24.3 A 30.4 A Total Connected Load 19.5 KVA Demand Factor 0.81 Max. Demand Load 15.8 KVA TCL 6290 6272.5 Ib Icb

The document provides details about a 24-way panel board located on the ground floor, including its bus bar rating, short circuit capacity, and 3-phase power supply. It then lists the connected lighting loads for each phase by circuit breaker number, load type, cable size, and load in VA. The total connected load is 19.5 KVA with a demand factor of 0.81 and maximum demand load of 15.8 KVA.

Uploaded by

Hossam Ahmed
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
163 views

24.3 A 30.4 A Total Connected Load 19.5 KVA Demand Factor 0.81 Max. Demand Load 15.8 KVA TCL 6290 6272.5 Ib Icb

The document provides details about a 24-way panel board located on the ground floor, including its bus bar rating, short circuit capacity, and 3-phase power supply. It then lists the connected lighting loads for each phase by circuit breaker number, load type, cable size, and load in VA. The total connected load is 19.5 KVA with a demand factor of 0.81 and maximum demand load of 15.8 KVA.

Uploaded by

Hossam Ahmed
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 9

PANEL BOARD : BUS BAR RATING (A): NO.

OF WAYS: LOCATION:
DB-F 32 A 24 WAY GROUND FLOOR
SHORT CIRCUIT INTERRUPTING CAPACITY :16 KA SYMMETRI POWER SUPPLY
FORM OF SEPARATION: 2B 3 PHASE 380 / 220 VOLT, 50 HZ
LOAD (VA) CABLE C.B. T.
Notes LOAD TYPE
R Y B mm² AMP NO.
LIGHTING 130 3x3 16 1
LIGHTING 520 3x3 16 3
LIGHTING 500 3x3 16 5
LIGHTING 500 3x3 16 7
LIGHTING 650 3x3 16 9
LIGHTING 500 3x3 16 11
LIGHTING 500 3x3 16 13
LIGHTING 602.5 3x3 16 15
LIGHTING 552.5 3x3 16 17
SPARE 16 19
SPARE 16 21
SPARE 16 23
1130 1773 1553
MCCB
Ib = 24.3 A ICB = 30.4 A TPN
Total Connected Load = 19.5 KVA 32 A A A A
Demand Factor = 0.81
Max. Demand Load = 15.8 KVA TCL 6290 6272.5

LTG SO P.SO W/H H/D A/C M/C TOT.


T.C.L. 4.46 3.24 10.5 1.26 19.46
D.F. 1.00 0.6 0.8 0.8 0.81
M.D.L. 4.455 1.94 8.40 1.01 15.81
LOCATION: MOUNTING : PROTECTION DEGREE :
GROUND FLOOR WALL MOUNTED IP 42
WER SUPPLY FEEDING CABLE SIZE : PVC/PVC-Laid direct in Gro
80 / 220 VOLT, 50 HZ (4X16+16) mm² CU, XLPE/PVC PVC/PVC-Laid in Ducts
T. C.B. CABLE LOAD (VA) PVC/PVC-Laid in free air
LOAD TYPE Notes
NO. AMP mm² R Y B XLPE/PVC-Laid direct in Gr
2 20 3x4 1260 socket XLPE/PVC-Laid in Ducts
4 20 SPARE XLPE/PVC-Laid in free air
6 20 3x4 1080 SOCKET
8 20 3x4 900 SOCKET
10 20 3x4 1500 P.S
12 20 3x4 1500 P.S
14 20 3x4 1500 P.S
16 20 3x4 1500 P.S
18 20 3x4 1500 P.S
20 20 3x4 1500 P.S
22 20 3x4 1500 P.S
24 20 3x4 1260 SOCKET
5160 4500 5340

V S

6892.5

(KVA)
19.46
0.81
15.81
(4x6)
(4x6)
(4x6)
(4x6)
(4x6)
(4x6)
Max
Conductor Current Rating
resistance
Nominal Cross Sectional
Egytech-Code Area PVC/PVC-Laid PVC/PVC- Approx.
PVC/PVC-Laid
DC at 70° C direct in Laid in in free air overall
Ground Ducts diameter
mm2 Ω/Km A A A mm
Four Core Cables
CP1-T104-U04 1.5 rm 14.600 21 18 18 11.4
CP1-T104-U06 2.5 rm 8.870 27 23 22 12.4
CP1-T104-U08 4 rm 5.540 35 30 31 14..8
CP1-T104-U09 (4x6) rm 3.690 45 36 39 16.0
CP1-T104-U10 (4x10) rm 2.190 60 48 53 18.5
CP1-T104-U11 (4x16) rm 1.390 75 60 72 20.9
CP1-T104-U12 (4x25) rm 0.870 100 80 94 25.0
CP1-T104-U13 (4x35) sm 0.628 120 95 110 25.1
CP1-T104-U14 (4x50) sm 0.464 145 115 138 29.3
CP1-T104-U15 (4x70) sm 0.322 175 145 171 32.9
CP1-T104-U16 (4x95) sm 0.232 210 165 209 37.8
CP1-T104-U17 (4x120) sm 0.185 240 195 242 41.2
CP1-T104-U18 (4x150) sm 0.151 270 220 275 45.9
CP1-T104-U19 (4x185) sm 0.121 300 245 314 50.7
CP1-T104-U20 (4x240) sm 0.084 345 290 374 57.0
CP1-T104-U30 (4x300) sm 0.077 390 320 440 63.3

PVC/PVC-Laid PVC/PVC- XLPE/PVC-


direct in Laid in PVC/PVC-Laid Laid direct in
in free air
Ground
A Ducts
A A Ground
A
1 2 3 4 5
(4x6) 45 36 39 57
(4x10) 60 48 53 75
(4x16) 75 60 72 97
(4x25) 100 80 94 128
(4x35) 120 95 110 155
(4x50) 145 115 138 185
(4x70) 175 145 171 220
(4x95) 210 165 209 265
(4x120) 240 195 242 305
(4x150) 270 220 275 335
(4x185) 300 245 314 375
(4x240) 345 290 374 435
(4x300) 390 320 440 490
PVC/PVC-Laid direct in XLPE/PVC-Laid direct in
PVC/PVC-Laid in Ducts PVC/PVC-Laid in free air
Ground Ground
0 (4x6) 0 (4x6) 0 (4x6) 0 (4x6)
45 (4x10) 36 (4x10) 39 (4x10) 57 (4x10)
60 (4x16) 48 (4x16) 53 (4x16) 75 (4x16)
75 (4x25) 60 (4x25) 72 (4x25) 97 (4x25)
100 (4x35) 80 (4x35) 94 (4x35) 128 (4x35)
120 (4x50) 95 (4x50) 110 (4x50) 155 (4x50)
145 (4x70) 115 (4x70) 138 (4x70) 185 (4x70)
175 (4x95) 145 (4x95) 171 (4x95) 220 (4x95)
210 (4x120) 165 (4x120) 209 (4x120) 265 (4x120)
240 (4x150) 195 (4x150) 242 (4x150) 305 (4x150)
270 (4x185) 220 (4x185) 275 (4x185) 335 (4x185)
300 (4x240) 245 (4x240) 314 (4x240) 375 (4x240)
345 (4x300) 290 (4x300) 374 (4x300) 435 (4x300)
390 (4x300) 320 (4x300) 440 (4x300) 490 (4x300)
Max
Conductor Current Rating
resistance Approx
Nominal Cross
Egytech-Code Sectional Area XLPE/PVC- XLPE/ XLPE/ .
DC at 70° C Laid direct PVC-Laid PVC-Laid overall
in Ground in Ducts in free air diamet
er
mm2 Ω/Km A A A mm
Four Core Cables
CX1-T104-U0 1.5 rm 15.400 26 23 22 10.6
CX1-T104-U0 2.5 rm 9.450 35 29 32 11.9
CX1-T104-U0 4 rm 5.880 45 36 41 13.4
CX1-T104-U0 (4x6) rm 3.930 57 45 50 14.6
CX1-T104-U1 (4x10) rm 2.330 75 60 68 17.0
CX1-T104-U1 (4x16) rm 1.470 97 75 89 19.4
CX1-T104-U1 (4x25) rm 0.927 128 102 120 23.5
CX1-T104-U1 (4x35) sm 0.669 155 120 145 23.6
CX1-T104-U1 (4x50) sm 0.494 185 145 179 27.1
CX1-T104-U1 (4x70) sm 0.343 220 180 225 31.4
CX1-T104-U1 (4x95) sm 0.248 265 210 268 35.1
CX1-T104-U1 (4x120) sm 0.197 305 245 310 39.2
CX1-T104-U1 (4x150) sm 0.160 335 275 352 43.7
CX1-T104-U1 (4x185) sm 0.129 375 310 404 48.7
CX1-T104-U2 (4x240) sm 0.099 435 365 483 54.5
CX1-T104-U3 (4x300) sm 0.081 490 405 562 60.1

XLPE/
XLPE/PVC- PVC-
Laid in Ducts Laid in
A freeA air
6 7
45 50
60 68
75 89
102 120
120 145
145 179
180 225
210 268
245 310
275 352
310 404
365 483
405 562
XLPE/PVC-Laid in
XLPE/PVC-Laid in free air
Ducts
0 (4x6) 0 (4x6)
45 (4x10) 50 (4x10)
60 (4x16) 68 (4x16)
75 (4x25) 89 (4x25)
102 (4x35) 120 (4x35)
120 (4x50) 145 (4x50)
145 (4x70) 179 (4x70)
180 (4x95) 225 (4x95)
210 (4x120) 268 (4x120)
245 (4x150) 310 (4x150)
275 (4x185) 352 (4x185)
310 (4x240) 404 (4x240)
365 (4x300) 483 (4x300)
405 (4x300) 562 (4x300)
Max
Conduc
tor Current Rating
resistan
Nominal Cross ce Laid Approx.
Egytech-Code Sectional Area DC at direct Laid in Laid in overall
70° C in Ducts free air diamet
Ground er
mm2 Ω/Km A A A mm
Four Core Cables
CX1-T104-U0 1.5 rm 15.400 26 23 22 10.6
CX1-T104-U0 2.5 rm 9.450 35 29 32 11.9
CX1-T104-U0 4 rm 5.880 45 36 41 13.4
CX1-T104-U0 (4x6) rm 3.930 57 45 50 14.6
CX1-T104-U1 (4x10) rm 2.330 75 60 68 17.0
CX1-T104-U1 (4x16) rm 1.470 97 75 89 19.4
CX1-T104-U1 (4x25) rm 0.927 128 102 120 23.5
CX1-T104-U1 (4x35) sm 0.669 155 120 145 23.6
CX1-T104-U1 (4x50) sm 0.494 185 145 179 27.1
CX1-T104-U1 (4x70) sm 0.343 220 180 225 31.4
CX1-T104-U1 (4x95) sm 0.248 265 210 268 35.1
CX1-T104-U1 (4x120) sm 0.197 305 245 310 39.2
CX1-T104-U1 (4x150) sm 0.160 335 275 352 43.7
CX1-T104-U1 (4x185) sm 0.129 375 310 404 48.7
CX1-T104-U2 (4x240) sm 0.099 435 365 483 54.5
CX1-T104-U3 (4x300) sm 0.081 490 405 562 60.1
A B

0 16
16 20
20 25
25 32
32 40
40 50
50 63
63 80
80 100
100 125
125 160
160 200
200 250
250 300
300 400
400 500
500 630
630 800
800 1000
1000 1250
1250 1600
1600 2000
2000 2500
2500 3000
3000 4000
4000 5000
5000 6000