Comparative Study of Optimization Methods For Optimal Coordination of Directional Overcurrent Relays With Distributed Generators
Comparative Study of Optimization Methods For Optimal Coordination of Directional Overcurrent Relays With Distributed Generators
Corresponding Author:
Zineb El Idrissi
Laboratory of Energy and Electric Systems, National School of Electricity and Mechanics
El Jadida Road, km 7, Casablanca, Morocco
Email: [email protected]
1. INTRODUCTION
The main role of protection relays is to detect and eliminate faults as quickly as possible by
transmitting an opening command to the related circuit breaker. This circuit breaker isolates the faulty part of
the network to ensure that the electrical equipment is not affected by the fault current [1]. The directional
overcurrent relay (DOCR) is the most widely used type of relay in the coordination of protection relays due
to their simplicity of application and their technical and economic characteristics [2]. The coordination of
DOCRs protection has been considered a necessity for distribution networks, as it quickly isolates the faulty
area, keeps the system safe and overcomes current faults so that the relays are reliable, flexible and
selective [3]. In a properly coordinated system, the main relay must first function on overcurrent faults within
a predefined time. After this predetermined time, known as the coordination time interval (CTI), the
emergency relay must operate to isolate the default if the main one failed to trip [4]. Relay coordination is
usually based on the evaluation of both fault currents and power flow. To optimize relay coordination, two
important parameters are considered; relay settings which include the time dial setting (TDS) and the plug
setting (PS) [5]. The main objective of relay coordination is to select its optimal parameters, taking into
account the limits of these parameters, its characteristic curves and especially the constraints of
coordination [6]. Coordination of protection relays can be a complicated problem in interconnected networks
because each main relay can have more than one emergency relay and a main relay can also be the
emergency relay of another relay, whereas coordination in radial networks is very simple because each relay
is an emergency relay of downstream relays [1]. The coordination of DOCRs in an interconnected
distribution network is a constrained optimization issue, which reflects the difficulty of this problem.
The Kyoto protocol is an international agreement, which came into force in 2005, for developing
countries. It aims to reduce the emission of greenhouse gases, with an emphasis on the increasing use of the
renewable energy production [7]. In this regard, the integration of distributed generators (DGs) using
renewable energy has become a global concern, given the decreasing costs of power transmission and large
power plants construction, the reduction of energy losses, and the decreasing demand for electrical energy on
the power grid [8]. Despite its many advantages, these generators have several impacts on electrical network
parameters [9], namely the impact on power flow and the modification of fault current values [10] that can
affect the operation of electrical network protection schemes. This influence can result in reduced system
reliability, increased corrective maintenance costs and poor coordination between existing protective relays
in the network [11]. The loss of coordination can lead to unnecessary disconnection of the healthy part of the
network, damage to electrical equipment, and larger fault zones [12]. To solve this problem, it is necessary to
adjust PS and TDS of the relays considering the existence of the DGs, in order to have a new optimal
coordination for the proper operation of the protection of the electrical system.
Many optimization approaches are used to determine the most appropriate coordination of DOCRs,
including linear programming (LP), two-phase simplex and double simplex methods, nonlinear programming
(NLP) and meta-heuristics. In LP, the PS parameter is assumed to be a fixed value that was calculated using
the data of maximum load currents and the fault current, which is why these methods are weakened [4].
Recently, the meta-heuristic methods used in the coordination of protective relays, show faster and more
reliable results. These methods include water cycle algorithm (WCA) [4], adaptive modified firefly algorithm
(AMFA) [3], improved firefly algorithm (IFA) [2], differential evolution algorithm (DE) [13], symbiotic
organism search (SOS) [14], genetic algorithm (GA) [7], particle swarm optimization (PSO) [15],
informative differential evolution algorithm (IDE) [16], ant colony optimization (ACO) [17], modified
particle swarm optimization (MPSO) [18] and harmony search algorithm (HSA) [19]. A thorough study of
the GA, PSO, DE, HSA, and simulated annealing (SA) optimization techniques that are implemented to
obtain the best DOCR coordination is presented in [20]. The performance of these methods has been
successfully verified for solving this problem.
This article compares optimization methods for determining the optimal parameters of DOCRs with
DGs in interconnected distribution networks. The problem has been presented in the second section, the
optimization methods PSO, GA and DE are detailed in the third section. The obtained results and discussion
are given in the fourth section, and the conclusion is provided in the fifth one.
𝐼𝑝
𝑃𝑆 = (2)
𝐶𝑇𝑅
The coordination constraint should be satisfied for all primary/backup relay pairs (P/B). This
constraint is indicated in (4). The CTI value depends on the type of relay (digital or electromechanical) and it
varies between 0.2 and 0.5 s. The parameters tp and tb are respectively the running time of the main and
emergency relays [23]. The reliability constraint is presented in (5), the relay must operate within a time
margin, it must respond in a minimum time tmin and it must not exceed a maximum time tmax, the relay
operating time generally varies between 0.1 and 4 s [21].
𝑡𝑏 − 𝑡𝑝 ≥ 𝐶𝑇𝐼 (4)
The sensitivity constraints are presented in (6) and (7). The parameters TDS and PS must respect the
minimum values TDSmin and PSmin and the maximum values TDSmax and PSmax. The limits of TDS are
generally 0.1 and 1.1 s [24]. The limits of PS are calculated using (8) and (9), where ILmax is the maximal load
current and IFmin is the minimal fault current [5].
(1.25×𝐼𝐿𝑚𝑎𝑥 )
𝑃𝑆𝑚𝑖𝑛 = 𝑚𝑎𝑥 {0.5, } (8)
𝐶𝑇𝑅
2
( ×𝐼𝐹𝑚𝑖𝑛 )
3
𝑃𝑆𝑚𝑎𝑥 = 𝑚𝑖𝑛 {2.5, } (9)
𝐶𝑇𝑅
𝑥 = {𝑥1 ; x2 ; . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ; x𝐷 } (10)
each iteration k. Where c1 is the personal learning coefficient, c2 is the global learning coefficient and w is the
inertia weight.
with a1, a2 and a3 ϵ {1, 2,…, N} are three mutually different random indices and F is the mutation factor that
regulates the differential variation amplification ( x a 2 , jk − x a3 , jk ) . A crossover is inserted to increase the
variety of perturbed parameter vectors to obtain the test vector. Crossover execution on the test solution is
performed using the crossover rate (CR) and the random index randk where randk equals randi(D), as
expressed in (14) [27], the Selection of the trial solution is made using system at (15), with TFi is the trial
fitness.
and 24 protection relays (R1, R2, . . ., R24). They have 44 pairs of P/B relays between them. The CTR is 500/1
for all relays.
Table 1 gives the optimal adjustments of the 24 protection relays, which are PS and TDS, obtained
by PSO, GA and DE optimization methods, while Table 2 shows the values for the running time of the main
and the emergency relays tp and tb, as well as the coordination time interval corresponding to 44 P/B relay
combinations for this optimization approach. The last two rows of Table 1 show the objective function (OF)
and the time of convergence for each method. The objective function is the total of the running times of all
main and emergency relays with the obtained optimal settings. The CTI between the main and emergency
relay running times of the 44 pairs of P/B relays for the different methods is illustrated in Figure 2.
Table 2. CTI values and running times of primary and emergency relays for a 9-bus distribution network
Relay pairs Rp/ RB PSO GA DE
tp tb CTI tp tb CTI tp tb CTI
1 1/15 0.3582 0.5582 0.2 0.4072 0.6150 0.2077 0.2809 0.4898 0.2089
2 1/17 0.3582 0.6812 0.3230 0.4072 0.8461 0.4388 0.2809 0.6372 0.3563
3 2/4 0.6047 0.8057 0.2010 0.7356 1.0580 0.3224 0.5739 0.7912 0.2173
4 3/1 0.4753 0.6755 0.2001 0.7485 0.9895 0.2410 0.4397 0.6853 0.2456
5 4/6 0.5491 0.7501 0.2010 0.7702 0.9962 0.2260 0.5757 0.7976 0.2220
6 5/3 0.4379 0.6437 0.2058 0.7712 0.9764 0.2052 0.4353 0.6669 0.2317
7 6/8 0.2992 0.5012 0.2020 0.5273 0.7574 0.2300 0.3280 0.5498 0.2218
8 6/23 0.2992 0.6724 0.3732 0.5273 0.8760 0.3487 0.3280 0.6882 0.3602
9 7/5 0.3235 0.5235 0.2 0.5910 0.9010 0.3100 0.3075 0.5087 0.2012
10 7/23 0.3235 0.6724 0.3489 0.5910 0.8760 0.2851 0.3075 0.6882 0.3807
11 8/10 0.4286 0.6305 0.2020 0.6482 0.8614 0.2131 0.4695 0.6911 0.2216
12 9/7 0.5373 0.7373 0.2 0.7853 1.0867 0.3014 0.5686 0.7886 0.220
13 10/12 0.4383 1.0937 0.6554 0.6632 0.9086 0.2454 0.5303 0.9454 0.4151
14 11/9 0.6091 0.8091 0.2 0.6555 1.0792 0.4236 0.5956 0.8135 0.2179
15 12/14 0.6834 0.8834 0.2 0.5677 0.7868 0.2190 0.4579 0.6626 0.2047
16 12/21 0.6834 0.8834 0.2 0.5677 0.7837 0.2159 0.4579 0.7236 0.2656
17 13/11 0.3875 0.6480 0.2 0.4787 0.6948 0.2161 0.3828 0.6320 0.2491
18 13/21 0.3875 0.8273 0.2605 0.4787 0.7368 0.2581 0.3828 0.6712 0.2883
19 14/16 0.5524 0.8160 0.4397 0.5240 0.7387 0.2147 0.4401 0.6513 0.2112
20 14/19 0.5524 0.7600 0.2636 0.5240 0.8924 0.3684 0.4401 0.7391 0.2990
21 15/13 0.3717 0.5717 0.2076 0.4070 0.6514 0.2444 0.3200 0.5236 0.2037
22 15/19 0.3717 0.5717 0.2 0.4070 0.6875 0.2805 0.3200 0.5694 0.2494
23 16/2 0.4657 0.6657 0.2 0.4601 0.8018 0.3417 0.4039 0.6263 0.2224
24 16/17 0.4657 0.6657 0.2 0.4601 0.8288 0.3687 0.4039 0.6245 0.2206
25 17/20 0.2697 0.6712 0.4015 0.3572 0.7226 0.3653 0.2733 0.5519 0.2785
26 17/22 0.2697 0.5752 0.3056 0.3572 0.6199 0.2626 0.2733 0.5828 0.3094
27 17/24 0.2697 0.6569 0.3872 0.3572 0.6623 0.3051 0.2733 0.6537 0.3803
28 18/2 0.4068 1.4872 1.0804 0.5244 1.5791 1.0548 0.4206 1.2511 0.8305
29 18/15 0.4068 1.0564 0.6497 0.5244 1.1834 0.6591 0.4206 0.9772 0.5566
30 19/18 0.2751 0.5429 0.2678 0.3439 0.7016 0.3577 0.2849 0.5673 0.2825
31 19/22 0.2751 0.5425 0.2673 0.3439 0.5843 0.2404 0.2849 0.5491 0.2643
32 19/24 0.2751 0.6150 0.3399 0.3439 0.6195 0.2756 0.2849 0.6119 0.3270
33 20/13 0.4207 1.6686 1.2480 0.4846 1.2995 0.8149 0.3699 1.0655 0.6957
34 20/16 0.4207 1.6483 1.2276 0.4846 1.2446 0.7600 0.3699 1.1062 0.7363
35 21/18 0.3693 0.5757 0.2065 0.3399 0.7445 0.4046 0.2780 0.6031 0.3251
36 21/20 0.3693 0.6712 0.3019 0.3399 0.7226 0.3827 0.2780 0.5519 0.2739
37 21/24 0.3693 0.6569 0.2876 0.3399 0.6623 0.3225 0.2780 0.6537 0.3757
38 22/11 0.4065 1.3627 0.9562 0.4370 1.3657 0.9288 0.4102 1.2669 0.8567
39 22/14 0.4065 2.0219 1.6154 0.4370 1.4882 1.0512 0.4102 1.2626 0.8524
40 23/18 0.2601 0.5307 0.2706 0.3391 0.6857 0.3466 0.2663 0.5541 0.2878
41 23/20 0.2601 0.6110 0.3509 0.3391 0.6683 0.3292 0.2663 0.5103 0.2440
42 23/22 0.2601 0.5303 0.2702 0.3391 0.5711 0.2320 0.2663 0.5367 0.2704
43 24/5 0.5238 1.1155 0.5918 0.5267 1.6596 1.1330 0.5210 0.9389 0.4179
44 24/8 0.5238 0.9281 0.4043 0.5267 1.3947 0.8681 0.5210 1.0252 0.5042
From Table 1, it is clear that the three methods give optimal values of TDS and PS that respect the
sensitivity constraint. However, it is observed that the optimization method DE has the lowest values of the
OF and the convergence time compared to the other methods. And from Table 2, it is noticed that the
reliability constraint is well verified since the operating time is within the limits indicated as well as the
coordination constraint is respected for the 44 pairs of P/B relays. It is also noticed from this table that the
values of CTI for the DE method are the smallest values compared to the other methods. Similarly, from
Figure 2, it can be seen that the values of CTI found by DE belong to the interval [0,1] whereas the values of
CTI of the methods PSO and GA belong to the interval [0,2], which explains why the method DE gives the
best result compared to the two other methods.
Table 4. CTI values and running times of primary and emergency relays for a 15-bus distribution network
(Continue…)
Relay pairs Rp/ RB PSO GA DE
tp tb CTI tp tb CTI tp tb CTI
1 1/6 0.5230 0.7251 0.2020 0.6896 1.0616 0.3719 0.6854 0.8992 0.2138
2 2/4 1.0011 1.2013 0.2002 0.5813 0.8453 0.2640 0.4072 0.9223 0.5151
3 2/16 1.0011 1.2011 0.2 0.5813 1.0278 0.4465 0.4072 1.2442 0.8370
4 3/1 0.6388 0.8396 0.20098 0.6177 0.9222 0.3045 0.6086 0.9167 0.3081
5 3/13 0.6388 0.9983 0.3595 0.6177 0.8820 0.2643 0.6086 0.8941 0.2855
6 4/7 0.6161 0.9330 0.3169 0.3703 0.8772 0.5068 0.5146 0.8703 0.3557
7 4/12 0.6161 0.8161 0.2 0.3703 0.8875 0.5172 0.5146 0.7900 0.2754
8 4/20 0.6161 0.9359 0.3198 0.3703 0.8926 0.5223 0.5146 0.8381 0.3235
9 5/2 0.5376 1.5050 0.9674 0.7076 1.0275 0.3199 0.5777 0.9094 0.3317
10 6/8 0.5025 0.7025 0.2 0.7206 0.9325 0.2119 0.5857 0.8967 0.3110
11 6/10 0.5025 0.9956 0.4931 0.7206 0.9406 0.2120 0.5857 0.9450 0.3593
12 7/5 0.7717 0.9717 0.2 0.7257 1.0133 0.2875 0.7096 0.9157 0.2061
13 7/10 0.7717 1.0593 0.2876 0.7257 0.9791 0.2533 0.7096 0.9838 0.2742
14 8/3 0.4051 0.9050 0.4998 0.5841 0.8911 0.3070 0.4878 0.8129 0.3251
15 8/12 0.4051 0.7971 0.3919 0.5841 0.8706 0.2865 0.4878 0.7678 0.2801
16 8/20 0.4051 0.9072 0.5020 0.5841 0.8601 0.2760 0.4878 0.8201 0.3324
17 9/5 0.5145 1.0450 0.5306 0.6448 1.0528 0.4080 0.5721 0.9648 0.3927
18 9/8 0.5145 0.7878 0.2734 0.6448 1.0226 0.3778 0.5721 1.0234 0.4513
19 10/14 0.6143 0.8143 0.2 0.6690 0.9868 0.3178 0.6720 0.9424 0.2704
Table 4. CTI values and running times of primary and emergency relays for a 15-bus distribution network
Relay pairs Rp/ RB PSO GA DE
tp tb CTI tp tb CTI tp tb CTI
20 11/3 0.4659 0.9244 0.4586 0.5951 0.9115 0.3164 0.5861 0.8269 0.2409
21 11/7 0.4659 0.9335 0.4677 0.5951 0.8776 0.2826 0.5861 0.8708 0.2848
22 11/20 0.4659 0.9368 0.4709 0.5951 0.8936 0.2985 0.5861 0.8386 0.2526
23 12/13 0.5312 0.8231 0.2919 0.6181 0.9177 0.2995 0.4788 0.7052 0.2264
24 12/24 0.5312 1.4513 0.9200 0.6181 0.9596 0.3414 0.4788 0.8007 0.3219
25 13/9 0.5473 0.7582 0.2109 0.7023 0.9435 0.2412 0.4850 0.7863 0.3013
26 14/11 0.4062 0.7856 0.3795 0.5889 0.9557 0.3668 0.3916 0.9485 0.5569
27 14/24 0.4062 1.5649 1.1588 0.5889 1.0589 0.4700 0.3916 0.8861 0.4945
28 15/1 0.5019 1.1142 0.6123 0.5691 1.0689 0.4998 0.3860 1.0627 0.6768
29 15/4 0.5019 1.1665 0.6645 0.5691 0.8125 0.2435 0.3860 0.8999 0.5140
30 16/18 0.8497 1.3972 0.5476 0.7690 1.2453 0.4763 0.6924 0.9831 0.2908
31 16/26 0.8497 1.0558 0.2061 0.7690 1.0392 0.2702 0.6924 1.0041 0.3117
32 17/15 0.7617 1.2445 0.4828 0.7895 1.4993 0.7097 0.7333 1.1457 0.4124
33 17/26 0.7617 1.1715 0.4098 0.7895 1.1400 0.3505 0.7333 1.1345 0.4012
34 18/19 0.5153 0.7250 0.2097 0.4685 0.9189 0.4504 0.3548 0.8297 0.4749
35 18/22 0.5153 0.7222 0.2068 0.4685 0.7987 0.3303 0.3548 0.8137 0.4589
36 18/30 0.5153 0.7201 0.2048 0.4685 0.9072 0.4388 0.3548 0.7690 0.4141
37 19/3 0.4845 0.9552 0.4708 0.6449 0.9438 0.2989 0.5873 0.8489 0.2616
38 19/7 0.4845 0.9611 0.4766 0.6449 0.9035 0.2586 0.5873 0.8987 0.3114
39 19/12 0.4845 0.8479 0.3634 0.6449 0.9154 0.2705 0.5873 0.8276 0.2403
40 20/17 0.4394 0.7739 0.3346 0.3802 0.7974 0.4172 0.4709 0.7457 0.2748
41 20/22 0.4394 0.6395 0.2 0.3802 0.7305 0.3503 0.4709 0.7419 0.2711
42 20/30 0.4394 0.6443 0.2049 0.3802 0.8271 0.4469 0.4709 0.7019 0.2310
43 21/17 0.5186 0.8968 0.3781 0.6113 0.8713 0.2600 0.4974 0.8706 0.3732
44 21/19 0.5186 0.7236 0.2050 0.6113 0.9173 0.3060 0.4974 0.8283 0.3309
45 21/33 0.5186 0.7189 0.2003 0.6113 0.9060 0.2947 0.4974 0.7679 0.2705
46 22/23 0.6223 2.1725 1.5502 0.7157 1.7221 1.0064 0.7265 1.1746 0.4481
47 22/34 0.6223 1.6425 1.0202 0.7157 1.0922 0.3764 0.7265 0.9933 0.2668
48 23/11 0.6631 0.8675 0.2044 0.7619 1.0426 0.2806 0.5196 1.0367 0.5172
49 23/13 0.6631 1.0787 0.4156 0.7619 1.0723 0.3104 0.5196 0.8966 0.3770
50 24/21 1.2617 1.7479 0.4862 0.8035 1.6088 0.8052 0.6674 1.3393 0.6718
51 24/34 1.2617 1.4622 0.2006 0.8035 1.0261 0.2226 0.6674 0.9320 0.2646
52 25/15 0.7649 0.9650 0.2001 0.8834 1.1359 0.2525 0.6013 0.8271 0.2258
53 25/18 0.7649 1.2317 0.4668 0.8834 1.1018 0.2184 0.6013 0.8631 0.2618
54 26/28 0.6922 0.8922 0.2 0.7068 1.0879 0.3811 0.6232 0.9171 0.2939
55 26/36 0.6922 1.1699 0.4777 0.7068 1.1839 0.4771 0.6232 0.8351 0.2119
56 27/25 0.7730 1.0415 0.2684 0.7513 1.1373 0.3861 0.5552 0.8355 0.2803
57 27/36 0.7730 1.0747 0.3017 0.7513 1.1180 0.3667 0.5552 0.7876 0.2324
58 28/29 0.6407 1.0107 0.3700 0.6982 1.0418 0.3436 0.6421 0.8758 0.2337
59 28/32 0.6407 1.2344 0.5936 0.6982 1.0358 0.3376 0.6421 1.0207 0.3785
60 29/17 0.4327 0.7702 0.3375 0.5109 0.7950 0.2841 0.4240 0.7419 0.3179
61 29/19 0.4327 0.6333 0.2006 0.5109 0.8176 0.3068 0.4240 0.7406 0.3166
62 29/22 0.4327 0.6369 0.2042 0.5109 0.7283 0.2174 0.4240 0.7396 0.3157
63 30/27 0.6532 1.2775 0.6243 0.8366 1.0994 0.2628 0.7099 1.0756 0.3657
64 30/32 0.6532 1.6800 1.0267 0.8366 1.2936 0.4570 0.7099 1.2639 0.5540
65 32/27 0.9550 1.1584 0.2033 0.8073 1.0246 0.2173 0.7196 0.9372 0.2176
66 31/29 0.9550 1.3655 0.4105 0.8073 1.3058 0.4985 0.7196 1.1050 0.3854
67 32/33 0.9764 1.7972 0.8208 0.8643 1.4378 0.5735 0.8565 1.2067 0.3501
68 32/42 0.9764 1.5160 0.5395 0.8643 1.3310 0.4668 0.8565 1.2093 0.3528
69 33/21 1.0322 1.2324 0.2002 0.9533 1.2491 0.2958 0.6543 1.0313 0.3769
70 33/23 1.0322 1.3133 0.2811 0.9533 1.2642 0.3109 0.6543 0.8621 0.2078
71 34/31 0.9301 1.4912 0.5611 0.7803 1.2875 0.5072 0.7053 1.0342 0.3289
72 34/42 0.9301 1.2242 0.2941 0.7803 1.0772 0.2969 0.7053 0.9166 0.2113
73 35/25 0.6387 1.1081 0.4694 0.8158 1.1945 0.3786 0.6656 0.8934 0.2277
74 35/28 0.6387 0.8904 0.2517 0.8158 1.0847 0.2688 0.6656 0.9150 0.2494
75 36/38 0.6371 1.1541 0.5169 0.7608 1.0792 0.3184 0.5323 0.9353 0.4029
76 37/35 0.5775 0.7776 0.2001 0.6144 0.9168 0.3024 0.5166 0.7484 0.2318
77 38/40 1.0442 1.2689 0.2248 1.0054 1.3304 0.3251 0.8711 1.1468 0.2757
78 39/37 0.7545 1.0167 0.2622 0.8100 1.2044 0.3944 0.5826 0.8183 0.2357
79 40/41 0.6165 1.7335 1.1170 0.8570 1.0630 0.2060 0.7265 0.9405 0.2140
80 41/31 1.5237 1.7237 0.2 0.9630 1.5022 0.5392 0.8555 1.1556 0.3001
81 41/33 1.5237 1.7267 0.2030 0.9630 1.3986 0.4357 0.8555 1.1531 0.29756
82 42/39 0.7104 0.9140 0.2036 0.6275 0.9765 0.3490 0.4800 0.7453 0.26530
5. CONCLUSION
This paper proposes three different optimization methods, PSO, GA and DE dealing with the
problem of coordination of directional overcurrent relays. These techniques are applied on two distribution
networks with 9 and 15 buses integrating distributed generators in order to determine the most efficient
method to solve this problem with the integration of DGs, the objective function and the time of convergence
obtained by each method are compared between them. The comparative analysis shows that the differential
evolution gives optimal values of the objective function and a shorter convergence time compared to the
other methods for both distribution networks. Even more, the CTI values obtained by DE are found to be the
most optimal, which explains the choice of DE as the method that offers the most satisfactory results among
the methods investigated in this work. Therefore, DE can be regarded as the most efficient method to reach
the best solution respecting the constraint of coordination between relays in the presence of DGs.
REFERENCES
[1] D. Solati Alkaran, M. R. Vatani, M. J. Sanjari, G. B. Gharehpetian, and M. S. Naderi, “Optimal overcurrent relay coordination in
interconnected networks by using fuzzy-based GA method,” IEEE Transactions on Smart Grid, vol. 9, no. 4, pp. 3091–3101, 2018,
doi: 10.1109/TSG.2016.2626393.
[2] T. Khurshaid, A. Wadood, S. Gholami Farkoush, C. H. Kim, J. Yu, and S. B. Rhee, “Improved firefly algorithm for the optimal
coordination of directional overcurrent relays,” IEEE Access, vol. 7, pp. 78503–78514, 2019, doi: 10.1109/ACCESS.2019.2922426.
[3] A. Tjahjono et al., “Adaptive modified firefly algorithm for optimal coordination of overcurrent relays,” IET Generation,
Transmission and Distribution, vol. 11, no. 10, pp. 2575–2585, 2017, doi: 10.1049/iet-gtd.2016.1563.
[4] N. El Naily, S. M. Saad, M. M. El Misslati, and F. A. Mohamed, “Optimal protection coordination for IEC microgrid Benchmark
using water cycle algorithm,” 2019 10th International Renewable Energy Congress, IREC 2019, 2019, doi:
10.1109/IREC.2019.8754511.
[5] P. P. Bedekar and S. R. Bhide, “Optimum coordination of directional overcurrent relays using the hybrid GA-NLP approach,” IEEE
Transactions on Power Delivery, vol. 26, no. 1, pp. 109–119, 2011, doi: 10.1109/TPWRD.2010.2080289.
[6] M. Thakur and A. Kumar, “Optimal coordination of directional over current relays using a modified real coded genetic algorithm: A
comparative study,” International Journal of Electrical Power and Energy Systems, vol. 82, pp. 484–495, 2016, doi:
10.1016/j.ijepes.2016.03.036.
[7] R. S. F. Ferraz, R. S. F. Ferraz, R. C. D. De Lima, L. G. R. Tonini, A. C. Rueda-Medina, and O. E. Batista, “Genetic optimization-
based overcurrent relay coordination in a feeder with high distributed generation integration,” 2019 IEEE PES Conference on
Innovative Smart Grid Technologies, ISGT Latin America 2019, 2019, doi: 10.1109/ISGT-LA.2019.8894961.
[8] T. Haidi, B. Cheddadi, F. El Mariami, Z. El Idrissi, and A. Tarrak, “Wind energy development in Morocco: Evolution and impacts,”
International Journal of Electrical and Computer Engineering, vol. 11, no. 4, pp. 2811–2819, 2021,
doi: 10.11591/ijece.v11i4.pp2811-2819.
[9] F. D. A. Kahar, I. Musirin, M. F. M. Nazer, S. Jelani, and M. H. Mansor, “Index-based transmission for distributed generation in
voltage stability and loss control incorporating optimization technique,” IAES International Journal of Artificial Intelligence, vol. 9,
no. 2, pp. 244–251, 2020, doi: 10.11591/ijai.v9.i2.pp244-251.
[10] Z. El Idrissi, F. Elmariami, T. Haidi, A. Belfqih, and J. Boukherouaa, “Analysis of the impacts of decentralized production on
distribution grids,” International Journal of Advanced Engineering Research and Science, vol. 6, no. 4, pp. 93–97, 2019,
doi: 10.22161/ijaers.6.4.11.
[11] N. K. Choudhary, S. R. Mohanty, and R. K. Singh, “Impact of distributed generator controllers on the coordination of overcurrent
relays in microgrid,” Turkish Journal of Electrical Engineering and Computer Sciences, vol. 25, no. 4, pp. 2674–2685, 2017,
doi: 10.3906/elk-1603-197.
[12] M. Bakhshipour, F. Namdari, and N. Bahador, “New hybrid non-dominated sorting differential evolutionary algorithm,” Bulletin of
Electrical Engineering and Informatics, vol. 5, no. 2, pp. 230–241, 2016, doi: 10.11591/eei.v5i2.533.
[13] M. Y. Shih, A. Conde Enríquez, T. Y. Hsiao, and L. M. Torres Treviño, “Enhanced differential evolution algorithm for coordination
of directional overcurrent relays,” Electric Power Systems Research, vol. 143, pp. 365–375, 2017, doi: 10.1016/j.epsr.2016.09.011.
[14] D. Saha, A. Datta, and P. Das, “Optimal coordination of directional over current relays in power systems using symbiotic organism
search optimisation technique,” IET Generation, Transmission and Distribution, vol. 10, no. 11, pp. 2681–2688, 2016,
doi: 10.1049/iet-gtd.2015.0961.
[15] L. Bougouffa and A. Chaghi, “Application of PSO for optimal coordination of directional over-current relays in distribution system
with distributed renewable energy sources,” International Journal of Advances in Applied Sciences, vol. 10, no. 2, p. 188, 2021,
doi: 10.11591/ijaas.v10.i2.pp188-192.
[16] M. Singh, B. K. Panigrahi, A. R. Abhyankar, and S. Das, “Optimal coordination of directional over-current relays using informative
differential evolution algorithm,” Journal of Computational Science, vol. 5, no. 2, pp. 269–276, 2014,
doi: 10.1016/j.jocs.2013.05.010.
[17] M. Y. Shih, C. A. Castillo Salazar, and A. Conde Enríquez, “Adaptive directional overcurrent relay coordination using ant colony
optimisation,” IET Generation, Transmission and Distribution, vol. 9, no. 14, pp. 2040–2049, 2015, doi: 10.1049/iet-gtd.2015.0394.
[18] A. I. Atteya, A. M. E. Zonkoly, and H. A. Ashour, “Optimal relay coordination of an adaptive protection scheme using modified PSO
algorithm,” 2017 19th International Middle-East Power Systems Conference, MEPCON 2017 - Proceedings, vol. 2018-February,
pp. 689–694, 2018, doi: 10.1109/MEPCON.2017.8301256.
[19] V. N. Rajput and K. S. Pandya, “Coordination of directional overcurrent relays in the interconnected power systems using effective
tuning of harmony search algorithm,” Sustainable Computing: Informatics and Systems, vol. 15, pp. 1–15, 2017,
doi: 10.1016/j.suscom.2017.05.002.
[20] M. N. Alam, B. Das, and V. Pant, “A comparative study of metaheuristic optimization approaches for directional overcurrent relays
coordination,” Electric Power Systems Research, vol. 128, pp. 39–52, 2015, doi: 10.1016/j.epsr.2015.06.018.
[21] A. A. Kalage and N. D. Ghawghawe, “Optimum coordination of directional overcurrent relays using modified adaptive teaching
learning based optimization algorithm,” Intelligent Industrial Systems, vol. 2, no. 1, pp. 55–71, 2016, doi: 10.1007/s40903-016-0038-
9.
[22] Z. El Idrissi, F. El Mariami, A. Belfqih, and T. Haidi, “Impact of distributed power generation on protection coordination in
distribution network,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 23, no. 3, pp. 1271–1280, 2021,
doi: 10.11591/ijeecs.v23.i3.pp1271-1280.
[23] S. Abeid and Yanting Hu, “Over current relays coordination optimisation methods in distribution systems for microgrids: a review,”
in 15th International Conference on Developments in Power System Protection (DPSP 2020), 2020, vol. 1999,
BIOGRAPHIES OF AUTHORS