B 4470767 - Modulo Control
B 4470767 - Modulo Control
Accessories Section
Product Bulletin
Issue Date 0600
6724mod2
Installation
The M300MJ modules mount directly to a
standard 101.6 mm (4 in.) square, 53.975 mm
(2.125 in.) deep electrical backbox. They may also
mount to the SMB500 surface-mount box.
Mounting hardware and installation instructions
are provided with each module. All wiring must Yellow Violet Red Black
conform to applicable local codes, ordinances, and
regulations. These modules are intended for
power-limited wiring only.
6720m101
Operation
Each 300 Series module uses one of Figure 2: M301MJ Module
159 available module addresses on an SLC that
supports the FlashScan communication protocol. Installation
It responds to regular polls from the control panel The M301MJ is intended for wiring and mounting
and reports its type and the status without rigid connections inside a standard
(open/normal/short) of its initiating device circuit. electrical box. All wiring must conform to
A flashing LED indicates that the module is in applicable local codes, ordinances, and
communication with the control panel. The LED regulations.
latches steady on alarm (subject to current
limitations on the SLC).
Applications
The M300CJ switches 24 VDC audible/visual
power, high-level 25 VRMS or 70 VRMS amplified
audio (speakers), or to control telephone devices.
Isolated Quadrant
Using the CB500
(see below)
6724mt2 6720mt2
CB500
6724mt1 6720mt1
Violet Yellow
IDC
6720wir1
To Next
SLC Device From Panel
or Previous
Initiating Device Circuit (IDC) Monitor SLC Device
NFPA Style B, Power Limited: Module
230 Micoramperes Maximum @ SLC Communication Line
12 VDC Maximum 9 0 32 VDC Maximum
8 1 Shielded/twisted-pair
47K EOL 7 TENS 2 is recommended.
Resistor 6 3
5 4 SLC Communication Loss
ELR-47K SLC
ONES
ADDRESS (optional connection for panels
which support this feature)
6720wir2
Figure 6: M300MJ in Typical 2-Wire Initiating Device Circuit Configuration, NFPA Style B
To Next
SLC Device From Panel
or Previous
Monitor SLC Device
Module
Initiating Device Circuit (IDC) SLC Communication Line
9 0
32 VDC Maximum
8 1
Shielded/twisted-pair
is recommended.
EOL resistor 7 TENS 2
is internal at 6 3
Terminals 8 and 9. 5 4 SLC Communication Loss
ONES
SLC ADDRESS (optional connection for panels
which support this feature)
6720wir3
Figure 8: M300MJ in Typical 2-Wire Initiating Device Circuit Configuration for Security Systems
(with Alarm vs. Short Capability)
From Panel
To Next
or Previous
SLC Device
SLC Device
Interface
Module SLC Communication Line
32 VDC Maximum
9 0 Twisted-pair is
8 1 recommended.
3.9K EOL IDC
7 TENS 2 Listed battery backup
6 3 switched DC
Resistor 5 4
(included) SLC
ONES
ADDRESS
power supply.
A2143-10 Optional Branch Circuit
To Next Interface Module
Module supervises supply
voltage and detector loop.
6720wir5
6720wir7
Figure 11: M300RJ Relay Control Module Used to Disconnect a Power Supply
Figure 14: M300CJ in Typical Wiring for Speaker Supervision and Switching,
NFPA Style Y Notification Appliance Circuit
Figure 15: M300CJ in Typical Fault-Tolerant Wiring for Speaker Supervision and Switching,
NFPA Style Z Notification Appliance Circuit
6724wir5
Additional Notes:
1. Connect modules to listed compatible control panels only.
2. Module does not supervise controlled circuits.