ITP For Diesel Generator .

This document provides an inspection and test plan for the installation of lighting systems at the Halat Ammar Land Port. It outlines 6 items to be inspected including checking the nameplate and equipment classification, inspecting for any damages, ensuring equipment is securely fixed and mounted, verifying earthing is completed according to design requirements, checking the neutral earthing resistor matches specifications, and testing auxiliary power panel circuit breakers. For each item, it identifies the responsible parties to perform the inspection and acceptance criteria, and references verifying documents. Inspection methods include review, surveillance, witnessing, and holding points where notification is required.

Uploaded by

Waleed Salih
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
452 views3 pages

ITP For Diesel Generator .

This document provides an inspection and test plan for the installation of lighting systems at the Halat Ammar Land Port. It outlines 6 items to be inspected including checking the nameplate and equipment classification, inspecting for any damages, ensuring equipment is securely fixed and mounted, verifying earthing is completed according to design requirements, checking the neutral earthing resistor matches specifications, and testing auxiliary power panel circuit breakers. For each item, it identifies the responsible parties to perform the inspection and acceptance criteria, and references verifying documents. Inspection methods include review, surveillance, witnessing, and holding points where notification is required.

Uploaded by

Waleed Salih
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

HALAT AMMAR LAND PORT ELE

AZM ALHADETHAH AND LIGHTING IMPROV

INSPECTION AND TEST PLAN FO


INSPECTION AND TEST PLAN
OF LIGHTING SYST

Inspection codes: E.CONTRACTOR C.COMPANY


R:DOCUMENT REVIEW S:SURVEILLANCE H:HOLD POING(re
W:WTTNESS(Notification required pr
item Description of Activity Control procedure Reference
Owner's specification
Name plate, equipment classification and IP Project procedure for field material control
1
rating checked QCP for installation of Diesel driven generator
Data sheet from vendor (fromP.O)t

Owner's specification
2 Equipment checked for any damages
QCP for installation of Diesel driven generator

AFC drawing
3 Equipment fixing and mounting are secure Owner's specification
QCP for installation of Diesel driven generator
Owner's specification
Earthing completed and checked against design QCP for installation of earthing & lightning
4
requirements protection systems
AFC drawing

AFC drawing
Neutral earthing resistor to be checked against Owner's specification
5
data sheet and drawing QCP for installation of Diesel driven generator
data sheets

Owner's specification
Auxiliary power panel circuit breaker and
6 QCP for installation of switchgear and MCC'S
auxiliary circuit tested
MAR LAND PORT ELECTRICAL POWER
Date : 31.10.2022
ND LIGHTING IMPROVEMENT

N AND TEST PLAN FOR INSTALLATION


REV : 00
OF LIGHTING SYSTEMS

C.COMPANY A.THIRD PARTY(TPI) I:INSPECTION/TEST


:HOLD POING(required presence notification mandatory)
on required presence not mandatory)
Responsible party Acceptance criteria Verifying document E C
Site Electrical
Engineer & QA/QC correct as per data sheets I/W W/R
Engineer/Officer

Site Electrical
Engineer & QA/QC no damage I/W W/R
Engineer/Officer

Site Electrical
Engineer & QA/QC As per AFC drawing I/W W/R
Engineer/Officer

Site Electrical SHOP DRAWINGS &


≤1Ω TECHNICAL DATA
Engineer & QA/QC I/W S/R
As per AFC drawing SHEET
Engineer/Officer

Site Electrical
As per AFC drawing
Engineer & QA/QC I/W W/R
As per data sheet
Engineer/Officer

Site Electrical
test results as per vendor
Engineer & QA/QC I/W W/R
specification
Engineer/Officer


A

≤1Ω Ω