Broken Conductor Protection
Broken Conductor Protection
CONDUCTOR PROTECTION:
Assignment EPSP
Abstract
In this assignment we understand the working principle of Broken conductor protection
In a power system, majority faults occur due to phase to ground faults. In these faults, there is
a high percentage of faults resulting from a conductor being broken midway in such a way,
that they do not touch the earth. That is why this protection is also known as Broken Jumper
Protection.
As this conductor is not grounded, it acts as an open circuit. Due to the nature of this fault,
high currents do not flow unless a path is made between the conductor and ground. Thus
detection of such fault becomes a challenging task.
One of the characteristic of such fault is that it incorporates imbalances in the system which
arise in the form of Negative Sequence components.
It is possible to apply a negative phase sequence overcurrent relay to detect the above
condition. However, on a lightly loaded line, the negative sequence current resulting from a
series fault condition may be very close to, or less than, the full load steady state unbalance
arising from CT errors, load unbalance etc. A negative sequence element therefore would not
operate at low load levels.
It is possible to calculate the ratio of I2/I1 that will occur for varying system impedances, by
referring to the following equations below.
I1F = Eg(Z1+ Z0) / (Z1Z2+Z0Z1+Z2Z0)
I2F = -EgZ0/ (Z1Z2+Z0Z1+Z2Z0)
Where
Eg = System Voltage
Z0 = Zero sequence impedance
Z1 = Positive sequence impedance
Z2 = Negative sequence impedance
Thus,
I1F / I2F= Z0 / (Z0+Z2)
A minimum value of 8% negative phase sequence current is required for successful Broken
Conductor relay operation.
Since sensitive settings have been employed, it can be expected that the element will operate
for any unbalance condition occurring on the system for example, during a single pole
autoreclose cycle. Hence, a long time-delay is necessary to ensure co-ordination with other
protective devices. Normally 5 second time-delay is provided for Broken Conductor
Protection.