Fire Management Sales Resource Manual 447

Accessories Section
Product Bulletin
Issue Date 0600

300 Series Intelligent Modules

The 300 Series intelligent modules are designed


for use with the Intelligent Fire Controller (IFC) line
of fire alarm control panels. The M300CJ control
module is used for a circuit of notification LED
appliances, or for monitoring of a telephone circuit.
The M300RJ relay module provides the IFCs with
a Form-C contact output for a variety of devices.

The M300MJ monitor module is a standard-sized


module that supervises either a Class A (Style D)
or Class B (Style B) circuit of dry contact input
devices. The M301MJ is a mini-monitor module
used to supervise a Class B (Style B) circuit. The SLC SLC Address
M302MJ is a standard-sized interface module
used to monitor and supervise compatible 2-wire,
24 volt conventional smoke detectors on a
Class A (Style D) or Class B (Style B) circuit.

6724mod2

Figure 1: M300MJ and M302MJ Modules

Features and Benefits


❑ Direct-Dial Entry of Offers convenient addressing of up to
Address (01-159) 159 devices per Signaling Line Circuit (SLC)
with FlashScan systems

❑ High Noise (EMF/RFI) Provides stable, trouble-free operation


Immunity

❑ Built-in Device Type Automatically identifies this device as a


Identification monitor module to the control panel

❑ Two-color Light-Emitting Indicates normal or alarm status at a glance


Diode (LED)

© 2000 Johnson Controls, Inc. 1


Code No. LIT-4470767 www.johnsoncontrols.com
M 300MJ Monitor Module M 301MJ Mini-Monitor Module
The M300MJ monitor module is intended for use The M301MJ mini-monitor module can be installed
in intelligent, addressable systems, where the in a single-gang junction directly behind the
individual SLC address of each module is selected monitored unit. Its small size and light weight allow
using the built-in rotary switches. It provides either it to be installed without rigid mounting. The
a 2-wire or 4-wire fault-tolerant Initiating Device M301MJ is intended for use in intelligent,
Circuit (IDC) for normally open contact fire alarm addressable systems where the individual SLC
and supervisory devices. The module has a address of each module is selected using rotary
panel-controlled LED indicator. The M300MJ can switches. It provides a 2-wire IDC for normally
be used to replace M500MJ modules in existing open contact fire alarm and security devices. The
systems. M301MJ can be used to replace M501MJ modules
in existing systems.
Applications
Applications
The M300MJ monitors a zone of 4-wire
conventional smoke detectors, manual fire alarm The M301MJ monitors a single device or a zone of
pull stations, waterflow devices, or other normally 4-wire smoke detectors, manual fire alarm pull
open dry contact alarm activation devices. The stations, waterflow devices, or other normally open
M300MJ also monitors normally open contact dry contact devices. The M301MJ may also be
supervisory devices with special supervisory used to monitor normally open supervisory
indication at the control panel. Monitored IDC may devices with special supervisory indication at the
be wired as a National Fire Protection Association control panel. Monitored circuit/device is wired as
(NFPA) Style B (Class B) or Style D (Class D) an NFPA Style B (Class B) IDC. A 47K ohm EOLR
IDC. A 47K ohm End-of-Line Resistor (EOLR) (provided) terminates the circuit.
terminates the Style B circuit. No resistor is Breakaway Tab for Extended Address
required for supervision of the Style D circuit. Range for Control Panels with FlashScan
Maximum IDC length is 762 m (2,500 ft), with a
maximum of 20 ohms.

Installation
The M300MJ modules mount directly to a
standard 101.6 mm (4 in.) square, 53.975 mm
(2.125 in.) deep electrical backbox. They may also
mount to the SMB500 surface-mount box.
Mounting hardware and installation instructions
are provided with each module. All wiring must Yellow Violet Red Black
conform to applicable local codes, ordinances, and
regulations. These modules are intended for
power-limited wiring only.

6720m101
Operation
Each 300 Series module uses one of Figure 2: M301MJ Module
159 available module addresses on an SLC that
supports the FlashScan communication protocol. Installation
It responds to regular polls from the control panel The M301MJ is intended for wiring and mounting
and reports its type and the status without rigid connections inside a standard
(open/normal/short) of its initiating device circuit. electrical box. All wiring must conform to
A flashing LED indicates that the module is in applicable local codes, ordinances, and
communication with the control panel. The LED regulations.
latches steady on alarm (subject to current
limitations on the SLC).

2 Accessories—300 Series Intelligent Modules


M 302MJ Interface Module M 300RJ Relay Module
The M302MJ interface module is intended for use The M300RJ addressable Form-C relay module
in intelligent, addressable systems, where the provides the IFC control panel with a dry contact
individual SLC address of each module is selected output for activating a variety of auxiliary devices,
using built-in rotary switches. This module allows such as fans, dampers, control equipment, etc.
intelligent panels to interface and monitor 2-wire Addressability allows the dry contact to be
conventional smoke detectors. It transmits the activated, either manually or through panel
status (normal, open, or alarm) of one zone of programming, on a select basis.
conventional detectors back to the control panel.
All 2-wire detectors being monitored must be
Underwriters Laboratories (UL) compatible with Applications
the module. The M302MJ can be used to replace The M300RJ operates dry contacts for door
M502MJ modules in existing systems. holders, Air Handling Unit (AHU) shutdown, etc.,
and resets 4-wire smoke detector power.
Applications
The M302MJ monitors an IDC zone of 2-wire Table 1: Relay Contact Ratings for
conventional smoke detectors. The monitored M300CJ and M300RJ
circuit may be wired as an NFPA (National Fire
Protection Association) Style B (Class B) or Load Maximum Current
Style D (Class A) IDC. A 3.9K ohm EOLR Description Voltage Rating
(provided) terminates the end of the Style B or D Resistive, non-coded 30 VDC 3.0 A
(Class B or A) circuit (maximum IDC resistance is
Resistive, coded 30 VDC 2.0 A
25 ohms). Install EOLR across Terminals 8 and 9
for Style D application. Resistive, non-coded 110 VDC 0.9 A
Resistive, non-coded 125 VAC 0.9 A
Inductive, coded 30 VDC 0.5 A
Installation (L/R=5 milliseconds)
Same as that of M300MJ monitor module. Inductive, coded 30 VDC 1.0 A
(L/R=2 milliseconds)
Inductive, non-coded 125 VAC 0.5 A

M 300CJ Control Module (PF=0.35)

The M300CJ addressable control module is used


for a supervised circuit of notification appliances
(horns, strobes, speakers, etc.) on an IFC control
panel, or for monitoring a telephone circuit.
Addressability allows the M300CJ to be activated,
either manually or through panel programming, on
a select (zone or area of coverage) basis.

Applications
The M300CJ switches 24 VDC audible/visual
power, high-level 25 VRMS or 70 VRMS amplified
audio (speakers), or to control telephone devices.

Accessories—300 Series Intelligent Modules 3


M ounting Diagrams

Isolated Quadrant
Using the CB500
(see below)
6724mt2 6720mt2

CB500

6724mt1 6720mt1

Figure 3: M300CJ and M300RJ Figure 4: M300MJ and M302 MJ

4 Accessories—300 Series Intelligent Modules


W iring Diagrams
SLC
To
Next
Device
UL Listed
Black Red
Compatible
Control M301MJ
67 8 9 56
789
Panel 4
5 10
11 4
3 12 3
2 13 2
1 0 15 14 10

Violet Yellow

47K EOL Resistor Included

IDC

6720wir1

Figure 5: M301MJ in Typical 2-Wire Style B Initiating Device Circuit Configuration

To Next
SLC Device From Panel
or Previous
Initiating Device Circuit (IDC) Monitor SLC Device
NFPA Style B, Power Limited: Module
230 Micoramperes Maximum @ SLC Communication Line
12 VDC Maximum 9 0 32 VDC Maximum
8 1 Shielded/twisted-pair
47K EOL 7 TENS 2 is recommended.
Resistor 6 3
5 4 SLC Communication Loss
ELR-47K SLC
ONES
ADDRESS (optional connection for panels
which support this feature)
6720wir2

Figure 6: M300MJ in Typical 2-Wire Initiating Device Circuit Configuration, NFPA Style B

To Next
SLC Device From Panel
or Previous
Monitor SLC Device
Module
Initiating Device Circuit (IDC) SLC Communication Line
9 0
32 VDC Maximum
8 1
Shielded/twisted-pair
is recommended.
EOL resistor 7 TENS 2
is internal at 6 3
Terminals 8 and 9. 5 4 SLC Communication Loss
ONES
SLC ADDRESS (optional connection for panels
which support this feature)
6720wir3

Figure 7: M300MJ in Typical 4-Wire Fault-Tolerant Initiating Device Circuit Configuration,


NFPA Style D

Accessories—300 Series Intelligent Modules 5


Initiating Device Circuit (IDC) To Next From Panel
NFPA Style B, Power Limited: SLC Device or Previous
230 Microamperes Maximum Monitor SLC Device
@ 12 VDC Maximum Module
SLC Communication Line
14K Series Resistor 32 VDC Maximum
9 0
8 1 Shielded/twisted-pair
47K EOL 7 TENS 2 is recommended.
Resistor 6 3
5 4 SLC Communication Loss
ELR-47K SLC
ONES
ADDRESS (optional connection for panels
which support this feature)
6720wir4

Figure 8: M300MJ in Typical 2-Wire Initiating Device Circuit Configuration for Security Systems
(with Alarm vs. Short Capability)

From Panel
To Next
or Previous
SLC Device
SLC Device
Interface
Module SLC Communication Line
32 VDC Maximum
9 0 Twisted-pair is
8 1 recommended.
3.9K EOL IDC
7 TENS 2 Listed battery backup
6 3 switched DC
Resistor 5 4
(included) SLC
ONES
ADDRESS
power supply.
A2143-10 Optional Branch Circuit
To Next Interface Module
Module supervises supply
voltage and detector loop.
6720wir5

Figure 9: M302MJ in 2-Wire Conventional Detector Interface,


NFPA Style B Initiating Device Circuit

To Next From Panel


or Previous
SLC Device
IDC SLC Device
Interface
Module SLC Communication Line
32 VDC Maximum
Twisted-pair is
9 0 recommended.
3.9K EOL resistor 8 1
(included) required 7 TENS 2 Listed battery backup
at Terminals 8 and 9. 6 3 switched DC
A2143-10 5
ONES
4 power supply.
SLC ADDRESS

+ + Optional Branch Power Circuit


To Next Interface Module
Module supervises supply
voltage and detector IDC.
6720wir6

Figure 10: M302MJ in 2-Wire Conventional Detector Interface,


NFPA Style D Initiating Device Circuit

6 Accessories—300 Series Intelligent Modules


To Next From Panel
SLC Device or Previous
Relay SLC Device
Control
DC Power Module
Supply
Listed for Fire SLC Communication Line
Protection with 9 0 32 VDC Maximum
Battery Backup 8 1 Twisted-pair is
7 2 recommended.
6 3
5 4
SLC ADDRESS

6720wir7

Figure 11: M300RJ Relay Control Module Used to Disconnect a Power Supply

SLC Communication Line 32 VDC Maximum


Twisted-pair is recommended.
To Next
SLC Device From Panel
or Previous
Control
Module 24 VDC CircuitSLC Device
Do not loop wire
47K EOL NAC on Terminals 3 and 4.
Resistor 9 0 Break wire to provide
ELR-47K 8 1
supervision of connections.
7 TENS 2
6 3
5 4
24 VDC
SLC
ONES
ADDRESS Power
Supply
Power Supply:
UL Listed • Isolated, regulated,
EOL relay • To next control module of EOL relay. power-limited
shown • One relay required for each circuit. per NFPA 70.
energized. • Some control panels have the relay built in • Listed for fire protection
24 VDC Coil and do not require external wiring. with battery backup.
A77-716B 6724wir1

Figure 12: M300CJ in Typical Notification Appliance Circuit (NAC) Configuration,


NFPA Style Y

Accessories—300 Series Intelligent Modules 7


SLC Communication Line 32 VDC Maximum
Twisted-pair is recommended.
To Next
SLC Device From Panel
or Previous
Control SLC Device
EOL resistor
Module 24 VDC Circuit
is internal at Do not loop wire
Terminals 8 and 9. NAC
9 0 on Terminals 3 and 4.
8 1 Break wire to provide
7 TENS 2 supervision of connections.
6 3
5 4
24 VDC
SLC
ONES
ADDRESS Power
Supply
Power Supply:
UL Listed • Isolated, regulated,
EOL relay • To next control module of EOL relay. power-limited
shown • One relay required for each circuit. per NFPA 70.
energized. • Some control panels have the relay built in • Listed for fire protection
24 VDC Coil and do not require external wiring. with battery backup.
A77-716B 6724wir2

Figure 13: M300CJ in Typical Fault-Tolerant Notification Appliance Circuit Configuration,


NFPA Style Z

32 VDC maximum twisted-pair is recommended.


SLC Communication Line
To Next
SLC Device From Panel
or Previous
Control SLC Device
Module Audio Circuit
Do not loop wire
9 0 on Terminals 3 and 4.
47K EOL Break wire to ensure
Resistor NAC 8 1
7 2 supervision of connections.
ELR-47K TENS
6 3 Audio Amplifier
5 4 70.7 VRMS Maximum
ONES
SLC ADDRESS
Use only models AA-30,
AA-100, or AA-120.
Amplifier must provide
To Next wiring supervision per NFPA.
Speaker Switching Circuit: NFPA Style Y Control Module Supervision
Speakers must be listed for fire protection. Last module must return
6724wir3
Refer to Table 1 for maximum load. wires for supervision.

Figure 14: M300CJ in Typical Wiring for Speaker Supervision and Switching,
NFPA Style Y Notification Appliance Circuit

8 Accessories—300 Series Intelligent Modules


EOL resistor is internal at
Terminals 8 and 9. SLC Communication Line 32 VDC maximum twisted-pair is recommended.
To Next
SLC Device From Panel
Bypass Capacitors: A2143-20, or Previous
100 Microfarads, Control SLC Device
16 Volts, Non-Polarized, Module Audio Circuit
< 10 Micoamperes Leakage Do not loop wire
NAC on Terminals 3 and 4.
9
0
8 1 Break wire to ensure
7 TENS 2 supervision of connections.
6 3 Audio Amplifier
5 4
SLC
ONES
ADDRESS
70.7 VRMS Maximum
Use only models AA-30,
AA-100, or AA-120.
Amplifier must provide
To Next wiring supervision per NFPA.
Speaker Switching Circuit: NFPA Style Z Control Module Supervision
Speakers must be listed for fire protection. Last module must return
wires for supervision. 6724wir4
Refer to Table 1 for maximum load.

Figure 15: M300CJ in Typical Fault-Tolerant Wiring for Speaker Supervision and Switching,
NFPA Style Z Notification Appliance Circuit

Notes regarding audio amplifier in Figures 14 and 15 above:


1. Audio circuit wiring must be twisted-pair as a minimum.
2. When a 70.7 V audio amplifier is used, Terminals 1 and 2 are power-limited, while Terminals 3
through 9 are non-power-limited. In this case, the CB500 barrier is required. Otherwise, all terminal
wiring is power-limited. The CM500 includes a label indicating which terminals are non-power-limited.
This label must be placed adjacent to the nameplate label, which is on the module housing.

To Next From Panel


SLC Device or Previous
SLC Device

SLC Communication Line


32 VDC Maximum
Shielded twisted-pair
is recommended.

6724wir5

Figure 16: M300RJ Relay Module Wiring Diagram

Additional Notes:
1. Connect modules to listed compatible control panels only.
2. Module does not supervise controlled circuits.

Accessories—300 Series Intelligent Modules 9


Table 2: Ordering Information
Product Code Description
M300MJ Standard sized monitor module that supervises either a Class A (Style B) or
Class B (Style D) initiating device circuit
M301MJ Miniature monitor module that supervises a Class B (Style D) initiating device circuit
M302MJ Standard sized interface module that monitors and supervises compatible 2-wire,
24 volt conventional smoke detectors on a Class A (Style B) or Class B (Style D)
initiating device circuit
M300CJ Intelligent addressable control module for Class A (Style Z) or Class B (Style Y)
notification appliance circuit
M300RJ Intelligent addressable dual Form-C relay module
A2143-20 Capacitor, required for Class A (Style Z) operation of speakers
SMB500 Optional surface-mount backbox
CB500 Control module barrier—required by UL for separating power-limited and
non-power-limited wiring in the same junction box as M300CJ

10 Accessories—300 Series Intelligent Modules


S pecifications for M300MJ
Nominal Operating 15 to 32 VDC
Voltage
Maximum Current Draw 5.1 milliamperes (LED on)
Average Operating 400 microamperes (LED flashing)
Current
EOL Resistance 47K ohms
Temperature Range 0 to 49°C (32 to 120°F)
Humidity Range 10% to 93% non-condensing
Height 114.3 mm (4.5 in.)
Width 101.6 mm (4 in.)
Depth 31.75 mm (1.25 in.)
Backbox Dimensions 4 in. (square) x 2.125 in.

S pecifications for M301MJ


Nominal Operating 15 to 32 VDC
Voltage
Average Operating 375 microamperes maximum
Current
EOL Resistance 47K ohms
Temperature Range 0 to 49°C (32 to 120°F)
Humidity Range 10% to 93% non-condensing
Height 33.02 mm (1.3 in.)
Width 69.85 mm (2.75 in.)
Depth 12.70 mm (0.5 in.)
Wire Length 152.4 mm (6 in.) minimum

S pecifications for M302MJ


Nominal Operating 15 to 32 VDC
Voltage
Maximum Current Draw 5.1 milliamperes (LED on)
Average Operating 270 micoramperes (LED flashing)
Current
EOL Resistance 3.9K ohms
DC Input Voltage 18 to 28 volts power-limited (applied to Terminals 3 and 4 for 2-wire detector
operating power)
Ripple Input Voltage 0.1 VRMS maximum
Maximum Input Current 90 milliamperes per module
Temperature Range 0 to 49°C (32 to 120°F)
Humidity Range 10% to 93% non-condensing
Height 114.3 mm (4.5 in.)
Width 101.6 mm (4 in.)
Depth 31.75 mm (1.25 in.)
Backbox Dimensions 4 in. (square) x 2.125 in.

Accessories—300 Series Intelligent Modules 11


S pecifications for M300CJ
Nominal Operating 15 to 32 VDC
Voltage
Maximum Current Draw 5.1 milliamperes (LED on)
Average Operating 390 microamperes (LED flashing)
Current
External Supply Voltage Maximum 80 volts (RMS or DC) applied to Terminals 3 and 4 for the notification
appliance circuit
Drain on External Supply 2 milliamperes maximum (using internal EOL relay)
EOL Resistance 47K ohms
Temperature Range 0 to 49°C (32 to 120°F)
Humidity Range 10% to 93% non-condensing
Height 114.3 mm (4.5 in.)
Width 101.6 mm (4 in.)
Depth 31.75 mm (1.25 in.)

S pecifications for M300RJ


Nominal Operating 15 to 32 VDC
Voltage
Maximum Current Draw 5.1 milliamperes (LED on)
Average Operating 270 microamperes (LED flashing)
Current
EOL Resistance Not used
Temperature Range 0 to 49°C (32 to 120°F)
Humidity Range 10% to 93% non-condensing
Height 114.3 mm (4.5 in.)
Width 101.6 mm (4 in.)
Depth 31.75 mm (1.25 in.)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond
these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.

Controls Group FAN 447


507 E. Michigan Street Fire Management Sales Resource Manual
P.O. Box 423 Printed in U.S.A.
Milwaukee, WI 53201 www.johnsoncontrols.com

12 Accessories—300 Series Intelligent Modules