2 and Jumper 3 must be removed on all other boards.
In a parallel system, each unit in the system needs it's own contact connected separately to the customer
interface IM 0005.
Please note: The programmable signals on X1 and J2 are disabled with Q1 open, with the exception of the signals for
Maintenance Bypass Q2 and Emergency OFF (EPO) !!!!!
Loading: Max. DC/AC 24V / 1,25A (IEC 950, SELV circuit)
Minimum signal level: % VDC / 50mA
J2 (sub D- Female 25 Pin) X1 Terminals
Default signal Default signal
Output Channels Contact type Pins Contact type
programmed programmed
1
NO, C, NC Mains failure X1 / 1, 2, 3 NO, C, NC Mains failure
J2 / 1, 2, 3
3
NO, C, NC Load Inverter X1 / 4, 5, 6 NO, C, NC Load Inverter
J2 / 4, 5, 6
5
NO, C, NC Stop operation X1 / 7, 8, 9 NO, C, NC Stop operation
J2 / 7, 8, 9
2
NO, C, NC Load on Mains X1 / 12,13,14 NO, C, NC Load on Mains
J2 / 14,15,16
4
NO, C, NC Common Alarm X1 / 15,16,17 NO, C, NC Common Alarm
J2 / 17,18,19
6
NO, C, NC Buzzer X1 / 18,19,20 NO, C, NC Buzzer
J2 / 20,21,22
Input Channels (closing contact)
1
Output Relay 1 X1 / 10,21 Output Relay 1
J2 / 10,23
2
Generator ON X1 / 11,22 Generator ON
J2 / 11,24
Bridge Ventilators with enhanced performance. See instructions for the replacement of the
Ventilators.
Modification on the connections of the Inverter bridge modules, to reduce stray inductance.
The fuses F37, 38 and 39 of the optional 3-wire kit are replaced with K40, a molded case
circuit breaker.
The lugs for the connection of input and output cables have been replaced with bus bars.
See the operating manual for a detailed description and instructions.
The fixing screw of the LEM for the Rectifier current measurement has now front access.
Initial Page
PMAD (Preventive Maintenance and Advanced Diagnostics)
Introduction
Installation
PMAD related Parameters
PMAD related Alarms
Features:
Communication Bus Detection
Connectivity Bus Detection
Lifetime Counters / Service Check
Current share detection
Peak current detection
DC Ripple detection
Cos - Phi measurement and Calibration
Initial page
Blockdiagrams
Simple blockdiagram
UPS blockdiagram
Inverter bridge blockdiagram 100-150kVA
Electronics blockdiagram
Power supply Blockdiagram
Inverter bridge Blockdiagrams
Initial page
Layout IM 0007D
Attention for the settings of Jumpers JP4, JP8, J29, J30 and J34. These can be different from the
Sitepro UPS's !!!
Attention: The red LED, which indicates the presence of AC Power, is not lit on the power range
225 - 500kVA, due to the fact, that the AC Voltage from transformer TR2 is rectified on the
Contactor board IM 0070, which is only used on unit's of 225 - 500kVA.
J1, J2, J3 Connect to Inverter drivers IM 0054, P8, 9, 10 , +12VR
J4 Connects to Rectifier driver IM 0063, P7, +18VT
J5 Connects to SSM driver IM 0064, P11, +18VT
J6 Not connected
J7 Connects to Power Interface IM 0049, P1, +24VK3
Connects to Control board IM 0007, P3
J8
5V, 12V, -12V, 12VDR, 24V, 24VR
J9 Connects to TR2, trafo for AC Voltage supply
J10 Connects to DC- Filter IM 6386 for UDC Voltage supply
Initial page
Layout IM 0006 and IM 0086
IM 0006
IM 0086
Attention:
IC2 is always inserted. Version 12.0 is compatible with version 7.0 and 7.1 of U36, the flash
Eprom for the DSP.
Version 13.0 is necessary for the functionality of PMAD and goes together with the versions
3.21 for U2 and U3, while U36 must be version 7.4.
Jumper settings
JP1 - JP6 ON Pullup resistors
JP15 - JP 20 ON Pullup resistors
JP7 ON Pin 2 / 3
JP10 OFF
JP 8, JP 9 ON Pin 2 / 3 with IC 2 OFF ON Pin 1 /2 with IC 2 ON
JP12, JP13, JP14 With IC2: OFF, ON, ON Without IC2: ON, OFF, OFF
JP11 OFF to enable old protocol on J11 (Sitepro)
BR. 1 - BR. 4 OFF
JP on Pin 9-10 on ISM and all
J4 No JP if only UPS
UPSs in configuration SCB
Layout IM 0005
The customer Interface IM 0005, inserted in the Connectivity Box, offers the following facilities:
6 programmable Output channels and 2 programmable Input channels on terminals or sub D plug,
see picture below.
Up to 3 Interfaces can be paralleled to increase the number of channels, but the connectivity box has
only space for either 2 customer interfaces, or 1 customer interface plus 1 SNMP card (IM 0025) plus
1 environmental card.
Attention: Do not pull out the customer Interface with the UPS running, as an "Emergency Power OFF"
(EPO) would result !!
In case of paralleled Interfaces (up to 3) the Emergency OFF contact is connected to one Interface only,
but the bridge on X2 and Jumper 3 must be removed on all other boards.
In a parallel system, each unit in the system needs it's own contact connected separately to the customer
interface IM 0005.
Please note: The programmable signals on X1 and J2 will be disabled with Q1 open, with the exception of
the signals for Maintenance Bypass Q2 and Emergency OFF (EPO) !!!!!
Loading: Max. DC/AC 24V / 1,25A (IEC 950, SELV circuit)
Minimum signal level: % VDC / 50mA
J2 (sub D- Female 25 Pin) X1 Terminals
Contact Default signal Default signal
Output Channels Pins Contact type
type programmed programmed
1
NO, C, NC Mains failure X1 / 1, 2, 3 NO, C, NC Mains failure
J2 / 1, 2, 3
3
NO, C, NC Load Inverter X1 / 4, 5, 6 NO, C, NC Load Inverter
J2 / 4, 5, 6
5
NO, C, NC Stop operation X1 / 7, 8, 9 NO, C, NC Stop operation
J2 / 7, 8, 9
2
NO, C, NC Load on Mains X1 / 12,13,14 NO, C, NC Load on Mains
J2 / 14,15,16
4
NO, C, NC Common Alarm X1 / 15,16,17 NO, C, NC Common Alarm
J2 / 17,18,19
6
NO, C, NC Buzzer X1 / 18,19,20 NO, C, NC Buzzer
J2 / 20,21,22
Input Channels (closing contact)
1
Output Relay 1 X1 / 10,21 Output Relay 1
J2 / 10,23
2
Generator ON X1 / 11,22 Generator ON
J2 / 11,24
Layout IM 0051B
A new board IM 0051C was introduced for the SG-CE Series 1.
This board replaces the version B and is mandatory for the UPSs SG-CE Series 1, but fully
compatible also for the SG-UL Units. Introduction 22.01.2007 with ECN 983.
After some cases of fan failure alarms (4522) without actual fan failure, a new version of
firmware, dated 04.12.2007 was introduced, with IC2 version 5.3 on the board IM 0051C. (ECN
1099)
Remember, this Alarm has no effect on the UPS function, but should alert customer or service of
a possible problem or damage of one or more ventilators.
Ventilators are of the same type for all UPS's in the power range 10 to 150 kVA (28 Watt) .
The ventilators of all SG Series UPS's are controlled for their function.
The current of each ventilator is measured and in case of an over current condition (mechanical wear out,
dirt or bad ball bearings) the alarm fan failure 4522 will be given.
When replacing this board an auto setup must be activated. Follow the steps below:
Attention: Be aware that high voltage (230V) connect to this board, in particular when doing the
procedure below, avoid to touch any possible live parts. Use isolated pliers to remove and insert Jumper
JP1 !!!
Connect Utility. After Self test close Q1 and verify if all the ventilators are running at full speed.
Remove Jumper JP1 on IM 0051. After a short while, LED1 should blink twice, thus indicating
activation of auto setup.
After a few seconds LED1 should blink as many times as ventilators are present.
This is the confirmation, that all ventilators have been recognized.
Should for whatever reason the count of ventilators result to be wrong, then a reset of the circuit is
necessary, by doing the following:
Reset Load OFF and remove then JP1 to start another auto setup. Verify if number of ventilators
corresponds to the number the LED is blinking.
Verify eventually the voltage on the secondary of TR3 (supply voltage for the ventilators), which should
be 230V +/- 10%.
The units of 225 - 500kVA have 2 boards IM 0051, with P18 mounted on top of P19. P19 supplies the
ventilators for the bridges, while P18 supplies the ventilators for the magnetics, as follows: ( Rx: R49 on
IM 0051 must be 62k for this configuration)
400-500kVA Bridges Magnetics
Number of Ventilators 6 x 1000m3/h 10x 500m3/h
Software 2.0 / P19 1.1 / P18
R ON R OFF
kVA IGBT
R21, 32, 72, 83, 118, 129 R12, 44, 64,95, 110, 141
10 50A 33 Ohm 51 Ohm
20 100A 22 Ohm 51 Ohm
30 150A 22 Ohm 51 Ohm
40 200A 22 Ohm 33 Ohm
Initial page ¦ PC Board listing
Layout IM 0050B
Layout Driver Inverter for UPS 50 and 80 kVA
IM
0061:
IM 0007: Main control board IM 0054: Driver Inverter
Power
supply
The Inverter bridge of the 750kVA is identical, however with an additional Inverter module,
thus totally 9 primary Transformer windings
R 302 R 298
UPS Power IS Max
Depends on A/D converter type. 12/14 (UDC
(kVA) Amps
Bit Max)
Power
7864 AS -1 7865 AS -3
IF IM
7865 BS -1 14 Bit
0075
10 75 6k2 5k6 1k2
20 150 1k5 1k2 1k2
20 (Healthcare) 180 4k3 3k9 1k2
30 200 3k 2k7 1k2
40 320 1k 820 1k2
50 500 2k2 1k8 1k2
80 500 2k2 1k8 1k2
100 900 1k 680 1k2
120 900 1k 680 1k2
150 900 1k 680 1k2
225 1750 2k7 2k 1k2
300 1750 2k7 1k8 1k2
400 2600 1k8 1k5 1k2
500 2600 1k8 1k5 1k2
2 Software version micro read only Each of this components has implemented software.
Software can be subject to changes, and has
3 Software version DSP read only therefore a label with a number for easy
identification.
4 Software version FPGA read only In this Parameter you can read the version number.
139 Temperature for ventilator 50 (°C) Set point for maximum ventilator speed
220 Min. Rectifier pulse 7000 Minimum Rectifier pulse length (1 unit = 400ns)
221 Secure pulse length 15000
Rectifier start delay after Mains return in seconds.
222 Rectifier delay 5
(Poss. values 1 - 300 sec)
Rectifier soft start speed
223 Rectifier soft start 30
26ms x Max. Rectifier pulse / Rectifier soft start
Mains Rectifier period:
224 Rectifier period 50000 50000 for 50 Hz, 41666 for 60 Hz (1 unit =
400ns)
Max. Mains Rect. period
225 5000 Max. Mains Rectifier phase error (1 unit = 400ns)
error
226 Rectifier Mains phase shift 16666 Phase to phase value L1 - L2 - L3 (1 unit = 400ns)
227 Max. Mains Rect. phase error 5000 Phase to phase error, L1 - L2 - L3 (1 unit = 400ns)
Parameters
Alarms
Setup values lost
During startup of the electronics or after a reset (watchdog or manual) the soft verifies the RAM
status by checking the value in Parameter 319. Should this value not be "26028", the CPU will insert
default values in various Parameters.
4000
This situation is indicated, as Parameter 5 will be set to 1, and thus inhibit the start of Rectifier and
Inverter.
Parameter 5 must be set to 0 manually and the setting of the rest of the Parameters verified with
PIOR, prior to start Rectifier and Inverter.
Watchdog reset
The watchdog circuit ordered a reset of the CPU.
In case the UPS did supply the load while the crash happened, a hardware circuit will activate the
4002 SSM and order the closure of K6. (Valid only for single units !!!)
The load is thus supplied from Mains.
After 30 seconds the Inverter will start automatically and supply the load if the actual conditions will
allow this and the Inverter was previously started manually.
UPS Failure
The master unit has detected the absence of a unit on the communication bus without the correct
4004
shut down sequence took place, i.e. the opening of Q1 of this unit.
Verify communication bus cabling.
Rectifier fuses
Micro switch on one or more of the Rectifier input fuses, indicate a blown fuse(s) and will cause the
shutdown of the Rectifier. As soon as the alarm is eliminated the Rectifier will again start
4100
automatically.
K4 closing failure
4102 Auxiliary contact on K4 indicates an open contactor after a closure command.
(Contact open with K4 open) Rectifier cannot start.
K4 opening failure
4103 Auxiliary contact on K4 indicates an closed contactor after a opening command.
(Contact open with K4 open)
Battery fuses (external)
(External Battery fuses) was programmed on one of the Input channels, of the three possible
Customer Interfaces IM 0005.
4104 The closure of this contact indicates either a failure of an external Battery fuse or failure of closure of
an external Battery contactor K3.
In case of paralleled Rectifiers on the same Battery, this causes the disabling of the Rectifiers current
share, however no other action.
4110 At least one of the voltages measured phase - phase, is out of tolerance.
Mains Rectifier frequency out of tolerance.
Incorrect phase rotation of the Mains Rectifier
Battery backup time is less then the time defined in Parameter 102, due to Mains Rectifier out of
tolerance. With no change i.e. Mains Rectifier voltage ok or a reduction of load, the Inverter will
shut down after timeout. The Inverter starts automatically, as soon as the backup time of the
battery has reached the time of Stop operation with the actual load.
The battery voltage results to be below the value set in Parameter 91.When the Battery voltage
4115
reaches the value in Parameter 90, the Inverter will shut down (Minimum voltage).
The Inverter restarts automatically as the battery voltage has reached the value in Parameter
92. (Nominal voltage)
The above mentioned conditions can be present at the same time. In this case Stop operation ends
only if backup time is superior then the time set in Parameter 102 and the Battery voltage is above
the value set in Parameter 92 (U-Nominal).
During Stop operation, the Inverter cannot be shutdown manually with the key OFF.
High Battery voltage
This Alarm can be from two independent sources. First source is the normal measurement of the DC
Voltage, second source is the UDC - Max detection circuit.
In the first case the Inverter is shut down if the situation persists to the following scheme:
(Remember that values indicated in the Parameters below are always displayed for 192 cells, to
obtain the actual value, calculate with the present number of cells.)
After 10 seconds if the voltage measured is within the values defined in Parameters 93 and 94.
4116
After 5 seconds if the voltage measured is within the values defined in Parameters 94 and 95.
Immediately if the voltage measured is superior the value defined in Parameter 95.Valid for any
type of Battery used !!
The Inverter will automatically start again, as soon as the voltage descends below the value of
Parameter 93.
In the second case the Rectifier is shut down, and will automatically start again as soon as the signal
from the UDC - Max detection has vanished. (Hardware circuit with hysteresis)
Battery fault
During Battery test the DC - Voltage resulted to be below the value set in:
In any of the above cases, the test will be stopped immediately, and the Rectifier returns to floating
voltage.
Inverter fuses
Signal from the auxiliary contact(s) of the Inverter output fuses This causes the shutdown of the
4301 Inverter which cannot be restarted as long as this condition persists.
Verify:
Fuses, u-switch fuses and related cabling
K7 closing failure
4304 After a closing command for K7 the auxiliary contact of K7 indicates the later is not closed.
(Auxiliary contact normally closed.)
K7 opening failure
The auxiliary contact of K7 indicates the closure of K7 without a closing command, consequently the
4305
Inverter cannot be started.
(Auxiliary contact normally closed.)
Inverter output transformer over temperature (150 - 500 kVA only)
The Klixon inside the transformer windings indicate a situation of over temperature.
With Mains available the load transfers immediately to Mains and the Inverter is shutdown.
4307
With Mains not available the load will be supplied for 3 Minutes from Inverter, then the Inverter is
shutdown, if the condition has not changed.
The Inverter starts automatically again as soon as the temperature reaches normal values.
Blown DC Fuse
4308 One or more of the DC fuses are blown and consequently the Inverter shutdown.
The Inverter can be restarted manually as soon as the alarm condition is removed.
Driver failure
Detection of a failure on one or more SKIIP modules of the Inverter. (Over current, over voltage or
4309 over temperature)
After removal of the failure condition(s), the Inverter can be started again manually.
(N.B. Only 400 tand 500kVA)
K6 closing failure
4404
The logic detects the auxiliary contact of K6 indicating K6 to be open or closed with delay.
K6 opening failure
4405
The logic detects the auxiliary contact of K6 indicating K6 to be closed or opened with delay.
SSM failure
Despite the blocking command for the SSM, a difference in the load currents at the input of K7 and
the input of Q1 was detected.
4406 A command to open K6 for 10 seconds is given, after which K6 is closed again. If after 3 times of
this, the currents are still different, then K6 remains open definitively.
Currently set to a value of 40000, which actually disables a detection. (17.05.02)
Parameter 297.
K8 closing failure
4408 Auxiliary contact on K8 indicates an open contactor after a closure command.
(Contact open with K8 open)
K8 opening failure
4409 Auxiliary contact on K8 indicates an closed contactor after a opening command.
(Contact open with K8 open)
Mains Bypass out of tolerance
Voltage Mains Bypass is signaled to be out of tolerance due to one of the following conditions:
At last one of the voltages measured phase - Neutral are out of the tolerance set in Parameters
4410
118, 119
Mains frequency out of tolerance
Incorrect phase rotation at the Mains Bypass input
K3 closing failure
4420 The logic detects that K3 after a closing command is not closed. (Aux. contact normally open)
With Q1 closed, the Inverter cannot be started.
K3 opening failure
4421
The logic detects that K3 after a opening command is not open. (Aux. contact normally open)
Fan failure
4522
The fan control board IM 0051 indicates a malfunction of one or more ventilators.
Load locked on Mains
The UPS has blocked the load on Mains after detection of 3 transfers Inverter - Mains in less than the
4530
time in seconds specified in Parameter 75.
The load is free again for transfer at the end of the time in seconds defined in Parameter 74.
Overload
See also chapter Overload.
UPS in overload condition, with load >125% on Inverter and Mains not available. This overload
condition will cause a timeout with stop operation, according to the table below, followed by a "Load
OFF" at the end of it.
On Mains, any load superior 150% is considered as overload, without however going into stop
operation, as in the previous Sitepros of series 4 and 5 !!
4570 Load on Inverter and bypass not available:
After timeout the Inverter is shut down and can be restarted after a delay of 3 Minutes.
DC Low
The Battery voltage measured is below the value installed in Parameter 90 (U-Minimum)
(Attention the displayed value always corresponds to 192 cells, while decision taking is based on the
4700
value calculated from the number of cells installed in Parameter 89 !!!)
The Inverter is shutdown and can be restarted only when the Battery has reached the level installed
in Parameter 92 (U-Nominal).
Any load superior 100% of the nominal output power, also if applied only to one of the three phases,
must be considered as overload.
Attention: The calculation for an overload condition is based on the load current of each phase. It's
therefore possible to read an overload percentage of a single phase, while the percentage of the UPS total
load indicates less then 100%, this often due to a phase shift, current - voltage, which is different to the
value of 0,9 or 0,8 specified.
The response of the UPS to an overload condition is depending on the percentage of overload as follows:
Important: The description below is valid also for paralleled UPS's. In this case however not the load of a
single UPS is considered, but the system load. Therefore the parallel system reacts identical to overload
as a single UPS would.
Please Note: Introduction of Firmware version 3.18 for the control board with ECN 1289. With this
version the timeout and percentage of some values of Stop operation have been modified as follows:
> 115%: With Utility available, transfer to Mains and Alarm 4571: Overload: Load on Mains. With
Utility not available Alarm 4570: Overload.
> 125% Alarm 4570: Overload + Stop operation, with timeout depending on load percentage. (125%
=10 Minutes, 150% = 30 Seconds) See Alarm 4570.
In case Utility voltage is not available, timeout of stop operation starts At the end of which the
Inverter is shutdown and the output transferred to Utility.
In case of separate inputs for Rectifier and Bypass and Utility failure only for the Rectifier, the load is
transferred to Bypass at the end of stop operation.
Should during the timeout of Stop operation the load decrease below 100%, then Stop operation
terminates and the message 4572: No more overload, will be issued.
Auto start: The Inverter starts again automatically after 3 Minutes recovery time, after the end of
Stop operation and Inverter shutdown.
See ALARMS 4570, 4571 and message 4561 for Stop operation timeout and Overload values with
load on Mains.
Initial page
Description of changes with Firmware 3.30 & 10.0
Adapting the Rectifier Mains input frequency range to the values in the Data sheet. (+/- 10%)
Parameter 313 for the programming of the functionality in case of Rectifier overtemperature. (4105
& 4106)
Parameter 360 allows to choose between Battery backup algorithms, in particular the calculation
based on active Load power.
In page 6, line 3 of the Display, the necessary number of UPS (x UPS) for redundancy in a parallel
system is indicated, instead of the previous Load percentage. On a single unit the this indication
remains blank.
Discontinuity on the communication lines of the parallel bus or the connectivity bus. (Parameters
249, 251, 262 and 263.)
Problems of Load sharing. (Parameters 350, 259 and 261)
High AC - Ripple on the DC-Link voltage. (Parameter 349)
Time out for the replacement of critical components, like Battery, DC-Capacitors, AC-Capacitors and,
or Ventilators.
Inverter Series current will be considered once the RMS Load current exceeds the threshold set in
Parameter 253,
in addition it takes into account the Inverter voltage, the active Load power, the AC-Capacitors value
and the output cos phi.
Active Load power is defined in Parameter 337.
Visualization of the Power factor can be activated in the measurement pages of the Display with
Parameter 388 with +/- 0.xx. While + indicates inductive Load, - indicates capacitive Load.
In Parameter 389 the behaviour of Contacter K6 can be defined. Now, with blocked Bypass, K6 opens
only when the SSM is switched OFF.
Battery Boost charge is introduced with Parameter 413 for Boost charge ON level, Parameter 414
defines the Boost charge OFF level, while Parameter 412 the Boost charge voltage per Battery cell
can be set.
New Service codes have been created for the monitoring of the fast A/D converters (9D10 - 9D1D).
Forthe slow A/D Converters the codes are 9D20 - 9D2A.
In Bit 02 of Parameter 411 the action of Load OFF in a Parallel system can be defined:
Bit 02 set for 0 = Load OFF (default) for all units of the paralleled system. Set to 1 = Load OFF only
on this Unit (in this case individual Load OFF reset on each unit).
In Parameter 366 the behaviuor of the UPS in case DC Power supply failure can be defined. Default
setting = 00002.
With this configuration Rectifier and Inverter will shutdown and K3 open in case of failure. (Alarm
4701 is issued)
Apart from a few Resistors Rx, all settings, adjustments, calibrations and personalization of the UPS,
must be done with the Parameters.
Parameters are divided into 3 levels: See also "Access to Parameters" below.
User Parameters: These Parameters can be directly accessed from the panel by pressing the key
"Parameters"
Expert Parameters: To access this Parameters a password is needed. Some basic settings of the UPS
like output voltages or number of battery cells can be defined.
Service Parameters: Access with a Password different to the above, only for Service engineers.
Expert Parameters are displayed first, when entering the service Parameters.
Attention:
Although you have complete access to all Parameters, this does not mean to have the permission to
change them all. In particular Parameters related to Rectifier and Inverter regulation shall not be
touched, unless ordered or suggested from our diagnostic experts which can be addressed under service-
[email protected] .
This Parameters are therefore neither listed nor explained in this document.
The value of some Parameters might change due to adaptions, new experiences or improvements. In the
page Software a chronological listing of some of this changes are shown.
Below a description of the main functions of the Parameters, followed by an explanation of how to access
the different levels of the Parameters.
Parameters of similar functions can be put into one of the main groups shown below:
Access to Parameters
Parameters offer in a most convenient way the possibility of adjustments, adaptions and other
interventions on the UPS, without any hardware changes, allowing thus to resolve many problems due to
specific loads or particular Mains conditions by simply changing a number or value.
As much this can help to resolve problems, as much it can create problems if settings of Parameters are
wrong.
To protect therefore the customer and the UPS from wrong manipulations, some of the Parameters are
accessible only with a password.
The Parameters are for that reason divided in 3 levels:
First level: Access without password, simply by pressing the key for the Parameters.
Parameters on this level have no influence on the function of the UPS and are translated in every
available language. See listing below.
To access the Password screen press the keys for "ok" and "parameter" simultaneously.
Second level: Intended for the customer with advanced knowledge and of course the service
engineer. Access only via password. (Parameters are displayed only in English) Listing see below.
Password: "YYYYYYYY"
Third level, reserved exclusively for the service engineer, with access to all Parameters, with a
password which is different to the above.
Listing see Parameters List. Password: "0XXXXXX0".
In third level Parameters also the second level Parameters are displayed.
After entering the desired level of Parameters, scroll with the "+" key to the page of the Parameter
you want to change.
Move then the cursor with Key "-" to the Parameter you want to change.
Press Key "ok" to enter edit mode.
Move with Key "+" the cursor to the Parameter value you want to change and change with Key "-".
Make sure for correct value, then confirm and install the new Parameter by pressing again Key "ok".
Press "metering" to return to the main screen.
N.B. As long as the new value is not confirmed with Key "ok", you can exit at any time the
Parameters without any change, by pressing either Key "measuring" or Key "alarms".
Initial page
Parameter 1st Level (User)
Press key "parameters" for access
Parameters on the screen Meaning of Parameter
DATE AND TIME
dd.mm.yy (must be later 1966)
Date
hh.mm.ss (format 24h)
Time
PROTOCOL SETUP
Y/N
Modem enabled
String of max. 15 characters
Init
Y/N
Alarm
Delay in seconds (0 - 99)
Delay
Tel 1 Max. 15 characters
Tel 1 enabled Y/N
Tel 2 Max. 15 characters
Tel 2 enabled Y/N
Tel 3 Max. 15 characters
Tel 3 enabled Y/N
Tel 4 Max. 15 characters
Tel 4 enabled Y/N
LCD Display Give the UPS any name you like. Max. 7
UPS name characters
Contrast Contrast of LCD Display (0 - 9)
Language Choose 1 of 10 possible languages.
PRINTER SETUP
600/1200/2400/4800/9600
Baud
Odd / even / X no (parity)
Parity
7 or 8
Bits
Xon / No
Handshake
Y/N
Print All
PRINTER COMMANDS
Y/N
Print Measure
Y/N
Print Alarms
Y/N
Print Parameters
Par. kVA
10 20 30 40 50 80 100 120 150 225 300 400 500
086 40 40 60 60 60 80 80 80 100 100 100 150 150
139 50 50 50 50 45 45 45 45 45 45 45 45 45
160 130 130 250 250 250 500 1000 1000 1000 2500 2500 3750 3750
163 16 24 40 56 80 160 160 160 320 320 320 480 480
164 65 65 125 125 250 250 500 500 500 1250 1250 1875 1875
166 65 65 125 125 250 250 500 500 500 1250 1250 1875 1875
199 40 40 45 45 45 55 70 70 110 110 110 110 110
200 270 400 800 800 800 1600 1600 1600 1600 4800 4800 8000 8000
202 270 400 800 800 800 1600 1600 1600 1600 4800 4800 8000 8000
204 270 400 800 800 800 1600 1600 1600 1600 4800 4800 8000 8000
228 9300 11300
234 32768 32768 32768 32768 8192 8192 8192 8192 2048 2048 2048 2048 2048
235 8192 8192 8192 8192 2048 2048 2048 2048 512 512 512 512 512
236 4096 4096 4096 4096 4096 4096 4096 4096 2048 2048 2048 2048 2048
237 512 512 512 512 512 512 512 512 128 128 128 128 128
254 2530 2530 2833 2833 2833 3035 3035 3035 3035 3035 3035 3035 3035
297 3 5 10 10 20 20 20 20 20 40 40 50 50
253 1 3 4 6 7 11 14 17 21 31 42 55 69
314 50 100 200 200 200 300 350 400 600 900 1200 1600 2000
351 8174 10267
337 3600 4500
350 14 29 43 58 72 115 144 176 216 328 432 576 722
395 100 100 100 100 150 150 150 150 200 200 200 300 300
110 12 24 36 48 60 96 120 144 181 271 361 481 602
111 36 72 108 144 181 289 361 433 542 812 1083 1444 1805
Remarks:
Further Action Required:
Initial page
Daisy
Same cable as for the old Protocol. Connection can be to the RS 232 port on the Customer Interface IM
0005 for the new protocol, or to J11 for the old protocol.
Daisy will recognise automatically either of the protocols. That means you can use this Daisy also on
Sitepro units of older series. Different plugs for old / new protocol.
However, the information from the UPS, also sometimes shown in a different form, is identical to the
information of the old Protocol.
Disadvantage: Due to the increased word length in the new Protocol (32 bit instead of 16) and identical
Baud rate, this Daisy is reacting very slow.
Advantage when used on Parallel systems: Since the new Customer Interface IM 0005 has a "Bus
structure", no enabling or disabling with Jumpers of the RS 232 port is necessary, as it is necessary with
the old Protocol.
You can plug in Daisy on any RS 232 port on any Parallel Unit of series 6.
In version 0.0 of Daisy, a file called codes.eve is missing. This file exists on all older versions and can be
copied directly from any Daisy to this new version.
To activate Daisy after starting it, you must first select the COM port. See below.
Initial page
Emergency OFF
In a case of danger it is possible to shut down immediately the UPS and to separate it from the load and
input by opening an external contact of a "Emergency switch", (Mushroom type) which must be
connected to the customer interface IM 0005 of the UPS.
See the page Customer Interface for connection details, or the operating manual.
The condition is signaled with the alarm Emergency off / Total off, 4563
The UPS remains in this condition as long as the contact stays open.
Press the key "OFF" (Inverter OFF) on the panel, for Reset of Emergency OFF.
K6 closes and the SSM activated then closes K8, if bypass utility is available and Q1 is closed.
The load is then supplied from utility.
K4 closes, the Rectifier starts and K3 will close at the end of soft start.
IMPORTANT:
In case of paralleled Interfaces (up to 3) the Emergency OFF contact is connected to one Interface only
(any of the 3), but the bridge on X2 and Jumper JP3 must be removed on all other boards.
In a parallel system, each unit in the system needs it's own contact connected separately to the customer
interface IM 0005, respecting the above, in case of more then one Interface.
Initial page| Customer Interface
Front view 10 and 20kVA
Cabinet size: 680 x 800 x 1800 mm (width, depth, height)
Component Reference
F16, F17, F18 Bypass reference L1, L2, L3
F19, F20, F21 Inverter reference L1, L2, L3
F22 U - Inverter L1 for K50,. 5th filter
F23, F24, F25 Load reference L1, L2, L3
F11, F12 Transformer TR2 for AC Power supply
F13, F14, F15 Rectifier reference L1, L2, L3
F26, F27 DC - Voltage reference - / +
F28, F29 DC - Voltage for Power supply
F31, F32, F33, F34, F35, F36 Surge suppressors Utility inputs
Initial page
Front view 30 and 40kVA
Click on any of the PCB's to access their layout
Cabinet size: 680 x 800 x 1800 mm (width, depth, height)
Component Reference
F16, F17, F18 Bypass reference L1, L2, L3
F19, F20, F21 Inverter reference L1, L2, L3
F22 U - Inverter L1 for K50,. 5th filter
F23, F24, F25 Load reference L1, L2, L3
F11, F12 Trafo TR2 for AC Power supply
F13, F14, F15 Rectifier reference L1, L2, L3
F26, F27 DC - Voltage reference - / +
F28, F29 DC - Voltage for Power supply
F31, F32, F33, F34, F35, F36 Surge suppressors Utility inputs
Terminals to Load, and connection to Rectifier utility in case
X1
of separate inputs for Rectifier and Bypass.
X2 Terminals for utility input
Step down transformer of Bypass utility voltage for AC
T2
power supply.
Step down transformer of UPS output voltage for the supply
T3
of ventilators and 24 Volt external supply. ( 277V - 230V)
3 Ventilators for Inverter and Rectifier bridge cooling.
Ventilators 3 (2 for 30kVA) Ventilators, accessible from the top of the
UPS, for the cooling of the magnetic components.
Initial page
Front view 50 and 80kVA
Click on any of the PCB's of the drawing below to access layout.
Cabinet size: 800 x 800 x 1800 mm (width, depth, height)
Component Reference
F16, F17, F18 Bypass reference L1, L2, L3
F19, F20, F21 Inverter reference L1, L2, L3
F22 U - Inverter L1 for K50, 5th harmonic filter
F23, F24, F25 Load reference L1, L2, L3
F11, F12 Trafo TR2 for AC Power supply
F13, F14, F15 Rectifier reference L1, L2, L3
F26, F27 DC - Voltage reference - / +
F28, F29 DC - Voltage for Power supply
F31, F32, F33, F34, F35, F36 Surge suppressors Utility inputs
Terminals to Load, and connection to Rectifier utility in case of
X1
separate inputs for Rectifier and Bypass.
X2 Terminals for utility input
Step down transformer of Bypass utility voltage for AC power
T2
supply.
Step down transformer of UPS output voltage for the supply of
T3
ventilators and 24 Volt external supply. ( 277V - 230V)
4 Ventilators for Inverter and Rectifier bridge cooling.
Ventilators 3 Ventilators, accessible from the top of the UPS for cooling of
the magnetic components.
Initial page
Front view 100-150kVA
UPS's of 100, 120 and 150 kVA have the same cabinet size and the same internal Layout.
Cabinet size: 1200 x 800 x 1800 mm (width, depth, height)
Different is only the number of filter Capacitors and the rating of magnetic components.
The ratings of SCR's for Rectifier and SSM and IGBT's of the Inverter bridge are identical for 100, 120
and 150kVA.
Component Reference
F16, F17, F18 Bypass reference L1, L2, L3
F19, F20, F21 Inverter reference L1, L2, L3
F22 U - Inverter L1 for K50,. 5th filter
F23, F24, F25 Load reference L1, L2, L3
F11, F12 Transformer TR2 for AC Power supply
F13, F14, F15 Rectifier reference L1, L2, L3
F26, F27 DC - Voltage reference - / +
F28, F29 DC - Voltage for Power supply
F31, F32, F33, F34, F35, F36 Surge suppressors Utility inputs
Initial page
Input Channels (Customer Interface)
Two input channels, for the programming of various functions are available on the customer interface.
The function is activated by closing a contact.
The programming of this functions is done from the second level Parameters. (Set Input relays) or in
Parameters 30 and 31.
A filter for these Input signals (0 - 10 seconds) can be set in page 6, Input filter, or in Parameter 318.
0 = No function
1 = Inverter ON
2 = Inverter OFF
4 = Status relay (allows to read the status of the input relay on one of the 6 output relays, when
these are programmed for "relay input 1 or 2". See Output channels.
5 = Generator ON
6 = Auxiliary closing contact of external Maintenance Bypass. (Same effect as the auxiliary contact of
the internal Q2. Also listed in the events as Q2 open - closed)
7 = External Battery fuses, or external K3. (from software version 2.0) See Alarm 4104, "Battery
fuses".
Voltages applied to contacts:
Rectifier ON
4161
Command Rectifier ON, internal or external (Daisy)
Rectifier OFF
Command to shut down the Rectifier due to:
Generator ON
4163 The function programmed to the input relay on the customer interface IM 0005 indicates a Generator
supplies the UPS, therefore the setting of Parameters 148, 149 and 150 are considered.
Generator OFF
4164 The function programmed to the input relay on the customer interface IM 0005 indicates no Generator
supplies the UPS, therefore Parameters 148, 149 and 150 are not considered.
The Inverter cannot start with the" Inverter On" key pressed on the panel due to one or more of the
following conditions:
The following conditions are only valid for the units 400 - 500kVA
Shutdown of the Inverter is not possible because of unavailable Mains and thus impossible to transfer
load.
Inverter ON
4361 Command to start the Inverter, either from the key on the panel, a remote source (Argus, Daisy or
remote monitoring system) or automatic Inverter start, Parameter 126 .
Inverter OFF
The command "Inverter shutdown" was issued, due to:
Mains Bypass ok
4411 All 3 phases of the Mains Bypass voltage are within the tolerances specified in Parameters 118 and
119, frequency in Parameter 124 (tracking range) and correct phase rotation.
Command Load OFF
The control logic ordered the opening of K7 and to turn off the SSM due to:
EBP Locked
4535 The setting of Parameters inhibits the transfer to Mains, and K6 opens.
Parameters 148, 149, 151
EBP Free
4536 The setting of Parameters enables again the transfer to Mains.
Parameters 148, 149, 151
DETOUR ON
The UPS has detected the closure of it's circuit breaker Q2, by reading the auxiliary contact (Normally
4562 open)
In case the load is supplied from Inverter, the output transfers immediately to Utility Bypass, blocking
any possibility of retransfer.
DETOUR OFF
4564 The UPS has detected the opening of it's circuit breaker Q2, by reading the auxiliary contact
(Normally open)
No more Overload
4572
End of an overload condition with load on Inverter >125% and stop operation (4570).
Command to synchronize
The UPS (Master) has enabled the synchronization with Mains:
4583
Mains Bypass ok (4411)
Setting of Parameters 148 149
Q1 open
4602 The control logic has detected the opening of Q1.
Contact normally open.
Q1 closed
4603 The control logic has detected the closure of Q1.
Contact normally open.
Remote control ON
4763 The commands "Inverter ON/OFF", "Rectifier ON/OFF" and "Reset load OFF" can be given from a
remote control. (Argus, Remote monitoring system etc.) Setting in Parameter 15.
On the Customer interface are 6 programmable output channels available. No more hard wired adaptions
as on the previous series but all 6 channels are free programmable with up to 26 different signals, shown
in the table below.
Programming is possible in second level Parameters or in third level Parameters, in this case using the
code numbers 1 - 26 in the table below.
Phase check
Q1 of UPS 1 closed Q1 of UPS 2 open Q1 of UPS 3-8 open
Stop operation means that the Inverter will shut down after a time which depends on the existing
conditions.
A condition of "Stop Operation" is indicated on the corresponding LED on the panel, and depending on the
type of stop operation, an alarm is signalized.
"Stop Operation" can occur under 3 different conditions:
UPS Overload
In Parameter 102 you can define the time of Stop operation for battery discharge, in Minutes. Possible
values: Minimum = 1 Minute, Maximum = autonomy or backup time set in Parameter 103.
The LED goes OFF at the end of stop operation i.e. shutdown of the Inverter together with the Alarm
4999, load off due to low Battery voltage.
In case of Mains return before the end of stop operation, the LED remains lit until the Battery is
recharged, to guarantee again a backup time corresponding to stop operation time, calculated with the
actual load.
As soon as, after Mains return, the Battery is recharged for a backup time corresponding to stop
operation time, with the actual load, the Inverter restarts automatically.
An eventual over temperature is measured and detected on the Inverter heatsink(s) for units up to
120kVA. UPS's from 150 to 500kVA have an additional detection inside the transformer(s).
Over temperature detection causes the Alarm 4955, and stop operation in case Mains Bypass voltage is
not available.
If the situation is not changing, the Inverter will shut down after 3 Minutes (fixed time) and the load
transferred to Mains, and the LED turned OFF. Alarm 4999, load off due to low Battery voltage or over
temperature.
With Mains available the load is transferred to Mains and the Inverter shutdown immediately.
The Inverter restarts automatically.
Overload
Any load superior 100% of the nominal output power, also if measured only on one of the three phases,
must be considered as overload.
> 115% With Utility available, transfer to Mains and Alarm 4571: Overload: Load on Mains. With Utility
not available Alarm 4570: Overload.
> 125% Alarm 4570: Overload + Stop operation, with timeout depending on load percentage. (125% =10
Minutes, 150% = 30 Seconds) At the end of Stop operation the Inverter is shut down and load
transferred to Mains.
< 100%: Should during the timeout of Stop operation the load decrease below 100%, then Stop operation
terminates and the message 4572: No more overload, will be issued together with the Alarm 4998, load
off due to overload.
Auto start: The Inverter starts again automatically after 3 Minutes recovery time, after the end of Stop
operation and Inverter shutdown.
All contactors, K4, K6, K7, K8 and apart from the 400 / 500kVA UPS's also K3 open. (400
/500kVA have fuses F8, F9), thus disconnecting completely the UPS from input and output.
See Blockdiagram.
Rectifier, Inverter and Static Switch are shutdown
In a parallel system it's sufficient to press "Total OFF" on one unit, to disconnect and shutdown
them all. All, that have of course Q1 closed !!!
(Exception: If Bit 2 0f Parameter 411 is set to 1, on all Modules, only the Module where the
Total OFF button was pressed is shutdown)
To return to normal function, a reset is necessary.
Reset is accomplished by pressing first the total OFF button and then simultaneously the
Inverter ON key.
After reset, K4 closes, the Rectifier starts and the Bypass connects to the output. (K6, SSM and
K8)
In a parallel system it's sufficient to press total OFF and Inverter ON on one unit, to return the
system to load supply from Utility and start their Rectifiers.
Attention: After a "Total OFF" condition verify very carefully for what reason this did happen
and do not reset unless there is absolute no danger, in particular to persons, or eventual
damage to equipment.
With Parameters 77, 78, 79 it's possible to activate or deactivate any of the below listed alarms, and store
it in the events memory as a simple message.
Each of the three Parameters consists of 16 bits, and each bit represents an alarm.
If a Bit is set to 0 (zero), means alarm not active, while set to 1 (one) means alarm active (standard).
Example:
We want to disable the alarms 4581, 4110, 4410 while all the others must remain enabled, which gives the
following result: (LSB, Low bit on the right)
For Parameter 77: High bit 1111001111100001 Low bit, Binary .Decimal = 62433
For Parameter 78: High bit 0111111111000111Low bit, Binary Decimal = 32711
For Parameter 79: High bit1111100000000011 Low bit, Binary Decimal = 63491
Therefore to obtain the value to be set in the Parameter we must first write the value for each alarm as a binary
number (0 or 1), according to whether we want to disable or enable the alarm (disable = 0, enable = 1), and then
convert it to the corresponding Decimal value, which will be then the value To be written as Parameter.
Following are the default values for the 3 Parameters: 77 = 65534 / 78 = 65479 / 79 = 65535
Below the 3 tables for each Parameter, and the corresponding alarm assigned to each bit:
Parameter 77
Bit Alarm
09 Overload (4570)
14 DC Low (4700)
Parameter 78
Bit Alarm
Parameter 79
Bit Alarm
Warning: these are samples, values and descriptions could change for different FW versions. You must always refer
to the official parameters tables you can find at the following link "http://libraries.ge.com/foldersIndex.do?
entity_id=8216003101&sid=101&SF=1"
Error Codes 9Dxx
Listing of 9Dxx Error codes of the Control board IM 0007:
Access to this codes:
On the old LCD Display: Press buttons "ok" and "alarms" simultaneously.
On the new Graphic Display: Press key "ALARM" move to SERVICE and press Enter.
Should any of the below codes be found, the control board IM 0007 must be replaced. (Exception
9D04)
Code Description
9D00 FPGA did not initialise, Change control board.
9D01 DSP did not initialise, Change control board.
Auto calibration of fast AD-Converters failed (ADC) See
9D02
Parameter 292
Auto calibration of slow AD-Converters failed (ADC) See
9D03
details below !!
This is not an error code, but must be present after startup
9D04
of the IM 0007.
9D10 Auto calibration failure for Bypass voltage L1
9D11 Auto calibration failure for Inverter voltage L1
9D12 Auto calibration failure for Inverter voltage L2
9D13 Auto calibration failure for Inverter voltage L3
Auto calibration failure for Rectifier bridge input voltage
9D14
UC12
Auto calibration failure for Rectifier bridge input voltage
9D15
UC23
9D16 Auto calibration failure for Rectifier series current IS GR 1
9D17 Auto calibration failure for Rectifier series current IS GR 2
9D18 Auto calibration failure for Rectifier series current IS GR 2
9D19 Auto calibration failure for Inverter output current L1
9D1A Auto calibration failure for Inverter output current L2
9D1B Auto calibration failure for Inverter output current L3
9D1C Auto calibration failure for Inverter series current IS INV 1
9D1D Auto calibration failure for Inverter series current IS INV 2
9D20 Auto calibration failure for Bypass voltage L2
9D21 Auto calibration failure for Bypass voltage L3
9D22 Auto calibration failure for Load current L1
9D23 Auto calibration failure for Load current L2
9D24 Auto calibration failure for Load current L3
9D25 Auto calibration failure for Load voltage L1
9D26 Auto calibration failure for Load voltage L2
9D27 Auto calibration failure for Load voltage L3
9D28 Auto calibration failure for Rectifier Mains voltage L1/L2
9D29 Auto calibration failure for Rectifier Mains voltage L2/L3
9D2A Auto calibration failure for Rectifier Mains voltage L3/L1
Fan detection failure from IM 0192: 1 or more from SSM fan
9D30
module
Fan detection failure from IM 0192: 1 or more from
9D31
Magnetic module
Fan detection failure from IM 0192: 1 or more from Inverter
9D32
module
Fan detection failure from IM 0192: 1 or more from Rectifier
9D33
module
Fan detection failure from IM 0192: 1 or more from SSM +
9D34
another module
9D38 Mains Rectifier input Error detector for fast transients
9D39 Mains Rectifier input, RMS value, out of tolerance
After each module of the parallel system has been tested separately, they can now be paralleled
following the procedure below:
We presume that all modules are completely shutdown, i.e. utility power and Batteries disconnected,
however the communication bus cables are connected and the outputs of all modules are connected
to a distribution cabinet.
Connect utility power to all modules. Power supply starts and display is activated.
Close Q1 on the first unit. K6 closes and the Rectifier starts. Wait for end of Rectifier soft start and
closure of K3.
When closing Q1 on the last unit, the SSM's are activated on all modules and K8 closes. The load is
now supplied from Bypass.
Start then the Inverters of all the other units, pressing again twice Inverter ON (Service mode !!) for
transfer of Inverter to output. (closure of K7)
Switch all Inverters OFF. When Inverter of unit 1 is switched OFF, the output will retransfer to
Mains.
Do never start an Inverter before the previously started has terminated it's Soft start and, with
redundancy, closed it's K7.
Verify with all units running the measurements, if possible also the load sharing and load
distribution, if load is available.
Initial page
Layout IM 0048
In a parallel system the communication cables connect to this board. Below the board layout
and connections.
External UPS's in a parallel system must have Jumpers JP1 -JP4 inserted for line termination.
These are the units with only 2 cables connected to IM 0048. (JA1 and JB1)
With date of February 2007 version C of this board was introduced. The change consists of the
control of the 24 Volt DC supply voltage. (Yellow LED) An additional plug J12 brings the
information to the control board IM 0007 / J27. In case of a failure of this voltage Alarm 4701,
24 Volt failure will be issued.
Layout A and B
TP1 + UDC J1 +12VDR Driver Inverter P8
TP14 + 5V BR.1 ON
Battery discharge current displayed in the measurements, is indicated as negative current, while charging
current is displayed positive.
In case of separate Mains input for Rectifier and Bypass, the Battery will be discharged, including to end
of stop operation, with Rectifier Mains voltage not available, before transfer of the load to Bypass.
Manual battery test must be done from the UPS panel and is not possible with DAISY!
The following Parameters determine the function of the manual Battery test:
Set in U. Test the test voltage, i.e. the voltage below which the Alarm Battery fault (4118) is given,
and the Rectifier
would immediately return to floating voltage.
Put start to Y (Yes) to start the test, or interrupt at anytime by setting it N (No).
Test voltage could also be set in third level Parameters, Parameter 22 and test time in Parameter 23,
while the start of the test must be done from second level Parameters, shown on the screen above.
Rectifier is running
With the start of the test, the voltage of the Rectifier is gradually decreased.
Should the battery voltage during test reach the test voltage + 2 Volts, or the voltage defined in
Parameter 91, the test will terminate, alarm 4118 "Battery fault" given, and the Rectifier returns
immediately to floating voltage.
The test can be terminated manually at any time. (Y to N)
2. Automatic Battery test
Rectifier is running.
In a parallel system the test can be programmed individually for each unit.
In case of paralleled Rectifiers on one (common) Battery, the test can be programmed on either unit.
At beginning of the test, the voltage of the Rectifier is reduced in order to allow the discharging of the
Battery.
Duration of the automatic Battery test previously was 1/5 (20%) of the time specified in Parameter 103,
Backup (Autonomy) time.
Now the duration of test is calculated 1/5 (20%) of the actual available and calculated autonomy time.
Therefore the test will terminate when the remaining autonomy on the display shows 80%.
From Software version 2.0 onwards only. Previously 1/5 of backup time.
Should the battery voltage during test reach the test voltage defined in Parameter 19 (Automatic test
voltage) + 2 Volts, or descend below the voltage defined in Parameter 91, (Battery under voltage), then
the test will terminate, alarm 4118, Battery fault given, and the Rectifier returns immediately to floating
voltage.
Automatic Battery test can be programmed either in second level Parameters or third level Parameters.
Test voltage must be set in third level Parameters (see below) Parameter 19.
Following are the Parameters for the programming of the test in third level:
d1 or 65535 = Saturday
d2 or 65534 = Sunday
d3 or 65533 = Monday
d4 or 65532 = Tuesday
d5 or 65531 = Wednesday
d6 or 65530 = Thursday
d7 or 65529 = Friday
13 = Every 4 weeks
26 = Every 2 weeks
52 = Every week
1 = Every 12 months
2 = Every 6 months
3 = Every 4 months
4 = Every 3 months
6 = Every 2 months
12 =Every month
lnitial page | Battery adjustment
Over Temperature
Depending on the UPS output power a various number of temperature sensors on the Rectifier
and Inverter bridges control the temperature.
A NTC resistor in series with Klixon (80°C) is used for the temperature measurement.
Ventilator failure.
In case of an over temperature condition, apart from the alarm 4955 (Over temperature UPS), the load is
transferred to Mains and the Inverter shutdown.
In case Mains voltage is not available, stop operation is issued and at the end of the timeout of 3 Minutes
the Inverter is shutdown, resulting in the alarm 4999, Load Off, due to over temperature.
Should the temperature during stop operation, or at any other time, result to be superior 90°C, then the
Inverter is shut down immediately and alarm 4999, "Load Off, due to over temperature" is issued.
With 25°C the NTC-Resistor has a value of 470 Ohm. With open circuit, i.e. no connection to the NTC-
Resistor the display will show 95°C.
As soon as the temperature decreases ca 20°C below the level set in Parameter 138, the Inverter will
automatically start again, followed by load transfer to Inverter.
Initial page
Error Detector
Error detector we call a circuit which can detect fast changes of an AC voltage.
Two identical circuits, one for the load, i.e. UPS output voltage, the other for the Utility Bypass voltage
are implemented on this units.
1. Error detector UPS voltage (Load voltage measured at the input of Q1)
An error detector signal causes, with available Utility, a transfer to Utility together with the Alarm
4531 Load on Utility by error detector. Automatic retransfer occurs in case the Inverter voltage stays
within tolerance.
With Utility voltage not available, the error detector signal has no influence on the UPS function. No
Alarm.
Parameters:
Parameter Value to adjust Test point
128 Threshold 100 (V)
J39: pin 2, Gnd pin1,
129 Phase Error det. < 150mV
on IM 0007
134 Enable Error det. 0= disable / 1= enable
Various adjustments.
For this adjustment and the one below: Start the Inverter in service mode (Q1 open). Press Inverter ON a
second time to connect the Bypass to the output. Adjust now.
An error detector signal disables the synchronization Inverter - Utility and Causes the opening of K6.
With Mains considered again to be ok, the Inverter synchronizes and K6 will close.
Parameters:
Parameter Value to adjust Test point
130 Threshold 100 (V)
J39: pin 3, Gnd pin1
131 Phase Error det. < 150mV
on IM 0007
135 Enable error det. 0= disable / 1= enable
Various adjustments.
Initial page
Load on Inverter
Closure of Q2 (4562)
The Inverter is no more supplying the load. (Fuses 4301, K7 closing failure 4304).
The UPS proceeds to status "LOAD OFF" e.g. K6, K7 and K8 open, SSM switched off with following
conditions:
The key "LOAD OFF" on the panel was pressed (4561).
The Inverter is no more supplying the load (4301 fuses) and transfer to Utility is not possible.
The load will remain being supplied from Utility with following conditions:
Q2 closed (4562)
The load will commutate to Inverter, close K7 and deactivate the SSM and open K8 with following
conditions:
Inverter ok and synchronized & load less then 100% & Q2 open & load not locked on Mains &
Command to synchronies. (4530)
The UPS proceeds to status "LOAD OFF", K6 open, K8 open, SSM deactivated and K7 open with following
conditions:
The load is no more supplied from Mains due to one of the following
Load OFF, ordered from the CPU due to the end of Stop operation, with Alarms 4998: Load off due to
overload, or 4999: Load off due to low Battery or Over temperature.
End of stop operation caused an internal Load OFF and the actual operating conditions of the UPS
inhibit load supply. (Discharged Battery , Overload timeout still running or condition of Over
temperature )
Conditions do not allow to commutate the load to Inverter. See LOAD ON INVERTER
Inverter switched ON and ok, means LED on panel for Inverter lit. (4361)
Q2 open (4564)
Parallel settings
The system does consider itself to be a parallel system with the parallel board IM 0006 inserted on the
control board IM 0007.
This number is also shown on the main page of the display. (P1.....P8)
Furthermore in Parameter 159 is indicated whether it's a single or parallel unit.
2 = Single, 9 = Parallel ( Read only)
A single UPS has always the setting as number 1, i.e. all jumpers ON.
Attention:
When using the RS 232 port J11 with the old protocol, the RS 232 port of only one module can
communicate, identical to the Sitepros of the previous series. The channels of all other modules must be
disabled by inserting Jumper JP4 on the parallel board IM 0006. See Layout for position.
The version of Software, i.e. Flash Eproms U2, U3 and U36 must be of the same version on all paralleled
UPS's.
See also the chapter "Software history", for changes, updates, modifications and improvements of
Software.
On the Customer Interface IM 0005 DIP - Switches according to the Interface number and the UPS
number must be set.
In a parallel system it's advisable to delay the Start of the Rectifiers after a Mains failure. We advice to
define in Parameter 222 the delay time in steps of 5 seconds:
Rectifier 1: 5 seconds
Rectifier 2: 10 seconds
Rectifier 3: 15 seconds
Rectifier 4: 20 seconds
Possible values for Parameter 222 are from 1 second to 300 seconds.
Once the settings and cable connections have been done on each UPS proceed to start up the parallel
system as described in "Parallel operation".
Initial page
IM0086 Parallel Board
Attention:
IC2 is always inserted. Version 13.0 is compatible with version 10.0 of U36, the Flash Eprom for
the DSP.
Version 13.0 is necessary for the functionality of PMAD and goes together with the versions
3.21 for U2 and U3, while U36 must be of version 7.4.
In case the signals of channels JA and JB are not identical, the yellow LED will be lit.
See Communication Bus Detection in PMAD for details.
Shutdown of one of the modules in a parallel system is required in case of maintenance, modification or
repair.
In case of system redundancy i.e. the remaining modules have sufficient output power to supply the
load, we can separate one Module of the Parallel system.
Without system redundancy, the load will automatically transfer to Utility, when one of the Inverters is
shutdown.
In this case the load should be connected to the maintenance Bypass, i.e. the Q2's of all modules. This
allows to make the rest of the UPS voltage free, and work on them without influence to the output
(Load).
Attention: The communication bus cables of all UPSs with the control board IM0007 must be connected or
disconnected with the UPS Module completely shutdown, including power supply.
Press the key Inverter off on the UPS you want to separate.
Open Q1 on the same UPS. The system, although still communicating with this UPS, is considering it
now as not available for load supply, because of the open Q1.
Press the Total Off button on the same UPS to separate it completely.
K4, K6 and K8 open and the Rectifier shutdown.
Disconnect then the Battery. Discharge the DC - Link capacitors (possibly with the Inverter) then
disconnect Utility voltage, thus disconnecting input and output of this module completely.
Make sure the logic power is OFF, the display is blank, and no LEDs are present on the control board
IM0007.
To prevent from disturbances on the communication bus, remove both communication cables JA and
JB on the communication bus interface IM0048, connecting to the parallel board IM0006 or IM0086.
Make sure the logic power is OFF, the display is blank, and no LEDs are present on the control board
IM0007.
Connect Utility power to the UPS. Power supply is running and the display active.
If you want to test the module in service mode, follow the description in the chapter "Operation with
Q1 open"
If not, close Q1. This will cause the closure of K4, start of the Rectifier and the closure of K6.
Press the Inverter ON key, to start the Inverter. As soon as the Inverter output voltage is considered
to be ok, synchronized and in phase, K7 will close and connect the Inverter to the parallel system.
In case of maintenance or repair with no redundancy but continuous load supply is required, then the
load must be switched to maintenance circuit breaker Q2 :
Shutdown
Press Inverter off on one module after the other, until all Inverters are off. Remember to press
Inverter OFF twice, to make sure it stays off.
Press the Total OFF button on each module, to shutdown the Rectifier and open K4, K6, K8.
If Utility must remain connected to the Modules, disconnect X3 on the Power interface IM 0049
(Bypass voltage for AC Power supply), to shut down the electronics.
Restart
Reconnect X3 on the Power Interface if previously disconnected. Power supply runs and the display
active.
If you want to test each module in Service mode, proceed as described in "Operation with Q1 open",
otherwise go to the next step below.
Close Q1 on each module. This causes the closure of K4 and K6 and start of the Rectifier.
At the closure of Q1 of the last module the Bypass of all units is activated, by closing their K8 and
SSM.
Open now Q2 on all modules. Verify for correct measurements, load current, output voltages and
load sharing.
Start the Inverter of the first module. With redundancy K7 will close and connect the Inverter to the
Load. Without redundancy a sufficient number of Inverters must start, to transfer the Load to
Inverter.
Proceed to start the remaining Inverters always waiting for the termination of it's start cycle, before
starting the next.
Verify with load on Inverter for correct measurements and load sharing.
Modifications
Software version for U2 and U3 must be 1.5 or higher.
On the main control board IM 0007D, 2 Resistors must be changed:
R 139 must be 3k, R 247 must be 11k, see Layout for position.
Modification number 107 refers to this change.
Boards with Modification 107 or higher have this values already changed !!!
Parameters
Two new Parameters were introduced:
Parameter 162 for the Battery current offset calibration (indicative value 410)
Parameter 160 for the Battery current calibration depending on output power. See below for values:
Startup
Start the Rectifier first as standard single Rectifier. Only in a next step, the configuration will be
modified.
ATTENTION: It's most important that each Rectifier has it's own Battery fuse, and the actual paralleling
is done on the Battery.
After closure of K3 or manual closure of Q3a at the end of Rectifier soft start, close immediately the
Battery fuses on all UPS's, thus activating the share regulation circuit of the 2 Rectifiers, which
works based on the status of the auxiliary contact.
Attention: Due to the fact that K3 separates only the negative pole of the Battery, never close the
Battery fuses before starting the Rectifier.
Battery test
Parameters for the Battery test must be identical on both UPS's in particular the Parameters 19
(Automatic test) and 22 (Manual test) which define the test voltage.
Below the table, showing the position of the Dip-switches, which have to be set according to the number
of the UPS and the Interface number. Remember up to 3 IM 0005 boards can be paralleled to increase
the available number of Input / Output channels.
Maximum 2 boards can be housed in the connectivity box, while the third, requires an external rack.
Dip Switch Number Number
UPS of
Number 1 2 3 4 5 6 7 8 Customer
Interface
ON ON ON OFF ON ON ON ON 1
1 ON ON OFF OFF ON ON ON ON 2
OFF OFF ON OFF ON ON ON ON 3
ON ON ON OFF ON ON OFF ON 1
2 ON ON OFF OFF ON ON OFF ON 2
OFF OFF ON OFF ON ON OFF ON 3
ON ON ON OFF ON OFF ON ON 1
3 ON ON OFF OFF ON OFF ON ON 2
OFF OFF ON OFF ON OFF ON ON 3
ON ON ON OFF ON OFF OFF ON 1
4 ON ON OFF OFF ON OFF OFF ON 2
OFF OFF ON OFF ON OFF OFF ON 3
ON ON ON OFF OFF ON ON ON 1
5 ON ON OFF OFF OFF ON ON ON 2
OFF OFF ON OFF OFF ON ON ON 3
ON ON ON OFF OFF ON OFF ON 1
6 ON ON OFF OFF OFF ON OFF ON 2
OFF OFF ON OFF OFF ON OFF ON 3
ON ON ON OFF OFF OFF ON ON 1
7 ON ON OFF OFF OFF OFF ON ON 2
OFF OFF ON OFF OFF OFF ON ON 3
ON ON ON OFF OFF OFF OFF ON 1
8 ON ON OFF OFF OFF OFF OFF ON 2
OFF OFF ON OFF OFF OFF OFF ON 3
Disconnect the supply connection wires from the terminals. (Yellow rectangle)
Remove the 4 nuts M4, which are fixing the Ventilator, marked yellow.
PMAD makes use of already existing measurements and detections, therefore no hardware modifications
are necessary. See the page Installation for necessary procedures.
The new features of PMAD can communicate, together with the already existing, through the following
structures:
PMAD helps to improve system reliability by alerting the user or service about critical conditions like
communication line problems, load share problems, the need of component replacements, or the
calculation of the actual Inverter loading, in order to avoid overload conditions.
Attention: In parallel systems the version of EEPROM IC2 on the parallel board IM 0086 must be 13,
together with the version 3.30 for U2 and U3 and 10.0 for U36 (or higher).
PMAD (Preventive Maintenance and Advanced Diagnostics) is based entirely on Software, and works with
all UPSs which are using the IM 0007 as control board. In fact only the 3 Flasheproms (U2, U3, and U36)
have to be replaced.
Shut down the UPS completely, including Power supply. If necessary supply the load through
Maintenance Bypass Q2.
Replace the Flash Eproms U2, U3 (v. 3.21) and U36 (v. 7.4) on the control board IM 0007 with the
PMAD version.
Restart only Electronic supply.
Verify, or and insert Parameter values according the listings in the page Parameters or Power
depending Parameters.
Restart now the UPS in normal mode (Q1 closed) and connect some load, ideally ca. 50%.
Verify for correct measurement of cos phi in Parameters 341, 342 and 343, either with a load with
known cos phi or by measuring with an adequate instrument. If necessary calibrate. See page
Cos Phi Measurement for calibration details.
In a parallel system verify the correct indication of Parameters 262, 263 of the communication bus
control. See page Communication Bus Detection.
Verify with and without load the current share values in a parallel system. See page Current Share.
In case of remote connections like IRIS, SNMP card or Modbus verify the functionality.
Information can be found in the appropriate Manuals.
PMAD Parameters
257 Read only RMS value of share current in a parallel system, phase L1 Value x 10
259 Read only RMS value of share current in a parallel system, phase L2 Value x 10
260 Read only Peak value of the load current of phase L3
261 Read only RMS value of share current in a parallel system, phase L3 Value x 10
Indication of the cos phi from the load current, seen from
341 Read only Value x 100
the UPS, phase L1. See page "Cos Phi Measurement".
Indication of the cos phi from the load current, seen from
342 Read only Value x 100
the UPS, phase L2. See page "cos phi measurement".
Indication of the cos phi from the load current, seen from
343 Read only Value x 100
the UPS, phase L3. See page "cos phi measurement".
All Alarms are auto reset, i.e. with the return to normal operation the Alarm will disappear.
This feature applies only to Paralleled UPSs and their Communication Bus !!
The Sitepro and SG series have redundant communication channels, named channel JA and channel JB.
Parameter 262 represents channel JA while Parameter 263 shows the value for channel JB.
These Parameters show the the number of UPSs detected on the communication bus, including itself.
The binary value consists of 8 bits, each bit corresponding to the number the UPS, which was assigned in
the parallel system on the control board IM 0007 with Jumpers J14, 15, 16.
Example:
Situation: 4 UPS in parallel, with numbers 1, 2, 3 and 4 assigned. (Jumpers J14, 15, 16 on IM 0007)
Case 1: Parameters 262 and 263 show a value of 00015. This corresponds in Binary to 00001111,
therefore this UPS can see 4 units in communication, on both channels.
Case 2: Parameter 262 shows a value of 00011. However 4 units are existing, and thus the correct value
should be 00015. In Binary 00011 corresponds to 00001011, indicating that unit number 3 is missing,
respectively not communicating on bus JA.
Another example:
The value of Parameters 262 = 3, corresponding to binary 00000011 and therefore for 2 units.
Value of Parameter 263 however, shows only 2, i.e. channel B shows only the presence of 1 unit
with the number 2.
Parameters 262 and 263 are not identical.
The lower value in Parameter 263 indicates a failure on Bus B of the UPS unit with number 1.
Bus A or Bus B failure, which is indicated with Alarms either 4008 or 4009, and at the same time we
can see in Parameters 262 and 263 which channel of which UPS is missing. See the examples above.
In Parameter 249 the sensitivity of this detection can be installed.
In case of disturbed communication however, another type of Alarm results. Alarm 4006 or 4007
indicate a CRC (Cyclic Redundance Check) failure. The Sensitivity can be adjusted with
Parameter251.
In addition to the Alarm, in case of an interrupted communication bus, a yellow LED is lit on the parallel
board IM 0086.
In case of a CRC (Cyclic Redundancy Check) failure however, the red LED on the parallel board of the
corresponding channel will be lit.
Initial page ¦ PMAD
Connectivity Bus Detection
The Sitepro and SG series have redundant communication channels, named channel A and channel B.
Apart from the UPS communication within the paralleled units, these cables have separate channels for
connectivity.
The signals of these connectivity buses are continuously controlled for their readability. In case a
malfunction is detected Alarm 4010 CONNECTIVITY BUS FAILURE, will be issued.
Attention: Only on the bus cable at which the communication is active (Cable A or B), a failure can be
detected !!
When the Bus communication changes from one channel to the other, automatically also the Connectivity
Bus will change on this same channel.
While Parameter 68 is not associated with a particular function, the 4 new Parameter are dedicated to
particular component(s), as follows: (Time in hours !!)
Parameter 264 Batt. depending Time of Service Check for the Batteries
Parameter 266 50000 Time of Service Check for the AC output Capacitors
Attention: The values in the table above are only examples, and can differ, depending on experience and
technical data from the supplier.
The Parameter will start to decrement when the corresponding value is set.
When the value of either of this Parameters becomes Zero, the LED Service Check starts flashing.
(Unless Q1 is open and thus overwriting the flashing)
The timer which caused the flashing of the LED must be verified in the Parameters, i.e. no message is
given on the display.
However with IRIS or the SNMP card, the single timeouts can be seen.
To cancel the flashing, no Reset operation is necessary. Simply introduce the desired number of hours
( Values from 0 - 65534 are possible, while with 65535 the function is disabled), and the countdown will
start automatically. N.B. this is valid also for the old Service check in Parameter 68. No reset required!
Particular time display on IRIS: The indication of time in hours will not stop when reaching zero, but will
continue counting. The indicated value however is not anymore hours but shows in RED color days and
weeks which have passed since reaching zero. This allows to confront the customer with an overdue
replacement of components, especially in case of failures.
PMAD alerts you in case the exchange current on one or more phases in a particular unit exceeds the
value set in Parameter 350, by issuing the Alarm 4321.
In Parameters 257, 259, 261 the RMS exchange current can be read.
Peak Current Detection
Highly nonlinear loads have often comparatively low RMS values , however high peak values.
This can lead to an over current condition on the Inverter bridge.
In Parameters 256, 258 and 260 we can read the peak values of the 3 phases of the load current,
enabling thus a valuation of the existing load(s), and if necessary take eventually corrective
measurements.
A regular inspection e.g. with IRIS could help to alert the customer before a critical situation for the load
could arise.
DC Ripple Detection
High DC ripple voltage indicates most probably a bad condition of the Electrolytic Capacitors in the DC-
Link, or eventually a Rectifier problem, like missing drive pulses.
The lifetime of the Electrolytic Capacitors is limited but can vary to great extend depending mainly on
temperature and superimposed AC Voltage.
Under normal operating conditions the end of the time set in Parameter 265 will indicate a due
substitution of these components, according the indication of the supplier.
In case of bad operational conditions, as indicated above, the measurement of increased ripple voltage
alerts you by issuing the Alarm 4121, HIGH DC RIPPLE.
The threshold of this Alarm is power depending and can be set in Parameter 349, while in Parameter 335
a significant indication of the RMS Battery ripple voltage can be read and verified.
The actual existing cos-phi for the 3 phases can be seen in Parameters 341, 342, 343.
In the page "Load on Phases" (Attention: Displayed in the selected language) the kVA and the power
factor of each phase are displayed.
A sign is applied to the power factor to discriminate between capacitive load (negative) and inductive
load (positive).
Calibration
Calibration Parameter 336 is valid for all 3 phases, which requires to find a compromise value for all 3
phases, since the cos phi might slightly differ from phase to phase.
In either case you should try to calibrate with Parameter 336 the values in Parameters 341, 342, 343 as
close as possible to the read or known value.
To achieve an acceptable accuracy a minimum amount of load is required, ideally around 50%.
The table below shows typical values of a cos phi measurements. Bit 5 indicates whether the load is
inductive (lagging power factor) with a 0, while a capacitive load (leading power factor) is shown with a
1.
Bit 1 and 2 show the measured cos phi.
Simple Blockdiagram
Initial page
Blockdiagram Electronics
A new, more powerful board, IM 0076, is used on the 400 and 500kVA units
instead of the IM 0061
IM 0007 replacement
Below a step by step description for the procedure when changing this board:
Shutdown the UPS, if necessary with load supplied from Maintenance Bypass Q2.
If not possible, you will have to check all Parameters with the PIOR from the Display and partly
adjust them manually, after replacing the board.
Disconnect X3 on the Power Interface IM 0049 to shutdown the power supply, in case Mains voltage
cannot be disconnected due to load supply through Q2.
Verify the setting of Jumpers and values of Rx's R302 and R298 with the PIOR or replace them from
the old board. R298 for UDC Max = 1k2 for UDC floating 485V.
R302 defines the level of IS Max and is therefore power dependent. See also board layout.
Change the Flash Eproms from the old to the new board, or in case of update insert the new ones in
the new board. (U2, U3, U36)
Verify after start of the power supply, on the main page of the display
"Self test board ok".
On IM 0007 LED 27 should be ON (Master) LED 28 OFF and LED's 29, 30, 31 blinking, LED 27 must be
ON (Master) LED 28 OFF (not used).
Verify for correct function and indication of the display including a "Lamp test".
The last 3 Alarms should read: 4411 Bypass Mains ok, 4763 Remote control ON (not always), 4583
Command to synchronize.
Connect Daisy and store with the function "Download" the previously uploaded Parameters on the
new board.
Also with Daisy, program the ID - Number (PIOR) and set correct date and time.
Before starting the UPS in Service mode, perform a Low voltage startup.
If ok, start the Rectifier by pressing simultaneously the keys "mute" and "lamp" .
At the end of soft start K3 closes. Verify for correct output voltage and value on the display. If
necessary Calibrate or adjust.
Verify for 0 Battery current. If necessary calibrate offset with Parameter 86.
Verify for correct Utility measurements of Rectifier and Bypass. If incorrect, calibrate.
K7 activation delay: Verify for values of Parameters 308 and 309 set according to PIOR. This setting
has influence on the load share signal during parallel operation.
Inverter ON to initialize transfer from Utility to Inverter. Verify for correct voltage adaption (Inverter
voltage 2 Volt above Utility) before transfer and closure of K7.
Before starting the UPS in normal mode i.e. with Q1 closed, make sure to have the Load OFF button
pressed in service mode, after Inverter shutdown.
For startup of a UPS single or parallel refer to the corresponding pages:
Single operation or Parallel startup.
In case of a parallel system check the diagnostic LED's on the Parallel board IM 0006.
Verify with load: Load currents, Rectifier current and Battery discharge current.
Eventually measure with current clamps for symmetrical currents on all 3 phases of the Rectifier
input.
Initial page
Layout IM 0048
In a parallel system the communication cables connect to this board. Below the board layout
and connections.
External UPS's in a parallel system must have Jumpers JP1 -JP4 inserted for line termination.
These are the units with only 2 cables connected to IM 0048. (JA1 and JB1)
IM 0086
Attention:
IC2 is always inserted. Version 12.0 is compatible with version 7.0 and 7.1 of U36, the flash
Eprom for the DSP.
Version 13.0 is necessary for the functionality of PMAD and goes together with the versions
3.21 for U2 and U3, while U36 must be version 7.4.
Jumper settings
JP1 - JP6 ON Pullup resistors
JP15 - JP 20 ON Pullup resistors
JP7 ON Pin 2 / 3
JP10 OFF
JP 8, JP 9 ON Pin 2 / 3 with IC 2 OFF ON Pin 1 /2 with IC 2 ON
JP12, JP13, JP14 With IC2: OFF, ON, ON Without IC2: ON, OFF, OFF
JP11 OFF to enable old protocol on J11 (Sitepro)
BR. 1 - BR. 4 OFF
JP on Pin 9-10 on ISM and all
J4 No JP if only UPS
UPSs in configuration SCB