OS2x60 AOS 5.1.R1 Hardware Users Guide
OS2x60 AOS 5.1.R1 Hardware Users Guide
A
July 2021
OmniSwitch 2x60
Hardware Users Guide
www.al-enterprise.com
This user guide documents OmniSwitch 2x60 hardware, including chassis and associated components. The
specifications described in this guide are subject to change without notice.
Class A Warning for Taiwan and Other Chinese Markets ...................................... A-8
Class 1M Laser Warning ......................................................................................... A-8
Network Cable Installation Warning ....................................................................... A-8
Translated Safety Warnings ........................................................................................... A-9
Blank Panels Warning ...................................................................................... A-9
Electrical Storm Warning ................................................................................. A-9
Installation Warning ......................................................................................... A-9
Invisible Laser Radiation Warning ................................................................. A-10
Operating Voltage Warning ........................................................................... A-10
Power Disconnection Warning ....................................................................... A-10
Proper Earthing Requirement Warning .......................................................... A-11
DC Power Supply Connection Warning ...................................................................... A-11
Read Important Safety Information Warning ................................................. A-12
Restricted Access Location Warning ............................................................. A-12
Wrist Strap Warning ....................................................................................... A-12
Instrucciones de seguridad en español ......................................................................... A-13
Advertencia sobre el levantamiento del chasis ............................................... A-13
Advertencia de las tapaderas en blanco .......................................................... A-13
Advertencia en caso de tormenta eléctrica ..................................................... A-13
Advertencia de instalación ............................................................................. A-13
Advertencia de radiación láser invisible ......................................................... A-13
Advertencia de la batería de litio .................................................................... A-13
Advertencia sobre la tensión de operación ..................................................... A-13
Advertencia sobre la desconexión de la fuente .............................................. A-13
Advertencia sobre una apropiada conexión a tierra ....................................... A-14
Leer “información importante de seguridad” ................................................. A-14
Advertencia de acceso restringido .................................................................. A-14
Advertencia de pulsera antiestática ................................................................ A-14
Clase de seguridad .......................................................................................... A-14
Advertencia de fuentes de poder .................................................................... A-14
This OmniSwitch 2x60 Hardware Users Guide describes OmniSwitch 2x60 switch components and basic
switch hardware procedures.
Supported Platforms
The information in this guide applies only to OmniSwitch 2260 and OmniSwitch 2360 switches.
Related Documentation
The following are the titles and descriptions of all the user manuals:
• OmniSwitch 2x60 Hardware Users Guide
Complete technical specifications and procedures for all OmniSwitch 2x60 chassis, power supplies,
fans, and Network Interface (NI) modules.
• OmniSwitch 2260/2360 AOS CLI Reference Guide
Complete reference to all CLI commands supported on the OmniSwitch. Includes syntax definitions,
default values, examples, usage guidelines and CLI-to-MIB variable mappings.
• OmniSwitch 2260/2360 WebView Guide
Includes procedures for readying an individual switch for integration into a network. Topics include the
software directory architecture, image rollback protections, authenticated switch access, managing
switch files, system configuration, using SNMP, and using web management software (WebView).
• Release Notes
Includes critical Open Problem Reports, feature exceptions, and other important information on the
features supported in the current release and any limitations to their support.
Refer to the information below for OmniSwitch 2x60 models and components.
Hot-Swapping
Hot-swapping refers to the action of adding, removing, or replacing certain hardware components without
powering off your switch and disrupting other components in the chassis. This feature greatly facilitates
hardware upgrades and maintenance and also allows you to easily replace components in the unlikely
event of hardware failure.
Hardware Monitoring
Automatic Monitoring
Automatic monitoring refers to the switch’s built-in sensors that automatically monitor operations. If an
error is detected (e.g., over-threshold temperature), the switch immediately sends a trap to the user. The
trap is displayed on the console in the form of a text error message.
LEDs
LEDs, which provide visual status information, are provided on the front and rear panels. LEDs are used
to indicate conditions, such as hardware and software status, link integrity, data flow, etc. For detailed
LED descriptions, refer to the corresponding hardware component section in the next chapter.
User-Driven Monitoring
User-driven hardware monitoring refers to CLI commands that are entered by the user in order to access
the current status of hardware components. The user enters “show” commands that output information to
the console. The show commands for all the features are described in detail in the CLI Reference Guide.
Site Preparation
Environmental Requirements
The switches have the following environmental and airflow requirements:
• The installation site must maintain a supported temperature and humidity range as given in the
specifications table for the chassis. See “OmniSwitch 2x60 Chassis Details” on page 3-2.
• Be sure to allow adequate room for proper air ventilation at the front, back, and sides of the switch.
Refer to “Airflow Considerations” on page 2-4 for minimum clearance requirements. No clearance is
necessary at the top or bottom of the chassis.
Electrical Requirements
Note. Switches must be installed by a professional installer. It is the responsibility of the installer to ensure
that proper grounding is available and that the installation meets applicable local and national electrical
codes.
• Every power supply that is connected to building power should be earth grounded.
• Earth grounding for the power cable, should be verified to be 0.01 ohm or less.
• Each switch should be grounded to same earth ground as the power supply.
2 Shielded cables (STP) offer some minimal level of additional protection over unshielded Ethernet
cables (UTP) but the use of a surge protector is still recommended.
• It is suggested to use STP Cat5e or better for 1Gbps Ethernet switches for any outdoor application or
applications where Ethernet cables come in close proximity to alternating current conductors.
• Always install cables according to manufacturer requirements.
3 For any connections where integrity of the cabling within a building ground is questionable (i.e outdoor
connections), copper Ethernet ports must be connected with an appropriate surge protection device, inline,
between the PSE and PD per the manufacturer’s recommendations for connection and grounding.
4 Caution should be taken for any cable connected to any outdoor device, not only on the device ground-
ing, but to ensure that any outdoor device cables that could carry surge currents, do not pass those surge
currents to upstream Ethernet switches.
5 Caution - Category 5e, Category 6, and Category 6a cables can store large amounts of static electricity
due to the dielectric properties of their construction materials in addition, this build up of electricity could
lead to a Cable Discharge Event (CDE). A CDE can occur due to the differential in charges on the cable
and the equipment it’s being connected to. It is recommended that installers momentarily ground all
copper Ethernet cables (especially in new cable runs) to a suitable and safe earth ground before connect-
ing them to the port.
Note. Failure to follow the above recommendations could result in voiding the warranty of the affected
product.
Items Included
Your OmniSwitch may include the following items:
• OmniSwitch chassis with power supplies, per order
• Transceivers, per order
• Blank cover panel
• Rack mount brackets
Weight Considerations
Weights vary depending on model type. Please refer to the chassis specifications table.
Airflow Considerations
To ensure proper airflow, be sure that your switch is placed in a clean, well-ventilated area free of dust and
debris and provide minimum recommended clearance at the front, back and sides of the switch.
Never obstruct chassis air vents.
Note. Clearance is not required at the top and bottom of the chassis.
Component LEDs
During the boot process, component LEDs will flash and change color, indicating different stages of the boot
For complete information on LED states, refer to “Chassis Status LEDs” on page 3-18.
Once the switch has completely booted and you have accessed your computer’s terminal emulation software
via the console port, you are ready to log in to the switch’s Command Line Interface (CLI) and configure basic
information. Continue to “Your First Login Session” on page 2-7.
You cannot specify more than one session type in a single command line. However, you can still unlock
multiple session types by using the aaa authentication command in succession. For example:
-> aaa authentication http local
-> aaa authentication telnet local
-> aaa authentication ftp local
Refer to the CLI Reference Guide for complete aaa authentication command syntax options.
1 Be sure that you have logged into the switch as user type admin (see “Logging In to the Switch” on
page 2-7).
2 Enter the keyword password and press Enter.
Note. Be sure to remember or securely record all new passwords; overriding configured passwords on an
OmniSwitch is restricted.
4 You will be prompted to re-enter the password. Enter the password a second time.
New password settings are automatically saved in real time to the local user database; the user is not required
to enter an additional command in order to save the password information. Also note that new password
information is retained following a reboot. All subsequent login sessions, including those through the console
port, will require the new password to access the switch.
This chapter includes detailed information on the chassis types. Topics include:
• Chassis details and technical specifications:
• Monitoring the chassis components via the Command Line Interface (CLI), page 3-28
C B
D
1 2 3 4 5 6 7 8 9 10 11 12 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-8) 10/100/1000 Base-T ports
D (9-12) SFP ports (1G)
A B
Item Description
A Chassis Grounding Lug
B Power Supply Connector (30W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2260-P10
OS2260-P10 Front Panel
C B
1 2 3 4 5 6 7 8 9 10
D 11 12 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-8) 10/100/1000 Base-T PoE(802.3at) ports
D (9-12) SFP ports (1G)
B
A
Item Description
A Chassis Grounding Lug
B Power Supply Connector (120W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-24
OS2x60-24 Front Panel
C B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
A
5.25V Max, 0.5A Max
Console / USB
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-24) 10/100/1000 Base-T ports
D (2260) (25-28) SFP (1G) ports
D (2360) (25-26) SFP (1G) ports
(27-28) SFP (1G) Uplink or SFP+ (10G) VFL ports
A B
Item Description
A Chassis Grounding Lug
B Power Supply Connector (65W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-P24
OS2x60-P24 Front Panel
C B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-24) 10/100/1000 Base-T PoE (802.3at) ports
D (2260) (25-28) SFP (1G) ports
D (2360) (25-26) SFP (1G) ports
(27-28) SFP (1G) Uplink or SFP+ (10G) VFL ports
B
A
Item Description
A Chassis Grounding Lug
B Power Supply Connector (260W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-P24X
OS2x60-P24X Front Panel
C B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26
D 27 28 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-24) 10/100/1000 Base-T PoE (802.3at) ports
D (2260) (25-26) SFP (1G) ports
(27-28) SFP+ (1G/10G) ports
D (2360) (25-26) SFP+ (1G/10G) ports
(27-28) SFP (1G) Uplink or SFP+ (10G) VFL ports
B
A
Item Description
A Chassis Grounding Lug
B Power Supply Connector (550W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-48
OS2x60-48 Front Panel
C D B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-48) 10/100/1000 Base-T ports
D (2260) (49-54) SFP (1G) ports
D (2360) (49-52) SFP (1G) ports
(53-54) SFP (1G) Uplink or SFP+ (10G) VFL ports
B
A
Item Description
A Power Supply Connector (65W Internal AC Power Supply)
B Chassis Grounding Lug
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-P48
OS2x60-P48 Front Panel
C D B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-48) 10/100/1000 Base-T PoE (802.3at) ports
D (2260) (49-54) SFP (1G) ports
D (2360) (49-52) SFP (1G) ports
(53-54) SFP (1G) Uplink or SFP+ (10G) VFL ports
B
A
Item Description
A Power Supply Connector (550W Internal AC Power Supply)
B Chassis Grounding Lug
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
OS2x60-P48X
OS2x60-P48X Front Panel
C D B
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
D
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 OK VC PWR
Item Description
A Status LEDs
B Console and USB port
C (1-48) 10/100/1000 Base-T PoE (802.3at) ports
D (2260) (49-52) SFP (1G) ports
(53-54) SFP+ (1G/10G) ports
D (2360) (49-50) SFP (1G) ports
(51-52) SFP+ (1G/10G) ports
(53-54) SFP (1G) Uplink or SFP+ (10G) VFL ports
A B
Item Description
A Chassis Grounding Lug
B Power Supply Connector (950W Internal AC Power Supply)
*Note On Chassis Versus Ambient Temperatures. Chassis temperature refers to the sensor reading of
the internal switch temperature (threshold or danger). Ambient temperature refers to the approximate room
temperature. The ambient temperature will typically be lower than the chassis temperature.
Airflow Recommendations
To ensure proper airflow, be sure that your switch is placed in a clean, well-ventilated area free of dust and
debris and provide minimum recommended clearance at the front, back and sides of the switch, as shown
below. Restricted airflow can cause your switch to overheat, which can lead to switch failure. Refer to the
following important guidelines regarding airflow:
Follow the guidelines below regarding the minimum clearance requirements when mounting
the chassis.
Note. Clearance is not required at the top and bottom of the chassis.
Rack-Mounting
Refer to the following important guidelines before installing the chassis in a rack:
• Two people are required to rack mount the switch: One person to lift the chassis into position and one
person to secure the chassis to the rack using the rack mount screws.
• The chassis has rack-mount flanges that support standard 19-inch rack mount installations.
• Alcatel-Lucent Enterprise does not provide rack-mount screws. Use the screws supplied by the
rack vendor.
• To prevent a rack from becoming top heavy, it is recommended that you install the switch at the
bottom of the rack whenever possible.
Note. If you are installing the switch in a relay rack, be sure to install and secure the rack per rack manu-
facturer’s specifications.
Clip in “Out”
(disengaged)
position
Tab
Slot
3 Press the flange and spring clip until the flange clicks into place and the clip is in the in
(engaged) position.
Clip in “In”
(engaged)
position
“CLICK”
5 Repeat steps 1 through 4 for the flange on the opposite side of the chassis.
2 One person should lift and position the chassis until the rack-mount flanges are flush with the
rack post.
3 Align the holes in the flanges with the rack holes marked in step 1.
4 Once the holes are aligned, the second person should insert a screw through the bottom hole on each
flange. Tighten both screws until they are secure.
5 Install the remaining screws in the top hole of each flange. Be sure that all screws are
securely tightened.
Note. Never attempt to operate a switch while it is placed on its top or side.
Note. Some factory-installed screws may need to be removed prior to mounting, depending on the kit
being used.
Note. For information on rack mounting full width 24- and 48-port switches, refer to
“Mounting the Switch” on page 3-19.
• If you are installing the switch on a relay rack, be sure to install and secure the rack per the rack
manufacturer’s specifications.
Note. Some factory-installed screws may need to be removed prior to mounting, depending on the kit
being used.
2 Align the holes in the flanges with the rack holes and insert rack mount screws (not provided) through
the bottom hole of each flange and then the top of each flange. Tighten both screws until they are secure
To view more detailed information, use the show module long command:
To check the switch’s current temperature status, use the show temperature command. For example:
For more information about this command, see the “Chassis Management and Monitoring Commands”
chapter in the CLI Reference Guide.
Temperature Errors
The switch monitors the chassis temperature at all times via an onboard sensor. If an over-temperature
condition occurs, there are two different levels of error severity:
• Warning threshold has been exceeded
Warning Threshold
If the temperature exceeds the switch’s Warning threshold, the switch sends out a trap. Traps are also
printed to the console in the form of text error messages.
When the Warning threshold has been exceeded, switch operations remain active. However, it is
recommended that immediate steps be taken to address the over-temperature condition.
Addressing Warning threshold temperature conditions may include:
• Checking for a chassis airflow obstruction
Power over Ethernet (PoE) provides inline power directly from the switch’s Ethernet ports. Powered
Devices (PDs) such as IP phones, wireless LAN stations, Ethernet hubs, and other access points can be
plugged directly into the Ethernet. From these RJ-45 the devices receive both electrical power and
data flow.
As the feature reduces devices’ dependence on conventional power sources, PoE eliminates many restric-
tions that traditional electrical considerations have imposed on networks.
In a PoE configuration, Power Source Equipment (PSE) detects the presence of a PD and provides an elec-
trical current that is conducted along the data cable. The PD operates using the power received via the
Ethernet data cable; no connection to an additional power source (e.g., an AC wall socket) is required.
Note on Terminology. There are several general terms used to describe the feature, PoE. The terms Power
over Ethernet (PoE), Power over LAN (PoL), Power on LAN (PoL), and Inline Power are synonymous
terms used to describe the powering of attached devices via Ethernet. For consistency, this chapter and the
CLI Reference Guide refer to the feature as Power over Ethernet (PoE).
Additional terms, such as Powered Device (PD) and Power Source Equipment (PSE) are not synonymous
with PoE, but are directly related to the feature:
• PD refers to any attached device that uses a PoE data cable as its only source of power. Examples
include access points, IP telephones, Ethernet hubs, wireless LAN stations, etc.
• PSE refers to power sourcing equipment, which provides power to a single link section. PSE main
functions include searching the PD, optionally classifying the PD, supplying power to the link section
only if the PD is detected, monitoring the power on the link section, and scaling power back to detect
level when power is no longer requested or required.
As the switches fully support 10/100/1000 Ethernet connectivity, you may also attach non-PD equipment,
such as computer workstations, printers, servers, etc. to the PoE ports.
Important. It’s recommended that PoE-enabled switches with attached IP telephones should have opera-
tional power supply redundancy at all times for 911 emergency requirements. In addition, both the switch
and the power supply should be plugged into an Uninterruptible Power Source (UPS).
In This Chapter
This chapter provides specifications and descriptions of hardware and software used to provide PoE for
attached devices.
The chapter also provides information on configuring PoE settings on the switch through the Command
Line Interface (CLI). CLI commands are used in the configuration examples; for more details about the
syntax of commands, see the CLI Reference Guide. Topics and configuration procedures described in this
chapter include:
• Power over Ethernet Specifications on page 4-3
Parameter
Command(s) Default Value/Comments
Description
PoE operational status lanpower slot service Disabled
Power available to a lanpower power 802.3at ports - 30000 milliwatts
port
Power available to an lanpower slot maxpower See “Power over Ethernet Budget”.
entire slot
Power priority level for lanpower priority low
a port
Capacitor detection lanpower capacitor-detec- Disabled
method tion
Priority disconnect sta- lanpower slot priority-dis- Enabled
tus connect
Power at Port
Standard Class Type Pairs
(Watts)
IEEE 802.3af 0 1 2 15.4
1 1 2 4.0
2 1 2 7.0
3 1 2 15.4
802.3at 4 2 2 30
Although class-detection is disabled by default, the switch still provides power to incoming PDs (if avail-
able in the power budget). However, to strictly enforce class detection it must be enabled using the
lanpower slot class-detection command.
Enabling class detection will reset all PoE ports on the chassis.
If power to a particular port has been administratively disconnected, you can reactivate power to the port
using the lanpower port admin-state command. For example:
-> lanpower port 2/1/1-24 admin-state enable
Note. You cannot use the lanpower port admin-state command to initially activate PoE on a port. This
syntax is intended only to reactivate power to those that have been disconnected via the lanpower slot
service command. To initially activate PoE, you must use the lanpower slot service command as
described above.
Disabling PoE
To disable PoE on a particular port, use the lanpower port admin-state command. For example:
-> lanpower port 1/1/12 admin-state disable
To disable PoE for all PoE-capable ports in a slot, use the lanpower slot service command. For example:
-> lanpower slot 1/1 service stop
Fast PoE
Fast PoE can be used to provide PoE power within a few seconds after powering on the chassis. Prior to
this feature PoE power was not provided until the chassis had completed boot-up. With Fast PoE the
default state of the PoE subsystem is set to enabled in the FPGA image and the PoE configuration is stored
in the controller EEPROM. This allows the chassis to immediately provide PoE power to any connected
devices immediately after being powered on without waiting for the chassis to complete the boot-up
process.
• Factory default switches that don't have any PoE configuration must have an initial PoE configuration
completed.
• The PoE configuration cannot be modified until the switch is up and the PoE software module is
completely initialized.
• LLDP-based PoE devices will not function as expected until the switch has completed the boot-up
process and the switch is in a state to respond to LLDP requests.
Perpetual PoE
Perpetual PoE allows the switch to provide uninterrupted power to connected power devices (PD) even
when the switch is rebooting or reloading, such as on a soft reset.
• The power to the PD devices will be interrupted if the PoE controller (MCU) firmware itself is being
upgraded.
Perpetual PoE can be enabled using the syntax below:
-> lanpower slot 1/1 ppoe enable
reduces the power allowance on port 24 to 3000 milliwatts. This new value is now the maximum amount
of power the port can use to power any attached device (until the value is modified by the user).
Important. Decreasing the slot-wide power could cause lower priority ports to lose power if the new
value is less than the total PoE power currently being consumed.
To increase or decrease the total power available to a slot, use the lanpower slot maxpower command.
Since you are setting the power allowance for an individual slot, you must specify a chassis/slot value in
the command line. For example, the syntax
-> lanpower slot 3/1 maxpower 400
reduces the power allowance of chassis 3, slot 1 to 400 watts. This value is now the maximum amount of
power the slot can use to power all attached devices (until the value is modified by the user).
Note. Changing the maximum power available to a slot or port does not reserve or immediately allocate
that power. These settings are only used for configuring a maximum amount of power that may be used,
any unused power is still available and remains a part of the overall PoE budget.
changes the priority value of port 6 to the highest priority level of critical. Now that the default value has
been reconfigured, this port should be reserved for those PDs that are mission critical for network opera-
tions.
Note. The capacitive detection method should only be enabled to support legacy IP phones. This feature
is not compatible with IEEE specifications. Please contact your Alcatel-Lucent sales engineer or Customer
Support representative to find out which Alcatel-Lucent IP phones models need capacitive
detection enabled.
• If the amount of power remaining is less than the port's configured maximum PoE power value or the PD's
class maximum power then the switch will not power up the PD.
• This applies even if the newly connected PD actually requires less than the maximum power available for
the port.
In this example the newly connected PD will not be powered on since the port's maximum PoE power value is
greater than the PoE power remaining on the switch.
To allow the PD to be powered, the port's maximum PoE value can be configured to be less than the power
remaining by issuing the following command to set the port's maximum PoE power to 10W:
-> lanpower power 1/1/1 power 10000
The newly connected PD will be powered on since the port's maximum PoE power value is now less than the
PoE power remaining on the switch. The examples assume the new PD has the same or lower priority as the
existing PDs, otherwise priority disconnect will override.
The Guard Band functionality does not apply to PDs that are already powered up. However, priority disconnect
will apply if there's not enough power to power all PDs in the case of the power budget being reduced, such as
the removal of a power supply.
Please refer to the “Understanding Priority Disconnect” on page 4-10 for additional details.
Reminder. Priority disconnect applies only when there is inadequate power remaining in the power
budget for an incoming device.
For information on setting the priority disconnect status, refer to the section below. For information on
setting the port priority status (a separate function from priority disconnect), refer to “Setting Port Priority
Levels” on page 4-8.
Reminder. Priority disconnect examples are applicable only when there is inadequate power remaining to
power an incoming device.
When a PD is being connected to a port with the same priority level as all other in the slot, the physical
port number is used to determine whether the incoming PD will be granted or denied power. Due to the
support of different PoE standards and PoE hardware on each platform the internal port priority is differ-
ent for each platform. The following should be used to determine PoE priority:
Reminder. Priority disconnect examples are applicable only when there is inadequate power remaining to
power an incoming device.
When a PD is being connected to a port with a higher priority level than all other in the slot, the incoming
PD will automatically be granted power over the other devices, regardless of its physical port number.
In order to avoid a power budget deficit, another port in the slot is disconnected. In determining which
port to power off, the system software first selects the port with the lowest configured priority level. For
example, if a critical priority device is being added to a slot in which five existing devices are attached to
high priority and one device is attached to a low priority port, the low priority port is automatically
disconnected, regardless of its physical port number.
If all existing devices are attached to with the same lower priority level, the system software disconnects
the port with both the lowest priority level and the highest priority physical port number. For example, if a
critical priority device is being added to a slot in which six existing devices are attached to high priority,
the high priority port with the lowest physical port priority number is automatically disconnected.
Reminder. Priority disconnect examples are applicable only when there is inadequate power remaining to
power an incoming device.
When a PD is being connected to a port with a lower priority level than all other in the slot, the incoming
PD will be denied power, regardless of its physical port number. Devices connected to other higher-prior-
ity will continue operating without interruption.
Reminder. Priority disconnect examples are applicable only when there is inadequate power remaining to
power an incoming device.
When priority disconnect is disabled, power will be denied to any incoming PD, regardless of its port
priority status (i.e., low, high, and critical) or physical port number (i.e., 1–24).
Aggregate slot and chassis management information is also displayed. This information includes:
• Maximum watts available to the corresponding slot
When entering the show lanpower command, you must include a valid slot number in the command line
syntax. For example:
(output truncated)
Note. For detailed information on show lanpower command output, refer to the CLI Reference Guide.
This appendix provides information on regulatory agency compliance and safety for the OmniSwitch.
Treatment applied at end of life of the product in these countries shall comply with the applicable national
laws implementing directive 2002/96/EC on waste electrical and electronic equipment (WEEE).
CB FB
Standards Compliance
The product bears the CE mark. In addition it is in compliance with the following other safety and
EMC standards.
Note. All hardware switching modules used in an OmniSwitch switch comply with Class A
standards. Modules with copper connectors meet Class A requirements using unshielded (UTP) cables.
Safety Standards
• US UL 60950-1
• UL-AR, Argentina
• EN 60825-1 Laser
• EN 60825-2 Laser
• CDRH Laser
• CCC, China
EMI/EMC Standards
• FCC Part 15:2012, Subpart B, Class A
• ANSI C63.4-2009
• VCCI (Class A)
• EN 61000-3-2
• EN 61000-3-3
• EN 55024 (Immunity)
• EN 61000-4-2
• EN 61000-4-3
• EN 61000-4-4
• EN 61000-4-5
• EN 61000-4-6
• EN 61000-4-8
• EN 61000-4-11
• IEEE 802.3: Hi-Pot Test
(2250 V DC on all Ethernet ports)
Environmental Standards
• IEC 60068-2-1
• IEC 60068-2-2
• IEC 60068-2-30
• IEC 60068-2-13
• IEC 60068-2-40
• IEC 60068-2-41
• IEC 6068-2-6
• IEC 60068-2-64
• IEC 60068-2-27
• GR-63-CORE
• MIL-STD-810F Method 516.5 IV
• MIL-STD-810F Method 516.5 C
• Plug the equipment into a different outlet so that equipment and receiver are on different branch
circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional
suggestions.
JATE
This equipment meets the requirements of the Japan Approvals Institute of Telecommunications
Equipment (JATE).
VCCI
This is a Class A product based on the standard of the Voluntary Control Council for Interference by
Information Technology Equipment (VCCI). If this equipment is used in a domestic environment, radio
disturbance may arise. When such trouble occurs, the user may be required to take corrective actions.
Installation Warning
Only personnel knowledgeable in basic electrical and mechanical procedures should install or maintain
this equipment.
Français: Toute installation ou remplacement de l'appareil doit être réalisée par du personnel qualifié et
compétent.
Deutsch: Dieses Gerät soll nur von Personal installiert oder gewartet werden, welches in elektrischen und
mechanischen Grundlagen ausgebildet ist.
Español: Estos equipos deben ser instalados y atendidos exclusivamente por personal adecuadamente
formado y capacitado en técnicas eléctricas y mecánicas.
Advertencia de instalación
Solamente el personal bien informado en procedimientos eléctricos y mecánicos básicos debe instalar o
mantener este equipo.
Clase de seguridad
Cumple con 21CFR 1040.10 y 1040.11 ó sus equivalentes.