Vol.2C Technical Specifications Distribution
Vol.2C Technical Specifications Distribution
Project - AKTP
Tender Documents
ZETDCAKTP001/2
ZETDC Tender No.______________________
Table of Contents
C6 – SUBSTATIONS – 33/11-0.4kV 8
1 D-SS-01-001 GENERAL 9
1.1 General Requirements 9
1.2 Grounding 9
1.3 Environmental and Protection Requirements (EPRS) 9
C6 – SUBSTATIONS – 33/11-0.4kV
1 D-SS-01-001 GENERAL
1.1 GENERAL REQUIREMENTS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
1.2 GROUNDING
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 5, Grounding.
60296 Specification for unused mineral oils for transformers and switchgear
2.2 DESIGN
2.2.1 Service Conditions
The transformer shall be designed for outdoor operation and continuous service. 250 kVA
transformers and smaller should be suitable for pole mounting.
2.2.2 Type
The transformer shall be of three-phase, oil-immersed, natural air cooled (ONAN) type. All distribution
transformers shall be of sealed type.
2.4 LOSSES
The losses should be stated and guaranteed in the Bid. These guarantees should be assumed as
maximum values and shall not be exceeded.
The capitalised value of the guaranteed losses will be taken into account when comparing Bids and
will be added to the Bid price.
Should it be found that any losses exceed the guaranteed values; the Supplier/Contractor shall for
the excess of the losses, over the guaranteed value, pay a penalty of the transformer(s).
2.5 MARKING
Each transformer should be provided with a rating plate including the information stated in the IEC
standards. The plate should be in English.
2.6 BUSHINGS
Bushings should withstand the same current as the windings and for the same period of time.
Current carrying outer parts should be made of copper or copper alloy.
It should be possible to change the bushings without dismantling the transformer cover.
Each bushing should be marked with manufacturer and type. The marking should be visible after
assembly of the fittings.
The outer creepage distance for the bushing should not be less than 25 mm/kV.
The insulation levels of the bushings should be at least equal to those specified for the windings.
The neutral connection should have a permanent, special marking, different from the phase
connections.
2.9.4 Oil
The transformer should be filled with oil before delivery. The oil should contain at least 0.3 per cent
by weight oxidation inhibitor of type diterbutyl paracresol (DBPC) according to IEC 60296
The oil must not contain PCB. If oil samples taken from the transformer on delivery contain 2 ppm or
more of PCB, the purchaser has the right to refuse the delivery of the transformer.
2.10 TESTING
All transformers should be routine tested according to IEC 60076.
The Purchaser’s/Employer’s representative will have the right to be present during the acceptance
testing.
One set of the routine test records for each individual transformer should be handed over to the
Purchaser/Engineer.
At the first delivery of a new type of transformer type test records should be submitted. Type test
records older than five years will not be accepted.
Larger transformers 601 - 1250 kg should be placed in a two pole (H) construction. Transformers
larger than 250 kVA should be placed either on four poles or mounted on the ground on a concrete
base if not placed in a compact substation.
3.3 FOUNDATIONS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 4, Foundations.
3.7 LV SWITCHGEAR
3.7.1 Reference Standards
The following publications shall be applicable:
- 50 kVA 100 A
- 100 kVA 200 A
- 160 kVA 350 A
- 200 kVA 400 A
Outgoing feeder cables. The MCCB:s should be of the discriminating type and with adjustable
ranges of the long-time delay with the below indicated current ratings and with a non-adjustable
instantaneous trip at 10 x Ith.
- 50 kVA transformers should be equipped for two (2) outgoing feeders, with a rating of 80 – 100A.
- All other transformers should be equipped for five (5) outgoing feeders with a rating of 100 –
125A.
The LV switchgear shall be equipped with moulded case breakers (MCB) for:
local power circuits with a fixed rating of 25 A
one voltmeter 0-500 V with a selector switch with four positions (OFF, Ll-L2, L2 -L3, L3 -Ll)
one 3-phase kWh meter measuring the total energy of the transformer.
The switchgear shall comply with IEC 60439. The switchgear shall be complete with all necessary
accessories.
Busbars shall be made of hard drawn electro-copper and be silver- or tin-plated at joints. The rated
current of the busbars should be 600 A
Enclosures shall be metal structures made of bolted or welded steel framing of sufficient strength to
maintain alignment and withstand the mechanical stress at the rated fault level. Degree of protection
shall IP 44, according to IEC 60529.
All connections to the 0.4 kV switchgear should be done from the front, the same with maintenance.
The switchgear shall be provided with full-scale ammeters, voltmeters, current-transformers and
selector switches mounted in the incoming feeder cubicle.
Legend
Three-way
switch
MV/0.4 kV
max. 200 kVA
Selector
A A A switch
A max Amax A max kWh
Supply for
Control Circuits V
6A
2A 600 A
0.4 kV
25 A
63 A
Control
Equipment
10 A
Space for a total number of 5 outgoing Feeders,
(50 kVA – 2 outgoing Feeders) 10 A
Op Test
Legend
Load break
switch Transformer
Local Power
with earthing
switch
Current transformers shall have thermal and mechanical ratings not less than those of the associated
main circuit.
Current transformers shall withstand 120% of the rated current without exceeding the temperature
limits prescribed.
Each transformer shall have a rating plate clearly and deeply engraved with the rating and marking
of windings.
MCB 10 A, 1-pole
2 socket-outlets, two-poled with earthing contacts according to IEC 600309, Group C, standard C2a.
4 MCB 25 A, 1-pole
1 Contactor 63 A, 230 V
1 Photocell
Only photocell connected via a 10 A MCB and a connection box for 2 x 25 mm2 OH cable is needed
for single-phase transformers.
3.7.7 Tests
Type test records not more than 5 years old shall be provided for all equipment, according to the
corresponding IEC Publications. All equipment shall pass through routine tests at the factory
according to the corresponding IEC Publications.
3.10.3 Rating
The rating of the surge arresters should be 28.8 kV for 33 kV and 9 kV for 11 kV.
Rated current
Creepage distances
3.12.2.1 Ratings
The rating of the fuses should correspond to the rated transformer capacity, in accordance with the
recommendations from the manufacturer of the fuses.
Fuses for cut-outs shall be adapted to the type of cut-out tendered.
3.13 CONDUCTORS
The Contractor/Supplier shall supply the conductors connecting the transformer LV bushings to the
LV switchgear. The conductor type should be XLPE-insulated 1 x 95 mm2 Cu-conductor for
transformers up to and including 250 kVA and 1 x 120 mm2 Cu-conductor for transformers above
250 kVA.
MV
LV MV
MV
Compact Substation
separate document. The procedures are subject to the Engineer’s review. The extent of the Tests on
Completion is tentatively summarized below.
A general check of the entire switchgear and ancillary equipment shall be made and shall
include a check of the completeness, correctness and condition of ground connections,
labelling, painted surfaces, cables, wiring, blanking plates and all other auxiliary and ancillary
items.
Checks shall be made for oil and gas leaks and that insulators are clean and free from external
damage.
Shutters, earthing procedures and the interchangeability of components shall be checked.
All interlocking arrangements both electrical and mechanical shall be fully checked and tested.
4.4.2 Power Transformers
After completion of erection, the transformer shall be inspected and tested as follows:
Visual inspection for oil leakage and correct erection.
Insulation test of high and low voltage windings, cables and accessories.
Visual inspection of oil level, valves, control cabinet, electric clearances between live parts
and grounding connections.
4.4.3 Switchgear and Control Gear
4.4.3.1 Switches
a. Switches shall be visually inspected.
b. Operational tests.
b. Static equipment which may be damaged by the application of test voltages shall have the
appropriate terminals short-circuited.
The switchgear shall be completely wired and ready for connection of external power and control
cables.
The switchgear cubicles shall be bolted together to form rigid, self-supporting assemblies.
An approved arc test according to IEC 60298 shall be performed.
Primary cable compartments shall be amply sized to accommodate cable stress cones, and shall
include cable connectors and cable supports.
The switchgear shall be provided with suitable interlocks and adequate safety devices to prevent
access to the live compartments.
Protection screens should be installed between the cable compartment and switch compartment with
a minimum degree of protection of IP 20.
Earthing device of the built in type, integrated with the switch-disconnector, shall be provided for
grounding of the cable feeders and the transformer feeder.
Insulation material used for switchgear and switch disconnectors shall be selected to ensure
continuity in operating under all conditions.
The insulation material shall maintain its dielectric strength under conditions of high humidity and
temperature, and shall provide high resistance to tracking, high flame retardance, low moisture
absorption, high mechanical strength and dimensional stability as well as a sufficiently low
deterioration ratio due to ageing.
Busbars shall be of high conductivity, electro-copper dimensioned for the rated continuous and
momentary currents within allowable rise in temperature limits, and shall not be tapered. Bolts shall
be made of a non-magnetic corrosion resistant material. Joints shall have at least 2 bolts as the
required minimum. The rated current of the busbars should be min. 630 A.
A ground bus extending the entire length of each switchgear assembly shall be provided according
to the standards, and shall be provided with a compression type terminal at each end for external
cable connections.
Measures shall be taken to compensate for expansion and contraction due to variations in
temperature.
The fused switch shall be furnished with a tripping device, activated by the fuse striker in case of trip
of a fuse in any phase.
The energy requirement for the tripping of the switch disconnector by the fuse striker shall, with a
good marginal, be less than the minimum energy available by the striker according to IEC 60282.
4.6 LV SWITCHGEAR
4.6.1 Reference Standards
The following publications shall be applicable:
60664-3 Insulation coordination for equipment within low-voltage systems - Part 3: Use
of coating, potting or moulding for protection against pollution.
60664-4 Insulation coordination for equipment within low-voltage systems - Part 4:
Consideration of high-frequency voltage stress
60664-5 Insulation coordination for equipment within low-voltage systems - Part 5: A
comprehensive method for determining clearances and creepage distances
equal to or less than 2 mm
60947-2 Low voltage switchgear and control gear. Part 2
60947-3 Switches, disconnectors and fuse-combination units
MCCB rating
315kVA 500kVA 800kVA
A
100 - 125 3 2 2
200 - 250 2 4 4
320 - 400 - - 2
Current transformers shall have thermal and mechanical ratings not less than those of the associated
main circuit.
Current transformers shall withstand 120 % of the rated current without exceeding the temperature
limits prescribed.
Each transformer shall have a rating plate clearly and deeply engraved with the rating and marking
of windings.
Type 2
MV4 MV1 MV3
200 A
Transformer
A A A
kVAr kWh Amax Amax Amax
0.5 kV 2000 A
25 A 63 A
Outgoing Feeders 63 A 10 A
6A 6A 6A
315 kVA 5 Feeders
500 kVA 6 Feeders
800 kVA 8 Feeders
Op Test
kWh
V
Loc al Power
25 A 25 A 25 A 25 A
4.9.2 General
Fuses shall comply with IEC 60282 and be of the current limiting type. The size of H.R.C. indoor fuse
shall be according to IEC 60282-1A, Type I. The fuse striker shall be medium type according to IEC
60282-1, Table XII.
4.9.3.1 Ratings
The rating of the fuses should correspond to the rated transformer capacity, in accordance with the
recommendations from the manufacturer of the fuses and IEC 60787.
Tender Documents
ZETDC Tender No.______________________
Table of Contents
1 D-LV-01-001 GENERAL 9
1.1 General Requirements 9
1.2 Mechanical Design 9
1.3 Poles and Crossarms 9
1.4 Foundations 9
1.5 Grounding 9
1.6 Environmental Protection Requirements (EPRS) 9
3 D-LV-01-001 CONDUCTORS 19
3.1 Reference Standards 19
3.2 Material 19
3.3 DESIGN and Dimensions 19
3.3.1 AAC or HDA Conductors .................................................................................................................... 19
4 D-LV-04-001 HARDWARE 26
4.1 General 26
4.2 Insulink Joint Sleeves 26
4.2.1 Reference Standards .......................................................................................................................... 26
4.2.2 General ............................................................................................................................................... 26
4.2.3 Strength .............................................................................................................................................. 26
4.3 Insulation Piercing Connectors 26
4.3.1 Reference Standards .......................................................................................................................... 26
4.3.2 General ............................................................................................................................................... 26
4.3.3 Types .................................................................................................................................................. 27
5 D-LV-05-001 APPARATUS 28
5.1 Pole Top Box 28
5.1.1 Reference Standards .......................................................................................................................... 28
1 D-LV-01-001 GENERAL
1.1 GENERAL REQUIREMENTS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
1.4 FOUNDATIONS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 4, Foundations.
1.5 GROUNDING
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 5, Grounding.
BS EN ISO 898-1 Mechanical properties of fasteners made of carbon steel and alloy steel,
Bolts, Screws and Studs
BS 3288 Insulator and conductor fittings for overhead power lines
BS EN 10244-2 Non-ferrous metallic coatings on steel wire – Part 2: Zinc or zinc alloy
coatings on steel wire
BS EN 61284 Overhead Lines – Requirements and tests for fittings
ISO 9001 Quality System Model for Quality Assurance in Design/ Development,
Manufacture and Testing
ISO 9002 Quality System Model for Quality Assurance in Production, Installation
and Servicing
IEC International Electrotechnical Committee Publications
60383-1 Insulators for overhead lines with nominal voltage above 1000V – Part
1: Ceramic or glass insulator unites for a.c. systems – Definitions, test
methods and acceptable criteria
60672-2&3 Ceramic and glass insulating materials – part2 : methods of test; part 3:
specification for individual materials
ENA Energy Networks Association
TS 43-15 Insulator Binds and Equivalent helical fittings for overhead lines
TS 43-40 Specification for single circuit overhead lines on wood poles for use at
high voltage up to and including 33kV
TS 43-88 Selection and treatment of wood poles and associated timber for
overhead lines.
TS 43-90 Anti-climbing devices and safety signs for HV lines up to and including
400kV
TS 43-91 Stay strands and stay fittings for overhead lines
These codes and standards set forth minimum requirements which may be exceeded by the
Contractor if, in the Contractor's judgment and Employer's acceptance, superior or more economic
designs or materials are available for successful and continuous operation of the Contractor's
materials as required by this specification.
In addition to the applicable standards, the Contractor shall comply with applicable national and local
laws, codes, regulations, statutes and ordinances.
The materials and services furnished shall comply with and not prevent the Employer's compliance
with all applicable standards of the local codes.
It is the intent of this specification to allow supply of hardware according to international standards.
If the Contractor customarily produces the specified hardware of national standards other than
mentioned, the Contractor shall describe the equivalences and/or differences of such standards with
his Tender.
For any such standards, which are not written in the English language, the Contractor shall make
available copies of an English translation thereof. In any event, the Contractor shall list all those
standards he proposes to use in the supply of the specified hardware.
In the event of any apparent conflict among standards or theses specifications, the Contractor shall
refer the conflict to the Employer for written resolution.
2.2.1.4 Insulators
Reel insulators shall be utilised for supporting conductors and they shall be of brown glazed porcelain
type, as illustrated below:
LV Line – Arrangement of Stays for Strain Pole (Lines Strung with AAC Conductors)
2.2.1.10 Accessories
Accessories shall include stay wire tensioning device, stay clamp, stay rod, thimble washer, stay
plate, stay wire anchors for soil and rock, and bolts and nuts and stay wire attachment devices to a
wood pole (preformed grip or clamp type).
Strain Clamp
The strain clam is used for termination of the cables to a pole or a wall by means of standard hooks.
The plastic parts shall be made of heat and UV-radiation resistant material and the steel parts shall
be hot-dip galvanised.
Suspension Clamp
The suspension clamp is used for suspension of the cable to poles or walls in straight lines and at
angles of up to 90o. The body of the clamp shall be made of weather- resistant aluminium alloy or
hot-dip galvanised steel
Rubber Insert
The rubber insert is used in suspension clamps to ensure even pressure on the cable. The inserts
shall be made of UV-radiation resistant rubber.
2.3.3 Testing
The clamps shall be type, sample and routine tested in accordance with the applicable standard for
Testing of suspension clamps for PE-insulated self-supporting aerial cable, type ALUS, rated voltage
1 kV.
Wedge
25 6.4 33.9
52 9.2 68.7
3 D-LV-01-001 CONDUCTORS
3.1 REFERENCE STANDARDS
The following standards shall be applicable:
60502 Extruded solid dielectric insulated power cables for rated voltages from 1 kV to
30 kV.
60888 Zinc-Coated Steel Wires for Stranded Conductors.
61394 Overhead lines - Characteristics of greases for aluminium, aluminium alloy and
steel bare conductors
61395 Overhead electrical conductors - Creep test procedures for stranded
conductors
62219 Overhead electrical conductors - Formed wire, concentric lay, stranded
conductors
3.2 MATERIAL
Conductors should be manufactured from aluminium alloy meeting the requirements on resistivity,
tensile strength, etc. given in this specification. In addition the material shall have a resistance against
corrosion at least on the level of Al/Mg/Si wire according to IEC 60104. Conductors intended for
SWER systems (if applicable) should be extra high strength ACSR conductors.
Calculated
Code Stranding
Nominal Sectional Overall Calculated Current –
Name & Wire Weight
Al Area Area Diameter Breaking Carrying
AAC or Diameter (kg/km)
(mm2) (mm2) (mm) Load (kN) Capacity
HDA (mm)
(A)1
3.3.2.1 Conductor
Compressed, stranded conductor of aluminium:
2
Cross-sectional area: 95, 50 or 25 mm
2
Conductor resistance: 95 mm 0.320 ohm/km
50 mm2 0.641 ohm/km
2
25 mm 1.200 ohm/km
3.3.2.2 Insulation
3
Polyethylene with the density 0,93 g/cm and of weather resistant quality.
Melt flow index: max. 0.5
Insulation thickness: 1.3 mm
Percentage of carbon black: 2 to 3% by weight.
Colour: Black
3.3.2.3 Construction
The cable has a symmetrical right hand lay with a length of lay of about 40 times the diameter Dy
over the cores, laid up. The cores are of the same length and lie close to each other.
2 x 25 17 200
4 x 25 20 400
4 x 50 27 700
4 x 50 + 25 29 800
4 x 95 37 1,300
4 x 95 + 25 39 1,400
3.3.2.4 Marking
The live cores are marked with longitudinal triangle-shaped ridges.
25 4.2
50 7.4
95 14
Whole Cable
Number of conductors x rated cross- Breaking Load
sectional area
mm2 kN (minimum)
2 x 25 8.4
4 x 25 16.8
4 x 50 29.6
4 x 50 + 25 29.6
4 x 95 56.0
4 x 95 + 25 56.0
25 75 1.2
50 120 2.4
95 190 4.6
3.3.5 Testing
The cables shall be tested and fulfil the requirements in accordance with the relevant IEC or local
standards.
3.3.7 Packing
The AAC conductors shall be delivered on sea-worthy wooden drums in lengths of 2000m, while
ABC cables shall normally be delivered on sea worthy wooden drums in 1000m lengths.
3.4.5 Tests
3.4.5.1 Type Tests
3.4.5.1.1 General
The type tests shall be performed by the manufacturer or a recognized test authority approved by
the Engineer. If a previous report on an identical cable has been produced, a copy of this report may
be submitted.
If any changes in the cable design are made, such as change of conductor type, change of insulation
thickness, change of conductor diameter or change of insulation material, then the type test shall be
repeated.
3.4.5.1.1.1 Bending Radius
Carefully bend the sample around a mandrel of diameter equal to eight times the diameter of the
cable, carefully bend a cable sample around the mandrel to make a 180° turn and check for
compliance with clause 6.4.3.
Apply a steady increasing load (in Newton) up to a value of 0.7 kN onto the cable and allow
it to settle for a period of 5 minutes.
Mark the cable at the inner end of the commercial clamp so that any slippage of the cable
sheath over the concentric layer is measurable.
Maintain the tension on the cable at a constant load of 0.7 kN for 15 minutes.
Mark the cable at the inner end of the commercial clamp and record the slippage.
Increase the load steadily to 1.0 kN.
Maintain the tension on the cable at a constant 1.0 kN load for 1 hour.
After the 1 hour has elapsed, mark and record the slippage from the 0.7 kN point
60502 Extruded solid dielectric insulated power cables for rated voltages from 1 kV to
30 kV.
60811 Common test methods for insulating and sheathing materials of electric cables.
3.5.2 Design
The cable shall be PVC-insulated, PVC-sheathed with Cu-conductors and copper screen. The
neutral conductor shall be of the same cross-section as the phase-conductors. The cable shall be
suitable for clamping directly on house walls. The PEN-conductor shall be coloured green-and-
yellow.
4 D-LV-04-001 HARDWARE
4.1 GENERAL
Clamps and fittings shall be of a design approved for the conductor in accordance with the relevant
clause.
The connecting attachments, including bolts, nuts and washers, shall be included in the assemblies.
All materials shall be free from folds, cracks and other exterior and interior defects, which can affect
its strength, ductility, durability of ability to function.
All materials shall be inspected and tested in full to prove compliance with the requirements of the
Specifications and to the satisfaction of the Purchaser/Engineer.
The testing shall be carried out according to the relevant standards approved by the
Purchaser/Engineer.
4.2.3 Strength
The tensile strength of a jointed wire should be at least 90% of the value required for an unjointed
wire. The elongation requirements need not to be fulfilled.
4.3.3 Types
Connectors should be supplied for the following type of conductors:
Covered Al-conductor 25 - 95/25 - 95 mm2.
Covered Al-conductor 25 - 95/Cu-conductor 6 - 35 mm2.
Covered Al-conductor 25/Cu-conductor 2.5 mm2 for street lighting luminaries.
5 D-LV-05-001 APPARATUS
5.1 POLE TOP BOX
5.1.1 Reference Standards
The following standards shall be applicable:
60664-3 Insulation coordination for equipment within low-voltage systems - Part 3: Use
of coating, potting or moulding for protection against pollution.
5.2.2 Design
The joint box shall be intended for connection of the service cable to the entrance cable to the meter.
Normally the box is only needed at three-phase supplies since the concentric service cable can be
used as entrance cable as well. The box shall be equipped with clamps suitable for Al-conductors
25-50 mm2 to Cu-conductors 10-35 mm2.
5.4 METERS
5.4.1 Reference Standards
The following standards shall be applicable:
5.4.2.2 Class
The meters should be of Class 2 according to IEC 60521
5.4.6 Testing
The meters should be tested and fulfil the requirements according to IEC 60521. The peak value in
IEC 60651, Clause 6.5.2 shall be 12 kV instead of 6 kV.
5.5 LUMINARIES
5.5.1 Reference Standards
The following standards shall be applicable:
The luminary shall be permanently engraved with the mark EDM and the marking of the type and
size of lamp should be visible from the ground.
The Spigot entry is 34mm OD x 80mm or 42mm OD x 100mm standard and via use of a spigot
adaptor ensuring all bracket sizes are catered for.
b. HID Aluminium Luminaries
The luminary shall be a totally enclosed street light luminary suitable for use with one of the 70-400W
high-pressure sodium vapour, high-pressure mercury vapours and metal halide lamps.
The optical compartment shall be IP class 54.
The optical and gear compartments are separated sealed via neoprene gasket.
The optic chamber is to be powder coated white internally, combined with high purity A aluminium
reflectors.
The control gear shall be isolated from the heat of the lamp via a separate compartment with
removable gear tray.
The luminary shall be protected by a 5A MCB.
c. Energy Saving Aluminium luminaries
The luminary shall be a totally enclosed street luminary suitable for use with one of 14-24W tubular
fluorescent lamp, T5, high CRI, colour day light.
The optical and gear compartment shall be IP class 65.
Internal optical reflector is made from a highly reflective material. Which gives 96% reflectivity.
The connection compartments to be separated to the optics.
Use an electronic Ballast with Power factor at 0.98.
5.5.3 Mounting
The luminary shall be mounted on a bracket suitable for wooden, concrete or steel poles. The bracket
with an outreach of 1.5 m shall normally be included in the supply. Longer outreach may be needed
in special cases.
The luminary shall be connected to the feeder with a 3 x 2.5 mm2 PVC-insulated Cu-cable. The light
blue and the green-and-yellow cores of the cable should be connected to the neutral of the ABC
cable and the black core should be connected to the phase conductor by insulation piercing
connectors.
Thus, the bracket is grounded via the luminary. The neutral and the protection ground should not be
connected together in the luminary.
6.1.3 Survey
As stated in Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
Backfill shall be carried out to a minimum height of 20 cm over the original ground surface to
compensate for future settlement of the filling.
All backfill of pole foundation shall be protected from being washed away by running water in an
approved manner.
At all pole positions, the surface of the ground shall be sloping from the pole to provide drainage as
required. No additional payment will be made for such work.
At certain places, additional protection against erosion may be required, such as installation of riprap
or ditches. Any such work, when decided in agreement with and authorised by the Engineer, will be
paid for on the basis of prices in the schedule of rates and prices in the contract.
6.2.4 Erection
Poles may be erected by any suitable method, provided that no overstressing of any component
parts occurs.
After initial assembly, but before stringing of conductors, thorough check shall be made so that all
bolts are tightened to correct torque and all nuts are locked in an approved manner.
Handling and storage of all material shall be such as to prevent injury to members or damage to the
zinc-coating. Steel in storage shall be blocked off ground.
At each pole, the Contractor shall install the relevant pole signs as shown on the drawings.
Poles shall be plumb. After clamping-in of conductors, the maximum tolerated deviation in any
direction from the vertical shall be 2 mm/m (0.2 %) of the pole height above ground level.
After erection, all poles shall be cleared of all foreign matters.
Immediately before and installation, the insulator shall be thoroughly cleaned, and all cotter pins shall
be checked for correct positioning and freedom from defects.
All screws, nuts and cotter pins shall be installed so as to facilitate easy, inspection and live line
maintenance work.
Compression joints and tension clamps shall be installed in accordance with good engineering
practice. The Contractor shall submit detailed written instructions for the complete installation
procedure for the approval of the Engineer.
Wherever possible, full use shall be made of maximum drum lengths of conductors in order to reduce
the number of joints.
The number of joints and their location in the spans shall be approved by the Engineer.
No joints shall be made in spans which cross main roads, power lines or in the major river crossings,
nor, whenever conductor drum lengths permit, in spans immediately adjacent thereto.
The distance between joints of the same conductor shall in no case be less than 100 m. Joints shall
in no case be installed closer than 20 m to the centre of suspension clamps.
The Contractor shall keep a record of all joints and tension clamps indicating the location, type and
date of each assembly.
6.3.4 Stringing
Conductors shall be pulled out and strung by an approved stringing method. Conductors shall, as far
as practicable, not be in direct contact with soil during laying an stringing.
The Contractor shall submit in writing, for the approval of the Engineer, a complete and detailed
description of the stringing equipment and the stringing and sagging procedure intended for use.
Unless otherwise approved by the Engineer, the stringing procedure shall be in strict conformity with
the recommendations of the manufacturer of the stringing equipment. Only specially trained linesmen
must be employed who are well acquainted with the handling and running of the particular equipment
to be used.
Reliable means of instantaneous two-way communication must be available between the pulling and
the braking crews, and between these crews and any observation posts that may be placed along
the stringing section.
The stringing equipment shall be set up so as not to cause excessive vertical loads on the poles.
The distance to the nearest pole through which the cables are being strung shall be selected with
due regard to the relative levels of the pulleys on the pole and the stringing equipment reasonable
allowance should also be made for possible accidental over-tensioning of the cables.
Stringing pulleys shall preferably be located at approximately the same levels as that which the
conductors will occupy when installed.
At all times during stringing, the conductors shall be handled and protected so as not to be scratched,
nicked, abraded, kinked or damaged in any way. If during stringing it should prove inevitable to lower
the conductors to the ground, suitable non-metallic lagging shall be placed underneath.
Conductors, which have been subject to bird-caging during stringing, will not be accepted.
Stringing tensions shall at no time exceed corresponding sagging tensions.
Clamps for attaching the conductors to the hauling device shall be of approved design and shall
prevent relative movement of strand or layers of the conductors or overhead ground wires. Freely
rotating ball bearing swivels shall be used for each cable to be strung.
If, for any reason, stringing operations in progress must be interrupted, the conductors may be left in
the stringing pulleys, but their tension shall be reduced as far as possible.
In all cases, however, the cables must be kept completely clear of the ground, not lower than the
min. clearances given in Clause 2.5 of Distribution Lines & Substations, Volume 2C, Section VI(C)2,
Distribution General Specifications, Chapter 1, General and sufficiently far from any obstacles which
might cause abrasion of the cables, if touched by them.
If the interruption lasts for more than 40 hours or if stormy weather has prevailed, the cables shall be
closely inspected for damage.
Such inspection applies particularly to the suspension points where the cables have been resting in
the pulley sheaves.
At all times during stringing, sagging and clamping operations, the conductors, reels and hauling
equipment shall be effectively grounded.
The Contractor shall make suitable arrangements for temporary staying of poles, where necessary.
Damages to the conductors shall be immediately reported to the Engineer who will instruct the
Contractor on how to proceed.
6.3.5 Sagging
The Contractor shall submit for the approval of the Engineer sag and tension charts for use during
erection, which shall be established with due regard to the specific stringing and sagging methods
to be employed so that remaining creep after clamping may be assessed and taken into account with
reasonable accuracy.
Erection sagging charts or tables shall display sag in still air against span length for temperatures
between +5o C and 70o C in increments of 5o C.
Sagging temperature shall be read from a certified thermometer, the bulb of which has been inserted
in an approximately 50 cm long piece of conductor with the inner layers removed. The thermometer
so equipped shall be freely suspended in the air without any shielding and not less than 3 m above
ground. Temperature readings will be taken only after 20 minutes exposure.
After finishing stringing operations, the conductors and overhead ground wires shall be sagged in
accordance with agreed sagging procedure and relevant erection sagging chart or table.
It is essential that prescribed hold periods before definite sagging are rigorously observed.
The Contractor shall check the sag of each conductor of a sagging section in at least one span of
approximate ruling span length. The sags shall also be checked in all spans exceeding 120 m and
in spans on each side of angle structures and sharp breaks in profile. Intermediate spans shall be
inspected for uniform sag.
Sag at the option of the Engineer will be checked by him, and the Contractor shall furnish such
assistance in equipment and personnel as may be required for this purpose.
Sagging sections shall be limited to such length as can be sagged satisfactorily.
Final sagging of conductors shall not be made earlier than 8 hours but not later than 48 hours after
they have been taken up to approximate specific sag. All conductors of a sagging section shall be
sagged at the same time.
Conductor tension shall be equalised between sagging sections so that the insulator strings will
assume the proper position when successive sagging sections have been clamped in.
The Contractor shall keep a record on approved schedules of the particulars of the sagging of
conductors and overhead ground wires on each sagging section.
6.3.6 Binding
After finishing sagging operations, the conductors shall be bound according to agreed procedure.
Tension clamps shall be installed and properly anchored prior to clamping-in at suspension strings.
In order to make future adjustments possible, approximately one half of the available length
adjustment of turn buckles shall remain after anchoring.
Binding shall be done within 48 hours after completion of sagging, unless otherwise agreed.
All markings of the conductors, e.g. for the centring of clamps or armour rods, shall be done with
tape or other inoffensive means. Scratch marks or similar will not be permitted.
Immediately after binding, sag tolerances shall be plus or minus 1 % of specified sag, provided that
all conductors in the span assume the same sag, and specified clearance to ground will be obtained.
Tender Documents
ZETDC Tender No.______________________
Table of Contents
Employer's Contractor's
33/0.4 kV Power Transformer Unit
Requirements Guarantees
Manufacturer’s Name
Country of Manufacture
3-phase, oil-
Type immersed, with on-
load tap changer
Employer's Contractor's
33/0.4 kV Power Transformer Unit
Requirements Guarantees
Temperature rises
-Windings average o
C ≤60
-Top oil o
C ≤55
-Winding hot spot o
C ≤70
-Core surface o
C ≤75
The transformer must withstand the short circuit special test as
per IEC 60076 part 5, on units seleceted at random by the Yes
Client's inspector from each lot submitted to acceptance test
At the Client's
discretion, after
Execution of Short Circuit Tests transformer
manufacturing per
lot
Short circuit test reports on similar transformers in an Shall be enclosed
independent test laboratory to the offer
Short circuit power of 34.5kV supply network for short circuit test Infinite
Construction
-Primary Copper
Copper or
-Secondary
Aluminium
-Cross section Uniform
-Current density in Copper A/mm2 HV: ≤3; LV ≤ 3
Magnetic Core
-Type 3 legged
Cold rolled grain
-Material oriented silicon
steel
-Flux density at rated voltage & frequency, with mean tap Tesla ≤1.65
-Bushing Characteristics IEC 137
-Type Porcelain
Primary Bushings
-Rated Voltage as per IEC 60694 kV 38
-Rated Current A
Withstand test voltage
-50Hz - 1 minute wet kVrms
-Lightning impulse (1.2/50µs) kVcrest
Creepage Distance mm
Secondary bushings
-Insulation level kV
-Rated Current A
Withstand test voltage
-50Hz - 1 minute wet kVrms
-Lightning impulse (1.2/50µs) kVcrest
Bushings Number
-Primary kVrms
-Secondary kVcrest
Employer's Contractor's
33/0.4 kV Power Transformer Unit
Requirements Guarantees
Tank Rib type Rib Type
Made of Corrosion
Valves and bolts
resistant material
Painting
Protected aginst
hot oil at a
-Internal surfaces, including the conservator
temperature of
105oC
For tropical
environment, as
-External surfaces
specified in the
detailed specs.
Accessories Required
-Conservator Yes
-Oil level indicator Yes
-Oil filling plug Yes
-Pocket thermometer dial type Yes
-Skid Yes
-Filling and draing valves Yes
-Lifting eyes Yes
-Hitching holes Yes
-Rating Plate Yes
Overall Dimensions
-Height mm
-Length mm
-Width mm
Alternative bid for tank hermetically sealed, for life
With corugated
-Tank walls completely
full of oil
-Max. internal pressure between 0oC and 110oC bar 0.3
gas; over
temperature
-Functions of the integrated protection relay
(alarm and trip);
over pressure
All technical deviations shall be listed with reference to the relevant Clause in the Technical Specifications. A
comprehensive description can be given in a separate attachment, to be indicated in the far right column
Employer's Contractor's
11/0.4 kV Power Transformer Unit
Requirements Guarantees
Manufacturer’s Name
Country of Manufacture
3-phase, oil-
Type immersed, with on-
load tap changer
Employer's Contractor's
11/0.4 kV Power Transformer Unit
Requirements Guarantees
Temperature rises
-Windings average o
C ≤60
-Top oil o
C ≤55
-Winding hot spot o
C ≤70
-Core surface o
C ≤75
The transformer must withstand the short circuit special test as
per IEC 60076 part 5, on units seleceted at random by the Yes
Client's inspector from each lot submitted to acceptance test
At the Client's
discretion, after
Execution of Short Circuit Tests transformer
manufacturing per
lot
Short circuit test reports on similar transformers in an Shall be enclosed
independent test laboratory to the offer
Short circuit power of 34.5kV supply network for short circuit test Infinite
Construction
-Primary Copper
Copper or
-Secondary
Aluminium
-Cross section Uniform
-Current density in Copper A/mm2 HV: ≤3; LV ≤ 3
Magnetic Core
-Type 3 legged
Cold rolled grain
-Material oriented silicon
steel
-Flux density at rated voltage & frequency, with mean tap Tesla ≤1.65
-Bushing Characteristics IEC 137
-Type Porcelain
Primary Bushings
-Rated Voltage as per IEC 60694 kV 12
-Rated Current A
Withstand test voltage
-50Hz - 1 minute wet kVrms
-Lightning impulse (1.2/50µs) kVcrest
Creepage Distance mm
Secondary bushings
-Insulation level kV
-Rated Current A
Withstand test voltage
-50Hz - 1 minute wet kVrms
-Lightning impulse (1.2/50µs) kVcrest
Bushings Number
-Primary kVrms
-Secondary kVcrest
Employer's Contractor's
11/0.4 kV Power Transformer Unit
Requirements Guarantees
Tank Rib type Rib Type
Made of Corrosion
Valves and bolts
resistant material
Painting
Protected aginst
hot oil at a
-Internal surfaces, including the conservator
temperature of
105oC
For tropical
environment, as
-External surfaces
specified in the
detailed specs.
Accessories Required
-Conservator Yes
-Oil level indicator Yes
-Oil filling plug Yes
-Pocket thermometer dial type Yes
-Skid Yes
-Filling and draing valves Yes
-Lifting eyes Yes
-Hitching holes Yes
-Rating Plate Yes
Overall Dimensions
-Height mm
-Length mm
-Width mm
Alternative bid for tank hermetically sealed, for life
With corugated
-Tank walls completely
full of oil
-Max. internal pressure between 0oC and 110oC bar 0.3
gas; over
temperature
-Functions of the integrated protection relay
(alarm and trip);
over pressure
All technical deviations shall be listed with reference to the relevant Clause in the Technical Specifications. A
comprehensive description can be given in a separate attachment, to be indicated in the far right column
Insulator Guarantees
12 months from 12 months from
commissioning or commissioning
Guarantee Period months 18 months from or 18 months
date of last from date of last
despatch despatch
Tests and Experience Requirements
Test Requirements
Design Test and Report Required (Yes, No.)* Yes Yes
Factory Acceptance Tests Test and Reports Required (Yes, No) Yes Yes
Quality Conformance Test and Report Required (Yes, No) Yes Yes
The material offered should have been in the actual service for
years 15 15
not less than
Insulator Guarantees
12 months from 12 months from
commissioning or commissioning
Guarantee Period months 18 months from or 18 months
date of last from date of last
despatch despatch
Tests and Experience Requirements
Test Requirements
Design Test and Report Required (Yes, No.)* Yes Yes
Factory Acceptance Tests Test and Reports Required (Yes, No) Yes Yes
Quality Conformance Test and Report Required (Yes, No) Yes Yes
The material offered should have been in the actual service for
years 15 15
not less than
The material offered should have been in the actual service for
years 15 15
not less than
The material offered should have been in the actual service for not less than years 15 15
Contractor's Exceptions and Clarifications (if Any)
Employer's Contractor's
Description Unit
Requirements Guarantee
Conductor Type SCA Gopher
Manufacturing International Standard IEC/ASTM
Country of Origin
Composition of Conductor:
Outer Layer
Material Aluminium
Source of Aluminium Rod
Stranding and Wire Diameter No. / mm 6/2.36
Layers no.
Cross Section mm2 25
Weight kg/km
Coefficient of Elongation
Core
Material Steel
Stranding and Wire Diameter No. / mm 1/2.36
Layers no.
Cross Section mm2
Weight kg/km
Coefficient of Elongation
Total
Overall diameter mm 7.08
Weight without grease kg/km 106
Weight with grease kg/km
Overall cross section mm2 30.62
Ultimate tensile strength kN 9.61
2
Modulus of Elasticity Ei (Initial) N/mm
Modulus of Elasticity Ep (Permanent) N/mm2
Coefficient of Elongation per oC
Permanent elongation factor due to creep m/m
DC resistance of conductors per km at 20oC Ohm/km
Conductor Ampacity (At 45oC) A 150
Conductor Lay (Right, Left)
Length of Lay
Name of Grease Used
Greasing System
Wiping System
o
Drop Point of Grease C
o
Maximum Temperature for 30min. Operation without Migration C
o
Maximum Temperature without Irreversible Property Changes C
Cable Reel/Drum
Drum/Reel Manufacturer
Length of Conductor Per Drum m
Drum Overall Diameter mm
Employer's Contractor's
Description Unit
Requirements Guarantee
Drum Battens Fitted (Yes/No) Specify
Diameter of Core mm
Axle Hole Diameter mm
Gross Weight of Loaded Drum kg
Material of Drum
Returnable (Yes/No)
Accessories for Conductor
Compression Splice Manufacturer
Compound Prefilled
Compression Repair Assembly Manufacturer
Filler Compounds
Employer's Contractor's
Description Unit
Requirements Guarantee
Conductor Type SCA Rabbit
Manufacturing International Standard IEC/ASTM
Country of Origin
Composition of Conductor:
Outer Layer
Material Aluminium
Source of Aluminium Rod
Stranding and Wire Diameter No. / mm 6/3.35
Layers no.
Cross Section mm2 50
Weight kg/km
Coefficient of Elongation
Core
Material Steel
Stranding and Wire Diameter No. / mm 1/3.35
Layers no.
Cross Section mm2
Weight kg/km
Coefficient of Elongation
Total
Overall diameter mm 10.05
Weight without grease kg/km 214
Weight with grease kg/km
Overall cross section mm2 61.72
Ultimate tensile strength kN 18.35
2
Modulus of Elasticity Ei (Initial) N/mm
Modulus of Elasticity Ep (Permanent) N/mm2
Coefficient of Elongation per oC
Permanent elongation factor due to creep m/m
DC resistance of conductors per km at 20oC Ohm/km
Conductor Ampacity (At 45oC) A 240
Conductor Lay (Right, Left)
Length of Lay
Name of Grease Used
Greasing System
Wiping System
o
Drop Point of Grease C
o
Maximum Temperature for 30min. Operation without Migration C
o
Maximum Temperature without Irreversible Property Changes C
Cable Reel/Drum
Drum/Reel Manufacturer
Length of Conductor Per Drum m
Drum Overall Diameter mm
Employer's Contractor's
Description Unit
Requirements Guarantee
Drum Battens Fitted (Yes/No) Specify
Diameter of Core mm
Axle Hole Diameter mm
Gross Weight of Loaded Drum kg
Material of Drum
Returnable (Yes/No)
Accessories for Conductor
Compression Splice Manufacturer
Compound Prefilled
Compression Repair Assembly Manufacturer
Filler Compounds
Employer's Contractor's
Description Unit
Requirements Guarantee
Conductor Type SCA Raccoon
Manufacturing International Standard IEC/ASTM
Country of Origin
Composition of Conductor:
Outer Layer
Material Aluminium
Source of Aluminium Rod
Stranding and Wire Diameter No. / mm 6/4.10
Layers no.
Cross Section mm2 75
Weight kg/km
Coefficient of Elongation
Core
Material Steel
Stranding and Wire Diameter No. / mm 1/4.10
Layers no.
Cross Section mm2
Weight kg/km
Coefficient of Elongation
Total
Overall diameter mm 12.3
Weight without grease kg/km 320
Weight with grease kg/km
Overall cross section mm2 92.4
Ultimate tensile strength kN 27.2
2
Modulus of Elasticity Ei (Initial) N/mm
Modulus of Elasticity Ep (Permanent) N/mm2
Coefficient of Elongation per oC
Permanent elongation factor due to creep m/m
DC resistance of conductors per km at 20oC Ohm/km
Conductor Ampacity (At 45oC) A 300
Conductor Lay (Right, Left)
Length of Lay
Name of Grease Used
Greasing System
Wiping System
o
Drop Point of Grease C
o
Maximum Temperature for 30min. Operation without Migration C
o
Maximum Temperature without Irreversible Property Changes C
Cable Reel/Drum
Drum/Reel Manufacturer
Length of Conductor Per Drum m
Drum Overall Diameter mm
Employer's Contractor's
Description Unit
Requirements Guarantee
Drum Battens Fitted (Yes/No) Specify
Diameter of Core mm
Axle Hole Diameter mm
Gross Weight of Loaded Drum kg
Material of Drum
Returnable (Yes/No)
Accessories for Conductor
Compression Splice Manufacturer
Compound Prefilled
Compression Repair Assembly Manufacturer
Filler Compounds
Employer's Contractor's
Description Unit
Requirements Guarantee
Conductor Type SCA Dog
Manufacturing International Standard IEC/ASTM
Country of Origin
Composition of Conductor:
Outer Layer
Material Aluminium
Source of Aluminium Rod
Stranding and Wire Diameter No. / mm 6/4.72
Layers no.
Cross Section mm2 100
Weight kg/km
Coefficient of Elongation
Core
Material Steel
Stranding and Wire Diameter No. / mm 7/1.57
Layers no.
Cross Section mm2
Weight kg/km
Coefficient of Elongation
Total
Overall diameter mm 14.15
Weight without grease kg/km 394
Weight with grease kg/km
Overall cross section mm2 118.5
Ultimate tensile strength kN 32.7
2
Modulus of Elasticity Ei (Initial) N/mm
Modulus of Elasticity Ep (Permanent) N/mm2
Coefficient of Elongation per oC
Permanent elongation factor due to creep m/m
DC resistance of conductors per km at 20oC Ohm/km
Conductor Ampacity (At 45oC) A 360
Conductor Lay (Right, Left)
Length of Lay
Name of Grease Used
Greasing System
Wiping System
o
Drop Point of Grease C
o
Maximum Temperature for 30min. Operation without Migration C
o
Maximum Temperature without Irreversible Property Changes C
Cable Reel/Drum
Drum/Reel Manufacturer
Length of Conductor Per Drum m
Drum Overall Diameter mm
Employer's Contractor's
Description Unit
Requirements Guarantee
Drum Battens Fitted (Yes/No) Specify
Diameter of Core mm
Axle Hole Diameter mm
Gross Weight of Loaded Drum kg
Material of Drum
Returnable (Yes/No)
Accessories for Conductor
Compression Splice Manufacturer
Compound Prefilled
Compression Repair Assembly Manufacturer
Filler Compounds
Employer's Contractor's
Description Unit
Requirements Guarantee
Conductor Type ACSR Wolf
Manufacturing International Standard IEC/ASTM
Country of Origin
Composition of Conductor:
Outer Layer
Material Aluminium
Source of Aluminium Rod
Stranding and Wire Diameter No. / mm 30/2.59
Layers no.
Cross Section mm2 150
Weight kg/km
Coefficient of Elongation
Core
Material Steel
Stranding and Wire Diameter No. / mm 7/2.59
Layers no.
Cross Section mm2
Weight kg/km
Coefficient of Elongation
Total
Overall diameter mm 18.13
Weight without grease kg/km 726
Weight with grease kg/km
Overall cross section mm2 194.9
Ultimate tensile strength kN 69.2
2
Modulus of Elasticity Ei (Initial) N/mm
Modulus of Elasticity Ep (Permanent) N/mm2
Coefficient of Elongation per oC
Permanent elongation factor due to creep m/m
DC resistance of conductors per km at 20oC Ohm/km
Conductor Ampacity (At 45oC) A 470
Conductor Lay (Right, Left)
Length of Lay
Name of Grease Used
Greasing System
Wiping System
o
Drop Point of Grease C
o
Maximum Temperature for 30min. Operation without Migration C
o
Maximum Temperature without Irreversible Property Changes C
Cable Reel/Drum
Drum/Reel Manufacturer
Length of Conductor Per Drum m
Drum Overall Diameter mm
Employer's Contractor's
Description Unit
Requirements Guarantee
Drum Battens Fitted (Yes/No) Specify
Diameter of Core mm
Axle Hole Diameter mm
Gross Weight of Loaded Drum kg
Material of Drum
Returnable (Yes/No)
Accessories for Conductor
Compression Splice Manufacturer
Compound Prefilled
Compression Repair Assembly Manufacturer
Filler Compounds
Employer's Contractor's
Description Unit
Requirements Guarantee
Name of Manufacture
Country of Manufacturer
Timber Species
ISO Certification of Manufacturer
Standard BS / SANS
Minimum Age of Poles years
Minimum Ultimate Fibre Stress in Bending N/mm2 55
Taper mm/m 5
Length m 13.5
Minimum pole top diameter mm >200
Minimum Pole Diameter at Ground Level mm
Pole Planting Depth m 1.8
Rated Load (at 60cm from top, planting depth) kN
Minimum Ultimate Load (at 60cm from pole top, planting depth) kN Steel
Method of Seasoning Kiln Dried
Maximum Moisture Content Before Treatment % 25
Type and Method of Treatment
Kind of Preservative Creosote
Standard Used for Preservative
Minimum Depth of Penetration of Preservative mm
Minimum Depth of Sapwood mm
Pole Top Protective Sleeve Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
Name of Manufacture
Country of Manufacturer
Timber Species
ISO Certification of Manufacturer
Standard BS / SANS
Minimum Age of Poles years
Minimum Ultimate Fibre Stress in Bending N/mm2 55
Taper mm/m 5
Length m 12.6
Minimum pole top diameter mm 175 - 200
Minimum Pole Diameter at Ground Level mm
Pole Planting Depth m 1.8
Rated Load (at 60cm from top, planting depth) kN
Minimum Ultimate Load (at 60cm from pole top, planting depth) kN Steel
Method of Seasoning Kiln Dried
Maximum Moisture Content Before Treatment % 25
Type and Method of Treatment
Kind of Preservative Creosote
Standard Used for Preservative
Minimum Depth of Penetration of Preservative mm
Minimum Depth of Sapwood mm
Pole Top Protective Sleeve Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
Name of Manufacture
Country of Manufacturer
Timber Species
ISO Certification of Manufacturer
Standard BS / SANS
Minimum Age of Poles years
Minimum Ultimate Fibre Stress in Bending N/mm2 55
Taper mm/m 5
Length m 10.8
Minimum pole top diameter mm 150-175
Minimum Pole Diameter at Ground Level mm
Pole Planting Depth m 1.8
Rated Load (at 60cm from top, planting depth) kN
Minimum Ultimate Load (at 60cm from pole top, planting depth) kN Steel
Method of Seasoning Kiln Dried
Maximum Moisture Content Before Treatment % 25
Type and Method of Treatment
Kind of Preservative Creosote
Standard Used for Preservative
Minimum Depth of Penetration of Preservative mm
Minimum Depth of Sapwood mm
Pole Top Protective Sleeve Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
Name of Manufacture
Country of Manufacturer
Timber Species
ISO Certification of Manufacturer
Standard BS / SANS
Minimum Age of Poles years
Minimum Ultimate Fibre Stress in Bending N/mm2 55
Taper mm/m 5
Length m 10
Minimum pole top diameter mm 125-150
Minimum Pole Diameter at Ground Level mm
Pole Planting Depth m 1.5
Rated Load (at 60cm from top, planting depth) kN
Minimum Ultimate Load (at 60cm from pole top, planting depth) kN Steel
Method of Seasoning Kiln Dried
Maximum Moisture Content Before Treatment % 25
Type and Method of Treatment
Kind of Preservative Creosote
Standard Used for Preservative
Minimum Depth of Penetration of Preservative mm
Minimum Depth of Sapwood mm
Pole Top Protective Sleeve Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
Name of Manufacture
Country of Manufacturer
Timber Species
ISO Certification of Manufacturer
Standard BS / SANS
Minimum Age of Poles years
Minimum Ultimate Fibre Stress in Bending N/mm2 55
Taper mm/m 5
Length m 9
Minimum pole top diameter mm 125-150
Minimum Pole Diameter at Ground Level mm
Pole Planting Depth m 1.5
Rated Load (at 60cm from top, planting depth) kN
Minimum Ultimate Load (at 60cm from pole top, planting depth) kN Steel
Method of Seasoning Kiln Dried
Maximum Moisture Content Before Treatment % 25
Type and Method of Treatment
Kind of Preservative Creosote
Standard Used for Preservative
Minimum Depth of Penetration of Preservative mm
Minimum Depth of Sapwood mm
Pole Top Protective Sleeve Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
33kV Lines
Line length (estimated total for 3 lines) km ~6
Right of Way
Width m 15
Bush Clearing (width) m 15
Clearing of Danger Trees Required Outside Servitude Yes
Construction of Access Track Within the Servitude no. Yes
Line Survey
Details to be shown from either side of centreline
1. Ground Details Within m 10
2. Permanent Buildings Within m 10
Preferred Pole Heights
13.5m long poles Yes
12.6m long poles Yes
Subject to
10.8m long poles
approval
Pole Planting Depth, all pole types (minimum) m 1.8
11kV Lines
Line length (estimated) km 23
Right of Way
Width m 10
Bush Clearing (width) m 10
Clearing of Danger Trees Required Outside Servitude Yes
Construction of Access Track Within the Servitude no. Yes
Line Survey
Details to be shown from either side of centreline
1. Ground Details Within m 7.5
2. Permanent Buildings Within m 7.5
Preferred Pole Heights
12.5m long poles Yes
10.8m long poles Yes
Subject to
9m long poles
approval
Pole Planting Depth (minimum), >10.5m long pole 1.8
Pole Planting Depth (minimum), ≤10.5m long pole 1.5
LV Lines
Line length (estimated) TBA
Right of Way
Width m <5
Bush Clearing (width) m 2
Clearing of Danger Trees Required Yes
Construction of Access Track Within the Servitude no. n/a
Preferred Pole Heights
9m long poles Yes
Subject to
10m long poles
approval
Pole Planting Depth (minimum), ≤10.5m long pole m 1.5
Employer's Contractor's
Description Unit
Requirements Guarantee
Substations
Pole Mounted Substations no. 23
Ground Mounted Substations no. 1
Safety Fence Yes
Soil Classification
Soil Type E
Description Sandy Gravel
Depth to Water Table m < 2.0
Density of Uplift kg/m3 1800
Cone Angle deg. 30
Ultimate Bearing Capacity (at depth 2.0m) kN/m2 400
Soil Type F
Description Silt
Depth to Water Table m 0
Density of Uplift kg/m3 1600
Cone Angle deg. 25
Ultimate Bearing Capacity (at depth 2.0m) kN/m2 200
Soil Type G1
Description Clayey Silt
Depth to Water Table m > 2.5
Density of Uplift kg/m3 1600
Cone Angle deg. 15
Ultimate Bearing Capacity (at depth 2.0m) kN/m2 50
Soil Type G2
Description Clayey Silt
Depth to Water Table m 0
Density of Uplift kg/m3 900
Cone Angle deg. 10
Ultimate Bearing Capacity (at depth 2.0m) kN/m2 20
Soil Type H
Description Rock
Depth to Water Table m -
Density of Uplift kg/m3 > 1800
Cone Angle deg. > 30
Ultimate Bearing Capacity (at depth 2.0m) kN/m2 > 900
Pole Earthing
Continuous or gapped (along the pole) Continuous
Submittals
The following documents are to be submitted by the Contractor
Proposed Time Bar Schedule (for Design, Drawings
Submission, Manufacture, Supply, Construction & Yes
Comissioning)
Reference Lists Yes
Certified Design Test Reports Yes
All Other Data Requested in the Specifications Yes
QA Program & ISO Certification (9001 or 9002) Yes
Employer's Contractor's
Description Unit
Requirements Guarantee
Environmental Considerations
Component: Effect:
Tender Documents
ZETDC Tender No.______________________
Table of Contents
1 D-UC-01-001 GENERAL 11
1.1 General Requirements 11
1.2 Grounding 11
1.3 Environmental and Protection Requirements (EPRS) 11
1 D-UC-01-001 GENERAL
1.1 GENERAL REQUIREMENTS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
1.2 GROUNDING
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 5, Grounding.
60287-1-1 Electric cables - Calculation of the current rating - Part 1-1: Current rating
equations (100 % load factor) and calculation of losses - General.
60287-1-2 Electric cables - Calculation of the current rating - Part 1: Current rating
equations (100 % load factor) and calculations of losses - Section 2: Sheath
eddy current loss factors for two circuits in flat formation.
60287-1-3 Electric cables - Calculation of the current rating - Part 1-3: Current rating
equations (100 % load factor) and calculation of losses - Current sharing
between parallel single-core cables and calculation of circulating current
losses.
60287-2-1 Electric cables - Calculation of the current rating - Part 2-1: Thermal resistance
- Calculation of thermal resistance.
60287-2-2 Electric cables - Calculation of the current rating - Part 2: Thermal resistance -
Section 2: A method for calculating reduction factors for groups of cables in
free air, protected from solar radiation.
60331-11 Tests for electric cables under fire conditions - Circuit integrity - Part 11:
Apparatus - Fire alone at a flame temperature of at least 750 °C
60331-12 Tests for electric cables under fire conditions - Circuit integrity - Part 12:
Apparatus - Fire with shock at a temperature of at least 830 °C..
60502 Power cables with extruded insulation and their accessories for rated voltages
from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV).
60811-1-2 Common test methods for insulating and sheathing materials of electric cables
60840 Power cables with extruded insulation and their accessories for rated voltages
from 1 kV (Um = 1.2 kV) up to 30 kV (Um = 36 kV). Test methods and
requirements
60853 Calculation of the cyclic and emergency current rating of cables.
61443 Short-circuit temperature limits of electrical cables with rated voltages above
30 kV (Um =36 kV)
The resistance of the outer semiconducting screen shall not exceed 5 MΩ per meter cable core.
2.2.3 Screen
The screen is laid outside the core and in such a way that it is in electrical contact with the
semiconducting screens of the core.
The screen should consist of one layer annealed, round copper wires with a nominal cross-sectional
area according to Table 1.
The screen wires should be mainly evenly distributed around the circumference of the cable and the
number of wires should be chosen so that the medium distance between the wires does not exceed
4 mm.
The screen wires could be laid in one of the following ways:
a) Wires laid spirally around the cable.
b) The same as in a), but with the wires embedded in conducting material.
c) Wires laid in waveform on the cable. The wires should be embedded in conductive material in
order to remain in its places.
d) Wave formed bent wires laid in parallel with the longitudinal axis of the cable. The wires should
be embedded in conductive material in order to remain in its places.
2.2.4 Sheath
The outer sheath shall be made of black PVC or PE.
2.4 MARKING
2.4.1 Designation of Origin
The cable shall in its entire length carry a designation of origin, e.g. a thread, a tape or a durable
marking on the outer side of the sheath. The spacing between adjacent markings shall not exceed
1m.
2.4.3 Designation
Cable shall be designated according to CENELEC HD 361 S2.
Example:
Type, number of conductors x cross sectional area
N12XC7V-AR1x150
2.5 SPLICING
Splicing during manufacture shall, unless otherwise agreed, be done in such a way as to fulfil all
requirements stated in this specification.
Conductors may be spliced by welding or other equivalent method.
2.7 TESTING
2.7.1 General Test Conditions
2.7.1.1 Ambient Temperature
The ambient temperature shall be 20 ± 15 °C unless otherwise specified in the details for the
particular test.
measurement shall not be performed before the sample has been kept in the test room for at least
24h. The ambient temperature shall be measured in the immediate vicinity of the sample.
The resistance is determined with direct current. The measured resistance value of the conductor,
recalculated to 20°C using the factors given in IEC 60228 shall not exceed the resistance values
indicated in IEC 60228. The resistance of the shield shall not exceed the value stated in the relevant
cable standard or agreed upon between purchaser and manufacturer.
Requirements:
- elongation under
load, max. % 175
- elongation after
unloading, max. % 15
2.7.4.10.3 Ageing test on insulation
Ageing conditions:
- temperature (± 3°C) °C 135
- duration h 7 x 24
Test conditions:
- length of test piece m 0.3
- temperature (± 3°C) °C 130
- duration h 6
Requirements:
- max. permissible shrinkage % 4
Requirements:
- elongation under %
load, max. 175
- elongation after %
unloading, max. 15
2.7.4.10.4 Ageing test on sheath
Requirements before
ageing:
- tensile strength, min. N/mm2 12.5 12.5 10.0 12.5 12.5
- elongation, min. % 150 150 300 300 200
Ageing conditions:
- temperature (± 2°C) °C 100 100 100 110 135
- duration h 7x24 7x24 10x24 14x24 7x24
Requirements after
ageing:
- tensile strength, min. N/mm2 12.5 12.5 - - -
- variation in tensile
strength, max. % ± 25 ± 25 - - ± 25
- elongation, min. % 150 150 300 300 -
- variation in
elongation, max. % ± 25 ± 25 - - ± 25
Ageing conditions:
- temperature (± 2°C) °C 100
- duration h 7x24
Requirements after
ageing:
- loss of mass, max. mg/cm2 1.5
2.7.4.10.7 Pressure test at
high temperature
Test conditions:
- temperature (± 2°C) °C 80 90 90 115 90
- duration h 6 6 6 6 6
2.7.4.10.8 Heat shock test
Test conditions:
- temperature for
elongation test (± 2°C) °C 150 150
- duration h 1 1
2.7.4.10.11 Carbon black content
in PE or XLPE sheath
Requirements:
- nominal value % 2.5 2.5 2.5
- tolerance % ± 0.5 ± 0.5 ± 0.5
2.7.3.8 Capacitance
The capacitance shall be measured between conductor and shield.
The measured value shall not exceed the nominal value declared by the manufacturer by more than
8%.
a) If the type test is made only on one conductor cross-section, the test is valid also for cables with
different materials in the outer non-metallic sheath if the cables have the same rated voltage,
conductor cross-section and construction. A condition is, however, that the sheath cannot be
expected to influence the result of the type test and that the material in the sheath is already type
tested according to d) below.
b) If the type test is made on two different conductor cross-sections, the test is valid also for
conductor cross-sections in-between, on the condition that the calculated electrical field stress in
the cables with the intermediate conductor cross-sections is not greater than in the cable with the
smallest conductor-cross section and that the insulation thickness in any cable is not less than in
the cable with the biggest conductor cross-section.
c) A type test on a cable with a given rated voltage and conductor-cross section/sections is also
valid for cables with lower rated voltage and with the same conductor cross-section/sections and
construction on the condition that the same manufacturing process has been used and that the
calculated electrical field stress is not greater than in the cable subjected to the type test.
d) A type test on insulation and non-metallic sheathing materials according to clause 2.7.4.4 must
not be repeated on cables with different conductor cross-sections or rated voltages if the same
materials and manufacturing processes have been used. The ageing test on complete cable
according to clause 2.7.4.10.5 shall, however, be repeated if combinations of materials, which are
in contact with each other, differs from the combination already tested.
The electrical tests according to clause 2.7.4.10 shall be carried out on the same sample of cable
and in the sequence specified in the specification. The loss angle measurement according to clause
2.7.4.6 may, however, be carried out on a different sample.
The tests on insulation and sheathing materials according to clause 2.7.4.10 may be carried out in
an optimal sequence. Test conditions, test methods and requirements are given in the appropriate
clauses and in Table 2 for the XLPE-insulation and in Table 3 for different sheathing materials.
A test report with all test results and signed by either:
a representative of a competent witnessing body, or
a technically responsible representative of the manufacturer
shall be accepted as an evidence of a type test.
2.7.4.10 Tests for Determining the Mechanical Properties of Insulation and Sheath
The tests according to the following clauses may be carried out in an optional sequence. Test
methods, test conditions and requirements are given in the appropriate clauses and in Table 2 for
XLPE-insulation and in Table 3 for sheathing materials. The extent of the tests for different sheathing
materials is evident from Table 3.
R × π × (D − T ) × T
ρ=
2L
where:
R = Measured resistance in ohms
L = Distance between potential electrodes in metres
D = Diameter over the conductor screen in metres
R × π × (D − T ) × T
ρ=
L
where:
R = Measured resistance in ohms
L = Distance between potential electrodes in metres
D = Diameter over the insulation in metres
T = Average thickness of screen in metres
The measurements shall be carried out at a sample temperature of 90 ± 2 °C.
The resistivity both before and after ageing shall not exceed
1000 Ωm for the conductor screen
60060-1 High-voltage test techniques. Part 1: General definitions and test requirements.
60287-1-1 Electric cables - Calculation of the current rating - Part 1-1: Current rating
equations (100 % load factor) and calculation of losses - General.
60287-1-2 Electric cables - Calculation of the current rating - Part 1: Current rating
equations (100 % load factor) and calculations of losses - Section 2: Sheath
eddy current loss factors for two circuits in flat formation.
60287-1-3 Electric cables - Calculation of the current rating - Part 1-3: Current rating
equations (100 % load factor) and calculation of losses - Current sharing
between parallel single-core cables and calculation of circulating current
losses.
60287-2-1 Electric cables - Calculation of the current rating - Part 2-1: Thermal resistance
- Calculation of thermal resistance.
60287-2-2 Electric cables - Calculation of the current rating - Part 2: Thermal resistance -
Section 2: A method for calculating reduction factors for groups of cables in
free air, protected from solar radiation.
60331-11 Tests for electric cables under fire conditions - Circuit integrity - Part 11:
Apparatus - Fire alone at a flame temperature of at least 750 °C
60331-12 Tests for electric cables under fire conditions - Circuit integrity - Part 12:
Apparatus - Fire with shock at a temperature of at least 830 °C.
60811-1-2 Common test methods for insulating and sheathing materials of electric cables
6 0.7
16 0.7
50 1.0
95 1.1
150 1.4
240 1.7
3.2.3 Lay-Up
The mean value of the length of lay for the cores shall be not more than 50 times the diameter across
the laid up cores.
<25 1.0
(25)-35 1.2
(35)-45 1.4
(45)-60 1.6
(60)-80 1.8
>80 2.0
The thickness of the tape filling layer should be 0.4 mm for diameters 40 mm under the layer. For
greater diameters the thickness should be increased to 0.6 mm.
The stated values are approximate.
3.2.5 Sheath
The sheath shall be black and of PVC with a nominal thickness according to Table 6 below:
4 x 16 Round 1.8
4 x 50 Round 1.9
4 x 95 Sector 2.1
3.4 MARKING
3.4.1 Designation of Origin
The cable shall in its entire length carry a designation of origin, e.g. a thread, a tape or a durable
marking on the outer side of the sheath. The spacing between adjacent markings shall not exceed
1m.
3.4.3 Designation
Cables shall be designated according to CENELEC HD 361 S2.
Example:
Type, number of conductors x cross sectional area
N1XV-AS4x150
3.5 SPLICING
Splicing during manufacture shall, unless otherwise agreed, be done in such a way as to fulfil all
requirements stated in this specification.
Conductors may be spliced by welding or other equivalent method.
3.7 TESTING
3.7.1 General Test Conditions
3.7.1.1 Ambient Temperature
The ambient temperature shall be 20 ± 15 °C unless otherwise specified in the details for the
particular test.
l • R • 10 −11
Ki = =10 −11 × 0. 367 × σMΩkm
D
lg
d
The calculated value of Ki must not be less than 0.037 MΩkm.
3.7.4.2 Type Test of the Mechanical Properties of the Insulation and the Sheath
3.7.4.2.1 Measurement of Insulation Thickness
The insulation thickness is measured on every core of the cable according to clause 3.7.3.2 above.
Cable weight
Conductor resistance in ohms/km.
Inductance in mH/km.
Capacitance in nF/km.
The value of the insulation resistance.
61442 Electric cables - Test methods for accessories for power cables with rated
voltages from 6 kV (Um = 7.2 kV) up to 30 kV (Um = 36 kV)
4.2.3 Instructions
Instructions in Portuguese shall be included in all joints and terminations and consist of detailed
instructions for all steps that are important for the quality of supply.
During type tests this instruction should be followed.
At the rated load, and with the ambient temperatures given above, there shall be no abnormal ageing
of the included material.
Furthermore consideration shall be paid to the fact that material in direct contact with the conductor
shall be able to withstand the overload and short-time temperatures that the conductor is allowed to
assume according to the applicable standards.
4.2.5.2 Terminals
The current outlet can consist of a cable lug, plate or smooth bolt of copper or aluminium with or
without surface coating.
Connectors for the earth conductor shall be provided for terminations with metallic covering. This
connector can, depending on the design of the termination, also serve as an earth connection for the
cable screen, metal sheath and armouring.
Earthing of the latter can also be done using a special earthing device. Special attention should be
paid to the method of earthing the armouring of single-phase cables when the armouring can carry
current.
In certain cases a connector for the earth conductor, according to the above, can also be specified
for a cable joint.
Unless otherwise stated, the test specimen shall be at ambient temperature during the test.
The test specimen shall be arranged according to Clause 4.3.2.4 above. The cable used for the
setting up shall have a length of at last 3 m outside the test specimen and shall have about the same
resistance/length value as the cable conductor.
The test specimen, connection points and cable shall be mounted securely on to a stable base.
Single-phase termination
A single-phase termination can be set up according to one of the following alternatives:
a) Three (or with two-phase testing two) similar test specimens are installed in parallel to each other
at the same height and with a mutual net distance.
b) Two (or in the case of two-phase testing one) of the test specimens in accordance with a) are
replaced by a busbar, the centre line of which coincides with that of the replaced test specimen.
The busbar shall be at least as long as the test specimen and securely fixed along its whole
length.
Note: If special accessories are supplied with single-phase terminations so that they can be
combined to form a three-phase device, these accessories shall be used for the test set-up. Three
single-phase terminations shall be set up and considered as one three-phase termination according
to three-phase termination with fixed terminals.
The testing should be carried out using the It, t and is values thus obtained. If the test equipment
does not allow all of these values to be met, the value of is must, however, always be met. Deviation
from the short-time current value It given above is permissible, in which case the short-circuit time tx
shall be converted using the formula
2
I
t =
x
t
2 ×t
I x
tx = 0.2 . . . 5 s
2) Visual inspection
After the electrical tests according to 1) above, the different components of the termination
shall be visually inspected in connection with dismantling. A check is then made that no
essential changes or damages have occurred during the tests.
A couple of complete type tests according to Table 8 should be carried out on each type of joint. The
number of type tests is determined according to the following principles:
a) At least two conductor areas should be tested for each type of joint. If the joint can be used for
jointing of different cross-sectional areas, at least one joint should be tested in this arrangement.
The type of cable materials, cross-sectional areas, etc., that can be assumed to be the most
difficult to joint, should be tested.
b) The test shall be carried out on XLPE-insulated cable.
Concerning number of test specimens in each type test and the arrangement of the test circuit see
clause 4.4.5 above.
If, during the type test according to Table 8, any of the test specimens does not withstand one of the
tests, the whole type test should be carried out on a new set of test specimens.
However, the test according to clause 4.4.6.1 above does not have to be repeated if it was approved
during the first test.
As long as the design and material remain unchanged, or are not changed in such a way as to impair
the properties investigated in the type tests, these tests need not to be repeated.
considered. If, at single-phase connection, all four conductors in a four-core cable are loaded in order
to get a symmetrical current in the cable, the current should be reduced by the factor 0.87.
5.2 TYPES
Cable lugs should be supplied for the following types of conductor:
Al-conductor 50, 70, 95, 150, 240 and 300 mm2.
Cu-conductor 6, 16, 25, and 35 mm2.
6.2 PACKING
The warning tapes shall be delivered in rolls in 250 m lengths.
7.1.1 Testing
Verification of impact resistance is performed by a drop weight with a mass of 10 kg and with a point
according to Fig. 1. The test is performed at an ambient temperature of ±0 ± 2°C and at +45 ±2 °C.
7.1.2 Packing
The protection sheets can be delivered either in short lengths down to 0.80 m or in large lengths of
several metres as rolls. When delivered in short lengths the ends of the sheets shall be formed as
notch and studs to lock the one to the other.
The foundation, fasteners and enclosure of the cable pillars shall be of a mechanical strength
sufficient to withstand the stresses they may be subjected to by man or a manually driven tool or
vehicle that unintentionally comes into contact with the cable pillar.
Parts of steel in the foundation and enclosure should be protected against corrosion by hot-dip
galvanisation or other similar treatment.
At the bottom of the pillars there shall be a bar equipped to support each cable.
The cable pillars shall be of the following size:
a. Pillars for the connection of 6 three-phase cables minimum, four (4) fused 6 to 95 mm2 and two
(2) direct connected 95 to 300 mm2. When used as junction pillars only, they shall be able to be
equipped for connection of six (6) cables of 95 to 300 mm2.
b. Pillars for the connection of six (6) three-phase cables minimum, four (4) fused 95 to 300 mm2
and two (2) direct connected 95 to 300 mm2. When used as junction pillars only, they shall be
able to be equipped for connection of six (6) cables of 95 to 300 mm2.
Opening for
emergency
cables
min. 90 mm
0.1 m
Ground surface
Cable pillars shall have sufficient strength against pointed objects penetrating the enclosure
8.4 FOUNDATION
The foundation shall be made of steel to be buried into the ground and equipped with bolts or other
arrangements for mounting the pillar to its top. It shall be high enough to be buried to a depth of 0.80
m underground minimum with the cabinet in correct position.
The foundation itself and its connection to the cabinet shall be strong enough to withstand all possible
forces that can be transferred from the cabinet.
The foundation shall be designed to protect the cables connected to the pillar from mechanical
damage down to a depth of 0.30 m underground minimum. Below this level it shall allow the cables
to enter from cable trenches both in front and behind the pillar. This means that the bottom of the
foundation ought to be "frame shaped". The base of the foundation shall have a bottom plate with a
size of 0.30 x 0.80 m minimum.
If the foundation is made of steel and includes parts, exposed to persons from the outside of the
pillar, or to persons doing work inside the cabinet, it shall have an earthing connection to the neutral
busbar. The equipment needed for such earthing should, if the design so requires, be delivered as
an integrated part of the foundation.
8.6 TESTING
8.6.1 Type Test
8.6.1.1 Verification of the Short-circuit Strength
8.6.1.1.1 Testing of the Main Circuits
It is assumed that half the maximum numbers of feeding groups in the pillar in a parallel connection
co-operate during the feeding of the short-circuit current (e.g. if the maximum number of feeder
cables possibly to connect is 6, then 3 of these are assumed to feed the short-circuit current) and
that the rated current of the equipment for the connection of the feeder cables as well as the rated
current of the fuses is limited (e.g. to maximum 400 A).
Fig. 3: Steel Ball for Verification of Resistance Against Penetration by Pointed Objects
60947-3 Low voltage switchgear and control gear. Part 3: Switches, disconnectors,
switch-disconnectors and fuse-combination units.
8.8.2 General
The knife blade fuse switches should be intended for cable pillars.
The knife blade switches should include switch covers.
The knife blade fuse switches shall fulfil the requirements for IP20 according to IEC 60529.
The knife blade fuse switches should comply with switching capacity AC23 according to IEC 60947-
3.
The connection and disconnection of cables shall be possible to do under live conditions with special
insulated tools (spanners). No pressing shall be needed.
The knife blade fuse switches should be designed in such a way that fuses can be changed in a safe
and simple manner without use of special tools.
The knife blade fuse switches should be of the following two sizes:
a) Size 00 according to DIN 43 620, i.e. rated current 160 A and intended for gl fuses according to
IEC 60269-2A and include connection terminals for Cu/Al-conductors 6 - 95 mm2.
b) Size 02 according to DIN 43 620, i.e. rated current 400 A and intended for gl fuses according to
IEC 60269-2A and include connection terminals for Cu/Al-conductors 50 - 300 mm2.
60238 Compression and mechanical connectors for power cables with copper or
aluminium conductors.
8.9.2 General
The terminal clamps should be intended for direct connection of copper or aluminium conductors to
the busbars in the cable pillar.
The terminal clamps shall fulfil the requirements for IP20 according to IEC 60529.
The connection and disconnection of cables shall be possible to do under live conditions with special
insulated tools (spanners). No pressing shall be needed. The connection equipment shall be
designed for both Aluminium and Cu-conductors.
The terminal clamps should be of the following three types:
a) Direct connection of Cu/Al conductor 50 - 300 mm2.
b) Direct connection of PEN-conductor Cu/Al 6 - 95 mm2.
c) Direct connection of PEN-conductor Cu/Al 50 - 300 mm2.
Fig. 2 Cable Trench – 33/11 kV. LV and signal cables in the same trench.
1.2
0.55
Pipe
When Installed 10 x De 8 x De
Tender Documents
ZETDC Tender No.______________________
Table of Contents
C8 – DISTRIBUTION DRAWINGS 6
1 DISTRIBUTION DRAWINGS 7
1.1 Preamble 7
1.1.1 General ................................................................................................................................................. 7
1.2 Distribution Line drawings 7
1.2.1 33kV Poles, Crossarms, Stays, Hardware and Fittings ........................................................................ 7
1.2.2 11kV Poles, Crossarms, Stays, Hardware and Fittings ........................................................................ 8
1.2.3 LV Line Drawings ................................................................................................................................. 9
1.2.3.1 For Aerial Bundled Conductors (ABC) 9
1.2.3.2 For All Aluminium (AAC) or Hard Drawn (HDA) Condours 9
1.2.4 Sag and Tension Charts ....................................................................................................................... 9
1.2.5 Substation Drawings ............................................................................................................................. 9
C8 – DISTRIBUTION DRAWINGS
1 DISTRIBUTION DRAWINGS
1.1 PREAMBLE
1.1.1 General
For an evaluation of tenders to be made, Tenderers (Contractors) shall supply drawings marked
“Issued for Tender Purposes Only”. Detailed drawings will need to be provided by the successful
Tenderer at detailed design stage.
Tenders supplied without drawings will cause the Technical Proposal to be regarded as incomplete.
The drawings supplied by the Employer/Engineer with this tender are only conceptual, and tenderers
shall refer to the drawings in coming up with their drawings to be issued with their tender submittals.
Where any of the Employer/Engineer’s conceptual drawings have dimensions, these shall be verified
by the Tenderer/Contractor, in accordance with the requirements set out in Section VI(C)7 - Technical
Schedules.
Particular requirements shall also be obtained from the Employer before commencement of detailed
manufacturing or placement of orders with Suppliers.
The design assumes that the 11kV and 33kV lines shall be constructed with a continuous earthwire
down the pole (without gaps) to prevent shattering of the pole.
Tender Documents
ZETDC Tender No.______________________
Table of Contents
Mozambique to the Feruka Oil Refinery and ultimately to Harare, where fuel is then distributed
nationally. Water transport is dominated by waterborne tourism, leisure activities, commercial and
small-scale fishing and sports on the Kariba Dam, the Zambezi River and other inland large dams.
There is however potential for water transport.
1.1.3 Background
The Karoi load is currently being supplied through 3 x 33kV, 54km feeders from Mhangura 88/33kV
substation which is an old substation. The 3 feeders also supply Tengwe, Magunje and Karoi North
loads with a lot of t-offs along the way. The network is characterized by overloaded 11kV and 33kV
lines. As a result of the existing capacity constraints, new customers can no longer be connected.
The line has an existing load of 12MVA with a suppressed demand of about 8MVA. Considering load
projections for areas in and around Karoi, a 33kV network can no longer sustain the load demands,
hence the proposal for a new 132kV Alaska- Karoi line and a substation at Karoi
• A new 132 kV line bay at existing Alaska 132/88kV substation, fully equipped;
• A new 132kV line (approximately 85km long) from Alaska Substation to a new 132/33kV
substation at Karoi;
• A new 132/33kV substation at Karoi;
• Connection of 3 existing 33kV lines to the new substation at Karoi, supply and construction;
• Supply and construction of 23km of new 11kV lines and installation of associated distribution
transformers;
• Supply and construction of 13km of new LV lines;
• Supply of distribution materials for refurbishment of existing MV and LV distribution networks
including distribution transformers;
• Supply of LV materials for connection of 4800 customers, inclusive of conductors, cables,
fittings, pre-paid meters, poles, fittings and other associated materials necessary for complete
supply.
1.1.5 Project Objective
The objective of the project is to strengthen and increase the country’s sub- transmission network
capacity resulting in increased reliability and quality of electricity supply in and around Karoi area
inclusive of LV reticulation, resuscitation and extension of 11kV lines and downstream 33kV network,
required to improve the quality of electricity supply within Karoi town, Makonde and Hurungwe
districts, thereby enabling increased economic activity for the local populace. Further, the project will
enable ZETDC to connect new consumers to their electricity grid and also improve environmental
quality by the use of cleaner electricity, replacing the current dependency on diesel generators and
firewood.
• Rerouting of 3 x 33kV lines from existing Karoi 33/11kV substation to be supplied from the
proposed Karoi 132/33kV substation located in Mashonaland West Province, Zimbabwe;
• Supply and construction of 23km of new 11kV lines in Karoi town;
• Supply of materials for 13km of new LV lines in Karoi town (Client will construct);
1.2.1 3 x 33kV Lines from Existing Karoi 33/11kV – Proposed Karoi 132/33kV
Substation
The 33kV distribution lines will consist of three (3) single circuit line strung with three (3) conductors
per phase of ACSR (SCA) Dog as specified in the Technical Schedules in this document. .
The works to be carried out for the 33kV distribution lines under this Contract will include but not be
limited to; e.g.
All works shall be executed as described in the specifications and/or as shown on the drawings.
Tender Documents
ZETDC Tender No.______________________
1 09 August 2020 Part 2: Employer’s Requirements, Distribution Lines & TRK OLO OLO
Substations (Volume 2C) - Section VI(C)2 – Distribution
General Specifications (revised)
Revision Date: Description Compiled Checked Accepted
Table of Contents
1 D-GS-01-001 GENERAL 10
1.1 Standards 10
1.2 Plant and Equipment 10
1.3 Workmanship 10
1.4 Design and Engineering 10
1.5 Climatic Conditions 10
1.6 General Electric Data 11
1.7 Documentation 11
1.7.1 General ............................................................................................................................................... 11
1.7.2 Documentation for Design and Manufacture ...................................................................................... 12
1.7.3 Documentation for Installation ............................................................................................................ 12
1.7.4 As-Built Documentation ...................................................................................................................... 13
1.7.4.1 General 13
1.7.4.2 General Manuals 13
1.7.4.3 Network Design Documentation 13
1.7.4.4 Material Documentation 13
1.8 Manufacture 14
1.9 Site Regulations, Safety and Environmental 14
1.10 Quality Control 14
1.11 Site and Commissioning Tests 15
1.12 Packing and Transport Marking 15
1.13 Corrosion Protection and Painting 15
1.13.1 General ............................................................................................................................................... 15
1.13.2 Galvanizing ......................................................................................................................................... 15
1.14 Wayleaves 16
1.15 Line Survey 16
1.16 Bush Clearing and Access Road 16
1.17 Commissioning of the Works 17
1.18 Maintenance Period 17
4 FOUNDATIONS 27
4.1 General 27
4.2 Soil Classification 27
4.3 Ground Excavations 28
4.4 Anchoring of Wooden Poles in Firm Soil Without Wedging 28
28
4.5 Anchoring of Wooden Poles in Firm Soil and on Rock with wedging 28
4.6 Anchoring of Wooden Poles in Soil of Low Bearing Capacity (Concrete or Plastic Pipe) 29
4.7 Anchoring of Wooden Poles in Soil of Low Bearing Capacity (Anchoring Logs) 30
4.8 Anchoring of Wooden Poles in Soil of Low Bearing Capacity (Anchoring Logs Reinforced Design) 31
4.9 Anchoring of Stayed Wooden Poles on rock 32
4.10 Anchoring of Stayed Wooden Poles on Soil Covered Rock 33
4.11 Anchoring of Concrete Poles in Firm Soil 33
4.12 Anchoring of Concete Poles in Soil of Low Bearing Capacity 34
4.13 ANchoring of Concrete Poles in Loose Sand 34
4.14 Anchoring of Steel poles 34
4.15 Stay Anchoring 34
4.15.1 Stay Anchoring in Firm Soil ................................................................................................................ 34
4.15.1.1 Mooring Screw 34
4.15.1.2 Concrete Disc and Railway Sleeper 35
4.15.2 Stay Anchoring in Soil of Low Bearing Capacity ................................................................................. 35
4.15.3 Stay Anchoring on Rock ..................................................................................................................... 36
4.15.4 Strut Pole ............................................................................................................................................ 36
5 GROUNDING 38
5.1 General 38
5.2 Earthing Rods 38
5.3 Earth Conductors 38
5.4 Connections 39
5.5 Grounding of 33kV and 11kV OH-Lines 39
5.6 Grounding of SWER OH-Lines (If Applicable) 39
5.7 Grounding of 0.4kV OH-Lines 40
5.8 Grounding of Underground cable Networks 41
5.9 Grounding of Pole Mounted Transformers 41
5.10 Grounding of Substations 43
1 D-GS-01-001 GENERAL
1.1 STANDARDS
All material used and equipment supplied and all workmanship and tests shall be in accordance with
the latest editions of IEC and ISO Standards, or where International Standards are not applicable,
with national standards, such as ANSI, ASTM, SANS, BS or VDE + DIN. Where such standards and
codes are national or relate to a particular country or region, other authoritative standards that ensure
substantial equivalence to the standards and codes specified will be acceptable.
Where no standards exist, as in the case of patent or special materials, all such materials and
workmanship shall be of the best quality, and full details of the material and any quality control tests
to which they may be subject shall be submitted to the Purchaser/Employer/Engineer for approval.
1.3 WORKMANSHIP
All work, methods of work and workmanship, whether fully specified herein or not, shall be of the
highest order. In all respects, the generally accepted requirements and commonly recognised good
practice for first class work of this nature are to be adhered to. All work shall be to the satisfaction
and approval of the Purchaser/Engineer.
1.7 DOCUMENTATION
1.7.1 General
The sizes of all documents and drawings shall conform to the ISO standard, and be of size A1, A2,
A3 or A4.
Larger sizes than A1 shall be avoided.
Maps, schematic diagrams, and apparatus lists shall have a size of A3 or A4. Scales to be used on
the drawings shall be 1:10, 1:20, 1:25, 1:50 and multiples of this series.
All text in the documentation shall be in the English language, and where the text refers to operational
and warning labels the Portuguese text shall also be indicated.
a. Data specifications.
b. Routine test certificates.
c. Data lists with by the Engineer required amendments incorporated. The contents of the lists
shall correspond to the schedules of this document. Data lists will be regarded as binding for
the manufacturer.
d. Dimension drawings. They shall be regarded as binding for the manufacturer and shall contain
measures, weights and features of the apparatus.
e. Detail drawings as required by the Engineer.
f. List of components and details of the apparatus. They may preferably be included in the
dimension sketch.
In case of alterations, new documents shall be issued.
1.8 MANUFACTURE
Before commencing any manufacture of the Plant the Supplier/Contractor shall submit for the
approval of the Purchaser/Engineer, the names of the manufacturers from whom he proposes to
order the material and the names of the subcontractors from whom he proposes to order any parts
of the Plant.
After such approval has been given, the manufacture shall be planned and performed according to
the Specifications and to the satisfaction of the Purchaser/Engineer.
The Purchaser/Engineer shall be afforded every opportunity to control and inspect the manufacture
and testing of materials in the steelworks, rolling mills, foundries etc., and their assembly in the
workshops of the Contractor and his Subcontractors.
The Supplier/Contractor shall provide all instruments and equipment necessary for testing. The test
reports shall be submitted to the Purchaser/Engineer, in three copies, for review and approval.
1.13.2 Galvanizing
Except where otherwise specified, all ferrous parts shall be galvanized.
Galvanizing shall be applied by the hot-dip process and shall consist of a continuous coating to
minimum weights as follows:
Weights g/m²
Rolled steel exposed to the atmosphere only 600
Rolled steel under the ground surface 1500
Cast iron and malleable iron 600
Bolts, nuts and washers 375
The zinc coating shall meet the requirements according to ISO 1461, ASTM, A123, A153 and A767.
All steel shall be fully fabricated before galvanizing, no machine or shop work, boring, punching, etc.
will be allowed after galvanizing.
1.14 WAYLEAVES
The Contractor will be provided with a full list of Way leaves, in respect of the line route from which
he shall ascertain whether there are any impediments on the route, and if any, it shall be brought to
the attention of the Authority before the work commences.
Should the Contractor wish to make a staff camp on any property he shall first obtain written authority
to do so from the occupant of such property, at the same time he shall keep the Client informed in
writing of any such arrangement. The Contractor shall be responsible for the movements of the
labour force from the camp site, to prevent trespass and to protect the interests of the Occupant or
Owner.
When the contractor is about to commence work on any property he shall be responsible for
ascertaining from the Client that the Wayleaves are in order and for giving the Occupant of such
property adequate notice of his intention to commence work thereon.
In any case, the contractor shall take steps to avoid damage or interference to farm road, ploughed
lands, watercourses, contours and land ridges to avoid soil erosion. The contractor shall pay for any
damage made as a result of his activities outside the wayleave area.
Arrangement will normally have been concluded by the Client with property owners for the removal
of buildings within the wayleaves strip before the contractor commences work. However, the
continued presence of such buildings should be notified to the Client without delay.
Q = 0.625×V 2×A×C
where
Q = wind load in N
V = wind speed in m/s
A = effective frontal area in m2
C = drag factor = 1.0
2.3.3 Conductors
The following design limitations shall apply to the conductors:
Conductors:
Temperature +10° C, still air, initial tension not exceeding 25% of the UTS
Temperature +20° C, still air, final tension not exceeding 20% of the UTS
2.5 CLEARANCES
2.5.1 Conductor Clearance to Ground and Objects on the Ground
The following minimum clearances shall be maintained at a maximum conductor temperature of
+70oC in still air and final sag, i.e. pole spotting temperature:
Table A: Ground Clearance on road-crossings and elsewhere
Line Voltage To ground elsewhere Above normal roads Above major roads
400V 4.9 5.5 6.5
11 000V 5.2 5.8 7.0
33 000V 5.2 5.8 7.0
2.5.3 Airports
Always take contact with the airport authorities before planning any overhead lines close to airports
since the recommendations are different for different categories of airports. The following is an
extract from ICAO Annex 14 to the Convention on International Civil Aviation, Aerodromes Volume
1, Aerodrome Design and Operations. Chapter 4, Obstacle Restriction and Removal.
As a general rule no fixed object, other than visual aids required for air navigation purposes, shall be
permitted on a runway strip:
a) within 77.5 m of the runway centre line of a precision approach runway category I, II or III where
the code number is 4 and the code letter is F; or
b) within 60 m of the runway centre line of a precision approach runway category I, II or III where
the code number is 3 or 4; or
c) within 45 m of the runway centre line of a precision approach runway category I where the code
number is 1 or 2
The table below gives the surfaces where no obstacles are allowed.
RUNWAYS MEANT FOR TAKE-OFF
Code Number
Surface and Dimensions 1 2 3 or 4
TAKE-OFF CLIMB
Length of inner edge 60 m 80 m 180 m
Distance from runway end 30 m 60 m 60 m
Divergence (each side) 10% 10% 12.5%
Final width 380 m 580 m 1 200 m
Length 1 600 m 2 500 m 15 000 m
Slope 5% 4% 2%
2.5.4 Conductor Configuration and Phase Distances for 33 kV and 11 kV Lines with
Bare Conductors
In all standard configurations horizontal configuration of the conductors shall be used. The insulators
shall be fitted on a cross arm.
The minimum horizontal spacing between fixing points of conductors on the cross arm shall be
derived from the following formula:
where:
D = horizontal spacing in m
f = final conductor sag at +70° C in m
l = length of insulator set in m (l = 0 for line-post insulators)
U = highest voltage in kV
In exceptional cases vertical configuration of the conductors can be used, i.e. at double circuits in
urban areas or similar. A special design has to be made from case to case and calculations and
drawing shall be submitted for approval by the Client. The minimum vertical spacing between fixing
points of conductors on the poles shall be derived from the following formula:
where:
V = vertical spacing in m
f = final conductor sag at +70 °C in m
l = vertical length of insulator set in m
U = highest voltage in kV
The vertical configuration is not recommended for normal standardized line construction.
3.2 MATERIALS
Materials for steel members such as crossarms shall comply with the requirements for materials in
the General Requirements.
All ferrous parts shall be galvanized.
Poles shall be designed with a minimum number of joints. Slip joints shall be designed for a minimum
overlap 1-1/2 times the inside diameter the female section at the joint, as per ASCE No. 72.
A removable plastic top cap shall be fitted to the pole.
All material shall be in accordance with the relevant standards referred to within this specification.
The poles shall be hot dip galvanized in accordance with the General Requirements, Clause 1.13.
3.6.2 Markings
The poles should be marked with length and year of manufacture. The marking should be placed 4
m from the base.
F C C
E
D
NOTE: Reference shall also be made to the Client’s specific requirements in accordance with the
drawings applicable to the project.
E
Mounting bracket welded to cross-
arm.
Cross-arm mounted in line or
above pole top.
Middle insulator can be mounted
symmetrical on cross-arm
NOTE: Reference shall also be made to the Client’s specific requirements in accordance with the
drawings applicable to the project.
4 FOUNDATIONS
4.1 GENERAL
Foundations shall be designed for all specified pole types for good and poor soils, both in dry and
fully submerged conditions and for rocks.
The foundations shall be designed to resist uplift, overturning and vertical and horizontal pressure.
Foundations shall also be able to withstand the stresses, which may be imposed upon them under
erection and stringing operations.
Poles on rock are normally anchored by rock pegs and bars on earth covered rock, also root pegs
can under certain circumstances be used.
Poles in soil are anchored in a way that ensures complete safety in a pit and to a depth suited to
ground conditions and type of pole.
Ultimate loads derived from the pole design shall be increased by 10% for application in the
foundation design. Where unstable soil conditions exist, as well as lack of sufficient soil data, an
increased load factor can cover uncertainties of the design.
The responsibility for proving the adequacy of the foundation type of each pole site shall rest with
the Contractor. All necessary soil surveys, including field or laboratory tests, shall be undertaken by
the Contractor. The results of these tests shall be recorded by the Contractor and submitted to the
Engineer.
NOTE: Reference shall also be made to the Client’s specific requirements in accordance with the
drawings applicable to the project.
G: Clayey silt - Soil of low bearing capacity. This class comprises saturated silts, soft clays
and organic soils.
H: Rock
PS2
Upper Wedging *)
Excavated
Depth
n Firm Soil
l
Lower
Wedging
Base Plate
Ø 1000 mm
*) Upper wedging to be made of crossed standard sleepers cut in order to obtain a good fit
between pole and pipe
Excavation depth and length of pipes**) at different length of poles
Class n l n l n l n l n l n l
BS:1990
Medium 2.0 2.0 2.0 2.5 2.3 2.5 2.3 3.0 2.3 3.0 2.3 2.0
Stout 2.0 2.0 2.0 3.0 3.0 2.6 2.6 3.0 2.6 4.0 2.6 4.0
**) If glass fibre reinforced plastic pipes are used the length (l) shall be increased by 200 mm.
3000 mm
min. 200mm
500
min. 1000 mm
7500 mm
Direction of line
1000 mm
7500 mm
1000 mm
180 mm
Bollards
The ties should be made of timber with dimensions 75x125 mm or poles with well jointed cross-bars
fixed with nails underneath the ties.
The ties are to be placed on both sides of the line and should cross the line in order that the ends of
the top jointed logs are placed on the ties.
The two logs with a medium diameter of approx. 180 mm are joined together and with the pole-leg
by a through bolt.
The pole-leg is stayed using min. 50mm2 stay wire, both for the transverse and parallel line directions.
The stays are fastened with a stay link at both ends of the log.
Before backfilling of excavated material two bollards shall be nailed to the pole and the transversal
logs.
All timber should be pressure impregnated.
3000 mm
min. 1000 mm
7500 mm
Direction of
line
1000 mm 7500 mm
850 mm
Bollards 180 mm
The ties should be made of timber with the dimensions 75x125 mm or poles well jointed with cross-
bars fixed with nails underneath the ties.
The ties to be placed on both sides of the line and cross the line in order that the ends of the top
jointed logs are placed on the ties.
The two logs with a medium diameter of approx. 180 mm are joined together and with the pole-leg
by a through bolt. The pole-leg is stayed using min. 50 mm2 Fe stay wire both transverse and parallel
to the line direction. The stays are fastened with a stay link at both ends of the log.
Before backfilling of excavated material two bollards shall be nailed to the pole and the transversal
logs.
All timber should be pressure impregnated.
PR1
PR2:1 PR2:2
≥ 0.5 m
PC:1
Concrete C15
PC:2
0.5m
8 x Ø 16 mm
Stirrups Ø 8 mm Min. 2.0 m (33/SWER/11 kV)
C/C 200 mm Min. 1.5 m (0.4 kV)
Concrete C20
PC:3
Backfilling
Concrete Beams
Sand
Concrete Plate
The rotation will end when the upper part of the anchor is level with the surface. The handle is then
pulled up and an eye bolt is threaded on to the top end. Max. allowed twisting moment is 650 Nm.
FS0
Approx.
1500mm
n n
Stay FS1 (Concrete Disc.) FS2 (Sleeper = 850 mm) FS2 (Sleeper = 1300mm) FS2 (Sleeper = 2600mm)
Dist. Bearing Bearing Bearing Bearing
Good Medium Good Medium Good Medium Good Medium
L Dry Water Dry Water Dry Water Dry Water Dry Water Dry Water Dry Water Dry Water
logged logged logged logged logged logged logged logged
½S 1.5 1.8 1.6 1.9 1.0 1.7 1.4 1.8 1.5 1.9 1.6 2.1 1.4 1.6 1.6 1.8
2/3 S 1.4 1.7 1.5 1.8 1.2 1.5 1.3 1.6 1.4 1.8 1.5 2.0 1.3 1.5 1.5 1.7
S 1.3 1.6 1.4 1.7 1.1 1.4 1.2 1.5 1.2 1.6 1.4 1.8 1.2 1.4 1.4 1.6
Where:
L = distance between the stay and the pole at ground level (in m).
S = distance between the ground and stay attachment on the pole (in m).
The above table to be used if ground water level is below 0.5 m, if not use anchoring type FS3, FS4
or FS5.
n n n
Stay Wire Stay Distance Soil, Shear Strength ~ 4N/cm2 Soil Shear Strength < 4N/cm2
(L) FS3 FS3 FS5 FS4 FS5
L = 1300mm L = 2600mm L = 2600mm L = 2600mm L = 2600mm
25 GSW S 1.5 1.1 1.4
50 GSW S 1.8 1.2 2.0
70 GSW S 1.6 1.6 *)
Where:
L = distance between the stay and the pole at ground level.
S = distance between the ground and stay attachment on the pole.
*) Backfilling with heavy material.
FR1 FR2
Extension link
Eye bolt
5 GROUNDING
5.1 GENERAL
All equipment cases and tanks shall be grounded. On pole mounted or supported equipment, the
cases or tank ground shall be 25 mm2 Cu-wire minimum and shall be carried between the tank and
the ground down lead.
Metal supports (frames, racks or platforms) supporting equipment shall be grounded in the same
manner as set forth above for equipment case ground.
This ground shall also serve as the tank for all equipment directly attached to the metal frame with a
clean tight connection.
Gang operated switch handles shall be grounded
Lightning arresters shall be connected to a driven ground located at the same pole as the arrestors.
The ground wire shall be kept as short and direct as possible.
The resistance shall be less than 10 ohms. The resistance of a separate driven ground shall not be
higher than 100 ohms if the contact resistance should be considered as a constant value.
The exposed length, 3m above ground and 0.5m underground of an earthing wire should be
protected against vandalism, e.g. by steel pipe. All costs for such arrangements shall be included in
the Contract price.
The maximum permissible current/mm2 during 1 second for different conductor material, and
equivalent electrical cross-sectional area factor is:
Copper 200 A 1 (i.e. 25mm2)
Aluminium 100 A 2 (i.e. 50mm2)
Steel 65 A 3.1 (i.e. 95mm2 standard size)
The minimum cross-sectional area of ground wires according to the Regulations is 16 mm2 Cu above
ground and 35mm2 in ground or equivalent electrical cross-sectional area of other material.
NOTE: Reference shall also be made to the Client’s specific requirements in accordance with the
drawings applicable to the project.
5.4 CONNECTIONS
The ground wire shall be directly connected to the pole with bolted connectors of an approved
material suitable for use with the ground wire such that galvanic action, i.e. chemical reaction
between copper and galvanised steel, is minimised.
Down lead
To be installed 180º
opposite the handle
Cu 25 mm2
or equivalent
Protection
3200 mm
500 mm
Grounding of Disconnector
1 core 50 mm2
ABC Cable or to
Client’s spec
Min. 50 mm
Protection
3200 mm
500 mm
Ground wire
GSW 95 mm2 Earthing rod
Grounding of Substation
6 ENVIRONMENTAL PROTECTION
REQUIREMENTS
6.1 INRTODUCTION
This chapter outlines the Contractor’s duties and responsibilities with respect to environmental
protection during the execution of the project. This Chapter shall be read in conjunction with Part 4
– Specifications for Worksite Environmental, Social, Health and Safety Management (ESHS) -
(Volume 4). Where there are any discrepancies between this Section 14 (T-S-11-001 –
Environmental Protection Requirements) and Part 4 – Specifications for Worksite Environmental,
Social, Health and Safety Management (ESHS) - (Volume 4), the provisions as provided in Part 4 –
Specifications for Worksite Environmental, Social, Health and Safety Management (ESHS) – Volume
4, shall take precedence after first seeking clarity with the Employer/Engineer.
Note: In the specifications, the terms: He/Her; His/Hers; Its, etc are gender neutral.
The Contractor shall carry out the specified environmental protection requirements to the approval
of the Employer.
The Contractor shall also implement additional mitigation measures in accordance with the
Environmental Management Plan (EMP), the Resettlement Plan (RP) and the Resettlement Action
Plan (RAP) as specified elsewhere in the Contract or in Part 4 – Specifications for Worksite
Environmental, Social, Health and Safety Management (ESHS) – Volume 4. Where reference is
made to Environmental Impact Assessment (EIA) or Environmental Management Plan (EMP) and/or
general environmental requirements, these shall be taken to also include the social component (e.g.
ESMP or ESIA).
It is not the Employer's intent to specify all environmental requirements or to set forth those
requirements adequately covered by applicable standards. The Contractor shall bear the full
responsibility with all the requirements herein and the costs of compliance are deemed to be included
in the unit rates in the Schedule of Quantities.
No deviations shall be made from this specification unless waived or modified in writing by the
Employer. The Contractor(s) shall obtain from its sub-contractor a statement as to compliance with
this specification without exception and/or if there are any exceptions, these shall be described in
detail and included in the Contractor’s Tender. The Contractor shall add a statement that no other
exceptions are taken to this specification.
The project must conform to environmental standards required by ISO 14001 and also all the
standards as stipulated in Part 4 – Specifications for Worksite Environmental, Social, Health and
Safety Management (ESHS) – Volume 4.
6.2 SCOPE
6.2.1 General
This chapter outlines the Contractor’s duties and responsibilities with respect to environmental
protection during construction of overhead AC distribution lines rated 11 kV and above.
The Contractor shall carry out the specified environmental protection requirements to the approval
of the Employer. It is recommended (but not a must) that the Contractor participates in local
initiatives beneficial to the communities along which the line route passes. Such activities will be to
the Contractor’s own expense. The Contractor shall not partake in any politically related activities
without seeking the approval of the Employer.
If so instructed by the Employer, the Contractor shall implement additional mitigation measures
payable under the applicable rates in the Daywork Schedule.
It is not the Employer's intent to specify all environmental requirements or to set forth those
requirements adequately covered by applicable standards. The Contractor shall bear the full
responsibility with all the requirements herein and the costs of compliance are deemed to be included
in the unit rates in the Schedule of Quantities.
No deviations shall be made from this specification unless waived or modified in writing by the
Employer. The Contractor(s) shall obtain from its sub-contractor a statement as to compliance with
this specification without exception and/or if there are any exceptions, these shall be described in
detail and included in the Contractor’s Tender. The Contractor shall add a statement that no other
exceptions are taken to this specification.
6.2.5 Sites
The work sites, located in Mashonaland West Province, are as follows:
Alaska 132kV substation extension, to accommodate a 132kV feeder bay to supply a
proposed 132kV transmission line to a new substation at Karoi substation;
Alaska – Karoi 132kV transmission line (approximately 85km long);
Proposed Karoi 132/33kV substation
3 x 33kV lines linking the proposed Karoi 132/33kV substation and existing Karoi 33/11kV
substation.
11kV and 33kV lines, located within Karoi town, Makonde and Hurungwe districts.
The Contractor shall provide a Site Environmental Protection Plan (SEPP) for each of the sites
mentioned above.
(iii) ESHS non-conformances and action taken to rectify the ESHS con-conformances
(iv)Accidents and incidents (i.e. Occupational health and safety)
(v) Complaints and disputes
(vi)Results / follow-up of inspections by local authorities, if any.
6.3 MONITORING
The Contractor shall provide all the resources needed for monitoring the project ESHS as stipulated
in Part 4 – Specifications for Worksite Environmental, Social, Health and Safety Management
(ESHS) – Volume 4. Such resources shall be required to be on site on a full time basis to monitor
the works. The Contractor’s ESHS monitoring resources will report to the Employer's Site Manager
and participate in all site meetings and the day-to-day running of the project.
The environmental monitoring will mainly concentrate on the following aspects of preventative or
potential impacts minimisation measures during construction:
• site establishment
• soil erosion
• noise and dust nuisance
• pollution (water, human waste, litter, etc.)
• disruption of the socio-economic fabric
• local employment and other specified benefits to indigenous communities.
• waste management / disposal
• storage of hazardous / inflammable substances
• toilet / wash facilities (etc.);
• local employment and other specified benefits to indigenous communities.
In addition, the ES Contractor’s ESHS resources for the project will assist in handling Right of Way
issues falling under the responsibility of the Employer and the Contractor.
The Contractor shall include clear procedures and means of verification, identification, control and
management of non-compliances as stipulated in Part 4 – Specifications for Worksite Environmental,
Social, Health and Safety Management (ESHS) – Volume 4.
pollution and environmental degradation. This Act repealed the Natural Resources Act [Chapter
20:13]; the Atmospheric Pollution Prevention Act [Chapter 20:03]; the Hazardous Substances and
Articles Act [Chapter 15:05] and the Noxious Weeds Act [Chapter 19:07].
It is the Contractor’s responsibility to familiarise himself and ensure compliance with the above Acts,
regulations and statutory instruments, and any other Acts not listed above which might be relevant
to his operations. Additional guidelines and/or protection measures issued by the respective
Government Ministries or Departments shall also be considered by the Contractor.
In addition, the Contractor shall also adhere to international standards as stated in Part 4 –
Specifications for Worksite Environmental, Social, Health and Safety Management (ESHS) –
Volume 4, including the African Development Bank (AfDB) Integrated Safeguards System (ISS).
The Contractor shall also ensure that international best practice and applicable AfDB ISS are strictly
adhered to.
6.7.2 Sub-Contracting
The Contractor shall endeavour to engage local sub-contractors where possible, particularly in areas
not requiring specialist substation construction skills, such as:
sump shall be covered with a steel grid overlaid by a layer of stones, to reduce oxygen supply and
thereby minimise the risk of oil fires. See also specifications for transformers and for civil works.
The following specific environmental guidelines shall be observed and implemented by the
Contractor in mitigation of potential environmental impacts in areas of activity, access roads, borrow
areas, spoil disposal areas, labour camps and storage areas.
• A minimum of two toilets for temporary camps, and full ablution facilities for permanent camps
shall be provided. The use of the bush for relieving oneself shall be strictly prohibited. Latrines at
camps will be closed and sealed after completion of works.
• Camps and storage areas shall be located away from drainage courses and wetlands. Wherever
possible, they will be sited within urban industrial areas.
• Camps and work-sites shall be kept clean and tidy.
• Fuel, lubricants and other chemicals shall be stored in above ground storage facilities such that
the entire surface area can be visually inspected. Tanks shall be inspected twice daily and any
leakage stopped immediately.
• Sumps surrounded by low bunds and floored with impermeable material shall be constructed
beneath all oil storage tanks. Other than trivial amounts, oil spilled to sumps will be removed for
recycling or safe disposal.
• Oil changes in machinery and equipment including vehicles shall take place only in depots (never
in the field). Drip pans will be placed under the equipment throughout oil changes and lubrication.
• Construction workers are discouraged from woodcutting and fishing, and shall be dismissed for
unauthorised hunting. Contractors and their workforce may use local supplies of wood, within
moderation, if there is no local shortage; but they should purchase wood from the local population
rather than just taking it freely.
• Demobilisation from a site will include removal and safe disposal of all temporary structures and
wastes. Stored topsoil shall be restored to site which will be planted with indigenous grasses,
where instructed by the Employer. No un-drained water will remain on site.
• Spoil shall not be heaped directly against trees if in so doing it can damage the stem.
• No tree or other combustibles outside the area of the works shall be burned for any purpose.
• Where the Works involve clearing and ground excavation, top-soil and sub-soil shall be selectively
removed and stockpiled separately for replacement in the reverse order in which they were
removed, to facilitate reinstatement of sites and their subsequent natural rehabilitation.
• Earth-moving equipment shall be thoroughly washed before bringing to site and the washings
caught in a sump, and incinerated. So doing is intended to destroy adhering seeds and soil
• Construction work shall, where possible, be restricted to the late dry season.
• Wetlands shall be excavated by approved methods, that avoid the development of quagmire
conditions and subsurface compaction that would result from the use of heavy machinery.
• After construction, the natural ground level and drainage pattern shall be restored.
• In carrying out construction of the Works, the Contractor, subcontractors and their suppliers of
materials shall comply with the provisions of local law.
• The Contractor shall ensure that key members of his staff are familiar with archaeological and
paleontological materials likely to be found in the project area.
• Should the Contractor expose any archaeological artefacts during excavation, work shall cease
immediately and the Employer shall be notified as soon as possible.
• Upon receipt of such notification, the Employer shall arrange for the excavation to be examined
as soon as is practicable, and shall advise the Contractor of necessary actions to be taken.
• Under no circumstances shall archaeological artefacts be removed, destroyed or interfered with
by the Contractor, his employees, his subcontractors or his subcontractors’ employees.
• The siting of spoil dumps, borrow areas, access roads and labour camps shall avoid areas where
valuable private property will be disturbed or destroyed.
• Where blasting is required, pre-blasting inspections of buildings falling inside the blast pressure
zone shall be carried out by the Contractor to establish and record the status of the buildings.
• Blasting shall be carried out in accordance with the provisions of relevant Zimbabwe regulations.
• The provisions in these technical specifications on pollution abatement shall apply.
• Where possible, the Contractor shall confine construction work through schools and institutions
to periods during school holidays. Where this is not possible maximum care shall be taken when
working in and around schools to avoid injuring children and damage to property.
• Work through crop fields shall, if possible, be carried out during the agricultural off-season.
• Where fences are breached or sports fields dug up, the Contractor shall reinstate them
immediately after completion of construction. Where required, alternative facilities shall be
provided.
• The Contractor shall ensure that access to services, fields, water supply by private property
owners is not disrupted.
• Any reasonable conditions demanded by the land owner shall be respected and complied with,
in as far as it is practicable.
• Where any of the above cannot be avoided or is infringed upon, fair compensation shall be
negotiated and paid by the Employer.
• Slopes may be stabilised with lines of brushwood anchored in place by driven stakes. The stakes
shall be of durable timber so as not to rot or be eaten too quickly by termites. The steeper the
bank, and the looser the soil, the more deeply shall the stakes be driven in.
a. Where there is a risk of pollution of water course from the Contractor’s operations, the
Contractor shall arrange to take water samples at each discharge point as and when
necessary, or as directed by the Employer, and shall have the samples analysed for pollutants
by an approved laboratory. Copies of the reports shall be submitted to the Employer within
fourteen days of the tests having been carried out.
b. In addition to samples from the discharge points, the Contractor shall take and have tested
water samples from 500 m upstream and 500 m downstream of the Works. The suspended
sediment concentration in the watercourse, 500 m downstream from the discharge point shall
be limited to 10% above baseline conditions.
6.17.3 Fuel Storage and Workshop Areas
• Fuel dispensing areas and workshop areas for machinery maintenance shall be provided with
concrete hard standing surfaces draining to oil separators.
• Drainage into watercourses from fuel storage and machinery maintenance areas shall be treated
to remove oil and/or fuel.
• Soil contaminated by fuel and oil leakage shall be removed and disposed of off Site in an
approved manner.
by the Employer. Construction of the ponds shall take place prior to topsoil stripping or any other
construction activity in the areas to be drained.
• Unless otherwise approved by the Employer, all water emanating from surface and underground
excavations shall be discharged into these sedimentation ponds, to remove sand, silt,
cementitious material and other suspended matter. The Contractor shall apply pH correction,
carry out other treatment as necessary to achieve the specified standard for water discharge from
the Works. Should any oil escape from the oil separator to enter the pond, the outflow from each
sedimentation pond shall be arranged so as to prevent any floating oil from leaving the pond
irrespective of the volume of water entering the pond.
• Drainage conduits or channels shall be sized to adequately handle the expected flows.
• Ponds shall be constructed using suitable materials natural to the site. They shall be sub-divided
to enable alternative sections to be cleaned while other sections are in operation.
• To ensure the satisfactory operation of the system, accumulations of silt and oil shall be removed
and disposed of by the Contractor at intervals, and in areas, approved by the Employer.
• The sedimentation ponds shall be emptied only by discharge from outlet pipes following treatment
of the stored water.
• Natural ground water and storm water from areas outside the immediate area of the Contractor’s
activities shall be prevented from flowing into the ponds.
6.17.7 Groundwater
• The Contractor’s working methods and systems shall be designed so as not to significantly affect
groundwater around the Works. Removal of ground water shall not cause damage to the Works,
or to the property of third parties, and shall not cause nuisance.
• Significant lowering of the natural groundwater table shall be avoided.
• Disposal of water taken from the works shall be in a safe and proper manner, and shall fulfil the
pollution control requirements specified in these specifications.
• Temporary works for the control of groundwater shall be removed and the ground reinstated when
they are no longer required.
6.20 EXPLOSIVES
• The Contractor shall use explosives only in circumstances where it is safe to do so, having due
regard to the safety of persons, third party property and the safety of the works.
• The Contractor shall obtain all necessary licences and shall provide and, where appropriate,
maintain a secure explosives store in accordance with the relevant Explosives Regulations and
to the approval of the Employer.
• Blasting shall be carried out carefully so as to avoid loosening or shattering rock beyond the
required line of excavation, and all loose or shattered rock shall be removed by scaling down or
other means before personnel will be permitted to restart operations after blasting.
• Notices of blasting operations shall be posted on site. Before each firing, the Contractor shall give
audible warning, clear the area, and shall take positive measures to prevent personnel from
entering the danger area.
• The Contractor shall strictly comply with the provisions of Zimbabwe law.
• Explosives shall be stored in structures appropriately designed for them.
• Where there is blasting in and close to rivers, no pollution of watercourses resulting from the
chemicals shall be permitted.
• Where explosives may damage existing foundations or structures, alternative methods, such as
silent demolition, shall be employed using approved chemicals.
d. Before undertaking any sand abstraction, the Contractor shall submit plans, including safety
provisions, for sand abstraction for approval by the Employer.
e. In accessing the riverbed to remove sand, care shall be taken not to damage the stream banks,
and where possible existing access routes shall be utilised. In all cases a single route shall be
used to access the river. The extraction of sand shall be limited to riverbed deposits. Priority
shall be given to desilting operations where possible.
f. The use of plant and machinery in the riverbed to abstract the sand shall be minimised as
much as possible. A back-acting excavator, with limited usage of a bulldozer or a shovel dozer,
shall undertake excavation and loading.
g. The Contractor shall take all measures necessary to minimise water pollution for the protection
of downstream users. The measures shall include temporary diversion of the stream, if
necessary.
h. The Contractor shall avoid stockpiling sand in the vicinity of the sand abstraction site, and
shall, as far as possible, load sand directly onto trucks for haulage. If stockpiling cannot be
avoided, the sand piles shall be located a minimum distance of 30 m from the riverbanks.
i. The contractor shall rehabilitate the sand abstraction site soon after extracting the required
amount of sand, in accordance with the provisions of these specifications.
j. Boulders shall reinforce unconsolidated bank material disturbed by sand abstraction works or
gabions fitted flush with the bank.
k. Slopes on bank approaches shall be adequately protected as appropriate to prevent erosion.
6.23 LABOUR CAMPS
In establishing labour camps, the following general guidelines shall apply:
• Camps shall be sited on naturally level ground and on deep soils suited to the construction of
ablution and toilet facilities.
• Sites shall not impinge on scenic undisturbed areas or other areas used by the public, and shall
be screened from major roads. No labour camp shall be established in National Parks.
• The provisions in these specifications for the protection of vegetation, wetlands, animals and
pollution control shall apply.
• Drainage facilities shall be installed in and around the site to prevent storm water from flooding
the site.
• Cutting of indigenous trees for firewood for cooking and warming shall be strictly prohibited. The
Contractor shall supply the labour force with adequate firewood.
• Grass and forest fires shall be prevented by sound control of cooking and warming fires.
• Proper security measures shall be employed to ensure that public property in the vicinity of the
site is not pilfered or damaged by the labour force.
• The Contractor shall provide own facilities so as to avoid over-stressing of existing local medical
facilities.
• A First Aid post and portable chemical toilets shall be provided at each temporary labour camp.
• Adequate accommodation and ablution facilities shall be provided to avoid overcrowding.
• All non-migratory labour camps shall be fenced and gated. Access into and out of the camps shall
ensure human and traffic safety, at all times.
• On demobilisation, the area shall be made good and re-vegetated in accordance with the
provisions in these specifications.
• Permanent structures shall be handed over to local communities at the end of the Contract.
6.24 HEALTH
The transient nature of distribution lines and substations construction could serve as a vehicle for
spreading disease such as cholera and some resistant strains of STD and malaria, particularly in
densely populated areas. To minimise the spread of communicable diseases the following guidelines
shall apply during construction:
• Where practicable, and without prejudice to the Contractor’s other contractual obligations,
preferential employment shall be given to members of the local community through which the
work front or fronts will be located during the course of construction of the transmission line. This
policy will minimise migrant labour and the spread of communicable diseases with which it is
associated.
• The Contractor shall provide health facilities and First Aid posts for the labour force to avoid over-
stressing existing facilities. Such facilities shall be properly staffed.
• In areas where malaria is prevalent, preventive medicines shall be distributed to the workforce
free of charge, on a regular basis.
• The Contractor shall take measures to educate and sensitise the labour force on the risks of
communicable diseases such as malaria, STD’s, including AIDS. Male and female condoms shall
be distributed to contract workers.
• In the case of serious injuries on site, traffic accidents etc., the Contractor shall formulate a plan
to deal with such emergencies, prior to possession of site, for approval by the Employer.
• Protective clothing shall be issued to categories of the workforce who require such clothing, free
of charge.
• The provisions in these specifications on pollution control and sanitation shall apply.
• All environmental and social aspects for the project, as well as all issues related to the ESHS
specifications (Part 4 – Volume 4).
• A basic understanding of the key environmental features of the Site and its environs.
• Thorough familiarity with the environmental protection requirements as they apply to the Works.
• The ability to identify archaeological artefacts, burial sites, special flora and fauna.
• Awareness of any other environmental matters, which are deemed to be necessary by the
Employer.
• Basic first aid.
6.27 COMPENSATION
Compensation related to the obtaining of Right of Way is the responsibility of the Employer, unless
otherwise agreed in the Contract between the Employer and the Contractor.
Damage occurring as a result of non-compliance with these specifications shall be made good by
the Contractor at his own expense.
All claims for private property accidentally damaged by the Contractor shall be paid by the Contractor
within a reasonable period of time.
6.28.3 Grassing
The method of establishing grass may be sodding, hydro seeding or hand seeding as approved by
the Employer.
• Sodding
Areas to be grassed by sodding shall be given a layer of topsoil at least 75 mm thick unless, due
to the presence of suitable subsoil, the Employer determines that the topsoil may be omitted. The
areas to be sodded shall be thoroughly watered beforehand, so that they are wet to a depth of at
least 150 mm when sods are placed. The surface shall be made slightly rough to ensure a good
penetration of roots into the soil. Sods shall be protected against drying out and shall be kept
moist from the time of harvesting until finally placed.
The first row of sods shall, where it is possible, be laid in a straight line and, if on a slope, starting
at the bottom of the slope. The sods shall be butted tightly against each other, care being taken
not to stretch or overlap sods. Where a good fit cannot be obtained, the intervening space shall
be filled with topsoil. Adjacent rows shall be placed with the joints staggered. Each sod shall be
• Maintenance of Grass
All planted grass shall receive a good dressing of suitable fertiliser at about one handful per
square metre (about 400 kg per hectare).
The Contractor shall maintain the grassed areas for a period of 3 months.
Tender Documents
ZETDC Tender No.______________________
Table of Contents
1 D-MV-01-001 GENERAL 10
1.1 General Requirements 10
1.2 Mechanical Design 10
1.3 Poles and Crossarms 10
1.4 Foundations 10
1.5 Grounding 10
1.6 Environmental Protection Requirements (EPRS) 10
3 D-MV-03-001 CONDUCTORS 33
3.1 Reference Standards 33
3.2 Material 33
4 D-MV-04-001 HARDWARE 35
4.1 General 35
4.2 Splices 35
4.3 Repair Sleeves 35
4.4 Repair Sleeves 35
4.5 Jumpers 36
5 D-MV-05-001 APPARATUS 37
5.1 Auto Reclosers, Pole Mounted 37
5.1.1 Reference Standards .......................................................................................................................... 37
5.1.2 Electrical Data .................................................................................................................................... 37
5.1.2.1 Short-Circuit Currents 37
5.1.2.2 Insulation level 37
5.1.2.3 Nominal Voltage Levels 37
5.1.2.4 Rated Current 37
5.1.2.5 Breaking Capacity 37
5.1.2.6 Duty Cycle 37
5.1.3 Protection and Auto Reclosure Functions........................................................................................... 37
5.1.4 Technical Requirements ..................................................................................................................... 38
5.1.4.1 Mounting 38
5.1.4.2 Design, Corrosion Protection 38
5.1.4.3 Terminals 38
5.1.4.4 Manoeuvre 38
5.1.5 Tests ................................................................................................................................................... 38
5.1.6 Information to be Submitted with the Tender ...................................................................................... 38
5.2 Load Switches 39
5.2.1 Reference Standards .......................................................................................................................... 39
5.2.2 Electrical Data .................................................................................................................................... 39
5.2.2.1 Short-Circuit Currents 39
5.2.2.2 Insulation Level 39
5.2.2.3 Nominal Voltage Levels 39
5.2.2.4 Rated Current 39
5.2.2.5 Breaking Capacity 40
5.2.3 Technical Requirements ..................................................................................................................... 40
5.2.3.1 Mounting 40
5.2.3.2 Mechanical Strength 40
5.2.3.3 Design, Corrosion Protection 40
5.2.3.4 Terminals 40
5.2.3.5 Manoeuvre 40
5.2.4 Tests ................................................................................................................................................... 41
5.2.5 Information to be Given with the Tender ............................................................................................. 41
5.3 Single-Phase Loadbreak Fuse Cut-Outs 41
5.3.1 Reference Standards .......................................................................................................................... 41
5.3.2 Electrical Data .................................................................................................................................... 41
5.3.2.1 Short-Circuit Currents 41
5.3.2.2 Insulation Level 41
5.3.2.3 Nominal Voltage Levels 41
5.3.2.4 Rated Current 41
1 D-MV-01-001 GENERAL
1.1 GENERAL REQUIREMENTS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
1.4 FOUNDATIONS
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 4, Foundations.
1.5 GROUNDING
See Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 5, Grounding.
60305 Characteristics of String Insulator Units of the Cap and Pin Type
60372 Locking Devices for Ball and Socket Couplings of String Insulators
60383-1, 2 Tests on Insulators of Ceramic Material or Glass for Overhead Lines with a
Nominal Voltage greater than 1000 V
60812 Analysis Techniques for System Reliability – Procedure for failure Mode and
Effects Analysis (FMEA).
61109 Composite Insulators for A.C. Overhead Lines with a Nominal Voltage
greater than 1 kV - Definitions, Test methods and Acceptance Criteria
61109-am1 Composite insulators for a.c. overhead lines with a nominal voltage greater
than 1000 V – Definitions, test methods and acceptance criteria
61211 Insulators of ceramic or glass for overhead lines. Impulse puncture test in
air
61245 Artificial Pollution Tests on High Voltage Insulators to be used on D.C.
Systems
61325 Insulators for Overhead Lines with a nominal voltage above 1000 V –
Ceramic or Glass Insulator Units for D.C. Systems
61466-1 Composite string insulator units for overhead lines. Standard strength
classes and end fittings
61466-2 Composite string insulator units for overhead lines. Dimensions and
electrical characteristics
61467 Insulators for overhead lines. A.C. power arc tests on insulator tests
61952 Insulators for overhead lines - Composite line post insulators for A.C. with
a nominal voltage above 100V.
ISO International Standards Organization
1459/1461 Hot Dip Zinc Coatings on Structural Steel & Other Allied Products
1460 Determination of Weight of Zinc Coating on Zinc Coated Iron and Steel
Articles
1461 (E) Recommended Practice for Hot Dip Galvanisation for Iron and Steel
These codes and standards set forth the minimum requirements which may be exceeded by the
Contractor if, in the Contractor's judgment and Employer's acceptance, superior or more economic
designs or materials are available for successful and continuous operation of the Contractor's
materials as required by this specification.
In addition to the applicable standards, the Contractor shall comply with applicable national and local
laws, codes, regulations, statutes and ordinances. The materials and services furnished shall comply
with and not prevent the Employer's compliance with all applicable standards of the local codes.
It is the intent of this specification to allow supply of insulators according to IEC Standards. If the
Contractor customarily produces the specified insulator of national standards other than mentioned,
the Contractor shall describe the equivalences and/or differences of such standards with his Tender.
For any such standards, which are not written in the English language, the Contractor shall make
available copies of an English translation thereof. In any event, the Contractor shall list all those
standards he proposes to use in the supply of the specified insulator.
In the event of any apparent conflict among standards or theses specifications, the Contractor shall
refer the conflict to the Employer for written resolution.
Note: In this document, when definition polymeric is used, it defines both composite and epoxy resin
insulators, as those form the subgroup of polymeric insulators. If used separately, composite or epoxy
resin terms are used to describe the specific property that belongs only to that subgroup.
Power-frequency withstand voltage: A rated insulation level. The voltage is sinusoidal, with a
frequency at 50 Hz, and a duration of 60 s. Unless stated otherwise this is the ‘wet’ withstand (as
opposed to ‘dry’ withstand).
Profile Factor (P.F.): The ratio of the simplified leakage distance to the actual insulating creepage
distance measured between the two points, which define the spacing - s.
Puncture Distance: The shortest distance through the insulating material between those parts which
normally have the operating voltage between them.
Radio Interference Voltage (RIV): Any effect on the reception of a radio signal due to an unwanted
disturbance within the Radio frequency spectrum. Radio interference is primarily of concern for
amplitude modulated systems (AM radio and television video signals) since other forms of modulation
(such as frequency modulation (FM) used for VHF radio broadcasting and television audio
signals) are generally much less affected by disturbances that emanate from overhead lines.
Rated insulation level: A set of standardised withstand voltages used to characterise an insulator’s
dielectric strength.
Ratios:
s/p: Ratio between shed spacing and overhang.
Note: The ratio s/p describes the limitation on providing arbitrarily too high a leakage distance by
either over dimensioning the shed overhang p or by unjustifiably increasing the number of sheds.
The ratio is important for self- cleaning properties of insulators.
Id/d: Ratio between the creepage distance and clearance.
Note: The ratio ld/d describes the use of the creepage distance in order to avoid local short-circuiting
Routine Test Load (RTL): The RTL is the load applied to all assembled composite suspension/strain
insulators during a routine mechanical test. The load applied to composite insulators that is equal to
or greater than 50 percent of the insulator Specified Mechanical Load (SML) rating. It is also
considered to be the maximum continuous working load of the insulator.
Silicone rubber: Elastomer polymer using silicone, typically polydimethylsiloxane.
Strain Insulator: An insulator placed in a structural support such as termination or any other
arrangement where the insulator is subjected to tensile load.
Specified Cantilever Load (SCL): A load specified by the manufacturer that represents the
ultimate strength of a polymeric line post insulator under cantilever loading. It is not the maximum
working load of the insulator. See MDCL. The strength should be verified during cantilever load tests,
and the historical failure loads (CBL) should justify the manufacturer’s choice of SCL. The SCL
forms the reference point for selection of a polymeric line post insulator.
Specified Mechanical Load (SML): A load specified by the manufacturer that represents the
ultimate strength of a composite suspension/strain insulator under tension. The strength should be
verified during Mechanical Load Tests, and the historical failure loads should justify the
manufacturer’s choice of SML. It is not the maximum working load of the insulator. See RTL. The
ultimate failing load shall be higher than the SML. It forms the basis of the selection of insulators
according to the Technical Schedules.
Note: The SML of an insulator may be reduced by the class of hardware used for the end fittings.
Specified Tensile Load (STL): The load specified by the manufacturer that represents the ultimate
strength of a polymeric line post insulator under tension. The strength is verified by the same testing
procedures used to determine the Specified Mechanical Load (SML) for composite suspension/strain
insulators. It forms the basis of the selection of a line post insulator according to the Technical
Schedules.
Standard lighting impulse withstand voltage: A rated insulation level. The voltage is an impulse,
with a front time of 1.2 µs and a time-to-half value of 50 µs.
Television Interference Voltage (TIV) (sometimes referred to as TVI): Special case of radio
interference for disturbances affecting the frequency ranges used for television broadcasting (video
signal).
Tracking: Irreversible degradation consisting of the formation of conductive paths starting and
developing on the surface of an insulating material. These paths are conductive even under dry
conditions.
UBL: Minimum mechanical failing load of a glass or ceramic type insulator.
ULS: Ultimate limit state.
2.4.4 General
ZETDC standardises its LV and MV insulators pin and shackle type insulators or suspension and
tension insulators (rated 0.4kV to 33kV) as follows:
1) Pin Insulators: These are mounted vertically, with the conductor above the insulator. They are
fixed to the crossarm by means of a threaded pin. They are also referred to as stand-off insulators.
2) Strain (Shackle) Insulators: These are mounted on a crossarm where the conductor is making
significant deviation. The conductor is supported on the side of the insulator, which is supported
from below by the crossarm.
3) Suspension Insulators: These are insulators which may be mounted vertically on a cross-arm.
These may either be of glass, ceramic (porcelain) or composite type
4) Strain Insulators: These are insulators which are attached to a crossarm (in a horizontal direction
of the line conductors) to hold a conductor at tension. These are used to terminate a conductor
at a crossarm or allow a conductor a significant deviation.
In addition to the above LV and MV insulators, Stay (Guy Type) insulators are also covered by this
specification.
0.4kV
11kV Pin 33kV Pin Disc Insulator 0..4kV
Description Shackle Stay
and Shackle and Shackle 11kV Reel Type
Type
Glass or Glass or Glass or
Insulator Type Porcelain
Porcelain Porcelain Porcelain
Reference Standard IEC 60672
Rated Voltage 11kV 33kV 11kV 0.4kV 0.4kV
Highest Voltage 12kV 36kV 12kV 0.6kV
1-min Dry 70-80kV 110-130kV 75-80kV 20-35kV 17kV 25kV
power
Flashover frequency Wet 40-55kV 85-95kV 45-50kV 10-25kV 9kV 12kV
Voltage
+ve 105-115kV 205-210kV 115-130kV -
Impulse
-ve 110-140kV 225-250kV 120-135kV -
1-min Dry 65-75kV 100-110kV 70-75kV ≥23kV
power
Withstand frequency Wet 35-50kV 80-90kV 40-45kV ≥10kV
Voltage
+ve 95-105kV 180-200kV 110-120kV -
Impulse
-ve 105-120kV 190-220kV 115-125kV -
1.3 x
Power Frequency Puncture actual Dry
105-120kV 200-210kV 110-130kV
Voltage Flashover
Voltage
Creepage Distance (min) 270-320mm 600-900mm 290 - 350 -
0.4kV
11kV Pin 33kV Pin Disc Insulator 0..4kV
Description Shackle Stay
and Shackle and Shackle 11kV Reel Type
Type
Cantilever Strength 10-12kN 10-12kN - -
Combined Electro-Mechanical
- - 70-120kN 15-16kN 60kN
Strength
Transverse Strength - - - - 13kN
Leekage Distance - - - 66-75mm
2.4.6.2 Material
The insulators shall be in accordance with IEC 60383 or IEC 61466. The insulating part shall be of
brown-glazed porcelain or toughened glass or composite material and be designed to withstand
alternating current (a.c.).
The cap shall be of malleable cast iron, spheroidal graphite cast iron, or forged steel. The socket
coupling shall be in accordance with IEC 60120 or IEC 61466-1 and have an internal height in
accordance with IEC 60372.
The pin shall be of forged steel. In tensile tests, the pins shall exhibit ductile fractures characterised
by a considerable contraction of area. The pin coupling shall be in accordance with IEC 60120 or
IEC 61466-1.
Cap and pin shall be hot-dip galvanised. The pin shall be protected by a zinc-collar sleeve.
Split-pins shall be of copper alloy or stainless steel and be in accordance with IEC 60372.
W-clips are not accepted.
The materials shall be free from folds, cracks and other exterior and interior defects that can affect
its strength, ductility, durability or ability to function.
All materials shall be inspected and tested in full to prove compliance with the requirements of these
Specifications and to the satisfaction of the Purchaser/Engineer. The testing shall be carried out
according to the relevant standards approved by the Purchaser/Engineer.
Assembly shall be performed in such a way that the mechanical properties cannot be affected and
to ensure that the insulating part is not subject to any mechanical stress due to pressure exerted by
the bottom edge of the cap.
Free surface of insulating parts shall be cleaned from cement and other impurities.
Each insulator unit shall be marked with the name or trade mark of the manufacturer and the year of
manufacture in accordance with IEC 60383 and means to ensure the system of traceability for each
of the component parts.
In addition, each insulator unit shall be marked with the specified electro-mechanical or mechanical
failing load in conformity with IEC 60383 or 61466-1, or the first part of the designation in accordance
with IEC 60305.
33kV
Nominal Voltage 11kV
19.1kV SWER (if applicable)
Lightning Impulse Withstand Voltage (kV) 75 170
Wet Power-Frequency Withstand Voltage (kV) 28 70
Minimum Nominal Creepage Distance (mm) 350 1000
Minimum Mechanical Failing Load 100 100
hydrolysis resistant. The FRP rod shall be manufactured through pultrusion process and shall be
void free.
1) Shed profile: S is standard, F is fog, A is aerodynamic, followed by ‘LP’ for ‘line pin’;
2) Two digits representing typical operating voltage; and
3) Three digits representing the nominal minimum creepage distance in mm.
For example ALP/33/710 is a line pin insulator with aerodynamic profile, for 33 kV, with a 710 mm
nominal minimum creepage distance.
e - Destination
f - Name of Supplier
g - Case Number
h - Shipping Unit (e.g., 1 of 3, etc.)
i - Dimensions
j - Handling instructions
k - Quantity
l - Gross weight (kg)
m - Net weight (kg)
n - Tare weight (kg)
For all other insulator units including polymeric insulators, adequate support shall be provided to
prevent breakage of the units during shipment and transport.
Each box or container of insulator units shall be marked with the number of pieces contained therein,
the catalogue number or class number or description of the contents and the manufacturer’s name.
2.4.17 Reliability
Contractors shall provide information on the reliability of the equipment and the performance of the
materials offered over an operational life of 50 years under the specified field of application and
conditions of service.
Information provided shall evidence the claimed reliability and performance for the equipment
offered, including information on failure mode and effect analysis, carried out in accordance with IEC
60812. Failure modes should be described: taking cantilever mechanical failure as an example, the
failure may be excessive deflection, or brittle fracture. Electrical failure may be material damage such
as puncture, polymer degradation, carbonisation, loss of hydrophobicity, etc.
Contractors may offer their standard equipment but any variation to the foregoing standards must be
clearly stated in writing at the time of the proposal. The products offered in the standing offer should
be equal to or better in quality and performance than the existing items as listed under this
Specification.
The Contractor shall carry out, at his own expense, all tests necessary to ensure the satisfactory
design and manufacture of the insulator units in accordance with IEC Standards.
If so required in the Technical Schedules the Employer or his authorized representative shall witness
all tests unless waived in writing, and no insulator units shall be shipped until released for shipment
by the Employer or his authorized representative.
The Contractor shall make all preparation for the tests and provide the test apparatus and personnel
and shall notify the Employer the date of the tests to be witnessed in accordance with the
requirements of this specification.
Actual test procedures to be used shall be subject to Employer’s acceptance and approval.
6. Electromechanical failing load test, in accordance with IEC 61325 Clause 23. The acceptance
criteria shall be as follows:
i) X > Rating + 3S where: X – mean value of test results
S – standard deviation of the test results
ii) Each value measured shall not be lower than the specified electromechanical failing load.
iii) Electrical puncture shall not occur before reaching ultimate failure.
7. Impulse over voltage test, in accordance with IEC 61325 Clause 17 with steepness of impulse:
2500 kV/microsecond
8. Residual mechanical performance test, in accordance with IEC 61325 Clause 26.
9. Porosity test, in accordance with IEC 61325 Clause 31.
10. Zinc sleeve test, in accordance with IEC 61325 Clause35.
11. Galvanizing test, in accordance with IEC 61325 Clause 32.
c. Routine Tests
The manufacturer shall carry out, at his own expense, the routine tests specified in IEC 61325.
The routine tensile load shall be 50% of the electromechanical failing load.
1. Routine visual inspection in accordance with IEC 61325 Clause 33.
Number of insulator units to be tested: All
2. Routine mechanical test in accordance with IEC 61325 Clause 34.
Number of insulator units to be tested: All
3. Routine electrical inspection in accordance with IEC 61325 Clause 21.
Number of insulator units to be tested: All
2.6.3.3 Horizontal Line Post /Long Rod Insulators and Insulator String Tests
The insulator units to be supplied shall comply with all the design tests specified in in accordance
with IEC Publ. 61109/1992 in context with IEC Publication 60383/1992, including Amendment 1 to
IEC Publication 61109/1992.
2.6.3.4 Horizontal Line Post /Long Rod Insulators and Insulator String - Inspection and
Test Plan
The inspection and test plan shall be as per the table below, in accordance with IEC 61109/1992
and the latest IEC60383 publication.
2.6.3.5 Quality Conformance Tests (for A.C. Suspension, Line Post and Long rod
Insulators)
If so specified in the Technical Schedules the Employer shall witness all quality performance tests.
All tests shall be in accordance with the applicable IEC standards, except for the acceptance criteria
for the combined Mechanical and Electrical Strength tests for ceramic and glass A.C. suspension
insulator units where the acceptance criteria shall be as follows:
𝑋𝑋 =≥ 𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟𝑟 + 3𝑆𝑆
where: 𝑋𝑋 = average value obtained on the sample of the ten insulator units tested
𝑆𝑆 = standard deviation for the ten insulator units tested
Each value measured shall not be lower than the specified mechanical and electrical strength.
Electrical puncture shall not occur before reaching ultimate failure.
All information submitted as part of the Tender Data will become part of contract data for the
successful Contractor. Any deviation from such data requires the Employer’s approval.
The Contractor shall furnish in the manner, number of copies and within the time set forth in the
Contract, instruction manuals in accordance with the requirements of the Contract.
The Contractor shall furnish information indicating recommended maintenance practice,
approximate time required for routine maintenance, and test of spare parts (if any) and tools required
for this maintenance.
The Contractor shall provide the required installation instructions and technical data for proper
installation.
2.8.2 General
The strain clamp shall be delivered incl. socket clevis 16 mm
2.9.1.1 Material
The insulating part should be made of porcelain or composite material.
The materials shall be free from folds, cracks and other exterior and interior defects that can affect
its strength, ductility, durability or ability to function.
Requirement Value
Lightning Impulse Withstand Voltage 40kV
Wet Power-Frequency 23kV
Minimum Nominal Creepage Distance 76mm
Minimum Tensile Strength 91kN
2.9.1.3 Marking
The insulating part should be clearly and lasting marked with the name of the manufacturer or
trademark, year of manufacture and type.
2.9.1.4 Testing
The Contractor shall carry out the type, sample and routine tests as prescribed in IEC 60383 for
ceramic stay insulators and IEC 61109 for composite ones.
Certificate from type tests shall be performed by an internationally known, independent testing
laboratory. Said test certificate shall be submitted together with the Bid.
3 D-MV-03-001 CONDUCTORS
3.1 REFERENCE STANDARDS
The following publications shall be applicable:
61394 Overhead lines - Characteristics of greases for aluminium, aluminium alloy and
steel bare conductors
61395 Overhead electrical conductors - Creep test procedures for stranded
conductors
62219 Overhead electrical conductors - Formed wire, concentric lay, stranded
conductors
3.2 MATERIAL
Conductors should be manufactured from aluminium alloy meeting the requirements on resistivity,
tensile strength, etc. given in this specification.
In addition the material shall have a resistance against corrosion at least on the level of Al/Mg/Si wire
according to IEC 60104. Conductors intended for SWER systems (if applicable) should be extra high
strength ACSR conductors.
Calculated
Code Stranding
Nominal Actual Overall Calculated Current –
Name & Wire Weight
Al Area Area Diameter Breaking Carrying
SCA Diameter (kg/km)
(mm2) (mm2) (mm) Load (kN) Capacity
/ACSR (mm)
(A)1
6x2.36 Al
Gopher 25 30.62 7.08 106 9.61 150
1x2.36 St
6x3.35 Al
Rabbit 50 61.72 10.05 214 18.35 240
1x3.35 St
6x4.10 Al
Raccoon 75 92.4 12.3 320 27.2 300
1x4.10 St
6x4.72 Al
Dog 100 118.50 14.15 394 32.7 360
7x1.57 St
30x2.59 Al
Wolf 150 194.90 18.13 726 69.2 470
7x2.59 St
Calculated
Code Stranding
Nominal Actual Overall Calculated Current –
Name & Wire Weight
Al Area Area Diameter Breaking Carrying
SCA Diameter (kg/km)
(mm2) (mm2) (mm) Load (kN) Capacity
/ACSR (mm)
(A)1
30x2.79 Al
Lynx 183.4 226.20 19.53 842 79.8 520
7x2.79 St
30x3.00 Al
Panther 200 261.50 21 974 92.25 560
7x3.00 St
1) At 45oC
4 D-MV-04-001 HARDWARE
4.1 GENERAL
Clamps and fittings shall be of a design approved for the conductor in accordance with the relevant
clause.
All hardware shall at least provide the same ultimate strength as the chosen insulator.
The connecting attachments, including bolts, nuts and washers, shall be included in the insulator
assemblies.
All materials shall be free from folds, cracks and other exterior and interior defects, which can affect
its strength, ductility, durability of ability to function.
All materials shall be inspected and tested in full to prove compliance with the requirements of the
Specifications and to the satisfaction of the Purchaser/Engineer. The testing shall be carried out
according to the relevant standards approved by the Purchaser/Engineer.
4.2 SPLICES
All splices shall develop at least 95% of the ultimate strength of the conductor, in accordance with
BS 3288 part 2.
The resistance of all splices shall not be more than 50% of the resistance of the conductor itself on
the same length as the splice.
Splices in jumpers shall consist of at least two parallel groove clamps.
4.5 JUMPERS
Jumpers are included in the contract.
The jumper for tension poles with tension clamps of wedged or bolted type shall consist of a jumper
conductor from both tension clamps spliced together with two parallel groove clamps.
The resistance over the parallel groove clamps shall be less than 50% of the resistance of the
conductor itself on the same length as the parallel groove clamps.
Bolts shall be used as clamping devices only and not as current carrying parts. All screws, nuts and
washers shall be of high strength galvanised steel.
5 D-MV-05-001 APPARATUS
5.1 AUTO RECLOSERS, POLE MOUNTED
5.1.1 Reference Standards
The following standards shall be applicable:
60265-1 High-voltage switches - Part 1: Switches for rated voltages above 1 kV and
less than 52 kV.
60694 Common specifications for high-voltage switchgear and control gear
standards.
5.1.2 Electrical Data
5.1.2.1 Short-Circuit Currents
According to Clause 1.1.
Reclosure
Trips in sequence to Lockout Range 1 to 3
Dead time after first trip in sequence Min. range 0.5 to 60 sec.
Dead time after second trip in sequence Min. range 5 to 180 seconds
Inverse time protection
Phase trip current setting range Minimum range 50 to 1000 A
Earth trip current setting range Minimum range 10 to 1000 A
5.1.4.3 Terminals
The terminals should be made of copper or aluminium suitable for connection of ACSR.
5.1.4.4 Manoeuvre
All three poles should be able to operate simultaneously from the ground level.
The position of the auto recloser should be clearly marked on the operating device.
5.1.5 Tests
The auto recloser should be type tested according to IEC 60056. Type test records not older than 5
years should be submitted on request.
60168 Test on indoor and outdoor post insulators of ceramic material or glass for
systems with nominal voltages greater than 1 000 V
60265-1 High-voltage switches - Part 1: Switches for rated voltages above 1 kV and
less than 52 kV
60694 Common specifications for high-voltage switchgear and control gear standards
60383-1 Insulators for overhead lines with a nominal voltage above 1000 V - Part 1:
Ceramic or glass insulator units for a.c. systems - Definitions, test methods and
acceptance criteria
60720 Characteristics of line post insulators
61109 Composite insulators for a.c. overhead lines with a nominal voltage greater
than 1000 V – Definitions, test methods and acceptance criteria
61109-am1 Amendment 1 - Composite insulators for a.c. overhead lines with a nominal
voltage greater than 1000 V – Definitions, test methods and acceptance criteria
61952 Insulators for overhead lines – Composite line post insulators for alternative
current with a nominal voltage > 1000 V.
5.2.3.4 Terminals
The terminals should be made of copper or aluminium.
5.2.3.5 Manoeuvre
All three poles should be operated simultaneously from the ground level.
Load switches should be operated by means of a linkage system and equipped with a control handle
of insulating material. The handle should be able to lock in both end positions with a pad lock.
The load switch should have fixed end positions so that it can not move from these positions by
influence form wind, etc.
The position of the load switch should be clearly marked on the operating device.
5.2.4 Tests
The load switch should be type tested according to IEC 60694. Type test records not older than 5
years should be submitted on request.
NEMA SG2
km OH line in
Number of Number of
km OH line in T- rough or
Item transformers in customers in T-
off inaccessible
T-off off
terrain1)
Single-Phase
loadbreak fuse 0 0 1 1
cut-out
1) Terrain with high bush or trees with increased risk of short circuit the line, rough terrain with
difficulties to access the line.
6.1.3 Survey
As stated in Distribution Lines & Substations, Volume 2C, Section VI(C)2, Distribution General
Specifications, Chapter 1, General.
Backfill shall be carried out to a minimum height of 20 cm over the original ground surface to
compensate for future settlement of the filling.
All backfill of pole foundation shall be protected from being washed away by running water in an
approved manner.
At all pole positions, the surface of the ground shall be sloping from the pole to provide drainage as
required. No additional payment will be made for such work.
At certain places, additional protection against erosion may be required, such as installation of riprap
or ditches. Any such work, when decided in agreement with and authorised by the Engineer, will be
paid for on the basis of prices in the schedule of rates and prices in the contract.
6.2.4 Erection
Poles may be erected by any suitable method, provided that no overstressing of any component
parts occurs.
After initial assembly, but before stringing of conductors, thorough check shall be made so that all
bolts are tightened to correct torque and all nuts are locked in an approved manner.
Handling and storage of all material shall be such as to prevent injury to members or damage to the
zinc-coating. Steel in storage shall be blocked off ground.
At each pole, the Contractor shall install the relevant pole signs as shown on the drawings.
Poles shall be plumb. After clamping-in of conductors, the maximum tolerated deviation in any
direction from the vertical shall be 2 mm/m (0.2 %) of the pole height above ground level.
After erection, all poles shall be cleared of all foreign matters.
Before assembly, all units shall be closely inspected. Bent pins will not be allowed. In order to
minimise the risk of pin bending, no rope slings shall be used for lifting assembled units, but a suitable
hook shall be applied to the insulator.
Damaged insulator units shall be replaced. Invisible cracks may be detected by sounding each unit
with a light wood or hard-rubber club. The cracked ones shall immediately be destroyed in order to
avoid unintentional re-use.
Immediately before and installation, the insulator shall be thoroughly cleaned, and all cotter pins shall
be checked for correct positioning and freedom from defects.
All screws, nuts and cotter pins shall be installed so as to facilitate easy, inspection and live line
maintenance work.
Compression joints and tension clamps shall be installed in accordance with good engineering
practice. The Contractor shall submit detailed written instructions for the complete installation
procedure for the approval of the Engineer.
Wherever possible, full use shall be made of maximum drum lengths of conductors in order to reduce
the number of joints.
The number of joints and their location in the spans shall be approved by the Engineer.
No joints shall be made in spans which cross main roads, power lines or in the major river crossings,
nor, whenever conductor drum lengths permit, in spans immediately adjacent thereto.
The distance between joints of the same conductor shall in no case be less than 100 m. Joints shall
in no case be installed closer than 20 m to the centre of suspension clamps.
The Contractor shall keep a record of all joints and tension clamps indicating the location, type and
date of each assembly.
6.3.4 Stringing
Conductors shall be pulled out and strung by an approved stringing method. Conductors shall, as a
principle, never be allowed to touch ground.
The Contractor shall submit in writing, for the approval of the Engineer, a complete and detailed
description of the stringing equipment and the stringing and sagging procedure intended for use.
Unless otherwise approved by the Engineer, the stringing procedure shall be in strict conformity with
the recommendations of the manufacturer of the stringing equipment. Only specially trained linesmen
must be employed who are well acquainted with the handling and running of the particular equipment
to be used.
Reliable means of instantaneous two-way communication must be available between the pulling and
the braking crews, and between these crews and any observation posts that may be placed along
the stringing section.
The stringing equipment shall be set up so as not to cause excessive vertical loads on the poles.
The distance to the nearest pole through which the cables are being strung shall be selected with
due regard to the relative levels of the pulleys on the pole and the stringing equipment reasonable
allowance should also be made for possible accidental over-tensioning of the cables.
Stringing pulleys shall preferably be located at approximately the same levels as that which the
conductors will occupy when installed.
At all times during stringing, the conductors shall be handled and protected so as not to be scratched,
nicked, abraded, kinked or damaged in any way. If during stringing it should prove inevitable to lower
the conductors to the ground, suitable non-metallic lagging shall be placed underneath.
Conductors, which have been subject to bird-caging during stringing, will not be accepted.
Stringing tensions shall at no time exceed corresponding sagging tensions.
Clamps for attaching the conductors to the hauling device shall be of approved design and shall
prevent relative movement of strand or layers of the conductors or overhead ground wires. Freely
rotating ball bearing swivels shall be used for each cable to be strung.
If, for any reason, stringing operations in progress must be interrupted, the conductors may be left in
the stringing pulleys, but their tension shall be reduced as far as possible.
In all cases, however, the cables must be kept completely clear of the ground, not lower than the
min. clearances given in Clause 2.5 of Distribution Lines & Substations, Volume 2C, Section VI(C)2,
Distribution General Specifications, Chapter 1, General and sufficiently far from any obstacles which
might cause abrasion of the cables, if touched by them.
If the interruption lasts for more than 40 hours or if stormy weather has prevailed, the cables shall be
closely inspected for damage.
Such inspection applies particularly to the suspension points where the cables have been resting in
the pulley sheaves.
At all times during stringing, sagging and clamping operations, the conductors, reels and hauling
equipment shall be effectively grounded.
The Contractor shall make suitable arrangements for temporary staying of poles, where necessary.
Damages to the conductors shall be immediately reported to the Engineer who will instruct the
Contractor on how to proceed.
6.3.5 Sagging
The Contractor shall submit for the approval of the Engineer sag and tension charts for use during
erection, which shall be established with due regard to the specific stringing and sagging methods
to be employed so that remaining creep after clamping may be assessed and taken into account with
reasonable accuracy.
Erection sagging charts or tables shall display sag in still air against span length for temperatures
between +5o C and 70o C in increments of 5o C.
Sagging temperature shall be read from a certified thermometer, the bulb of which has been inserted
in an approximately 50 cm long piece of conductor with the inner layers removed. The thermometer
so equipped shall be freely suspended in the air without any shielding and not less than 3 m above
ground. Temperature readings will be taken only after 20 minutes exposure.
After finishing stringing operations, the conductors and overhead ground wires shall be sagged in
accordance with agreed sagging procedure and relevant erection sagging chart or table.
It is essential that prescribed hold periods before definite sagging are rigorously observed.
The Contractor shall check the sag of each conductor of a sagging section in at least one span of
approximate ruling span length. The sags shall also be checked in all spans exceeding 120 m and
in spans on each side of angle structures and sharp breaks in profile. Intermediate spans shall be
inspected for uniform sag.
Sag at the option of the Engineer will be checked by him, and the Contractor shall furnish such
assistance in equipment and personnel as may be required for this purpose.
Sagging sections shall be limited to such length as can be sagged satisfactorily.
Final sagging of conductors shall not be made earlier than 8 hours but not later than 48 hours after
they have been taken up to approximate specific sag. All conductors of a sagging section shall be
sagged at the same time.
Conductor tension shall be equalised between sagging sections so that the insulator strings will
assume the proper position when successive sagging sections have been clamped in.
The Contractor shall keep a record on approved schedules of the particulars of the sagging of
conductors and overhead ground wires on each sagging section.
6.3.6 Binding
After finishing sagging operations, the conductors shall be bound according to agreed procedure.
Tension clamps shall be installed and properly anchored prior to clamping-in at suspension strings.
In order to make future adjustments possible, approximately one half of the available length
adjustment of turn buckles shall remain after anchoring.
Binding shall be done within 48 hours after completion of sagging, unless otherwise agreed.
All markings of the conductors, e.g. for the centring of clamps or armour rods, shall be done with
tape or other inoffensive means. Scratch marks or similar will not be permitted.
Immediately after binding, sag tolerances shall be plus or minus 1 % of specified sag, provided that
all conductors in the span assume the same sag, and specified clearance to ground will be obtained.