Transformer Protection
Transformer Protection
Busbar
protection
Busbar
protection
Feeder
protection
Feeder
protection
Simplified of Protection Scheme
R R R
11kV 3.3kV
Unit protection:- The boundary of operation is clearly defined in terms of primary plant. Unit protection is designed to
operate for abnormal conditions inside the protected zone while remaining stable for abnormal conditions outside the
protected zone.
Non-unit protection:- Time degrade protection. It is arranged so that the protection within the faulted zone operates
first and removes the fault, thus allowing protection in other zones to reset before completing their tripping function.
Protection Function for Power Transformer
71 Oil Level
50G
80 Buchholz
(not applicable for sealed transformer)
50G/51G
50 Instantaneous Overcurrent 11kV
87T
50N Instantaneous Earth Fault (residual sum)
64REF
51N Inverse Time Earth Fault (residual sum)
Upstream CB Permissive closing Downstream CB open & Downstream CB open by intertrip Upstream 86 activate:
Downstream ES open 50/51, 50G
Upstream CB open command Downstream incomer emergency Downstream CB open by intertrip Upstream 86T activate:
pushbutton activate 26OT, 49WT, 63, 71, 80
64REF, 87T, 50G/51G
***NOTE
Downstream CB open due Upstream CB open status
upstream CB open status
• General requirement
Below transformer damage curve
Above transformer inrush
Meeting the required time grading
• For instantaneous:
Pickup before arcing current Ia
Inverse Definite Minimum Time (IDMT)
• Consideration
CB opening time
Relay timing error
Relay overshoot
CT error
Safety margin
Earth Fault - Residual Connection (N)
During the incident SB-321-C-02 flash over on 20th Sep 2019, is found that upstream 33kV feeder and
downstream 11kV incomer trip.
Fault location is at busbar of SB-321-C-02
Normal conditions, I1 = I2
1) A transformer has a turns ratio so the current in is not really equal to the current out. The current transformers are
not likely exactly matched to the transformer turns ratio so there will always be an unbalance current in the
operating coil of a transformer differential relay.
11kV 3.3kV
operate
2) Transformers require magnetizing current. There will be a small current flow in the transformer primary even if the
secondary is open circuited.
3) A transformer has an inrush current. There is a time period after a transformer is energized until the magnetic field
in the core in alternating symmetrically. The size and the length of this inrush depends on the residual field in the
core and the point in the ac cycle the transformer is re-energized.
SOLUTION: there are restraining coils in addition to the operating coil of the relay
Differential relay: Impact on differential current (Id) due to
CT mismatch and Transformer ratio
10MVA
11/3.45kV
IFLC = 552.5A -5% tap IFLC = 1637.5A
11kV 600/1 2500/1 3.3kV For 10MVA 33/11kV -5% tap position,
26.6% Unbalance current in the
operating coil of a transformer
differential relay.
I1 = 0.921A I2 = 0.655A
operate
Id = 0.266A
10MVA
11/3.45kV
IFLC = 449.9A +5% tap IFLC = 1637.5A
11kV 600/1 3.3kV
For 10MVA 33/11kV +5% tap position,
2500/1
9.5% unbalance current in the
operating coil of a transformer
differential relay.
I1 = 0.750A I2 = 0.655A
operate
Id = 0.095A
Differential relay: Impact on differential current (Id) due to
external fault
10MVA
11/3.45kV
IFLC = 552.5A -5% tap, z=8.5% IFLC = 1637.5A
11kV 600/1 2500/1 3.3kV
Consider transformer configuration as
per figure on the left, during normal
operation, Id is 0.226A.
I1 = 0.921A I2 = 0.655A
operate
Id = 0.266A
10MVA
11/3.45kV
IFLC = 6.5kA -5% tap, z=8.5% ISC = 19.26kA
11kV 600/1 2500/1 3.3kV
However, during external fault, due to
CT mismatch, Id is becoming larger; in
this case, Id is 3.13A.
I1 = 10.83A I2 = 7.70A
operate
Id = 3.13A
Differential Relay - Restrain characteristic
The current differential protection needs to be biased because the possible appearance of a differential current
can be due to something else than an actual fault.
Under normal and through fault conditions, restrain current is greater than operate current. Thereby relay remains
inactive.
When internal fault occurs, the operating force exceeds the bias force and hence the relay is operated.
11kV 3.3kV
restrain
operate
• Assuming:
-10% CT error on 11kV
restrain
+10% CT error on 3.3kV
+5% FLC on 3.3kV (max transformer tap position) operate
Result:
Id = |I1 – I2| = 0.15 pu = 25%
Ib = |I1 + I2| ÷ 2 = 1.025 pu = 102.5%
STABLE..!
Bias Differential – Protection operate
11kV If = 3 pu I2 = 0 3.3kV
• Assuming:
Transformer internal fault which with fault current
equal to 300% FLC restrain
operate
Result:
Id = |I1 – I2| = 3.00 pu = 300%
Ib = |I1 + I2| ÷ 2 = 1.50 pu = 150%
PROTECTION OPERATE..!
Magnetizing Inrush Current
The phenomenon of magnetizing inrush current occurs when a transformer is energized. When the primary side of
a transformer is energized from the supply system, with the secondary on open-circuit, it acts as a simple
inductive reactor.
This current flows only in the winding connected to the source of supply, and thus causes a spill current into the
biased-differential-operate winding.
Magnetizing inrush has a large second-harmonic component of current and therefore, as shown in figure above, it
is usual to arrange an additional bias winding, which is responsive to second-harmonic currents, to offset the
effect of magnetizing inrush current in the operate winding.
Restricted Earth Fault
• Fault detection is confined to the zone between the two CTs hence the name
'Restricted Earth Fault'.
Case Study
https://www.academia.edu/38812187/TRANSFORMER_STABILITY_TEST_REPORT_TR_321_CD_02A
Type Of Fault
Analysing Electrical Trip
Concern Action
What had happen What was the ongoing activities prior to trip
Where is the tripping Identify the trip breaker – check also upstream and
downstream breaker
When is the tripping Record down the date and time.
Verify relay time against actual time.
What is the impact of tripping Check and record down the following:
1) Active LED/indication light
2) Lockout status
3) List of equipment stop/interrupted
How the trip happen Record down alarm and event list from relay
Download disturbance recorder
RECORD
SHARE FACTS
DO NOT MAKE ASSUMTION
Open
Protection Relay Maintenance
• Kirchhoffs Current Law or KCL, states that the “total current or charge entering a junction or node is exactly equal to
the charge leaving the node as it has no other place to go except to leave, as no charge is lost within the node“. In
other words the algebraic sum of ALL the currents entering and leaving a node must be equal to zero,
I(exiting) + I(entering) = 0. This idea by Kirchhoff is commonly known as the Conservation of Charge.
Fortescue’s methodology
• Positive sequence voltages (Figure 1) are supplied by generators within the system and are always present.
• Negative sequence component has a rotation opposite that of the power system (Figure 2).
• Zero-sequence component represents an unbalance that causes current flow in the neutral. It is equal in magnitude
and in phase with each other, however since there is no rotation sequence (Figure 3) this is known as a zero
sequence.
Thank you for your passion!