2964 - 313 - 2 BLR CX Embraer Fator de Potencia Ligação

The document is an operation manual for the BLR-CX capacitor switching relay. It provides instructions for installation, commissioning, operation and troubleshooting of the relay. The manual outlines safety procedures and technical specifications, describes the display interface and navigation controls, and provides guidance on setting parameters and operating the relay in both automatic and manual modes. Troubleshooting tips are also included to address common issues that may occur during commissioning.

Uploaded by

Saulo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
135 views16 pages

2964 - 313 - 2 BLR CX Embraer Fator de Potencia Ligação

The document is an operation manual for the BLR-CX capacitor switching relay. It provides instructions for installation, commissioning, operation and troubleshooting of the relay. The manual outlines safety procedures and technical specifications, describes the display interface and navigation controls, and provides guidance on setting parameters and operating the relay in both automatic and manual modes. Troubleshooting tips are also included to address common issues that may occur during commissioning.

Uploaded by

Saulo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Operation Manual

BLR-CX (MB_EN_ACX-R_BEL_10)

ATTENTION!
Installation of the BLR-CX must only be undertaken by technically qualified
persons, since live terminals can cause electric shock.
The appropriate safety regulations in the country of installation must be strictly
adhered to.
Equipment with damaged casing or terminals must not be used and must be
disconnected from the mains supply immediately.
Beluk GmbH Phone: 08861/23320
Taubenstrasse 1 Fax: 08861/233222
86956 Schongau [email protected]
Germany http://www.beluk.de
load
from incoming feeder
L1
X/1A oder X/5A
L2
L3

interface

S1 S2 Um1Um2 M A TTL K1-K14


15mA - 6A 90V - 550V

BLR-CX

T1 T2 MS 1 14 1-14
K1 K14
T

N
PE
external ‘All in Order’- Max 14 steps fan operation
temperature contact closes can be selected
or for one of the
temperature sensor switch step switching relays
(parallel operation
possible)
Installation and Commissioning:
1) Check that the mains voltage and CT current input are suitable for
the relay!
2) Disconnect panel from mains voltage,
and check that the voltage is off
3) Ensure CT short-circuited or not in operation.
An open circuit CT produces a high voltage which endangers
people and equipment. It will also damage the CT and affect ist
accuracy.
4) Disconnect and remove any previous pfc-relay.
5) Mount BLR-CX in the control panel with the two mounting clips.
(cutout 138x138mm)
6) Connect the earth protection cable to ‘PE’ on BLR-CX metal case.
7) Connect BLR-CX according to wiring diagram.
(CT/P1 towards incoming feeder, CT/P2 towards load!)
8) Remove short-circuit from CT
9) Connect mains voltage to panel.
10) If relay has been correctly connected and the mains voltage and CT
output comply with the ratings and settings of BLR-CX, the LCD will
show AUTO and the control function will start automatically!
FAQ during Commissioning:
1) No indication AUTO " the relay does not switch
Cause: Relay set to manual operation
In SETUP/100 menu the selection for PFC is on OFF or HOLD
temperature is too high,
current < 15mA, voltage or THD U is out of tolarance.
2) Indication U ALARM " voltage out of tolerance
Check settings for nominal voltage (SETUP/Un) and
voltage transformer (SETUP/Pt)
3) Indication I Lo ALARM " CT current < 15mA
Cause: connection error of CT; short-link of CT is not removed;
CT-ration is too high compared to real current; no current
4) Indication EXPORT " kW export
if there is no real kW export, voltage and current connection to
BLR-CX has to be checked! See Wrong Connections / AI
5) Wrong Cos j indication " wrong connection
voltage and current connection to BLR-CX has to be checked!
See Wrong Connection / AI
6) Steps switch in and then quickly switch out again
See Stepsize Detection / Defective Capacitors
7) Frequent switching of steps
size of capacitors has not been completly detected
Display:
INFO: step database information
AUTO: relay is working in AUTO mode
MANUAL: relay is working in manual mode
SETUP: Setup of parameters

EXPORT: kW export
NT: 2nd target-cosj is working
ALARM: blinking during alarm

1. line:
cosj
menu items

2. line:
measuring values
parameters
alarm codes

Step indication:
state of step (on/off)
step defective (blinking)
Handling:
BLR-CX has 4 keys for navigation and input of parameters.

increase values
select menu items

exit menu open menu


move cursor left esc move cursor right
reset alarm confirm input
(hold for 5 sec)

Decrease values
select menu items

Input parameter:
p, q setting of number
u selection of next digit
p, q after setting of last digit, selection of:
- multiplier k (kilo) or M (Mega)
- leading sign I (induktive) or C (capacitive) (blinking of I or C)
u storage of setting
t abort input
Main Menu:
Select menu items by pressing p, q, enter submenu by pressing u
Measuing Values: (selcted using p, q)
ULL, ULN, A (I), kW (P), kVar (Q), DkVar (DQ),
kVA (S), THD U, 3. -19. Har. U, cosj, L (PF),
fL (APF), tan j (tAn), Hz (F), °C(t), °Cmax (thi),
operation hours (OPh)
INFO Step Database:
size and derating of steps,
switch cycles, steptype
(see INFO Step Database)

MANUAL Operation:
Selective switching in and out of control exits
(see MANUAL Operation)

SETUP Parameters:
Nominal voltage (Un),CT-ratio Ct, VT-ratio (Pt),
Automatic Initialising (Ai), PFC ON/OFF/HOLD
(PFC), target-cosj (CP1), switch time delay
(St), steptype (Out)
(see SETUP Parameters)
INFO Step Database:
Attention: Actual state of control outputs is not shown!
Choose step by p, q and enter by u . The selected step is blinking. By
using p, q following information can be selected:
Actual Size of Capacitor
the value is rated to nominal voltage

Derating of Capacitor:
present kvar value / original kvar value in %

Switch Cycles of Contactor:

Step Setting:
AUTO: automatically switched step
Fon: step is permanently switched on
Foff: step is permanently switched off
AL: step used for fan control
FLty: defective step
MANUAL Operation:
For manual operation u has to be pressed for 3 seconds!
Selection of step by p, q. Number of selected step is shown in line 2 of
LCD. By pushing u selected step will switch on / off.
Manual operation escape by pressing t .

Important Information:
- Menu Manual Operation cannot be opend in modes LIFO and
Combi-Filter. (see Reference book!)
- Discharging lockout time is also active during manual operation
(steps are locked in to allow for discharge time after switching-off)
- If voltage is out of tolerance all steps are disconnected.
- THD U-alarm and over temperature alarms will prevent steps
switching in on manual mode.
- Only steps with step type AUTO can be switched!
- After leaving manual operation menu, relay sitches to the actual
load.
SETUP Parameters:
Choosing SETUP, sub menu 100 is indicated. Pressing u opens menu 100.
p, q menue 200-600 (protected by pin, see reference book)

Un Nominal voltage (very important!)


OV / UV monitoring, reference for step database.
Ct CT-ratio
indication of measuring values. (enables many measuring values)
Pt VT-ratio
important base for nominal voltage
AI Automatic Initialising
see wrong connection / AI
PFC PFC ON / OFF / HOLD
on, off, freezing of automatic pfc-correction
CP1 Target-cosj 1
base for compensation target
St Switch time delay of each step
definition of speed of regulation
OUt Step type
definition of step type: AUTO, Fon, Foff, AL
reset of defective steps (FLty)
Wrong Connection / AI - Automatic Initialising:
A pfc-relay demands correct connection of voltage and current (polarity and
phase) to function correctly. If this is not the case, the connection must be
corrected. As this is not always possible, BLR-CX is offering the following
possibilities:
Manual Correction: SETUP / 200 see Reference book
Automatic Initialising: SETUP/ 100 / Ai
Ai is connecting and disconnecting all control exits several times by
switching them on and off. This lasts several minutes! Exits which are not
connected are designated as Foff (permanently off). Stepsizes are not
detected by this function!
After Ai is complete, the BLR-CX has to be checked for correct
operation!
Requirements for successful operation of Ai:
- voltage is within tolerance
- CT is connected (no simulation!)
- capacitor banks are installed and fuses are inserted
Possible problems for function of Ai:
- load variations
- small current signals (big CT-ratio, small stepsizes)
Failure indication Ai / Abrt:
Ai is aborted, as no clear result could be achieved,PFC = OFF.
Step Size Detection:
At each switching operation, step size is measured (except this function
is not active SETUP / 300 see Reference book)
Setting of c/k value is not necessary. Switching sequence is carried out
automatically by selecting capacitor steps with the most suitable kvar
value to match the load requirement.
The recognised values are stored in a step data base. Loss of output of
each capacitor step can be seen there.
If a step fails to function during the first 3 switching operations after a
reset of the step data base, steptype Foff is set automatically.
Defective Steps:
When a step is switched 3 times in series without measured size, it is
detected as defective and it is blocked for 24h.
Step state: flashing
Status: Flty, step is blocked
Failure analysis:
After commissioning, all steps have step type Foff:
Is short link of CT secondary removed?
Is position of CT correct?
Are all fuses present and in order?
In normal operation, one or more steps are flashing?
Check condition of fuses, contactors and capacitors of this faulty step.
Reset in SETUP / 100 / OUt or by re-start (interruption of supply
voltage) of BLR-CX!
Alarms:
Settings of alarm system: SETUP / 500 see Reference book
U ALARM : Voltage out of tolerance
I LO ALARM : Current < 15mA (check current path)
I Hi ALARM : Current > 6A. (CT rating is too small)
PFC ALARM : Target cannot be reached (check panel)
HAr ALARM : Limit of THD U is exceeded
StEP/FLtY ALARM : Defective steps
SPL/Nr ALARM : Derating of stepsize (< 70% of original size)
stepnumber and code are flashing in rotation
thi ALARM : Over temperature - disconnection of steps
OPH ALARM : max. operation hours are reached (maintenance)
OPC/Nr ALARM : max. switch cycles per step (maintenance)
stepnumber and code are flashing in rotation
AI/Abrt ALARM : Abort of automatic initialising
Start AI again at more quiet load conditions or do
manual setting of phase offset
(SETUP / 200 see Reference book)
Factory Default Settings when delivered by Beluk
SETUP / 100 - for user SETUP / 300 - CONTROL
(open access-no password needed) (locked access - password needed)
Important paramters 301/sensitivity: 60%
Un: 400V 302/target-cosj1: 1.00
Ct: 1 303/target-cosj2: i0.95
Pt: 1 304/EXPORT cosj2: NO
Ai: (no setting) 305/switch time delay: 10s
PFC: ON 306/St step exchange: 2s
CP1: 1 307/step exchange: YES
St: 10s 308/step recogn. off: NO
OUt: Auto 309/lock defective steps: YES
SETUP / 200 - MEASURING 310/PFC: ON
(locked access - password needed)
311/Algorithm: Automatik
201/nominal voltage: 400V
312/kvar offset: 0kvar
202/CT-ratio 1
313/asymmetric St: 1
203/VT-ratio: 1
314/Qcap steps off: NO
204/tolerance voltage: 10%
205/Ph-Ph/Ph-N: (automatic)
SETUP / 400 -STEP DATABASE
206/phase offset: 0° (locked access - password needed)
207/Ai: (no setting) 401/discharge lock time: 75s
208/countdown with Ai: NO 402/nom. stepsize CT=1: 5var
209/synchronising: AUTO 403/step type: Auto
210/temperature offset: 0°C 404/switch cycles: 0
Factory settings from Beluk
SETUP / 500 - ALARM SETTINGS SETUP / 600 - RESET
(locked access - password needed) (locked access - password needed)
501/Reset manual NO 601/factory settings
502/THD U alarm NO 602/reset step database
503/THD U limit 20% 603/reset operation hours
504/THD steps off NO 604/reset APF
505/delay time THD, temp2 60s 605/reset max. temperature
506/I=0 freeze PFC NO 606/reset alarm
507/maintenance alarm NO 607/info software version
508/limit switch cycles 262k 608/change password
509/limit operation hours 65.5k
510/target-cosj2 by DI=1 NO
511/DI=1 when T1/T2 closed NO
512/temperature alarm NO
513/temp1 limit 30°C
514/temp2 limit 55°C
515/control alarm NO
516/defective steps alarm NO
517/derating alarm NO
Technical Data:
Voltage: 90-550V, 1ph., 50/60Hz, 6VA
Current: 15mA-6A, 1ph., <1VA,
Control exits: relay, N/C, common root
250V AC / 5A, 400V AC / 2A
Temperaturemeasuring: by plug-in thermistor
Alarm contact: relay, voltfree, N/C operated,
250V AC / 5A, 400V AC / 2A
Fan control: using of control exit
Interface: TTL, rear (standard)
optional: RS485 Modbus, USB
Ambient temperature: operation: -20°V - 70°C
storage: -40°C - 85°C
Humidity: 0% - 95%, without condensation
Overvoltage: II, dirt class 3
Connection: screw type, pluggable
Case: front: instrument case plastic
rear: metal
Protection: front: IP50, (IP54 by using a gasket)
rear: IP20
Weight: ca. 0,6kg
Size: 144x144x58mm hxwxd
cutout: 138 (+0,5) x 138 (+0,5)mm