CT Knee Point Calculation For SGS

1) Five current transformers are required for a bus sectionalizer breaker with the following purposes and specifications: metering, differential protection for 3 phases, and overall protection. 2) The minimum voltage for correct operation (Vk) is calculated to be 1816 volts based on a short circuit current of 50kA, CT dimensioning factor of 2, and lead resistance of 6mm2 copper cable. 3) The CTs must have a maximum resistance of 12 ohms at 75°C and a maximum leakage current of 20mA to limit errors in protection and metering.

Uploaded by

Meghavahina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
68 views1 page

CT Knee Point Calculation For SGS

1) Five current transformers are required for a bus sectionalizer breaker with the following purposes and specifications: metering, differential protection for 3 phases, and overall protection. 2) The minimum voltage for correct operation (Vk) is calculated to be 1816 volts based on a short circuit current of 50kA, CT dimensioning factor of 2, and lead resistance of 6mm2 copper cable. 3) The CTs must have a maximum resistance of 12 ohms at 75°C and a maximum leakage current of 20mA to limit errors in protection and metering.

Uploaded by

Meghavahina
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

220KV class CT required for Bus Sectionaliser breaker (Hybrid Type circuit breaker) at SGS, KPCL

Out put Min. Vk at Max. Ie at Max CT resistance


Core No Purpose Ratio Accuracy ISF highest rated Vk at 75 deg C at
class current (1200) highest ratio
1 Metering 2500/1 0.2 ≤5 - - -
2 Differential 4000/2500/1200/800/1 - PS - 20mA < 12 Ohms
3 Differential 4000/2500/1200/800/1 - PS - 20mA < 12 Ohms
4 Differential 4000/2500/1200/800/1 - PS - 20mA < 12 Ohms
5 Protection 4000/2500/1200/800/1 - 5P20 - - -

Calculation for selecting Vk


If = Short circuit thermal current and its duration- 50KA for 3 secs
Rl = Lead resistance= selecting 6 Sqmm copper cable= Maximum DC resistance per Km= 3.08 Ohms/Km
Vk= K*If [Rct+(2*Rl)]
Where K is CT dimensioning factor i.e., selected as 2
Vk = 2 X 50 [12+(2 X 3.08)]
Vk = 1816 volts
Leakage current shall be limted to 20mA

* CT's shall be at both side limbs of bushings and same for all R,Y,B phases.