EPRI Power System Dynamics Tutorial
EPRI Power System Dynamics Tutorial
12422963
12422963
EPRI Power Systems Dynamics
Tutorial
1016042
12422963
DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES
THIS DOCUMENT WAS PREPARED BY THE ORGANIZATION(S) NAMED BELOW AS AN
ACCOUNT OF WORK SPONSORED OR COSPONSORED BY THE ELECTRIC POWER RESEARCH
INSTITUTE, INC. (EPRI). NEITHER EPRI, ANY MEMBER OF EPRI, ANY COSPONSOR, THE
ORGANIZATION(S) BELOW, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM:
NOTE
For further information about EPRI, call the EPRI Customer Assistance Center at 800.313.3774 or
e-mail [email protected].
Electric Power Research Institute, EPRI, and TOGETHER…SHAPING THE FUTURE OF ELECTRICITY
are registered service marks of the Electric Power Research Institute, Inc.
Copyright © 2009 Electric Power Research Institute, Inc. All rights reserved.
12422963
CITATIONS
Principal Investigator
M. Terbrueggen
This report describes research sponsored by the Electric Power Research Institute (EPRI).
The report is a corporate document that should be cited in the literature in the following manner:
EPRI Power Systems Dynamics Tutorial. EPRI, Palo Alto, CA: 2009. 1016042.
iii
12422963
12422963
REPORT SUMMARY
Background
EPRI developed the first version of the power system dynamics tutorial in 1989, with the aim of
enhancing training of power system operators and operation engineers. Addressing industry
concerns, the tutorial was designed as an easily understandable supplement to utility-specific
training materials. Earlier versions of this tutorial were well received, with thousands of copies in
use by system operators throughout the world. A number of important industry-wide changes led
to revision of the 2002 version of the power system dynamics tutorial. These changes included:
• The appointment of NERC as the Electric Reliability Organization for North America.
NERC has moved from a voluntary compliance organization to an organization with
government authority to enforce the Reliability Standards. Many changes were made to this
tutorial to reflect NERC’s expanding role.
• Training requirements for system operators have been substantially increased. The technical
material in this tutorial has been expanded to reflect the changing needs of system operators.
• The Eastern Interconnection outage of August 14, 2003, initiated many changes to how the
North American power system is operated. This revised tutorial addresses many of these
changes.
Objective
• To address the current needs of North American power system operators and operations
engineers through a comprehensively updated tutorial on power system dynamics
Approach
In revising the tutorial, the author has incorporated material from the presentations of numerous
power system dynamics seminars, coupled with industry knowledge and experiences. Unique
design features were employed to enhance the effectiveness of the tutorial, both as a training tool
and as a reference source. This revised edition updates terminology to be consistent with current
v
12422963
versions of the NERC Reliability Standards. In addition, many new illustrations have been
added, and all other illustrations have been updated.
Results
This edition of the tutorial includes a tutorial overview and an introductory review of power
system fundamentals, followed by chapters on active and reactive power flow, frequency and
voltage control, voltage and angle stability, and power system oscillations. The tutorial includes
chapters on harmonics, resonance, subsynchronous resonance, ferroresonance, and solar
magnetic disturbances. An entire chapter is devoted to the construction and operation of high
voltage direct current (HVDC) systems and phase shifting transformers. This edition has been
expanded to explain the causes of power system shutdowns, with emphasis on the theory of
power system restoration and the methods used in such restoration. Topics of great interest in
this area include voltage and frequency control, equipment and protective relay issues, and
synchronizing issues that may be encountered during power system restoration. Also discussed
are possible strategies to employ during system restoration along with lessons learned from
actual restoration events occurring in North American power systems. A new section has been
added to briefly introduce the basic concepts of the Wide Area Measurement System (WAMS)
and Wide Area Control System (WACS). Like its predecessors, this edition uses a direct style,
relying on physical analogies, intuitive reasoning, and actual case histories rather than on
complex engineering terminology and numerous mathematical equations. This tutorial
supersedes EPRI reports EL-6360-L and TR-107726-R1.
EPRI Perspective
Thousands of readers in the power system community have benefited from earlier editions of this
tutorial as a training tool and reference source on power system operation and engineering. This
tutorial—which has become well known in the industry over the past 20 years—provides a
comprehensive overview of the knowledge that operators need in understanding power system
dynamics. EPRI’s goal with this tutorial is to ensure that system operators acquire the necessary
knowledge to exercise critical judgment in emergency situations that fall outside the scope of
step-by-step utility procedures. EPRI believes that the use of this tutorial promotes operator
proficiency, while supporting economic and reliable power system operation.
Keywords
High voltage direct current (HVDC)
Power system control
Power system dynamics
Power system engineering
Wide Area Control System (WACS)
Wide Area Measurement System (WAMS)
vi
12422963
ABSTRACT
Significant industry restructuring under the vision of the Federal Energy Regulatory Commission
(FERC) is leading to the formation of large regional transmission organizations, which have
dramatically increased the geographical areas over which a system operator has responsibility.
Consequently, blackouts in one power system can potentially impact a huge portion of North
America at one time—making cost-effective training more and more critical to system reliability.
The EPRI Power System Dynamics Tutorial represents a complete update of key topics to reflect
this restructuring as well as current Reliability Standards issued by the North American Electric
Reliability Council (NERC). This revised edition includes a power system dynamics tutorial
overview and an introductory review of power system fundamentals, followed by chapters on
active and reactive power flow, frequency and voltage control, voltage and angle stability, and
power system oscillations. The tutorial includes chapters on harmonics, resonance,
subsynchronous resonance, ferroresonance, and solar magnetic disturbances. An entire chapter is
devoted to the construction and operation of high voltage direct current (HVDC) systems and
phase shifting transformers. A new section has been added to briefly introduce the basic concepts
of the Wide Area Measurement System (WAMS) and Wide Area Control System (WACS).
Finally, and most important, this edition has been expanded to explain the causes of power
system shutdowns, with emphasis on the theory of power system restoration, methods used in
such restoration, and lessons learned from actual restoration events occurring in North American
power systems. Use of the tutorial promotes operator proficiency, while supporting economic
and reliable power system operation.
vii
12422963
12422963
CONTENTS
ix
12422963
2.4 AC Electricity Review.................................................................................................2-20
2.4.1 Alternating Current Systems .............................................................................2-20
2.4.2 Vectors and Phasors.........................................................................................2-22
2.4.3 Magnetism & Magnetic Fields ...........................................................................2-26
2.4.4 AC Impedance ..................................................................................................2-28
2.4.5 AC Power ..........................................................................................................2-35
2.5 Protective Relaying Review .......................................................................................2-41
2.5.1 Introduction to Power System Relaying ............................................................2-41
2.5.2 Purpose and Function of Protective Relays ......................................................2-42
2.5.3 Power System Faults ........................................................................................2-42
2.5.4 Instrument Transformers...................................................................................2-45
2.5.5 Relay Construction & Operation........................................................................2-46
2.5.6 Types of Relays ................................................................................................2-54
2.5.7 Synchronizing and Synchronizing Equipment...................................................2-64
2.6 Power System Equipment Review.............................................................................2-70
2.6.1 Introduction to Equipment Review ....................................................................2-70
2.6.2 Generators ........................................................................................................2-70
2.6.3 Power Transformers..........................................................................................2-95
2.6.4 Transmission Lines .........................................................................................2-100
2.6.5 AC Circuit Breakers & Switches......................................................................2-104
2.6.6 Thyrister Systems ...........................................................................................2-107
2.7 Power System Operations .......................................................................................2-108
2.7.1 The Interconnections.......................................................................................2-108
2.7.2 The Role of NERC ..........................................................................................2-110
2.8 Fundamentals Review Questions ............................................................................2-111
2.9 Fundamentals Review References ..........................................................................2-113
x
12422963
3.3.3 Use of the Reactive Power Transfer Equation ..................................................3-16
3.4 Graphical Tools for Power Transfer ...........................................................................3-18
3.4.1 Power-Angle Curve ...........................................................................................3-19
3.4.2 The Power-Circle Diagram................................................................................3-21
3.5 Power Transfer Limits ................................................................................................3-28
3.5.1 Thermal Limits...................................................................................................3-28
3.5.2 Angle Stability Limits .........................................................................................3-29
3.5.3 Voltage Limits....................................................................................................3-30
3.5.4 Determining Power Transfer Limits...................................................................3-30
3.5.5 Total and Available Transfer Capability ............................................................3-31
3.6 Distribution Factors ....................................................................................................3-32
3.6.1 Determining Distribution Factors.......................................................................3-32
3.6.2 Using Distribution Factors .................................................................................3-33
3.7 Summary of Active and Reactive Power .......................................................................3-34
3.7.1 Active, Reactive and Complex Power ...............................................................3-34
3.7.2 Phase Angle, Power Angle, and Torque Angle.................................................3-34
3.7.3 Development of Power Transfer Equations ......................................................3-34
3.7.4 Use of Active Power Transfer Equation ............................................................3-35
3.7.5 Use of Reactive Power Transfer Equation ........................................................3-35
3.7.6 Power-Angle Curve ...........................................................................................3-36
3.7.8 The Power-Circle Diagram................................................................................3-36
3.7.9 Thermal Limits...................................................................................................3-36
3.7.10 Angle Stability Limits ........................................................................................3-36
3.7.11 Voltage Limits ...................................................................................................3-36
3.7.12 Determining Power Transfer Limits..................................................................3-37
3.7.13 Total and Available Transfer Capability............................................................3-37
3.7.14 Determining Distribution Factors ......................................................................3-37
3.7.15 Using Distribution Factors ................................................................................3-37
3.8 Active and Reactive Power Questions ..........................................................................3-38
3.9 Active and Reactive Power Flow References ...............................................................3-40
xi
12422963
4.1.3 Definition of a Control System.............................................................................4-2
4.1.4 The Energy Balance Concept .............................................................................4-2
4.1.5 Normal and Abnormal Frequency Deviations .....................................................4-4
4.1.6 The Load/Frequency Relationship ......................................................................4-7
4.1.7 Power System Inertia ..........................................................................................4-8
4.2 Governor System Components and Operation..........................................................4-10
4.2.1 Introduction to Governors..................................................................................4-10
4.2.2 Centrifugal Ballhead Governor..........................................................................4-11
4.2.3 Modern Electronic Governors ...........................................................................4-13
4.2.4 Governor Droop Curves ....................................................................................4-14
4.2.5 Governor Control in an Islanded Power System ...............................................4-19
4.2.6 Governor Control in an Interconnected System ................................................4-25
4.2.7 Frequency Traces .............................................................................................4-27
4.2.8 Generator Response and Droop Settings .........................................................4-28
4.2.9 System Frequency Response Characteristic ....................................................4-31
4.2.10 Response to a Loss of Generation ...................................................................4-35
4.2.11 Limitations to Governor Response ...................................................................4-36
4.3 Automatic Generation Control (AGC) ........................................................................4-40
4.3.1 Introduction to Automatic Generation Control ...................................................4-40
4.3.2 Balancing Authorities ........................................................................................4-41
4.3.3 Types of Interchange ........................................................................................4-44
4.3.4 Function of an AGC System..............................................................................4-49
4.3.5 Components of an AGC System .......................................................................4-50
4.3.6 Modes of AGC Control ......................................................................................4-51
4.3.7 Tie-Line Bias Control.........................................................................................4-53
4.3.8 Balancing Authority Implementation of AGC.....................................................4-58
4.4 Reserve Policies ........................................................................................................4-59
4.4.1 Operating Reserves ..........................................................................................4-59
4.4.2 Spinning and Non-Spinning Reserves ..............................................................4-60
4.4.3 Responsive Reserves .......................................................................................4-61
4.4.4 NERC Reserve Definitions................................................................................4-63
4.5 Time Error Control .....................................................................................................4-63
4.5.1 Definition of Time Error .....................................................................................4-63
4.5.2 Monitoring Time Error .......................................................................................4-64
xii
12422963
4.5.3 Correcting Time Error........................................................................................4-65
4.6 NERC Control Performance Standards .....................................................................4-66
4.6.1 NERC’s Old Control Performance Criteria ........................................................4-67
4.6.2 NERC Performance Standards .........................................................................4-70
4.7 Impact of Frequency Deviations ................................................................................4-74
4.7.1 Effects on Steam Turbine Blades......................................................................4-74
4.7.2 Effects on Hydro and Combustion Turbines .....................................................4-75
4.7.3 Effects on Other Power System Equipment......................................................4-75
4.7.4 Effects on Active Power Flows..........................................................................4-76
4.8 Underfrequency Protection ........................................................................................4-76
4.8.1 Power System Islands.......................................................................................4-77
4.8.2 Underfrequency Load Shedding (UFLS)...........................................................4-78
4.8.3 Underfrequency Generator Protection ..............................................................4-81
4.9 Nature of a Frequency Deviation ...............................................................................4-82
4.9.1 Analysis of a Frequency Deviation....................................................................4-82
4.9.2 Actual Expanded Frequency Plots ....................................................................4-84
4.9.3 Effect of Time and Distance ..............................................................................4-86
4.9.4 Frequency Relation to Power Angle..................................................................4-87
4.9.5 Speed of the Traveling Frequency Wave..........................................................4-89
4.10 Staged Response to a Generation Loss ...................................................................4-91
4.10.1 The Electromagnetic Energy Stage..................................................................4-91
4.10.2 The Inertial Stage .............................................................................................4-92
4.10.3 The Governor Response Stage........................................................................4-92
4.10.4 The AGC Stage ................................................................................................4-92
4.10.5 The Economic Dispatch Stage .........................................................................4-92
4.10.6 Illustration of a Staged Response.....................................................................4-93
4.11 Role of the System Operator.....................................................................................4-96
4.11.1 Frequency Control Duties.................................................................................4-97
4.11.2 Islanded Systems and Frequency Control........................................................4-97
4.11.3 A Simple Example ............................................................................................4-98
4.12 Summary of Frequency Control ..............................................................................4-100
4.12.1 The Changing Load........................................................................................4-100
4.12.2 Need for Frequency Control Systems ............................................................4-100
4.12.3 Definition of a Control System ........................................................................4-100
xiii
12422963
4.12.4 The Energy Balance Concept ........................................................................4-100
4.12.5 Normal and Abnormal Frequency Deviations.................................................4-100
4.12.6 The Load/Frequency Relationship .................................................................4-100
4.12.7 Power System Inertia .....................................................................................4-100
4.12.8 Introduction to Governors ...............................................................................4-100
4.12.9 Centrifugal Ballhead Governor .......................................................................4-101
4.12.10 Modern Electronic Governors.........................................................................4-101
4.12.11 Governor Droop Curves .................................................................................4-101
4.12.12 Governor Control in an Islanded Power System ...........................................4-101
4.12.13 Governor Control in an Interconnected System ............................................4-101
4.12.14 Frequency Traces .........................................................................................4-101
4.12.15 Generator Response and Droop Settings .....................................................4-102
4.12.16 System Frequency Response Characteristic ................................................4-102
4.12.17 Response to a Loss of Generation................................................................4-102
4.12.18 Limitations to Governor Response ................................................................4-102
4.12.19 Introduction to Automatic Generation Control ...............................................4-102
4.12.20 Balancing Authorities.....................................................................................4-103
4.12.21 Types of Interchange.....................................................................................4-103
4.12.22 Function of an AGC System..........................................................................4-103
4.12.23 Components of an AGC System ...................................................................4-103
4.12.24 Modes of AGC Control ..................................................................................4-104
4.12.25 Tie-Line Bias Control.....................................................................................4-104
4.12.26 Balancing Authority Implementation of AGC .................................................4-104
4.12.27 Operating Reserves ......................................................................................4-104
4.12.28 Spinning and Non-Spinning Reserves ..........................................................4-104
4.12.29 Responsive Reserves ...................................................................................4-105
4.12.30 NERC Reserve Definitions ............................................................................4-105
4.12.31 Definition of Time Error .................................................................................4-105
4.12.32 Monitoring Time Error....................................................................................4-105
4.12.33 Correcting Time Error....................................................................................4-105
4.12.34 NERC’s Old Control Performance Criteria ....................................................4-105
4.12.35 NERC Performance Standards .....................................................................4-105
4.12.36 Effects on Steam Turbine Blades..................................................................4-106
4.12.37 Effects on Hydro and Combustion Turbines..................................................4-106
xiv
12422963
4.12.38 Effects on Other Power System Equipment ..................................................4-106
4.12.39 Effects on Active Power Flows ......................................................................4-106
4.12.40 Power System Islands ...................................................................................4-106
4.12.41 Underfrequency Load Shedding (UFLS) .......................................................4-107
4.12.42 Underfrequency Generator Protection...........................................................4-107
4.12.43 Analysis of a Frequency Deviation ................................................................4-107
4.12.44 Actual Expanded Frequency Plots ................................................................4-107
4.12.45 Effect of Time and Distance ..........................................................................4-107
4.12.46 Frequency Relation to Power Angle ..............................................................4-108
4.12.47 Speed of the Traveling Frequency Wave ......................................................4-108
4.12.48 The Electromagnetic Energy Stage...............................................................4-108
4.12.49 The Inertial Stage ..........................................................................................4-108
4.12.50 The Governor Response Stage.....................................................................4-108
4.12.51 The AGC Stage .............................................................................................4-108
4.12.52 Illustration of a Staged Response..................................................................4-108
4.12.53 Frequency Control Duties..............................................................................4-108
4.12.54 Islanded Systems and Frequency Control.....................................................4-109
4.12.55 A Simple Example .........................................................................................4-109
4.13 Frequency Control Questions..................................................................................4-110
4.14 Frequency Control References ...............................................................................4-114
xv
12422963
5.3.2 Long Term Overvoltages...................................................................................5-16
5.3.3 Short Term Overvoltages ..................................................................................5-21
5.3.4 Transient Overvoltages .....................................................................................5-24
5.4 Effects of Low Voltages .............................................................................................5-26
5.4.1 Effect of Low Voltage on System Equipment ....................................................5-27
5.4.2 Effect of Low Voltage on Load Magnitude ........................................................5-27
5.4.3 Effect of Low Voltage on Angle Stability ...........................................................5-33
5.4.4 Effect of Low Voltage on Customer Equipment ................................................5-34
5.4.5 Effect of Low Voltage on Power Losses............................................................5-34
5.5 Effects of High Voltages.............................................................................................5-35
5.5.1 General Effects of High Voltages ......................................................................5-35
5.5.2 Effect of High Voltage on Power Transformers.................................................5-36
5.5.3 Effect of High Voltage on Load Magnitude........................................................5-38
5.5.4 Effect of High Voltage on Angle Stability...........................................................5-38
5.5.5 Effect of High Voltage on Customer Equipment................................................5-38
5.5.6 Effect of High Voltage on Power Losses...........................................................5-39
5.6 Use of Voltage Control Equipment.............................................................................5-40
5.6.1 Use of Capacitors and Reactors .......................................................................5-40
5.6.2 Use of Transformers .........................................................................................5-44
5.6.3 Use of Generators.............................................................................................5-51
5.6.4 Use of Static Var Compensators (SVC) ............................................................5-57
5.6.5 Line Switching for Voltage Control ....................................................................5-61
5.7 Role of the System Operator .....................................................................................5-61
5.7.1 Monitoring Voltage ............................................................................................5-61
5.7.2 Actions to Raise Voltage ...................................................................................5-62
5.7.3 Actions to Lower Voltage ..................................................................................5-62
5.7.4 Reactive Reserves ............................................................................................5-63
5.8 Summary of Voltage Control......................................................................................5-65
5.8.1 Review of Active, Reactive and Complex Power ..............................................5-65
5.8.2 Reactive Power and Low Voltages ...................................................................5-65
5.8.3 Heavy Power Transfers.....................................................................................5-65
5.8.4 Transmission Line Outages ..............................................................................5-65
5.8.5 Reactive Equipment Outages ...........................................................................5-65
5.8.6 Failure to Get Ahead of the Voltage..................................................................5-66
xvi
12422963
5.8.7 Motor Stalling ....................................................................................................5-66
5.8.8 Reactive Power and High Voltages...................................................................5-66
5.8.9 Long Term Overvoltages...................................................................................5-66
5.8.10 Short Term Overvoltages .................................................................................5-66
5.8.11 Transient Overvoltages ....................................................................................5-66
5.8.12 Effect of Low Voltage on System Equipment ...................................................5-67
5.8.13 Effect of Low Voltage on Load Magnitude........................................................5-67
5.8.14 Effect of Low Voltage on Angle Stability...........................................................5-67
5.8.15 Effect of Low Voltage on Customer Equipment................................................5-67
5.8.16 Effect of Low Voltage on Power Losses ...........................................................5-67
5.8.17 General Effects of High Voltages .....................................................................5-67
5.8.18 Effect of High Voltage on Power Transformers ................................................5-67
5.8.19 Effect of High Voltage on Load Magnitude .......................................................5-67
5.8.20 Effect of High Voltage on Angle Stability ..........................................................5-68
5.8.21 Effect of High Voltage On Customer Equipment ..............................................5-68
5.8.22 Effect of High Voltage on Power Losses ..........................................................5-68
5.8.23 Use of Capacitors and Reactors.......................................................................5-68
5.8.24 Use of Transformers.........................................................................................5-68
5.8.25 Use of Generators ............................................................................................5-68
5.8.26 Use of Static Var Compensators (SVC) ...........................................................5-69
5.8.27 Line Switching for Voltage Control ...................................................................5-69
5.8.28 Monitoring Voltage ...........................................................................................5-69
5.8.29 Actions to Raise Voltage ..................................................................................5-69
5.8.30 Actions to Lower Voltage..................................................................................5-70
5.8.31 Maintaining Reactive Reserves ........................................................................5-70
5.9 Voltage Control Questions .........................................................................................5-71
5.10 Voltage Control References ......................................................................................5-73
xvii
12422963
6.3 Types of Voltage Instability ..........................................................................................6-3
6.3.1 Long-Term Voltage Instability .............................................................................6-4
6.3.2 Classical Voltage Instability.................................................................................6-4
6.3.3 Short-Term or Transient Voltage Instability.........................................................6-4
6.4 Long-Term Voltage Instability ......................................................................................6-5
6.4.1 Introduction to Long-Term Voltage Instability......................................................6-5
6.4.2 Radial Power Systems ........................................................................................6-5
6.4.3 Use of the P-V Curve ..........................................................................................6-6
6.4.4 Conditions for Long Term Voltage Instability ....................................................6-10
6.4.5 Long Term Voltage Instability Process..............................................................6-11
6.4.6 Role of Tap Changing Equipment .....................................................................6-12
6.4.7 Tap Changing and Load Magnitude..................................................................6-14
6.4.8 Example of Long Term Voltage Instability.........................................................6-15
6.5 Classical Voltage Instability .......................................................................................6-16
6.5.1 Introduction to Classical Voltage Instability.......................................................6-16
6.5.2 Loss of Load Diversity.......................................................................................6-17
6.5.3 Simulation of Classical Voltage Instability.........................................................6-17
6.5.4 Response of Generation ...................................................................................6-19
6.5.5 Phases of Classical Voltage Instability..............................................................6-21
6.5.6 Introduction to the V-Q Curve ...........................................................................6-21
6.5.7 Usage of the V-Q Curve....................................................................................6-22
6.5.8 Combining P-V & V-Q Curves...........................................................................6-23
6.5.9 Example of Classical Voltage Instability............................................................6-25
6.6 Short-Term or Transient Voltage Instability ...............................................................6-28
6.6.1 Introduction to Short-Term or Transient Voltage Instability...............................6-28
6.6.2 Voltage Instability & Induction Motor Stalling ....................................................6-28
6.6.3 Example of Transient Voltage Instability ...........................................................6-30
6.6.4 Voltage Collapse & Loss of Synchronism .........................................................6-33
6.7 Preventing Voltage Instability.....................................................................................6-34
6.7.1 Dynamic Reactive Reserves .............................................................................6-34
6.7.2 Voltage Control Zones ......................................................................................6-35
6.7.3 Load Shedding ..................................................................................................6-35
6.8 Role of the System Operator .....................................................................................6-36
6.8.1 Detecting Voltage Instability..............................................................................6-37
xviii
12422963
6.8.2 Responding to Voltage Instability......................................................................6-37
6.8.3 Relationship of the Types of Voltage Instability ................................................6-39
6.9 Summary of Voltage Stability.....................................................................................6-41
6.9.1 Introduction to Voltage Collapse & Voltage Stability .........................................6-41
6.9.2 Voltage Stability & Instability Definitions ...........................................................6-41
6.9.3 Voltage Collapse Definition ...............................................................................6-41
6.9.4 Voltage Stability Versus Angle Stability ............................................................6-41
6.9.5 Long-Term Voltage Instability ...........................................................................6-41
6.9.6 Classical Voltage Instability...............................................................................6-41
6.9.7 Short-term or Transient Voltage Instability........................................................6-41
6.9.8 Introduction to Long-Term Voltage Instability....................................................6-41
6.9.9 Radial Power Systems ......................................................................................6-42
6.9.10 Use of the P-V Curve .......................................................................................6-42
6.9.11 Conditions for a Long-Term Voltage Instability.................................................6-42
6.9.12 Long-Term Voltage Instability Process.............................................................6-42
6.9.13 Role of Tap Changing Equipment ....................................................................6-42
6.9.14 Tap Changing and Load Magnitude .................................................................6-42
6.9.15 Example of Long-Term Voltage Instability........................................................6-43
6.9.16 Introduction to Classical Voltage Instability ......................................................6-43
6.9.17 Loss of Load Diversity ......................................................................................6-43
6.9.18 Simulation of Classical Voltage Instability ........................................................6-43
6.9.19 Response of Generation ..................................................................................6-43
6.9.20 Phases of Classical Voltage Instability .............................................................6-43
6.9.21 Introduction to the V-Q Curve...........................................................................6-43
6.9.22 Usage of the V-Q Curve ...................................................................................6-43
6.9.23 Combining P-V & V-Q Curves ..........................................................................6-43
6.9.24 Example of a Classical Voltage Collapse .........................................................6-44
6.9.25 Introduction to Short-Term or Transient Voltage Instability ..............................6-44
6.9.26 Voltage Stability & Induction Motor Stalling......................................................6-44
6.9.27 Example of Transient Voltage Collapse ...........................................................6-44
6.9.28 Voltage Collapse & Loss of Synchronism.........................................................6-44
6.9.29 Dynamic Reactive Reserves ............................................................................6-44
6.9.30 Voltage Control Zones......................................................................................6-44
6.9.31 Load Shedding .................................................................................................6-44
xix
12422963
6.9.32 Detecting Voltage Instability .............................................................................6-45
6.9.33 Responding to Voltage Instability .....................................................................6-45
6.9.34 Relationship of the Types of Voltage Instability................................................6-45
6.10 Voltage Stability Questions .......................................................................................6-46
6.11 Voltage Stability References .....................................................................................6-48
xx
12422963
7.8.1 Purpose of Out-of-Step Protection ....................................................................7-37
7.8.2 Review of Three-Zone Stepped Distance Protection ........................................7-37
7.8.3 Out-of-Step Protection ......................................................................................7-39
7.9 Angle Instability Example...........................................................................................7-41
7.10 Introduction to the Swing Equation............................................................................7-47
7.10.1 Equation for Accelerating Torque .....................................................................7-47
7.10.2 Equation for Accelerating Power ......................................................................7-49
7.10.3 The Swing Equation .........................................................................................7-50
7.11 Synchrophasor Measurements .................................................................................7-51
7.11.1 Concept of a Synchrophasor ............................................................................7-51
7.11.2 The Global Positioning System ........................................................................7-51
7.11.3 Phasor Measurement Units ..............................................................................7-52
7.11.4 The Usage of Synchrophasors .........................................................................7-53
7.12 Role of the System Operator.....................................................................................7-56
7.12.1 Enforce System Operating Guidelines .............................................................7-56
7.12.2 Additional Actions to Maintain Angle Stability...................................................7-56
7.13 Summary of Angle Stability .......................................................................................7-58
7.13.1 Angle & Voltage Stability ..................................................................................7-58
7.13.2 Changing Torque & Power Angles ...................................................................7-58
7.13.3 Out-of-Step/Loss of Synchronism ....................................................................7-58
7.13.4 Angle Stability & Generator Speed...................................................................7-58
7.13.5 Out-of-Step From a Voltage Perspective..........................................................7-58
7.13.6 Relative Nature of Angle Stability .....................................................................7-58
7.13.7 Rotor Dynamics ................................................................................................7-59
7.13.8 Review of Active Power Transfer Equation ......................................................7-59
7.13.9 Review of Power-Angle Curves........................................................................7-59
7.13.10 Maximum Angle Spread ...................................................................................7-59
7.13.11 Angle Stability Classifications...........................................................................7-59
7.13.12 Introduction to Angle Stability Classifications ...................................................7-59
7.13.13 Process of Steady State Stability .....................................................................7-60
7.13.14 Example of Steady State Instability ..................................................................7-60
7.13.15 Process of Transient Stability ...........................................................................7-60
7.13.16 Process of Transient Instability.........................................................................7-60
7.13.17 Transient Stability Following a Fault.................................................................7-60
xxi
12422963
7.13.18 Further Observations with Power-Angle Curves ..............................................7-60
7.13.19 Process of Oscillatory Stability .........................................................................7-60
7.13.20 Process of Oscillatory Instability.......................................................................7-61
7.13.21 Purpose of Out-of-Step Protection ...................................................................7-61
7.13.22 Review of Three-Zone Stepped Distance Protection .......................................7-61
7.13.23 Out-of-Step Protection......................................................................................7-61
7.13.24 Angle Instability Example .................................................................................7-61
7.13.25 Equation for Accelerating Torque .....................................................................7-61
7.13.26 Equation for Accelerating Power ......................................................................7-62
7.13.27 The Swing Equation .........................................................................................7-62
7.13.28 Concept of a Synchrophasor ............................................................................7-62
7.13.29 The Global Positioning System ........................................................................7-62
7.13.30 Phasor Measurement Units ..............................................................................7-62
7.13.31 The Usage of Synchrophasors .........................................................................7-62
7.13.32 Enforce System Operating Guidelines .............................................................7-62
7.13.33 Additional Actions to Maintain Angle Stability...................................................7-63
7.14 Angle Stability Questions ..........................................................................................7-64
7.15 Angle Stability References ........................................................................................7-66
xxii
12422963
8.3.2 Factors that Impact the Natural Frequency.......................................................8-16
8.3.3 Oscillation Frequency Effect on Damping .........................................................8-17
8.3.4 Modes of Oscillation..........................................................................................8-18
8.4 Oscillations & Excitation Systems..............................................................................8-22
8.4.1 Operation of an Excitation System....................................................................8-22
8.4.2 Modern Excitation Systems...............................................................................8-23
8.4.3 Benefits of Fast, Powerful Excitation.................................................................8-24
8.4.4 Excitation Systems and Oscillatory Stability .....................................................8-24
8.4.5 Power System Stabilizers (PSS).......................................................................8-25
8.5 Additional Causes of Oscillations...............................................................................8-26
8.5.1 Cyclic Loads......................................................................................................8-27
8.5.2 Governor Control System..................................................................................8-27
8.5.3 HVDC Systems .................................................................................................8-28
8.5.4 Generator Pole Slipping ....................................................................................8-29
8.6 Role of the System Operator .....................................................................................8-31
8.6.1 Detecting Oscillations........................................................................................8-31
8.6.2 Responding to Oscillations................................................................................8-32
8.7 Summary of Power Oscillations .................................................................................8-33
8.7.1 Definition of Oscillations....................................................................................8-33
8.7.2 Triggering Events ..............................................................................................8-33
8.7.3 Mechanical Analogy for Oscillations .................................................................8-33
8.7.4 Typical Oscillation Frequencies ........................................................................8-33
8.7.5 Oscillation Envelopes........................................................................................8-33
8.7.6 Oscillation Damping ..........................................................................................8-33
8.7.7 Oscillation Classifications..................................................................................8-33
8.7.8 Changes to Power, Speed, and Angle ..............................................................8-34
8.7.9 Feedback Loop for Power, Speed, and Angle ..................................................8-34
8.7.10 Comparison of Power, Speed, and Angle ........................................................8-34
8.7.11 Summary of the Power Oscillation Process .....................................................8-34
8.7.12 Natural Frequency Analogy ..............................................................................8-34
8.7.13 Factors that Impact the Natural Frequency ......................................................8-34
8.7.14 Oscillation Frequency Effect on Damping ........................................................8-35
8.7.15 Modes of Oscillation .........................................................................................8-35
8.7.16 Operation of an Excitation System ...................................................................8-35
xxiii
12422963
8.7.17 Modern Excitation Systems ..............................................................................8-35
8.7.18 Benefits of Fast, Powerful Excitation ................................................................8-35
8.7.19 Excitation Systems and Oscillatory Stability.....................................................8-35
8.7.20 Power System Stabilizers.................................................................................8-36
8.7.21 Cyclic Loads .....................................................................................................8-36
8.7.22 Governor Control Systems ...............................................................................8-36
8.7.23 HVDC Systems ................................................................................................8-36
8.7.24 Generator Pole Slipping ...................................................................................8-36
8.7.25 Detecting Oscillations .......................................................................................8-36
8.7.26 Responding to Oscillations ...............................................................................8-36
8.8 Power Oscillations Questions ....................................................................................8-37
8.9 Power Oscillations References ..................................................................................8-39
xxiv
12422963
9.4.7 Forms of SSR....................................................................................................9-26
9.4.8 When is SSR a Concern? .................................................................................9-29
9.4.9 SSR Example....................................................................................................9-30
9.4.10 Preventing SSR .............................................................................................9-32
9.5 Ferroresonance .........................................................................................................9-32
9.5.1 Introduction to Ferroresonance .........................................................................9-32
9.5.2 Definition of Ferroresonance.............................................................................9-33
9.5.3 Distribution Ferroresonance..............................................................................9-34
9.5.4 Ferroresonance in a Transmission Substation..................................................9-39
9.6 Geomagnetic Disturbances .......................................................................................9-44
9.6.1 Introduction to Geomagnetic Disturbances .......................................................9-44
9.6.2 Sunspots ...........................................................................................................9-46
9.6.3 The Solar Wind .................................................................................................9-47
9.6.4 ESPs & GICs.....................................................................................................9-48
9.6.5 Factors that Influence the Impact of GMDs.......................................................9-50
9.6.6 GIC Entry to the Power System ........................................................................9-53
9.6.7 Impact of GMDs ................................................................................................9-57
9.6.8 Controlling the Impact of GMDs ........................................................................9-63
9.6.9 Hydro Quebec GMD Incident ............................................................................9-66
9.6.10 Role of the System Operator ............................................................................9-69
9.7 Summary of Additional Topics ...................................................................................9-71
9.7.1 Introduction to Additional Topics .......................................................................9-71
9.7.2 Introduction to Harmonics .................................................................................9-71
9.7.3 Description of Harmonics ..................................................................................9-71
9.7.4 Harmonic Content .............................................................................................9-71
9.7.5 Sources of Harmonics.......................................................................................9-71
9.7.6 Flow of Harmonic Current .................................................................................9-71
9.7.7 Effects of Harmonics .........................................................................................9-71
9.7.8 Control of Harmonics ........................................................................................9-72
9.7.9 Introduction to Resonance ................................................................................9-72
9.7.10 Series Resonance ............................................................................................9-72
9.7.11 Parallel Resonance ..........................................................................................9-72
9.7.12 Introduction to Subsynchronous Resonance....................................................9-72
9.7.13 SSR and Series Capacitors..............................................................................9-72
xxv
12422963
9.7.14 Resonance Frequency .....................................................................................9-72
9.7.15 Definition of Subsynchronous Resonance........................................................9-73
9.7.16 Components of System Current .......................................................................9-73
9.7.17 Generator Modes of Oscillation ........................................................................9-73
9.7.18 Forms of SSR ...................................................................................................9-73
9.7.19 When Is SSR a Concern? ................................................................................9-73
9.7.20 SSR Example ...................................................................................................9-73
9.7.21 Preventing SSR ................................................................................................9-74
9.7.22 Introduction to Ferroresonance ........................................................................9-74
9.7.23 Definition of Ferroresonance ............................................................................9-74
9.7.24 Distribution Ferroresonance .............................................................................9-74
9.7.25 Ferroresonance in a Transmission Substation .................................................9-74
9.7.26 Introduction to Geomagnetic Disturbances ......................................................9-74
9.7.27 Sunspots ..........................................................................................................9-74
9.7.28 The Solar Wind.................................................................................................9-74
9.7.29 ESPs & GICs ....................................................................................................9-74
9.7.30 Factors that Influence the Impact of GMDs ......................................................9-75
9.7.31 GIC Entry to the Power System........................................................................9-75
9.7.32 Impact of GMDs ...............................................................................................9-75
9.7.33 Controlling the Impact of GMDs .......................................................................9-75
9.7.34 Hydro Quebec GMD Incident ...........................................................................9-75
9.7.35 Role of the System Operator ............................................................................9-75
9.8 Additional Topics Questions ......................................................................................9-76
9.9 Additional Topics References ....................................................................................9-78
xxvi
12422963
10.3 Summary of Equipment...........................................................................................10-40
10.3.1 Introduction to HVDC Systems.......................................................................10-40
10.3.2 Types of HVDC Systems................................................................................10-40
10.3.3 Components of an HVDC System ..................................................................10-40
10.3.4 Operation of an HVDC System.......................................................................10-40
10.3.5 Introduction to PSTs .......................................................................................10-41
10.3.6 Construction of PSTs .....................................................................................10-41
10.3.7 Operation of PSTs ..........................................................................................10-41
10.4 Equipment Questions ..............................................................................................10-42
10.5 Equipment References............................................................................................10-44
xxvii
12422963
11.4.3 Lightning Arresters .........................................................................................11-54
11.4.4 Transformers ..................................................................................................11-55
11.4.5 Circuit Breakers and Restoration Conditions..................................................11-59
11.4.6 Telecommunication Systems and SCADA .....................................................11-61
11.4.7 Generators and Power System Restoration ...................................................11-62
11.4.8 Usage of Emergency Generators ...................................................................11-69
11.5 Protective Relay Issues Related to System Restoration .........................................11-71
11.5.1 Restoration Conditions and Protective Relaying ............................................11-71
11.5.2 System-Wide Protective Relay Issues............................................................11-73
11.5.3 Transmission Line Protection .........................................................................11-79
11.5.4 Generator Relays ...........................................................................................11-83
11.6 Synchronizing and System Restoration ..................................................................11-87
11.6.1 Review of Synchronizing Theory ....................................................................11-87
11.6.2 Synchronizing Equipment...............................................................................11-88
11.6.3 Synchronizing Examples ................................................................................11-90
11.6.4 Guidelines for Synchronizing Islanded Systems ............................................11-91
11.7 Lessons Learned From Actual System Restorations ..............................................11-93
11.7.1 Problems with Backup Power Sources...........................................................11-93
11.7.2 Problems with Black-Start Capable Generators .............................................11-93
11.7.3 Problems with Circuit Breakers ......................................................................11-93
11.7.4 Problems with Telecommunications ...............................................................11-93
11.7.5 Problems with Computers ..............................................................................11-93
11.7.6 Problems with DC Control Circuitry and Interlock Schemes ..........................11-94
11.7.7 Problems with the Frequency Control Process ..............................................11-94
11.7.8 Problems with the EMS Man-Machine Interface (MMI) ..................................11-94
11.7.9 Problems with Protective Relays ....................................................................11-94
11.7.10 Problems with Special Protection Systems (SPS)..........................................11-95
11.7.11 Problems with Transmission System Design .................................................11-95
11.7.12 Problems Encountered During System Operations........................................11-95
11.7.13 Problems with System Operator Training.......................................................11-95
11.7.14 Problems with the Voltage Control Process ...................................................11-95
11.8 Summary of Power System Restoration .................................................................11-96
11.8.1 Definition of a Restoration Condition ..............................................................11-96
11.8.2 Causes of System Shutdowns .......................................................................11-96
xxviii
12422963
11.8.3 Overview of Key Technical Restoration Issues ..............................................11-96
11.8.4 Restoration Planning ......................................................................................11-97
11.8.5 Voltage Control as a Local Issue....................................................................11-97
11.8.6 Review of Voltage Related Restoration Theory..............................................11-97
11.8.7 Voltage Control in Restoration Conditions......................................................11-97
11.8.8 Operation of the System at Reduced Voltage ................................................11-98
11.8.9 Voltage Based Automatic Load Shedding ......................................................11-98
11.8.10 Frequency Control as an Interconnection Issue .............................................11-98
11.8.11 Maintaining Frequency During Restoration Conditions ..................................11-98
11.8.12 Usage of Governors to Control Frequency.....................................................11-98
11.8.13 AGC and System Restoration ........................................................................11-99
11.8.14 Connecting Islands .........................................................................................11-99
11.8.15 Cold Load Pick-Up Concerns .........................................................................11-99
11.8.16 Maintaining Operating Reserves During Restoration Conditions ...................11-99
11.8.17 Load Curtailment ............................................................................................11-99
11.8.18 Substation Stored Energy ............................................................................11-100
11.8.19 Pipe-Type Cable Systems ............................................................................11-100
11.8.20 Lightning Arresters .......................................................................................11-100
11.8.21 Transformers ................................................................................................11-100
11.8.22 Circuit Breakers and Restoration Conditions................................................11-100
11.8.23 Telecommunication Systems and SCADA ...................................................11-100
11.8.24 Generators and Power System Restoration .................................................11-101
11.8.25 Usage of Emergency Generators .................................................................11-101
11.8.26 Restoration Conditions and Protective Relaying ..........................................11-101
11.8.27 System-Wide Protective Relay Issues..........................................................11-101
11.8.28 Transmission Line Protection .......................................................................11-102
11.8.29 Generator Relays .........................................................................................11-102
11.8.30 Review of Synchronizing Theory ..................................................................11-102
11.8.31 Synchronizing Equipment.............................................................................11-103
11.8.32 Synchronizing Examples ..............................................................................11-103
11.8.33 Guidelines for Synchronizing Islanded Systems ..........................................11-103
11.8.34 Lessons Learned from Actual System Restorations.....................................11-103
11.9 Power System Restoration Questions...................................................................11-104
11.10 Power System Restoration References ................................................................11-107
xxix
12422963
APPENDIX A: GLOSSARY..................................................................................................... A-1
xxx
12422963
LIST OF FIGURES
xxxi
12422963
Figure 2-32. Line-to-Line & Line-to-Ground Voltages .............................................................2-40
Figure 2-33. Power System Current Flow Path ......................................................................2-43
Figure 2-34. Line-to-Ground Faults.........................................................................................2-43
Figure 2-35. Line-to-Line Faults..............................................................................................2-44
Figure 2-36. CT Symbols & Photograph and ..........................................................................2-45
Figure 2-37. PT Symbol & Photograph ...................................................................................2-45
Figure 2-38. Magnetic Attraction Relay Element ....................................................................2-46
Figure 2-39. Induction Disc Relay Element.............................................................................2-47
Figure 2-40. Electromechanical, Solid State & Microprocessor Relays ..................................2-48
Figure 2-41. EM Relay Target.................................................................................................2-49
Figure 2-42. Common IEEE Device Numbers ........................................................................2-51
Figure 2-43. Single-Line Diagram Using IEEE Device Numbers ............................................2-52
Figure 2-44. Zones of Protection Diagram ..............................................................................2-53
Figure 2-45. Voltage Relays on a Single-Line Diagram ..........................................................2-55
Figure 2-46. Overcurrent Relay⎯Time Characteristic Curves ...............................................2-56
Figure 2-47. Normal (No Trip) Conditions for a Differential Relay ..........................................2-57
Figure 2-48. Fault Conditions (Relay Trips) for a Differential Relay........................................2-57
Figure 2-49. One-Line with Bus Differential ............................................................................2-58
Figure 2-50. Single-line Diagram with Differentials .................................................................2-59
Figure 2-51. MHO Characteristic on an R-X Diagram ............................................................2-61
Figure 2-52. Distance Relay Scheme .....................................................................................2-62
Figure 2-53. Simple Transmission Line Pilot Protection Scheme ...........................................2-63
Figure 2-54. Voltage Phase Angle Difference.........................................................................2-66
Figure 2-55. Synchronizing Two Islands.................................................................................2-67
Figure 2-56. Establishing the Second Transmission Tie.........................................................2-67
Figure 2-57. Synchroscope in a Synch Panel.........................................................................2-68
Figure 2-58. Synchronizing System for a Substation Breaker ................................................2-70
Figure 2-59. Rotating Armature With Stationary Field Winding ..............................................2-71
Figure 2-60. Armature Rotation & Voltage Production............................................................2-72
Figure 2-61. Single Phase AC Power Generator ....................................................................2-73
Figure 2-62. Three Phase AC Power Generator.....................................................................2-74
Figure 2-63. 3Φ Power Generator Photograph .......................................................................2-75
Figure 2-64. Two-Pole Rotor Winding Configuration ..............................................................2-77
Figure 2-65. Four-Pole Rotor Winding Configuration..............................................................2-78
Figure 2-66. Torque Wrench Analogy of a Torque Angle .......................................................2-80
Figure 2-67. Torque Angle & Voltage .....................................................................................2-82
Figure 2-68. Pelton Wheel Turbine .........................................................................................2-83
Figure 2-69. Francis Turbine...................................................................................................2-84
xxxii
12422963
Figure 2-70. Wicket Gate Operation .......................................................................................2-85
Figure 2-71. Components of a Wind Turbine..........................................................................2-86
Figure 2-72. Photograph of Wind Turbine Generators............................................................2-89
Figure 2-73. Steam Turbine Stages........................................................................................2-90
Figure 2-74. Steam Turbine Components...............................................................................2-91
Figure 2-75. Basic Combustion Turbine .................................................................................2-93
Figure 2-76. Model of Basic Governor Control System ..........................................................2-94
Figure 2-77. Block Diagram of a Generator Excitation System ..............................................2-95
Figure 2-78. Basic Transformer ..............................................................................................2-96
Figure 2-79. Transformer Turns Ratio ....................................................................................2-97
Figure 2-80. Autotransformer Evolution From a Two-Winding Transformer ...........................2-98
Figure 2-81. Photograph of an Autotransformer .....................................................................2-98
Figure 2-82. 3Φ Transformer Connections .............................................................................2-99
Figure 2-83. Transmission Line Structures ...........................................................................2-101
Figure 2-84. ACSR Conductor ..............................................................................................2-102
Figure 2-85. Typical Transfer Limits .....................................................................................2-103
Figure 2-86. Natural Capacitance of a Transmission Line ....................................................2-104
Figure 2-87. Transmission Line Impedance Model...............................................................2-104
Figure 2-88. Circuit Breaker Opening Process .....................................................................2-105
Figure 2-89. Photograph of Circuit Breaker ..........................................................................2-106
Figure 2-90. Thyrister Symbol & Operation ..........................................................................2-107
Figure 2-91. The Four Major Interconnections of North America..........................................2-109
Figure 3-1. Voltage Phase Angle ............................................................................................3-2
Figure 3-2. Concept of a Voltage to Current Phase Angle (q) ................................................3-4
Figure 3-3. Measurement of the Power Angle (d) ...................................................................3-5
Figure 3-4. Determining Approximate Power Angle from Phase Angles ................................3-6
Figure 3-5. Illustration of Phase & Power Angles ...................................................................3-6
Figure 3-6. Illustration of Actual Power Angle Data ................................................................3-7
Figure 3-7. Synchroscopes & Power Angles ..........................................................................3-8
Figure 3-8. Generator Torque Angle Illustration .....................................................................3-9
Figure 3-9. Transmission Line PI Model ...............................................................................3-10
Figure 3-10. Use of the Active Power Transfer Equation........................................................3-13
Figure 3-11. Use of a Phase Shifting Transformer .................................................................3-16
Figure 3-12. The Power-Angle Curve .....................................................................................3-20
Figure 3-13. Sending End Power-Circle Diagram ...................................................................3-22
Figure 3-14. Sending & Receiving End Circle Diagrams ........................................................3-23
Figure 3-15. System for Illustrating the Use of a Power-Circle Diagram.................................3-24
Figure 3-16. Power-Circle Diagram with a δ of 0° ...................................................................3-25
xxxiii
12422963
Figure 3-17. Power-Circle Diagram with a δ of 40° .................................................................3-26
Figure 3-18. Power-Circle Diagram with a δ of 86° .................................................................3-27
Figure 3-19. Power-Circle Diagram with a δ of 120° ...............................................................3-28
Figure 3-20. Evaluating Power Transfer Limits .......................................................................3-31
Figure 3-21. Illustration of the TTC Concept...........................................................................3-31
Figure 3-22. Determining Distribution Factors ........................................................................3-33
Figure 4-1. Summer Load Curve ............................................................................................4-1
Figure 4-2. Simple Frequency Control System .......................................................................4-2
Figure 4-3. Load/Resources Balance Analogy .......................................................................4-3
Figure 4-4. Accumulating Time Error ......................................................................................4-4
Figure 4-5. Normal Frequency Deviations ..............................................................................4-5
Figure 4-6. Abnormal Frequency Deviations ..........................................................................4-6
Figure 4-7. Frequency Deviations Summary ..........................................................................4-6
Figure 4-8. Relationship Between Load Magnitude & Frequency...........................................4-8
Figure 4-9. Inertia of a Steam Generator Rotor ......................................................................4-9
Figure 4-10. Simple System to Illustrate Governor Control ....................................................4-11
Figure 4-11. Basic Centrifugal Ballhead Governor .................................................................4-12
Figure 4-12. Electro-Hydraulic Governor Block Diagram ........................................................4-13
Figure 4-13. Isochronous Governor Characteristic Curve ......................................................4-15
Figure 4-14. Governor Characteristic Curve with 5% Droop...................................................4-17
Figure 4-15. Droop in a Centrifugal Ballhead Governor..........................................................4-18
Figure 4-16. 300 MW Unit with 5% Droop – Frequency Rise .................................................4-19
Figure 4-17. Changing the Set-Point to 140 MW @ 60 HZ.....................................................4-20
Figure 4-18. 300 MW Unit with 5% Droop – Frequency Drop.................................................4-22
Figure 4-19. Changing the Set-Point to 160 MW @ 60 HZ.....................................................4-23
Figure 4-20. Load/Frequency Relationship & Droop Curves ..................................................4-24
Figure 4-21. Interconnected System Governor Response......................................................4-26
Figure 4-22. Frequency Trace ................................................................................................4-27
Figure 4-23. Comparison of Large & Small Frequency Deviations .........................................4-28
Figure 4-24. Load Sharing – Same Unit Ratings – Same Droop ............................................4-29
Figure 4-25. Load Sharing – Same Unit Ratings – Different Droop ........................................4-30
Figure 4-26. Load Sharing – Same Unit Ratings – One in Isochronous .................................4-31
Figure 4-27. Eastern Interconnection......................................................................................4-33
Figure 4-28. Western Interconnection.....................................................................................4-34
Figure 4-29. ERCOT Interconnection .....................................................................................4-35
Figure 4-30. Definition of a Balancing Authority......................................................................4-42
Figure 4-31. Balancing Authority Interchange.........................................................................4-45
Figure 4-32. Inadvertent Interchange......................................................................................4-46
xxxiv
12422963
Figure 4-33. Primary / Unintentional Versus Secondary / Intentional Inadvertent ..................4-48
Figure 4-34. Components of an AGC System ........................................................................4-50
Figure 4-35. Summary of Modes of AGC Control ...................................................................4-53
Figure 4-36. Tie-Line Bias Control ACE Calculation ...............................................................4-55
Figure 4-37. ACE for an External Generation Loss ................................................................4-56
Figure 4-38. ACE for an Internal Generation Loss..................................................................4-57
Figure 4-39. A Simple Implementation of a Balancing Authority AGC System .......................4-58
Figure 4-40. Operating Reserve Types...................................................................................4-60
Figure 4-41. Operating Reserve Sources ...............................................................................4-61
Figure 4-42. Responsive Reserves.........................................................................................4-62
Figure 4-43. NERC Reliability Coordinators ...........................................................................4-64
Figure 4-44. Interconnection Time Monitors ...........................................................................4-65
Figure 4-45. Initiating Time Error Corrections .........................................................................4-65
Figure 4-46. Conformance with A1 & A2 Criteria....................................................................4-68
Figure 4-47. Violation of A1 & A2 Criteria ...............................................................................4-68
Figure 4-48. Concept of a MW-HZ ..........................................................................................4-72
Figure 4-49. Steam Turbine Off-Frequency Limits..................................................................4-75
Figure 4-50. Formation of an Island........................................................................................4-77
Figure 4-51. Western Interconnection UFLS ..........................................................................4-78
Figure 4-52. UF Load Shedding & Governor Response .........................................................4-79
Figure 4-53. Western Interconnection Automatic Load Restoration .......................................4-81
Figure 4-54. Plot of a Simulated Frequency Disturbance .......................................................4-82
Figure 4-55. Western Interconnection Disturbance Frequency Plot .......................................4-85
Figure 4-56. Eastern Interconnection Disturbance Frequency Plot ........................................4-86
Figure 4-57. Illustration of Frequency Undershoots ................................................................4-88
Figure 4-58. Distance and Frequency Undershoots ...............................................................4-89
Figure 4-59. Speed of the Traveling Frequency Wave ...........................................................4-90
Figure 4-60. Stages of a Generator Response .......................................................................4-91
Figure 4-61. Stage #1 – The Electromagnetic Energy Stage .................................................4-93
Figure 4-62. Stage #2 – The Inertial Stage.............................................................................4-94
Figure 4-63. Stage #3 – Governor Response Stage...............................................................4-95
Figure 4-64. Stage #4 – The AGC Stage................................................................................4-96
Figure 4-65. Data Available to a Generation Control System Operator ..................................4-97
Figure 4-66. Frequency Incident on PJM System ...................................................................4-99
Figure 5-1. Active, Reactive and Complex Power ..................................................................5-1
Figure 5-2. Reactive Power Storage.......................................................................................5-3
Figure 5-3. Use of a Shunt Capacitor .....................................................................................5-4
Figure 5-4. Direction of Reactive Power Flow.........................................................................5-5
Figure 5-5. Radial Power System ...........................................................................................5-6
xxxv
12422963
Figure 5-6. MW & Mvar Losses ..............................................................................................5-7
Figure 5-7. MW Required Versus Mvar Transferred ...............................................................5-8
Figure 5-8. Illustration of Surge Impedance Loading ............................................................5-10
Figure 5-9. Concept of Unscheduled flow.............................................................................5-11
Figure 5-10. Introduction to the P-V Curve .............................................................................5-12
Figure 5-11. Reactive Power & Line Outages – Normal System ............................................5-13
Figure 5-12. Reactive Power & Line Outages – Line Outage .................................................5-13
Figure 5-13. 138 kV Shunt Capacitor Bank Output.................................................................5-15
Figure 5-14. High Voltage Types ............................................................................................5-16
Figure 5-15. Charging Current Flowing into an Open-Ended Line..........................................5-18
Figure 5-16. Voltage Profile Due to Ferranti Effect .................................................................5-18
Figure 5-17. Calculating the Ferranti Effect Voltage Rise .......................................................5-19
Figure 5-18. Ferranti Voltage Rise for Different Length Lines ................................................5-20
Figure 5-19. Source End Voltage Rise ...................................................................................5-21
Figure 5-20. Self-Excitation of a Generator ............................................................................5-22
Figure 5-21. Harmonic Overvoltages ......................................................................................5-23
Figure 5-22. Energizing a Line-Transformer Combination ......................................................5-24
Figure 5-23. Capacitive Switching ..........................................................................................5-26
Figure 5-24. Effect of Voltage on Load Magnitude .................................................................5-28
Figure 5-25. Effect of Voltage on Load Magnitude .................................................................5-29
Figure 5-26. EPRI Load Magnitude Equations .......................................................................5-30
Figure 5-27. Central Air Conditioner Type Load .....................................................................5-32
Figure 5-28. Resistive Space Heater Type Load ....................................................................5-32
Figure 5-29. Voltage and Frequency Decay ...........................................................................5-33
Figure 5-30. Transformer Saturation Curve ............................................................................5-37
Figure 5-31. Transformer Over-Excitation ..............................................................................5-38
Figure 5-32. Information Technology Industry Equipment Voltage Limits...............................5-39
Figure 5-33. Shunt and Series Capacitors..............................................................................5-41
Figure 5-34. Series Compensation .........................................................................................5-42
Figure 5-35. Shunt and Series Reactors.................................................................................5-44
Figure 5-36. Illustration of a Tap Changer ..............................................................................5-45
Figure 5-37. Under Load Tap Changing Mechanism..............................................................5-47
Figure 5-38. A ULTC Control Scheme ....................................................................................5-48
Figure 5-39. Tap Change and Reactive Power.......................................................................5-49
Figure 5-40. Circulating Reactive Power ................................................................................5-51
Figure 5-41. Block Diagram of a Generator Excitation System ..............................................5-52
Figure 5-42. Generator Reactive Capability Curve .................................................................5-54
Figure 5-43. Actual Steam Unit Reactive Capability Curve ....................................................5-55
Figure 5-44. Actual Hydro Unit Reactive Capability Curve .....................................................5-56
xxxvi
12422963
Figure 5-45. Reactive Production Limitations .........................................................................5-57
Figure 5-46. Static Var Compensator (SVC) One-Line ...........................................................5-58
Figure 5-47. Static Var Compensator (SVC) Photograph .......................................................5-59
Figure 5-48. Static Var System (SVS) ....................................................................................5-60
Figure 5-49. Types and Sources of Reactive Reserve ...........................................................5-64
Figure 6-1. Definition of Voltage Stability................................................................................6-2
Figure 6-2. Definition of Voltage Collapse ..............................................................................6-2
Figure 6-3. Voltage Stability Versus Angle Stability................................................................6-3
Figure 6-4. Voltage Instability Types & Time Frames .............................................................6-5
Figure 6-5. Simple Radial Power System ...............................................................................6-6
Figure 6-6. A Sample P-V Curve ............................................................................................6-7
Figure 6-7. P-V Curve Illustration of Voltage Instability ..........................................................6-7
Figure 6-8. Shunt Capacitor Effect on P-V Curves .................................................................6-9
Figure 6-9. Sample Systm to Demonstrate Usage of P-V Curves ........................................6-10
Figure 6-10. P-V Curves for System of Figure 6-9..................................................................6-10
Figure 6-11. Radial Power System for Long Term Voltage Collapse .....................................6-11
Figure 6-12. Tap Changers and Load Overshoot ...................................................................6-13
Figure 6-13. Tokyo Electric’s Shin-Fuji 500 kV Substation Voltage ........................................6-16
Figure 6-14. Conditions at Receiving Bus Prior to Adding 10 MW Load.................................6-18
Figure 6-15. High and Low-Side Voltages After 10 MW Load is Added .................................6-18
Figure 6-16. Adjusting the Generator Operating Point............................................................6-20
Figure 6-17. Temporary Mvar Boost .......................................................................................6-20
Figure 6-18. The V-Q Curve ...................................................................................................6-22
Figure 6-19. Disturbance Report V-Q Curve...........................................................................6-23
Figure 6-20. P-V & V-Q Analysis ............................................................................................6-24
Figure 6-21. Additional View of P-V & V-Q Curves .................................................................6-24
Figure 6-22. One-Line Diagram for July 2, 1996 Disturbance.................................................6-26
Figure 6-23. Boise 230 kV Voltage Collapse ..........................................................................6-27
Figure 6-24. Fan Load Torque/Speed Curve ..........................................................................6-29
Figure 6-25. Air-Conditioner Compressor Load Torque/Speed Curve....................................6-30
Figure 6-26. TVA and MLG&W Power Systems .....................................................................6-31
Figure 6-27. Post Disturbance System Conditions .................................................................6-33
Figure 6-28. Voltage Collapse Due to a Loss of Synchronism ...............................................6-34
Figure 6-29. Voltage Control Zones........................................................................................6-35
Figure 6-30. Time Frames for Voltage Instability ....................................................................6-40
Figure 7-1. Stability: Voltage and Angle..................................................................................7-1
Figure 7-2. Out-of-Step Generator Closing.............................................................................7-3
Figure 7-3. Out-of-Step from a Voltage Perspective...............................................................7-6
Figure 7-4. Relative Nature of Angle Instability.......................................................................7-7
xxxvii
12422963
Figure 7-5. Rotor Torques.......................................................................................................7-8
Figure 7-6. The Power-Angle Curve .....................................................................................7-10
Figure 7-7. Accelerating and Decelerating on a Power-Angle Curve....................................7-11
Figure 7-8. Maximum Possible Angle ...................................................................................7-12
Figure 7-9. Types of Stability/Instability ................................................................................7-14
Figure 7-10. Steady State Instability .......................................................................................7-16
Figure 7-11. Power-Circle Diagram & Steady State Instability................................................7-18
Figure 7-12. Manual Excitation and Steady State Instability...................................................7-19
Figure 7-13. Power System for Transient Stability & Instability ..............................................7-20
Figure 7-14. Power-Angle Curves for 1,000 MW Generator Loading .....................................7-21
Figure 7-15. Strip Chart Equivalent of Figure 7-11 .................................................................7-24
Figure 7-16. Power Angle Curve for Transient Instability .......................................................7-25
Figure 7-17. Transient Stability and a Fault ............................................................................7-27
Figure 7-18. Extended Power-Angle Curve ............................................................................7-28
Figure 7-19. Fast Valving in Steam Units ...............................................................................7-30
Figure 7-20. The BPA Braking Resistor..................................................................................7-31
Figure 7-21. Power System for Oscillatory Stability ................................................................7-32
Figure 7-22. Power-Angle Curve for Oscillatory Stability ........................................................7-33
Figure 7-23. Illustrating Oscillations on a Power-Angle Curve................................................7-34
Figure 7-24. MW Plot Illustration of Oscillatory Stability .........................................................7-35
Figure 7-25. Power-Angle Curve for Oscillatory Instability......................................................7-36
Figure 7-26. MW Plot Illustration of Oscillatory Instability .......................................................7-37
Figure 7-27. R-X Diagram for Three Zone Impedance Protection ..........................................7-38
Figure 7-28. Out-of-Step Relay Characteristic........................................................................7-40
Figure 7-29. Sammis-Star 345 kV Transmission Line R-X Diagram.......................................7-41
Figure 7-30. Twin Cities Area Map .........................................................................................7-43
Figure 7-31. Island Formations ...............................................................................................7-45
Figure 7-32. Island Frequencies .............................................................................................7-46
Figure 7-33. Out-of-Step Voltage Oscillations ........................................................................7-47
Figure 7-34. Concept of a Synchrophasor ..............................................................................7-51
Figure 7-35. The GPS Constellation .......................................................................................7-52
Figure 7-36. North American PMU Locations .........................................................................7-53
Figure 7-37. The WAMS Concept...........................................................................................7-54
Figure 8-1. Rubber Band – Weight Analogy ...........................................................................8-1
Figure 8-2. Rubber Band – Weight Analogy ...........................................................................8-3
Figure 8-3. Three-Phase Power Flow on a Strip-Chart...........................................................8-5
Figure 8-4. Current Oscillation Envelope ................................................................................8-6
Figure 8-5. Normal (Positively) Damped Power Oscillations ..................................................8-8
Figure 8-6. Sustained (Undamped) Power Oscillations ..........................................................8-9
xxxviii
12422963
Figure 8-7. Negatively Damped Power Oscillations..............................................................8-10
Figure 8-8. Loss of a Line to Start an Oscillation ..................................................................8-10
Figure 8-9. Feedback Loop for Power, Speed & Angle ........................................................8-12
Figure 8-10. Plots of Power Output, Angle Spread & Rotor Speed ........................................8-14
Figure 8-11. Steps in a Generator Oscillation.........................................................................8-15
Figure 8-12. High & Low Frequency Oscillations ....................................................................8-18
Figure 8-13. Inter-Area Mode of Oscillation ............................................................................8-19
Figure 8-14. Intra-Area Mode of Oscillation ............................................................................8-20
Figure 8-15. Local Mode of Oscillation ...................................................................................8-20
Figure 8-16. Intra-Plant Mode of Oscillation ...........................................................................8-21
Figure 8-17. Comparison of Local and Inter-Area Mode Oscillations .....................................8-22
Figure 8-18. Generator Excitation System Block Diagram .....................................................8-23
Figure 8-19. Exciter Output Effect on Oscillations ..................................................................8-25
Figure 8-20. Power Oscillations With and Without PSS In-Service ........................................8-26
Figure 8-21. Oscillations Due to Disabling Transient Droop ...................................................8-28
Figure 8-22. Oscillations Caused by Misoperating HVDC Controls ........................................8-29
Figure 8-23. Generator Increasing Angle................................................................................8-30
Figure 8-24. Out-of-Step Conditions .......................................................................................8-31
Figure 9-1. The Ideal 60 HZ Wave..........................................................................................9-2
Figure 9-2. Voltage Wave with Harmonic Content..................................................................9-3
Figure 9-3. Summation of Fundamental with Harmonic..........................................................9-4
TH TH TH TH TH TH RD TH
Figure 9-4. Sum of Fundamental, 5 , 7 , 11 , 13 , 17 , 19 , 23 , & 25 ..........................9-4
Figure 9-5. Static Var Compensator (SVC) One-Line Diagram ..............................................9-7
Figure 9-6. PC Current Waveform ..........................................................................................9-8
Figure 9-7. Flow of Harmonic Current.....................................................................................9-9
Figure 9-8. Autotransformer with Delta Tertiary ....................................................................9-12
Figure 9-9. Simple Harmonic Filter .......................................................................................9-13
Figure 9-10. Sample Tuning of a Filter ...................................................................................9-13
Figure 9-11. Series Resonance ..............................................................................................9-15
Figure 9-12. Series Resonance by Varying Frequency ..........................................................9-16
Figure 9-13. Series Capacitors Usage and Photo ..................................................................9-18
Figure 9-14. Voltages During Series Resonance....................................................................9-19
Figure 9-15. Parallel Resonance ............................................................................................9-20
Figure 9-16. HVDC Converter Simplified One-Line ................................................................9-21
Figure 9-17. 50% Series Compensation .................................................................................9-22
Figure 9-18. Turbine/Generator Shaft Modes .........................................................................9-25
Figure 9-19. SSR Scenario I – Torsional Interaction ..............................................................9-27
Figure 9-20. SSR Scenario II – Transient Torques .................................................................9-28
Figure 9-21. SSR Scenario III – Induction Generator Effect ...................................................9-29
xxxix
12422963
Figure 9-22. Mojave SSR Case Study ....................................................................................9-31
Figure 9-23. Distribution System Ferroresonance ..................................................................9-34
Figure 9-24. Series Resonance Circuit ...................................................................................9-35
Figure 9-25. One-Line for Distribution Ferroresonance ..........................................................9-36
Figure 9-26. Electrical Circuit With Phase “C” Closed ............................................................9-37
Figure 9-27. Electrical Circuit With Phases “B” & “C” Closed .................................................9-38
Figure 9-28. Methods of Preventing Distribution Ferroresonance ..........................................9-39
Figure 9-29. One-Line for Transmission System Ferroresonance ..........................................9-40
Figure 9-30. One-Line for Transmission System Ferroresonance ..........................................9-41
Figure 9-31. Equivalent One-Line of Figure 9-29....................................................................9-42
Figure 9-32. Ferroresonance Voltage Waveform....................................................................9-43
Figure 9-33. Resistor in a Delta Connected Secondary..........................................................9-44
Figure 9-34. Photograph of the Northern Lights .....................................................................9-45
Figure 9-35. Monthly Sunspot Count 1900 – Present.............................................................9-46
Figure 9-36. Solar Wind and Earth Currents...........................................................................9-47
Figure 9-37. Creation of Earth Surface Potentials ..................................................................9-49
Figure 9-38. Geomagnetic Induced Currents..........................................................................9-50
Figure 9-39. Igneous Rock Locations in North America .........................................................9-52
Figure 9-40. Flow of GIC.........................................................................................................9-54
Figure 9-41. GIC Entry to Power System................................................................................9-55
Figure 9-42. Summary of GIC Creation and Entry to Power System......................................9-56
Figure 9-43. Transformer Saturation Curve ............................................................................9-58
Figure 9-44. Excitation Current During Normal & Saturated Operations ................................9-59
Figure 9-45. Transformer Susceptibility to GIC Induced Saturation........................................9-60
Figure 9-46. Use of Neutral Blocking Capacitors ....................................................................9-63
Figure 9-47. Connection Diagram for Neutral Blocking Capacitor ..........................................9-64
Figure 9-48. Summary of K & A Indices..................................................................................9-66
Figure 9-49. Hydro Quebec GMD Incident .............................................................................9-68
Figure 10-1. Advantages of HVDC Systems...........................................................................10-2
Figure 10-2. Disadvantages of HVDC Systems ......................................................................10-3
Figure 10-3. Types of HVDC Systems ....................................................................................10-4
Figure 10-4. Components of an HVDC System .......................................................................10-6
Figure 10-5. Photograph of an HVDC Tower...........................................................................10-6
Figure 10-6. Mercury Arc Valve (MAV) ...................................................................................10-7
Figure 10-7. Photograph of a Mercury Arc Valve....................................................................10-9
Figure 10-8. Thyrister Symbol.................................................................................................10-9
Figure 10-9. Photograph of a Thyrister .................................................................................10-10
Figure 10-10.Single-Phase Converter ...................................................................................10-11
xl
12422963
Figure 10-11. Waveforms for 1Φ Converter..........................................................................10-12
Figure 10-12. Three-Phase One-Way Converter ..................................................................10-12
Figure 10-13. Waveforms for 3Φ One-Way Converter..........................................................10-13
Figure 10-14. Three-Phase Two-Way Converter ..................................................................10-14
Figure 10-15. Waveforms for 3Φ Two-Way Converter..........................................................10-16
Figure 10-16. Twelve-Pulse Converter .................................................................................10-17
Figure 10-17. Comparison of 6 & 12 Pulse Converter Voltages ...........................................10-17
Figure 10-18. Benefits of Multi-Pulse Operation ...................................................................10-18
Figure 10-19. A Bipolar HVDC System.................................................................................10-19
Figure 10-20. Harmonic Content of HVDC Converters .........................................................10-20
Figure 10-21. Six-Pulse Converter Operation Without Gate Control ....................................10-23
Figure 10-22. Two-Pulse Operation Without Gate Control ...................................................10-24
Figure 10-23. Two-Pulse Converter Operation with Gate Control ........................................10-25
Figure 10-24. Six-Pulse Converter Ignition Delay Angles of 0° - 90°....................................10-26
Figure 10-25. Six-Pulse Converter Ignition Delay Angles of 90° - 180°................................10-27
Figure 10-26. Phase Displacement in an HVDC Converter ..................................................10-30
Figure 10-27. HVDC MW Flow Control .................................................................................10-32
Figure 10-28. Use of a PST ..................................................................................................10-33
Figure 10-29. Varying Construction of a PST .......................................................................10-34
Figure 10-30. Phase Angles in a PST...................................................................................10-35
Figure 10-31. Phasor Diagram for Regulating Transformers ................................................10-36
Figure 10-32. PST Operation – Part A..................................................................................10-37
Figure 10-33. PST Operation – Part B..................................................................................10-38
Figure 10-34. PST Operation – Part C..................................................................................10-39
Figure 11-1. Three Types of Restoration Condition..............................................................11-2
Figure 11-2. Concept of Angle Instability Using a Phasor Diagram ......................................11-3
Figure 11-3. Michigan and Ontario Out-of-Step Condition....................................................11-4
Figure 11-4. Voltage Stability MW & Mvar Margins ..............................................................11-6
Figure 11-5. Ice Accumulation on Transmission Conductor .................................................11-7
Figure 11-6. Summary of GMD Cause and Impact...............................................................11-8
Figure 11-7. Phases of the Restoration Process ................................................................11-15
Figure 11-8. Substation and Individual Feeder Restoration Priority....................................11-19
Figure 11-9. Ferranti Effect Open-End Percent Voltage Rise .............................................11-21
Figure 11-10. Diagram of a Generator’s Excitation Control System .....................................11-23
Figure 11-11. Reactive Capability Curve ..............................................................................11-24
Figure 11-12. ULTC Usage in Normal and Restoration Conditions ......................................11-28
Figure 11-13. Plot of a Frequency Disturbance ....................................................................11-31
Figure 11-14. Steam Turbine Frequency Operating Limits ...................................................11-33
xli
12422963
Figure 11-15. 300 MW Unit with 5% Droop Responding to Frequency Drop........................11-36
Figure 11-16. Isochronous Governor Response to Frequency Drop ....................................11-38
Figure 11-17. Tie-Line Frequency Bias Control ACE Calculation .........................................11-40
Figure 11-18. Illustration of Cold-Load Pick-Up ....................................................................11-44
Figure 11-19. UFLS Illustration .............................................................................................11-49
Figure 11-20. Pipe-Type Cable Design.................................................................................11-53
Figure 11-21. Pipe-Type Cable Photograph .........................................................................11-53
Figure 11-22. Transformer In-Rush Current .........................................................................11-56
Figure 11-23. Energizing Back-to-Back Transformers ..........................................................11-57
Figure 11-24. Transformer Over-Excitation ..........................................................................11-58
Figure 11-25. DC Control Schematic for a CB......................................................................11-60
Figure 11-26. Steam Turbine Abnormal Frequency Limits ...................................................11-66
Figure 11-27. Reduced Fault Current Levels........................................................................11-73
Figure 11-28. Operation of a UFLS Scheme ........................................................................11-74
Figure 11-29. CB Closing DC Control Logic Circuitry ...........................................................11-77
Figure 11-30. Use of a Fault Detector in a Distance Scheme...............................................11-80
Figure 11-31. Imbalanced Phase Conductors and Transposition .........................................11-84
Figure 11-32. Large Standing Power Angle..........................................................................11-87
Figure 11-33. A Synch Panel ................................................................................................11-89
Figure 11-34. Synchronizing Two Islanded Systems ............................................................11-90
Figure 11-35. Establishing the Second Transmission Link ...................................................11-91
xlii
12422963
1
TUTORIAL INTRODUCTION
12422963
12422963
Tutorial Introduction
TUTORIAL INTRODUCTION
SECTION OVERVIEWS
1.1 Introduction
Chapter 1 Introduction
1.2 Fundamentals Review
Chapter 2 Introduction
1.3 Active and Reactive Power
Chapter 3 Introduction
1.4 Frequency Control
Chapter 4 Introduction
1.5 Voltage Control
Chapter 5 Introduction
1.6 Voltage Stability
Chapter 6 Introduction
1.7 Angle Stability
Chapter 7 Introduction
1.8 Power Oscillations
Chapter 8 Introduction
1.9 Additional Topics
Chapter 9 Introduction
1.10 Equipment
Chapter 10 Introduction
1.11 Power System Restoration
Chapter 11 Introduction
SO-1
12422963
12422963
Tutorial Introduction
TABLE OF CONTENTS
TOC-1
12422963
Tutorial Introduction
TOC-2
12422963
Tutorial Introduction
TOC-3
12422963
12422963
Tutorial Introduction
1.1 Introduction
This chapter summarizes the contents of the remaining 10 chapters in this tutorial.
1.2 Fundamentals Review
Chapter 2 provides a review of the basic concepts a reader must understand to
gain the maximum benefit from the remainder of the Tutorial. Chapter 2
addresses the following topics:
1.2.1 Introduction to Fundamentals Review
A brief review of Chapter 2 content.
1.2.2 Mathematics Review
Review of basic math concepts of use to a system operator.
1.2.3 DC Electricity Review
Review of DC electrical theory. Topics addressed include current, voltage,
resistance, electrical circuits, Ohm’s law, Kirchhoff’s laws, power and energy.
1.2.4 AC Electricity Review
Review of AC electrical theory. Topics addressed include the advantages of AC
over DC, frequency, vector and phasor diagrams, magnetism and magnetic fields,
AC impedance, phase angle, and AC power.
1.2.5 Protective Relaying Review
Review of basic concepts of power system protection.
1.2.6 Power System Equipment Review
Review of the function of key types of power system equipment such as
transformers, circuit breakers, etc.
1.2.7 Power System Operations
A brief review of the fundamentals of interconnected power system operations.
1-1
12422963
Tutorial Introduction
1-2
12422963
Tutorial Introduction
1-3
12422963
Tutorial Introduction
1-4
12422963
Tutorial Introduction
1-5
12422963
Tutorial Introduction
1-6
12422963
Tutorial Introduction
1-7
12422963
Tutorial Introduction
1-8
12422963
Tutorial Introduction
1-9
12422963
Tutorial Introduction
1.10 Equipment
Chapter 10 describes the construction and operation of high voltage direct current
(HVDC) systems and phase shifting transformers (PSTs). Chapter 10 addresses
the following topics:
1-10
12422963
Tutorial Introduction
1-11
12422963
12422963
2
FUNDAMENTALS REVIEW
12422963
12422963
Fundamentals Review
FUNDAMENTALS REVIEW
SECTION OVERVIEWS
2.1 Introduction to Fundamentals Review
This chapter serves as a review of the basic concepts the reader must understand
to gain the maximum benefit from the remainder of this text.
2.2 Mathematics Review
Review of basic math concepts of use to a system operator.
2.3 DC Electricity Review
Review of DC electrical theory. Topics addressed include current, voltage,
resistance, electrical circuits, Ohm’s law, Kirchhoff’s laws, power and energy.
2.4 AC Electricity Review
Review of AC electrical theory. Topics addressed include the advantages of AC
over DC, frequency, vector and phasor diagrams, magnetism and magnetic fields,
AC impedance, phase angle, and AC power.
2.5 Protective Relaying Review
Review of basic concepts of power system protection.
2.6 Power System Equipment Review
Review of the function of key types of power system equipment such as
transformers, circuit breakers, etc.
2.7 Power System Operations
A brief review of the fundamentals of interconnected power system operations.
SO-1
12422963
12422963
Fundamentals Review
TABLE OF CONTENTS
TOC-1
12422963
Fundamentals Review
TOC-2
12422963
Fundamentals Review
LIST OF FIGURES
LOF-1
12422963
Fundamentals Review
LOF-2
12422963
Fundamentals Review
LOF-3
12422963
12422963
Fundamentals Review
2-1
12422963
Fundamentals Review
As noted in the example above, given a right triangle and the lengths of two of the
three sides, solving for the third side is a simple process. Now that the three side
lengths are known, the next step in solving the right triangle is to determine the
two unknown angles (α & θ) of the triangle. The fact that the three angles of any
triangle always sum to 180°, and that one of the angles of a right triangle is 90°,
simplifies this process. Once one of the unknown angles is determined, the
remaining angle can be found by subtracting the known angle from 90°. To find
the first unknown angle a few basic trigonometric functions must be applied.
2-2
12422963
Fundamentals Review
Sine
The sine of either of
The sine function is a periodic function. A periodic function continually repeats the unknown angles
itself. Figure 2-2 illustrates one cycle or repetition of the sine function. Note that of a right triangle is
the value of the sine function ranges between maximum and minimum values of the ratio of the
opposite side to the
+1 and –1. The sine function value is zero at 0°, 180° and 360°. (360° is the hypotenuse.
same as 0° for the next cycle of the sine function.) In order to solve right
triangles, it is only necessary to know the value of the sine function between
0° and 90°.
Cosine
Figure 2-4 illustrates one cycle of the cosine wave. It is important to note that The cosine of either
the cosine function is identical to the sine function except that the cosine leads of the unknown
angles of a right
the sine function by 90°. When the cosine function “leads” by 90°, it means that triangle is the ratio
the cosine function will reach a certain value 90° before the sine function reaches of the adjacent side
the same value. For example, the value of the cosine function at 0° is one to the hypotenuse.
whereas the sine function does not reach one until 90°.
2-3
12422963
Fundamentals Review
2-4
12422963
Fundamentals Review
Example 1:
Given: Side h =5 and Side a =4
Find Side o, Angle θ, and Angle α
Solution:
To Find Side o, Apply the Pythagorean Theorem:
Side h 2 = Side a 2 +Side o2
25=16 +Side o2
25-16=Side o2
Side o2 =9
Side o = 9 =3
To Find θ, Use Either of the Trig Functions. That is:
Sin θ=Side o/Side h =3/5=0.6→ Therefore Using the Arcsine θ=36.9o
Cos θ=Side a/Side h=4/5=0.8 → Therefore Using the Arccosine θ=36.9o
The Angle α is all That is Left:
180o -90o -36.9o =α =53.1o
2-5
12422963
Fundamentals Review
1000 MW 800 MW
=
0.1HZ ? HZ
800 MW x 0.1HZ = 1000 MW x ? HZ
800 MW x 0.1HZ
?= = 0.08 HZ
1000 MW
When using ratios, it is important to remember that ratios only provide exact
answers in linear systems. A “linear” system means that the relationship between
two variables in the system is the same regardless of the magnitude of the two
variables. Referring back to our previous example with the frequency, as long as
the frequency drops in proportion to the MW loss, regardless of the size of MW
loss, ratios can be used. Few power system dynamic events, including the
frequency, are truly linear. However, this method at least provides an
approximate means to estimate the power system’s performance based
on past events.
Per-Unit Voltages
Figure 2-6 illustrates the use of the per-unit system in a simple power system.
The base voltages are 20 kV for the generator, 345 kV for the transmission and
138 kV for the sub-transmission. The actual and per-unit voltages are illustrated
in the figure.
2-6
12422963
Fundamentals Review
The per-unit system allows a system operator to view a power system and rapidly
obtain a feel for the voltage profile. For example, Figure 2-6 per-unit data
illustrates that the voltage of the lowest magnitude 345 kV bus is 3.2% lower than
any other 345 kV bus.
Per-Unit Impedances
The concept of impedance is explained and illustrated in the next two sections of
this text. Impedance is stated in ohms and is a measure of an element’s ability to
impede or restrict the flow of current. The greater an element’s impedance, the
less current that will flow through the element. Our purpose in bringing up the
concept of impedance at this point is with respect to per-unit quantities.
The impedance of an element (such as a transformer) is often stated as a per-unit
or a per-cent value. For example, a large power transformer may have an
impedance of 5%. Stating the impedance in a percentage form is a variation of
the per-unit system. To convert from a % impedance value to a per-unit value
simply divide the % value by 100. Therefore, a transformer with a 5% impedance
has a 0.05 p.u. (5/100) impedance.
To convert from a p.u. impedance value to the actual impedance stated in ohms,
multiply the p.u. value by the base impedance. The base impedance is dependent
on the voltage level the equipment operates at and the rating (in MVA) of the
equipment. The base impedance is equal to the voltage squared divided by the
MVA. For example, assume a 345 to 138 kV transformer has a 5% or .05 p.u.
impedance. Further, assume the transformer is rated at 100 MVA. To calculate
the transformer’s impedance in ohms first determine the base impedance and then
multiply by the per-unit impedance as illustrated in the following example box.
2-7
12422963
Fundamentals Review
Note in this example, that you would calculate the base impedance and the actual
ohms differently depending on which voltage level you wished to state the
impedance.
345/138 kV Transformer
Impedance Equals 5% = 0.05p.u.
The Greek letter Ω Rating = 100 MVA
(Omega) is used to kV 2 3452
represent the ohms of 345 kV Base Ohms = = = 1190.3Ω
impedance. MVA 100
1382
138kV BaseOhms = = 190.4Ω
100
Actual Ohms on a 345 kV Base = .05 × 1190.3 = 59.5 Ω
Actual Ohms on a138 kV Base = .05 × 190.4 = 9.5 Ω
2.3.1 Current
The 6.24x1018
Definition of Current
represents a very Electrical current is the rate of flow of electrical charge through a conductor.
large number equal
to 6.24 times a 1
Figure 2-7 illustrates how the electrical charge in a conductor is carried by the
with 18 trailing electrons that form the conductor. Current is measured as the amount of charge
zeros. 6.24x1018 is passing through a cross section of a conductor over time. Specifically, current is
simply a shorthand measured in amperes (amps). One ampere of current is equivalent to 6.24x1018
way of writing this (6.24 billion-billion) electrons passing through a cross section of the conductor
large number.
per second.
Current Flow
Electrons in a conductor (like water in a river) require a force to cause a current
flow to occur. The force that causes water to flow in a river is gravity. The
source of the river is higher than the mouth, and therefore the water flows
downhill driven by gravity. The force that causes charge to flow in a conductor
is the voltage. Voltage is the separation of charge between two points on a
conductor. This separation of charge is represented in Figure 2-7 as a battery
connected in series with a conducting path. Electrons have a negative charge and
2-8
12422963
Fundamentals Review
are drawn towards the positive terminal of the battery. Figure 2-7 illustrates a
negative charge flowing from the negative terminal of the battery to the positive
terminal of the battery.
Electrons carry a
negative charge and
are attracted
towards the positive
terminal of the
battery. As the
negative charge
moves, a positively
charged “hole” is
left. The holes can
be viewed as
moving towards the
negative terminal.
Conventional
current flow is
typically thought of
as a movement of
holes from the
positive to the
negative terminal.
2-9
12422963
Fundamentals Review
bigger pipe. The water from the 3 ft2 pipe will flow into the other two pipes in
inverse proportion to the amount of resistance offered by each pipe. Specifically,
2/3 of the water will flow into the 2 ft2 pipe, and 1/3 of the water will flow into
the 1 ft2 pipe.
Electrical current likewise flows proportionally through the conducting paths that
offer the least resistance. When current in a circuit encounters multiple paths, the
current divides and flows along those paths in inverse proportion to the paths’
resistance.
2.3.2 Resistance
Resistance is a measure of the opposition of an electrical circuit to the flow of
current. Every component of the power system has a resistance associated with it.
The resistance of a component is measured in ohms. The Greek letter omega (Ω)
is the symbol used for ohms.
The resistance of a given component is a function of:
Î The resistivity of the material from which the component is made.
(Electrical components are often called conductors.)
Î The length of the component
Î The cross sectional area of the component
Definition of Resistance
Referring to Figure 2-9, resistance is defined as:
2-10
12422963
Fundamentals Review
2-11
12422963
Fundamentals Review
2.3.3 Voltage
The force that causes charge to flow (current) in a conductor is the voltage. The
separation of charge between two points in a conductor gives rise to a potential
difference or a voltage. Electric charge flows down this potential “gradient”, just
as water flows down the physical gradient of a hill or a slanting pipe.
Voltage Source
Generators are a A voltage source is a device that is capable of producing or creating a voltage
very common difference across its terminals. The voltage produced by a generator is called an
voltage source. electromotive force (or EMF) and for this reason is often represented by the letter
“E”. Sources of voltage, such as a generator, are typically also used to convert
non-electrical energy (coal, water, gas, etc.) to electrical energy.
Measured Voltage
The measured voltage is the voltage detected by a voltmeter connected to a point
in the power system. A measured voltage is usually taken between phases in high
voltage systems. A measured voltage can also be taken from phase to ground. A
measured voltage is typically represented with the letter “V”. Any subscript on
2-12
12422963
Fundamentals Review
the measured voltage indicates where the voltage is referenced. For example, VA-
G is the measured voltage from phase “A” to ground. The voltage VA-B is the
measured voltage between phases “A” and “B”.
Voltage Drop
Recall that voltage is the separation of charge that results in a potential for current
flow. Current is the movement of that charge through a conductor. The voltage
drop is the amount of potential lost by the charge as it passes through circuit
elements such as resistors. The voltage drop across a resistor is equal to the
product of the current through the resistor in amperes and the resistance of the
resistor in ohms. This relationship is known as Ohm’s law. Ohm’s law will be
described later in this section in greater detail.
Elements of a Circuit
An electrical circuit is composed of a voltage source, a load, and a supply and
return path connecting the source to the load. An example of an electrical circuit
is the flashlight circuit of Figure 2-11. The voltage source is the two batteries and
the load is the light bulb. The supply path is the direct contact between the
batteries and the light bulb. The return path is the metal case from the bulb to a
spring that the batteries rest on. When the flashlight switch is closed, the circuit is
complete and the bulb glows. Each of the ingredients of an electrical circuit is
described below:
The Source
A voltage source is any device that can serve as a source of voltage. Sources of
voltage typically convert non-electrical energy to electrical energy. Batteries are
a typical source of DC voltage, (batteries convert chemical energy to electric
energy) whereas generators are typical AC voltage sources.
The Load
Any device that consumes electrical energy is called a load. Lights, motors,
heaters and air conditioners are all examples of electrical loads.
2-13
12422963
Fundamentals Review
The return path for an electrical circuit need only be an electrically common point
joining the load and the source. Earth is often the return path in power systems.
Electric generators are normally grounded to the earth. Customer load is
normally grounded to the earth. A utility need only supply the path from the
source to the load and the earth can serve as the return path.
2-14
12422963
Fundamentals Review
V E
I= or I=
R R
Where:
I = Current (Amps)
V = Measured Voltage (Volts)
E = Electromotive Force (Volts)
R = Resistance (Ohms)
2-15
12422963
Fundamentals Review
V 3 Volts
I= = = 4 Amps
R .75 ½
The Sum of All the Currents Flowing Into and Out of Any One
Point In an Electrical Circuit Equals Zero.
The second law is known as Kirchhoff’s Voltage Law and is stated as:
The Sum of All the Voltage Rises and Voltage Drops Around Any
Closed Path In an Electrical Circuit Equals Zero.
2-16
12422963
Fundamentals Review
Using the principles introduced in Section 2.3.2, we can combine the two parallel
resistors into one equivalent resistor as follows:
1 1 1 1 1 3
= + = + =
R EQ R 1 R 2 12 6 12
R EQ = 4½
The simplified circuit is given in Figure 2-14(b). Ohm’s Law can now be used to
find IT.
V 12 V
IT = = = 3A
R EQ 4½
2-17
12422963
Fundamentals Review
Using Kirchhoff’s second law, which states that the sum of the voltages around
any closed path in a circuit equals zero, we can find the current flowing through
resistors R1 and R2. Applying Kirchhoff’s second law to Figure 2-14(a), the
voltage drop across resistor R1 must equal 12 V. Therefore, the current I1 through
resistor R1 equals:
V 12 V
I1 = = = 1A
R1 12 ½
Restated, this law says that the sum of the currents going into a point on a circuit
must equal the sum of the currents going out of that same point. In our example,
this law applied to point “A” yields:
I T = I1 + I 2
3A = 1A + I 2
∴ I 2 = 2A
All the currents in this resistive circuit have now been calculated by applying
Kirchhoff’s and Ohm’s laws.
Power Definitions
Power is the rate at which energy is expended to do work. DC power is defined
as voltage times current and is measured in watts.
PowerDC = VDC × I DC
Instantaneous Demand
The instantaneous demand of a power system is equal to the amount of power
delivered to the system at one point in time. The instantaneous demand is equal
to the voltage times the current and is measured in watts. The instantaneous
demand is constantly changing in a power system.
2-18
12422963
Fundamentals Review
System Load
The system load is equal to the average power delivered over a period of time.
On a power system, the system load is usually stated as the average megawatt (a
megawatt is one million watts) delivered over a particular hour.
Energy Definitions
Energy is defined as the power used over a period of time and is measured in
watt-hours. For example, a 100 watt light bulb which is on for 10 hours uses
1,000 (10 × 100) watt-hours of energy.
Integrated Demand
Energy is more accurately defined as the integrated demand over time. The
integral of demand is equal to the area between the demand curve and the time
axis as illustrated in Figure 2-15. For a load with constant demand, such as the
light bulb mentioned earlier, the integrated demand is equal to the demand times
the period of time that the load is in service. However, if we look at the demand
of a typical household load, we would see an instantaneous demand that is
constantly changing, as lights and appliances are switched in and out-of-service.
The energy consumed by the house is the sum of all the products of instantaneous
demand and time for each time period.
2-19
12422963
Fundamentals Review
AC or DC?
Why use seemingly complicated AC over relatively simple DC? There are
several reasons but the most important is that the AC voltage level can be easily
adjusted using transformers. With AC one can generate at a medium voltage
2-20
12422963
Fundamentals Review
level, transmit at a high voltage level, and then transform down to a much lower
voltage for customer use. As will be explained shortly, the principle of
electromagnetic induction, by which AC transformers operate, does not apply to
direct current.
There are isolated
Frequency pockets of 25 HZ &
50 HZ frequency
Power system frequency is the number of sine wave cycles that the alternating power systems in
current completes each second. In North America, the power system frequency North America but,
is 60 cycles per second. One cycle per second is equal to one hertz (HZ). by far, the majority
Therefore, we say that the power system frequency is 60 HZ. The majority operates at 60 HZ.
of the countries in the world utilize a 50 HZ frequency.
2-21
12422963
Fundamentals Review
2-22
12422963
Fundamentals Review
345R5o 138R10o
2-23
12422963
Fundamentals Review
The term phase A phase angle can be conveniently illustrated on a phasor diagram. A phase angle
angle is normally is the angle between any two phasors. The phase angle may be between two
used to refer to an voltages, two currents, or between a voltage and a current. Figure 2-19 is a
angle between a simple phasor diagram. The phase angle for this circuit is the angle (θ) between
voltage and a
current. However,
the voltage and current. For this example, the current phasor “lags” the voltage
a phase angle can phasor.
be between two
voltages or two
currents. If the
angle is between
two voltages or two
currents, this text
will clearly state the
point.
2-24
12422963
Fundamentals Review
Inductive circuits
have positive or
lagging phase
angles and
capacitive circuits
have negative or
leading phase
angles.
Φ is the symbol
commonly used
to mean phase.
For example 3Φ
means 3-phase.
2-25
12422963
Fundamentals Review
Sources of Magnetism
Magnetism is a property of matter associated with moving charges. The moving
charges may be within the atomic structure of the materials as in magnetized
pieces of iron or steel. These type materials are called permanent magnets.
Magnetism also arises any time there are moving charges associated with an
electric current. For example, an electric current flowing through a straight
conductor or a coil produces a magnetic field. The magnetic field is generally
much stronger for a coil because of the number of turns of wire in which the
current flows. If the coil is wound around a core made of magnetic material,
an electromagnet is created.
Magnetic Fields
A field can be thought of as a force distributed over an area. For example, gravity
is a field. The earth’s gravitational field can be thought of as lines of force that
extend outward from the earth’s center, and weaken with distance. Any object
within the earth’s gravitational field experiences the force of gravity pulling it
toward the earth. Similarly, magnetic fields can be viewed as lines of magnetic
force. Any other magnet placed within a magnetic field will experience a
magnetic force.
Permanent
magnets retain The geometry of magnetic fields varies depending on the source of the field as
their magnetic illustrated in Figure 2-22. Permanent magnets have two poles designated north
field strength. and south. The lines of magnetic force run by convention from the north pole to
Electromagnets
require a current
the south pole. The Earth is a permanent magnet with a magnetic field that can be
source to sustain detected with a compass.
their magnetic
fields.
The magnetic field due to a current in a straight conductor is concentric about the
conductor as illustrated in the right side of Figure 2-22. The intensity of the
magnetic field, due to the current, decreases as the distance from the conductor
increases. The magnetic field due to a coil is similar to that of a permanent bar
magnet. This type of magnetic field is illustrated in the left of Figure 2-22.
Magnetic fields can be confined within magnetic materials such as the iron in a
transformer’s core. In other words, if a magnetic field is set up in an iron
structure, the lines of magnetic force tend to be confined to that structure.
Figure 2-23 contains a simplified transformer core. The core is a rectangular iron
doughnut. If a wire is wrapped around the core and current is passed through it as
shown, a magnetic field is created in the core as illustrated. Because iron is a
better magnetic material than air, most of the magnetic field remains in the core.
2-26
12422963
Fundamentals Review
Electromagnetic Induction
If there is relative motion between a magnetic field and a conductor or if there A voltage is
generated in a
is a change in the magnetic field linking a conductor for some other reason, an conductor if there is
electromotive force⎯or voltage⎯is generated. This voltage causes current to relative movement
flow if an electrical circuit is formed. This concept is called electromagnetic between the
induction. Electromagnetic induction is a very important principle as it is the conductor and a
magnetic field.
basis upon which many types of power system equipment (transformers,
generators, etc.) operate. Figure 2-24 illustrates the concept of electromagnetic
induction.
2-27
12422963
Fundamentals Review
The relative motion between the conductor and the magnetic field may be due to
physical motion of the magnetic field or the conductor or both. The relative
motion may also be due to changes in the magnitude or direction of the magnetic
field. In other words, if a conductor is placed in a fluctuating magnetic field, a
voltage is induced in the conductor.
The magnitude of the induced voltage is dependent on the alignment between the
magnetic field and the conductor. For example, if a conductor is passed through
the densest part of the magnetic field, a large voltage will be produced. However,
if the conductor is passed through the weakest part of the magnetic field a smaller
voltage will be produced.
2.4.4 AC Impedance
Impedance is the AC version of resistance. Actually, resistance is one component
of AC impedance. AC Impedance is made up of two components: resistance and
reactance. Resistance in a power system consists of the resistance of the
conductors and the circuit elements as described earlier in the review of DC
electricity. Reactance arises from the presence of capacitive and inductive effects
in an AC power system. There are two types of reactance, capacitive reactance
and inductive reactance.
Capacitors
A dielectric is an
insulator or a A capacitor is a simple and very common electrical device. All that is needed to
material in which create a capacitor are two pieces of conducting material and a dielectric between
an electrical field the conductors. A capacitor is a circuit element that stores energy in the form of
can be maintained an electrical charge. A capacitor’s stored energy creates an electric field.
with minimum loss
of power.
2-28
12422963
Fundamentals Review
2-29
12422963
Fundamentals Review
2-30
12422963
Fundamentals Review
When an AC voltage is applied to a capacitor, a current flows from the voltage A simple way to view
source and an electrical charge builds up on one plate of the capacitor. There a capacitor in an AC
is no current through the dielectric itself as the dielectric is an insulator. As circuit is to view it as
the AC voltage magnitude increases, charging current flows from the voltage a battery whose
source towards the capacitor’s plate. When the applied AC voltage is polarity varies with
the system frequency.
decreasing, current flows away from the capacitor towards the voltage source.
With an alternating voltage applied, the capacitor alternately charges and
discharges, provided an alternating current flow in the electrical circuit.
Capacitive Reactance
Capacitive reactance (XC) is a measure of how a capacitor affects the flow of AC
current. When a capacitor is placed in an AC circuit, the capacitor builds up a
charge and opposes any further change in the voltage. A capacitor’s natural
opposition to a voltage change is accounted for by calculating the capacitive
reactance of the capacitor. Capacitive reactance is measured in ohms. To
determine the capacitive reactance, it is necessary to know the value of
capacitance (C) in Farads and the frequency (f) of the circuit in Hertz. The
formula for determining the capacitive reactance is:
The term “π”
(Greek letter PI)
1
XC = refers to a constant.
2πfC PI is the ratio of the
circumference to the
Note that the capacitive reactance varies inversely with the frequency. This point diameter of a circle.
is emphasized in later Chapters of this text. Capacitive reactance is a vector as it PI is approximately
equal to 3.14.
does not rotate but does have both a magnitude and a phase angle. The phase
angle for capacitive reactance is -90°.
Inductors
Note that many
An inductor is also a simple and common device. An inductor is a coiled power system
conductor. Inductors are circuit elements that store energy in their magnetic components, such as
transmission lines,
fields. Inductance is a measure of how much energy an inductor can store. are naturally
Figure 2-26 illustrates an inductor and its magnetic field. Note from Figure 2-26 inductive.
that an inductor’s ability to store energy in its magnetic field increases with:
Î The number of turns of the coil
Î The size of the cross-sectional area of the magnetic core
Î The tighter spacing between the coil turns
Î The strength of the magnetic core
2-31
12422963
Fundamentals Review
Inductive Reactance
Inductive reactance (XL) is a measure of how an inductor affects the flow of
current. Inductive reactance is measured in ohms. When AC current flows in a
conductor a “back emf” is produced which causes the current to lag the voltage
and restricts the magnitude of the current flow. This effect is represented with the
inductive reactance. To determine the inductive reactance one must know the
value of inductance (L) in Henries and the frequency (f) of the circuit in Hertz.
The formula for determining the inductive reactance is:
X L =2πfL
2-32
12422963
Fundamentals Review
Z= R + jX T
Where:
Z = Impedance
R = Resistance
X T = X L + XC
X T = Total Reactance
X L = Inductive Reactance
X C = Capacitive Reactance
Keep in mind that XL and XC are 180° out of phase. XL can be considered a
positive reactance while XC can be considered a negative reactance. If you had a
circuit whose inductive reactance was 10 Ω and whose capacitive reactance was 5
Ω, then the total reactance would be 5 Ω (10-5) inductive.
Phase Angle
The phase angle (θ) of a circuit is defined as the angular separation between two
phasors. Figure 2-28 illustrates portions of the voltage and current sine waves for
a circuit. The spacing between the zero crossings of the two waveforms illustrates
2-33
12422963
Fundamentals Review
the phase angle (θ) of the circuit. The phase angle of a circuit is directly related
to the impedance of the circuit. If the impedance of the circuit is purely resistive,
then the voltage and current are in phase, and the phase angle will be zero.
However, the impedance of AC power system circuits is rarely purely resistive.
2-34
12422963
Fundamentals Review
The ELI portion helps you remember the I (current) lags E (voltage) in an
inductive (L) circuit while the ICE portion reminds you that I leads E in a
capacitive (C) circuit.
2.4.5 AC Power
The power that flows in a power system is composed of active and reactive
power. Both power components are necessary to serve customer loads. Without
active power our lights would be dark. On the other hand, all the active power in
the world will not turn the shaft of an electric motor without sufficient reactive
power.
Active Power
Active power is often referred to as real power to distinguish it from reactive
power. Active power is the useful or working energy supplied by a power source.
Note that although the term real power is often used, this may be misleading since
reactive power is also very real. The term active power is preferred and is used in
this text.
Active power is used to perform work such as lighting a room or heating a
building or turning a motor shaft. The unit of active power is the watt (W) but the
more common unit is the megawatt (MW) - equal to one million watts. The
symbol for active power is the letter “P”. The energy a customer consumes and
pays for is expressed as power (for example, kW) used per hour (for example,
kilowatt-hours or kWh).
A generator does
A turbine/generator converts energy from one form to another. For example, not consume
a generator may convert the potential energy of water to electrical energy, or the significant fuel to
chemical energy of coal to electrical energy. When a turbine/generator’s MW produce reactive
power but there still
output is increased, more fuel (water, coal, etc.) must be added to produce more may be a cost
MW. A significant fuel addition is generally not required to produce more associated with the
reactive power. When more reactive power is required, the generator’s reactive power.
excitation system is adjusted or additional capacitors are added to the power Chapter 5 will
system. examine this point.
2-35
12422963
Fundamentals Review
Reactive Power
Reactive power supports the magnetic and electric fields necessary to operate
power system equipment. Reactive power is never consumed by the power
system. Reactive power is stored in the electrical and magnetic fields that exist in
the system. An exchange (at twice system frequency) of reactive power is
continually in progress between those devices that produce reactive power
and those that store reactive power in their electric and magnetic fields.
When electrical equipment is energized via AC voltage, an electric field is
created. When AC current flows through a conductor a magnetic field is created.
These electric and magnetic fields continually build and collapse with the
changing magnitudes of the AC voltage and current. When the electric and
magnetic fields are building, the fields store reactive power. When these fields
are collapsing, the reactive power is returned to the system. No actual energy is
expended (except losses). Reactive power flow is simply a continual exchange of
power and energy.
A look at the inside of a motor⎯even a small one⎯reveals a gap between the
The “Q” symbol for rotating component of the motor and the stationary component of the motor. This
reactive power gap is necessary to allow the rotor to turn and perform some type of work. But
derives from the how do the watts of power used to run the motor get across this gap to be used to
word “quadrature”. turn the rotor? The answer is that the component of AC power called reactive
Quadrature means a
power creates a magnetic field in this air-gap and serves as a type of bridge to
90° phase difference
exists between active allow active power to turn the motor’s rotor.
(P) and reactive (Q)
Reactive power is measured in var. Var stands for volt ampere reactive. The
power.
abbreviation kVar is used for 1,000 var and Mvar for 1,000,000 var. The symbol
for reactive power is the letter “Q”.
A large percentage of electrical loads could not run without var. For example,
all AC-powered rotating equipment, such as refrigerators, washers, dryers, and
Another commonly
heard analogy is industrial motors use var. Transformers could not operate (step-up or step-down
that reactive power voltages) without var.
is the “foam on the
beer” while active Reactive Power Analogy
power is the beer.
The analogy is that Reactive power is often described in terms of an analogy. A useful analogy is to
the foam takes up assume you are part of a 3-person crew who must push a large ball across an
room in the glass of inclined plane from point #1 to point #2. Figure 2-29(a) illustrates this analogy.
beer but it is not
real beer. In the To move the ball from point #1 to #2, the 3-person crew must both push the ball
same manner, in the proper direction but also prevent the ball from rolling down the incline.
reactive power
takes up room in In Figure 2-29b, the active power or MW is the power required to move the ball
the transmission from point #1 to point #2. Two of the 3-person crew performs this task. The
system but does no reactive power or Mvar is the power required to keep the ball rolling in the right
useful work. direction. The Mvar is needed to keep the ball from rolling down the incline.
One of the 3-person crew performs this task.
2-36
12422963
Fundamentals Review
Complex Power
Together, active power and reactive power equals the total or complex power.
Utilities use generators to produce both active and reactive power. Utilities use
the transmission and distribution system to distribute the power to the customer
loads. Complex power is the combination of active and reactive power. Complex
power is the total power the transmission system is carrying. This total flow (the
product of voltage and current) has units of volts-amperes (VA). Electric utilities
commonly use the abbreviation kVA for 1,000 VA and MVA for 1,000,000 VA.
The symbol for complex power is the letter “S”.
Active power and reactive power are quantities that have both magnitude and
direction so they must be treated as vectors when they are added together. The
vector addition of MW and Mvar is described in the next section.
2-37
12422963
Fundamentals Review
MVA 2 = MW 2 +Mvar 2
Power Factor
The cosine of the phase angle between the MVA and MW in the power triangle is
called the power factor. The power factor is also equal to the ratio of active
power and complex power on the system.
Active Power
Power Factor = P.F. =
Complex Power
2-38
12422963
Fundamentals Review
If a load has a unity power factor, the load is purely resistive and requires no
reactive power. If the power factor were zero, the load would be purely reactive
and would not require any MW. Suppose that the load on a power system is 100
MVA with an active power component of 85 MW. The power factor is then 85
MW/100 MW = 0.85. or 85%.
The power factor of a load is a simple way of determining how many MW and
Mvar are needed to serve the load. If the power factor and MVA of the load are
known, the Mvar and MW components can be calculated. For example, in Figure
2-31 the MVA is 100, θ is 25.8°, and the power factor is 0.9 (cos 25.8°). The
MW is easily calculated as 100 x 0.9 = 90 MW and the power triangle used to
calculate that Mvar is 43.6.
2-39
12422963
Fundamentals Review
A balanced 3Φ Figure 2-32 illustrates the relationships between the phase voltage and the line
circuit means that
voltage in a balanced 3Φ circuit. The figure illustrates that the magnitude of the
all three phase
voltages and line voltage is equal to the magnitude of the phase voltage times the square root of
currents are equal three ( 3 ).
in magnitude.
2-40
12422963
Fundamentals Review
The reactive power in a 3Φ circuit is calculated in the same manner. Recall that
the power factor is equal to the cosine θ. The active power is therefore equal to:
2-41
12422963
Fundamentals Review
Selectivity
Selectivity is the ability of the relay to isolate the smallest area of the power
system in order to ensure that no further damage is done. The goal is to not
disrupt more of the power system than is necessary.
Sensitivity
It is vital that relays be able to detect all faults that jeopardize the power system.
Relays must be set sensitive enough to accomplish this goal. However, if set too
sensitively, a relay may initiate tripping for events which are not a threat to the
system.
Reliability
Reliability takes into account most of the principles just described. A reliable
protective relay system should operate when called upon with sensitivity and
selectivity, yet is secure against tripping when not necessary.
2-42
12422963
Fundamentals Review
Line-to-Ground Fault
The most common type of fault on the power system is a line-to-ground (L-G)
fault. One way of incurring a L-G fault is illustrated in Figure 2-32. The
overwhelming majority of L-G faults are caused by lightning either striking or
inducing a large voltage on the line conductors.
A line-to-ground
fault is also called a
phase-to-ground
fault.
2-43
12422963
Fundamentals Review
L-G fault current magnitudes can range from barely noticeable up to values equal
to 3Φ faults. Equipment can be damaged due to the high current magnitudes.
L-G faults also create an imbalance in the power system. Balanced power
systems have equal currents and voltages on all three phases. During L-G faults,
the imbalance may damage rotating equipment such as motors and generators.
Line-to-Line Fault
Line-to-line (L-L) faults are the next most common fault on the power system.
L-L faults can be caused by something as simple as wind blowing two phase
conductors together as in Figure 2-35. L-L faults also cause an imbalance in the
3Φ system. The imbalance impact on generators is the most severe with this fault
type.
A line-to-line fault is
also called a phase-to-
phase fault.
Automatic
Three-Phase Faults
reclosing is an Faults where all three phases are involved are the least likely to occur. However,
automatic attempt
to reenergize a 3Φ faults are usually the most severe as far as levels of fault current are
transmission line concerned. One way of producing a 3Φ fault would be energization of a
(following a short transmission line with a 3Φ ground switch still closed. Since 3Φ faults are the
time delay) after a least likely to occur and are usually of a permanent nature (a structure down or a
transmission line
trip. ground switch closed) automatic reclosing is normally not initiated on the
transmission system for this type of fault.
2-44
12422963
Fundamentals Review
Current Transformers
Instrument transformers designed for transforming current magnitudes are called
current transformers (CTs). CTs produce a small secondary current flow (a few
amps) that is proportional to a larger primary current flow in the power system.
The schematic symbols for CTs are given in Figure 2-34. Two symbols are
illustrated. A bushing CT is located in the bushings of electrical equipment. The
standard CT is a stand-alone device. Also contained in Figure 2-36 is a
photograph of a stand alone CT.
Potential Transformers
Instrument transformers designed for the purpose of transforming voltage are
called potential transformers (PTs). Potential transformers are also commonly
referred to as voltage transformers (VTs). PTs produce a small secondary voltage
(perhaps 120 volt) that is proportional to the higher primary voltage in the power
system. The schematic symbol for a potential transformer is given in Figure 2-37.
2-45
12422963
Fundamentals Review
There is also a picture of 3 PT’s which would be used to form is also a picture of
3 PT’s which would be used to form a 3Φ PT.
A variation on the PT concept is the capacitively coupled voltage transformer or
CCVT. A CCVT is a combination of a PT and a capacitive voltage divider
circuit. CCVTs are often used in place of PTs in applications where high
accuracy is not required.
Electromechanical Relays
Electromechanical (EM) relays were the original type of relays responsible for
protection of the power system. EM relays use electrical inputs (voltage or
current) to control some form of mechanical operation based on magnetic
attraction or induction. Magnetic attraction relay types are either plunger
operated or hinged armature operated as illustrated in Figure 2-38. In a magnetic
attraction relay, the greater the current through the wires, the stronger the
magnetic attraction until a set of electrical contacts close.
2-46
12422963
Fundamentals Review
Induction relay types are typically rotating discs as illustrated in Figure 2-39. Watt-hour meters
Induction relays often produce circular motion. The greater the coil current, operate on the same
the larger the force on the rotating disc. Until eventually a set of contacts principal as
close initiating an action. induction relays.
2-47
12422963
Fundamentals Review
2-48
12422963
Fundamentals Review
Microprocessor-Based Relays
A recent advance in relay technology led to microprocessor based relays.
Microprocessor relays use the same technology as personnel computers to bring
even more functions to relaying. Microprocessor relays can store large Fault detectors
amounts of fault data, perform self-checks, monitor line conditions, and utilize either
carry out the tasks of dozens of individual relays. information on the
fault current
A very important feature (from an operations perspective) is that microprocessor magnitude or the
relays often have internal fault detectors. A fault detector, combined with time delays from
telecommunications capabilities, allows system operators to determine the type voltage and current
pulses to determine
and location of a fault. Fault locations can be determined almost instantly, which
a fault location.
speeds the power system recovery process. Current trends are towards the
purchase of microprocessor-based relays. Figure 2-40 illustrates one type of
microprocessor based relay.
Relay Targeting
A critical factor for system operators doing system restoration following a fault is
interpreting the information provided by the various relays. This information is
provided by relay targets or flags. Relay targets are brief descriptions of what
caused a relay to operate.
Electromechanical relays have targets that drop down when activated. Figure 2-
41 illustrates a typical electromechanical relay target in the reset and tripped state.
When the relay trips a “T” symbol (for a timed operation) is visible. Once the
cause of the relay operation is identified, a button on the relay is pushed to reset
the target. The target for the electro-mechanical relay is visible through the front
glass cover of the relay.
2-49
12422963
Fundamentals Review
2-50
12422963
Fundamentals Review
2-51
12422963
Fundamentals Review
Zones of Protection
It is critical for the proper operation of a power system that protective relaying
covers all areas of the system. To ensure complete coverage, the power system is
divided into zones of protection. Zones are formed around system equipment
such as generators, buses, transformers, transmission and distribution lines, and
motors. What defines a zone is the limit of the relays sensing ability, which are
usually the current transformer (CT) locations.
Figure 2-44 illustrates how a simple power system is broken down into different
zones of protection. Note how the zones overlap at the circuit breakers. In this
manner, no area of the system is left unprotected. Many areas of the power
system are actually in multiple zones of protection as zone overlap often takes
place. When two zones overlap, backup protection is supplied.
2-52
12422963
Fundamentals Review
2-53
12422963
Fundamentals Review
Voltage Relays
Voltage relays include undervoltage and overvoltage relays. In an
electromechanical voltage relay, as voltage magnitude changes magnetic forces
cause relay contact movement. If an overvoltage relay is desired, the relay
contacts are designed to close on increasing voltage. If an undervoltage relay is
desired, the relay contacts close on decreasing voltage.
The value at
which a relay Voltage relays can be designed to operate with no intentional time delay
begins to operate (instantaneous) or with intentional time delay. Once the voltage hits the pickup
is referred to as value, an instantaneous voltage relay begins to operate. In a time delay voltage
the “pickup” relay, the higher the voltage over (or under) a pickup value the faster the relay
value for the
relay. operates.
Voltage relays can also be implemented using solid-state (electronic)
construction. In a solid-state relay, input AC voltages are first converted to a low
magnitude DC voltage. The DC voltages are then compared to a DC voltage
representing the pickup value. In a microprocessor-based relay, input voltages are
converted to digital quantities and decisions made from the digital data.
2-54
12422963
Fundamentals Review
Overcurrent Relays
Overcurrent relays operate if current rises above a pickup value. Overcurrent
relay construction is almost the same as that of the voltage relays described
earlier. The one difference is the input quantity is current rather than voltage.
For the typical overcurrent relay, the amount of time it takes to operate versus the
input current level is known as an “inverse” time characteristic. The inverse term
means that the higher the level of current, the less time it takes the relay to
operate.
Some possible time characteristic curves for overcurrent relays are illustrated in
Figure 2-46. The protection design engineer would choose the correct relay based
on how fast they want the relay to operate for a given amount of input current.
Overcurrent relays are divided into two general categories: non-directional and
directional.
2-55
12422963
Fundamentals Review
a reference from which the relay can determine current flow direction. The
polarizing quantity can be a voltage or a current. If voltage is used, the relay is
voltage polarized. If current is used, the relay is current polarized.
2-56
12422963
Fundamentals Review
Differential Relays
The operating principle of differential relays is that the current flowing into the
protected equipment (or protection zone) must equal the current flowing out. If
what flows in does not match what flows out, a fault is assumed present and the
relay operates. Current transformers surround the protected area and form the
boundary of the zone of protection. The sum of all the CT currents is input to the
differential relay. If power system currents are flowing normally, no current
flows through the relay as illustrated in Figure 2-47.
Differential relays are
simply an application
of Kirchhoff’s Current
Law. Note how the
CT currents circulate
through the relay
wiring but never enter
the 87 relay itself. As
long as the IIN
magnitude is close to
the IOUT magnitude,
the 87 relay does not
activate.
2-57
12422963
Fundamentals Review
Bus Differential
When performing A substation bus is usually protected by a differential relay. The application of a
switching, be sure
switching actions do
differential relay to a bus is demonstrated in Figure 2-49. The important point is
not trigger a to measure all current flows into and out of the bus. If the current that flows into
differential relay the bus does not flow out of the bus, a fault is assumed and the 87B relay
operation. operates. Problems can arise if the bus configuration is changed through
switching. Bus differential relays often have an associated control switch that
will change the current paths from the CT’s to reflect a different bus
configuration.
Figure 2-49 follows on the next page.
Transformer Differential
Differential relaying is applied to most transformers. With transformers,
however, a “percentage” differential relay is often used. A percentage differential
relay requires that the relay tripping current be a certain percentage (possibly
25%) of the transformer’s load current. This helps avoid transformer tripping for
external faults, but still allows the relay to detect and operate for internal faults.
Figure 2-50 illustrates the application of a transformer differential relay. The 87T
is the IEEE device number for a transformer differential.
2-58
12422963
Fundamentals Review
When protecting
a transformer
with a differential
relay, the
protection
designer must
account for the
natural current
difference on the
high and low
sides of the
transformer. This
is accomplished
by properly
choosing the CT
ratios of CT22 and
CT345.
Figure 2-50. Single-line Diagram with Differentials
A problem for transformer differential protection is the high levels of current flow
when the transformer is first energized. This “in-rush” current lasts a very short
time (a few cycles) but can be several times the full load current rating of the
transformer. The in-rush current flows into the transformer to magnetize the core
and does not flow out the other side. In-rush current could cause the differential
relay to operate unless counter measures are taken. Fortunately, transformer Harmonics are
differential relays are available that can tell the difference between load current described in
and in-rush current. These types of differential relays are equipped with a Chapter 9.
“harmonic restraint” feature. Harmonic restraint enables the differential relay to
identify and avoid tripping due to in-rush current.
Generator Differential
Differential relays used in the protection of a generator’s stator windings are
similar to a transformer differential. Generator differentials typically operate
based on a “variable percentage” characteristic. Recall, a percentage differential
relay operates if the relay operating current reaches a specified percentage of the
load current. A variable percentage relay operates on the same principle but the
percentage required for relay operation varies with the load level. A generator
differential at low generator loading would require less of a percentage of load
current to trip than at high loading. Figure 2-50 also illustrates the application of
a generator differential (87G).
2-59
12422963
Fundamentals Review
Distance Relays
Impedance is
measured in ohms Distance relays have both current and voltage inputs. A distance relay divides its
and is a measure of voltage input by its current input (V/I) to calculate the system’s “Z” or effective
electrical distance. impedance. The effective impedance is the impedance of the power system from
The terms the distance relay’s perspective.
impedance and
distance are often If a fault occurs close to a distance relay’s location, current increases and voltage
used decreases, and the relay’s effective impedance shrinks. If a fault occurs far away
interchangeably to
refer to relays that
from a relay’s location, the relay’s impedance does not change significantly.
measure impedance. Assume that a distance relay is installed to protect a transmission line. The
impedance of the protected line is known and input to the relay as part of the
relay’s initial installation procedures. If a fault occurs on the protected line, the
impedance measured by the relay is suddenly less than the known line impedance.
The relay then operates and trips the line.
A distance relay is set to operate based on a certain percentage of the protected
line’s impedance. This is known as the distance relay’s “reach”. For example,
assume a line section has an impedance of 100 Ω. A distance relay may be set to
trip for any impedance detected that is less than 90 Ω. If a fault occurs anywhere
within the first 90% of the line’s length, the relay operates. The reach of this
relay is then 90Ω or 90% of the lines’ natural impedance (100Ω) or length.
Distance relay reaches are stated in terms of zones of protection. For example,
zone #1 reach is usually set between 80 to 90% of the lines length. The reach of
zone #1 is less than 100% to ensure that the relay does not “overreach” or trip for
faults in an adjacent line section.
2-60
12422963
Fundamentals Review
This impedance
plot is called an
R-X diagram.
2-61
12422963
Fundamentals Review
Zone #3 reach is usually 150% (or more) of the protected line’s impedance. Zone
#3 may reach the entire length of the next line section (200%). Zone #3 is also a
time-delayed trip. A typical zone #3 time delay may be 1 second. Zone #3 is
providing time-delayed backup to both zone #2 and zone #1. It should be
apparent to the reader that distance protection schemes are designed to be very
reliable.
Figure 2-52 contains a single-line diagram of a simple distance relay scheme
incorporating three zones of protection. Note that the zones are only shown for
substation “A” of the line. There will be a duplicate set of distance relays at
substation “B” looking back towards substation “A”. If a fault were to occur at
the fault “X” location in Figure 2-52, all three zones of substation “A” would
detect the fault. Zones #2 and #3 are time-delayed backups and would not cause
any circuit breaker tripping unless zone #1 failed to clear the fault. For the line’s
protection to completely fail, all three zones of protection would have to fail to
operate at both substations, “A” and “B”. This is highly unlikely.
2-62
12422963
Fundamentals Review
Pilot Relaying
Faults on the high voltage transmission system often involve tens of thousands of
amps. It is imperative to “clear” the fault (trip the circuit breakers) in as short a
time as possible. Assume a protection scheme relies on zone #2 to trip for faults
beyond zone #1 but before the end of the line. Such a fault location is illustrated
as fault “Y” in Figure 2-52. Since substation “A” zone #2 trips only after a time
delay, the fault is allowed to exist for the duration of the zone #2 time delay. This
could result in a severe system disturbance or equipment damage.
Pilot relaying is widely used to achieve rapid tripping of all terminals of a
transmission line for any fault location on the protected line.
2-63
12422963
Fundamentals Review
Theory of Synchronizing
When closing a circuit breaker between two energized parts of the power system,
it is crucial to match voltages on both sides of the circuit breaker before closing.
If this matching or “synchronizing” process is not done correctly, a power system
disturbance results and equipment (including generators) can be damaged. In
order to synchronize properly, three different aspects of the voltage across the
circuit breaker must be closely monitored.
Note that as used The three aspects of the voltage are called the synchronizing variables and are:
here the term
“phase angle” is 1. The voltages magnitude difference
the phase 2. The frequency difference of the voltages
difference
between two 3. The phase angle between the voltages
voltage
waveforms.
2-64
12422963
Fundamentals Review
Synchronizing Examples
The importance of synchronizing cannot be overstated. All system operators
should understand the theory and practice of synchronizing. If two power
systems are synchronized via an open circuit breaker, and the synchronizing
process is not done correctly, generators and customer equipment could be
severely damaged. Two scenarios for synchronizing are presented to describe the
synchronizing process. In addition, Chapters 3 and 11 will further examine this
important topic.
2-65
12422963
Fundamentals Review
2-66
12422963
Fundamentals Review
If one side of an
Figure 2-56. Establishing the Second Transmission Tie
open circuit breaker
is at 61 Hertz and
Synchronizing Equipment the other side at 60
HZ, the
Synchroscope synchroscope
needle will rotate at
A synchroscope is a simple piece of equipment that is used to monitor the three one revolution
synchronizing variables. A basic synchroscope (illustrated in Figure 2-57) inputs (360 degrees) per
voltage waveforms from the two sides of the open circuit breaker. If the voltage second.
2-67
12422963
Fundamentals Review
waveforms are at the same frequency, the synchroscope does not rotate. If the
voltage waveforms are at a different frequency, the synchroscope rotates in
proportion to the frequency difference. The synchroscope’s needle always points
to the voltage phase angle difference at that moment in time.
A synchroscope is often a manual device in that an operator must be watching
the “scope” to ensure they close the circuit breaker at the correct time. The
synchroscope is normally mounted above eye level on a “synch panel”. The
synch panel also contains two voltmeters so that the voltage magnitudes can be
simultaneously compared.
The synchroscope in Figure 2-57 reflects a slight voltage magnitude mismatch,
and a stationary needle with a phase angle of approximately 35°. The fact that the
synchroscope needle is not rotating indicates frequency is the same on either side
of the circuit breaker. Figure 2-57 also contains a photograph of a synchroscope.
Synchro-Check Relays
In some power
systems, the A synchro-check or synch-check relay electrically determines if the difference in
operator can voltage magnitude, frequency and phase angle falls within allowable limits. The
monitor the three allowable limits vary with the location on the power system. Typically, the
synchronizing
further away from generation and load, the more phase angle difference is
variables via their
SCADA system. tolerated. Synch-check relays typically do not provide indication of the voltage
magnitude, frequency or phase angle. A synch-check relay decides internally
whether its conditions for closing are satisfied. The synch-check relay either
allows or prevents closing depending on its settings. A typical synch-check relay
may allow closing if the phase angle across the circuit breaker is less than 30°.
2-68
12422963
Fundamentals Review
2-69
12422963
Fundamentals Review
2-70
12422963
Fundamentals Review
2-71
12422963
Fundamentals Review
2-72
12422963
Fundamentals Review
armature coil built into the stator. This is the opposite to the configuration of the
simple machine in Figure 2-59.
The generator’s magnetic field is produced by running a DC current (called an The generator’s
exciter is the
excitation current) through the field windings that are embedded in the rotor. source of the DC
This DC current turns the rotor into an electromagnet. The strength of the excitation
generator’s magnetic field can be changed by adjusting the amount of DC current.
current flowing through the field winding.
The rotor is connected to a prime mover, such as a steam or water turbine. The
prime mover provides the mechanical input power to turn the generator’s rotor.
As the rotor turns, a rotating magnetic field is created about the rotor. This field
induces an AC voltage in the armature coil that is embedded in the stator.
Figure 2-61 illustrates the process used to produce electricity in a typical power
generator. The rotating field coil induces an AC voltage in the stationary
armature coil. The excitation current is provided to the rotating field winding
via a brush and slip-ring assembly.
2-73
12422963
Fundamentals Review
The shape,
frequency, and
magnitude of the
voltage produced by
the generator are
dependent on the
generator design
and operation.
The term “AC There are two general types of AC machine: synchronous and asynchronous.
machine” can mean The terms synchronous and asynchronous refer to the relationship between the
either an AC
generator or an AC
machine rotor’s speed of rotation and the power system speed. Power system
motor. speed (or synchronous speed) is the speed of rotation of the AC electrical system
to which the generator attaches.
2-74
12422963
Fundamentals Review
2-75
12422963
Fundamentals Review
Induction Machines
An induction machine operates on the same principal as a transformer (electro-
magnetic induction). Consider the operation of a 3Φ induction motor. The
currents absorbed from the power system via the 3Φ conductors of the induction
motor, create a rotating magnetic field about the stator of the induction motor.
This rotating magnetic field cuts through the induction motor’s rotor conductors,
inducing a voltage in these conductors. Currents then flow in the rotor conductors
creating a rotor magnetic field. The stator magnetic field drags the rotor magnetic
field along with it resulting in motor action.
If the rotor of an induction machine rotates faster than synchronous speed, the
machine is an induction generator. (Note that for this to occur there must be a
prime mover⎯steam turbine, etc.⎯to turn the rotor of the induction machine.) If
the rotor spins slower than synchronous speed, the machine is an induction motor.
The difference between synchronous speed and the speed of the rotor is called the
slip of the induction machine.
An induction In an induction machine, the excitation needed to produce the magnetic field
machine (motor or about the rotor is supplied by the power system to which the machine is
generator) is connected. An induction machine draws in reactive power from the external
always a lagging
load.
power system to magnetize its rotor. Without Mvar from the power system, the
induction machine could not operate. Because induction machines cannot supply
With some Mvar to the system, they are rarely used for large-scale power generation.
modern, large Typically, induction generators have outputs less than one MW. A common
scale, induction usage for induction generators is either as small hydroelectric units or as small
generators (such wind turbines. The reason for using induction instead of synchronous generators
as used in newer
is often cost. Induction generators are considerably cheaper to build due to their
model wind
turbines) relatively simple design.
electronic means
are used to
This text focuses on synchronous generators instead of induction generators.
produce the When this text refers to a generator, a synchronous generator is implied unless
required reactive noted otherwise.
power. Therefore,
larger size (many Synchronous Machines
MW) induction
generators have Synchronous machines are the most common type of generator used for large-
become a reality. scale power production. Synchronous machines can be used to produce both
active and reactive power. This is in contrast to induction machines, which
2-76
12422963
Fundamentals Review
2-77
12422963
Fundamentals Review
F
RPM=120 ×
P
Where:
Î RPM (revolutions per minute) is the speed of the generator rotor
Î F is the frequency of the power system
Î P is the number of magnetic poles in the generator rotor
As can be seen from the formula, as the number of rotor poles increases, the speed
at which the generator rotates decreases. For example, assuming a 60 HZ power
system, a two-pole synchronous generator’s rotor speed is as follows:
60
RPM=120 × =3600
2
60
RPM=120 × =1800
4
2-78
12422963
Fundamentals Review
Generators for steam turbines typically use two or four pole rotors. Most 60 HZ steam
Hydroelectric units rotate at considerably slower speeds and have a much turbine generators
larger number of poles. For example, the speed of a 40 pole hydroelectric spin at 3600 RPM but
generator is: a typical nuclear unit
spins at 1800 RPM.
60
RPM=120 × =180
40
2-79
12422963
Fundamentals Review
2-80
12422963
Fundamentals Review
Now increase the mechanical power input (steam, water, wind, etc.) to the
turbine. The rotor speed briefly picks up above synchronous speed and then
returns to synchronous speed. The angle between the rotor’s magnetic field axis
and the stator’s magnetic field axis (torque angle) increases during the rotor’s
brief acceleration period. A force now exists trying to realign these two magnetic
fields. Since this force is a twisting force about the rotor shaft, it is referred to as
a torque.
If turbine power remained constant, the positive torque angle created by the brief
rotor acceleration would remain constant. The magnetic forces that result from
the existing torque angle result in a current flow in the stator windings. Active
power flows out of the generator.
If turbine power is steadily reduced, the torque angle returns to zero. If turbine
power was reduced even more, the torque angle eventually becomes negative. A
generator with a negative torque angle is actually a motor. The concept of
adjusting a torque angle from a positive to a negative value is a commonly used
operating strategy at large steam power plants. Turbine power is gradually
reduced until the plant’s anti-motoring protection detects the condition and
initiates an orderly plant trip. An equation for active
power flow will be
The torque created between the two magnetic fields of a generator is developed in Chapter
proportional to the sine of the torque angle. This is very important as it 3. This equation will
means that the maximum torque between the stator and rotor fields occurs illustrate the
when the torque angle equals approximately 90°. This is the maximum dependence of active
(theoretical) active power output point of a generator. power flow on the sine
of the torque angle.
Positive Torque Angle for a Generator
When a generator is producing active power, its torque angle is typically less than
20°. If the torque angle is steady, the mechanical force applied by the prime
mover is equal to the opposing electrical force applied by the power system to
which the generator is attached. To change a generator’s torque angle, the
generator must slightly accelerate or decelerate with respect to the power system
to which it is attached.
2-81
12422963
Fundamentals Review
The phase relationship between two rotating magnetic fields can be visualized
in terms of the induced voltages of the two magnetic fields. For example,
Figure 2-67(a) illustrates a generator synchronized to the power system. The
rotating magnetic field of the rotor is in alignment with the rotating magnetic field
of the stator. The voltage waveforms at the bottom of Figure 2-67(a) illustrate
how the magnetic field alignment looks in terms of voltage. EG is the generator’s
internal voltage and VS is the stator voltage. EG and VS are in-phase with one
another. There is no torque angle and no active power output from this generator.
Figure 2-67(b) illustrates a 45° torque angle. The rotor magnetic field leads the
stator’s magnetic field by 45°. Below this graphic is the voltage equivalent. Note
how the torque angle is visible as a difference in-phase between the two voltage
waveforms. The Greek letter “δ” (delta) is commonly used to represent a
synchronous machine’s torque angle.
Generator Turbines
Water Turbines
The prime mover used in hydroelectric power houses is the hydraulic turbine.
Hydraulic turbines are classified into two main divisions: impulse turbines and
reaction turbines.
2-82
12422963
Fundamentals Review
2-83
12422963
Fundamentals Review
The Francis
turbine is used
for medium
(≈ 30 to 1000
feet) head
applications.
The propeller turbine can have either fixed or movable blades. The propeller
design of the turbine allows it to operate at higher speeds than the Francis
turbines. Propeller turbines with movable blades are called Kaplan turbines.
Propeller turbines are used for low (<120 feet) head applications.
The speed control of a hydraulic turbine generator is a function of water flow.
As the load on the generator is increased, the turbine speed decreases. To
compensate, and maintain the relatively constant speed that is necessary for
system frequency control, more water is passed through the turbine.
The speed of a Pelton Wheel turbine is controlled using a nozzle-type control
valve. The amount of water is controlled by opening, shutting, or changing the
direction of needle valves in the nozzles.
The speed of Francis and propeller turbines is controlled using wicket gates.
Wicket gates are located around the inlet flow of the turbine. The gates operate as
a unit and provide a smooth flow of water to the turbine. Figure 2-70 illustrates
wicket gate operation.
The needle valves and wicket gates are managed by the governor control system.
The governor system adjusts the control valves and wicket gates to assist with
maintaining a constant system speed.
A major advantage of a hydroelectric power plant is that there are normally no
turbine thermal restraints that limit how fast the generator can be loaded. A
hydroelectric power plant may be able to supply full electrical power output from
The penstock is the a stopped condition in just a few minutes or possibly even in seconds. Different
water intake types of hydro plants can respond with additional MW at different rates. A high
structure for the head turbine with a long penstock may be severely limited in its MW response
hydro turbine. rate due to water hammer (pressure transients) impacts on the penstock.
2-84
12422963
Fundamentals Review
Wind Turbines
The concept of wind power has been around for thousands of years. Early wind
machines were used to mill grain or pump water for agriculture. In modern times,
wind turbines are often used to convert the energy of the wind into the mechanical
power of rotating blades. The rotating blades are then used to drive the rotor of a
generator and produce a voltage.
Wind turbine installations are suitable for areas with average wind speeds of
approximately 13 mph. Fortunately, large portions of North America are suitable
for wind turbine installations.
Utility-scale wind turbines range in size from 50 kW to as large as 5 to 6 MW.
Many wind turbines are often grouped together to form wind farms. Wind farms
then provide bulk power to the electrical grid. A wind farm typically has enough
turbines to produce 100 MW or more.
The components of a typical wind turbine are illustrated in Figure 2-71 and
described in the text that follows the figure.
2-85
12422963
Fundamentals Review
Blades
The rotor blades capture the wind’s energy and transfer the energy to the low
speed shaft. The design of the blades is based on many of the same principles of
an aircraft wing. The size of the blade varies but a large wind turbine can have
blades over 100 feet in length. Most wind turbines have either two or three
blades. Wind blowing over the blades causes the blades to lift and rotate.
Brake
A disc brake is used to stop the spinning rotor in emergencies.
Controller
The controller is a computer system that monitors current operating conditions.
The controller starts a typical turbine at wind speeds of about 8 to 16 miles per
hour (mph) and shuts off the turbine at about 60 mph. A typical wind turbine
2-86
12422963
Fundamentals Review
cannot operate at wind speeds above about 60 mph because their generators
would overheat. The controller also provides directions to the yaw drive.
Gear Box
Gears connect the low-speed shaft to the high-speed shaft and increase the
rotational speed from about 30 to 60 RPM to about 1200 to 1500 RPM. Most
wind turbine generators spin at 1200 to 1500 rpm. The gear box is a costly (and
heavy) part of the wind turbine and new wind turbine designs are experimenting
with generators that operate at lower rotational speeds and do not require gear
boxes.
Generator
Older wind turbine generators are typically induction machines but newer designs
often utilize synchronous machines. Utility scale generators are typically 600 kW
to 3 MW. Generators produce heat so a cooling system is required. Most wind
turbines use a large fan for air cooling but a few manufacturers use water cooled
generators. Water cooled generators may be built more compactly but they
require a radiator in the nacelle to remove the heat from the liquid cooling system.
High-Speed Shaft
The high-speed shaft drives the rotor of the generator.
Low-Speed Shaft
The wind turbine rotor turns the low-speed shaft at about 30 to 60 RPM. The gear
box speeds up the rotation and interconnects the low and high speed shafts.
Nacelle
The rotor attaches to the nacelle. The nacelle is connected to the top of the tower
and contains the gear box, low- and high-speed shafts, generator, cooling system,
controller, and brake. A cover protects the components inside the nacelle. On a
large wind turbine, the nacelle is large enough for a technician to stand inside
while working. The technician may enter the nacelle through the tower.
Pitch
Blades are turned, or pitched, out of the wind to keep the rotor from turning in
winds that are too high or too low to produce electricity.
Rotor
The blades and the hub together are called the rotor.
2-87
12422963
Fundamentals Review
Tower
The tower of the wind turbine carries the turbine blades and the nacelle. Towers
are made from tubular steel or steel lattice. Because wind speed increases with
height, taller towers enable turbines to capture more energy and generate more
electricity. Typical tower height increases with the MW size of the machine and
will vary from 100 to over 300 feet.
Wind Direction
The design illustrated in Figure 2-71 is an "upwind" turbine because it operates
facing into the wind. Other wind turbines are designed to run "downwind", facing
away from the wind.
2-88
12422963
Fundamentals Review
Steam Turbines
A typical steam unit is composed of more than one turbine. The turbines are
classified by the steam pressure at which they operate. For example, one unit may
include high-pressure (HP), intermediate-pressure (IP), and low-pressure (LP)
turbines. Figure 2-73 illustrates an arrangement of multi pressure stages in a
steam turbine. The turbines themselves are composed of a series of blades or
buckets. Steam strikes the blades and turns the turbine. The blades grow longer
as the stage pressure decreases due to the increase in the volume of the steam.
2-89
12422963
Fundamentals Review
2-90
12422963
Fundamentals Review
2-91
12422963
Fundamentals Review
steam. As the steam goes through the turbine, it expands, which is why a
turbine is larger on one end than the other.
Î Extractions are points along the turbine blade path where steam is bled off
and piped to the boiler feedwater heaters.
Î The exhaust from the high-pressure turbine is piped back to the boiler to
be reheated. This exhaust is called cold reheat steam. Cold reheat steam
is reheated up to about the same temperature as the inlet to the high-
pressure turbine. The steam returning from the boiler returns to the
intermediate pressure turbine and is called hot reheat steam.
Î The intercept valve is located in the hot reheat steam line before the
intermediate pressure turbine. The intercept valve is provided to control
the steam flow from the large storage capacity of the reheat boiler.
Î The reheat stop valve is also located in the hot reheat steam line near the
intercept valve. It is provided for quickly shutting off the supply of
reheated steam to the intermediate pressure turbine. This valve works in
conjunction with the intercept valve.
Î The intermediate-pressure turbine is very similar to the high-pressure
turbine. One major difference is that the blades are longer. Again, this is
because the steam is expanding as the pressure reduces.
Î The crossover is the pipe or duct that contains and guides the steam from
the intermediate pressure turbine to the low-pressure turbine. The
crossover is likely the largest steam line in the entire turbine, as the steam
at this point has expanded 15 to 20 times from the main steam header
volume.
Î The last bit of work will be extracted from the steam in the low-pressure
turbine. After the steam passes through the last row of turbine blades, it
will pass into the condenser where it will turn into liquid water and return
to the boiler.
Steam is created in fossil plants by burning fossil fuels such as coal, oil, and
natural gas. The heat is used to produce steam. The fuel is usually burned in a
furnace or boiler. The walls of the furnace or boiler are lined with tubes through
which water is run. This arrangement is called a waterwall, and is where the
steam is actually created.
In a nuclear plant, heat from a nuclear reaction is used to create steam. The steam
may be produced via a heat exchanger arrangement with the reactor or the reactor
vessel itself may be the steam generator.
Combustion Turbines
Combustion turbines are rotating internal combustion engines that can be used to
turn an electric generator. Combustion turbines⎯often referred to as gas turbines
or peakers⎯utilize the energy released by the burning of a gas or oil fuel to
provide a rotational force to spin the turbine blades.
2-92
12422963
Fundamentals Review
A variation on this
simple cycle
combustion turbine
plant is the combined
cycle plant. In a
combined cycle
plant, the combustion
gases are not
exhausted to
atmosphere. The
exhaust gas is used
to produce heat for a
companion steam
turbine. The
Figure 2-75. Basic Combustion Turbine combined cycle
process is more
After burning occurs, the combustion gases leave the combustion section and efficient than a
strike the turbine blades at a temperature as high as 1600°F and at pressures of simple cycle process
approximately 200-225 pounds per square inch (psi). as less heat is
wasted.
2-93
12422963
Fundamentals Review
The governor shown in Figure 2-76 senses the speed of the generator shaft. The
governor has the ability to adjust the speed of the shaft by adjusting the amount of
steam supplied to the turbine. The speed of the shaft is fed back as an input for
speed control. A governor control system is an example of a feedback control
system. Variations of this type of control system are used in the control of many
devices in the modern world.
2-94
12422963
Fundamentals Review
At normal excitation levels, a generator is neither supplying nor absorbing The term "normal
reactive power from the system. The unit is at unity power factor. When a excitation" is not meant
to imply that a generator
generator is overexcited, it is supplying reactive power to the system. An normally runs at unity
overexcited generator may be referred to as a boosting, lagging or pushing power factor. The term
generator. When a generator is under excited, it is absorbing reactive power means that the
from the system. An underexcited generator may be referred to as bucking, generator's exciter is
leading, or pulling generator. supplying exactly the
excitation the generator
needs to operate.
2-95
12422963
Fundamentals Review
Turns Ratio
The magnitude of voltage induced in a winding depends primarily on the number
of turns in the winding. The voltages in the primary or secondary windings are
proportional to the total number of turns in each winding. By varying the number
of turns between the primary and secondary windings, the voltage that is
transformed via the magnetic linkage can be adjusted. The turns ratio of a
transformer is defined as:
VP V V N
= S or P = P
NP NS VS NS
2-96
12422963
Fundamentals Review
If a transformer
reduces the voltage
level, the current
level must be
increased.
Types of Transformers
A two winding transformer consists of two windings, which are not physically
connected, wrapped around a common core. The transformers illustrated in
Figures 2-78 and 2-79 are examples of two winding transformers.
Figure 2-80 illustrates the evolution from a two winding transformer to an
autotransformer. In an autotransformer the primary and secondary windings are
physically connected. The advantages of an auto-connected transformer include
lower impedance, lower losses, and a smaller excitation current than two winding
transformers. Autotransformers are typically applied when the primary to
secondary voltage ratio is less than 2.5:1. The direct electrical connection
between the high and low voltage sides can be a disadvantage. A two winding
bank provides a certain degree of electrical isolation between the primary and
secondary. Autotransformers do not provide this electrical isolation. Figure 2-81
contains a photograph of a large autotransformer. This transformer has a 500 kV
high side and a 230 kV low side. It is rated at 600 MVA.
2-97
12422963
Fundamentals Review
An autotransformer
can be created by
starting with a two
winding transformer
and then physically
connecting the
primary and
secondary windings.
2-98
12422963
Fundamentals Review
Transformer Connections
Large power transformers are 3Φ transformers. A 3Φ transformer may be
constructed as a 3Φ unit or composed of three separate 1Φ transformers
connected for 3Φ operation. The most common 3Φ connections are the delta and
wye configurations. Figure 2-82(a) illustrates a 3Φ transformer connected in wye
on the high side and delta on the low side. Note that the wye connection has a
common point for all windings while the delta has all three windings connected in
series. A wye winding is also called a star winding.
2-99
12422963
Fundamentals Review
Transformer Capacity
When a company purchases a power transformer, they specify the maximum rated
load. The transformer’s nameplate lists this rated load. The rated load is a
function of the transformer design and the type of auxiliary cooling systems with
which the transformer is equipped. For example, a transformer may have three
rated loads such as 30/40/50 MVA. The different rated loads apply depending on
the available cooling systems.
A 30/40/50 MVA bank may have a 30 MVA limit if no auxiliary cooling is used.
If a first stage of fan cooling is operational, the bank has a 40 MVA limit. If a
second stage of fans is operational, the bank has a 50 MVA limit. The maximum
temperature rise in a transformer is typically 65° C above ambient. This
temperature limit applies no matter what cooling systems are available.
2-100
12422963
Fundamentals Review
The wire positions at the top of the towers in Figure 2-83 are for shield wire
connections. Shield wires are used to protect the transmission line from lightning
strikes.
2-101
12422963
Fundamentals Review
are power losses due to the intense electric field that surrounds high voltage
conductors. Larger diameter conductors have reduced corona losses.
2-102
12422963
Fundamentals Review
230 300
345 700
500 1400
2-103
12422963
Fundamentals Review
2-104
12422963
Fundamentals Review
2-105
12422963
Fundamentals Review
2-106
12422963
Fundamentals Review
2-107
12422963
Fundamentals Review
Once a thyrister has been turned on by a pulse of gate current it can be turned off
with changes to its anode or cathode voltage. The gate current is only used to turn
the device on, not to turn it off. Thyristers are small devices by power system
standards. Each thyrister is about the size of a hockey puck. In a typical power
application, thousands of thyristers are arranged in series/parallel combinations to
achieve the desired voltage and current ratings. Common utility applications of
thyristers are static var compensators (SVC) and high voltage direct current
(HVDC) converters.
2.7 Power System Operations
Electric suppliers from throughout North America have many things in common.
The shared goal is to provide reliable service to the customers in a safe and
efficient manner. This section explains how the North American power system is
configured and briefly describes the role of the North American Electric
Reliability Corporation (NERC).
2-108
12422963
Fundamentals Review
2-109
12422963
Fundamentals Review
In the late 1960’s and early 1970’s, attempts were made to tie the Eastern and
Western Interconnections together with AC transmission lines. The lines
frequently tripped and caused more problems than they solved. The capacity of
the lines was too small to tie such large systems together. The AC ties were
opened permanently in the early 1970’s. The East and West Interconnections are
currently tied together but the ties are via HVDC, not AC.
2-110
12422963
Fundamentals Review
A. Leading
B. Lagging
C. Underexcited
D. Dropping
A. 87
B. 86
C. 67
D. 50
2-111
12422963
Fundamentals Review
6. The actual voltage is 362 kV on a 345 kV bus. What is the p.u. voltage?
A. 1.0
B. 1.05
C. 1.5
D. .95
7. A load has a power factor of 0.9 lagging. If the load draws 100 MVA,
what is the MW draw?
A. 100
B. 90
C. 111
D. 44
A. Phase angle
B. Frequency difference
C. Voltage magnitude difference
D. MW flow differential
A. 199 kV
B. 230 kV
C. 345 kV
D. 500 kV
2-112
12422963
Fundamentals Review
2-113
12422963
12422963
3
ACTIVE AND REACTIVE POWER
Power
Circle
Diagram
12422963
12422963
Active and Reactive Power
SECTION OVERVIEWS
3.1 Introduction to Active and Reactive Power
A brief introduction to the concepts of MW and Mvar.
3.2 Review of Active and Reactive Power
A review of active power, reactive power, complex power, phase angles, power
angles, and torque angles.
3.3 Equations for Power Transfer
Equations are developed for active and reactive power transfer.
3.4 Graphical Tools for Power Transfer
Graphical techniques are developed to analyze power flow including:
Î Power-angle curve to help determine angle stability
Î Power-circle diagram to illustrate active and reactive power flows as
voltage, impedance, and power angle change
3.5 Power Transfer Limits
Active power transfers are constrained by thermal, angle stability, and voltage
limits.
3.6 Distribution Factors
Distribution factors are calculated to estimate how MW flow distributes in the
power system.
SO-1
12422963
12422963
Active and Reactive Power
TABLE OF CONTENTS
TOC-1
12422963
Active and Reactive Power
TOC-2
12422963
Active and Reactive Power
LIST OF FIGURES
LOF-1
12422963
12422963
Active and Reactive Power
LIST OF EQUATIONS
LOE-1
12422963
12422963
Active and Reactive Power
3-1
12422963
Active and Reactive Power
Different names are Phase, power, and torque angles are used to describe the operation of a power
often used for these system. This section explains the difference between the three angles.
angles. For
example, the terms Voltage & Current Angles
bus angle, load
angle and voltage To fully understand the concept of a phase angle, first understand voltage and
angle are sometimes current angles. Recall the shape of power system voltage and current waves from
used in place of
power angle. The
Chapter 1. The voltage and current waves are sine waves that repeat themselves
term rotor angle is every 1/60TH of a second. Each full cycle of the voltage and current sine wave
sometimes used in can be further broken down into 360°.
place of torque
angle. At the beginning of the sine wave cycle, the magnitude is zero since the sin 0° is
equal to zero (0). The maximum value of the sine wave occurs at 90° and is equal
to one (1) while the minimum value occurs at 270° and is equal to minus one (-1).
An alternating voltage behaves like a sine wave as illustrated in Figure 3-1(b).
3-2
12422963
Active and Reactive Power
Current waves may have current angles. The current angle (θI) is the angular
separation between two current waveforms. In the sections that follow it is
sometimes useful to look at the voltage angle of a bus with respect to the current
angle at the same bus.
The equations for the two voltage waves in Figure 3-1 are written below each The Greek letter
wave. The term “ωt” represents the time changing nature of the voltage wave. “w” (omega) is the
Notice how in the right Figure 3-1(b) equation the sine value is purely a function angular frequency.
Omega is equal to
of the ωt term. There is no voltage angle in this equation. In contrast, the left 2p times the
Figure 3-1(a) voltage wave equation is for the sine of (ωt + 45°). The 45° is the frequency (w =2pf).
voltage angle and represents a 45° left shift of the voltage wave with respect to
the other voltage waveform. The Greek letter “ω” (omega) is the angular
frequency. Omega is equal to 2π times the frequency (w = 2pf).
Figure 3-1 illustrated how voltage angles are shown graphically and in equation
form. Throughout this text a shorthand method of stating a current or voltage
magnitude and angle is used. For example, if the voltage magnitude is 355 kV
and the voltage angle is 45°, a shorthand way of stating this is 355 ∠45°.
Phase Angle
The phase angle at a point in a power system is the angular separation, or
difference in phase, between the current and the voltage waves. The Greek letter
theta with no subscript (θ) is used to represent the phase angle. Recall that if
current lags voltage—as in an inductive system—θ is positive. If current leads
voltage, as in a capacitive system, θ is negative. The phase angle is defined to be
positive when voltage leads current. The phase angle relationships are illustrated
in Figure 3-2.
Recall also that the phase angle between current and voltage is the same as the
angle between active (MW) and complex power (MVA). The value of θ varies
from one point in a power system to another.
3-3
12422963
Active and Reactive Power
3-4
12422963
Active and Reactive Power
Figure 3-3. Measurement of the Power Angle (d) Active power flows
downhill on power
There is a simple rule of thumb that states that active power flows downhill on angle.
power angle. Active power flows from points where the measured voltage is
more leading to points where the measured voltage is more lagging. In
Figure 3-3, the active power must flow from the sending bus (VS) to the
receiving bus (VR).
When a phase angle between voltage and current is measured it is for a point in The two voltage
the power system. For example, the phase angle for a bus may be 20°. When a waves must be
compared at exactly
power angle is measured it is a measurement between two locations. The power the same time to
angle is the angular difference between voltages at two points. In Figure 3-3, the measure an
power angle is approximately 75°. A δ of 75° means there is a 75° angle between accurate power
the sending and receiving bus voltages. angle.
The larger the power angle (up to approximately 90°), the larger the active power
flow between the two points. Sustained operation with a δ greater than 90° leads
to an out-of-step condition. Out-of-step is
defined in Section
3.4 of this chapter.
Approximate Relationship Phase & Power Angles
Now that we have defined phase angle and power angle separately, we can
describe their approximate relationship to one another. Consider the simple two
bus system of Figure 3-4. Assume that there is no angular difference between the
current waves at the two buses (i.e., the two current vectors are in-phase). The
power angle is then equal to the difference between the phase angles at the buses
or:
3-5
12422963
Active and Reactive Power
Note that θI is
negative in both of
these calculations.
3-6
12422963
Active and Reactive Power
A typical transmission system operator is not normally aware of the phase and
power angles in the system. However, every time a system operator uses a
synchroscope or a synch-check relay to close a circuit breaker, the power angle is
monitored.
3-7
12422963
Active and Reactive Power
Use of Synchroscopes
The three
A circuit breaker synchroscope is illustrated in Figure 3-7. A synchroscope
quantities compares the frequency, voltage phase angle, and voltage magnitude on both
monitored by a sides of an open circuit breaker. If the frequency on either side of the circuit
synchroscope are breaker is different the synchroscope rotates. The position of the rotating needle
called the represents the voltage phase angle across the circuit breaker or the power angle.
synchronizing
variables. The If the needle is at 12:00, the power angle is 0°. If the needle is at 6:00, the power
synchronizing angle is 180°. Ideally, the needle is rotating very slowly and reaches 0° at the
variables are: instant the circuit breaker is closed.
1. Frequency
Difference When synchroscopes are used in the transmission system, the frequency
2. Phase Angle difference is usually very small. If the power angle measured is too large, a
Difference system operator adjusts generation levels in the system to lower the angle and
3. Voltage
Magnitude
allow a closure.
Difference
3-8
12422963
Active and Reactive Power
about the rotor and fed DC current from the generator’s excitation system. A
synchronous generator is designed so the rotor turns at synchronous speed. This
creates a rotating electromagnetic field.
When a generator is first connected to the power system, the rotating
electromagnetic field of the rotor is synchronized to the rotating electromagnetic
field that naturally exists in the 3Φ power system. The generator is synchronized
by adjusting the generator speed, voltage magnitude, and phase to within a desired
range. Once voltage and speed are within this range the generator circuit breaker
is closed and the two rotating fields combine. The two rotating fields are “in-
step” with one another when they are synchronized.
The torque angle of a generator is the angular difference between the rotor’s
rotating magnetic field and the rotating magnetic field about the stator of the
generator. Figure 3-8(a) represents a generator that is synchronized to the system
but has no MW output. The angular difference between the rotor and stator
magnetic fields is 0°. Both fields are rotating in lock-step with one another.
Figure 3-8(b) represents a generator that is synchronized and sending MW to the
system. Notice that the rotor field leads the stator field by a torque angle of 30°.
The magnetic field of the rotor is pulling the magnetic field of the stator along
with it. The generator is injecting a large amount of energy into the power system
as a result of the magnetic force it is exerting on the system. The generator has a
MW output as a result of this torque angle.
The torque angle of a generator has a large impact on the MW delivered by the See Figure 2-67
generator to the system. Within certain limits, the larger the torque angle the for an illustration
of torque angle in
more MW the generator outputs. The torque angle of a generator is very similar terms of a voltage
to the power angle measured between locations in the power system. A angle difference.
generator’s torque angle is the difference in phase between a generator’s internal
or excitation voltage and the unit’s stator voltage. Both torque and power angles
are voltage angle differences. The torque and power angles determine the
direction and magnitude of active power flow in the system.
3-9
12422963
Active and Reactive Power
In the PI model for a transmission line, Z is equal to the series impedance of the
transmission line. Z includes both the line’s series reactance (XL) and the line’s
series resistance (R). XC is the line’s capacitive reactance. The line’s capacitive
reactance represents the natural capacitive nature of the transmission line.
Also shown on the model are the sending end voltage (VS) and current (IS) and the
receiving end voltage (VR) and current (IR). The model of Figure 3-9 is used to
develop simple equations for the transfer of active and reactive power between the
sending and receiving ends of the line.
3-10
12422963
Active and Reactive Power
Using the data from our transmission line model in Figure 3-9 and applying
Kirchhoff’s voltage and current laws, the four equations in Equation 3-1 are
developed. These equations define the sending and receiving end voltages (VS
and VR) and currents (IS and IR). Note the bar symbols above the voltage, current,
and impedance values. The bar symbol means the quantity is a vector or phasor.
For example, the symbol means the receiving end voltage phasor has both a
magnitude and an angle.
⎛ VR ⎞ ⎛ VS ⎞
VS = V R + ⎜ I R − ⎟Z V R = VS − ⎜ IS − ⎟Z
⎝ XC ⎠ ⎝ XC ⎠
VS VS − V R VR VS − V R
IS = + IR = − +
XC Z XC Z
Equation 3-1. Power Transfer Equation Set #1
The complex power (the MVA or S) is always equal to the voltage times the
current. The equations in Equation 3-2 are for the MVA flowing out of the
sending end of Figure 3-9 and into the receiving end of the line. The sending end
MVA is equal to the sending end voltage times the sending end current. The
receiving end MVA is equal to the receiving end voltage times the receiving end
current.
A few of the symbols used in Equation 3-2 require further explanation.
Î The “j” symbol signifies that the reactive power terms are 90° out-of-
phase with the active power terms.
Î The angle term “δ” (Greek letter delta) is the voltage phase angle (the
power angle) between the sending (VS) and receiving (VR) buses.
Î The hat symbol (^) is a math concept (called a conjugate) used to ensure
the proper sign conventions are used for reactive power.
3-11
12422963
Active and Reactive Power
VS
The “Z” term has PS = ⎡ V R − RVR cosδ + X L VR sin δ ⎤⎦
been separated into Z2 ⎣ S
its R+jXL
components in V ⎡ V ⎤
QS = S2 ⎢ VS X L − X L VR cosδ + RVR sin δ − S Z2 ⎥
these equations. Z ⎣ XC ⎦
V
PR = R2 ⎡⎣ −VR R + RVS cosδ + X L VS sin δ ⎤⎦
Z
VR ⎡ VR 2 ⎤
QR = ⎢ −VR
X L
+ X L
VS
cosδ − RVS
sin δ + Z ⎥
Z2 ⎣ XC ⎦
Equation 3-3. Power Transfer Equation Set #3
The equations of Equation 3-2 are simplified by assuming that the series
Ignoring the series
resistance is a good
resistance (R) is much smaller than the series reactance (XL) and then ignore the
approximation for series resistance. The simplified equations in Equation 3-4 are the result:
high voltage
transmission lines. VS × VR VS2 − VS VR cosδ VS2
PS = sin δ QS = −
XL XL XC
VS × VR −VR2 + VS VR cosδ VR2
PR = sinδ QR = +
XL XL XC
Equation 3-4. Power Transfer Equation Set #4
The four equations in Equation 3-4 define the sending and receiving end active
and reactive power flows. When the bus voltages, the series reactance (XL), the
line charging (XC), and the power angle (δ) are known, the active and reactive
powers can be calculated. If the voltages used are line-to-line values, the power
flows calculated are 3Φ values.
To simplify our usage of the power transfer equations, from this point on, we
concentrate on the sending end equations. The sending end equations are listed in
Equation 3-5.
3-12
12422963
Active and Reactive Power
VS × VR
PS = sin δ
XL
The MW flow is
from the leading bus
to the lagging bus.
3-13
12422963
Active and Reactive Power
VS × VR
P= δ = PMAX δ
XL
This simplification
of the active power In this very simple form of the active power transfer equation the angle δ is stated
transfer equation in radians. Angles can be stated in terms of degrees or in terms of radians. To
only applies if d is
convert from degrees to radians multiply the number of degrees by . For
less than 20° and d
is expressed in example, assume we wanted to determine the MW transfer between two points
radians (not with a power angle of 20°. To convert 20° to an equivalent number of radians
degrees). multiply 20 by 2π 360 . The result is 0.35 radians. The active power transfer
between our two points is now .35 x PMAX. To determine the actual MW transfer,
we need determine only PMAX.
Voltage Magnitude
If the voltage magnitude of either the sending or receiving bus is increased, either
the active power transferred increases or the power angle decreases. Higher
voltages allow transfer of more active power, or transfer of the same amount of
active power with a lower angle. Assume we have a system with several possible
paths from the source to the load. If the voltage levels along one of the paths are
increased, more active power flows on that path.
Path Impedance
We use “XL” as
the path The “XL” in the denominator of the active power transfer equation is the
impedance
impedance impact on active power flow. As “XL” is increased either active
because we are
assuming the power flow decreases or the power angle increases. As “XL” is decreased active
resistance (R) is power flow increases or the power angle decreases. If two paths exist between a
much smaller than source and a load, more power flows on the lower impedance path. Every system
the reactance (XL) operator should understand the statement that “power flows the path of least
and so ignore
impedance”. More power flows on the lower impedance path.
resistance.
3-14
12422963
Active and Reactive Power
System Equipment
System equipment can have a large impact on active power flow. As new
transmission lines are added system active power flows redistribute to incorporate
the new path. System equipment such as transmission lines, transformers, etc.,
has natural impedance and so impacts the flow of active power.
Phase shifting
There are some types of equipment whose primary function is to adjust system transformers or
active power flows. One example of this type of equipment is a phase shifting PSTs may also be
transformer (PST). PSTs are transformers whose function is to adjust the flow of called phase angle
active power. Figure 3-11 illustrates the use of a PST. In Figure 3-11(a), 530 regulators or PARs.
MW of active power is flowing into a two path system. Power splits according to
the path of least impedance so most flows over the lower impedance underground
cable. Assume this power split overloads the underground cable while barely
loading the overhead line.
From a system operations perspective something must be done to relieve the
overloading on the underground cable. An option is to decrease the total system
flow below 530 MW to some manageable level for the underground cable.
However, this option prevents the transmission path operator from fully utilizing
their transmission system.
In Figure 3-11(b) a PST is installed in the underground cable. The PST is used to
control the magnitude of the power angle across the underground cable. If the
power angle can be controlled, the flow of MW can be controlled. The PST in
Figure 3-11(b) pushes a portion of the MW that normally flows across the cable
onto the parallel overhead line.
3-15
12422963
Active and Reactive Power
Chapter 10 of this
text describes the
construction,
operation and use of
PSTs in greater
detail.
⎡ V 2 − VS VR cos δ ⎤ VS2
QS = ⎢ S ⎥−
⎢⎣ XL ⎥⎦ X C
The last term in the equation ( ) represents the effect of transmission line
capacitance. (Notice that the higher the line voltage, the greater the line’s Mvar
production.) For now, ignore the line capacitance. The reactive power transfer
equation then simplifies to:
⎡ V 2 − VS VR cos δ ⎤
QS = ⎢ S ⎥
⎢⎣ XL ⎥⎦
The reactive power transferred between two points is therefore determined by the
voltage magnitudes at the two points and the cosine of the power angle between
the points.
3-16
12422963
Active and Reactive Power
In normal power system operations, the power angle between two connected
The Cosine of 20 is
buses is small. If δ is small (< 20°) the cosine δ term is very close to one (1). equal to 0.94.
If we assume that the power angle stays small then the reactive power transfer
simplifies even further to:
VS (VS − VR )
QS =
XL
The critical part of this equation is the portion in parenthesis or (VS – VR). This
portion tells us that Mvar will flow from the higher voltage to the lower voltage.
Reactive power does normally flow from the high to the low voltage bus. This is
a rule of thumb every system operator should know.
However, we also determined the conditions for which this rule of thumb is true.
Recall that we assumed the power angle was small and so ignored the cosine
term. If δ had been large (> 20°), we could not have ignored the cosine term.
When power angles exceed approximately 20°, the rule of thumb that reactive
power flows from high to low voltage no longer applies. Reactive power can
flow from the low to the high voltage bus if the power angle between the buses is
large enough.
VS2 − VS VR cos δ
QS =
Factors that Effect Reactive Power Flow XL
By considering the reactive power transfer equation and other factors we can VS2
−
judge the impact of various actions and system equipment on reactive power XC
flow. For reference, the reactive power transfer equation is repeated in the Equation 7
margin.
Voltage Magnitude
Reactive power flow is strongly tied to voltage magnitudes. When a generator is
asked to increase its terminal voltage it does so by increasing its DC excitation
current. This increases the generator’s internal excitation voltage. The higher
internal voltage of the generator leads to more Mvar flowing out of the unit.
3-17
12422963
Active and Reactive Power
When shunt capacitors are placed in-service the voltage at the point of the
capacitor insertion increases. Reactive power flows from this high voltage point
and disperses throughout the power system.
Path Impedance
The “XL” also appears in the denominator of the reactive power transfer equation.
As the “XL” of a path is increased, the reactive power usage of the path increases
(greater I2XL) and the reactive power transfer across the path decreases. As the
“XL” of a path is decreased, the reactive power usage of the path decreases and
the reactive power transfer increases. In the same manner as active power flow,
reactive power flows the path of least impedance.
System Equipment
System equipment has a very strong impact on reactive power flow. When
voltage control equipment such as capacitors, reactors, or tap changing
transformers are used to adjust voltage this equipment is actually controlling the
flow of reactive power. Voltage control is reactive power flow control. The two
cannot be separated. Chapter 5 of this text will examine the operation and use of
several types of voltage (reactive power flow) control equipment.
3-18
12422963
Active and Reactive Power
tool for visualizing how MW and Mvar flow with changing power system
conditions.
VS × VR
PS = sin δ
XL
The [(VS x VR)/XL] portion is a relatively constant value and is called PMAX.
PMAX is the largest possible MW transfer between two strong buses. The MW
transfer can only reach PMAX if the power angle is 90°. The amount of PMAX
actually transferred between the two points is dependent on the term sine δ. For
example, assume the power angle is 30°. The sine of 30° is ½ so ½ of PMAX is
transferred between two points if the power angle is 30°.
Figure 3-12 is a plot of the active power transfer equation. This plot is called the
power-angle curve. The power-angle curve is obtained by multiplying the PMAX
value by the sine δ term. Since the value of the sine function varies from 0 to 1 to
0 to -1 to 0, the power-angle curve magnitude varies from 0 to +PMAX to 0 to -
PMAX to 0. With active power transfer we are normally only concerned with the
first ½ cycle of the power-angle curve so we ignore the negative half cycle.
The power-angle curve graphically illustrates that the maximum continuous active The maximum
power transfer between any two strong buses occurs when the power angle power transfer
between these same two points is 90°. (This also could be determined from the actually occurs at
active power transfer equation as the maximum value of sine δ occurs when the transmission
line’s impedance
δ = 90°.) angle. The
impedance angle is
Point “A” in Figure 3-12 represents a point at which a medium amount of active
dependent on the
power (PA) is being transmitted from the sending bus (VS) to the receiving bus relative amounts of
(VR). The power angle for the active power transfer at point “A” is δA which is line resistance and
much less than 90°. Point “B” represents a point at which the maximum amount reactance. The
of power (PMAX) is being transmitted between the two buses. The power angle at line’s impedance
angle is always less
point “B” is 90°. Point “C” is for a power transfer with a δ greater than 90°. Note than 90° since there
that the power transfer at point “C” is less than at point “B”. As the power angle is always some
rises above 90°, the active power transfer decreases. resistance. Our use
of 90° is a
simplification that
assumes the line’s
resistance is much
smaller than its
reactance.
3-19
12422963
Active and Reactive Power
If the power angle reaches a high level (above 90°) and attempts to stay there,
synchronism is eventually lost between the two buses. It is impossible to operate
to the right of point “B” for an extended (more than a few cycles) period of time.
There is a very important feature to the power-angle curve of Figure 3-12. The
mechanical power input line is the horizontal dashed line through the power-angle
curve. This line represents the amount of mechanical power input to the generator
connected to the sending end. The mechanical power input line may cross the
power-angle curve at any point. Figure 3-12 shows the mechanical power input
line crossing near the middle of the power-angle curve. As the mechanical power
input to the generator varies, the mechanical power input line position varies.
The intersection of the mechanical power input line and the power-angle curve
yields the possible operating points. One of these points is an acceptable
operating point while the other would be unacceptable. For example in
Figure 3-12 point “A” is acceptable while point “C” is unacceptable. Operation at
point “C” would result in a loss of synchronism.
3-20
12422963
Active and Reactive Power
terms used to indicate angle instability are loss of synchronism, slipping poles,
and out-of-step operation.
When a section of the power system is operated in a state where the power angle
between the ends of a transmission line is close to 90°, we say that the system is
being operated at PMAX or at its steady state stability limit. For example, if a
major transmission line were operated with a power angle of 90° it would be at its
steady state stability limit. This is not an acceptable normal point of operation, as
any system disturbance, even minor, would cause the power system to lose
synchronism.
When the interconnected power system loses synchronism, portions of the system
operate at slightly different frequencies than the remainder of the system. A loss
of synchronism means that the magnetic bond that existed between points within
the interconnected power system is too weak to maintain a constant frequency.
The magnetic bond fails and the system eventually separates into smaller sections
or islands. Each island would then attempt to maintain its own separate 60 HZ
frequency.
Power systems lose synchronism when power transfers rise to such large
magnitudes that power angles reach excessive values. Power systems cannot
operate in an interconnected manner after synchronism is lost. When
synchronism is lost protective relays likely operate and system separation often
occurs. Some portions of the interconnected system may end up as electrical
islands that are unable to maintain scheduled frequency. System generators and
customer motors in these low or high frequency islands may be damaged if the
island is allowed to exist for too long a period with the abnormal frequency.
The term out-of-step is another way of saying that a section of power system has
lost synchronism with the remainder of the power system. The magnetic bond
between a generator’s rotor and the power system the generator is connected to
normally holds the generators respective magnetic fields in-step. When this bond
is broken, the generators are no longer in-step with the system but are out-of-step.
3-21
12422963
Active and Reactive Power
⎡ VS2 VS2 ⎤ ⎡ VS VR ∠δ ⎤
SS = ⎢ + + −
⎢⎣ Zö X ö ⎥⎥ ⎢ Zö ⎦
⎥
C⎦ ⎣
S1 S2
⎡ VR2 VR2 ⎤ ⎡ VS VR ∠δ ⎤
SR = ⎢ − − +
⎢⎣ Zö X ö ⎥⎥ ⎢ Zö ⎦
⎥
C⎦ ⎣
R1 R2
Equation 3-6. Equations for the Power-Circle Diagram
The sending and receiving end complex power equations form the outlines of
circles when plotted on the appropriate axis. Figure 3-13 is an example of a
possible circle diagram plot if sending end data from the equations of Equation 3-
12 are plotted. The complex power out of the sending end (SS) is equal to S1 plus
S2. The vector S1 starts at the origin and determines the center of the sending end
circle. The vector S2 starts at the end of S1 and determines the radius of the
sending end circle. A circle is then drawn with the end of S1 as the center and
with a radius of S2.
This diagram
assumes that the
system voltages and
impedance do not
change. If we
wanted to illustrate
voltage or
impedance changes
we would draw a
new sending end
circle with a
different diameter
and center location.
The sending end circle in Figure 3-13 can be used to determine the active and
reactive power flows out of the sending end for any power angle. For example,
Figure 3-13 illustrates that with a power angle of 0° (δ is equal to 0° along the
vector S2) the sending end MW is equal to P0 and the sending end Mvar is equal
to -Q0. The negative sign on the reactive power means the Mvar is flowing from
the line into the sending end bus. Figure 3-13 also illustrates the MW and Mvar if
3-22
12422963
Active and Reactive Power
the power angle is increased to 70°. Note the MW is P70 and the Mvar Q70 (the
Mvar flow is positive so it has reversed direction.)
Given a simple power system we are often interested in what happens to the
sending and receiving end MW and Mvar flows as we vary the power angle.
Figure 3-14 expands on the illustration of Figure 3-13 by adding the receiving end
circle to the diagram.
The power angle is the angle between the sending and receiving voltages so it is
the same from either end of the line. As the power angle is raised to 70°, the MW
and Mvar flows for the sending and receiving buses change. You could determine
the MW and Mvar flows out of the sending bus and into the receiving bus by
noting the positions of the 70° power angle lines in Figure 3-14.
3-23
12422963
Active and Reactive Power
3-24
12422963
Active and Reactive Power
Figure 3-17 is a power-circle diagram for the same system. All that has changed
from Figure 3-16 is that power angle has been increased to 40°. Note the increase
in both the MW and Mvar flows at both ends of the system. As the power angle
is raised the system is pushed harder and harder. Figure 3-17 shows us that with a
power angle of 40° our system has a:
Î Power flow from the sending bus into the transmission line of 640 MW
and +150 Mvar.
Î Power flow from the transmission line into the receiving bus of 610 MW
and -200 Mvar.
The 40° angle has resulted in increased MW and Mvar flow. Note the MW flow
out of the sending bus is 640 while the MW flow into the receiving bus is 610.
The difference is the line losses. The line losses grow as the power angle is
increased. Also note the Mvar flow is now into the line from both buses. The
heavy current flow on the line has resulted in large reactive power usage. The
system must supply this reactive power to the line or the bus voltages will fall.
3-25
12422963
Active and Reactive Power
Î Power flow from the sending bus into the transmission line of 1030 MW
and 825 Mvar.
Î Power flow from the transmission line into the receiving bus of 900 MW
and -870 Mvar.
Power circle
diagrams are not The active power losses for the system have climbed to 130 MW. The
designed to evaluate transmission line is absorbing 1,695 Mvar to support its bus voltages. Figure 3-18
a system’s angle has a power angle of 86° which is unacceptably high. Operating at this high an
instability risk. angle would likely be unstable as this angle is across only one line section.
The high power flow levels of Figure 3-18 are likely beyond the thermal
Section 3.5 of this capability of the transmission line. The equations we described in this chapter
chapter describes and the graphical tools presented are for calculating the power flows on system
thermal operating elements. The equipment itself may be thermally damaged when the power angle
limits. and flows grow to high values. It is often up to the system operator to ensure
system power flows do not violate thermal limits.
3-26
12422963
Active and Reactive Power
If the power angle is increased above 86°, the MW flow starts to decrease. The
Mvar flow, however, continues to increase. The maximum Mvar flow occurs at
an angle near 180°. Remember that any angle greater than approximately 90°
cannot be sustained without the power system losing stability.
In Figure 3-19 the power angle has risen to 120°. This is not an acceptable
operating angle. This large of an angle is illustrated only to show its effect on
system power flows. Note that the MW flow has shrunk from its previous peak
value. The Mvar flow has climbed to a very high value. With a power angle of
120° we have:
Î Power flow from the sending bus into the transmission line of 930 MW
and 1,360 Mvar.
Î Power flow from the transmission line into the receiving bus of 720 MW
and -1,430 Mvar.
Angles in excess of 90° are not an acceptable operating point but do briefly occur
on occasions. When a system suffers a loss of synchronism power angles grow
beyond 90°. As noted in Figure 3-19, when power angles grow beyond 90°, Mvar
flows reach very high magnitudes.
3-27
12422963
Active and Reactive Power
3-28
12422963
Active and Reactive Power
3-29
12422963
Active and Reactive Power
3-30
12422963
Active and Reactive Power
It does not
matter which
way the reactive
power is
flowing, it still
contributes to
the current
magnitude.
3-31
12422963
Active and Reactive Power
TTC numbers are directional. The TTC in Figure 3-21 is from area 1→2. The
TTC from area 2→1 may be more or less than 1200 MW.
The available transfer capability or ATC of a transmission path is the amount of
the TTC that the Transmission Service Provider for the transmission path has
available for sale to any marketing entities that may want to purchase the transfer
capability. In other words, the ATC is that portion of the TTC that is available for
further commercial activity.
For example, in Figure 3-21, assume the transmission operator sells 1000 MW of
the area 1 to area 2 TTC. The ATC from area 1 to area 2 is now reduced to 200
MW.
3.6 Distribution Factors
Power flows in inverse proportion to the impedance of the available transmission
paths. In other words, more MW and Mvar flows on the path with the lowest
impedance. Distribution factors are a convenient method of describing how
power flow distributes on the available transmission paths.
3-32
12422963
Active and Reactive Power
The term
For a 100 MW intended or scheduled flow from Bus “A” to Bus “B” path “A-B”
“participation
therefore has a 75% (or .75 per unit) distribution factor and path “A-C-D-B” has factor” is
a 25% (or .25 per unit) distribution factor. Distribution factors are simply the sometimes used
percentage of a given schedule between any two locations that flows on a specific in place of
transmission line. “distribution
factor.
3.6.2 Using Distribution Factors
If the distribution factors are known for a given scheduled power flow, the impact
of that schedule on existing transmission line flows can be estimated. System
operators in all of the major Interconnections of North America use databases of
distribution factors to guide their actions to both relieve existing overloaded
transmission lines and to foresee and prevent future transmission system
overloads.
3-33
12422963
Active and Reactive Power
3-34
12422963
Active and Reactive Power
Î The critical part in the above equation is the portion in parenthesis or (VS
– VR). This tells us that Mvar will normally flow from the higher voltage
to the lower voltage.
Î Mvar flows from sources to loads in the same manner as MW. However,
reactive sources are not just limited to generators. Shunt capacitors,
synchronous condensers, and transmission lines are all possible reactive
power sources. Reactive loads include not only the customer load but
also shunt reactors and the transmission system.
Î Reactive power is closely related to system voltage levels. When voltage
levels need to be increased the solution is often to increase the reactive
supply. When voltage levels need to be reduced the solution is often to
reduce the reactive supply.
Î While active power is strongly impacted by changing power angles,
reactive power is typically weakly impacted.
3-35
12422963
Active and Reactive Power
3-36
12422963
Active and Reactive Power
3-37
12422963
Active and Reactive Power
A. True
B. False
3. At what line power angle does the MW transfer across a transmission path
equal ½ of the path’s PMAX?
A. 15 degrees
B. 20 degrees
C. 30 degrees
D. 45 degrees
A. Yes
B. No
C. Impossible to determine
D. The line has no load
5. The TTC limit has been determine to be 1000 MW from east to west for a
particular transmission path. The transmission path operator sells 500
MW of this TTC. What is the path’s ATC?
A. 1000 MW
B. 1500 MW
C. 0 MW
D. 500 MW
A. True
B. False
3-38
12422963
Active and Reactive Power
A. 0 degrees
B. 45 degrees
C. 90 degrees
D. 180 degrees
A. 0 degrees
B. 45 degrees
C. 90 degrees
D. 180 degrees
10. 200 MW is scheduled to flow from Bus “X” to Bus “Y”. Transmission
line “A-B” has a 10% distribution factor for this schedule. How much of
the 200 MW schedule will flow on transmission line “A-B”?
A. 20 MW
B. 40 MW
C. 180 MW
D. 200 MW
3-39
12422963
Active and Reactive Power
3-40
12422963
4
FREQUENCY CONTROL
12422963
12422963
Frequency Control
FREQUENCY CONTROL
SECTION OVERVIEWS
4.1 Introduction to Frequency Control
The load/frequency effect and system inertia help control frequency deviations
caused by a generation-to-load mismatch.
4.2 Governor System Components and Operation
Generating unit governors adjust the MW output of units in the power system in
response to frequency deviations.
4.3 Automatic Generation Control (AGC)
AGC calculates an area control error (ACE) signal which is used to adjust the
output of regulating units and restore frequency to 60 HZ.
4.4 Operating Reserve Requirements
Operating reserve requirements ensure sufficient MW capability to control normal
frequency deviations and respond to large generation contingencies.
4.5 Time Error Control
Accumulated time error is corrected by mutually agreed changes to the scheduled
frequency.
4.6 NERC Control Performance Standards
NERC has developed performance standards that apply during normal and
disturbance conditions.
4.7 Impact of Frequency Deviations
Substantial frequency deviations for prolonged periods can be damaging to power
system equipment and performance.
4.8 Underfrequency Protection
Underfrequency protection includes underfrequency load shedding and
underfrequency generator tripping.
4.9 Nature of a Frequency Deviation
A frequency deviation includes the undershoot, which varies according to
location, and a stabilization point, which is the same throughout the
Interconnection.
SO-1
12422963
Frequency Control
SO-2
12422963
Frequency Control
TABLE OF CONTENTS
TOC-1
12422963
Frequency Control
TOC-2
12422963
Frequency Control
TOC-3
12422963
Frequency Control
TOC-4
12422963
Frequency Control
LIST OF FIGURES
LOF-1
12422963
Frequency Control
LOF-2
12422963
Frequency Control
4-1
12422963
Frequency Control
4-2
12422963
Frequency Control
When generation
and imports exceed
load, the frequency
rises. When load,
losses and exports
exceed resources,
the frequency falls.
Time Error
A natural consequence of over and under generation is time error. Electric clocks
(those driven by motors connected to the power system) keep accurate time by
counting the cycles of the power system frequency. If the frequency varies from
60 HZ, the time kept by electric clocks also varies. Over a period of days the
clocks may develop errors, typically of a few seconds.
For example, if frequency decreases to 59.98 HZ and holds that value for two
hours, electric clocks run slower, losing 2.4 seconds in the two-hour period. Section 4.5 will
describe time error
Figure 4-4 illustrates how sustained frequency deviations lead to time error. control in greater
Utilities have developed methods to correct these time errors that are the direct detail.
result of over or under generation. The basic concept of time error correction
involves targeting or scheduling the system frequency at either a low value (59.98
Hz) or a high value (60.02 Hz) to eliminate past time error accumulations.
4-3
12422963
Frequency Control
If frequency holds at
60 HZ, no time
error accumulates.
If frequency holds at
less than 60 HZ,
clocks run slower
and negative time
error accumulates.
If frequency holds at
greater than 60 HZ,
clocks run faster
and positive time
error accumulates.
4-4
12422963
Frequency Control
These frequency
deviations would be
typical for a large
Interconnection
such as the Eastern
Interconnection. A
smaller
Interconnection
would routinely
experience larger
frequency
deviations than
these.
4-5
12422963
Frequency Control
This magnitude of
frequency deviation
is called abnormal
in this text. This
does not imply that
this size of deviation
is rarely seen. In
fact, depending on
the Interconnection,
frequency
deviations of this
magnitude may be
quite common,
occurring several
times a month.
4-6
12422963
Frequency Control
Non-Motor Load
Resistive load is
Non-motor loads, such as heaters, light bulbs, and electronic equipment, varies in sensitive to the
magnitude (MW) depending on the voltage and frequency of the power system to voltage squared.
If voltage drops
which it is connected. Non-motor load magnitude is more dependent on voltage by 10% to 90% of
than on frequency. It is a reasonably accurate statement to say that non-motor nominal, resistive
load magnitude does not vary as frequency is varied. In contrast, non-motor load load will drop to
is very dependent on the voltage of the system. For example, if the voltage of the 81% (0.9 X 0.9) of
power system drops 10% (to 90% of normal) the MW drawn by resistive electric nominal.
heater loads falls by approximately 19% (to 81% of nominal).
Motor Load
Motor load makes up a large portion of a utility’s total load (typically 40 to 60%).
The more populated the service territory, the more common are motor loads.
Most motor load is formed of induction motors. Typical uses for induction
motors are as air-conditioner compressor motors, vacuum cleaner motors, etc.
Large portions of commercial and industrial load are induction motor loads.
Motor load is also dependent on the voltage and frequency of the power system to
which it is attached. If the voltage or frequency declines, the connected motor If the voltage
load magnitude also declines. The frequency has a greater impact on motor load level falls
magnitude than the voltage. To simplify the description of the impact of voltage enough, motors
and frequency on motor load magnitude ignore the smaller effects of voltage and may stall. Motor
stalling is
concentrate on the larger effects of frequency. A rule of thumb is that the addressed in
connected motor load MW decreases by 3% if the frequency decreases by 1%. Chapter 6,
4-7
12422963
Frequency Control
4-8
12422963
Frequency Control
When a large
generator
turbine/rotor is
spinning at 3600
rpm, it has a large
amount of
rotational or
inertial energy that
resists changes to
the speed of
rotation.
4-9
12422963
Frequency Control
Small variations in the system load normally cause little change in frequency.
This is because the inertial forces of a typical power system are so large that when
compared to the load variation, the generators and motors in the system keep
rotating at almost the same speed. When large loads are added to the power
system, the utility may see a change in a generator’s speed of rotation. For
example, if a utility were to suddenly add a 1000 MW load in the vicinity of a
generating station, the generator’s frequency (speed) monitors would detect a
reduction in rotational speed. Note that this reduction in speed should be
temporary, as this generator and other system generating units have control
systems to eventually return the speed to normal.
Section 4.10
describes the role of Consider another example. Assume that a utility suddenly loses a large generator.
inertia following a This lost energy causes an under-generation condition and must be made up by
generation loss in other generating resources. Other system generating units each supply a share of
greater detail. the lost energy by converting a portion of their rotational energy to electric energy
to help supply the generation shortage.
These generating units are using their inertial energy to replace the power
shortage caused by the loss of the unit. As a consequence of sacrificing some of
their inertial energy, the units experience a decline in rotational speed.
4.2 Governor System Components and Operation
4-10
12422963
Frequency Control
We say "hopefully"
increase the shaft
speed since it
depends on how
much rotational
energy was drained
from the generator
shaft as to how
much more new
input energy is
required before
shaft speed starts to
increase.
The further opening of the throttle valve increases the steam input to the generator
turbine and adds rotational energy to the shaft “hopefully” increasing the shaft
speed. If the shaft speed is still less than the desired value, the governor further
opens the throttle valve. The process continues over several seconds until the
desired shaft speed is attained.
All types of utility generators use governor control systems:
Î Hydro turbine/generators use governors to control the water flow to the
hydro turbine. The valve for controlling water input to the turbine is
either a wicket gate or a nozzle.
Î Steam turbine/generators use governors to control the steam flow to the
turbine blades. The valves for controlling the steam flow are called
throttle valves in this text.
Î Combustion turbines use governors to control the amount of fuel input to
the combustion chamber.
4-11
12422963
Frequency Control
As shown this
governor controls
shaft speed to a
scheduled value.
For example, to the
equivalent of 60 HZ.
Governors on units
in the
interconnected
power systems use
what is called a
droop
characteristic. This
simple governor
model is expanded
later to include the
droop
characteristic.
When the flyweights pivot in or out, the speeder rod moves up or down which in
turn repositions a control valve. The control valve position determines whether
oil will be allowed in or out of the oil reservoir. The oil level in the oil reservoir
controls the fuel rod piston. If the fuel rod piston moves down, the throttle valve,
which controls the input (steam, water, etc.) to the turbine, is moved towards the
closed position. If the fuel rod piston moves up, the throttle valve is further
opened.
The speed of the generator is directly tied to the throttle valve position. If the
generator governor detects the generator speed is rising, it closes the throttle valve
further and arrests the speed increase. If the governor detects that shaft speed is
falling, it opens the throttle valve further and arrests the speed increase.
Ballhead governors can be used to control steam inlet valves to a steam turbine,
wicket gates or nozzle openings in a hydro turbine, or fuel pumps in a combustion
turbine. All systems use hydraulics to amplify the small flyweight forces to make
the force large enough to drive the appropriate control valves.
4-12
12422963
Frequency Control
4-13
12422963
Frequency Control
Also illustrated in Figure 4-12 are two inputs; “AGC Signal” and “Manual
Control Access”. The Manual Control input is an access point for a plant operator
to assume control of the governor system. The AGC Signal is a control signal
sent by a utility’s system operations center to adjust governor settings. This AGC
signal is described in great detail in Section 4.3.
Depending on the age of the electronic governor it may be composed of analog or
digital electronic components. Latest generation electronic governors use digital
components. These governors are provided with data about the generator (speed,
target MW, etc.) and use digital components to perform the governor function.
Access to the performance characteristics (settings) of a digital governor are often
via software. For example, the plant operator may be able to adjust governor
characteristics by making adjustments in a software program.
4-14
12422963
Frequency Control
4-15
12422963
Frequency Control
Islanded power A generator’s governor could use the isochronous control mode illustrated in
systems are power Figure 4-13 if it were the only generator on isochronous governor control in the
systems that as a
result of a system
power system. This generator then provides the majority of the governor control
disturbance are no response. An islanded power system may use isochronous control. During the
longer connected restoration of the system following a blackout, a utility may have guidelines for
via AC lines to any operating islanded sections of the power system with selected generators on
other power system. isochronous control.
Chapter 11
examines the use of The units chosen to operate on isochronous control must carry sufficient spare
isochronous capacity to control or regulate the frequency. Assume the frequency drops and
governors in
islanded power
the governor exhausts the unit capacity in an attempt to return frequency to 60
systems. HZ. The system frequency could then continue to fall unless additional MW can
be found.
4-16
12422963
Frequency Control
generators are rarely operated under load outside of a 59.5 to 60.5 frequency
range.
This characteristic
curve droops from
left to right. The
governor moves the
generator along the
droop curve to
arrest frequency
changes.
3 HZ
300 MW
This ratio states the frequency change needed for a 300 MW output change.
What if the frequency only dropped by 1.5 HZ?
Using our ratio above for this 5% droop 300 MW unit we calculate:
3 HZ 1.5 HZ
≈
300 MW ? MW
Using either cross-multiplication or observation the MW response to a 1.5 HZ
frequency drop can be calculated as 150 MW.
4-17
12422963
Frequency Control
4-18
12422963
Frequency Control
4-19
12422963
Frequency Control
1) The load
reference set-point
has been adjusted
from 150 MW to
140 MW to restore
the frequency to 60
HZ. The movement
of the set-point is
done slowly so as
not to shock the
unit.
2) The load
reference set-point
adjustment is made
either manually via
the power plant
controls or
automatically via
the AGC system.
AGC is described in
Section 4.3.
4-20
12422963
Frequency Control
4-21
12422963
Frequency Control
In response to a
declining frequency,
the governor moves
the generator down
its droop curve. MW
output is increased
and the frequency
decline is arrested
at 59.9 HZ.
In an isolated power Figure 4-18. 300 MW Unit with 5% Droop – Frequency Drop
system, plant
operators are often The governor has done its job by arresting the system frequency decline at 59.9
responsible for HZ. The eventual goal is to return the frequency to 60 HZ but the governor does
frequency control. not recover frequency on its own. The governor will not return the frequency to
The plant operator 60 HZ unless its set-point is adjusted. For this isolated generator, assume the
may allow the plant operator adjusts the governor set-point.
governor to control
frequency Figure 4-19 illustrates the movement of the governor set-point from 150 MW @
automatically 60 HZ to 160 MW @ 60 HZ. Notice that as the set-point is moved, the frequency
(isochronous
control) or the plant of the isolated power system recovers from 59.9 HZ to 60 HZ.
operator may The set-point adjustment returns lost rotational energy to the system and allow
manually adjust the
governor set-point system frequency to recover. The movement of governor set-points may be done
to control by a plant operator as illustrated above, but in practice an additional control
frequency. system (AGC) is used to adjust set-points. AGC is described in Section 4.3.
4-22
12422963
Frequency Control
The governor
completed its
mission by
arresting the
frequency drop
at 59.9 HZ. To
recover the
frequency to 60
HZ, the plant
operator
adjusted the
governor set-
point.
4-23
12422963
Frequency Control
Compare Figures 4-19 and 4-20. Note that the frequency does not drop as much
in Figure 4-20 as it does in 4-19. This is due to the load/frequency relationship.
As the frequency drops, the load magnitude also drops. In Figure 4-20 if the
load/frequency effect was not accounted for frequency would drop down to point
n. Counting the load-frequency effect means frequency only drops to point o.
Section 4.2.7 When the governor set-point is adjusted to recover the frequency, both frequency
illustrates the and generator MW output increase. The generator output increases because as the
differences frequency is recovered to 60 HZ, the load magnitude also rises to a higher value.
between
governors The load/frequency relationship is very important in the operation of an
arresting a interconnected power system. In a large power system, the load/frequency
frequency
deviation and
relationship is often all that is needed to arrest frequency deviations. A governor
the load/ system response is required in a large Interconnection only when the mismatch
frequency between generation and load is large. For most mismatches, the change in load
relationship magnitude that accompanies a frequency deviation is sufficient to arrest the
arresting a frequency deviation.
frequency
deviation.
4-24
12422963
Frequency Control
4-25
12422963
Frequency Control
4-26
12422963
Frequency Control
4-27
12422963
Frequency Control
Section 4.2.9 The frequency trace on the right is for a smaller frequency deviation. Note there
examines is no pronounced tail to this frequency trace. The absence of a tail indicates that
frequency plots
in greater
the load/frequency relationship was enough to arrest the frequency deviation. The
detail. load/frequency effect does not recover frequency, it simply stops the decline.
Governor response will show a recovery to frequency, which is why the tail exists
when widespread governor response occurs.
4-28
12422963
Frequency Control
4-29
12422963
Frequency Control
Figure 4-25 illustrates that if the same 200 MW of load is added to the system
resulting in frequency declining to 59.7 HZ, Unit “A” assumes 133 MW of the
new MW load while Unit “B” assumes the remaining 67 MW. Unit “A” has ½
the droop setting of generator “B” so it picks up twice as much of the new load.
4-30
12422963
Frequency Control
Now assume that instead of a 100 MW load increase, a 200 MW load increase
occurs. Which unit will pick up this load change? Since Unit “B” is on
isochronous control it tries to maintain frequency and pick up the entire 200 MW
load change. However, Unit “B” only has 150 MW of spare capacity available.
Once Unit “B” reaches its capacity limit, the frequency starts to fall. When the
frequency starts to fall, Unit “A” starts to pick up load. Figure 4-26 illustrates the
split of the additional load. Notice that the system frequency falls to 59.8 HZ.
4-31
12422963
Frequency Control
4-32
12422963
Frequency Control
4-33
12422963
Frequency Control
4-34
12422963
Frequency Control
The ERCOT
Interconnection is a
relatively small
Interconnection. That
is why a 700 MW loss
causes such a large
frequency deviation. If
700 MW were lost in
the ERCOT
Interconnection,
frequency would likely
stabilize at
approximately 59.9 HZ
following governor
response.
Frequency Bias
The FRC for a Balancing Authority (a Balancing Authority is a physical division
of a power system) is an important measure of that areas response to a
disturbance. An estimate of the FRC (the symbol for the FRC is the Greek letter
β) for a Balancing Authority is an important setting for the automatic generation
control (AGC) system of the Balancing Authority. The term frequency bias or
symbol “B” is used when referring to a Balancing Authority’s estimate of their
FRC. The correct use and importance of the frequency bias term is described in
greater detail in Section 4.3.
4-35
12422963
Frequency Control
respond with a large output change. If a large unit in North Dakota were suddenly
lost, that same unit in Florida would also respond with an increase in MW output.
However, the initial response would typically not be as large as the electrical
distance is much greater and the Florida unit would not initially see as large of a
frequency decline.
The rock in the
pond analogy is One way to visualize frequency disturbances in the interconnected power system
also similar to a is to think of an interconnected power system as a smooth pond. When a
power system frequency disturbance occurs it is equivalent to tossing a rock into the pond. The
frequency
disturbance in that larger the waves in the pond, the greater the frequency disturbance. As you move
it takes time for the further away from the point where the rock initially struck the pond, the waves
waves to propagate slowly melt away.
throughout the
pond. In the same Frequency disturbances spread out from their original impact point in the same
manner, when a manner. The farther away from the disturbance location, the smaller the initial
generator is lost in frequency change. Eventually, after all the interconnected units in the power
the power system it system have responded, the system resumes operating at a common frequency.
takes several
seconds for all the This may take 10 to 20 seconds.
utilities in a large
Interconnection to 4.2.11 Limitations to Governor Response
see their maximum
frequency Governors are not designed nor is it intended that they perform perfect frequency
disturbance. control. Limitations to governor control, both intentional and unintentional,
include:
Î Spinning Reserve
Î Mismatch Size
Î Governor Deadband
Î Type of Generating Unit
Î Boiler Control Modes
Î Blocked Governors
Spinning Reserve
If a governor is to move a unit down along its droop curve in response to a
frequency drop, it can only do so if the generator has unused MW capability.
This unused MW capability is generally referred to as spinning reserve capability.
Spinning reserve is the difference between the current output level of the
synchronized generator and the maximum sustainable output level of the unit. A
generator can have a perfectly tuned governor, but if the unit is not carrying any
spinning reserve it will not respond when frequency drops.
Section 4.4 A generator may be carrying a large amount of spinning reserve and still not
describes the types adequately respond to governor commands. Not all spinning reserve is
of reserves in necessarily responsive to governor commands. That portion of the spinning
greater detail. reserve that is responsive to governor commands is called the unit’s responsive
spinning reserve. In general, the responsive spinning reserve attributable to a
4-36
12422963
Frequency Control
4-37
12422963
Frequency Control
The smaller the Interconnection, the more likely available governor response is
inadequate and other, more drastic actions taken. The Eastern Interconnection is
so large that it is highly unlikely a single contingency loss of generation could
lead to an unrecoverable frequency depression. The Alaskan Interconnection, on
the other hand, is so small that underfrequency load shedding is routinely used to
respond to first contingency generation losses.
Governor Deadband
A control system (such as a governor) maintains a designated variable close to a
target value based on a series of measured inputs. There is a certain “dead” area
around the target value within which the control system does not function. So
instead of a target value, a control system actually maintains a target range. For
example, if the controlled variable is frequency, instead of maintaining exactly 60
HZ, a governor control system may maintain frequency within a band of 60.03
HZ to 59.97 HZ. The inactive range around the target value is called the
deadband. In our example of a governor holding frequency within a range of
59.97 HZ to 60.03 HZ, the target value is 60.00 HZ and the deadband is ±0.03
HZ.
In older mechanical governor systems, deadband was impossible to eliminate.
Interaction between the moving parts resulted in deadband whether it was desired
or not. In newer mechanical and electronic governor systems, deadband can be
largely eliminated if so desired. However, in practice some deadband is desired.
The governor’s role is to arrest frequency deviations, not to control frequency
within a narrow range of 60 HZ. Other control systems are available to keep
frequency within a narrow band of 60 HZ. If governor deadband were eliminated,
the governor would constantly direct the generator to chase minor frequency
deviations. Generator components would suffer excess wear for no good reason.
Power oscillations could develop as the governor sends the generator conflicting
signals in a bid to correct minor frequency oscillations. Power oscillations could
also develop between neighboring generators as both try to keep their own,
unequal, versions of 60 HZ.
The IEEE (an industry standards organization) recommends a deadband of 0.036
HZ for governor control systems. By looking closely at plots of frequency
disturbances in the interconnected systems, one would note that the “tail” to the
frequency trace is normally not visible until the frequency deviation is larger than
approximately .03 HZ. This is evidence of an industry practice to set effective
governor deadbands in the neighborhood of 0.03 to 0.04 HZ.
Type of Unit
The type of unit (hydro, steam, combustion turbine) has a direct bearing on
governor response. While the governor control systems used on different units
may be identical, what is more important is the MW response from the unit. If the
4-38
12422963
Frequency Control
unit cannot deliver what the governor asks of it, the unit is of less value to the
system for frequency control.
Hydro
Hydro units are, in general very responsive to governor commands as they may The penstock
store a great deal of energy in their water storage reservoirs. Depending on the delivers the
size and type of hydro unit, response rates of 100’s of MW can be achieved in a water to the
few seconds. Not all hydro units respond well. Those with long penstocks may hydro turbine.
respond poorly to large frequency deviations due to turbulence in the incoming
water.
Combustion Turbine
Depending on the design of the combustion turbine, the unit may or may not be
responsive to governor commands. On those systems dependent on combustion
turbines for a large part of their generation, difficulties have been encountered
with respect to the combustion turbine maintaining their initial governor response.
These difficulties center on the reduced compressor output during low frequency
conditions.
Steam
Steam units make up the majority of system generators. The governor response of
steam units varies from very poor to very good depending on the type of steam
unit. The initial governor response from a steam unit is from stored steam. This
initial response may be quite fast. The difficulty may be in sustaining this initial
response.
Approximately 30% of a generators output power is developed in the high-
pressure turbine of a typical steam unit. The remaining 70% is developed in the
lower pressure stages. The high-pressure turbine is very responsive to governor
commands as the governor typically directly controls the high-pressure turbine
control valve. Lower pressure stages are indirectly controlled by the governor.
The lower pressure stages are fed steam via a reheat cycle of the boiler. The
reheat cycle adds several seconds of time delay from an initial call for MW from a
governor until the generator can actually deliver the majority of its MW response.
4-39
12422963
Frequency Control
Blocked Governors
All governor response can be prevented. By adjusting the generator’s controls, a
generator operator can intentionally prevent the unit from responding to a
frequency disturbance. This is called blocking a governor. For example, nuclear
units are often operated at their maximum licensed output. The nuclear operating
company may choose to prevent steam valves from opening further in response to
a frequency decline. In effect, the nuclear plant operator has blocked the
governor’s response to a frequency drop.
4.3 Automatic Generation Control (AGC)
Governor control does not provide adequate frequency regulation for several
reasons including:
Î Governors do not return frequency to the scheduled value (normally 60
HZ) due to the required % droop characteristic of interconnected system
generator governors.
Î Governor control does not adequately consider the cost of power
production so control with governors alone is usually not the most
economical alternative.
Î Governor control is intended as a primary means of frequency control.
As such governor control is course and not suited to fine adjustment of
the interconnected system frequency
4-40
12422963
Frequency Control
Therefore, another form of control system is required to balance generation The first AGC
to load and maintain a constant system frequency. This other control system system was
implemented by an
is the automatic generation control (AGC). While governors control individual east coast utility in
generators, AGC systems simultaneously control many governors to balance 1927.
generation to load.
An AGC system operates at a much higher level of control than a governor.
Where a governor control system monitors and controls only one generator, an
AGC system monitors a section of the power system, known as a Balancing
Authority area, and controls multiple generators. Governor control is often
referred to as primary frequency control while AGC is referred to as secondary
frequency control. Power plant
operators can also
Recall from Section 4.2 how a governor arrests changes in generator adjust governor set-
frequency, and how the governor is not typically used to restore frequency points. The
to 60 HZ. Remember how frequency is restored by adjusting the load reference mechanism for
set-point of the governors. AGC is the control system that normally makes adjusting set-points
these important set-point adjustments. With control over the load reference set- is commonly called
a "speed changer".
points of the generators, AGC matches its Balancing Authority’s generation to
load and maintains frequency.
4-41
12422963
Frequency Control
Each Balancing Authority operates an AGC system to balance its total generation
resources (including energy purchases) to its total load (including energy sales
and system losses). The AGC system monitors power system conditions within
the Balancing Authority including generation supply, load demand, losses, sales,
purchases, and system frequency. The AGC system analyzes all this data and
computes a control error.
The control error is called the ACE (area control error) signal. ACE represents
the discrepancy between the generation supply and total MW obligations of the
Balancing Authority. Dependent on the ACE signal, the AGC system send
signals or pulses to selected generating units within its Balancing Authority to tell
the generators what generation levels to hold (adjust the generator set-points).
This figure
illustrates five
Balancing
Authorities. The
Balancing Authority
in the middle is
shown in detail
while the other four
are just labeled.
Each Balancing
Authority monitors
frequency and their
tie-line flows to
other Balancing
Authorities. Note
the meters on the
tie-lines. The meters
are necessary to
monitor actual tie-
line MW flows.
4-42
12422963
Frequency Control
4-43
12422963
Frequency Control
4-44
12422963
Frequency Control
The MW
flows shown
are actual
interchange
flows.
4-45
12422963
Frequency Control
Actual net interchange is seldom exactly equal to scheduled net interchange. For
example, if generation exceeds demand, the Balancing Authority over-generates
and excess MW flows out of the area. Actual net interchange is then greater than
scheduled. Similarly, if the Balancing Authority under-generates, MW flows into
the area and actual net interchange is less than scheduled.
This inadvertent
flow is created
because Balancing
Authority "A" is
under-generating by
100 MW and
Balancing Authority
"B" is over-
generating by 100
MW.
4-46
12422963
Frequency Control
produced when over-generating should then cancel the negative net inadvertent
produced while under-generating. This match between positive and negative net
inadvertent does not always occur but in general Balancing Authorities do a good
job of minimizing their net inadvertent flows.
Inadvertent flow is an indication of an imbalance between generation and load in
a Balancing Authority. If the net inadvertent is positive, the Balancing Authority
has been over-generating. If the net inadvertent is negative, the Balancing The size of a
Authority has been under-generating. When a Balancing Authority has a net Balancing
inadvertent flow on its tie-lines it may be a signal that there is a difference Authorities
accumulated
between power supplied and used. The Balancing Authority’s AGC system may
inadvertent account
respond by changing the set-points of the generators on AGC control. is not a good judge
of the performance
The AGC system and the system operator work to minimize inadvertent
of the Balancing
interchange. However, even with the AGC system functioning as expected and Authority.
the system operator doing their best, inadvertent power flows does occur. Over a Accumulated
period of time, a Balancing Authority may accumulate a considerable amount of inadvertent
net inadvertent, either positive or negative. As net inadvertent represents a accounts can grow
large from
mismatch in the interchange of power between Balancing Authorities,
responding to other
Balancing Authorities may make special arrangements with each other to Balancing
reduce their accumulated inadvertent. Authority’s poor
operations.
When disturbances occur on an interconnected power system, inadvertent
interchanges occur. Power automatically flows between Balancing Authorities to
supply deficiencies. For example, if in Figure 4-32 Balancing Authority “B”
loses a generator, the generating units in Balancing Authority “A” would rapidly
increase their output and increase actual power flow from Balancing Authority
“A” to Balancing Authority “B” on the tie-line. This would change the
inadvertent flow on the tie-line between the two Balancing Authorities.
A Balancing Authority’s accumulated inadvertent can be viewed as composed of
two components; primary or unintentional inadvertent and secondary or
intentional inadvertent. Secondary / intentional inadvertent results from a
Balancing Authorities MW response to external generation/load mismatches. The
largest component of intentional inadvertent is due to governor response. Primary
/unintentional inadvertent results from internal scheduling errors, metering errors,
or failures to keep up with load changes.
In terms of frequency deviations, the Balancing Authority who causes a frequency
deviation incurs primary / unintentional inadvertent. The Balancing Authority
who responds to a frequency deviation some other Balancing Authority caused,
incurs secondary / intentional inadvertent. Figure 4-33 illustrates the concept of
primary / unintentional and secondary / intentional inadvertent.
In Figure 4-33a, Balancing Authority “A” loses a generator. Note the frequency
drops from 60 to 59.95 Hz. Balancing Authority “A” then absorbs primary
inadvertent from the other three Balancing Authorities who are responding to the
low frequency. The other three Balancing Authorities did not cause the low
frequency condition so their inadvertent is classified as secondary.
4-47
12422963
Frequency Control
In Figure 4-33b, Balancing Authority “C” loses a load. Note the frequency rises
from 60 to 60.05. Balancing Authority “C” then provides primary inadvertent to
the other three Balancing Authorities who are responding to the high frequency.
The other three Balancing Authorities did not cause the high frequency condition
so their inadvertent is classified as secondary.
4-48
12422963
Frequency Control
Any difference between generation and load would cause the AGC system to
calculate and send control signals to selected generators to adjust their MW
output. These control signals are used to adjust the load reference set-points of
the generators. If generation in the isolated system were greater than load, the
AGC system would call for a decrease in generation. If generation were less than
load, the AGC system would call for an increase in generation.
Actual power systems, however, are normally not isolated. They are
interconnected with many other systems. The tie-lines between the different
Balancing Authorities allow power to flow between each and enable the system
participants to buy and sell energy between one another. In an interconnected
power system with multiple Balancing Authorities, the AGC systems must do
more than just match internal generating resources to internal load and losses.
AGC must also take into account the power flows that occur back and forth
between Balancing Authorities over the interconnecting tie-lines. An AGC
system in a Balancing Authority must therefore maintain a 60 HZ balance of the
following equation:
The new term in the above equation, net scheduled interchange, is the sum of the
scheduled or intended MW flow on all the tie-lines between the Balancing
Authority in which this AGC system is located and all adjacent Balancing
Authorities. The addition of the net scheduled interchange term greatly affects
the operation and complexity of an AGC system.
Since power systems are interconnected, it might appear that one AGC system
could be used to control the frequency of the entire Interconnection to the desired
60 HZ value, without the need to measure and control power flows between
Balancing Authorities. This is not always feasible, however, due to the sheer size
of some interconnected power systems and the fact that utilities often desire
4-49
12422963
Frequency Control
control over the operation of their own generating units and transmission system.
Instead, the larger interconnected power systems are broken down into smaller
sections (Balancing Authorities) in which individual AGC systems can function.
The standard
time input is a
feature of time
error control.
Time error
control is
described in
Section 4.5.
4-50
12422963
Frequency Control
Î The system operators enter scheduled net interchange (NIS) data into the
data monitoring computer. Actual interchange data (NIA) is gathered
from all the Balancing Authority tie-line meters. Telemetry channels are
used to gather the interchange data from remote locations in the
transmission system. The actual interchange is compared to the
scheduled interchange and a net interchange error (NIA-NIS) value is
calculated in the data monitoring computer.
Î The data monitoring computer uses the frequency error and the net
interchange error to compute an ACE value.
Î The AGC control computer distributes the ACE signal to the controlled
generators. This can be a complicated process. Not only must the ACE
signal be distributed to the proper generators but also the results of past
ACE signal distributions must be checked to be sure the generators are
moving in the direction AGC has sent them.
The process illustrated in Figure 4-34 is continuous. A new ACE signal may be
calculated and new set-points distributed to controlled generators every few (2-6)
seconds.
4-51
12422963
Frequency Control
4-52
12422963
Frequency Control
The ACE Equation for Tie-Line Bias Control If the ACE quantity
In tie-line bias control, an area control error (ACE) signal is calculated is negative, the
Balancing Authority
based on the differences between scheduled and actual frequency and is deficient in
between scheduled and actual tie-line flows. ACE for tie-line bias control is generation. If the
defined as: ACE quantity is
positive, the
Balancing Authority
has an oversupply
of generation.
4-53
12422963
Frequency Control
( )(
− ⎡⎣ 10 × B × Actual Frequency−Scheduled Frequency ⎤⎦ )
or
( ) ( )
ACE = ⎡⎣ NI A − NIS ⎤⎦ − ⎡⎣ 10 × B × FA − FS ⎤⎦
The first part of the equation, [actual net interchange - scheduled net interchange],
is the ACE equation for constant net interchange control. A portion of the second
part of the equation, (actual frequency – scheduled frequency), is the ACE
equation for constant frequency control. The whole equation is the ACE equation
for tie-line bias control.
4-54
12422963
Frequency Control
Some Balancing Authorities put a great deal of effort into calculating their bias Frequency bias
value. Equations may be used that adjust bias based on the time of day, the size values are
of the load, the size of the disturbance, or other factors. Within the NERC reported yearly to
Interconnections several Balancing Authorities have implemented a form of real NERC. The
time bias calculation. The frequency bias value is continually updated based on minimum value
that can be
what generating units are on-line. This is an accurate way of computing reported is 1% of
bias as most of the bias is due to the governor response of on-line generators. the Balancing
The importance of the “B” term becomes apparent as the use of the tie-line bias Authority's past
control method of AGC is examined. year's peak load or
peak generation.
Figure 4-36 is a graphical summary of the calculation of the ACE value using tie-
line bias AGC control. Diagrams similar to Figure 4-36 are used in this text to
illustrate the operation of a Balancing Authority’s use of tie-line bias control. The top portion of
the figure is for
determining the
frequency error.
The bottom portion
determines the net
interchange error.
The frequency error
is multiplied by the
bias (B) value. The
resultant MW
number is
compared to the net
interchange error
to determine an
ACE value. The
ACE value is used
to adjust
generation.
4-55
12422963
Frequency Control
When the
disturbance is
external and AGC
works as intended
no ACE value is
developed.
The bottom portion of the figure illustrates how AGC calculates the actual
response of this Balancing Authority. Since any MW response to the disturbance
must flow out over the tie-lines, the actual response is simply the difference
between scheduled and actual tie-line flows. In Figure 4-37 the actual response
is found by subtracting the scheduled interchange of 1000 MW from the actual
interchange of 1200 MW. The actual is greater than scheduled by 200 MW
so the actual response is +200 MW.
4-56
12422963
Frequency Control
The AGC system now compares the expected response to the actual response. When ACE is zero
The actual response is +200 MW and the expected +200 MW. Since actual is the Balancing
equal to expected, the error or ACE is equal to zero MW. When ACE is equal to Authority is
zero it means that the response of the Balancing Authority is exactly as intended. responding exactly
No adjustment to Balancing Authority generation is required. as expected. No
generator set-point
adjustments are
Internal Generation Loss needed.
Figure 4-38 also illustrates the operation of tie-line bias AGC within a Balancing
Authority. This example assumes the same size generator is lost but now it is one
of the illustrated Balancing Authority’s generators. This generation loss is
internal to the Balancing Authority. Every Balancing Authority again detects a
frequency depression to 59.9 HZ.
4-57
12422963
Frequency Control
The AGC system now compares the expected response to the actual response.
The actual response is -500 MW and the expected +200 MW. The actual
response is less than the expected response by 700 MW. The ACE is therefore
equal to -700 MW. An ACE of -700 MW indicates that this Balancing Authority
is under generating by 700 MW. To reduce this ACE the generators in the
Balancing Authority under AGC control must have their set-points adjusted to
increase MW output. As the generator outputs increase the ACE value reduces
towards zero.
Smoothing filters
eliminate short term
bumps in the ACE
value. Probability
filters attempt to
guess future ACE
values.
4-58
12422963
Frequency Control
Economic Dispatch
Our previous description of how the ACE signal is distributed to the units under
AGC control was greatly simplified. The process by which generators are pulsed
is actually complex. ACE signals are continually being sent to controlled
generators. The AGC system must keep track of what signals have been sent and
where the generators are currently operating. Modern AGC systems are often
capable of estimating where the generator will be pulsed in the future.
One important process that has been ignored to this point is the economic dispatch
process. Economic dispatch is a process by which a Balancing Authority attempts
to minimize their overall cost of power production. The economic dispatch
process is an important part of the AGC process for those companies that choose
to implement it. In simple terms, the economic dispatch function is an added
feature to AGC systems. Economic dispatch determines the best economic Power systems
operating points for controlled generators. define reserves in
many different
The best operating points are based on many factors including system security ways. The reserve
and minimizing the cost of power production. Base operating points (MW descriptions used in
values) for generators are determined and signals sent to the generators to move this section are
towards these base operating points. When an ACE signal is developed, the general. Your
signal distribution to the generators is based on which controlled units can particular system
may have different
produce the power required at the least cost and with the least impact on power reserve definitions
system security. and requirements.
4.4 Reserve Policies
Reserves are unused MW capability. The ability of a power system to control
normal frequency deviations and to survive large disturbances is directly related
to their reserve requirements. All power systems have some rules as to what
constitutes reserves and what are sufficient reserve levels. This section reviews
several general classifications of reserves.
4-59
12422963
Frequency Control
Interruptible load Spinning and non-spinning reserves are reserve sources. Regulating reserve and
is customer load contingency reserve are composed of either spinning or non-spinning reserve
available for sources. Figure 4-41 illustrates the concepts of spinning and non-spinning
shedding within a reserves.
set time period. A
contractual
agreement must
exist.
4-60
12422963
Frequency Control
Spinning Reserves
Spinning reserves consist of unloaded generating capacity that is synchronized to
the power system. A governor cannot increase generation in a unit unless that
unit is carrying spinning reserves. An AGC system cannot increase a unit’s MW
output unless that unit is carrying spinning reserves. NERC also includes some
forms of interruptible load in the spinning reserve category. The load must be
automatically controlled and be available within a set time period.
Non-Spinning Reserves
Non-spinning reserve is a reserve MW capability that is not currently connected
to the system but that can be available within a specified time period. The exact
time period varies but a 15 minute window is common. Examples of non-
spinning reserves are combustion turbines while in cold standby. NERC also
allows interruptible load to be counted as non-spinning reserve.
4-61
12422963
Frequency Control
The ERCOT
Interconnection
specifies required
responsive reserve
levels. ERCOT
utilities may use all
four of these
responsive reserve
categories.
4-62
12422963
Frequency Control
4-63
12422963
Frequency Control
4-64
12422963
Frequency Control
Other
Interconnections
such as Hydro
Quebec or Alaska,
may also designate
a time error
monitor.
There are three columns across the top of Figure 4-45. Each column is briefly
explained below:
Î The first column is labeled “Type of Correction”. The two possible types
of time correction are slow and fast. If accumulated time error is slow or
negative the slow row is used. If time error is fast or positive the fast
row is used.
4-65
12422963
Frequency Control
4-66
12422963
Frequency Control
Normal Conditions
During normal system conditions, the goal was to minimize ACE. The question
asked was how much ACE fluctuation was normally admissible? How far above
and below zero can ACE deviate? How can a Balancing Authority ensure that the
ACE deviation nets to zero over a period of time? Remember that if ACE was
high or low for sustained periods, it was an indication that the Balancing
Authority was accumulating inadvertent interchange and not contributing to
frequency regulation.
In 1973, NERC implemented two criteria for control performance during normal
conditions, referred to as “A1 - Zero Crossing” and “A2 - Ld Compliance”.
A1 – Zero Crossing
The A1 criterion specified that a Balancing Authority’s ACE should return to zero
within 10 minutes of previously reaching zero. That is, the time interval between
successive zero values should never exceed 10 minutes. This criterion was
intended to help minimize inadvertent interchange. Periods of over-generation
(positive ACE) should be balanced by periods of under-generation (negative
ACE).
A2 – LD Compliance
The A2 criterion was designed to limit the magnitude of ACE. A2 stated that the
average ACE for each of the six ten-minute periods during the hour should be less
than or equal to a limit value known as Ld. Ld was representative of the largest
hourly load change experienced by the Balancing Authority in the past year. If
the Balancing Authority’s load pick-up were typically steep, Ld would be high.
For Balancing Authorities with a slow, gradual load pick-up, Ld was lower.
Figures 4-46 and 4-47 illustrate the application of NERC’s old A1 and A2
criterion. Figure 4-46 is a Balancing Authority ACE chart that indicates
compliance with both the A1 and A2 criteria. Figure 4-47 illustrates violations of
both the A1 and A2 criteria.
4-67
12422963
Frequency Control
4-68
12422963
Frequency Control
Disturbance Conditions
Normal load
When a frequency disturbance occurred, the normal conditions criteria were variations should
replaced with the disturbance criteria. NERC defined a disturbance as occurring not trigger the use
when ACE reached a magnitude of three times the Balancing Authority’s Ld. of disturbance
NERC defined two criteria that apply during disturbances, the B1 and B2 criteria. criteria.
B1 – System Recovery
The B1 criterion required that ACE return to zero within 10 minutes of the initial
disturbance. If a Balancing Authority lost a generator, their ACE value would not
cross zero again until the Balancing Authority had replaced the lost generation.
The B1 criterion gave Balancing Authorities 10 minutes to recover from
disturbances.
B2 – Recovery Initiation
The B2 criterion required that ACE start to return to zero within one minute of a
disturbance. Once a disturbance occurred, the Balancing Authority was obligated
to begin recovery within one minute.
4-69
12422963
Frequency Control
CPS1
CPS1 is intended to provide a Balancing Authority with a frequency sensitive
evaluation of how well the Balancing Authority is meeting its demand
requirements. CPS1 is a statistical measure of the Balancing Authority’s ACE
variability. CPS1 measures ACE in combination with the Interconnection’s
frequency error.
Each Balancing Authority is obligated to continually gather sufficient data to
determine its “control parameter” for each minute of the day. Every Balancing
Authority, using the following equation, calculates their control parameter:
The control
parameter can be
ACE MINUTE
derived from the Control Parameter = × ΔFMINUTE
ACE equation if you −10B MINUTE
realize that
inadvertent sums to Definitions for the terms used in this equation include:
zero in an
Interconnection. Î ACEMINUTE is the one-minute average of the Balancing Authority’s ACE
value.
Î ΔFMINUTE is the one-minute average of the Interconnection’s frequency
error.
Î -10BMINUTE is the one-minute average of the Balancing Authority’s
frequency bias value.
Balancing Every minute of every day, each Balancing Authority gathers data to calculate
Authorities must their control parameter. The control parameters for each minute are then
continually gather averaged together to determine the control parameters for each hour, day, month,
the required data to year, etc. (The control parameters that are most important to the CPS are the
calculate their
Balancing Authority’s monthly average and their sliding 12-month or yearly
control parameter.
average value.)
The control parameter values are then used to determine the Balancing
Authority’s “compliance factor”. The compliance factor is a ratio of the control
parameter to the Interconnection’s allowable frequency error. In equation form
the compliance factor is:
4-70
12422963
Frequency Control
Control Parameter
Compliance Factor =
(ε )
2
1
The term in the denominator (ε1 or epsilon-one) represents the allowable 1-minute
average frequency error for the particular Interconnection. Epsilon’s magnitude is
determined by NERC. (Think of epsilon as the target bandwidth for the
frequency error.) NERC has monitored each Interconnection’s historic frequency
error to determine an acceptable frequency error. As of the writing of this section,
the ε1 values for the three major Interconnections are: NERC may
change the
Î Eastern Interconnection — 0.018 HZ magnitude of
epsilon as
Î Western Interconnection — 0.0228 HZ operating
experience is
Î ERCOT Interconnection — 0.030 HZ gained with
For the final step in the CPS1 process, the compliance factor is used to determine CPS1.
the Balancing Authority’s CPS1 % conformance. The compliance factor is input
to the following formula:
(
CPS1 = 2 − Compliance Factor × 100% )
This formula was developed to judge a Balancing Authority’s CPS1 conformance
on a percentage scale. The formula can be used to determine a Balancing
Authority’s conformance to CPS1 across any time period. The compliance factor
is first determined for the desired time period. NERC is most concerned with the
value of CPS1 across a sliding one-year period. NERC also pays attention to one-
month averages of the CPS1 to detect problems with a Balancing Authority’s
compliance to CPS1 before any major generation control problems develop.
A CPS1 magnitude of 100% is the minimum acceptable performance. When a
Balancing Authority achieves a CPS1 of 100% it means the Balancing Authority
is adjusting their generation in a manner that just meets their obligation to
maintaining the Interconnection’s frequency. If a Balancing Authority’s CPS1 is
greater than 100%, they are doing more than their share of frequency control. If a
Balancing Authority’s CPS1 is less than 100%, they are doing less than their fair
share of frequency control.
4-71
12422963
Frequency Control
CPS1 encourages all Balancing Authorities to control their generation such that
their MW-HZ numbers are negative. For example, assume the Interconnection’s
frequency error is negative (frequency is lower than scheduled). Further assume
that a Balancing Authority has a positive ACE (over-generating). The Balancing
Authority’s MW-HZ product would then be a negative number, which means the
Balancing Authority is helping reduce the frequency deviation. If the Balancing
Authority’s MW-HZ numbers were positive, that Balancing Authority is
contributing to the frequency deviation.
Figure 4-48 graphically illustrates the concept of MW-HZ. A simple ACE chart
and a frequency chart (in milli hertz or mHz) are shown. If a Balancing Authority
is over-generating when frequency is low, they are helping the Interconnection’s
frequency. If a Balancing Authority is over-generating while frequency is high,
they are hurting the Interconnection’s frequency.
The frequency in
this plot is shown in
milli-hertz. A milli-
hertz is a
thousandth of a
hertz or 1 mHZ =
0.001 HZ.
CPS2
Note the strong The second component of the CPS is CPS2. CPS2 is designed to limit the
similarity magnitude of a Balancing Authority’s ACE. The intent of CPS2 is to limit the
between CPS2 unscheduled power flows across tie-lines that can result from excessive ACE
and the old A2 values.
criterion.
CPS2 states that the average ACE value for each 10-minute period shall not
exceed a constant called “L10”. L10 is calculated for each Balancing Authority
using the following formula:
4-72
12422963
Frequency Control
Pass/Fail CPS
CPS1 and CPS2 are evaluated together to determine if a Balancing Authority has
complied with CPS. To pass the CPS standard, a Balancing Authority must
conform to CPS1 100% of the time and conform to CPS2 90% of the time. A
Balancing Authority fails CPS if they fall below 100% compliance with CPS1 or
fall below 90% compliance with CPS2.
CPS Enforcement
Compliance with the old performance criteria was voluntary. NERC relied on
peer pressure as the driving force to keep Balancing Authorities in compliance.
The new CPS uses more than peer pressure. There are definite penalties for non-
conformance. These penalties typically involve monetary fines for non-
conformance.
4-73
12422963
Frequency Control
4-74
12422963
Frequency Control
4-75
12422963
Frequency Control
Chapter 5 will Î Transformers can be damaged by low frequency operation. The strength
describe the over- of the magnetic field in a transformer’s core is a function of both voltage
excitation of and frequency. If a transformer is exposed to prolonged underfrequency
transformers in operation, the transformer can overexcite. Low frequency operation can
greater detail.
damage a transformer, especially if it is combined with high voltage.
Î Electronic equipment timing circuits may be dependent on a relatively
accurate system frequency. If this frequency is abnormal, the equipment
The period of may operate abnormally.
acceleration is
typically brief (a
few seconds) and 4.7.4 Effects on Active Power Flows
the frequency
In Chapter 2 an equation for MW transfer was developed. The equation is
difference is
typically small repeated below:
(fractions of a V × VR
hertz). PSR = S sin δ SR
X SR
According to this simple formula for MW transfer, the largest factor in
The Florida power determining the level of MW flow is the power angle, δ. The power angle can
system used to be
very susceptible to only change if a condition of relative acceleration existed. If MW transfer is to
island formation. increase between two locations, their must briefly be relative acceleration
At one time between the two locations. Relative acceleration is simply a difference in
Florida was frequency. Frequency differences between two locations in the same
weakly tied to the Interconnection lead to power angle changes. Section 4.9.4 will explore this point
rest of the Eastern
Interconnection. further.
Florida would
often separate and
4.8 Underfrequency Protection
form an island This section describes the use of underfrequency load shedding and
when major
disturbances
underfrequency generator tripping relays. Underfrequency protection schemes
occurred in the are required if the Interconnection frequency falls below acceptable levels. In a
East. The tie-lines large Interconnection (like the Eastern) it is unlikely that large mismatches
between Florida between generation and load will develop unless major disturbances occur. It is
and the rest of the therefore unlikely that underfrequency protection will activate unless a large
Eastern system are
much stronger
Interconnection splits into islands following a major disturbance.
today but the
Florida system is
still very lively!
4-76
12422963
Frequency Control
4-77
12422963
Frequency Control
In general, the larger the Interconnection, the higher the frequency at which UFLS
begins. Smaller Interconnections may not begin UFLS until the frequency falls
below 59 HZ. Smaller Interconnections are susceptible to large frequency swings
4-78
12422963
Frequency Control
even during normal interconnected operations and they do not want false tripping
of UFLS relays.
Figure 4-52 illustrates the operation of three stages of UFLS. The first stage
activates at 59.3 HZ, the second stage at 59 HZ and the final stage at 58.7 HZ.
Note that the rate of frequency decline improves after each stage of UFLS. The
intent of UFLS is not to recover the frequency to 60 Hz but rather to arrest or stop
the frequency decline. Once UFLS has operated, manual intervention by the
system operators is likely required to restore the system frequency to a healthy
state.
All Interconnections require some form of UFLS be implemented by member
systems. Interconnections may coordinate UFLS on an Interconnection basis or
divide the Interconnection into smaller regions in which separate UFLS programs
are administered. Periodically utilities evaluate their UFLS programs to ensure
enough load is being shed and that it is being shed at the proper frequencies.
Interconnections typically provide general requirements for UFLS. Individual
utilities work within these general requirements to match their own system
characteristics.
4-79
12422963
Frequency Control
4-80
12422963
Frequency Control
4-81
12422963
Frequency Control
4-82
12422963
Frequency Control
4-83
12422963
Frequency Control
AGC Response
Once the governor response has stabilized the frequency at point “B”, it is up to
the AGC system to restore the frequency back towards 60 HZ. The AGC system
in the Balancing Authority that suffered the generation loss pulses those units on
AGC control to replace the generation loss. When the loss is replaced the
Balancing Authority’s ACE moves towards zero and the system frequency is
restored. Only a fraction of the AGC response is illustrated on Figure 4-54 since
AGC has 15 minutes to recover ACE according to the NERC DCS.
Governor Deadbands
One other important setting for a governor control system is illustrated in Figure
4-54. The deadband setting is 0.03 HZ for the governors of the system
represented in the figure. Recall, the governor deadband is a range of frequency
around 60 HZ for which the governor does not respond. A typical deadband
ranges from 0.02 to 0.04 HZ. For the system in Figure 4-54, the governors do not
begin to adjust unit outputs until the frequency has declined to below 59.97 HZ.
4-84
12422963
Frequency Control
(many generators tripped) it took the Balancing Authorities involved longer than
15 minutes to get the frequency back to normal levels. However, steady progress
was made and frequency was recovered to 60 Hz about 17 minutes after the start
of the event.
Figure 4-56 illustrates the frequency in the New Brunswick area of the Eastern
Interconnection during the August 14, 2003 disturbance. This was one of the
largest disturbances ever in the North American power system. 70,000 MW of
load was lost. The system separation starts at time “0” on the time scale of the
figure. The New Brunswick area becomes part of a large northeast island that
separates from the remainder of the Eastern Interconnection. Note the frequency
oscillations that occur due to many generators, loads, and transmission lines
tripping. Eventually system operators in the northeast island get the frequency
under control and back down to 60 Hz.
4-85
12422963
Frequency Control
4-86
12422963
Frequency Control
The “SR”
VS × VR subscripts are
PSR = × sin δ SR referring to a
X SR measurement
between the
sending and
Recall from Chapter 2 that the amount of MW transferred between two locations receiving ends of
is primarily dependent on the impedance and the power angle (δSR) between the the system.
two locations. If the power angle stays the same, the MW transferred does not
vary significantly. Following the loss of a large generator, the lost MW must be
replaced. Neighboring generators supply the MW from their inertia energy. The
MW flow must therefore increase on the lines feeding into the area that lost the
generation.
If the power flows increase it means that the power angle must have increased.
Power angles only change if there has been a momentary change in relative speed
or an acceleration between two areas of the power system. When a major
generator is lost the areas of the power system that replace the lost generation
must briefly accelerate with respect to the area that lost the generation.
If the frequency undershoots were measured at the point where the generation was
lost and also near the different generators that respond by increasing generation,
one would find that these undershoots have slightly different magnitudes. The
point where the generation is lost has a larger frequency undershoot then the
points from which the generation is replaced.
The different undershoots represent the supplying areas briefly accelerating with
respect to the area that lost generation. For several seconds the supplying areas
run slightly faster than the receiving areas to allow power angles to increase and
power flows into the generation deficient area to increase.
4-87
12422963
Frequency Control
Figure 4-58 further illustrates this concept. Figure 4-58 (a) represents a simple
power system with frequency initially at the normal value of 60 HZ. Assume a
large generator is lost. Frequency immediately begins to drop throughout this
sample system. At the point where the generation is lost the frequency
undershoot reaches its minimum value of 59.9 HZ as illustrated in Figure 4-58
(b). At the ends of the simple power system, the frequency undershoot is 59.95
HZ. The differences in the frequency undershoot values between the ends and
middle of the system result in a power angle change. For example, the difference
in undershoots is 0.05 HZ (59.95-59.90). If this difference lasts for 2 seconds
then the power angle can change within this two second window. The
calculations are shown below:
4-88
12422963
Frequency Control
59.95−59.90 = 0.05HZ
Assume this Difference Lasts for 2Seconds
0.05 Cycles × 2Seconds × 360 Degrees
Second Cycle
Equals a 36°Change in Power Angle
4-89
12422963
Frequency Control
In the late 1960’s a utility in Kentucky was one of the first utilities to install a
digital AGC system. This system had a capability to automatically record
frequency data following a disturbance. The frequency recorder function was
known as a frequency trap. An Iowa utility, located west of the Kentucky utility,
also installed a digital AGC system with frequency trap capability.
In early 1970 a Tennessee utility lost a generating unit that was then carrying 800
MW. A frequency disturbance wave propagated throughout the Eastern
Interconnection. The Kentucky and Iowa utility frequency traps activated and
recorded the frequency disturbance.
Utilities in this time period did not have accurate time measurement equipment.
The Kentucky and Iowa utilities could not tell each other exactly what time their
frequency traps were triggered. The two utilities could, however, exchange
frequency response data. Figure 4-59 is a plot of both the Kentucky and Iowa
frequency data following the disturbance. Note that at a plot time of -4 seconds
The subsequent both frequencies start to plunge. This is in response to the Tennessee disturbance.
disturbance was the Also note that at a plot time of 40 seconds both frequencies start to plunge again.
loss of the tie-lines This was due to a subsequent disturbance that occurred west of Iowa.
between the
Western and
Eastern
Interconnections.
The
Interconnections
were connected
with AC tie-lines at
the time. These lines
frequently tripped
and were eventually
removed from
service due to this
constant tripping.
By lining up the initial frequency plunges due to both disturbances the utilities
were able to compare frequency response data with accurate time scales. Note
that as the first frequency wave from the Tennessee disturbance travels through
the Interconnection, Kentucky records the maximum frequency plunge 3.6
seconds later than Iowa does. For the subsequent disturbance, Iowa records the
maximum disturbance 3.6 seconds later than Kentucky records it.
4-90
12422963
Frequency Control
The conclusion is that it took 3.6 seconds for a frequency disturbance wave to Note that this speed
travel between the Kentucky and Iowa frequency recorders. Since the distance was for this
particular
between the frequency recorders was known, the utilities were able to estimate disturbance. Other
that the frequency disturbance wave traveled at approximately 200 miles/second. disturbances will
have different
4.10 Staged Response to a Generation Loss speeds due to
changing system
A four-stage process can be used to describe the response of the power system to
conditions.
a generation loss. Assume that a major generator is lost. The power system
progresses through the stages listed in Figure 4-60.
Given modern
Stages of a Generation Loss telecommunication
systems, more
accurate methods
1. Electromagnetic Energy Storage are now available
to calculate the
2. Inertial Stage speed of the
traveling wave.
This example is
3. Governor Response Stage used due to the
interesting manner
4. AGC Stage in which the
answer was
Figure 4-60. Stages of a Generator Response obtained.
4-91
12422963
Frequency Control
The approximate The remainder of the interconnected system has not yet experienced a frequency
time frames given decline. As the frequency pocket develops in the area that suffered the loss, the
for each of the remainder of the interconnected system begins to supply inertial (rotational)
stages overlap one energy to the low frequency pocket. Over the next several seconds, the frequency
another. This is throughout the Interconnection moves towards a common lower value. The
intentional; the
stages are not frequency of the pocket recovers significantly during this period while the
discreet but tend frequency of the remainder of the interconnected system falls slightly. This
to overlap one second stage of the response is called the inertial stage. The inertial stage has an
another. approximate time period from 1/3 second after the generation loss to 5 seconds
after the loss.
During the inertial stage all the interconnected system generators supply MW in
proportion to their relative size. Large (massive) generators respond with more
MW.
4-92
12422963
Frequency Control
During the
electromagnetic
energy stage the
generators
respond with
energy stored in
their magnetic
fields. Those units
electrically
closest to the
point of loss will
provide more
MW.
4-93
12422963
Frequency Control
4-94
12422963
Frequency Control
During the
governor response
stage the generators
respond in
accordance with
their respective
governor settings,
their spinning
reserve levels, and
the ability of the
generators to
provide the
requested governor
response.
4-95
12422963
Frequency Control
4-96
12422963
Frequency Control
4-97
12422963
Frequency Control
If the AGC is disabled, the system operator must return the frequency of the
islands to 60 HZ. To raise an island’s frequency, a system operator can have on-
line generators raise generation levels, start peaking units, or if no generation is
available, manually drop load within the island. To lower frequency, a system
operator would request that generators within the islanded area lower generation.
If the interconnected system breaks into or is restored into islands and AGC is
used, the method by which AGC controls the power system may be modified.
During normal interconnected operations, AGC is typically set in a “tie-line bias”
mode of operation. This means that frequency is monitored to maintain 60 HZ
but any corrections are “biased” or modified based on the difference between
scheduled and actual net interchange.
During islanded operation, the island’s tie-lines to neighboring systems are
severed. The islanded system cannot control to non-existent tie-line flows so
AGC may be switched to a mode of operation called “flat-frequency” control. In
this mode of operation the difference between the actual and scheduled frequency
is all that drives the AGC control signals.
4-98
12422963
Frequency Control
4-99
12422963
Frequency Control
4-100
12422963
Frequency Control
4-101
12422963
Frequency Control
4-102
12422963
Frequency Control
4-103
12422963
Frequency Control
ACE = ⎡⎣ NI A − NIS ⎤⎦ − 10 × B × ⎡⎣ FA − FS ⎤⎦ − ⎡⎣ I ME ⎤⎦
4-104
12422963
Frequency Control
4-105
12422963
Frequency Control
4-106
12422963
Frequency Control
4-107
12422963
Frequency Control
4-108
12422963
Frequency Control
4-109
12422963
Frequency Control
A. 500 MW
B. 1000 MW
C. 200 MW
D. 50 MW
A. True
B. False
4-110
12422963
Frequency Control
A. 2.0 seconds
B. 2.4 seconds
C. 1.0 second
D. 1.2 seconds
A. -75
B. +75
C. -150
D. +150
A. 5%
B. 0%
C. 10%
D. 8%
10. What element of the power system is typically most susceptible to damage
from prolonged operation at frequencies above or below 60 HZ?
4-111
12422963
Frequency Control
A. 75%
B. 100%
C. 0%
D. 25%
13. What magnitude of frequency change would cause a 10% droop governor
to move its generator from zero to full output in a 60 HZ system?
A. 6 HZ
B. 10 HZ
C. 3 HZ
D. 5 HZ
A. DCS 1
B. DCS 2
C. CPS1
D. CPS2
4-112
12422963
Frequency Control
A. 50%
B. 100%
C. 200%
D. No limit
4-113
12422963
Frequency Control
4-114
12422963
5
VOLTAGE CONTROL
12422963
12422963
Voltage Control
VOLTAGE CONTROL
SECTION OVERVIEWS
5.1 Introduction
Voltage control is closely related to the availability of reactive power.
5.2 Causes of Low Voltage
Heavy power transfers are a principle cause of low voltage due to the Mvar
losses.
5.3 Causes of High Voltage
Lightly loaded transmission lines are a principle cause of high voltage.
5.4 Effects of Low Voltage
Low voltages can impact power system equipment and operations in numerous
ways.
5.5 Effects of High Voltage
High voltages can lead to the breakdown of equipment insulation, cause
transformer over-excitation, and adversely affect customer equipment.
5.6 Use of Voltage Control Equipment
Capacitors, reactors, LTCs, and SVCs supplement generators as means of
controlling system voltage.
5.7 Role of the System Operator
The system operator is usually responsible for maintaining reactive reserves and
controlling voltage deviations.
SO-1
12422963
12422963
Voltage Control
TABLE OF CONTENTS
TOC-1
12422963
Voltage Control
TOC-2
12422963
Voltage Control
TOC-3
12422963
12422963
Voltage Control
LIST OF FIGURES
LOF-1
12422963
Voltage Control
LOF-2
12422963
Voltage Control
5-1
12422963
Voltage Control
The middle portion of Figure 5-1 is a plot of the complex power (“S” or MVA)
being delivered by this system. This complex power wave was formed by
multiplying a point in time on the voltage wave by the corresponding point in
time on the current wave. Notice how the complex power wave oscillates up and
down and is at times negative. The negative portion of the wave represents
periods in which power is actually being absorbed back into the system
generators.
The bottom portion of Figure 5-1 breaks down the complex power wave into two
separate waves. One wave is always positive and has an effective value of “P”.
This is the active power or MW portion of the power. A second wave oscillates
equally between positive and negative. Over each cycle the average value of this
power wave is zero. This wave represents reactive power and has maximum and
minimum values of “±Q”. The summation of active (“P”) and reactive power
(“Q”) is done using the power triangle as illustrated in the bottom right of Figure
5-1.
Figure 5-2 further illustrates the concepts of active and reactive power. Three
types of systems are represented in this figure: pure resistive, pure inductive and
pure capacitive. In the resistive system voltage and current are in-phase with one
another. The complex power (“S” or MVA) is found by multiplying the voltage
and current waves together. Notice that the complex power is always positive.
This means that there is no reactive power in a purely resistive system. All the
complex power is active power or MW.
In the pure inductive system of Figure 5-2 the current wave lags the voltage wave
by ¼ cycle or 90°. The complex power wave oscillates equally between negative
and positive. The complex power has an average value of zero. In a pure
inductive system there is no active power; all of the complex power is reactive or
Mvar.
The last system illustrated in Figure 5-2 is a pure capacitive system. Notice that
the current leads the voltage by 90°. The complex power again oscillates equally
between positive and negative and has an average value of zero. In a pure
capacitive system there is no active power; all the power is reactive.
5-2
12422963
Voltage Control
5-3
12422963
Voltage Control
losses as it flows through the system. One way to reduce these voltage drops and
losses is to reduce the amount of reactive power flowing through the system.
A simple way to reduce the amount of reactive power flowing is to add capacitors
near the inductive load. The capacitor can take the place of the generator as the
source of reactive power. When the inductive load needs to store reactive power
the capacitor is ready to give its reactive power back to the system. The reactive
power does not have to come from the generators so less voltage drop and fewer
losses occur across the power system.
Figure 5-3 illustrates the use of a capacitor to supply the reactive needs of an
inductive load. As far as the power system is concerned, the capacitor acts like a
source of reactive power for the inductive load. The generator’s reactive power
obligation is reduced when the capacitor is switched in-service. Less reactive
power flow from the generator means less system current flow, less power loss,
and less voltage drop.
5-4
12422963
Voltage Control
If these conventions for the flow of reactive power are used we can further say
that reactive power normally flows from the high voltage to the low voltage point.
For example, to get more reactive power to flow from a generator, simply raise
the generator’s voltage level.
Figure 5-4 summarizes conventions for the flow of reactive power. In the top of
the figure reactive power is flowing from the generator to an inductive load. In
the bottom portion of the figure the generator is absorbing reactive power from a
capacitive load.
A generator
supplies reactive
power to an
inductive load. A
generator absorbs
reactive power from
a capacitive load.
5-5
12422963
Voltage Control
Reactive Losses
Reactive power is As complex power (both active and reactive) flows through the radial system of
never actually lost. Figure 5-5 voltage drops occur. The magnitude of the system voltages is directly
The term reactive related to the availability of reactive power. The greater the amount of spare
losses is used to reactive power, or reactive reserves, the more capable the system is of
refer to reactive
power that is in
maintaining its voltages. One way to increase reactive reserves is to minimize the
use by a system reactive usage by the system, or to reduce the reactive losses of the system.
element.
The formulas given in Figure 5-6 for active and reactive power losses can be
easily derived (using Ohm’s Law) from the simple radial power system illustrated
in Figure 5-5. These two formulas are used to calculate the active and reactive
power losses as power flows through the transmission system.
5-6
12422963
Voltage Control
⎡ P2 +Q2 ⎤
MWLoss =3× ⎢ 2 ⎥ ×R=3× I2 × R
⎣ V ⎦
⎡ P2 +Q2 ⎤
MvarUsage =3× ⎢ 2 ⎥ ×X=3× I2 × X
⎣ V ⎦
5-7
12422963
Voltage Control
5-8
12422963
Voltage Control
The Mvar provided to the system from a transmission line’s natural capacitance Lightly loaded lines
can be stated mathematically as: are capacitive while
heavily loaded lines
are inductive.
V2
MvarProduced =
XC
Where XC is the line’s capacitive reactance. Note that the Mvar produced is a
function of voltage, not current.
The Mvar used by a line can be stated mathematically as:
MvarUsed = I 2 × XL
Where XL is the line’s inductive reactance. Note that the Mvar used is a function
of current, not voltage.
The SIL of a line occurs when:
MvarProduced = MvarUsed
or when:
V2 2
= I «X L
XC
When a transmission line is loaded below its SIL, the line is equivalent to a
capacitor. The line provides Mvar to the power system. When a transmission line
is loaded above its SIL, the line is equivalent to a reactor. The line absorbs Mvar
from the system.
Much can be inferred about voltage levels across a transmission line if the SIL of
the line is known. When a line is loaded below its SIL, the high voltage point on
the line is toward the middle of the line. When a line is loaded at its SIL the line
voltage profile is almost flat. When a line is loaded above its SIL the low voltage
point is in the middle of the line. Figure 5-8 illustrates these points. The vertical
dashed lines in Figure 5-8 represent voltage levels across a simple transmission
system when the line is below, at, and above its SIL.
5-9
12422963
Voltage Control
5-10
12422963
Voltage Control
5-11
12422963
Voltage Control
Chapter 6 “Voltage
Stability” addresses
the use of P-V
curves in greater
detail.
5-12
12422963
Voltage Control
An indication of just
how heavily loaded
the remaining line is
can be seen in the
line’s power angle.
Note the angle
spread across the
transmission path
has increased from
26° in Figure 5-11
to 68° in Figure 5-
12.
5-13
12422963
Voltage Control
2
⎡V ⎤
MvarActual = MvarRated x ⎢ ACTUAL ⎥
⎣ VRATED ⎦
This formula states that the Mvar output of a shunt capacitor is equal to its
nameplate or rated value times the square of the per-unit voltage at which the
capacitor is energized. As an example, if a 100 Mvar capacitor (rated 100 Mvar
at 345 kV) is energized at 362 kV the capacitor output is:
2
⎡ 362 ⎤
MvarActual =100 x ⎢ ⎥ =110 Mvar
⎣ 345 ⎦
5-14
12422963
Voltage Control
5-15
12422963
Voltage Control
5-16
12422963
Voltage Control
Ferranti Rise
The Ferranti rise effect is a long term overvoltage condition that is associated with
high voltage lines that have their receiving ends open. Overvoltages greater than
10% above nominal can easily occur. The magnitude of the overvoltage depends
on the length of the open-ended line and the strength of the system tied to the
closed-end of the line.
Figure 5-15 illustrates an open-ended high voltage transmission line. The voltage
at the closed or sending end is VClosed. The voltage at the open or receiving end is An open-ended
VOpen. Since the line is open there is no significant active (MW) power flow. line may still have
However, there is Mvar flow on the line. Recall that a transmission line is the a small MW flow
due to line losses.
equivalent of a shunt capacitor. When a line is open-ended the shunt capacitor
effect still exists.
The current flow on an open-ended line is that current needed to charge the line’s
natural shunt capacitance. In Figure 5-15, current flow is shown from the system
into the closed-end of the line. This current flow is charging the line’s natural
capacitance which is spread out over the entire length of the line. The current
flow into an open-ended line is called the “charging” current since this current is
charging the natural capacitance of the line.
Charging current is a “leading” reactive current flow. Normally when we think of
reactive current flow we think of lagging reactive current. For example, induction
motors draw lagging reactive current from the power system. When lagging
reactive current passes through a transmission line’s inductive reactance (X) it
results in a voltage drop.
5-17
12422963
Voltage Control
5-18
12422963
Voltage Control
the beginning of the line. By the time the charging current reaches the open-end
of the line there is not much capacitance left to charge and the rate of increase in
voltage is smaller.
This equation is
actually based on
traveling wave
theory. When the
line is open-ended a
standing wave
develops and the
open-end voltage
magnitude is a
function of the
length of the line.
5-19
12422963
Voltage Control
Figure 5-18 was developed from the equation for the Ferranti voltage rise. This
figure plots the expected voltage rise from the closed to the open-end for various
lengths of line. The plot can be used to estimate the Ferranti effect for any length
high voltage line.
These magnitudes of
Ferranti rise
assume no series or
shunt compensation
is in use.
5-20
12422963
Voltage Control
depends on how much Mvar (QS) is flowing from the equivalent system into the
closed-end bus prior to the line being open-ended. The greater the Mvar into the
closed-end bus prior to opening the receiving end, the higher the closed-end
voltage will rise.
X Equivalent × Q s ⎡ X Equivalent × PS ⎤
E Equivalent = VClosed + + j⎢ ⎥
VClosed ⎢⎣ VClosed ⎥⎦
What this means from a practical standpoint is that you should always be
concerned about open-ending a line. However, when open-ending a high voltage
line that depended heavily on reactive support from the closed-end, you should be
even more concerned. This type of situation occurs if there is a long thin system
feeding a remote load, and a line that forms part of this system is open-ended.
5-21
12422963
Voltage Control
5-22
12422963
Voltage Control
Harmonic Overvoltages
Harmonic overvoltages (illustrated in Figure 5-21) are caused by the interaction Harmonic over-
voltages are
of capacitive and inductive elements, and sources of harmonics. The circuit of introduced here.
Figure 5-21 is typical of the circumstances that can cause harmonic overvoltages. Chapter 9 provides
The “L” and “R” of the transformer and the “C” of the capacitor form a natural greater detail.
“RLC” circuit that “resonates” or oscillates at a certain frequency value. If the
harmonics generated by the HVDC converter have a frequency close to this
resonant frequency high magnitudes of current could pass back and forth between
the capacitor and transformer. These high currents could produce voltages high
enough to damage the transformer or shunt capacitor.
Figure 5-21 follows on the next page.
5-23
12422963
Voltage Control
Lightning Overvoltages
Lightning strikes lead to transient overvoltages. This is one reason for installing
surge or lightning arresters, to arrest or trap the high voltage surge caused by
lightning strikes to a transmission line or substation. Lightning strikes are a very
rapid event. A typical lightning strike may last less than 0.00005 seconds.
However, a lightning strike packs a large amount of energy in this short period.
Transient overvoltages may be in the millions of volts.
5-24
12422963
Voltage Control
Switching Overvoltages
Power system switching also leads to transient overvoltages. Each time a circuit A switching surge is
breaker or disconnect switch is opened under load the power system experiences a a large change to
switching surge. It is not uncommon for lightning arresters to operate in system voltage that
substations during switching of high voltage breakers. These surges are very lasts only a fraction
of a cycle.
rapid, lasting only milliseconds, but may exceed 200% of the scheduled voltage.
A 500 kV breaker may initiate a switching surge of 1000 kV when first opened.
Capacitive Switching
Switching of capacitors or open-ended lines is especially susceptible to switching
surges. When switching a capacitive element, the circuit breaker (or other
switching device) could end up with opposite polarity voltages on either side of
the switch. This could lead to twice nominal voltage across the circuit breaker.
For example, a 500 kV breaker could end up attempting to interrupt near 1000 kV
if it is used to open a long unloaded 500 kV line. The voltage that appears across
the open switching device is called the “recovery voltage”. The higher the
recovery voltage across the open contacts, the greater the likelihood of a re-strike
occurring.
Figure 5-23 illustrates the opening of a capacitive load. When the circuit breaker
interrupts the capacitive current the voltage is at a maximum or minimum value
(minimum in Figure 5-23). One-half cycle after the circuit breaker opens, the
capacitor is still charged to a minimum value but the system voltage has reached a
maximum. The circuit breaker now has twice system voltage across it. The
probability of a re-strike has increased.
5-25
12422963
Voltage Control
5-26
12422963
Voltage Control
5-27
12422963
Voltage Control
A rule of thumb is
that a 5% reduction
in the customer’s
voltage will result in
approximately a 3%
reduction in the
customer’s load
magnitude.
5-28
12422963
Voltage Control
5-29
12422963
Voltage Control
5-30
12422963
Voltage Control
PV Pf
⎡V ⎤ ⎡f ⎤
PNew = PRated × ⎢ Actual ⎥ × ⎢ Actual ⎥
⎣ VRated ⎦ ⎣ f Rated ⎦
QV Qf
⎡V ⎤ ⎡f ⎤
Q New = Q Rated × ⎢ Actual ⎥ × ⎢ Actual ⎥
⎣ VRated ⎦ ⎣ f Rated ⎦
The first column in the table describes the load type. For example, “resistive
space heater” and “heat pump space heating” are the first two load types. The
second column labeled “PF” is a typical power factor for that particular load. For
example, a resistive space heater typically has a unity (1.0) power factor.
The third column is labeled “PV”. The PV value predicts how that particular
load’s MW magnitude varies with a change in service voltage. The greater the
positive magnitude of PV the more that load’s MW magnitude decreases as its
service voltage decreases. The fourth column is labeled “Pf”. Pf predicts how the
MW load magnitude varies with frequency. The fifth column is QV and the sixth
Qf. QV predicts how the Mvar load magnitude varies with voltage and Qf predicts
how the Mvar load magnitude varies with frequency. Note that if any of the four
load coefficients (PV, Pf, QV, Qf) is negative then a drop in voltage or frequency
leads to a rise in MW or Mvar load magnitude.
The best way to illustrate the use of these load magnitude equations is to step
through a few simple examples.
5-31
12422963
Voltage Control
For a Typical Central Air Conditioner Load if Voltage Drops 10% the MW
Load Drops 2.1% While the Mvar Load Drops 21%.
Figure 5-27. Central Air Conditioner Type Load
The new load magnitude as a result of a 10% reduction in voltage is 97.9 MW and
47.5 Mvar. Our conclusion is that the 10% voltage reduction has little impact on
the MW load but a strong impact on the Mvar load. This is expected since an air
conditioner load is predominantly a motor type load and we would not expect
voltage to impact its MW magnitude that strongly.
For a Typical Resistive Space Heater Load if Voltage Drops 10% the MW
Load Drops 19% While the Mvar Load Does Not Change.
Figure 5-28. Resistive Space Heater Type Load
The new load magnitude as a result of a 10% reduction in voltage is 81 MW and 0
Mvar. Our conclusion is that the 10% voltage reduction has a strong impact on
the MW load and no impact on the Mvar load. This is expected since resistive
type load magnitude varies with the voltage squared. If the voltage drops to 90%
of nominal the load magnitude will drop to 81% (0.9 x 0.9) of nominal.
5-32
12422963
Voltage Control
⎡ V × VR ⎤
PTRANSFER = ⎢ S ⎥ sin δ S − R
⎣ XS−R ⎦
5-33
12422963
Voltage Control
Chapter 6 on Once motors stall due to exposure to low voltages, the motor may try to recover
Voltage Stability speed automatically as system voltages recover. To recover speed the motor
examines the impact draws large amounts of Mvar in the same manner as when it was first started.
of motor stalling on The combined reactive power needs of many motors trying to recover from a
system voltage in
stalled condition could prevent system voltage recovery. Eventually an entire
greater detail.
power system could collapse.
S3φ =3x I *x V
This is the same equation used to calculate the MVA losses in a power system.
The “I*” term is the phase current in the circuit while the “V” term is the line-to-
ground voltage drop across the element. To make our study of the effect of low
voltage on power system losses clearer this MVA loss equation is broken down
into two separate equations - one for the active power (MW) losses and one for
the reactive power (Mvar) losses.
Ohm’s law states that the voltage is equal to the product of the current and the
impedance (V = I x Z). It follows then that the MVA loss is also equal to:
5-34
12422963
Voltage Control
“Z” is the series impedance of the power system. As you recall, the series
impedance is composed of the inductive reactance (X) and the resistance (R). If
the resistance and reactance is substituted for the impedance two simple equations
for power loss are derived as stated below:
PLOSS = 3 × I 2 × R = MWLOSS
Q USAGE = 3 × I 2 × X = MvarUSAGE
Note the dependence of both losses on the current magnitude. If the current
magnitude is increased both types of losses increase. If the current magnitude is
decreased both types of losses decrease.
5-35
12422963
Voltage Control
transmission lines can withstand long term high voltages if the magnitude does
not lead to insulator flash-over. Major areas of high voltage impact include:
Î Transformers
Î Customer Equipment
Î System Load Magnitude
Î Angle Stability
Î Power Losses
Transformer Saturation
Transformers are very susceptible to damage from sustained high voltages.
Transformers operate based upon the principle of electro-magnetic induction.
Recall from Chapter 2 that a voltage is induced in one of the transformer’s
windings via an alternating magnetic field that links this winding to the
transformer’s other energized windings.
A transformer is an inductive load as it draws reactive power from the power
system to support its magnetic field. The magnetic field is required to transfer
active power between the windings. A transformer is designed to operate at a
rated voltage level. This rated voltage level is directly related to the strength of
the magnetic field in the core of the transformer. If the transformer’s rated
voltage level is substantially exceeded (greater than 10-20%) the transformer
draws additional Mvar from the system to support a spread of the transformer’s
magnetic field. The magnetic field spreads out from the core of the transformer to
areas that are not designed for changing magnetic fields. This could lead to
excessive heating in parts of the transformer and eventually may lead to
transformer failure.
Figure 5-30 illustrates the relationship between the operating voltage of a
transformer and the excitation current it draws to magnetize its core. Note that
when the transformer is operated near its rated voltage the excitation current is
small. As voltage is increased above rated the excitation current rapidly
increases. This excitation current is a reactive current. By noting the rapid
increase in excitation current in Figure 5-30 one can see why the reactive needs of
a transformer rise sharply when it is operated at too high a voltage.
5-36
12422963
Voltage Control
Transformer Over-Excitation
A transformer can saturate even when the operating voltage is near its rated value.
Transformer saturation is a function of both the operating voltage and the
operating frequency since both voltage and frequency impact the magnetic field
strength. If the voltage is high, the transformer core is subjected to a sustained
high magnitude voltage which increases its magnetic field strength. If the
frequency is low, the transformer is subjected to longer periods of the AC voltage
peak magnitude which also increases the magnetic field strength.
Transformer over-
The ratio of the operating voltage to the operating frequency is called the excitation and
transformers “% excitation”. Figure 5-31 is a plot of % excitation versus time of saturation is treated
exposure. For example, Figure 5-31 tells us that a transformer can be exposed to in greater detail in
a 20% “over-excitation” for less than 2 minutes before probable failure. The data the solar magnetic
disturbances section
in Figure 5-31 is for a typical transformer. (Remember, no transformer is of Chapter 9.
typical!) Note that for this typical transformer, a 10% over-excitation can be
handled indefinitely.
5-37
12422963
Voltage Control
Power plant
transformers are
often protected with
over-excitation
relays. These relays
look at the ratio of
voltage to
frequency. This type
of protection is used
in power plants
since both high
voltage and low
frequency operation
is possible,
especially during
start-up of the
generator.
Figure 5-31. Transformer Over-Excitation
⎡ V × VR ⎤
PTRANSFER = ⎢ S ⎥ × sin δ S− R
⎣ X S− R ⎦
5-38
12422963
Voltage Control
Note the dependence of both types of losses on the square of the current. If the
current can be reduced both active and reactive losses can be reduced by the
square of the current reduction. For example, if current can be reduced to 95% of
its initial value then power losses can be reduced to 90% (0.95 x 0.95) of their
initial value.
5-39
12422963
Voltage Control
Capacitors
Capacitors are viewed as sources of reactive power. Capacitors can be connected
to the power system in either a shunt or series connection. Shunt capacitors are
used to supply reactive power to the system. Series capacitors are used to reduce
the impedance of the path in which they are inserted.
Shunt Capacitors
Shunt capacitors are a source of Mvar that are installed in close proximity to the
point at which the extra Mvar is needed. When a shunt capacitor is switched in
the local voltage rises. Shunt capacitor switching is often used to control normal
daily fluctuations in system voltage levels due to load changes. Shunt capacitors
are connected to the power system as illustrated in the bottom of Figure 5-33.
When the shunt capacitor is in-service it effectively serves as a source of reactive
power. System voltages typically rise as the current draw from other reactive
sources is reduced.
5-40
12422963
Voltage Control
5-41
12422963
Voltage Control
5-42
12422963
Voltage Control
Reactors
Reactors can be viewed as absorbers or sinks of reactive power. Reactors can be
connected to the power system in either a shunt or series connection. Shunt
reactors are used to absorb reactive power from the system. Series reactors are
used to increase the reactance of the path in which the series reactor is inserted.
Shunt Reactors
Shunt reactor banks are used to absorb excessive reactive power from the power
system and thereby reduce system voltages. When high voltage transmission
lines are built, fixed and switchable reactor banks are often installed to help
reduce the overvoltages caused by lightly loaded high voltage lines. The
switchable reactor banks are typically under SCADA control. Switched reactor
banks are often found on transformer tertiary windings. These reactor banks are
remotely switched in and out-of-service to control high voltages. The bottom
portion of Figure 5-35 illustrates a shunt reactor bank.
Figure 5-35 follows on the next page.
5-43
12422963
Voltage Control
Series Reactors
Reactors can also be installed in series. Series reactor installations are not
uncommon in the distribution system or within older power plants. Series
reactors add inductive reactance to a path thereby increasing the overall path
impedance. The primary use of series reactors is to limit fault current. Fault
Chapter 8 describes
current is limited due to the increase in the path’s impedance. Series reactors can
power oscillations.
also be installed in the transmission system to help reduce power oscillations
between generators. The top portion of Figure 5-35 illustrates the connection of a
series reactor.
5-44
12422963
Voltage Control
5-45
12422963
Voltage Control
following major changes to the power system. OLTCs are used to correct long
term (often seasonal) voltage problems.
Operation of ULTCs
ULTCs can be operated in either a manual or an automatic mode of operation.
When in manual mode, tap positions are adjusted via selector switches installed in
the ULTC control cabinet. These selector switches are also operated via SCADA
if the utility has installed the necessary equipment. While in manual mode the
ULTC does not automatically respond to voltage changes in the system. An
operator must intervene to adjust the tap positions.
5-46
12422963
Voltage Control
5-47
12422963
Voltage Control
Figure 5-38 illustrates an ULTC control scheme. Note the PT and CT used to
input secondary current and voltage to the ULTC. The ULTC in this figure
adjusts tap positions if either the PT reads a voltage out of range or the CT reads a
current out of range. This combination of voltage and current monitoring allows
the ULTC to control the voltage at a remote secondary point. The ULTC adjusts
tap positions to compensate for changes in load. The load changes are detected
by monitoring the circuit current. This control scheme is commonly referred to as
load drop compensation (LDC).
5-48
12422963
Voltage Control
5-49
12422963
Voltage Control
Similar In Figure 5-39(c) the secondary taps are raised 16 positions. Sixteen positions is
transformers have equivalent to a 10% change in winding size. In our example, this tap change has
the same turns
ratio, tap changing
resulted in a 5.7% voltage rise to 146 kV. Note the change in the reactive flows
capability, and in Figure 5-39(c). The transformer is now pulling a large amount of reactive
impedances. power from the primary winding. The 345 kV voltage has dropped 3 kV (to 342
kV) as a result of this reactive power flow. When the secondary voltage is raised
via a tap change the primary often drops. Typically the voltage drop is so small
as to not be noticeable. The greater the tap change and the weaker the primary
side, the greater the primary voltage drop.
5-50
12422963
Voltage Control
5-51
12422963
Voltage Control
Excitation Systems
The excitation systems of the generating units on the power system are used to
control the overall voltage profile of the power system. Changes made to the
generator’s terminal voltages are subsequently spread throughout the power
system. Figure 5-41 illustrates the major elements of a generator’s excitation
system. The excitation system is used to control the terminal voltage and Mvar
production of the generator.
5-52
12422963
Voltage Control
process. Power plant operators may occasionally need to place voltage regulators
in manual mode. The voltage regulators should be returned to automatic mode as
soon as possible.
5-53
12422963
Voltage Control
When operating in
the upper half of the
curve the generator
is supplying
reactive power to
support the system
voltage. This type of
operation is called
lagging or
overexcited. When
operating in the
lower half of the
curve the generator
is absorbing
reactive power to
lower system
voltage. This type of
operation is called
leading or
underexcited
operation.
5-54
12422963
Voltage Control
5-55
12422963
Voltage Control
5-56
12422963
Voltage Control
Synchronous Condensers
A synchronous condenser is very similar to a synchronous generator with the
exception that it is not capable of producing any sustained active power.
Synchronous condensers produce /absorb reactive power. Synchronous
condensers do not need a prime mover as they are operated as a synchronous
motor. The power system supplies the MW to turn the rotor. An excitation
system is used to control the amount of Mvar produced or absorbed by the
synchronous condenser.
Synchronous condensers are an expensive source of reactive power and are Utilities that
seldom used in modern power systems. However, some companies do use operate HVDC
systems are good
synchronous condensers for Mvar support. The most common reason is that the
candidates for
company also wants the increased inertia from the spinning mass of the owning synchronous
synchronous condenser. condensers.
Some types of generating units (typically hydro) can be used in a synchronous
condenser mode. For example, in light load conditions utilities in the Pacific
Northwest may switch hydro generators from a generating to a motoring mode
and then use the generator excitation systems to absorb reactive power. Steam
units are rarely operated as synchronous condensers, although there are a few
exceptions.
Components of an SVC
A static var compensator (SVC) is similar to a synchronous condenser in that it is
also used to supply or absorb reactive power. However, in an SVC there are no
rotating parts, every element is static. SVCs are composed of shunt reactors and
5-57
12422963
Voltage Control
Thyristers were shunt capacitors. High speed electronic switching equipment (thyrister switches)
introduced in are used to adjust the amount of reactors or capacitors in-service at any one time.
Section 1.6.5.
SVCs have the equivalent of automatic voltage regulator systems to set and
maintain a target voltage level.
Figure 5-46 is a one-line diagram of a modern SVC. Note there are two shunt
There are many
variations to SVCs.
capacitor legs and two shunt reactor legs. A control system for the SVC sends
The SVC signals to the thyristers to control the amount of current flow through the
illustrated in this capacitor and reactor legs. For example, if the 230 kV bus voltage were to dip
figure is only one below the target value the control system would send electronic signals to the
possibility. thyristers. These signals may be either to reduce the current flow to the reactors
or to switch more shunt capacitors in-service. Either action raises the 230 kV bus
voltage. Figure 5-47 contains a picture of an actual SVC.
5-58
12422963
Voltage Control
SVC Filters
When thyristers are used to continuously control a current magnitude (as in the
TCRs of Figure 5-46) the 60 HZ current and voltage waveforms are affected. Harmonics are
addressed in
Harmonics are created. Harmonics are whole multiples of the fundamental greater detail in
frequency. (For example, the 3RD harmonic is 180 HZ.) When harmonics exist in Chapter 9.
the power system, the 60 HZ voltage and current waveforms no longer resemble
5-59
12422963
Voltage Control
pure sine waves. There will be some degree of waveform distortion. This
distortion can damage utility and customer equipment. Utilities try to remove
whatever harmonic content is present in the power system waveforms.
One method of reducing the impact of harmonics is to add harmonic filters.
Harmonic filters are combinations of capacitors, resistors and inductors. These
filter elements are tuned to absorb specific frequencies of harmonic energy. For
example, in Figure 5-46 the far left of the figure illustrates harmonic filters for the
5TH, 7TH and 13TH harmonics. In addition, a “high pass” (HP) filter is included.
The HP filter is tuned to absorb all high frequency harmonics.
5-60
12422963
Voltage Control
5-61
12422963
Voltage Control
5-62
12422963
Voltage Control
5-63
12422963
Voltage Control
5-64
12422963
Voltage Control
5-65
12422963
Voltage Control
5-66
12422963
Voltage Control
5-67
12422963
Voltage Control
5-68
12422963
Voltage Control
5-69
12422963
Voltage Control
5-70
12422963
Voltage Control
A. 40.5
B. 45
C. 55.6
D. 61.7
2. A 5% change in voltage will typically lead to what change in the total load
magnitude?
A. 2%
B. 3%
C. 5%
D. 10%
A. High voltage
B. Low frequency
C. High voltage and low frequency
D. All of the above
A. 1/3
B. 3/4
C. 2.0
D. 5.0
A. 345 kV
B. 340 kV
C. 350 kV
D. 360 kV
5-71
12422963
Voltage Control
A. 25%
B. 40%
C. 50%
D. 80%
A. 1/3
B. 3/4
C. 2.0
D. 5.0
9. Given a purely inductive load, what can be said about the MVA this load
draws from the power system?
A. True
B. False
5-72
12422963
Voltage Control
5-73
12422963
12422963
6
VOLTAGE STABILITY
12422963
12422963
Voltage Stability
VOLTAGE STABILITY
SECTION OVERVIEWS
6.1 Voltage Stability
Introduction to an extreme type of voltage deviation that can result in a voltage
collapse.
6.2 Definitions
Definitions of voltage collapse and voltage stability are presented.
6.3 Types of Voltage Instability
Long term voltage instability, classical voltage instability, and transient voltage
instability.
6.4 Long Term Voltage Instability
Description of a long term voltage instability.
6.5 Classical Voltage Instability
Description of a classical voltage instability.
6.6 Transient Voltage Instability
Description of a transient voltage instability.
6.7 Preventing Voltage Instability
Techniques to prevent voltage instability.
6.8 Role of the System Operator
A system operator may be able to recognize the conditions during which a voltage
instability can occur and take appropriate actions.
SO-1
12422963
12422963
Voltage Stability
TABLE OF CONTENTS
TOC-1
12422963
Voltage Stability
TOC-2
12422963
Voltage Stability
TOC-3
12422963
12422963
Voltage Stability
LIST OF FIGURES
LOF-1
12422963
12422963
Voltage Stability
6-1
12422963
Voltage Stability
6-2
12422963
Voltage Stability
6-3
12422963
Voltage Stability
6-4
12422963
Voltage Stability
6-5
12422963
Voltage Stability
6-6
12422963
Voltage Stability
6-7
12422963
Voltage Stability
6-8
12422963
Voltage Stability
the knee of the P-V curve moves out and up into the range of normal system
voltages. From a system operator perspective this is very dangerous. The best
warning signal - rapidly declining system voltages - is taken away with increased
use of shunt capacitors. As more and more shunt capacitors are installed, the
point of voltage instability is hidden or “masked”.
As additional shunt
capacitors are
placed in-service
the nose of the P-V
curve is pushed out
and up. The point of
voltage instability is
“masked”.
6-9
12422963
Voltage Stability
6-10
12422963
Voltage Stability
Figure 6-11. Radial Power System for Long Term Voltage Collapse
A summary of the steps to long-term voltage instability follows. (Refer to
Figure 6-11 as you progress through these steps.)
Î In response to increasing customer load, the power system ULTCs act to
raise declining low-side voltages. ULTCs raise voltage by adjusting the
transformer turns ratio. When the low-side turns are increased, the
transformer draws Mvar from the high side to support the larger winding
on the low side. The increased Mvar supply to the low voltage system
should raise low side voltage levels.
Î The Mvar supplied to the low voltage system was drawn from the high
voltage (345 kV in Figure 6-11) transmission system. This will cause a
reduction in the already low transmission system voltage levels. The
amount of reduction depends on how much additional Mvar can be
obtained from the sending end sources. (Assume that all available shunt
capacitors are already in-service.)
Î The generators at the sending system attempt to increase their Mvar
output. These generators are already close to their reactive capability
limits and can manage only small Mvar increases. In addition, only a
6-11
12422963
Voltage Stability
small portion of this Mvar makes it to the receiving end. The higher I2X
losses absorb the majority of the increased Mvar generation.
Î The failure to obtain additional reactive power results in a system voltage
decline. This reduction in voltage reduces the Mvar output of the shunt
capacitor banks and reduces line charging. (Recall the dependence of
shunt capacitors and line charging on the square of the voltage level.)
This further reduces the system voltages.
Î Over a several minute to several hour period the customer load increases
further. The ULTCs continually attempt to raise low-side voltage. These
ULTC adjustments have little impact on low-side voltages as there is
little Mvar available from the high side transmission system. Besides
being of no help to the low-side voltages, the tap changer action further
depresses high side voltages.
Î As new load is added the system voltage decays further, eventually
reaching the knee of the P-V curve. Once the system passes over the
knee, voltage and MW transfer could collapse following minor system
condition changes. The only way to save the system is to reduce the MW
load, or add additional Mvar, prior to reaching the point of voltage
instability.
6-12
12422963
Voltage Stability
Upstream ULTCs
should be
configured to adjust
their taps before
downstream
ULTCs.
6-13
12422963
Voltage Stability
Recall that load magnitude is dependent on voltage. The voltage overshoot yields
MW and Mvar load overshoot. The Mvar load increase may be enough to push
the system over the brink to voltage instability. The solution to this dilemma is to
allow the upstream ULTC to adjust voltage before the downstream ULTC starts
its tap movement. ULTCs are equipped with time delays that can be adjusted.
6-14
12422963
Voltage Stability
The tap changer could then runaway and eventually move to full boost. The
result of all the tap changes is lower high and low-side voltages. This sequence of
events is called a “self-defeating” tap change.
6-15
12422963
Voltage Stability
6-16
12422963
Voltage Stability
6-17
12422963
Voltage Stability
6-18
12422963
Voltage Stability
6-19
12422963
Voltage Stability
6-20
12422963
Voltage Stability
Phase 1 immediately follows the triggering event. For example, a large line trips
quickly driving down local area voltages. Voltages stabilize during phase one at a
low value but the voltage does not collapse. Voltages do not collapse due to a
combination of the impact of voltage on load magnitude and the short term
reactive boost from area generators. Phase 1 may last for a few minutes, at most,
due to the response of the generator overexcitation protection systems.
Phase 2 is the period in which the system actually experiences voltage instability
and likely collapse. As a loss of load diversity develops and generators
automatically run-back their Mvar outputs, the voltage collapses.
6-21
12422963
Voltage Stability
6-22
12422963
Voltage Stability
6-23
12422963
Voltage Stability
Figure 6-21 contains the same P-V and V-Q curves of Figure 6-20. The V-Q
curve in Figure 6-21 is simply a rotation and mirror image of the V-Q in Figure 6-
20.
6-24
12422963
Voltage Stability
6-25
12422963
Voltage Stability
6-26
12422963
Voltage Stability
6-27
12422963
Voltage Stability
The following day - July 3RD - a similar chain of events unfolded. At 2:03 p.m.,
the Jim Bridger-to-Kinport 345 kV line contacted a tree and tripped. The parallel
345 kV Jim Bridger-to-Goshen line falsely tripped due to ground relay
misoperation. The SPS activated and tripped two units at Jim Bridger.
Fortunately, operating conditions on July 3RD were substantially different than
July 2ND or a similar system response may have occurred. Schedules and
generator outputs had changed substantially from the previous day so area MW
and Mvar stress was substantially less. In addition, a key generator in the area
(Brownlee #5) was now in-service and delivering needed Mvar support.
Generators throughout the west again responded with inertial and governor
support. Voltages in the Boise area declined but stabilized at near normal
levels—97% on the 230 kV system. The Brownlee hydro units were the key units
in the area. Plant operators were concerned with the high Mvar output of the units
(field alarms had triggered) due to their support of the low system voltages. The
plant operators began to manually reduce the Mvar output to relieve unit thermal
stress. Voltages throughout the Boise area began to decline further. Idaho Power
Company system operators noted the declining voltages - recognized the
possibility for another voltage collapse - and immediately took the only option
available to them; shedding of Boise area load. All loads were restored, and the
system returned to normal within 1 hour.
These July 2ND and 3RD events in the Boise, Idaho area emphasize the need for
effective and sufficient dynamic Mvar reserve. If large amounts of rapidly
responsive dynamic reactive reserve had been available both incidents would
likely have resulted in no more than localized system disturbances. The July 3RD
events also illustrate how the rapid response of system operators can be the
difference between minor inconveniences and major system outages.
6.6 Short-Term or Transient Voltage Instability
6-28
12422963
Voltage Stability
The amount of Mvar an induction motor draws from the power system is directly
related to its speed. When an induction motor is first started, it draws high current
as it accelerates from a standstill position. Once the motor reaches its operating
speed, the current draw reduces sharply.
Torque/Speed Curves
Figures 6-24 and 6-25 illustrate the relationship between motor speed and the
available accelerating torque for two types of motors. Figure 6-24 is for a fan
type motor. The three curves in Figure 6-24, labeled rated voltage, 80% voltage
and 60% voltage, represent the available torque to accelerate the motor at three
different system voltage levels. The fourth curve in Figure 6-24 is for the load
torque of the fan. This is the torque applied to the fan shaft. A fan type motor
rises towards rated speed as long as the available accelerating torque is greater
than the load torque.
6-29
12422963
Voltage Stability
(pressure has bled-off) compressor. Notice that if a hot compressor motor slows
down below 60% of rated speed it cannot regain speed even if the rated system
voltage is available.
Motor Stalling
Assume a severe voltage disturbance strikes a system with a heavy concentration
of induction motors. System voltage declines which causes the induction motors
to slow down. Once the system voltage starts to recover the motor load
automatically tries to pick up speed. The in-rush of Mvar to return the motors to
rated speed may be enough to trigger transient voltage instability.
The declining voltages due to the sudden increase in Mvar demand may cause
uncontrolled tripping and the rapid collapse of the area power system. This
sequence of events is classified as short-term or transient voltage instability due to
the speed of the events. The entire process typically last less than 15 seconds.
Systems with dense concentrations of 1Φ air conditioning load are most
susceptible to this type of voltage instability.
6-30
12422963
Voltage Stability
state area. MLG&W is a large municipal power system. Figure 6-26 is a one-line
diagram of the MLG&W system and the surrounding TVA system.
The transient
voltage collapse
was initiated by the
failure of a circuit
breaker at the
Southeast Gate
substation. This
substation is shown
in the lower left of
the figure.
6-31
12422963
Voltage Stability
There was no differential relaying on the Southeast Gate 115 kV bus. The fault
lasted for 78 cycles until it was finally cleared by various backup relays. (The
shaded breakers in Figure 6-26 illustrate where the fault was cleared.) Bus
voltages in the area depressed to as low as 60% of normal during the fault. After
the fault was cleared area voltages recovered to about 75% of normal.
The initial low voltage and the subsequent recovery to only 75% of nominal
caused many area motors to trip or stall. The tripping of area motors was
beneficial since this reduced the connected load. However, many motors simply
stalled, and as they attempted to regain speed drew huge amounts of Mvar from
the system. As was mentioned earlier, this in-rush current may be 5 to 8 times the
normal load current requirements of the motors.
Much of the motor load consisted of 1Φ air-conditioner compressors. These
motors often do not have any type of undervoltage protection to trip off-line.
Instead the motors stall which aggravates the low voltage situation. During the
disturbance, which lasted 10 to 15 seconds, large portions of compressor motor
load stalled and tried to regain speed. As the Memphis area reactive demands
increased the surrounding TVA system was called upon to supply the additional
reactive power.
The most severe impact was 70 miles to the north in the Covington, Jackson, and
A reverse zone 3 Milan areas where reactive power is supplied primarily by shunt capacitor banks.
relay is a distance
relay that is set to
The prevailing low voltage resulted in low shunt capacitor reactive output. In
look in a reverse addition, several key area lines and generators were out for maintenance. The two
direction. This is 161 kV lines from Johnsonville to South Jackson were heavily loaded with MW
done to reduce and Mvar power. Within two seconds of the initial disturbance both of these lines
false trips due to tripped due to operation of reverse zone 3 distance relays. After the loss of these
line overloads.
two lines voltage at South Jackson fell to 67% of normal.
Over the next 5 seconds, the rest of the 161 kV lines into Covington, Milan, and
South Jackson tripped due to the low voltage and the high current flows. Auto-
reclosing efforts failed throughout the system. TVA lost a total of 565 MW of
load while MLG&W lost 700 MW of load. Figure 6-27 illustrates the breakers
that tripped. The oval boxes state the MW lost and the time it took to restore the
load.
In hindsight, the lack of a differential protection scheme on the 115 kV bus at
Southeast Gate substation was critical. However, the point to emphasize from this
event is the impact of large numbers of small 1Φ air-conditioners. The combined
reactive needs of many stalled air-conditioning compressors led to this transient
voltage instability and collapse.
6-32
12422963
Voltage Stability
6-33
12422963
Voltage Stability
This example
assumes that all
mid-point reactive
support comes from
the ends of the
system. The line
charging is also
ignored.
6-34
12422963
Voltage Stability
6-35
12422963
Voltage Stability
6-36
12422963
Voltage Stability
6-37
12422963
Voltage Stability
power systems. The following precautions can be taken to prevent a long term
voltage collapse in a radial power system:
Î Ensure that the power plants at the sending end of the power system have
sufficient reactive power reserves to support the system and the loads.
These dynamic reserves must meet the requirements of the heaviest
possible load period for both normal and contingency conditions
Î All available reactive power sources at the receiving end, such as shunt
capacitors, should be in-service and in proper working order. (Shunt
reactors should be out-of-service.)
Î If series capacitors are available in the radial system they should be in-
service. Series capacitors lower line reactance. When series capacitors
are in-service the system’s Mvar losses decrease.
Î If voltages are low in the transmission system a conservative rule of
thumb is to avoid the use of area ULTCs. ULTC operation can impact
voltage instability in two ways. System load naturally decreases with
decreasing voltage. When an ULTC operates to raise voltage it also
increases load magnitude. In addition, when ULTCs raise low-side
voltage they often depress high side voltage. ULTC operation may
increase the chances of a voltage collapse.
Î As a last resort a system operator should consider manually dropping
load. If all possibilities to control the voltage instability are exhausted, it
is better to drop load in a controlled manner than to let the system
collapse in an uncontrolled manner. Systems may have automatic
undervoltage relay schemes installed to trip load during low voltage
periods. It is critical that these schemes are in operation during the
voltage collapse prone periods of the year.
6-38
12422963
Voltage Stability
6-39
12422963
Voltage Stability
6-40
12422963
Voltage Stability
6-41
12422963
Voltage Stability
6-42
12422963
Voltage Stability
6-43
12422963
Voltage Stability
6-44
12422963
Voltage Stability
6-45
12422963
Voltage Stability
A. True
B. False
A. Induction motors
B. Motor type load
C. Nominal load
D. Non-motor type load
5. P-V curves indicate the __________ margin from voltage instability while
V-Q curves indicate the __________ margin from voltage instability.
A. Mvar / MW
B. MW/ Mvar
C. MW / current
D. Power / Mvar
6-46
12422963
Voltage Stability
7. In which type of voltage instability does a key element outage trigger the
voltage instability?
6-47
12422963
Voltage Stability
6-48
12422963
7
ANGLE STABILITY
12422963
12422963
Angle Stability
ANGLE STABILITY
SECTION OVERVIEWS
7.1 Introduction to Angle Stability
Angle stability is related to the phase angle separation between power system
buses.
7.2 Definition of Angle Stability
In an angle stable system the torque and power angles are controllable. In an
angle unstable power system angles and power flows are out of control.
7.3 Active Power Transfer and the Power Angle Curve
The power angle curve is used to determine the angle at which the mechanical
input to the power system is equal to the electrical power transferred out of the
generator.
7.4 Types of Angle Stability
Angle instability can occur in steady state, transient, or oscillatory environments.
7.5 Steady State Stability/Instability
Steady state angle instability develops gradually over time without any sudden
disturbance.
7.6 Transient Stability/Instability
Transient instability arises rapidly, in the first few seconds after a disturbance.
7.7 Oscillatory Stability/Instability
Oscillatory angle instability is characterized by power and voltage oscillations.
7.8 Out-of-Step Protection
Out-of-step protection is provided by protective relays that measure the apparent
impedance and the time it takes for the impedance to change.
7.9 Angle Instability Example
An example of angle instability is presented that occurred in the summer of 1998
in the upper mid-west power system.
7.10 Introduction to the Swing Equation
A brief introduction to the mathematical equation that describes the motion of a
generator’s rotor.
SO-1
12422963
Angle Stability
SO-2
12422963
Angle Stability
TABLE OF CONTENTS
TOC-1
12422963
Angle Stability
TOC-2
12422963
Angle Stability
TOC-3
12422963
12422963
Angle Stability
LIST OF FIGURES
LOF-1
12422963
Angle Stability
LOF-2
12422963
Angle Stability
LIST OF EQUATION
LOF-1
12422963
12422963
Angle Stability
In a stable power
system voltage
magnitudes and
angle differences
have acceptable
magnitudes and
are controllable.
7-1
12422963
Angle Stability
The torque and power angles may temporarily rise above 90° but only for short
(fraction of a second) periods of time. A system is angle unstable when system
operators lose their ability to control angles and power flows. Torque and power
angles grow beyond 90°, up to 180° and larger.
7-2
12422963
Angle Stability
Consider the voltage at the terminals of a generator with a two-pole (north and
south) cylindrical rotor. The rotor is spinning at 3600 rpm, which is equivalent to
60 revolutions per second. The terminal voltage of this generator reaches its
maximum and minimum peak values once during each revolution. For
synchronous power system operation, all of the generators in the interconnection
must hit their maximum and minimum voltage values within very small time
differences of one another.
Figure 7-2 illustrates two units at a power plant. Assume unit “A” is
synchronized (paralleled) to the system while unit “B” is about to be
synchronized. As illustrated, unit “B” will be 180° out-of-phase with the system
when its circuit breaker is closed. Unit “B’s” magnetic field will not match
cleanly with the power system’s rotating field. If a synchronizing attempt is
made, there could be several consequences. For instance, the synchronizing
attempt may be aborted, the unit may rapidly adjust its magnetic field alignment
or the unit could be damaged by the attempt to close out of synchronism.
This scenario
should not
happen in
normal system
operation
because
generator
synchronization
procedures exist
to prevent this
type of error.
7-3
12422963
Angle Stability
7-4
12422963
Angle Stability
7-5
12422963
Angle Stability
7-6
12422963
Angle Stability
single generator determines the speed of rotation of this entire system so there can
never be any relative acceleration.
7-7
12422963
Angle Stability
TA = TM − TE
Where:
TA = Accelerating Torque
TM = Mechanical Input Torque
TE = Electrical Output Torque
For purposes of An accelerating torque causes the rotor speed to vary. If TA is positive, the rotor
this Chapter, a speed increases above synchronous speed. If TA is negative, the rotor speed
generator’s rotor decreases below synchronous speed.
includes
everything that Since power is directly proportional to torque, power can be substituted for torque
rotates. This in the previous equation to yield:
includes the
turbine. PA = PM − PE
Where:
PA = Accelerating Power
PM = Mechanical Input Power
PE = Electrical Output Power
7-8
12422963
Angle Stability
This equation is a power balance equation for the rotor. Whatever mechanical
power is input to the rotor should come out as electrical power to the system. If
what goes in does not match what comes out then an accelerating term (PA) exists.
When the mechanical power (PM) input to the generator exceeds the electrical
power output (PE), the rotor accelerates and in that way stores the excess energy.
When the mechanical power input to the generator is less than electrical power
output, the generator draws the difference from its stored rotor energy, and
decelerates.
For a generator’s torque angle to change there must be accelerating power.
Accelerating power is obtained by either varying the mechanical power input or
the electrical power output. When a fault occurs near a generator the electrical
power output is sharply reduced. This causes the generator rotor to accelerate and
its torque angle to increase. If the mechanical power input to a generator is
suddenly reduced, the generator rotor decelerates reducing the unit’s torque angle.
The importance of the concept of accelerating power will become evident as the
types of angle stability are explored. The power-angle curve is a useful tool for
examining the impact of accelerating power on a generator’s angle stability.
7.3 Active Power & the Power-Angle Curve
This section reviews the use of the active power transfer equation and expands on
the use of the power-angle curve.
VS × VR
PS = × sinδ
XL
The [(VS – VR)/XL] portion is a relatively constant value and is called PMAX.
PMAX is the largest possible MW transfer between two locations. The MW
transfer can only reach PMAX if the angle spread is 90°. The amount of PMAX
actually transferred between the two points is dependent on the sine of the power
angle δ.
7-9
12422963
Angle Stability
7-10
12422963
Angle Stability
the angle grows above 90° the MW transfer further shrinks. This causes the
generator to accelerate even faster and the system to go unstable.
Figure 7-7 contains another illustration of a power-angle curve. The power
system operates at the intersection of the mechanical power input line and the
power-angle curve. The angle is approximately 35° and the MW transfer (PT) is
100 MW. Assume the angle and MW are holding steady at 35° and 100 MW.
The mechanical power input to the generator then equals the MW output. There
is no accelerating energy. This is a desired point of operation.
7-11
12422963
Angle Stability
The simple power systems used to illustrate points in this text always operate on
their power-angle curves. The operating point along the curve may be above, at,
or below the mechanical power input line and still be a stable operating point.
The important consideration is what the angle difference is at the time. If the
angle is greater than 90° and the system is operating below the mechanical power
input line, the situation is hopeless. The generator’s rotor is forced to accelerate
and the generator pulls out-of-step with the remaining power system.
The next sections examine three general classifications of angle stability. Power-
angle curves are used to illustrate all three angle stability classifications.
7-12
12422963
Angle Stability
7-13
12422963
Angle Stability
7-14
12422963
Angle Stability
In the right of Figure 7-9(b) the system is exposed to a more severe disturbance.
This time the system does not recover from the disturbance. The angle grows and
continues to grow until the system is unstable. Following a severe disturbance, a
system may become transiently unstable very rapidly. The time lapse from initial
disturbance to instability is typically less than a few seconds.
Many power systems restrict their MW transfers due to transient stability
concerns. In general those power systems with long transmission lines and
remote generation are most susceptible to transient instability. Power systems
that are most concerned with the possibility of transient instability include:
Any power system
Î The far western portion of the Eastern Interconnection can be made
susceptible to
• The Dakotas, Western Kansas, Western Nebraska, etc transient instability
Î Most areas of the Western Interconnection if it is weakened
enough. Remove
Î Most of the Canadian systems enough lines from
even a strong
Î Most small, weakly interconnected systems such as those found in system and it will
Alaska eventually be
subject to transient
Oscillatory Stability / Instability instability.
7-15
12422963
Angle Stability
7-16
12422963
Angle Stability
The receiving end load grows further. Mechanical power input rises to level #3.
The angle rises to 50° and MW transfer to 910 MW. This system is now highly
stressed. The MW loading is likely close, or possibly exceeding, the thermal limit
of the transmission path. The angle is less than 90° so the system is still steady
state stable.
Receiving end load grows even further. The mechanical power input rises to level
#4. The system is now at its steady state stability limit. The MW transfer is 1,190
and the angle 90°. If any disturbance occurs, even a small one, this system could
go unstable.
Assume the load grows further by a small amount. The mechanical power input
is raised to level #5 to meet the new load. The mechanical power input is now
greater than the electrical power the system can possibly transfer. More
mechanical power is coming in to the generator than can be transferred across the
system. The difference is stored in the generator’s rotating components. Rotor
speed rises above synchronous speed. The angle increases due to this relative
acceleration. As the angle rises above 90°, the MW transfer starts to shrink.
Even more excess energy is now stored in the rotor. The angle increases further
and the system goes unstable. This system has reached steady state angle
instability.
The above description illustrated how steady state stability is theoretically
possible, but highly improbable, in the real world. A realistic power system
would collapse long before such high MW transfer levels are reached. System
voltage limits, thermal limits, or power oscillations would likely limit the loading
on this system long before the 90° point is reached. Even though this scenario is
improbable it does illustrate the process of steady state instability. Section 7.5.2
illustrates a more likely occurrence of steady state instability.
7-17
12422963
Angle Stability
The power-circle
diagram in this
figure is a very
basic diagram as
we have ignored
the line resistance
and the natural
line charging.
7-18
12422963
Angle Stability
7-19
12422963
Angle Stability
A remote
generator tied to
a large power
system is used to
keep our
description
simple. The large
power system is
not impacted
significantly by
what happens to
the generator or
the two-line
transmission
system.
Figure 7-13. Power System for Transient Stability & Instability
The top portion of Figure 7-14 contains the initial or pre-disturbance power
system. The remote generator is initially producing 1,000 MW. This MW is
transmitted to a large power system via two transmission lines. The large system
has 101,000 MW of load, 100,000 MW of which is fed from local generation.
A disturbance is created in this power system to study the transient stability of the
system. The circuit breakers at both ends of one of the transmission lines are
opened. From the generator perspective, once a line is opened the generator
suddenly has to transmit its mechanical power input across a much higher
impedance system. The generator must now work harder to transmit its MW
across the transmission system to the load area.
The bottom portion of Figure 7-14 contains power-angle curves for this system.
There are two curves; one for pre-disturbance conditions and one for after the line
7-20
12422963
Angle Stability
Transient
stability is a
rapid event.
From the initial
disturbance to
the peak of the
angle swing is,
at most, a few
seconds.
7-21
12422963
Angle Stability
If the generator
had not slowed speed. The angle keeps increasing as long as the generator’s speed is greater than
down to synchronous speed. The generator must rid itself of the excess stored energy
synchronous before it can return to synchronous speed and stop the angle increase.
speed by the time
it reached point As the operating point rises above point “C”, the generator starts to slow down.
“F” it would have The generator slows because it is now sending out more electrical power than it is
been transiently taking in mechanical power. The generator rises above point “C” until it slows
unstable. This down to synchronous speed. This occurs at point “D” in Figure 7-14. If the
possibility is
addressed in the generator had not slowed down to synchronous speed by the time it reached point
next section. “F” it would have gone unstable.
Maximum Angle
Our angle stability descriptions to this point have stated that the angle difference
between any two adjoining points in the power system can never stabilize at a
value greater than 90°. Note that we have emphasized, “stabilize” at a value. The
angle can exceed 90° for short periods of time as long as its final value returns to
less than 90°. This can happen if the angle is oscillating about a point that is less
than 90°.
7-22
12422963
Angle Stability
Note that the angle in Figure 7-14 could have swung all the way to point “F” as
long as it did not pass through point “F”. Once the operating point has passed
point “F”, the system is unstable. Once past point “F”, the electrical power output
is again less than the mechanical power input. The angle must increase, as energy
is again stored in the rotor. As the angle is already greater than 90° when past
point “F” the only option is a further angle increase and eventual angle instability.
Figure 7-15 illustrates the same information as Figure 7-14 but in a different
format. Points “A”, “B”, “C” and “D” are labeled on Figure 7-15. These labeled
points correspond to the labeled areas on Figure 7-14. Note that once disturbed
the MW output of the generator oscillates about 1,000 MW before finally settling
down at 1,000 MW.
In this example of transient stability the MW output starts and ends at 1,000 MW.
During the oscillation the output may swing between 1,500 to 500 MW. Note the
time frames in Figure 7-15. Once the angle started to reduce from point “D”, it
indicates that the system was transiently stable. It took approximately 1 second to
determine whether this system was transiently stable or unstable.
It takes only a few seconds to determine if the angle recovers from the first
swings. However, the oscillations that follow the first few swings may last for
many more seconds. When the oscillations finally settle down or dampen, the
operating point is at “C”. The angle at point “C” is greater than the initial angle at
point “A”. This is expected since the system has lost a line and the path
impedance is now greater. For transient stability we are only concerned with the
first several swings. Oscillatory stability concerns itself with subsequent swings.
7-23
12422963
Angle Stability
7-24
12422963
Angle Stability
Since the
decelerating
area (area #2) is
smaller than the
accelerating
area (area #1)
this generator
goes out-of-step
with the larger
power system.
7-25
12422963
Angle Stability
7-26
12422963
Angle Stability
The faulted
system curve is
the smallest of
the three curves
as system
voltage is
depressed
during the fault.
7-27
12422963
Angle Stability
7-28
12422963
Angle Stability
7-29
12422963
Angle Stability
Following a
severe
disturbance it
may take ½
second to shut the
intercept valve.
The valve then
remains closed
for a few seconds.
Ideally no steam
is vented and the
generator is
rapidly brought
back to initial
loading.
7-30
12422963
Angle Stability
Generator Dropping
An additional option for rapidly reducing the power system’s accelerating energy
is to quickly trip generation. Generator dropping refers to the intentional tripping
of generating units. Generators may be tripped to avoid an accelerating condition
that could lead to instability.
NERC utilities drop both steam and hydro generation. However the dropping of
hydro generation has definite advantages, as it is often simple and rapid process to
re-synchronize a hydro unit. In contrast, there are many events that could occur
which could delay the re-synchronizing of a steam unit.
7.7 Oscillatory Stability/Instability
This section describes oscillatory stability and instability and presents several The causes, effects,
illustrated examples. The oscillatory environment is characterized by a system and control of the
oscillations that
that is constantly changing. MW, Mvar, voltage magnitudes, angles, and
accompany
frequency may be oscillating. oscillatory stability
and instability are
The study of oscillatory stability is similar to steady state stability in that no
further addressed
severe triggering event is required. A system may enter into a period of Chapter 8.
oscillatory instability as the result of a minor disturbance such as a line switching
operation. Oscillatory instability may be a slowly developing event. A system
may begin a period of oscillations that last for several seconds, minutes, or even
7-31
12422963
Angle Stability
7-32
12422963
Angle Stability
7-33
12422963
Angle Stability
The oscillations
are shown in this
manner for
illustration only.
Actually all the
movement
between “B” and
“D” is along the
power-angle
curve.
7-34
12422963
Angle Stability
7-35
12422963
Angle Stability
7-36
12422963
Angle Stability
magnitude. Finally the power oscillations grow so large that protective relays in
the system are forced to operate.
7-37
12422963
Angle Stability
(activate) and, once the applicable timers elapsed, trip the circuit breaker at bus
“A”. Stepped distance protection schemes are very common but they do have a
weakness that exposes them to false tripping during power system disturbances
7-38
12422963
Angle Stability
out in the transmission system. If unusually high power flows and low voltages
were to occur in the power system, not due to a fault condition, zone #3 relays
would likely be the most sensitive to false trips.
Any power flow value can be converted from a MW and Mvar format to an
equivalent impedance. The formula for the conversion between power flow and
impedance is:
V2
ZAPP = R + jX =
P − jQ
If the MW and Mvar flow values are known, the power and voltage values can be
converted to an equivalent impedance. Assume that the power flow on the
protected line in Figure 7-27 is 200 MW and 50 Mvar. This flow is out of bus
“A” and into the protected line. If these flow numbers are converted to an
equivalent impedance, the impedance value might plot on the “R-X” diagram as
point “1”. Note that this point is not within the zone #3 relay operating
characteristic so the relay does not activate for this flow level.
Assume that a system disturbance occurs that creates large power flows and low
voltages in the area of bus “A”. (There is no fault.). The power flow out of bus
“A” to the fault changes immediately to 250 MW and 500 Mvar. This flow is
plotted as point “2” in Figure 7-27. Note that this apparent impedance activates
the relay. If the apparent impedance stays at point “2” long enough for the zone
#3 timer to activate the relay trips the circuit breaker at Bus “A”.
7-39
12422963
Angle Stability
By measuring how long it takes for the apparent impedance to change one could
tell if the impedance change was due to a fault or out-of-step condition. This is
how out-of-step relays operate, by measuring how fast the apparent impedance
changes.
Note the out-of-step tripping line in Figure 7-28. As the impedance changes it
first crosses the operating characteristic at point “A”. By measuring the time
difference as the impedance locus moves from point “A” to “B” the relay decides
if a fault or out-of-step condition has occurred.
7-40
12422963
Angle Stability
elapsed and the Sammis-Star 345 kV line tripped. This event triggered the
cascading outage in the Eastern Interconnection that eventually lead to the loss of
70,000 MW and impacted 70,000,000 people.
Figure 7-29 follows on the next page.
7-41
12422963
Angle Stability
7-42
12422963
Angle Stability
7-43
12422963
Angle Stability
the Twin Cities east and eventually to the Chicago area. This line is typically the
most heavily loaded of the three 345 kV lines that form the TCEX. At the time of
the trip the King-Eau Claire 345 kV line was loaded at approximately 1,050 MW
and the TCEX flow was approximately 1,000 MW.
Shortly after the loss of the second 345 kV line critical lower voltage
subtransmission lines began to trip due to the overloads caused by the outages of
the two 345 kV TCEX lines. At 02:21 CDT cascade tripping of the remaining ties
(including the last 345 kV line of the TCEX) between the upper mid-west and the
rest of the Eastern Interconnection occurred. The islanded area initially consisted
of large portions of Minnesota, North Dakota, South Dakota, Montana, and
Wisconsin in the U.S. and the Canadian provinces of Manitoba and
Saskatchewan.
In terms of the amount of load loss (approximately 1,000 MW) this disturbance
was not that severe. However, two very interesting events occurred during this
disturbance that make it a valuable learning tool.
The initial island was quite large and included several states and provinces.
Shortly after the initial island formation, two HVDC lines connecting the western
and eastern portions of the island tripped. The HVDC line tripping caused
cascading AC line tripping and the initial island broke into two separate islands.
Figure 7-31 illustrates the boundaries of the initial and subsequent islands.
7-44
12422963
Angle Stability
Ontario also
suffered during this
disturbance. The
entire western
portion of the
province was
blacked out.
7-45
12422963
Angle Stability
island were reconnected to the Eastern Interconnection. The North and South
Dakota portions of the island were not reconnected until approximately ½ hour
later.
7-46
12422963
Angle Stability
7-47
12422963
Angle Stability
d 2θ M
TAcc =J× = TMech − TElec
dt 2
Where:
TAcc is accelerating torque of the generator
J is the moment of inertia of the rotating mass
θ M is the angular displacement of the generator's rotor
d2
is a math symbol for second derivative
dt 2
TMech is the mechanical input torque
TElec is the electrical output torque
Equation 7-3. Equation for Generator Torque
In normal conditions TAcc is zero and the rotor is spinning at constant speed. To
relate this complex equation to our earlier work with the power angle (δ) the
equations of Equation 7-4 are presented.
θ M = ω St + δ M
d 2θ M d 2δ M
=
dt 2 dt 2
Where:
θ M is the angular displacement of the rotor
ω S is the synchronous angular speed of the rotor
δ M is the torque angle
Equation 7-4. Relationship Between Rotor and Torque Angles
The rotor angle θM is constantly changing. The torque angle δM is the angular
separation between the rotor and power system’s magnetic fields. The top
equation in Equation 7-4 simply states that although the rotor angle (θM) is
constantly moving the torque angle (δM) is fixed as long as the machine continues
to rotate at synchronous speed (ωS).
The second equation in Equation 7-4 illustrates the relationship between the
torque (δM) and rotor angles (θM) as they vary with time.
If the equations in Equations 7-3 and 7-4 are combined the result is as shown in
Equation 7-5.
7-48
12422963
Angle Stability
d 2δ M
J× = TAcc
dt 2
Where:
TAcc is the accelerating torque
J is the moment of inertia of the rotating mass
δ M is the torque angle
d2
is a math symbol for second derivative
dt 2
Equation 7-5. Accelerating Torque in Terms of Torque Angle
d 2δ M
J × ωM × = PAcc
dt 2
Where:
PAcc is the accelerating power
J is the moment of inertia of the rotating mass
ω M is the angular velocity of the rotor
δ M is the torque angle of the generator
d2
is a math symbol for second derivative
dt 2
J × ω M = M = Inertial Constant
Equation 7-6. Accelerating Power in Terms of Torque Angle
The value J × ω M is referred to as “M” and is called the inertial constant of the
generator. The value “M” is rarely used in practice. A more common variation
on “M” is the “H constant”. The “H constant” is related to “M” as shown in
Equation 7-7.
7-49
12422963
Angle Stability
1
× M × ωS
H= 2
SMach
Where:
H is the H constant
M is the inertia constant of the generator
ω S is synchronous speed of the generator
SMach is the 3Φ rating of the machine
Equation 7-7. Relationship Between “M” & “H” Values
Think of the “H constant” as a measurement of the energy stored in the machine
as a function of the MVA size of the machine. For example, assume two
machines have the same H constant. Even if one machine is twice the size of the
other, on an MVA to MVA comparison the machines have the same stored
energy. The larger the H constant for a machine, the more stored energy on a per-
MVA basis.
2×H d 2δ
× = PAcc
ωS dt 2
Where:
PAcc is the accelerating power
H is the H constant of the generator
ω S is the synchronous speed of the machine
δ is the torque angle
d2
is a math symbol for second derivative
dt 2
Equation 7-8. Accelerating Power in Terms of Torque Angle
The equation in Equation 7-8 is called the swing equation. This equation relates
how the torque angle of the machine varies when the generator experiences
periods of accelerating power.
The mathematics used in this series of equations is beyond the scope of this text.
This derivation of the swing equation is provided only as a reminder of the
complex dynamics of generator rotation.
7-50
12422963
Angle Stability
7-51
12422963
Angle Stability
7-52
12422963
Angle Stability
Figure 7-36 illustrates the locations of PMUs in the North American power
system as of April 2009. Note that several of the PMUs in Figure 7-37 are
installed but have not yet been connected to a data network via high-speed
telecommunication systems. Over the next few years many more PMUs are
scheduled for installation.
7-53
12422963
Angle Stability
7-54
12422963
Angle Stability
actions of special protection systems (SPS) that help ensure real-time angle
stability.
Many North American utilities face challenges integrating variable generation Recall the
description of
such as wind turbines. Several of these utilities are looking at synchrophasor data oscillatory
to better monitor real-time variable generation and integrate these resources instability in Section
economically while protecting system reliability. 8. Synchrophasor
data is proving to be
When synchrophasor data is used to drive power system control actions the very valuable for
concept is referred to as a wide area control system or WACS. Future WACS both monitoring and
applications will both extend the transfer capability of the power system while damping power
further enhancing reliability. A challenge is to balance the speed and computing system oscillations.
power of WACS with the knowledge and experience of the System Operators.
Power System Planning
Power system planners use computer simulation tools to study power system
events. The power system’s generators, transmission lines, loads etc., are all
modeled in these software simulation tools. Simulations are performed to study
both dynamic and static power system conditions. The results of the power system
simulations are used to determine operating security limits.
The more accurate the computer models, the greater the accuracy of the operating
security limits. Synchrophasor data is valuable for benchmarking simulation
models. For example, given the occurrence of a system disturbance, the
synchrophasor data is used to judge the accuracy of the computer simulations
(both static and dynamic) and improve the modeling techniques used for power
system equipment.
Disturbance Analysis
Synchrophasor data is valuable for analysis of power system disturbances. PMUs
collect and store high volumes of high-speed, time-synchronized data related to
conditions throughout the Interconnection. PMU data can be gathered quickly
following a disturbance and analyzed to determine the sequence of events and
what caused the disturbance. Highly accurate simulations can be developed
following the disturbance and system operators can “replay” the event to evaluate
their response.
Smart Grid Concept
The smart grid concept combines distributed power system sensors and high- The Smart Grid is a
speed communications/controls with distributed computing technology to coordinated effort
by North American
optimize the efficiency, reliability, and safety of electricity production, delivery governments and
and use. utilities to improve
the efficiency and
At the bulk power level, synchrophasor methods are an ideal technology to reliability of the
implement smart grid concepts. Synchrophasor systems collect, distribute, and North American
analyze critical data and convert the data into real-time information that power system.
improves or “smartens” the grid.
7-55
12422963
Angle Stability
7-56
12422963
Angle Stability
7-57
12422963
Angle Stability
7-58
12422963
Angle Stability
with respect to another part for the angle spread to grow and the system
to become unstable.
7-59
12422963
Angle Stability
7-60
12422963
Angle Stability
V2
ZAPP = R + jX =
P − jQ
7-61
12422963
Angle Stability
7-62
12422963
Angle Stability
7-63
12422963
Angle Stability
A. Angle stability
B. Loss of synchronism
C. Out-of-step
D. All of the above
A. Relative power
B. Synchronizing power
C. Stability power
D. Accelerating power
4. Match a type of angle instability from the left column with a unique
definition from the right column:
A. True
B. False
7-64
12422963
Angle Stability
7-65
12422963
Angle Stability
7-66
12422963
8
POWER OSCILLATIONS
12422963
12422963
Power Oscillations
POWER OSCILLATIONS
SECTION OVERVIEWS
8.1 Introduction to Power Oscillations
Low frequency power oscillations may be triggered by many events in the power
system. Most oscillations are damped by the system, but undamped oscillations
can lead to system collapse.
8.2 Power Oscillations on a Sample System
Oscillations develop as a result of rotor acceleration and/or deceleration following
a change in the MW output of a generator.
8.3 Natural Frequency of Oscillation
Low frequency inter-area oscillations are less damped than higher frequency local
area oscillations and are more likely to cause power system problems.
8.4 Oscillations and Excitation Systems
PSS or power system stabilizers are used to correct the harmful effects of fast
excitation systems and help reduce system oscillations. PSS usage is mandatory
in some operating regions.
8.5 Additional Causes of Oscillations
Large cyclic loads, incorrect governor droop settings, HVDC systems, and
generator pole slipping may lead to power oscillations.
8.6 Role of the System Operator
Power system oscillations are difficult to monitor. To prevent oscillations, the
system operator should hold power transfers within established limits and
maintain strong system voltages and adequate reactive reserve margins.
SO-1
12422963
12422963
Power Oscillations
TABLE OF CONTENTS
TOC-1
12422963
Power Oscillations
TOC-2
12422963
Power Oscillations
LIST OF FIGURES
LOF-1
12422963
12422963
Power Oscillations
8-1
12422963
Power Oscillations
8-2
12422963
Power Oscillations
For example, if a large generator trips, one typically would expect larger power
oscillations than if a small, lightly loaded transmission line trips. Note how the
preceding statement is qualified with the word “typically”. At times even a minor
event, such as the addition of a small load, may trigger an oscillation. This
oscillation may then grow in size until the system is forced to respond with
generator trips, line trips, etc.
8-3
12422963
Power Oscillations
8-4
12422963
Power Oscillations
on a major 500 kV line may have a frequency of 0.3 HZ (18 cycles per minute),
while oscillations confined to a single generating unit may be in the neighborhood
of 2 HZ or 120 cycles per minute.
8-5
12422963
Power Oscillations
8-6
12422963
Power Oscillations
8-7
12422963
Power Oscillations
Normal oscillations
are always
occurring. The
power system
provides enough
positive damping to
quickly reduce their
amplitude to
harmless values.
8-8
12422963
Power Oscillations
Sustained
oscillations are
neither positively
nor negatively
damped. They are
undamped.
8-9
12422963
Power Oscillations
8-10
12422963
Power Oscillations
VG × VL
PG − L = × sin δ G − L
XG − L
The loss of line #2 immediately increases the reactance (XG-L) of the system. An
inspection of the above equation tells us that the increase in reactance forces an
immediate decrease in the generator’s MW output (PG-L).
8-11
12422963
Power Oscillations
8-12
12422963
Power Oscillations
8-13
12422963
Power Oscillations
Figure 8-10. Plots of Power Output, Angle Spread & Rotor Speed
There are many other interesting comparisons that can be made between the plots
in Figure 8-10. Take a few minutes to study these plots to determine further
relationships between power output, phase angle and generator speed. For
instance, note in Figure 8-10 that the phase angle can only increase if the
turbine/rotor speed is greater than synchronous speed.
8-14
12422963
Power Oscillations
8-15
12422963
Power Oscillations
bridge’s roadbed and eventually these oscillations toppled the bridge into the
water below.
8-16
12422963
Power Oscillations
As the generator’s torque angle rises toward 90° its natural frequency of
oscillation reduces.
8-17
12422963
Power Oscillations
Since several At any one time there may be several distinct oscillations occurring within a
different frequency power system. Different frequency oscillations may occur simultaneously.
oscillations can The situation is similar to mechanical systems, such as in an automobile. For
occur at the same example, as a car increases its speed, different frequency oscillations may be
time it may be triggered. At one speed the car may violently shake while at a higher or lower
difficult to pick out
one specific speed this shaking stops. At a different speed some other mode of oscillation
frequency of may be triggered.
oscillation.
To simplify our description of the frequencies at which the power system
oscillates, the typical frequencies of oscillation (0.05 to 3.0 HZ) are divided
into four modes of oscillations. Each mode covers a range of frequencies.
This section describes each of the four modes of oscillation:
Î Inter-Area Mode (0.05 to 0.5 HZ)
Î Intra-Area Mode (0.4 to 1.0 HZ)
Î Local Mode (0.8 to 2.0 HZ)
Î Intra-Plant Mode (1.5 to 3.0 HZ)
8-18
12422963
Power Oscillations
8-19
12422963
Power Oscillations
power system and not between two distinct power systems. This mode is a low
frequency oscillation and is not well damped. Figure 8-14 illustrates intra-area
oscillations.
When a group of
generators oscillate
together the group
is referred to as
“coherent”
generators. A
coherent group acts
as if it is one large
generator.
Local Mode
Oscillation frequencies from 0.8 to 2.0 HZ are called the local mode of
oscillation. In this mode of oscillation each generator oscillates with respect to
the rest of the power system. When a generator is tied to a large power system via
a long radial line, it is especially susceptible to local mode oscillations. The local
mode is a high frequency oscillation and is usually well damped by the power
system. Figure 8-15 illustrates local mode oscillations.
8-20
12422963
Power Oscillations
Intra-Plant Mode
Intra-plant mode oscillations range from 1.5 to 3.0 HZ. In multi-unit stations, the
generators may oscillate with respect to neighboring units. These high frequency
oscillations are called intra-plant oscillations. Intra-plant oscillations are well
damped and usually do not cause any problems. Figure 8-16 illustrates intra-plant
mode oscillations.
Note that as a
progression was
made from the inter-
area mode to the
intra-plant mode the
oscillation
frequency increased
while the amount of
oscillating inertia
decreased. This is
expected as the
natural frequency of
oscillation increases
with decreasing
inertia.
8-21
12422963
Power Oscillations
By counting the
cycles and noting
the time lapse, the
frequency of this
local mode can be
calculated as
approximately 1.0
HZ. The inter-area
mode as 0.17 HZ.
8-22
12422963
Power Oscillations
of DC current to send to the rotor field winding. The combination of the AVR
and exciter maintains a constant terminal voltage and allows the generator
operators to choose (within capability limits) the voltage at which the generator
operates.
8-23
12422963
Power Oscillations
8-24
12422963
Power Oscillations
8-25
12422963
Power Oscillations
Figure 8-20 illustrates the effect a PSS can have on reducing low frequency
(approximately 1.0 HZ in Figure 8-20) power system oscillations.
PSS can also be
used for local The WECC and the MRO Regions have operating requirements that mandate the
oscillatory stability use of PSS. All units with fast excitation systems must be equipped with well-
concerns. These tuned PSS in these Regions. It is important that a large number of units have
PSS are typically
operational PSS. A 1000 MW generator with a properly tuned PSS may only
designed and tuned
to deliver a contribute one to two MW of damping. This small amount of damping from an
substantial amount individual unit is not enough damping to make much of a difference. PSS are
of damping. typically installed in the majority of generating units in the problem area. The
Several units in the combined effect of many PSS has a significant impact in damping oscillations.
PJM system are
equipped with PSS
to address local
oscillatory stability
concerns.
8-26
12422963
Power Oscillations
8-27
12422963
Power Oscillations
This strip-chart
automatically
switched to a finer
resolution time
scale when the
oscillations grew
in amplitude.
Chapter 10 HVDC (high voltage direct current) systems can cause frequency and power
describes the oscillations. The power converters at the ends of an HVDC transmission line
components and convert power between AC and DC. The HVDC control system’s operation must
operation of be coordinated with AC system generation levels to ensure the HVDC does not
HVDC systems.
cause AC system frequency disturbances.
8-28
12422963
Power Oscillations
HVDC Modulation
HVDC systems can also be used to dampen AC system power oscillations. The HVDC systems
power that flows in an HVDC system is removed from the AC system at the within the MRO
rectifier end of the HVDC. Assume that a low frequency oscillation is occurring Region are used to
in the AC system. If power could be removed from the AC and input to the dampen AC power
HVDC at the proper frequency, the AC system oscillation could be dampened or oscillations in
much the same
modulated. HVDC modulation systems remove AC system energy in such a manner as PSS.
manner as to dampen AC system oscillations. Several of the HVDC systems in
use within NERC use forms of HVDC modulation.
8-29
12422963
Power Oscillations
8-30
12422963
Power Oscillations
8-31
12422963
Power Oscillations
8-32
12422963
Power Oscillations
8-33
12422963
Power Oscillations
8-34
12422963
Power Oscillations
8-35
12422963
Power Oscillations
8-36
12422963
Power Oscillations
A. 0.001 HZ to .0001 HZ
B. 100 HZ to 80 HZ
C. 60 HZ to 30 HZ
D. 0.05 HZ to 3.0 HZ
A. Intra-area mode
B. Inter-area mode
C. Intra-plant mode
D. Local mode
5. High speed excitation systems tend to extend _____ stability limits but
may lead to _____ instability.
8-37
12422963
Power Oscillations
A. HVDC modulation
B. Amortisseur windings
C. PSS
D. All of the above
7. Which type of power oscillations are of most concern?
A. Negatively damped
B. Damped
C. Undamped
D. Positively damped
A. 2 and 4
B. 1 and 2
C. 4
D. 1, 2, and 3
A. Intra-plant mode
B. Inter-area mode
C. Intra-area mode
D. Local mode
10. On August 10, 1996, large 0.224 HZ power oscillations were measured in
the Western Interconnection’s Pacific AC Intertie 500 kV lines. These
oscillations were:
A. Intra-area mode
B. Local mode
C. Inter-plant mode
D. Inter-area mode
8-38
12422963
Power Oscillations
8-39
12422963
12422963
9
ADDITIONAL TOPICS
12422963
12422963
Additional Topics
ADDITIONAL TOPICS
SECTION OVERVIEWS
9.1 Additional Topics
Introduction to the varied topics addressed in this section.
9.2 Harmonics
Harmonics are integer multiples of the fundamental frequency. For example, the
3rd harmonic is 180 HZ.
9.3 Resonance
When electrical circuits resonate, high currents and voltages can develop and
cause system damage.
9.4 Subsynchronous Resonance
Subsynchronous resonance arises due to an interaction between the power system
and the natural mechanical oscillations of a steam turbine/generator.
9.5 Ferroresonance
Ferroresonance is a resonance condition due to a tuning between an electrical
circuit’s capacitance and iron-core inductance.
9.6 Geomagnetic Disturbances
Geomagnetic disturbances (GMD) can lead to geomagnetic induced currents
(GIC) that enter the power system through ground connections. These currents
can lead to thermal damage in power transformers.
SO-1
12422963
12422963
Additional Topics
TABLE OF CONTENTS
TOC-1
12422963
Additional Topics
TOC-2
12422963
Additional Topics
TOC-3
12422963
12422963
Additional Topics
LIST OF FIGURES
LOF-1
12422963
Additional Topics
LOF-2
12422963
Additional Topics
Harmonics
Harmonics are integer multiples of the fundamental frequency. The fundamental
frequency of North American power systems is 60 HZ. The second harmonic is
therefore 120 HZ, the third 180 HZ, etc. A system operator may think all power
system voltages and currents are 60 HZ but in practice the voltage and current are
formed of the fundamental frequency plus various harmonics. Modern power
systems cannot avoid harmonics but utilities strive to control the amounts of
harmonics.
Resonance
A possible result of harmonics is a condition called “resonance”. During
resonance, power system voltages and currents can reach very high magnitudes.
The magnitudes can grow so large that power system equipment, such as
transformers, can be destroyed. This chapter will concentrate on two resonance
phenomena: ferroresonance and subsynchronous resonance.
Geomagnetic Disturbances
Geomagnetic disturbances (GMD) are solar induced disturbances to the earth’s
magnetic field. GMDs can damage power systems by causing low frequency
currents to flow in the grounded neutrals of power system equipment. GMDs are
related to harmonics and resonance in that the low frequency currents may
saturate transformers. A saturated transformer is a source of harmonics. Once
harmonics exist, resonance effects may follow.
9.2 Harmonics
9-1
12422963
Additional Topics
Figure 9-1. The generators must turn at just the right speed, the generator
components such as the stator and rotor must have a specific shape and fit
together perfectly, and the stator and field coils must be located in just the
right positions to produce the 60 HZ voltage and current values expected.
Fundamental Frequency
The ideal 60 HZ wave is called the fundamental wave or the fundamental
component. As illustrated in Figure 9-1 the fundamental wave is a sine wave
that repeats itself 60 times per second. The positive and negative ½ cycles of the
wave are identical.
The electrical equipment used in industrial processes often counts on the
repetitive nature of the fundamental wave. For example, an electronic device may
produce timing signals based on the expected zero crossings of the fundamental
wave. The voltage or current should cross zero every 0.0083 seconds for a 60 HZ
wave. If the wave does not cross zero every ½ cycle or 0.0083 seconds, the
electrical equipment may malfunction.
The power system is not a perfect world and the 60 HZ power system is, in
reality, not composed of pure 60 HZ waves. There are always some additional
frequency components mixed in with the fundamental component. Figure 9-2
illustrates a voltage wave that might occur in a heavily industrialized area. Notice
that the waveform in Figure 9-2 is not a pure sine wave but has jagged edges and
may not cross zero at the expected time. In addition to the fundamental
component, this wave contains frequency components of other than 60 HZ.
These additional components are called the harmonic components.
9-2
12422963
Additional Topics
Fourier Analysis
Methods have been developed to study and quantify the harmonic content of Fourier was a 19th
century
repeating waveforms. These methods, called Fourier analysis, assign harmonic mathematician who
numbers or harmonic orders to the different frequency components. For example, helped develop the
if there is a 120 HZ component mixed in with the fundamental component, this science of frequency
component is called the 2ND harmonic. analysis.
The 2nd title refers to the fact that the component’s frequency is a multiple of two
(x2) of the fundamental frequency of 60 HZ. Harmonic components of any
integer multiple of the fundamental frequency can exist. For example, the 3RD
harmonic (180 HZ) is very common but the 25TH harmonic (1,500 HZ) or the
47TH harmonic (2,820 HZ) may also exist.
Figure 9-3 illustrates the impact of harmonic components on the shape of a
voltage or current wave. Figure 9-3(a) is a perfect 60 HZ fundamental wave.
Figure 9-3(b) is a large 3rd harmonic (180 HZ) component that was somehow
injected into the power system. Figure 9-3(c) is what is actually viewed on an
oscilloscope when the fundamental frequency and the 3RD harmonic are
combined. Notice how the addition of this large 3RD harmonic component
has made the resultant wave assume almost a square wave shape.
9-3
12422963
Additional Topics
TH TH TH TH TH TH RD
Figure 9-4. Sum of Fundamental, 5 , 7 , 11 , 13 , 17 , 19 , 23 , &
TH
25
9-4
12422963
Additional Topics
9-5
12422963
Additional Topics
Transformers
Transformers are a common source of the 2ND harmonic when the transformer is
first energized. When a transformer is energized, a large current in-rush occurs to
magnetize the transformer’s core. This reactive in-rush current will have a high
concentration of 2ND harmonic current. This harmonic content is short lived.
Transformer Transformers are even more important as harmonic sources when they are
saturation was saturated. A transformer can saturate when it is exposed to voltages above its
introduced in design rating. When saturated, a transformer’s magnetic field spreads from the
Chapter 5 and is
further described in central core area of the transformer. The magnetizing current drawn from the
Section 9.6.7. system to support the spread of the magnetic field also grows. The magnetizing
current is very high in harmonics. Saturated transformers are sources of odd
harmonics such as the 3RD, 5TH, etc.
Power Converters
Another common utility source of harmonics is the power converters used to
convert between AC and DC. These converters function by passing only a
portion of the incoming voltage waveform to produce either an AC or DC output.
For example, consider the conversion of an incoming AC voltage to a DC voltage.
The peaks of the incoming phases of the AC voltage positive and negative
waveforms are clipped off via high speed switching equipment to produce
relatively constant positive and negative DC voltages. The AC waveforms that
remain on the AC side of the conversion process are no longer pure 60 HZ waves
but are now combinations of many harmonic components. The harmonics exist
on the AC side due to the selective clipping of the waveform’s peak values.
The harmonic content of the AC side of AC/DC converters has been analyzed and
is well understood. Depending on the type of converter used, the AC side may
have high concentrations of the 5TH, 7TH, 11TH, 13TH, 17TH, 19TH, 23RD, 25TH, etc.
harmonics.
Chapter 10 will
describe the The possible harm that harmonics can cause has not yet been described, but
construction and severe consequences can result. It is best to minimize the amount of harmonics
operation of high
voltage DC (HVDC) if this is possible. HVDC (high voltage DC) converters are always equipped with
systems including filters that are designed to absorb the expected harmonics created in the power
harmonic creation system.
and harmonic
filtering. Thyrister Based Equipment
Thyristers were A type of utility equipment that is often a strong source of harmonics is the class
introduced in of equipment that is controlled via high powered solid-state switches called
Chapter 2 while thyristers. Thyrister based equipment is capable of very rapid switching actions.
SVCs were
described in
Chapter 5.
9-6
12422963
Additional Topics
Figure 9-5 contains a one-line diagram of a static var compensator or SVC. SVCs
are rapidly adjustable sources or sinks of reactive power. SVCs use thyristers to
quickly adjust the reactive power the SVC is taking from or inserting into the
power system.
9-7
12422963
Additional Topics
Î Arc furnaces and arc welders, which have a changing load characteristic
during each ½ cycle. These type loads produces harmonics.
Î Rotating machinery will produce harmonics if the phase coils are not
sufficiently symmetrical. In addition, the machine’s stator iron may
saturate which leads to harmonic production.
Î Industrial static power converters that use thyristers to control the speed
and torque of AC and DC motors. Industrial power converters produce
harmonics in much the same manner that utility HVDC converters
produce harmonics.
Î Electronic equipment powered via switch mode power supplies. Switch
mode power supplies are economical power supplies used in most
modern electronic equipment. This type of load draws current for only a
portion of each ½ cycle thereby producing harmonics. Figure 9-6
illustrates the current waveform for a typical personnel computer (PC).
Figure 9-6(a) illustrates the current the PC draws when energized by a 60
Hz voltage. Note the current only flows for a portion of the voltage
cycle. Figure 9-6(b) illustrates how the PC current wave can be
illustrated as a summation of the fundamental, 3RD and 5TH harmonics.
Note that if a more accurate result was desired more harmonic orders
would be included in the summation (7TH, 9TH, etc).
9-8
12422963
Additional Topics
For example, some portion of IH will flow towards the other customer loads and
the utility system (IH2), while some portion will flow into the shunt capacitor (IH1).
In subsequent sections of this chapter the damage that can be caused by harmonic
currents will be described. The harmonic currents that flow into the capacitor
may cause the capacitor’s protective relays to function while the harmonic
currents that flow into other customer loads or the utility system may result in
thermal damage to equipment.
Rotating Equipment
Rotating equipment such as motors and generators are very susceptible to Section 9.4 will
harmonics. Different order harmonics will have different effects. In general, the describe an extreme
harmonics will induce current flows in areas of the rotating equipment that are not example of this
torque creation
designed for current flow. Overheating could then result. The harmonics can also called SSR or
create torques or forces in the rotating equipment shafts, which may lead to subsynchronous
cracking and eventually failure of the shaft. resonance.
The 5TH and 11TH harmonics are especially important with respect to rotating
equipment. When 3Φ motors are exposed to 5TH or 11TH harmonic voltages a
magnetic field is automatically created that attempts to rotate the motor in its
reverse direction. This reverse torque can damage the motor shaft and cause
thermal damage.
9-9
12422963
Additional Topics
Transformers
Transformers are susceptible to harmonics due to the overheating that may occur.
As the frequency of the harmonic rises, its impact on overheating rises. High
frequency harmonics increase the intensity and spread of the magnetic field and
induce currents in areas that are not designed for currents. These induced currents
lead to overheating. An audible sign of harmonic content in a transformer is the
loud buzzing sound that often accompanies the harmonics.
Transformers may also be exposed to high harmonic overvoltages. These
overvoltages are likely due to a resonance condition developing between the
transformer and a local capacitance. Voltages can rapidly rise to 20 or 30% above
nominal values and lead to saturation with accompanying transformer loss of life
or even internal faults within the transformer.
Shunt Capacitors
As you may recall from Chapter 2, the capacitive reactance, XC, in ohms is equal
1
to: X C = . What is important in this equation is the frequency term in the
2πfC
denominator. The higher the frequency the shunt capacitor is exposed to, the
lower its capacitive reactance (in ohms). Currents with high frequency (high
harmonic orders) are drawn to the grounded shunt capacitors in the system since
the capacitor presents a low impedance path to these currents. This can (and has
often done so) lead to false tripping of capacitor banks when high order
harmonics are present.
For example, certain system conditions (such as geomagnetic storms) may create
an abundance of harmonics. The high frequency harmonics seek out the local
grounded capacitor banks. The capacitor’s protective relaying may falsely
assume the sudden in-rush of current is due to a fault and trip the capacitor.
Individual capacitor cans are often protected with fuses. High harmonic currents
can blow these fuses and lead to tripping of the capacitor bank.
Protective Relaying
Protective relays may misoperate due to harmonic currents and voltages. Both
electro-mechanical and solid-state relays are impacted. Electro-mechanical relays
may respond to the harmonic voltages and current in the same manner that they
respond to the fundamental component. For example, a high harmonic current
magnitude may cause enough disk rotation in an induction disk overcurrent relay
to activate a trip circuit even though a high fundamental fault current does not
exist. Solid-state relays may respond to transient values of voltage and current.
Often the harmonic components are large but short lived. A solid-state relay may
act quickly enough to falsely trip for a very rapid harmonic transient.
Manufacturers have designed versions of solid-state and electro-mechanical relays
to be less susceptible to harmonics. However, not all the relays in the power
system are equipped with these features. One relay that is typically equipped with
9-10
12422963
Additional Topics
Telecommunications Equipment
A common result of harmonics is interference with the local telephone systems.
When harmonic currents and voltages exist they produce electric and magnetic
fields of a like harmonic frequency. These fields can induce voltages and currents
in neighboring telephone equipment. The unwanted fields can easily disrupt
telephone communications causing problems for both the telephone company and
the local telephone system users. Low frequency harmonics (for example the 5TH)
do not significantly impact telephone systems. Higher frequency harmonics (for
example the 25TH) are often troublesome as their frequency of oscillation is within
the audio frequency range that is used by telephone systems.
Proper shielding of telephone equipment and/or filtering of utility power supplies
can reduce the effects of harmonic interference between electric and telephone
systems. However, shielding and filtering are expensive and not used unless
required.
9-11
12422963
Additional Topics
of-phase with one another. In contrast, triplen harmonic voltages and currents are
in-phase with one another. When three in-phase currents flow in a delta
connected winding, the currents are essentially trapped within the delta as
illustrated in Figure 9-8.
Figure 9-8 illustrates an autotransformer with a delta connected tertiary winding.
The delta connected winding will trap the triplen harmonics and prevent them
from impacting the power system. The 3RD harmonic is the major concern since
as the harmonic order increases its impact on the power system generally
diminishes.
The triplen
harmonic currents
add in the neutral of
a wye connected
load. This can lead
to thermal failure of
the neutral wire.
Harmonic Filtering
A simple harmonic filter is illustrated in Figure 9-9. This particular filter is a
series combination of an inductor, capacitor, and resistor. Variations of this filter
can be connected in parallel or in shunt to the power system. The filter will be
tuned to present a low impedance to whatever frequency harmonic the utility
wants to remove from the power system. The tuning can be accomplished by
varying the size of the inductor or capacitor but is normally done by adjusting the
capacitor size.
9-12
12422963
Additional Topics
Remember that
capacitance is
measured in farads
and inductance in
henrys.
9-13
12422963
Additional Topics
Two series filters are illustrated in Figure 9-10. Assume that both filters have a
0.2 Henry (fixed size) inductor. The equation for the resonance frequency that
was given in Figure 9-9 is used to determine the capacitance, C, values required
for each filter. One filter’s “C” value would be chosen to achieve resonance at the
11TH (660 HZ) harmonic and the other filter’s “C” value chosen to achieve
resonance at the 13TH (780 HZ) harmonic. Both calculated “C” values are listed
in Figure 9-10.
Once capacitors with the required “C” values are installed, the filters will be
operational. Now anytime the 11TH or 13TH harmonics appear in this system, the
filters will absorb these currents since the filters present a very low impedance
path to currents of these frequencies. Filters of this type of design are very
common in HVDC converter stations. HVDC converters naturally produce
harmonics so filters are used to absorb the harmonics from the power system
before they can cause any damage.
9.3 Resonance
9-14
12422963
Additional Topics
currents, which may cause thermal damage to system equipment, and to high
voltages, which may saturate transformers and lead to insulation failures.
In more technical terms, electrical resonance occurs when the capacitive reactance Transmission
owners may
of a circuit matches or is tuned to the inductive reactance of the circuit. When the choose to install
capacitive reactance is tuned to the inductive reactance the two reactances will series capacitors
compensate one another. The capacitive reactance is composed of capacitive in their high
circuit elements, which may include line charging and series and shunt capacitors. voltage
The inductive reactance is composed of the inductive circuit elements, which may transmission lines
to increase the
include the line reactance, transformer reactance, and series and shunt reactors. line’s MW
There are two general types of resonance: series resonance and parallel resonance. transfer
capability.
9.3.2 Series Resonance
Figure 9-11 is used to describe series resonance. The figure illustrates a high
voltage transmission line section. The transmission line has inductive reactance,
XL, and resistance, RL. There is also a series capacitor, XC, installed in the line.
Series resonance will occur in the system of Figure 9-11 if, at some specific
frequency, the inductive reactance of the transmission line is fully compensated
by the line’s capacitive reactance or when the magnitude of XL equals XC. At
series resonance the total circuit impedance is reduced to the series resistance or Note that when the
magnitude of XL
RL value. The circuit of Figure 9-11 would present the low resonance impedance equals XC they
(the RL value) to currents near the resonance frequency. Currents of frequencies cancel one
other than the resonance frequency would see a higher impedance. This is an another as they
important point to remember. The resonant condition applies to currents close to are 90° out-of-
the resonant frequency. Currents at other frequencies would see higher circuit phase.
impedance values.
A series resonant condition can be achieved using two possible methods: either
by adjusting the frequency of the system, or by changing the size of the system’s
series capacitance or reactance.
9-15
12422963
Additional Topics
9-16
12422963
Additional Topics
Section 9.2.7 of this chapter described the use of filters to provide low impedance
paths to harmonic currents. These filters were intentional creations of series
resonant conditions. The capacitive and inductive parts of the series filter are
chosen to achieve resonance at whatever harmonic frequency the designer wants
the filter to absorb energy from the power system. For example, the filters
described in Figure 9-10 were designed to absorb currents with 11TH and 13TH
order frequencies. Anytime currents of these frequencies appear in the area of the
filter they are absorbed by the filters and their energy dissipated as heat via the
filter resistance.
9-17
12422963
Additional Topics
9-18
12422963
Additional Topics
A delta connected
tertiary is normally
installed in an
autotransformer to
assist with
harmonic control
and help prevent
resonance
problems.
9-19
12422963
Additional Topics
9-20
12422963
Additional Topics
9-21
12422963
Additional Topics
One of these filters could be tuned to absorb 11TH harmonic current. In an actual
HVDC station the utility would analyze the converter to determine just what
harmonics are created. Individual filters would be tuned to absorb the most
critical harmonic frequencies and then a special type of filter called a high pass or
HP filter would be tuned to absorb all the higher order harmonics.
9.4 Subsynchronous Resonance
9-22
12422963
Additional Topics
The amount of series compensation used is limited by several restrictions. A first The use of series
restriction is that series capacitors cause a voltage rise as inductive (lagging) capacitors also
current passes through the capacitor. This limits the amount of series capacitance complicates
to the tolerable voltage rise at the series capacitor’s physical location. A second power system
protection.
limitation to the use of series capacitors is that the probability of SSR problems
increases with the increasing amount of series capacitance.
This formula tells us that the frequency at which series resonance occurs (fR) is
dependent on the ratio of the series capacitive (XC) and series inductive reactance
(XL). For example, if the series capacitive reactance is 2Ω and the series
inductive reactance is 400Ω,the series resonance frequency can be calculated
from the above formula to be approximately 4.2 HZ.
Normally, the high voltage transmission system is primarily an inductive power
system. The series impedance is primarily composed of inductive reactance (XL).
The ratio of XC to XL is very small so the series resonance frequency is well
below 60 HZ. When the series resonance frequency is this low it normally does
not cause any significant problems. When a utility inserts series capacitors and
increases the series XC value the series resonance frequency will raise. If enough
series capacitors are added to the system to raise the series resonant frequency to a
value in the neighborhood of 10 to 50 HZ, SSR problems can occur.
9-23
12422963
Additional Topics
9-24
12422963
Additional Topics
9-25
12422963
Additional Topics
9-26
12422963
Additional Topics
scenarios. All three scenarios for an SSR occurrence are similar but there are
important differences. The three scenarios are described below.
The 26 HZ stator
currents will induce
34 HZ rotor
currents. This will
excite mode #4 of
the
turbine/generator
shaft.
9-27
12422963
Additional Topics
The forces on the generator shafts do not build up slowly as in SSR Scenario I,
but appear suddenly in direct proportion to the amount of fault current from the
generator. Shaft damage may quickly follow the disturbance. Figure 9-20
illustrates this type of SSR.
9-28
12422963
Additional Topics
Another way of describing the rotor’s amplifier effect is to say that the rotor If a rotor has a
resistance appears negative to the subsynchronous currents. If the negative negative resistance
to subsynchronous
rotor resistance overcomes the positive resistance of the power system to
currents it is
which the generator is attached, the subsynchronous currents will grow larger equivalent to the
and larger until the generator must be tripped. Figure 9-21 summarizes the rotor acting as an
induction generator scenario for SSR. The induction generator effect is amplifier to these
typically not as severe a scenario for SSR as when a shaft’s natural mode is currents.
excited.
RR is the per-phase
rotor resistance.
RS is the per-phase
system resistance.
IS is the per-phase
system current.
9-29
12422963
Additional Topics
If a power system has generating units that are susceptible to SSR, the system
designers should have studied the characteristics of the generators and
transmission system to determine when SSR could occur. Operating guidelines
should then be prepared (in consultation with system operations) to avoid the
conditions that may lead to SSR.
For example, several western utilities have system operating guidelines that forbid
switching of specific high voltage lines when system conditions are within certain
limits. Many utilities with series capacitors limit the amount of series capacitors
or the amount of series compensation, which can be used at a time. This avoids
raising the series resonance frequency to levels that could induce SSR.
The likelihood of SSR occurring is also a function of the loading on the local
turbine/generators. SSR is more likely to occur when generating units are lightly
loaded and their natural damping action reduced.
9-30
12422963
Additional Topics
9-31
12422963
Additional Topics
Filtering devices were eventually installed at the Mojave station to detect the
presence of subsynchronous oscillations and trigger remedial actions. Various
methods of preventing and/or responding to SSR events are briefly described in
the next section.
9-32
12422963
Additional Topics
involves a tuning between the circuit’s capacitance and inductance. However, the
inductance must be of a particular type for ferroresonance to occur, a type called
an “iron-core” inductance. Transformers (both power and instrument) are
common examples of iron-core inductances. An iron-core inductance has the
unique property that its inductance will vary depending on whether its magnetic
field is saturated.
Two scenarios of ferroresonance are examined: one in a distribution system and The concept of
one in a transmission substation. This does not mean that there are only two power system
ferroresonance possibilities. These two ferroresonance scenarios are simply ferroresonance
was first
typical and offer a varied picture of this interesting phenomenon. The section identified in the
describes the cause of ferroresonance for each of the examples given and methods 1920’s.
of avoiding its occurrence.
9-33
12422963
Additional Topics
9-34
12422963
Additional Topics
9-35
12422963
Additional Topics
Figure 9-25 illustrates a 3Φ distribution system. The load is to the right of a wye-
delta transformer. The transformer is fed from the overhead system via an
underground cable. Each phase is individually switched. The dotted lines for
shunt capacitors simulate the cable’s natural capacitance, which is relatively high
in underground cables. Notice how this line charging is in shunt or parallel with
the distribution line. As long as the capacitance is in parallel, ferroresonance is
not a concern.
9-36
12422963
Additional Topics
9-37
12422963
Additional Topics
Figure 9-27. Electrical Circuit With Phases “B” & “C” Closed
9-38
12422963
Additional Topics
While energizing
Î Energize or de-energize the transformer with resistive load attached to a transformer
the secondary winding. The secondary resistive load will appear to be with load
much larger in the primary and damp out any ferroresonance condition attached
that develops. Generally, a resistive load of 10% of the transformer kVA minimizes
ferroresonance,
rating is adequate to prevent sustained ferroresonance. it also exposes
Î Use a grounded-wye winding connection for the primary winding. This the customer to
type of winding offers a parallel path to the line’s natural capacitance for a disturbance.
current flow.
Î Examples of distribution transformer connections which will reduce the
likelihood of ferroresonance occurring are:
— Grounded Wye - Grounded Wye
— Grounded Wye - Wye
— Grounded Vee - Open Delta (2Φ connections)
Figure 9-28 summarizes methods used to avoid ferroresonance in the distribution
system.
9-39
12422963
Additional Topics
9-40
12422963
Additional Topics
9-41
12422963
Additional Topics
9-42
12422963
Additional Topics
9-43
12422963
Additional Topics
Resistance could be added to the actual high voltage circuit. This method could
in theory be used to eliminate ferroresonance but it is not practical. The large
high voltage resistance would be expensive and would likely cause more
problems than it solves including thermal and system stability difficulties. A
better method is to add resistance to a PT secondary circuit.
The resistor need
only be connected in For example, the PT circuits in Figure 9-29 could be equipped with a delta-
the PT secondary connected secondary winding as illustrated in Figure 9-33. A small resistance of
when the last
several ohms would be tied in the delta secondary. This resistance would be
substation breaker
is opened. Control reflected through to the primary based on the square of the turns-ratio of the PT.
schemes are used to This method of reducing the impact of ferroresonance is commonly applied in
switch in the high voltage substations.
resistor only when
needed.
9-44
12422963
Additional Topics
9-45
12422963
Additional Topics
9.6.2 Sunspots
The sun is 93,000,000 miles away from earth. Scientists throughout the world
still do not understand the mechanics of the sun’s operation. Scientists have for
hundreds of years observed sunspots, which appear from earth to be small dark
spots on the surface of the sun. Little is known about these sunspots except that
they indicate areas of intense solar activity.
Sunspots are indicators of several types of energy disturbances on the surface of
the sun. The types of solar disturbances include solar flares (analogous to lighting
storms on the earth) and coronal mass ejections (analogous to hurricanes on the
earth). These disturbances are solar energy storms, which eject charged particles
from the surface of the sun into the surrounding inter-planetary space. After one
to six days a portion of these charged particles will reach the earth’s outer
atmosphere.
9-46
12422963
Additional Topics
9-47
12422963
Additional Topics
9-48
12422963
Additional Topics
9-49
12422963
Additional Topics
Latitude
Positions on the earth are pinpointed with latitude and longitude measurements.
Latitude indicates how far north or south a position is relative to the equator.
GMD activity is typically confined to northern latitudes since these areas are
closest to the electrojets circulating about the north magnetic pole. In general,
Canadian utilities are more impacted by GMDs than U.S. utilities. This is due to
the northern latitudes of Canadian utility service territories.
9-50
12422963
Additional Topics
Earth Resistivity
When large magnitudes of current are circulating about the earth’s surface,
changes occur to the earth’s magnetic field and ESPs are created. The magnitudes
of the ESPs that develop depend on the positions proximity to the north magnetic
pole and on the type of soil contained in the area. Soils with very low resistance
will change their ESP magnitudes very slowly. For example, a large area with a
low resistance soil may only develop an ESP of ½ volt per mile. As long as the
potential difference between two points within an area remains small the
magnitudes of the resulting GICs will remain small. Low resistance soils limit the
size of the ESP and reduce the impact of GMDs.
In contrast, high resistance soils increase the potential differences across the
earth’s surface and lead to increased magnitudes of ESP. The GICs that flow in
high resistance soils are more likely to enter the power system since they see the
power system as a more attractive current path than the high impedance earth.
Many sections of the earth are formed of rock that was the result of long ago
volcanic eruptions. Rock from volcanic origins is called igneous rock. Igneous
rock has a high resistivity. Areas of the earth that contain igneous rock will be
more prone to damaging GMD. Figure 9-39 illustrates those areas of North
America that contain igneous rock.
9-51
12422963
Additional Topics
9-52
12422963
Additional Topics
To conclude this brief description of the geography of GMDs; those areas of the
earth that are most prone to GMD effects are northern areas that contain igneous
rock and are bordered by large water bodies. The northeast coast of North
America fits this description well. This does not mean that only the northeast
coast will experience GMD activity. What this means is that the northeast coast
will be more likely to experience GMD activity than, for example, Iowa or Texas.
GMDs have caused problems in Minnesota even though there is no salt water in
the area. Minnesota is situated in a northern area, the earth in this region is often
igneous rock, and the area contains large bodies of water.
9-53
12422963
Additional Topics
9-54
12422963
Additional Topics
9-55
12422963
Additional Topics
9-56
12422963
Additional Topics
9-57
12422963
Additional Topics
9-58
12422963
Additional Topics
operations. Note that normally the bank uses just a few amperes to excite its
magnetic core. During saturated operations the excitation current rises to a peak
of 300 amperes. Remember this excitation current is primarily a reactive current
so when saturated this transformer uses a large amount of Mvar.
9-59
12422963
Additional Topics
9-60
12422963
Additional Topics
Effects on Generators
Utility generators are normally connected to the power system using
delta/grounded-wye step-up transformers. This type of transformer connection
prevents GICs from entering the generator since there is no ground current path
through a delta connection. However, high levels of GIC in the step-up bank may
cause the transformer to saturate. Severe levels of transformer saturation can
damage the step-up transformer as was experienced at a northeast U.S. nuclear
plant during the intense GMD of March 1989. Saturation will also create
harmonic currents, which can work their way into the generator.
Generators are not designed to carry harmonic currents. The high frequency
currents may create magnetic field components, which spread to areas of the
generator that are not designed for the resulting current flows. Thermal damage
may result. A typical generator protection package will not detect low levels of
harmonic current. The generator could be exposed to these harmonic currents for
long periods of time without any relay protection.
In addition to thermal damage, there are two additional concerns if the generator
step-up transformer saturates and becomes a source of harmonics. When
transformers saturate 2ND and 3RD order harmonic currents are produced. The
generator may enter a condition called supersynchronous resonance. This
condition could result in damaging shaft torques.
The final concern involves a generator’s excitation system. High speed excitation
systems are designed to rapidly detect and correct variations in the generator’s
terminal voltage. A large harmonic current content will lead to harmonic voltage
variations. The voltage regulator/exciter system may falsely respond to harmonic
voltage components. This may lead to fundamental frequency voltage control
problems.
9-61
12422963
Additional Topics
quantities. False relay operation could follow. With high levels of GICs the CTs
themselves may suffer thermal failures.
Protective relays are designed to monitor a quantity such as current and trip if the
quantity maintains a set level for a set period. Protective relays may respond to
harmonic components in a similar manner as they respond to fundamental
components. For example, an electro-mechanical overcurrent relay's induction
disk unit may rotate just enough due to harmonic currents that its contacts close
and a false trip occurs.
The impact of harmonics is more severe on solid-state relays. One of the
advantages of solid-state relays is their rapid response time. Solid-state relays are
fast enough that they may respond to rapidly varying harmonic voltages or
currents and falsely trip. Relay manufacturers have designed relay packages that
are relatively immune or hardened to harmonics. Utilities may choose to utilize
these relays if the possible harm to the system justifies the extra cost.
9-62
12422963
Additional Topics
9-63
12422963
Additional Topics
Note the series capacitors in the neutrals of the two transformers. The reactance
of a capacitor is inversely related to the frequency - the lower the frequency, the
higher the capacitive reactance. The capacitors in Figure 9-46 will block the GIC
flow since the GIC frequency is very low. These capacitors are referred to as
neutral blocking capacitors. Figure 9-47 illustrates possible connections for the
neutral blocking capacitor. The capacitors are placed in series in the neutrals of
the transformers. Neutral blocking capacitors are now installed on several utility
systems with GMD concerns.
There are difficulties associated with neutral blocking capacitor operation. One
reason for grounding transformers is to access a source of ground current during
system faults. The neutral blocking capacitors will reduce this current during
system transients. Also, the high currents associated with system transients could
lead to damaging levels of voltage across the capacitors. A combination of
operating procedures and protective devices may solve the problems with these
capacitors. The capacitors are only switched in when the probability of GICs is
high. The capacitors are also equipped with spark-gaps to short the capacitors out
if the neutral current magnitude is excessive.
9-64
12422963
Additional Topics
compensation. Smaller size series capacitors can be used to block the flow of
GICs in transmission lines. These series capacitors would require small ohmic
values since they are not being used to cancel out the line’s reactance. The series
capacitors present high impedance to low frequency GIC and block its flow
through the transmission line. An eastern U.S. utility has installed series
capacitors for the purpose of blocking GIC.
KP and AP Indices
The U.S. National Oceanic and Atmospheric Administration (NOAA) operates
the Space Weather Prediction Center (SWPC) which distributes several
measurements of solar and GMD activity. Two of these indices, Kp and Ap, are
commonly used by utilities as a measurement of the intensity of GMD activity.
The indices are both based on data gathered from Earth based equipment and data
from orbiting satellites.
Site specific “K”
The Kp index is a three-hour planet (p for planet) wide average of the magnitude and “A” indices
of the earth’s magnetic field. Measurements of Kp are taken at many observation are of more value
points from around the world. The values of Kp can range from 0 to 9. Kp values to individual
toward the low end (0-1-2) indicate little GMD activity while a value from 7 to 9 utilities as the
impact of GMDs
indicates severe GMD activity. (The March 13, 1989, GMD had Kp values varies widely
ranging from 8 to 9.) depending on
location.
The Ap index is a 24 hour planet wide average of GMD activity that is derived
from the same data used to compute the Kp index values. Ap values can range
from 0 to 400. Values toward the low end indicate low levels of GMD activity
during the past 24 hours while values toward the 400 end indicate high levels of
GMD activity during the past 24 hours. (The March 13, 1989, Hydro Quebec
disturbance had an Ap value of 248.)
The SWPC also issues GMD warnings. The GMD warnings are similar to Natural Resources
weather forecasting. The agency tries to predict the occurrence of GMD Canada provides a
similar form (to
activity. Automatic message distribution systems have been setup by SWPC and SWPC) of GMD
NERC to ensure that utilities are notified if a Kp value of 7 or greater is predicted activity notification.
to occur.
Figure 9-48 summarizes NERC guidance on the significance of the K and A
indices. NERC requires that the Reliability Coordinators establish notification
systems so they keep their Transmission Operators and Balancing Authorities
informed of actual and possible GMD activity. These requirements are stated in
the NERC Reliability Standards.
9-65
12422963
Additional Topics
9-66
12422963
Additional Topics
9-67
12422963
Additional Topics
9-68
12422963
Additional Topics
9-69
12422963
Additional Topics
Î Ensure that the power system’s reactive reserves are adequate. Reactive
reserves should be spread throughout the system. Sufficient dynamic
reactive reserve levels are especially important.
Î Ensure your system’s MW reserves are adequate.
Î HVDC converters are susceptible to GMD related outages. HVDC
converters are more likely to avoid GMD related trouble if initially
operating within 40% to 90% of their nominal rating.
Î Keep verbal communication channels open with neighboring utilities.
GMDs are widespread events. Be aware of what your neighbor is
experiencing and let your neighbor know about unusual events in your
system.
9-70
12422963
Additional Topics
9-71
12422963
Additional Topics
9-72
12422963
Additional Topics
9-73
12422963
Additional Topics
9.7.27 Sunspots
Î Sunspots are indications of energy disturbances on the surface of the sun.
Peak years of sunspot activity occur approximately every 11 years.
9-74
12422963
Additional Topics
Î The ESPs lead to the flow of low frequency currents in the earth’s
surface called geomagnetic induced currents or GICs.
9-75
12422963
Additional Topics
A. Odd harmonics
B. Even harmonics
C. High order harmonics
D. Triplen harmonics
2. If the inductance is 0.001 henry and the capacitance is .000782 farad, what
is the resonance frequency?
A. 300 HZ
B. 60 HZ
C. 180 HZ
D. 240 HZ
4. SSR is more of a concern with hydroelectric units than with thermal units.
A. True
B. False
6. The currents that flow in the earth’s surface as a result of solar magnetic
disturbances are called:
A. Electrojets
B. Geomagnetic induced currents
C. Earth surface potentials
D. Sunspot currents
9-76
12422963
Additional Topics
A. Series capacitors
B. Shunt capacitors
C. Transformer delta windings
D. Transformer grounded neutrals
A. 480 HZ
B. 100 HZ
C. 200 HZ
D. 300 HZ
10. Assume a transmission line has a series inductive reactance of 100 ohms
and a series capacitive reactance of 50 ohms. What amount of series
capacitance (in ohms) must be added to create a series resonance
condition?
A. 100
B. 50
C. 25
D. 150
9-77
12422963
Additional Topics
9-78
12422963
Additional Topics
9-79
12422963
12422963
10
EQUIPMENT
12422963
12422963
Equipment
EQUIPMENT
SECTION OVERVIEWS
SO-1
12422963
12422963
Equipment
TABLE OF CONTENTS
TOC-1
12422963
12422963
Equipment
LIST OF FIGURES
LOF-1
12422963
12422963
Equipment
10-1
12422963
Equipment
Certain types of
HVDC converters Î To span long distances (more than 25 to 30 miles) underground or
are heavy users of underwater. High voltage AC cable systems are strong sources of
reactive power but reactive power. A high voltage AC cable may produce 20 to 30 Mvar
the DC transmission per mile. The charging effect of high voltage cable is so large that shunt
does not experience
reactive compensation must be used on long systems or the thermal
any significant
reactive effects. ratings of the cable are exceeded due to just the flow of charging current.
If it is not possible to shunt compensate the AC system then HVDC may
be the best option as HVDC transmission does not produce or absorb
reactive power.
Advantages of HVDC
Some advantages of HVDC systems are summarized in Figure 10-1. Each of
these advantages is briefly explained below the figure.
1. Lower Line Construction Costs
2. Lower Line Losses
3. Ability to Make Asynchronous Interconnections
4. No Power Angle Required
5. EMF Consequences Minimized
6. Complete Control of MW Transfer
7. Use for Long Underground or Submarine Crossings
8. Less Right-of-Way Required
9. Ability to Use HVDC Modulation
10. Possible Tool in Frequency Control Process
11. Possible Tool in Voltage Control Process
12. Fault Isolation Between AC and HVDC Systems
Figure 10-1. Advantages of HVDC Systems
1. HVDC transmission lines are less costly to construct than the equivalent AC
line. (However, the cost of the HVDC converters must be accounted for in
any total cost comparison.)
2. When compared to an AC transmission system with the same power transfer,
the same insulation levels, and over the same size conductors, HVDC
transmission system losses are approximately 33% lower than AC
transmission system losses.
3. HVDC systems can be used to interconnect systems that operate
asynchronously (with different frequencies). A DC interconnection often
allows different systems to share generating capacity and lower power
Generator tripping production costs.
schemes are often
used to reduce the 4. HVDC power transfer does not require a voltage phase angle (δ) across the
AC system impact conducting path. (However, if the HVDC line trips the AC power system may
following an HVDC have to absorb a power swing, which would then lead to an angle increase.)
line trip.
10-2
12422963
Equipment
Disadvantages of HVDC
Some disadvantages of HVDC systems are summarized in Figure 10-2. Each of
these disadvantages is briefly explained below the figure.
1. Inability to Transform Voltages
2. Difficult to Tap HVDC Lines
3. AC is Typically Less Costly for Shorter Lines
4. HVDC Converters are Complex Equipment
5. HVDC Converters are Strong Harmonic Sources
Figure 10-2. Disadvantages of HVDC Systems
1. AC transformers work via the principle of electromagnetic induction. HVDC
systems do not produce alternating magnetic fields and consequently cannot
use conventional transformers. This limits the ability of an HVDC system to
be used to interconnect with the AC system and serve customer load.
2. AC lines are easily tapped while HVDC lines are not easily tapped. The basic
problem is that AC circuit breakers interrupt at a current zero whereas there is
no current zero in a DC current. HVDC circuit breakers are still in the
development stage. While there are multi-terminal HVDC systems, each
10-3
12422963
Equipment
10-4
12422963
Equipment
Monopolar
A monopolar HVDC system uses one conductor (the HVDC transmission line)
energized with a DC voltage and a return path. The return path may be the earth,
the sea, or a metallic conductor. A return path is necessary to complete the
electrical circuit and allow a current to circulate. The equipment that forms an
energized DC conductor (converter and the HVDC transmission line) is called a
“pole”. The converters shown in Figure 10-3 convert between AC and DC.
Bipolar
A bipolar system uses two DC poles. One pole is normally energized with a
positive voltage and the other with a negative voltage. Note that no current flows
in the return path unless a current imbalance exists between the two DC
conductors. The return path may again be the earth, the ocean, or a wire
conductor.
10-5
12422963
Equipment
10-6
12422963
Equipment
An MAV is a large
piece of equipment.
Each MAV may
stand 20 feet high
and be several feet
wide. An HVDC
converter will
include perhaps 14
MAVs.
10-7
12422963
Equipment
Note that the 3. The control grid is used to either turn the valve on (conduct current) or to
control grid is
used to turn a block the valve from conducting. A positive voltage pulse of a few hundred
valve on or block volts is used to turn the valve on while a negative voltage pulse blocks valve
the valve. The conduction. It is important to understand that the control grid cannot be used
control grid is to turn a valve off once it has started conducting. The term “blocking” means
not used to turn to block the valve from conducting current.
the valve off once
the MAV has 4. The MAV will conduct current or “fire” when all of the following are true:
started
conducting. Î An electron stream exists between the cathode spot and the excitation
electrode.
Î The voltage of the anode is more positive than the cathode.
Î A positive voltage pulse is applied to the control grid.
An MAV is simply a high power, controllable switch. The MAV firing control is
accomplished via the gate pulse of voltage.
Other components of the MAV include the voltage divider and the grading
electrodes, which are used to avoid a concentration of voltage near the anode.
The steel tank contains a vacuum in which resides a mercury vapor that is the
conducting medium for the valve current. The upper portion of the valve is made
of porcelain. The operating temperature of an MAV is a critical factor. Extensive
temperature control systems are used to both heat and cool the MAV to ensure
tight operating temperature tolerances are enforced.
MAVs were used in HVDC systems from the mid 1950’s until the early 1970’s.
While some MAVs are still in-service, most modern HVDC converters use solid
state valves called thyristers. Figure 10-7 contains a picture of an MAV.
Figure 10-7 follows on the next page.
10-8
12422963
Equipment
p Thyrister Valves
A thyrister valve is a semiconductor device (similar to a high power transistor) Thyristers were
that has replaced the MAV in modern HVDC converters. The symbol for a introduced in
Chapter 2. This
thyrister valve is illustrated in Figure 10-8. A thyrister conducts current (IA) if the
symbol is used from
anode voltage (VA) is more positive than the cathode voltage (VC) and a gate this point forward to
pulse (IG) of current is applied. refer to any type of
valve.
10-9
12422963
Equipment
Each individual thyrister has a voltage and current rating. Depending on the
voltage and current ratings of the HVDC converter, each valve is composed of
hundreds of thyristers and each converter composed of a dozen valves. A large
HVDC converter therefore contains thousands of thyristers. Each thyrister is
about the size of a hockey puck as illustrated in Figure 10-9.
q HVDC Converters
Several valves (MAV or thyrister) can be combined in an electrical circuit to form
a converter. Our interest in this chapter is in HVDC converters, but converters
can also be used in other processes (for example, adjustable speed motor drives).
Within the converter itself, the valves may be grouped together. A collection of
valves to perform a specific function is called a valve group. A single converter
may be composed of many valves formed into several valve groups.
A valve conducting
solely based on This section begins by describing the operation of a simple converter with a few
their anode to valves and gradually builds to a type of converter used in a typical HVDC system.
cathode voltage is a This section also begins by assuming that no gate/grid control is used. The valves
simplification. The are turned on whenever the anode voltage is more positive than the cathode. This
role of gate/grid is a simplification to ease the learning process. In a later section the role of
control is described
shortly. gate/grid control is explained.
10-10
12422963
Equipment
Single-Phase Converter
A description of HVDC converters begins with the 1Φ converter illustrated in
Figure 10-10. This simple converter accepts an AC input and converts it to a DC
output. The converter’s AC input voltages (V1 and V2) are produced from two
secondary transformer windings and each applied to a valve. Note that these two
voltages are 180° out-of-phase. The two valves (upper and lower) each conduct
when their anodes are more positive than their cathodes.
The output DC
voltage magnitude
is 64% of the peak
value of the
incoming AC
voltage for this
simple converter.
10-11
12422963
Equipment
10-12
12422963
Equipment
Figure 10-13 illustrates the voltage and current waveforms for the converter of
Figure 10-12. The three AC voltage input waveforms are shown at the top of the
figure. Note that when VA is more positive than VB and VC, valve #1 conducts
and current I1 flows. Valve #2 conducts and current I2 flows when VB is highest,
and valve #3 conducts and current I3 flows when VC is highest.
The output DC
voltage magnitude
is 83% of the peak
value of the
incoming AC
voltage for this type
of converter. As the
number of pulses
increases the
conversion from AC
to DC becomes
more effective.
The output DC
current is the
summation of
currents I1, I2, and
I3. Note that a
smoothing reactor
is used to eliminate
the current ripple.
10-13
12422963
Equipment
The output DC
voltage magnitude
is 166% of the peak
value of the
incoming AC
voltage for this type
of converter. The
output DC voltage
is the sum of the
upper and lower
valve group
voltages. The output
voltage for this two-
way converter is
twice the output
voltage of the one-
way converter.
10-14
12422963
Equipment
is the sum of 1/3 cycle (120°) long segments of the positive portions of the input
AC voltages (VA, VB, and VC). The lower valve groups output voltage (VL) is the
sum of 1/3 cycle (120°) long segments of the negative portions of the input AC
voltages (VA, VB, and VC).
The sum of VU and VL is the converters output voltage (VCONVERTER) prior to
smoothing. This voltage is illustrated across the top of Figure 10-15. VCONVERTER
can be viewed as a line-to-line voltage as it is measured between the positive and
negative voltages (VU and VL) of the converter outputs. To illustrate the line-to-
line nature of VCONVERTER note the point labeled “1” in Figure 10-15. The vertical
dashed line through point “1” shows that each 1/6 cycle (60°) segment of the
VCONVERTER voltage labeled VCA is formed by adding the upper valve group
output voltage at the time (+VC) to the lower valve group output voltage at the
time (-VA).
Note that for each cycle of input AC voltage there are six pulses to the converters
output voltage (VCONVERTER). This is a six-pulse converter. Many modern HVDC
systems can operate as six or twelve-pulse converters. (The next section
describes a twelve-pulse converter.)
The current waveforms for the converter are also shown at the bottom of Figure
10-15. There are ten currents illustrated, one for the total output DC current (IDC),
one for each of the six valves (I1 to I6), and the three phase currents being drawn
from the AC source (IA, IB, IC). The total DC current flow is the sum of the six
valve currents. The output DC current is at all times the sum of two valve
currents, one current from the upper valve group and one from the lower valve
group.
10-15
12422963
Equipment
Twelve-Pulse Converter
Harmonics were
Figure 10-16 illustrates two 3Φ/two-way converters connected in series. This
described in configuration is commonly called a twelve-pulse converter. The converter output
Chapter 9. voltages contain 12 pulses for each cycle of the incoming AC voltage. The more
pulses to the converter, the smoother the DC output voltage. An additional
benefit of a higher pulse converter is that the conversion process produces fewer
harmonics.
Versions of the twelve-pulse converter are typically used in HVDC systems. This
converter type can often be operated in six-pulse mode if one of the converter
valve groups is for some reason unavailable.
10-16
12422963
Equipment
Figure 10-17 compares the converter output voltages for six-pulse and twelve-
pulse converters. Note that the twelve-pulse converter has a smoother (less
ripple) output voltage. Figure 10-18 illustrates how the higher pulse number
converters can both produce a smoother DC output and draw more of a sine wave
of current from the AC supply. The current waves drawn from the AC system for
the two six pulse converters add to form a smoother sine wave of current supplied
by the AC power system.
10-17
12422963
Equipment
10-18
12422963
Equipment
r AC Supply Transformers
Transformers supply AC voltage and current to the HVDC converters. The
conversion process requires that the transformers be able to exist in a punishing A common failure
mode in HVDC
operating environment. During the commutation process in which a converter systems is failure of
switches from one valve’s “on” position to the next valve’s “on” position, one the AC supply
winding of the supply transformer is subjected to a short term, phase-to-phase transformers.
fault. The supply transformers also have a DC potential connected to one
winding. These two operating conditions combine to require special designs
for the transformers used to supply HVDC converters.
DC MW flow is controlled by adjusting the converter (inverter and rectifier)
voltages. The supply transformers must have under load tap changing (ULTC)
capability to allow voltage adjustment. The ULTC capability range may be
significantly larger than that encountered in a typical power transformer ULTC.
10-19
12422963
Equipment
t HVDC Filters
A simple way to view the process of converting from AC to DC is to visualize
the converter as clipping only the peak (negative and positive) portions of the
incoming AC voltage waveforms. These peak values are then used to create a DC
voltage. The voltage that is left on the AC side of the converter is no longer a
perfect sine wave but now has a large harmonic content. The designers of HVDC
systems have studied the characteristics of the conversion process and can predict
what harmonics are present in the AC and DC systems.
For a six-pulse converter a mathematical analysis predicts that the dominant AC
harmonics are the 5th (300 HZ) and 7th (420 HZ). The dominant DC harmonic is
the 6th. The 11th, 13th, 23rd, and 25th are also be present on the AC side and the
12th and 24th on the DC side. For a twelve-pulse converter the dominant AC
harmonics are the 11th and 13th while the dominant DC harmonic is the 12th. The
23rd, 25th, 35th, and 37th orders are also be present on the AC side and the 24th and
36th on the DC side. Higher order harmonics are also be present in both types of
converter.
Figure 10-20 lists which harmonics are present in the AC system for both six and
twelve-pulse converters. Theoretical and typical values are listed. The theoretical
column is what a mathematical analysis predicts while the typical column is what
may actually occur in practice. The numbers are stated in percent of the
fundamental (60 HZ) component. For example, for a six pulse converter the
theoretical 5th harmonic content is 20%. The 20% is of the fundamental (60 HZ)
component.
Six Pulse Twelve Pulse
Harmonic
Theoretical Typical Theoretical Typical
th
5 20% 17.5% ----- 2.6%
The harmonic 7th 14.3% 11.1% ----- 1.6%
production of a th
converter also 11 9.1% 4.5% 9.1% 4.5%
varies with the th
13 7.7% 2.9% 7.7% 2.9%
converter design, th
method of 17 5.9% 1.5% ----- 0.2%
operation, and 19 th
5.3% 1.0% ----- 0.1%
loading level. rd
23 4.3% 0.9% 4.3% 0.9%
th
25 4.0% 0.8% 4.0% 0.8%
Figure 10-20. Harmonic Content of HVDC Converters
Every HVDC converter has a substantial filtering network that is designed to
absorb the AC and DC harmonics. The filters on the AC side are designed to
absorb AC harmonics and make the AC sine wave look more like a perfect sine
wave. The filters on the DC side are designed to absorb the DC harmonics and
eliminate as much of the DC ripple as possible.
10-20
12422963
Equipment
u HVDC Electrodes
Most HVDC systems are designed to use either the earth or the ocean as their An HVDC
return path at least during a portion of their operating time. (A wire return path grounding electrode
can also be used.) To ensure a low impedance connection to earth or to the ocean may be composed of
a grounding electrode is used at each converter station. The grounding electrode 50 metallic bars,
each with a 5 inch
is similar to the grounding rods used to ground many types of electrical
diameter, driven 10
equipment, although more substantial to handle the possibly large currents and feet into the ground.
ensure a low impedance path. The grounding electrode also provides a voltage
reference for the converter.
In a bipolar system the return path carries the imbalance current. If there is no
imbalance (each pole current is identical) the return path does not carry any
current. Systems may be designed so that the return path is only used if one of the
DC poles is lost. The system can then continue operating with one pole and the
return path but at a reduced power rating.
10-21
12422963
Equipment
Computer
The SCR is calculated by dividing the AC system’s fault duty by the HVDC
simulation converter’s MW capacity. The AC system’s fault duty is the amount of power
techniques are used (in MVA) that flows to an intentionally placed 3Φ fault at the HVDC system’s
to determine the connecting point to the AC system. The greater the fault duty, the stronger the
SCR. AC system.
If the SCR or the IR (inertial ratio) is less than 2 or 3, the AC system would be
considered a weak system. A common method used to strengthen a weak AC
system is to install synchronous condensers.
10-22
12422963
Equipment
In a six-pulse
converter, the
converter output
voltage is measured
between the
converter’s two
output terminals.
This voltage is
composed of 60°
long segments of the
AC source line-to-
line voltages.
10-23
12422963
Equipment
10-24
12422963
Equipment
Commutation does
not take place until
the gate/grid
control pulse is
applied. Each
successive
commutation is
delayed by the same
number of degrees.
10-25
12422963
Equipment
that the output voltage is measured between the two output terminals of the
converter. A six-pulse converter’s output voltage is composed of 1/6 cycle or 60°
segments of the AC input line-to-line voltages.
10-26
12422963
Equipment
the zero axis line and half below. The average value of the converter output
voltage is therefore zero.
The ignition delay angle’s impact on the DC output voltage magnitude of an
HVDC converter can be stated in terms of this simple equation: This simple
equation is modified
VDC−α = VDC−0 × cosα later to account for
the effects of the
This equation also predicts what happens as the ignition delay angle is raised overlap angle.
above 90° and increased towards 180°. The polarity of the converter output With an ignition
voltage reverses. Figure 10-25 illustrates ignition delay angles of 90°, 120°, 150°, delay angle of 180°
and 180°. Note how the converter output voltage is zero at 90° and then rises to the voltage is at its
its greatest possible negative value at 180°. greatest negative
magnitude but it is
meaningless, as
commutation cannot
take place with this
large a delay angle.
As the ignition delay angle rises above 90°, the polarity of the converter output
voltage reverses. The extinction advance angle (γ) is equal to 180° minus the
ignition delay angle (α).
Ignition delay angles greater than 90° mean that the converter is operating as an
inverter instead of a rectifier. When operating as a rectifier a converter is
transmitting MW from the AC system to the DC system. When operating as an
inverter a converter is transmitting MW from the DC system to the AC system.
10-27
12422963
Equipment
10-28
12422963
Equipment
Commutation between valves during the inversion process is produced by the A strong AC source
voltages of the AC system that the inverter connects to. The extinction advance is important for
angle (γ) is adjusted to control the magnitude of the DC voltage at the inverter both the rectifier
end. Inverters require a strong AC source, as their valve commutation is and the inverter.
However, the
dependent on steady, dependable AC system voltage levels. inverter end is more
subject to operating
p The Effects of Commutation Overlap problems if the AC
source is too weak.
This chapter is intended only as an introduction to HVDC systems. Several of the
more complicated operating characteristics have been either simplified or ignored.
However, one additional concept is very important and is briefly described. This
is the concept of commutation overlap.
When valve commutation occurs, a switch is made between conducting valves.
Current flow is stopped in one valve and started in another. There is a natural
inductance in the electrical circuit in which valve commutation occurs. The
presence of inductance means that a valve’s current cannot be interrupted
instantaneously. In other words it takes time to turn off one valve and turn on
another. The net result is that during the commutation process, an overlap period
occurs in which both valves are conducting. During the overlap period, a phase-
to-phase fault exists for the time period it takes to completely stop the current in
one valve and start it in the next.
The term overlap angle is used to describe the length of the commutation overlap
period. The Greek letter “μ” (mu) symbolizes the overlap angle. A typical
overlap angle would be 15° to 25°. The overlap angle is similar to the ignition
delay angle in that it delays the valve commutation. However, the ignition delay
angle is an intentional angle while the overlap angle is a natural consequence of
inductive switching.
The overlap angle impacts the voltage produced by the converter. The following
equations account for the impact of the overlap angle (μ) on the converter output
voltage:
where:
cosφ=
(
cosα + cos α + μ )
2
These equations tell us that the converter output voltage (VDC-φ) is reduced by
both the ignition delay angle (α) and the overlap angle (μ). The overlap angle is
not controllable but the ignition delay angle is controllable. To control the DC
voltage magnitude, ignition delay angle adjustments are made with full
consideration that the overlap angle exists.
10-29
12422963
Equipment
10-30
12422963
Equipment
Note the approximate symbol (≈) in the above equation for the converter power
factor. A more exact relationship for the power factor of a converter would have
to account for the effects of the overlap angle. A power factor equation that
accounts for the ignition delay angle and the overlap angle is stated below:
cos α + cos ( α + μ )
Converter Power Factor =
2
This equation for the converter power factor tells us that the power factor is
impacted by both the ignition delay angle and the overlap angle. The greater the
ignition delay angle, the lower the power factor and the more converter Mvar
usage. The larger the overlap angle, the lower the power factor. The overlap
angle is dependent on the converter’s MW loading level. It follows that the
converter power factor is also dependent on the converter loading (MW) level. In
general, as the converter approaches its rated power level, it requires more Mvar
from the system.
10-31
12422963
Equipment
The primary devices for controlling the converter voltage magnitudes are the
AC supply transformer ULTCs and the converter ignition delay and extinction
advance angles. The ULTC control is a course control while the angle control is a
fine control. For rapid changes to DC MW flow levels, angle control is used.
Figure 10-27 is a simple illustration of MW flow control in an HVDC system.
MW is flowing from the rectifier end to the inverter end. The rectifier end
voltage level is maintained by adjusting ULTC tap positions and by adjusting the
ignition delay angle (α). The inverter end voltage level is maintained by
adjusting ULTC tap positions and by adjusting the extinction advance angle (γ).
Figure 10-27 follows on the next page.
PSTs were briefly Figure 10-28 illustrates a possible use for a PST. Assume that 530 MW of MW
described in enters a bus with two possible output paths. One path is via a higher impedance
Chapter 3. overhead line while the other is a lower impedance underground line. Assume
that each line has a 300 MW thermal rating. The power flow splits according to
the relative path impedance. In this example 440 MW flows in the underground
and 90 MW in the overhead.
10-32
12422963
Equipment
The underground conductor is overloaded while the overhead conductor has spare
capacity. As a system operator you must reduce the loading on the underground
path. One option is to reduce the total system loading below 530 MW until the
underground path flow is below 300 MW. This is not a good option, as it does
not fully utilize the overhead path.
An alternative (though expensive) option is to install a PST in the underground
cable path. The voltage phase angle difference across the PST could then be
adjusted until the flow on the underground cable is reduced below 300 MW. The
MW removed from the underground path is pushed to a parallel path. In this
example the only parallel path is the overhead line. The use of the PST allows the
system operator to make full use of both the overhead and underground portions
of the power system.
10-33
12422963
Equipment
10-34
12422963
Equipment
10-35
12422963
Equipment
10-36
12422963
Equipment
10-37
12422963
Equipment
10-38
12422963
Equipment
10-39
12422963
Equipment
10-40
12422963
Equipment
Î If we ignore the effects of the overlap angle (μ), the power factor of a
converter is approximately equal to:
Converter Power Factor ≈ cos α
10-41
12422963
Equipment
A. Semipolar
B. Bipolar
C. Unipolar
D. Monopolar
A. Transformers
B. Electrodes
C. Valves
D. Filters
A. Delay inversion
B. Delay commutation
C. Delay conversion
D. Delay rectification
A. series / quadrature
B. series / series
C. quadrature / quadrature
D. quadrature / series
10-42
12422963
Equipment
7. Several HVDC systems are used to electrically connect the Eastern and
Western Interconnections of North America. Since both Interconnections
are 60 HZ systems, why would HVDC be used?
A. True
B. False
A. Reducing DC ripple
B. Reducing DC fault duty
C. Assisting with the commutation process
D. Filtering the AC harmonics
A. 67-100
B. 101-201
C. 400-600
D. 1000 or greater
10-43
12422963
Equipment
10-44
12422963
11
POWER SYSTEM RESTORATION
12422963
12422963
Power System Restoration
SECTION OVERVIEWS
11.1 Introduction to Power System Restoration
An introduction to the theory of power system restoration and the methods used
to restore a power system.
11.2 Voltage Control and System Restoration
An explanation of voltage control theory and practice during power system
restoration.
11.3 Frequency Control and System Restoration
An explanation of frequency control theory and practice during power system
restoration.
11.4 Equipment Issues Related to System Restoration
A description of the unique equipment issues that may be encountered during
power system restoration conditions.
11.5 Protective Relay Issues Related to System Restoration
A description of the unique protective relay issues that may be encountered during
power system restoration conditions.
11.6 Synchronizing and System Restoration
An explanation of the synchronizing issues that may be encountered during power
system restoration conditions.
11.7 Lessons Learned from Actual System Restorations
A summary of lessons learned from restoration events that have occurred in
North American power systems.
SO-1
12422963
12422963
Power System Restoration
TABLE OF CONTENTS
TOC-1
12422963
Power System Restoration
TOC-2
12422963
Power System Restoration
TOC-3
12422963
12422963
Power System Restoration
LIST OF FIGURES
LOF-1
12422963
12422963
Power System Restoration
11-1
12422963
Power System Restoration
Islanded System
An islanded power system occurs when, following a disturbance; pockets of
generation remain operational but isolated from the remainder of the power
system. Typically some portion of the initial customer load is still served in the
isolated, islanded system.
11-2
12422963
Power System Restoration
Angle Instability
Chapter 7 described the issues involved in maintaining angle stability and the
causes of angle instability. (Figure 11-2 illustrates the concept of angle instability
using a phasor diagram to simulate the uncontrolled growth of the voltage phase
angle.) Normally power system angle stability limits are clearly identified and the
appropriate operating procedures are in place to ensure angle stability limits are
not exceeded. However, given a necessary sequence of events angle instability
can occur, resulting in major system disturbances possibly including: generator
tripping, system separation, and system shutdown.
Figure 11-3 contains a plot of the voltage, MW flow, and Mvar flow from the The August 14,
230 kV transmission system that connects Michigan (Detroit area) to Ontario, 2003 outage was the
Canada. This plot indicates that Michigan pulled out-of-step with Ontario on largest loss of load
August 14, 2003. The system lost synchronism only after many high voltage ever in the NERC
power systems.
transmission lines in Ohio and Michigan had first tripped. Note how the MW
flow swings from approximately 3,800 from Ontario to Michigan to 2,000 from
Michigan to Ontario in a one second period from 16:10:39 to 16:10:40.
11-3
12422963
Power System Restoration
The MW transfer equation was first developed in Chapter 3 and was stated as:
VS × VR
PS− R = sin δ S− R
X S− R
Recall that PMAX is
equal to the product This equation tells us that the potential for angle instability increases as
of the voltages
divided by the
impedance increases and system voltages decline. As the quantity PMAX
impedance. decreases, the angle required for a given MW transfer increases.
Unusual system configurations, such as substation bus outages, can increase
system impedance and/or reduce voltages. The outage of transmission lines and
transformers can also increase system impedance and/or reduce voltage. Normal
operating procedures may not ensure angle stability given the occurrence of
maintenance or forced outage conditions.
For a generator to maintain synchronism with the power system, the machine’s
field winding must receive adequate DC excitation current under all operating
conditions. When a generator’s voltage regulator is placed in a manual mode, the
Recall from Chapter ability of the generator to remain angle stable is reduced, especially if a system
8 that a PSS is used fault occurs. Improperly adjusted voltage regulators and the voltage regulator’s
to dampen power associated power system stabilizer (PSS) can also contribute to angle instability.
system oscillations.
Removal of high-speed protection schemes from service results in generator
acceleration for a longer period of time during fault conditions. Likewise removal
of high-speed transmission line reclosing schemes lengthens the time before
system impedance is reduced following a disturbance, increasing the potential for
angle instability. Transmission line synch-check relays may be set so narrowly
that they prevent the prompt reclosing of critical equipment following a system
disturbance thereby increasing the potential for angle instability.
11-4
12422963
Power System Restoration
Equipment Overload
The overload of equipment can result in the equipment’s failure or tripping via
protective relaying. Equipment overloads normally occur when the system is
already stressed as the result of the prior removal from service of key facilities or
during high load conditions. The failure or tripping of overloaded equipment
under stressed system conditions can lead to a power system shutdown.
Switching Errors
The switching process involves the safe and orderly removal or rearrangement of
power system equipment. Most switching is done in the substation. Switching
errors may result in the removal from service of important load serving facilities.
Switching errors can also create system faults (due to the switching process itself
or due to the unintentional grounding of energized equipment) resulting in the
removal of facilities from service by protective relaying. Switching errors can
create overloads on the remaining system equipment.
Cascading Outages
Once an overloaded facility in a system either fails or is removed from service by
protective relaying, the load the facility was initially carrying moves to other
system facilities. As a result of this redistribution of load, other system facilities
may become overloaded. These overloaded facilities may in turn either fail or be
removed from service by protective relaying. This repeated, uncontrolled cycle of
overload and equipment failure/removal from service is called a cascading outage.
When very large disturbances occur cascading failure is usually part of the event.
Generator Overload
Generators that overload may be damaged while in-service or trip due to
protective relaying prior to any damage occurring. When evaluating a generator
overload, both MW and Mvar loading are monitored as both power values
determine the generator’s MVA loading. The potential for generator damage is
increased if operation is at an abnormal frequency (high or low) or at an excessive
voltage. The loss of significant generation under stressed system conditions may
precipitate a system shutdown. In many disturbances the generator’s Mvar
response is the cause of the generator overload. The system needs the Mvar to
support depressed voltages but the generator can be damaged if it exceeds its
MVA limits.
Voltage Instability
Chapter 6 explained
Voltage collapse is a phenomenon that can result in a system shutdown the concept and
and/or system separation, placing the system in a restoration condition. described the
Figure 11-4 reviews the concept of voltage stability from the point of view process of voltage
of maintaining adequate MW and Mvar margins from the possible point of instability.
voltage collapse.
11-5
12422963
Power System Restoration
Natural Phenomena
Power systems are designed to withstand the majority of the anticipated natural
phenomena that occur in a particular area. However, severe natural phenomena
can exceed design standards and system failures and shutdowns sometimes
occur. Some types of natural phenomena are so severe that it would be nearly
impossible⎯and certainly not cost effective⎯to design the system to withstand
such events.
Weather
Severe ice storms are one example of weather having the capability of shutting
down a power system. For example, from January 5 to the 10, 1998 a series
of ice storms hit the northeastern portion of North America. The ice storms
resulted in the accumulation of large amounts of ice on power system equipment
(Figure 11-5 illustrates the ice loading on a transmission line conductor in
Quebec.) and led to the failure of facilities ranging from 765 kV transmission
to low voltage distribution from the weight of the ice.
Although numerous transmission facilities failed, the bulk transmission system
remained largely intact. Customer outages were due primarily to the failure of
distribution facilities.
11-6
12422963
Power System Restoration
Earthquake
A severe earthquake can result in major and widespread damage to power
system facilities. Substation equipment in particular may be severely damaged.
Electromechanical relays may trip facilities falsely due to vibration from the
earthquake. For example, on October 17, 1989 a severe earthquake hit
California’s San Francisco Bay area. This earthquake (magnitude 7.1 on the
Richter scale) resulted in major damage to several key substations and the
immediate trip of a major generating unit.
Substation buses, circuit breakers, and transformer bushings were damaged.
The loss of key facilities resulted in the creation of an island in the San Francisco
area with a large generation to load imbalance. The imbalance caused a rapid
frequency decline. Generation within the island tripped and the island blacked
out within a few minutes.
Service was lost to 1.4 million customers, which amounted to approximately
4,150 MW of load. Service was restored to all but 70,000 customers within
48 hours.
11-7
12422963
Power System Restoration
GMDs
Minor geo-magnetic disturbances (GMDs) occur on a regular basis as was stated
in Chapter 9. Figure 11-6 summarizes the cause of GMDs and their impact on the
power system. The major harm from GMDs results from low frequency GICs
(geomagnetic induced currents) entering the power system via the transformer
grounded neutrals. These currents can be so large that the transformers are
damaged and severe harmonics are produced.
GMDs were
described in Severe GMD events, which can simultaneously affect numerous power systems,
Chapter 9. The have the potential of causing a system shutdown/separation. For example, on
Hydro Quebec
GMD event is also
March 13, 1989, a major GMD event occurred. This GMD created a widespread
presented as an disturbance in North America including the blackout of the Hydro Quebec system
example of GMDs and damage to generator step-up transformers at an eastern U.S. generating
in Chapter 9. station.
The tripping of seven SVCs within the Hydro Quebec system resulted in an
inability to control the transmission system. Transmission lines and generators
tripped resulting in a blackout of the system. Facilities damaged in the system
included transformers, surge arrestors, and a shunt reactor. Three electrical
islands were formed in the course of the disturbance. Power was restored to most
customers over the course of a nine-hour period.
The step-up transformer for a large nuclear unit was damaged from core magnetic
saturation during this GMD. The saturation occurred due to geomagnetic induced
currents (GICs) driving the step-up transformer into half-cycle saturation.
11-8
12422963
Power System Restoration
Fires
Major fires can burn across key power system right-of-ways severing critical
transmission paths. The 500 kV transmission system in California has been
compromised several times in recent years due to grass fires in the right-of-way.
The system may not be able to withstand such an event especially if the situation
develops rapidly.
Sabotage
Intentional damage or the sabotage of power system facilities can result in power
system failures/separations.
Control Systems
The inappropriate operation of system protection and control systems may cause
power system failures and separations. Equipment can trip when it should not
have been removed from service. Equipment that should be automatically
returned to service may not return due to control system failure or inappropriate
design and/or settings. Equipment may not be removed from service as promptly
or effectively as desired. For example, circuit breaker failure protection schemes
may fail to operate.
Right-of-Way Maintenance
A heavily loaded transmission line can sag into trees that have grown too tall
within the line’s right-of-way. The resulting line-to-ground fault trips the
transmission line. This type of event can be very serious as other transmission
elements in the system may be heavily loaded and could be impacted by the
sudden line loss. A cascading outage and partial or total system shutdown is
possible.
For example, two major outages that occurred in the WECC on July 2nd and
August 10th of 1996 can both be traced to insufficient tree trimming practices.
Major lines were lost due to tree contact starting a chain of events during both
disturbances that eventually blacked-out parts of the WECC and caused the entire
Western Interconnection to split into multiple islands.
11.1.3 Overview of Key Technical Restoration Issues
Operation of the power system in restoration conditions differs significantly from
normal system operation. Standard day-to-day operating practices are frequently
incorrect or inappropriate in restoration conditions. There are a number of unique
technical issues that should be considered in the course of restoration. This
section identifies some of the technical issues that warrant special consideration
during restoration conditions.
11-9
12422963
Power System Restoration
Voltage Issues
The energizing of transmission lines and the switching of reactive equipment
under normal system conditions typically produces only modest incremental
changes to system voltages and reactive flows. Under restoration conditions, the
control of system voltages is often a very delicate control process. The switching
of a single element can create a runaway voltage condition, potentially resulting
in equipment damage and system shutdown.
Chapter 5 described
several runaway A runaway voltage condition occurs when available voltage and reactive control
voltage conditions capabilities are fully committed. This control capability deficiency can result in
including self- system voltages and transmission line Mvar production spiraling higher and
excitation of a
higher in a runaway condition. As each new transmission system element is
generator.
Runaway voltage switched in service, on-line generation must be able to absorb the new Mvar
conditions are more produced by the element while simultaneously maintaining voltages within
likely in a acceptable limits. Additionally the ULTC’s that are set in an automatic control
restoration mode may produce unacceptable high side voltage conditions. Voltage control
condition. issues during restoration conditions are further explored in Section 11.2.
Frequency Issues
The frequency in a large interconnected power system is normally very stable.
The tripping of generation and/or switching of customer load in a large
interconnected system usually have only a small impact on system frequency.
In contrast, during restoration conditions the control of frequency can be highly
challenging. With few generating units on-line, the pick-up of load can have a
significant impact on frequency. The load pick-up from the energization of only
a single distribution feeder can result in unacceptable frequency deviations,
potentially resulting in a system shutdown. The tripping of a generator in a
restoration condition may also result in unacceptable frequency and shutdown.
The planning for sufficient operating reserve levels and the recognition of the
dynamic frequency capabilities of available generators must be sufficiently
studied. Frequency control issues during restoration conditions are further
explored in Section 11.3.
Equipment Issues
There are many restoration issues involving power system equipment and the
control systems that support the operation of the power system. Equipment
related restoration problems range from the operation of substation equipment to
control center functions to telecommunication systems. Equipment may have
been damaged due to the initial disturbance or be damaged in the course of the
system shutdown. The loss of station service power immediately effects the
operation of some equipment (for example, the motors for ULTCs may not be
available due to loss of substation station service).
11-10
12422963
Power System Restoration
Angle Stability
Maintaining angle stability is a concern as weak systems are tied together and
generation is delivered to loads via weak transmission paths. During restoration
conditions, generating units are typically leading (absorbing Mvar) which results
in a relatively weak magnetic bound. Generators that are not in automatic voltage
regulator control may further aggravate any potential angle stability problem, as
the generators may not provide adequate voltage support.
On the plus side, in most instances the lower MW flows in the early stages of
restoration tend to keep torque and power angles small. Each system should be
evaluated for its susceptibility to angle stability problems during restoration
conditions and the appropriate operating procedures established.
11-11
12422963
Power System Restoration
Resonance
The lightly loaded power systems that exist during restoration conditions have
high inductive reactance and significant natural capacitance. Large power
transformers must be energized at some point in the early stages of the restoration
process. This combination of factors is favorable for the initiation of a resonant
condition. Each system should be evaluated for its susceptibility to resonance
problems under restoration conditions and appropriate operating procedures
established.
Voltage levels may be very high during restoration conditions. High voltage can
cause power transformers to saturate. Saturated transformers increase the power
system’s harmonic content. High harmonic levels can trigger ferroresonance and
result in tripping or damage to important equipment.
Switching Surges
A power system in restoration conditions is lightly loaded and exposed to the
energization of large power transformers. Under these circumstances switching
surges (rapid increases in voltage and current) can create transient over voltages
(TOVs) that can potentially damage power system equipment. Each system
should be evaluated with respect to switching surges and their impact on system
equipment under restoration conditions. Appropriate operating procedures should
be established for controlling switching surge voltages.
11.1.4 Restoration Planning
The restoration of a power system is not only complex from a technical
perspective; the restoration process is also complex from an organizational
perspective. A restoration process involves the coordinated efforts of a large
number of personnel. The careful planning for a possible restoration condition is
critical to the success of any restoration effort.
Restoration planning has two aspects. The first aspect is the planning that must
Although a correct
restoration strategy be conducted well in advance of an actual restoration condition. The second
for a power system aspect is the real-time fine-tuning of the plan that is necessary for the successful
may appear to be management of a restoration condition.
obvious, careful
evaluation Each power system is unique and each must be studied to determine the best
frequently reveals approach for system restoration. Restoration planning should consider a full
serious deficiencies range of reasonable scenarios. The capabilities and limitations of generating units
in the intended
under restoration conditions must be carefully evaluated. Restoration approaches
restoration plan. It
may be impossible should be analyzed on a step-by-step basis. As each step is evaluated, potential
to implement a problems are considered, and appropriate solutions determined.
planned approach
due to unidentified The advance planning process frequently uncovers problems that would hinder
restoration the restoration. The modification of control systems, reconfiguration of power
problems. system elements, and the addition of new equipment are possible results of
thorough advance restoration planning.
11-12
12422963
Power System Restoration
The restoration plan must coordinate with the restoration plans of other power
systems in the Interconnection. The Reliability Coordinator for the area to be
restored must be knowledgeable of all its member’s systems restoration plans.
Each power system’s operators should be knowledgeable of the restoration plans
of its neighbors and of their Reliability Coordinator.
A well documented restoration plan must be developed for each power system.
This restoration plan should describe alternate approaches for recovery from a
restoration condition. Key attributes of a well designed restoration plan include:
Î An organized approach to the restoration
Î Clear and concise documentation of the restoration strategy
Î Identification of all notification and organizational issues
Î Logistics planning
Î Explanation of key technical issues
Î Detailed plans for the reporting and dissemination of information
Î Methods for the tabulation of key restoration information
System operators must be competent in the application of their system’s
restoration plan. Restoration procedure drills must be conducted to familiarize
system operators with the procedures and to uncover any unexpected problems
associated with the restoration plan. Identified problems must be resolved and
appropriate changes made to the restoration plan.
Power systems and their support equipment and organization are constantly in
flux. Restoration plans must be periodically reviewed and updated to incorporate
necessary changes.
11-13
12422963
Power System Restoration
Assessment
It may seem obvious that a system operator is able to easily identify a system
shutdown condition. However, during an emergency condition the extent of an
outage may not be easily recognized, as the available information may be suspect.
For example, an observation that all power flows and voltages at a particular
substation are zero could easily be perceived as a SCADA problem. System
separations may not be obvious in many instances.
In order to quickly and reliably confirm that a restoration condition exists,
appropriate procedures and SCADA displays must be available for use by the
system operator. These procedures and displays must provide an accurate
evaluation of the restoration condition. Voice communications to selected
generating stations, neighboring power systems, and the appropriate Reliability
Coordinator are typically part of this evaluation process. A system operator needs
to clearly understand the conditions in which a restoration condition exists in their
unique power system.
11-14
12422963
Power System Restoration
Phase 1: Assessment
The first phase of the restoration process consists of a detailed assessment
of the state of the power system. An initial, rapid assessment has already been
completed to determine if a restoration condition exists. The purpose of this
phase is a more detailed assessment to determine an appropriate strategy for the
restoration of the power system. Normally this assessment guides the system
operator in selecting which of the restoration strategies contained in the system
restoration plan is most appropriate under the specific circumstances.
11-15
12422963
Power System Restoration
11-16
12422963
Power System Restoration
- Ensure that the generator has safely shut down. A list of items to
check for each generator should be included in the generator’s
restoration plan.
- Review any generator alarms for relevant information
- Determine if the generator is available for restart
Î For generators with black-start capability:
- Review any generator alarms for relevant information Generating unit
governor control
- Check that the generator is available for restart pressures may
bleed down over
- Start any necessary on-site emergency generation for the time on some
generator’s auxiliary equipment units, making the
unit unavailable
- Prepare the generator for black-start for immediate
Î For generating units that were not in-service: restart.
11-17
12422963
Power System Restoration
Restoration Priorities
Each system must carefully consider its load restoration priorities. Guidelines
pertaining to load restoration priorities should be contained in the restoration plan.
Public and employee safety, health and welfare, and system reliability are obvious
considerations when selecting priority customer loads. Priority customer loads
are often determined in consultation with the appropriate emergency management
organizations. Community impact, contractual obligations, and regulatory
requirements are frequently factored into customer load priority guidelines.
11-18
12422963
Power System Restoration
11-19
12422963
Power System Restoration
Industry guidelines
Higher priority customer loads are energized once system conditions are such that
for power system they can be accommodated. Care must be taken to ensure that in the haste to
restoration restore high priority loads, the energized system is not placed in jeopardy of
recommend that the another shutdown. As the restoration process progresses, additional loads are
load block restored picked up based on their relative priority. As more substations are energized,
during the initial
stages of restoration
larger blocks of load can be safely picked-up by on-line generating units.
be limited to no Frequently a gradual transition occurs from picking up load based on technical
more than 5% of the needs to picking up load based on load priority. (There may be a need to strip
total synchronized some of the load from heavily loaded feeders before they can be restored to
generation. service.) Eventually customer loads are picked up based exclusively on load
priority.
11.2 Voltage Control and System Restoration
Control of system voltage levels and the reactive balance is very important
during a system restoration condition. A restoration conditions power system is
This section builds
extremely sensitive and responds differently then during normal operating
on the voltage conditions. Extreme care must be exercised as system voltage can rapidly move
control material either high or low, well outside of acceptable limits. This section describes
that was presented various issues involved when controlling voltages and maintaining Mvar balance
in Chapter 5. during the restoration process.
11.2.1 Voltage Control as a Local Issue
Recall from Chapter 5 that transmission lines and transformers use Mvar when
current flows through the equipment. This Mvar usage can also be thought of as
Mvar losses. The behavior of the transmission system is such that in order to
maintain an acceptable system voltage profile, Mvar support must be provided
locally to compensate for the Mvar usage of the particular area of the system. The
Mvar usage of transmission lines and transformers is proportional to the square of
the current flow. This means that in a heavily loaded power system, the Mvar
usage can be very high. To support heavily loaded transmission systems,
sufficient Mvar resources must be strategically positioned to respond when
needed.
In restoration conditions, transmission lines and transformers are often initially
loaded at very low levels. The initial voltage control concern is therefore high
voltage. Sufficient Mvar absorption capability must be located close to the areas
where the higher voltages are expected to occur. Under certain circumstances,
equipment that provides a large amount of Mvar (such as long high voltage
11-20
12422963
Power System Restoration
transmission lines) may have its restoration delayed until the system is
strong enough to energize the equipment without losing control of voltage.
11.2.2 Review of Voltage Related Restoration Theory
Chapter 5 described the fundamentals of system voltage and reactive power
control. Several of the topics from Chapter 5 have particular importance in
restoration conditions and are reviewed and expanded in this section.
11-21
12422963
Power System Restoration
An additional concern with Ferranti rise is that the elevated voltages heighten the
potential for ferroresonance and switching surge problems as explained in the
next section.
Review of Resonance
Ferroresonance was During a system restoration condition, the potential for ferroresonance is greatly
described and increased. System voltage can quickly rise, possibly driving a transformer into
illustrated in
Chapter 9.
saturation, which, as was explained in Chapter 9, is a part of the ferroresonance
mechanism.
The initiation of a resonant condition is also possible due to capacitive and
inductive combinations at harmonics of the power system frequency. The
presence of harmonics during transformer energization may trigger this type of
resonance.
In normal conditions, customer load dampens switching surges and harmonics
and reduces the potential for resonance. However, during restoration conditions
there may be little or no load on the system, and hence reduced load damping.
The potential for resonance must be evaluated well ahead of any restoration
events and recommendations for minimizing resonance possibilities included in
the restoration plan.
11-22
12422963
Power System Restoration
exposure eventually breaks down the equipment so that a relatively mild TOV
results in significant damage.
The possibility of equipment damage from TOVs is enhanced if the steady-state
system voltage is high. TOVs are a transient over-voltage that is compounded on
top of the steady-state voltage. If the steady-state voltage is high, applying a TOV
on top of it increases the risk. Some power systems intentionally energize their
system at a lower steady-state voltage (for example, 90% of normal) to reduce the
risks of damage from TOVs.
TOVs are a relatively common problem in power system restoration. A system’s
exposure to TOV related damage during restoration conditions should be
identified and evaluated by conducting a switching surge study of the intended
restoration approach. The system restoration plan should reflect the results of the
switching surge studies and include methods to avoid TOV equipment damage.
11-23
12422963
Power System Restoration
The physical capabilities of a generator limit the extent to which it can control
system voltage without sustaining thermal related damage. Figure 11-11 contains
a reactive capability curve for a 100 MVA generator. In theory, the generator can
operate at various combinations of MW and Mvar loading as long as the MVA of
the combination is within the limits of the capability curve.
11-24
12422963
Power System Restoration
As a generator is operated more deeply into the leading region of its Mvar
capability, a limit is eventually reached beyond which generator stability could be
in jeopardy. Loss-of-field (LOF) protective relays are installed and set to trip the
generator before it enters an unstable operating area.
The generator’s voltage regulator typically includes a minimum excitation limiter
(MEL) or an under-excited reactive ampere limiter (URAL). The MEL or URAL
alarms the operator and possibly blocks movement into a dangerous operating
area. The MEL/URAL is typically set to ensure that the generator does not move
so far into the leading area that the LOF relay operates and trip the unit. The
intended coordination between the MEL/URAL and the LOF protection may not
be adequate under restoration conditions and false tripping of an LOF relay is
possible.
A generator’s automatic voltage regulator is typically designed so that the
generator’s field current is adjusted to keep the Mvar operating point above
the URAL/MEL set point. During normal operating conditions, once the
URAL/MEL limit is reached, the generator automatically stops further movement
into the leading area and maintains the URAL/MEL dictated minimum Mvar
loading. Under normal operating conditions, available system voltage control
equipment and other available generators would assume control of the system
voltage.
Under restoration conditions, there may be one or only a few generators
connected to the system. Under these circumstances the available generators must
absorb all of the new Mvar as transmission facilities are energized. If the Mvar
produced by the newly energized transmission lines exceeds the generator’s
ability to absorb Mvar due to the generator’s URAL/MEL settings, the
URAL/MEL typically starts increasing the generator’s field current.
The increase in field current would normally reduce the amount of Mvar absorbed
by the generator. However, under an islanded situation increasing the field
current further increases the area voltage and increases the Mvar produced by the
transmission system. This forces the generators to absorb more Mvar rather than
less. This series of events can create an out-of-control situation. Eventually the
rising system voltage could cause the generator to trip.
When a generator’s voltage regulator is out-of-service, field current control is
done manually. If field current is reduced too low during manual voltage
regulator control, the generator could trip via its LOF relay, as there would
not be any automatic movement to raise the field current.
11.2.3 Voltage Control in Restoration Conditions
There are three key objectives with respect to voltage control during restoration
conditions:
11-25
12422963
Power System Restoration
11-26
12422963
Power System Restoration
Usage of Generators
Generators are the primary voltage control tool during a restoration condition.
Generators are used to absorb or produce Mvar as the system requires. The
ability of the on-line generators to absorb or produce Mvar must always
exceed the ability of the restored power system to produce or absorb Mvar.
Usage of ULTCs
Although there are many different control strategies, under load tap changing
(ULTC) transformers are typically operated either manually or automatically to
control a low-side voltage magnitude. Under normal operating conditions, the
high-side voltage is typically a stronger source than the low-side voltage. In this
11-27
12422963
Power System Restoration
condition, when tap positions are adjusted, the high-side voltage remains the same
or changes slightly while the low-side voltage of the transformer experiences
most of the voltage change.
Under system restoration conditions, the low-side voltage of the transformer
may be connected to generation and the high-side may be isolated from other
generators or only weakly connected. Under this scenario, changes to tap
positions create little effect on transformer low-side voltages, but have great
impact on the transformer’s high-side voltage. Under these conditions the ULTC
can be used to control high-side system voltage and the generator can be used to
control its Mvar loading and terminal voltage. Coordinating the tap-changer
position and generator voltage adjustment permits a broad range of operating
flexibility with respect to the generator and the power system. Figure 11-12
illustrates the usage of ULTCs in normal and restoration conditions.
Figure 11-12 follows on the next page.
11-28
12422963
Power System Restoration
11-29
12422963
Power System Restoration
11-30
12422963
Power System Restoration
governor settings but rather of the stored energy in the power system, including
the energy stored in the generators’ rotating mass.
Eventually (within a few seconds), the governor response dominates over the
inertial response as the system frequency decays. Assuming there is sufficient
MW reserve capacity, and further assuming that the disturbance is not so severe
that it causes a complete shutdown, the frequency decay is arrested at a certain
point. The lowest frequency dip following a disturbance is referred to as the
“undershoot”. (The undershoot point is labeled “C” in Figure 11-13.) Eventually
the frequency recovers to the stabilization point. The stabilization point is labeled
point “B” in Figure 11-13.
11-31
12422963
Power System Restoration
11-32
12422963
Power System Restoration
When interconnected with other systems, the most restrictive frequency limits for
the entire system should be respected.
The following issues should be addressed⎯in the planning stage⎯when
establishing restoration conditions frequency operating limits:
Î Evaluate possible damage to steam turbine blades
- A typical steam turbine can operate between 59.5 and 60.5 HZ
indefinitely. (Figure 11-14 illustrates typical steam turbine
frequency related operating limits.)
11-33
12422963
Power System Restoration
Î Consider the possible problems that could result from the undesirable
automatic pick-up of load via automatic load restoration schemes
Î Consider the possible problems that could result from the undesirable
shedding of load via automatic under-frequency load shedding (UFLS)
schemes
When establishing restoration conditions frequency limit guidelines, establish
both short term exposure limits (the undershoot area) and longer term (the
stabilization area) limits.
NERC publishes a
Î Frequency should normally be held within a range of 59.75 to 61 HZ with
series of standards an attempt to regulate toward 60 HZ. A system operator may want to hold
(the EOP series) the frequency high (61 HZ) if a large load block is about to be restored.
with requirements The frequency should be kept at least above 59.75 HZ to avoid load
related to power additions activating under-frequency tripping relays.
system restoration.
Î Avoid energizing load blocks that are greater than 5% of the total restored
area’s synchronized generation. This conservative rule is designed to
avoid activating under-frequency relays.
Î If the restored system’s frequency has stabilized below 60 HZ, and the
goal is to raise the frequency back to 60 HZ, shed 6-10% of the connected
system load to raise the frequency 1 HZ.
Î Operating reserve (especially the frequency responsive spinning
component) should be provided to cover the loss of the largest load
carrying generating unit currently in-service.
11-34
12422963
Power System Restoration
Î If the frequency regulation burden is too great for any one generator, two
or more generators should share the frequency regulation. Preferably the
two generators are located at the same generating station to ensure a
coordinated response.
Î In general, the amount of regulating reserve carried in restoration
conditions should be approximately double that carried during normal
operating conditions.
Î Generating units not controlling frequency should be loaded such that the
regulating units remain roughly in the middle of their operating range.
This optimizes the regulating reserve capability.
Î When two or more systems are synchronized together to form a larger
system, only one system should control the frequency. If two systems
attempt to simultaneously regulate the frequency, an undesired
competition could result. In general, one system (the one with the best
responding generation) should control frequency while the other systems
assist when asked for help.
Regional Reliability Councils and/or Reliability Coordinators may also provide
guidance for frequency control during restoration conditions.
11.3.3 Usage of Governors to Control Frequency
Following a large enough frequency disturbance, a generator’s governor attempts The theory and
to adjust its MW output in accordance with the droop setting. Figure 11-15 operation of a
governor control
illustrates the response of a 300 MW generator with a 5% governor droop. When system was described
governors have a % droop setting (greater than 0% droop), no attempt is made by and illustrated in
the governor/generator to recover the frequency. Rather the generator arrests the Chapter 4.
frequency drop. Note that the frequency is arrested at 59.9 HZ in Figure 11-15.
The MW response from a unit due to governor action is not simply a function of
governor droop settings. The generator itself must have the stored energy A once-through type
available to accomplish the governor’s directions. In the case of CT and hydro boiler is a boiler
design in which
units, the MW response can often be delivered within 10 seconds and sustained there is no re-heat
indefinitely. In contrast, the MW response of a steam unit may be delivered cycle. Once
within 10 seconds, but may not be sustained very long beyond the initial through type boilers
10-second response. Depending on the design of the steam unit, very little steam have very little
storage may be maintained so the unit cannot sustain its initial response. steam storage.
Sustaining the MW response from a steam unit is dependent on the unit’s prime
mover design and performance. In the case of once through type boilers,
governor response may be minimal as there is little steam storage in the unit.
Attempts to energize large blocks of load from steam generator sources should be
preceded with a thorough analysis of the impact on frequency and the generator’s
operation. Attempts to rapidly load a steam unit can create dramatic excursions
on the steam side of the operation and result in the unit tripping.
11-35
12422963
Power System Restoration
Droop Control
When generators
compete for a MW When generators are operated in parallel in a power system, each unit should have
change and their a droop setting so the unit shares MW response with other generators in the
MW outputs system. If each generator were attempting to control to a precise frequency value
oscillate it is (using low values of droop), generators tend to compete with the MW response
referred to as a actions of other generators. A generator attempting precise frequency control
“hunting”
condition. may tend to overload, motor, or cause other generators within the restored system
to do the same. Overly sensitive frequency control settings can create instability
and MW oscillations resulting in generator tripping and system shutdown.
The effectiveness of restoration frequency control using normal conditions droop
settings is frequently questioned. Although an argument can be made that droop
settings should be set lower (well below 5%) during restoration conditions to
provide better frequency control, this action may not be easily accomplished. The
changing of generator droop settings is typically a function performed by plant
maintenance personnel and may even require a unit outage to accomplish.
11-36
12422963
Power System Restoration
Consideration should be given to the impact on system stability from any changes
to droop settings. Governor instability using low droop values is an especially
serious issue during light loading conditions. Furthermore, if droop settings are
lowered, the eventual transition to normal operating conditions may present a
difficult problem.
During restoration conditions, frequency must be closely and continuously
monitored. Governor response should be followed up with manual adjustments to
generator loading to ensure acceptable frequency. The system operator in charge
of the restoration process should:
Î Designate the largest, fastest responding unit as the regulating unit within
each island. If more than one generator is required to share the frequency
control burden, it is desirable that all the units are at the same plant
location, under the control of a single plant operator.
Î Utilize operating guidelines, or preferably an automatic calculation tool, to
estimate the frequency dip when picking up new loads or for assessing the
impact of a generator trip.
Î Maintain and distribute operating reserves such that the post-contingency
loading of generators and the frequency level remains within acceptable
limits.
Isochronous Control
Isochronous governor control refers to a governor droop setting of 0%. This
mode of governor operation results in the generator’s governor attempting to
control frequency solely in accordance with the governor’s frequency target
value. When operating in isochronous, the governor attempts to fully recover the
frequency to its target (assume 60 HZ) value. Figure 11-16 illustrates a 300 MW
unit using 0% droop. In theory, the unit operating point slides left and right along
the operating curve in an effort to control frequency to 60 HZ.
The concept of operating a generator governor in isochronous control initially is
very appealing. However, there are several issues that should be considered:
Î Isochronous control is well suited to a single generator serving an isolated
block of load. Under these circumstances, the generator frequency
automatically adjusts as the customer load varies. Isochronous operation
may be an advantage when an isolated block of load is to be served for a
lengthy period, for example, for several days. Generator operators may
install a selector switch in their unit’s control panel so the unit can easily
be switched between isochronous and normal droop modes.
11-37
12422963
Power System Restoration
Auto-Load Control
Generators, especially CTs, are sometimes equipped with an “auto-load” control
feature. Under normal operating conditions, the auto-load feature is used to load
a generator to a target load level (for example, to a minimum value or to a base
value). In normal operating conditions within a large interconnected power
system, the MW levels of other on-line generators are adjusted to accommodate
the MW changes of the auto-load unit.
During restoration conditions, extreme care must be exercised in the use of the
auto-load feature. The auto-load control logic attempts to load the generator to
the desired load level. If the generator is isolated from the power system, the
auto-loading action could result in the frequency being driven either high or low
11-38
12422963
Power System Restoration
as an attempt is made to reach the target MW. If the unit is operating in parallel
with other generators, the auto-load feature shifts the MW load on other on-line
generators, potentially creating undesirable loading conditions in these units.
11.3.4 AGC and System Restoration
AGC (automatic generation control) can be a very effective tool during
restoration, although AGC usage in restoration conditions is substantially
different than normal conditions usage. AGC software is normally designed to
control a defined portion (within the Balancing Authority boundaries) of the
interconnected system. To accomplish the AGC control function, control
parameters are continuously monitored. The control parameters consist of an
actual frequency reading and all tie-line MW flows to neighboring Balancing
Authority areas. These control parameters are selected and normally fixed for the
portion of the system being controlled. A key assumption to the typical AGC
control strategy is that the power system is operating in an interconnected mode.
However, under restoration conditions the restored power system may:
Î Not be fully interconnected
- There may be a single or multiple islands
- There may be a surviving portion or portions of the system
interconnected to adjacent systems while simultaneously one or
more islands exist
Î Not have appropriate frequency indication
- Although AGC systems have multiple frequency sources available,
there is no guarantee that any frequency source can be accessed for
the surviving portions of the system or the various islands that may
form
- The frequency source currently utilized by the AGC software may
not be located within the surviving portions of the system or
islands that exist
For a frequency based AGC system to function correctly the frequency source
must be located within the same boundaries as the generation under control. AGC
systems normally select one of several possible predefined frequency sources.
The system operator must ensure that an appropriate frequency source is utilized,
and remains utilized during the restoration process.
For a tie-line flow based AGC system to function correctly, the tie-line meters
must accurately monitor the MW flow in and out of the controlled area’s
boundaries. However, if a tie-line is not in-service, no AGC control problem
exists as the tie-line’s MW flow is equal to zero and there is no impact on AGC
calculations.
11-39
12422963
Power System Restoration
11-40
12422963
Power System Restoration
11-41
12422963
Power System Restoration
11-42
12422963
Power System Restoration
When large power plant motors are started during a restoration condition, the
ability to maintain adequate voltage levels is a concern. Excessive voltage drop
during large motor starting events can create multiple problems. If the voltage dip
is too large, the newly energized motor may be unable to build to a normal
operating speed. The aborted startup attempt can damage the motor and/or
activate protective devices.
The startup of a large generating station motors may create a generalized low
voltage condition effecting plant auxiliaries and local customer equipment. Other
motors connected to the system may trip. The trip of a critical plant auxiliary may
lead to the trip of generating equipment and a subsequent system shutdown. The
generator restoration plan must ensure that adequate voltage support is available
to start large motors.
11-43
12422963
Power System Restoration
Sectionalizing of Load
In situations where cold load pick-up results in equipment overload, the operation
of over-current relays, or unacceptable frequency deviations, the connected
load must be reduced prior to energizing the feeder. The process of reducing
distribution feeder load is referred to as sectionalizing. Sectionalizing consists
of opening selected switches associated with the feeder in order to reduce the
amount of connected load. This process can be time consuming and frequently
requires manual switching at a number of field locations.
Once a feeder has been energized, the sectionalized load can be gradual returned
to service. The switching associated with this gradual load pick-up can be a time
consuming process.
11-44
12422963
Power System Restoration
11-45
12422963
Power System Restoration
Reserve Distribution
Reserves should be distributed throughout the power system to provide optimal
loading of the reserves in response to potential generator and tie-line trips. When
determining an appropriate distribution of reserves, the following points should be
considered:
Î Reserves should be distributed such that their usage following generator
and tie-line contingencies does not result in the post-contingency overload
of any transmission facilities.
Î Reserves should be distributed such that the frequency dip that follows
a generation loss is effectively managed. Optimal frequency dip
management is achieved when reserves are distributed in proportion to
each generator’s rapid responsive capability. In other words, ensure
enough rapidly responding (within seconds) reserves are distributed
appropriately throughout the restored system.
11-46
12422963
Power System Restoration
11-47
12422963
Power System Restoration
11-48
12422963
Power System Restoration
11-49
12422963
Power System Restoration
Automatic load restoration schemes, those based on frequency, are normally not
appropriate during restoration conditions. The restoration of load during weak
restoration conditions in general should be a system operator function. Automatic
schemes may restore load at the wrong time or in the wrong amount. If a utility
has installed an automatic load restoration scheme, its impact on system
restoration must be examined. If appropriate, a means of de-activating the
scheme should be provided for the system operators’ usage. At a minimum, the
automatic load restoration scheme should be described in the system restoration
plan and any restoration related scheme options fully explained.
11.4 Equipment Issues Related to System Restoration
A variety of equipment related problems could occur during restoration
conditions. Some of these problems exist at the onset of the restoration condition,
while others develop over time. In some instances an initiating event, such as an
earthquake, damages equipment. Equipment may also be damaged in the course
of a system shutdown, for example as the result of a sudden overload.
Equipment issues may start to develop within minutes of the shutdown. For
example, as little as a 15 minute power failure to a generator’s turning-gear can
result in a warped turbine/generator shaft and lead to a several day long forced
outage of the unit. Other equipment issues develop over lengthier periods, such
as over a number of hours or days. For example, the battery system in a
substation normally supplies emergency energy for several hours but eventually
runs down as the energy storage in the battery bank is drained.
11.4.1 Substation Stored Energy
Substations are typically designed so that following the loss of substation station
service AC power; all critical operating functions remain serviceable. Less
critical functions, such as substation control room heating, may be lost when the
AC power failure occurs.
CB tripping and Stored Energy in CB Mechanisms
closing coils
typically consist of CBs use various forms of stored energy to provide mechanical tripping (opening)
an electro-magnet (a power. Compressed springs are often used for tripping power. For example,
solenoid) which,
when energized, when a CB is opened a spring may be automatically compressed. Stored energy
triggers a is now available in this spring for tripping power. The CB’s tripping coil⎯the
mechanical latch coil is the electrical device (an electro-magnet) that releases the stored energy in
allowing the CB to the tripping spring⎯normally receives power from the substation battery or from
either open or close
by releasing some
a charged capacitor device.
form of stored CBs typically use stored energy to close the CB given a loss of AC power. The
energy. The stored
energy is often in a
power to activate the closing coil of a CB is normally provided from the
spring type device. substation batteries. The stored energy that is needed to actually close the CBs
contacts is provided from various sources including: compressed air, springs,
hydraulic mechanisms, and substation battery banks.
11-50
12422963
Power System Restoration
The disconnect switches used in a substation may be motor operated. The power
to operate these motor operated disconnects (MODs) is normally provided from
the substation battery banks.
Battery Maintenance
Battery banks are obviously a key piece of equipment as batteries are used to
power many critical functions. The regular monitoring and maintenance of
battery banks is necessary to ensure that batteries are available when needed. If a
major shutdown occurs, and battery banks are discovered dead, the length and
impact of the outage can be dramatically extended. For example, if a substation’s
battery banks are available, the SCADA system can be used to speed the pace of
system restoration. However, if the battery banks are dead, personnel have to be
sent to the substation to open and/or close CBs manually.
11-51
12422963
Power System Restoration
Î To ensure that the charging system for the substation battery bank is
operational
Î To ensure the charging of the stored energy sources used to open and close
CBs
Î To ensure the operation of lighting systems to provide a safe working
environment for personnel
Î To ensure that substation temperature control systems (heating or cooling)
are operational
Î To ensure the operation of oil pumps used by underground cable systems
Î To ensure the operation of all other critical substation equipment
Every power system restoration strategy should plan for the rapid energization of
a source of station service as each substation is energized.
11.4.2 Pipe-Type Cable Systems
Pipe-type cable systems consist of a metal pipe within which are placed three
oil-impregnated, paper-insulated conductors. The pipe is initially filled with oil
and any remaining air is vented from the cable. Oil is pumped into the cable until
the normal operating pressure of the cable (perhaps 250 PSI) is achieved. The
oil-pressure is constantly monitored to ensure proper operation.
When initially pressurized, it may take several hours to eliminate all of the voids
(air bubbles, vacuum pockets, etc.) in the conductor’s paper insulation and vent
any remaining air from the pipe. This period is commonly referred to as the
pipe’s soaking period. Figure 11-20 illustrates the basic construction of a pipe-
type cable while Figure 11-21 contains a photograph of a section of pipe-type
cable.
The operating pressure of a pipe-type cable system is determined in the design
stage. The cable system must be operated within an acceptable margin of its
design pressure or faults can develop within the cable system.
An important part of a pipe-type cable system is the oil pumping facilities. The
pumping system consists of pumps, regulating valves, and oil reservoirs. The
pumping facility must maintain the oil pressure within the pipe between its high
and low limits. SCADA alarms are often installed to provide warning if the oil
pressure is outside of acceptable operating limits. The oil pumping facility is
typically located at one (or both) of the terminals of the cable system.
11-52
12422963
Power System Restoration
11-53
12422963
Power System Restoration
within the pipe. If the current flow on the cable drops, the cable temperature
drops and so does the oil pressure within the pipe. When the oil pressure reaches
its low operating limit, an oil pump automatically starts and pumps oil from the
storage reservoir into the pipe, raising the oil pressure within the pipe. This
continuous process keeps oil pressure within the operating limits of the cable
Some pipe-type system.
cable systems allow
a reduced cable If the pipe-type cable pressure drops below a minimum level, the cable must be
pressure mode of de-energized. De-energizing is necessary because voids and bubbles can develop
operation for in the paper insulation that surrounds the cable conductors resulting in a cable
maintenance and
leakage control
fault. The cable must now be soaked until pressure is again within acceptable
purposes. This limits. Once oil pressure is acceptable, the cable can be re-energized.
reduced oil pressure
mode of operation is Special Procedures Following Loss of Oil Pressure
normally not
sufficient to permit During restoration conditions, AC oil pumping power is often lost. Once a
the cable to be system shutdown occurs, pipe-type cables start cooling and oil pressure drops.
energized. The more heavily loaded a cable is prior to shutdown, the higher the cable’s
operating temperature and the greater the reduction in temperature as the cable
cools toward ambient conditions. The greater the temperature drop, the greater
the resulting pressure drop. In other words, a cable with little load current is
already operating near ambient temperature and does not experience a large
pressure drop. Conversely, a heavily loaded cable experiences a large drop in
temperature and oil pressure when a shutdown occurs.
11.4.3 Lightning Arresters
Zinc-oxide lightning arresters may operate when switching surges initiate
sufficient magnitude and duration TOV events. Under normal operating
conditions, most TOV events are quickly damped by system load. However,
during restoration conditions, TOVs are numerous and not well damped.
When a TOV event occurs, zinc-oxide arresters may allow some current flow
through the arrester to ground. This current flow results in arrester heating. The
arrester can only withstand a certain heating level, beyond which the arrester is
subject to thermal failure.
During a restoration condition there are several reasons why zinc-oxide arresters
are subjected to greater than normal duty including:
Î There is a greater potential for elevated system voltage. High voltage
increases the potential for TOV events and also increases the severity of
the TOV event.
Î Restoration conditions always include multiple switching surges as
equipment is energized. Each switching surge potentially creates a TOV.
Î TOV events persist for longer periods as restoration conditions provide
poor damping to the TOVs
11-54
12422963
Power System Restoration
Each power system’s exposure to TOVs and the allowable duty (limits of high
voltage exposure) of zinc-oxide arresters should be studied. Suitable guidelines
should be incorporated into the restoration plan to avoid arrester failure during the
restoration process.
11.4.4 Transformers
Transformer energization may cause several restoration conditions operating
problems including:
Î High in-rush currents that lead to large switching surges
Î An increased potential for resonance
Î An increased possibility of voltage control problems
Energizing Transformers
The composition of
The process of energizing a large power transformer creates a substantial operating reserves
includes responsive
disturbance in a weak power system. Ideally, no transformer is energized until
and non-responsive
the restored power system is strong enough to absorb the energization shock. elements. The
Unfortunately, in many instances of restoration, the energization of a transformer responsive elements
cannot wait and the transformer must be energized from a weak system. For are critical during
example, once a black-start generator is on-line, the generator’s step-up restoration conditions
as the large inertial
transformer (GSU) must be energized. Once the GSU is energized, several
response of a normal
relatively large power transformers⎯large when compared to the size of the conditions power
generator⎯are typically energized before any load can be restored. system is not available.
11-55
12422963
Power System Restoration
Transient Over-Voltages
Steady-state voltage is often high during the early stages of restoration. The
major cause of the high voltage is the abundance of Mvar from energizing
transmission lines. Ferranti raise and improper transformer tap settings may also
contribute to the high voltage condition. Voltage levels at various locations in the
system may be close to maximum acceptable levels.
When a transformer is energized, a switching surge is created. The magnitude of
the switching surge is dependent upon the point in the voltage wave at which the
switching device (CB, etc.) used for energization actually closes. Once created, a
switching surge voltage wave reflects back and forth throughout the restored
power system until it is damped by system load and resistive losses.
The magnitude of the resulting voltage is a combination of the switching surge
magnitude and the steady-state system operating voltage. The switching surge
voltage transient combines with⎯and rides upon⎯the 60 HZ steady-state power
system voltage. The combined voltage contains a base steady-state value with
switching surge frequency oscillations added above and below the steady-state
value. The peak voltage of the combined waveform can rise high enough to be
considered a TOV event. Reducing the initial steady-state operating voltage
(for example, to 90% of nominal), reduces the magnitude of the combined
waveform and reduces the impact of the TOV event.
Resonance Phenomena
Weak, lightly loaded power systems⎯typical in the early stages of system
restoration⎯are more susceptible to resonant conditions than normal conditions
power systems. The dampening effects of a tightly interconnected system and its
connected load are highly effective in reducing the potential for a resonant
condition. During the early stages of restoration, the initial elements energized
11-56
12422963
Power System Restoration
11-57
12422963
Power System Restoration
11-58
12422963
Power System Restoration
CB Control Circuitry
The design of a CBs control circuitry can interfere with the CBs switching during
restoration conditions. The DC power used for initiating CB tripping is typically
drawn from the station battery bank. As long as the station’s battery remains
charged, CBs can typically be opened electrically either from the substation’s
control panel or via SCADA.
The designs used in CB closing circuits vary. Substation CB closing is typically
initiated using DC power from the substation batteries. CB closing may only
require a DC power source. However, the CB closing sequence may utilize more
selective control circuitry. For example, the control circuitry may require both a
DC power source and the satisfaction of certain permissives for the CB to close.
For example, a CB may not close if the substation bus to which the CB is
connected is de-energized. The permissive in this case is the required
energization of the substation bus.
Figure 11-25 contains a simple CB control circuitry schematic that illustrates the
usage of a substation bus energized permissive. The battery provides the 120 volt
DC power. The DC power is provided to the CBs close coil only if the two
contacts between the close coil and the battery are closed. Contact “A” closes
when the CB close button is pressed. Contact “B” closes if the bus to which the
CB is connected to is energized. Once both contacts are closed, the close coil is
energized and a command is sent to the CB to close. If the CB has enough
mechanical energy to close it rapidly closes its contacts.
11-59
12422963
Power System Restoration
11-60
12422963
Power System Restoration
11-61
12422963
Power System Restoration
RTU Communications
EMS is a very broad Generating stations and substations are often equipped with a remote terminal unit
term. The EMS (RTU). The RTU is an electronic device that acts as an interface between a
includes both the company’s energy management system (EMS) and their various generators and
SCADA and AGC
substations. If a substation or generator RTU loses power, the utility loses both
systems.
indication and remote control of the facility. The communications between
RTUs and the control center’s EMS are vitally important during a restoration
condition and the continued availability of RTU telecommunications should be
addressed in the restoration plan.
11.4.7 Generators and Power System Restoration
Generation related restoration issues are examined in a general manner in this
section. Each generating unit is unique and each must be studied to determine its
restoration related strengths and weaknesses.
11-62
12422963
Power System Restoration
11-63
12422963
Power System Restoration
DC power from the station’s battery banks. The emergency lube-oil pumps are
designed to ensure adequate bearing oil pressure in shutdown conditions. The
availability of emergency lube-oil pumps and the DC power to drive the pumps
are critical in system restoration conditions.
11-64
12422963
Power System Restoration
11-65
12422963
Power System Restoration
When activated, a
generator’s UF
protective relays
The frequency and time of exposure limits for each generator’s operation should
may alarm the be documented in the restoration plan. The documentation should include the
operator and/or trip generator abnormal frequency limits and also the settings on any under and
the unit. System over-frequency relays that are used to protect the generator.
operators must be
aware of their
generator UF relay
Concerns with Black-Start Capable Units
settings. Black-start capable generating units have the capability of starting when the
power system that the generator normally connects to is shutdown. Even though a
generator may be classified as black-start capable, there are a number of issues
that can interfere with the black-start process. If any of the following issues are
applicable to a particular system, the issues should be documented in the
appropriate restoration plan.
11-66
12422963
Power System Restoration
11-67
12422963
Power System Restoration
11-68
12422963
Power System Restoration
11-69
12422963
Power System Restoration
Control Centers
Emergency generators are normally provided at control center locations. The
emergency generator provide power to all elements necessary for the operation of
the control center during restoration conditions. Computers, lighting, and
telecommunications equipment are obvious high priority loads. The importance
of other types of equipment may not be so obvious. For example, cooling power
for computers and inverter equipment may be critical to prevent thermal
overloads. Sewage and storm water pumps may also be critical to control center
operations at certain locations.
The emergency power supply must be designed to restore full functionality to
critical equipment. For example, in one actual case, power was provided so that
all telephones worked in the control center, but the indicator lights on the
telephones were not powered. When a call was made to the control center, with
no line indicators working, it was a matter of chance to determine which line to
answer.
Black-Start Units
Black-start capable generators often use an emergency generator to provide power
to critical unit loads. The emergency generator is the feature that makes the unit
black-start capable. The types of critical auxiliary loads vary from unit to unit.
Typical uses for a black-start unit emergency generator include:
Î Turning gear motors
Î Large motor cranking power
Î Battery bank charging
Î Oil and air control pressure
Î Fuel-forwarding pumps
Î Emergency lighting systems
Î Lift-oil pumps
Substations
Important substations may be provided with an emergency generator to power
critical station service loads during restoration conditions. The natures of the
critical loads vary depending upon the substation. Typical substation critical
loads include:
Î Battery bank charging
11-70
12422963
Power System Restoration
11-71
12422963
Power System Restoration
11-72
12422963
Power System Restoration
O/S is the
symbol for
out-of-service.
The O/S
elements have
not yet been
restored.
Under-Frequency Protection
UFLS relays are used to shed system load in coordinated steps when system
frequency falls below acceptable levels. Figure 11-28 illustrates the operation of
a UFLS scheme that sheds 30% of the total customer load in three 10% steps at
59.3 HZ, 59.0 HZ, and 58.7 HZ. Notice how each step in the UFLS scheme
operation brings the system closer to a match between generation and load and
slows the decline in frequency. The system frequency is finally arrested at 58.8
HZ and the system operators can now bring the system gradually back to 60 HZ.
11-73
12422963
Power System Restoration
The designers of UFLS schemes normally assume that most of the normal system
load is in-service at the beginning of an under-frequency load shedding event.
The timing, frequency set-point for tripping, and the size (MW) of the load blocks
tripped are selected to arrest the under-frequency condition at an acceptable point.
The system operators involved can then coordinate the restoration of system
frequency.
In some power systems, the load shed by UFLS operation is automatically
restored once system frequency recovers above a pre-set level. The intent
of these automatic load restoration schemes is typically to avoid over-frequency
conditions from excessive load shedding and also to restore system load in a more
coordinated manner. Automatic load restoration schemes may also be applicable
in substations that do not have SCADA control capability.
As described earlier in this chapter, UF relays are often used to trip generating
units. The UF relays are designed to protect the generator turbines from a
prolonged exposure to low frequency conditions.
UF relays are sometimes applied in the transmission system. These UF relays are
designed to separate a portion of the power system when system frequency drops
below a specified level for a specified period of time. Transmission UF relays
trip the appropriate CBs to intentionally create an islanded system that hopefully
contains enough generation capability to support the island’s frequency.
11-74
12422963
Power System Restoration
11-75
12422963
Power System Restoration
11-76
12422963
Power System Restoration
Until one set of the conditions stated above is satisfied, the CB does not close.
For example, if the substation bus is energized and the transmission line is
de-energized, the CB does not close.
Figure 11-29 illustrates the control logic described above on a CB logic diagram.
CB #1 control logic is illustrated. Note that there are two control logic paths to
the closing coil for CB #1. If either path is satisfied, the proper DC switches are
closed and the DC battery bank energizes the CB closing coil.
Each proposed restoration strategy should be studied ahead of time and any
control logic problems identified. For example, the developers of a restoration
plan may want to use a generator to initially energize a small portion of the
system. However, the generator’s control circuitry may intentionally prevent the
closing of its main CB if the external system is de-energized. For example, the
generator’s control circuitry may:
Î Permit the closing of the main CB if the system and the generating station
are both energized and in synchronism with each other
11-77
12422963
Power System Restoration
Î Permit the closing of the main CB if the system is energized and the
generating station is de-energized
Î Block the closing of the main CB when the generating station is energized
and the system is de-energized
The modern control circuitry used in power system’s generators and substations is
gradually growing more complex. Frequently microprocessor and computer
systems are incorporated into the DC control logic. A thorough understanding of
all DC control system logic is a must when developing restoration strategies.
Transformer Protection
This section addresses transformer protection related issues that may have an
impact during restoration conditions.
Volts-per-Hertz Protection
Transformers can be damaged from over-excitation. Over-excitation is due to a
combination of high voltage and low frequency. Unfortunately, both conditions
(high voltage and low frequency) are increasingly likely during restoration
conditions. Volts-per-hertz relays are designed to detect over-excitation and
alarm or trip. Volts-per-hertz relays are more likely to operate in restoration
conditions.
11-78
12422963
Power System Restoration
Directional Relays
Directional relays (for example, impedance relays and directional over-current
relays) are sometimes installed on the low side of transformers. Directional relays
frequently require a polarizing source. The polarizing source is what makes the
relay directional. Polarizing sources are often drawn from substation PT circuits.
In a restoration condition, when a substation is in the process of re-energization,
the appropriate PTs may not be initially energized. Directional relays may then
falsely operate. Polarizing source issues should be identified and appropriate
solutions documented in the restoration plan.
11.5.3 Transmission Line Protection
This section addresses transmission line protective relay issues that may have an
impact during restoration conditions.
11-79
12422963
Power System Restoration
fault detector (#50). The series insertion of the fault detector in the control
circuitry ensures the distance relay does not activate for low voltage conditions
only, the current flow must also be high.
Not all distance relays have fault detectors. If fault detectors are not used, it is
essential that the distance relay’s voltage input is available at all times to avoid
false trips.
Even if a fault detector is used, problems can still surface. The current (amp)
setting of the fault detector may be greater or less than the normal full load
current of the protected line. The current setting of a fault detector is often a
difficult compromise between setting the value high enough to avoid false trips
and setting the value low enough so the protected line trips given the minimum
anticipated fault current level.
11-80
12422963
Power System Restoration
occurs. In a typical distance relay scheme, the failure of the fault detector to
activate prevents CB tripping. For example, if a lightning arrester was to fail in a
substation (which could easily occur during restoration conditions switching), the
fault may be detected very slowly or not detected at all. Delayed or backup
clearing of the fault could jeopardize the restoration effort and contribute to
equipment damage.
A restoration strategy should be evaluated from a distance relay performance
perspective. If fault detector activation during fault conditions is a problem due to
low levels of available fault current consideration should be given to:
Î Decreasing the fault detector current settings
Î Increasing the available fault current by starting additional generators
- Fault current levels may not increase markedly with the starting of
additional generators, depending upon the system configuration.
Short-circuit computer simulations should be completed to
determine the anticipated fault currents in restoration conditions.
Î Changing the switching step sequence to increase fault current levels
- Changing the switching step sequence could decrease the system
impedance, which may raise fault current levels.
Î Installing control schemes which by-pass selected fault detectors or place
more sensitive fault detectors in-service in restoration conditions.
Over-Current Relays
Two major issues associated with transmission line over-current relay operation
during a restoration condition are addressed in this section.
11-81
12422963
Power System Restoration
over-current relays and clear the faults that were not detected by the over-current
relays.
The switching steps in the system restoration plan should be evaluated to ensure
that adequate protection is maintained on energized transmission lines and
distribution feeders. Transmission lines and feeders that use over-current
protection should not be energized until adequate levels of fault current are
available to permit proper operation of the relays. In addition, distribution feeders
that use fuse protection may not clear properly due to a lack of fault current.
Reclosing Relays
Reclosing relays are routinely used in transmission and distribution systems.
Reclosing relays automatically reclose CBs following specific types of tripping
events. Automatic CB reclosing can produce disastrous results in restoration
conditions.
For example, a transmission substation may be totally de-energized with several
transmission line CBs open. When a power source is energized into the
substation, the reclosing relays on the transmission CBs may operate, suddenly
picking up many miles of transmission line (and the associated Mvar) and a large
amount of load. This automatic reclosing could drive voltage so high and
frequency so low that the system collapses.
11-82
12422963
Power System Restoration
system restoration⎯ cause voltage phase angles to grow so rapidly that OOS
relays activate collapsing the weak power system.
If several islands have formed as a result of restoration conditions, a decision
must be made where and when to tie the islands together. If the islands are
synchronized with a large frequency difference, a large power angle, or a large
voltage magnitude difference, a large power swing can occur. If the transmission
system has OOS relays installed, the relays may activate and cause transmission
line tripping.
Not every power system installs OOS protective relays. If a system has installed
OOS relays, any issues related to the OOS relay operation in restoration
conditions should be documented in the restoration plan.
11.5.4 Generator Relays
This section addresses generator protective relay issues that may have an impact
during restoration conditions.
Under-Excitation Protection
On-line generators are often used to absorb any excess Mvar in the power system.
During the early stages of a system restoration, Mvar load and transmission
system Mvar usage are very low. The difference between the Mvar used by the
system and loads and the Mvar supplied by the energized transmission lines must
often be absorbed by only a few on-line generators.
Generators are equipped with several features that prevent the generator from
absorbing excessive amounts of Mvar. The voltage regulator may have a URAL
(under-excited reactive ampere limit) or a MEL (minimum excitation limiter) that
limits the amount of Mvar absorbed to safe levels. In addition, the generator
operator may install protective relays (loss-of-field or LOF) that operate and
either alarm or trip the generator if the Mvar absorbed rises above a pre-set level.
If the Mvar that a generator is forced to absorb exceeds the generator’s voltage
regulator controls and/or protective relay settings, the generator may trip or the
Mvar absorbed may suddenly reduce. The exact action taken depends on the
particular generator’s control systems and protective relay settings.
11-83
12422963
Power System Restoration
The inductive reactance (XL) of each of the three phases of a transmission line is a
function of that phase’s magnetic field strength. The magnetic field surrounding
each of the three phases of a horizontally constructed line is different than the
magnetic field of the other two phases. The three fields are different because the
fields interact with one another as a function of their tower positions relative to
one another. For example, the magnetic field surrounding the center phase on the
support tower is impacted strongly by the two end-position phases. However, the
magnetic field of an end-phase has little impact on the magnetic field of the other
end-phase because the phases are physically so far apart.
The result of the differences in the phase conductor magnetic fields is different
impedances (XL) in the three phases. When transmission line phases are
transposed, the position of each phase on its support tower is periodically
switched with a different phase. Ideally, each phase occupies the same tower
position an equal amount of time along the entire length of the line.
Some transmission
lines use delta The impedance of each phase of a horizontal construction transmission line is
phase different than the other two phase impedances unless the phases are transposed. If
arrangements.
These phase transposition is used, an approximate match can be obtained
impedances are
balanced.
11-84
12422963
Power System Restoration
between the three phase impedances. A transmission line does not have to be
transposed at every structure. For example, a 100 mile long line may be
transposed once to get the necessary impedance match.
If transposition is not used, and the phase impedances are different, the current
magnitudes in the three phases are different. When the three phase currents are
not the same magnitude, the phases are said to be imbalanced. Imbalanced phase
currents can damage rotating equipment. Generators and large motors are often
equipped with negative sequence relays. A negative sequence relay is designed to
detect imbalance conditions and either alarms the operator or trips the machine
(motor or generator).
Phase imbalance issues are especially important when high voltage transmission
lines are used. High voltage transmission (for example, 345 kV, 500 kV, and 765
kV) is often used to move power from generating units to far-off load centers. A
phase imbalance in the transmission system that connects to the generator can
result in imbalance currents in the generator and severe damage to the unit.
Volts-Per-Hertz Relays
Generators can be damaged due to over-excitation in a similar manner as
transformers. Over-excitation results in the heating of the generator’s stator core
and can cause permanent damage to the generator.
Over-excitation is a function of both high voltage and low frequency. A generator
is in a unique position in that both high voltage and low frequency are
simultaneously possible, especially during restoration conditions. Generators are
often protected with volts-per-hertz relays in recognition of the high probability
that over-excitation can occur.
11-85
12422963
Power System Restoration
generation but in a large interconnection the frequency rise may not even be
noticed.
In restoration conditions, the operating situation is substantially different. There
may be only a few generators on-line. Load and generation must be in balance at
all times or large frequency deviations rapidly develop.
Frequency levels can rise rapidly if a customer load suddenly trips or a generator
is synchronized and starts adding MW faster than other on-line units are backed
down. An on-line generator’s MW output may be backed-off so rapidly that the
unit becomes a motor. For example, assume generator “A” is initially lightly
loaded and has a fully operational governor control system. Assume a new
generator (“B”) is synchronized and rapidly loaded. The generator “A” governor
reacts and reduces the unit’s MW output until the unit is actually absorbing MW.
Generator “A” is now a motor.
Some generator’s can motor with no adverse effects. For example, hydro units
can often motor. The hydro unit is said to be condensing when it is absorbing
MW. However, most steam units cannot motor as the steam turbine may be
damaged if motoring occurs. Most steam units are protected with reverse-power
or anti-motoring relays that alarm the operator or trip the unit if motoring occurs.
Synch-Check Relays
Synch-check relays are often installed in high-voltage substations to block the
closing of transmission line CBs when the power angle across the CB exceeds a
set value. Most synch-check relays also incorporate features that block CB
closing if the frequency difference or voltage magnitude difference across the CB
exceeds set values.
During restoration conditions, generation levels are low and the system
impedance is high. Large standing power angles can develop across open CBs.
For example, Figure 11-32 illustrates a weak islanded power system. Only a few
transmission lines and two generators are in-service. A large power angle (45°) is
measured at open CB #1 and the synch-check relay installed at CB #1 does not
allow the CB to close due to its 40° setting. The system operator must either
reduce the magnitude of the power angle to below 40°, or reduce the angle setting
on CB #1’s synch-check relay to above 45° in order to close the CB. The next
section of this chapter examines the issue of synchronizing during restoration
conditions.
11-86
12422963
Power System Restoration
11-87
12422963
Power System Restoration
Synchroscope
A synchroscope panel contains equipment to monitor the three synchronizing
variables. A synch-panel contains a synchroscope and two voltage meters.
Figure 11-33 is an illustration of a synch-panel. The synchroscope connects to
voltage inputs from the two sides of an open CB. If the voltage sine waves
are at the same frequency, the synchroscope does not rotate. If the voltage sine
waves are at a different frequency, the synchroscope rotates in proportion to the
frequency difference. The synchroscope needle always points to the power angle
across the open CB at that moment in time.
11-88
12422963
Power System Restoration
Substation Synchronizers
The synchronizers used in transmission substations typically monitor the three
synchronizing variables and do not allow a CB close until all three are within
limits. Substation automatic synchronizers sometimes have timer features. For
example, the timer might be set at five minutes. Once the automatic synchronizer
is activated, all three of the synchronizing variables must fall within tolerance
within five minutes or the process is aborted. The automatic synchronizers used
in substations may also be configured to control a local generator’s MW and
Mvar output. The generator’s MW and Mvar outputs are automatically adjusted
11-89
12422963
Power System Restoration
Synch-Check Relays
The primary function of a synch-check relay is to prevent a CB closing if the
power angle across the CB is too large. Synch-check relays are typically installed
in transmission substations to prevent:
Î The out-of-synch reclosing of transmission CBs following a system
separation
Î The closing of transmission CBs where a power angle is so high that the
closure could damage generating equipment or initiate a system shutdown
11.6.3 Synchronizing Examples
Two scenarios for synchronizing are presented to describe the synchronizing
process.
11-90
12422963
Power System Restoration
11-91
12422963
Power System Restoration
When
Î The speed of one or both of the islands is adjusted so that the
synchronizing a synchroscope needle is rotating very slowly
generator, the
- Typically, slowing the “running” side system slows the clockwise
running side is the
energized power rotation of the synchroscope and speeding up the running system
system and the slows counter-clockwise rotation
incoming side is
the new generator. - A slight initial speed adjustment is often used to verify the
The terms running appropriate speed adjustment needed to slow the scope down
and incoming are
sometimes used in
Î Once all the previous steps have been taken and verified, the CB should be
the transmission closed at the moment when the scope needle is approaching the 12 o’clock
system. position
- The 12 o’clock position is a 0° power angle
Î The newly interconnected system should now be placed in a suitable
frequency control mode as described earlier in this chapter
11-92
12422963
Power System Restoration
11-93
12422963
Power System Restoration
11-94
12422963
Power System Restoration
11-95
12422963
Power System Restoration
11-96
12422963
Power System Restoration
11-97
12422963
Power System Restoration
11-98
12422963
Power System Restoration
11-99
12422963
Power System Restoration
11-100
12422963
Power System Restoration
11-101
12422963
Power System Restoration
11-102
12422963
Power System Restoration
11-103
12422963
Power System Restoration
A. True
B. False
3. Generators and large motors are often equipped with negative sequence
relays. The negative sequence relay is designed to:
4. During which phase of the restoration process is the voltage and frequency
of the generators that survived the initial disturbance adjusted to optimum
values:
A. Phase 4: Billing
B. Phase 2: Preparation of Subsystems
C. Phase 1: Assessment
D. Phase 3: Establishment of Target Systems
11-104
12422963
Power System Restoration
6. A 200 mile long 500 kV line is transposed at two locations along the line.
The purpose of transposition is to:
9. Which of the following types of units could most likely operate, without
damage, as a motor?
A. Hydro turbine
B. Nuclear drive steam turbine
C. Combustion turbine
D. Coal driven steam turbine
10. Given the following types of turbine/generators, which typically has the
highest frequency response rate?
11-105
12422963
Power System Restoration
11. The high probability of switching surge induced TOVs and the potential
for ferroresonance may necessitate operation at reduced steady-state
voltage levels during the early stages of restoration. These reduced
steady-state voltage levels are typically in the __________ range.
A. 105 to 110%
B. 90 to 95%
C. 70 to 80%
D. 80 to 90%
12. When a switching surge occurs, the power system is exposed to a wave
like effect as the switching surge voltage propagates through the area
power system. The propagating surge voltage can add to the power
system steady-state voltage, producing a __________.
A. LOF
B. TOV
C. AGC
D. URAL
A. 150 MW
B. 10 MW
C. 25 MW
D. 50 MW
11-106
12422963
Power System Restoration
11-107
12422963
12422963
A
GLOSSARY
12422963
12422963
Glossary
GLOSSARY
A-INDEX
A daily index of GEOMAGNETIC activity derived as the average of the eight 3-hourly indices.
A-INDEX WATCH
An A-Index Watch is issued when the daily Boulder, Colorado A-index is predicted to be greater
than 20, 30, 50, or 100, with one day or greater lead-time, in the daily forecasts issued by SEC.
A-index watches are issued for valid times corresponding to entire calendar days, based upon the
daily analyses and forecasts produced by SEC. They serve as a long lead-time prediction of the
expected trend in GEOMAGNETIC activity, within the limits of what the 24-hour A-index value can
describe.
ACCELERATING POWER
In a GENERATOR, the difference between the MECHANICAL INPUT POWER and the electrical output
POWER (assuming no LOSSES). For a GENERATOR’s TORQUE ANGLE to change, the GENERATOR
must have accelerating POWER.
ACCUMULATED INADVERTENT
The accumulation over time of INADVERTENT ENERGY. The accumulated inadvertent account of a
BALANCING AUTHORITY represents the amount of excess ENERGY a BALANCING AUTHORITY has
either supplied to the INTERCONNECTION or absorbed from the INTERCONNECTION. BALANCING
AUTHORITIES monitor their accumulated inadvertent to ensure the accounts do not grow too large.
ACTIVE POWER
The component of the COMPLEX POWER that performs the work. The common unit of active
power is the MW and the symbol is “P”. Active power is sometimes called REAL POWER.
ACTUAL INTERCHANGE
The metered INTERCHANGE over a specific INTERCONNECTION between two PHYSICALLY
ADJACENT BALANCING AUTHORITIES.
ACTUAL LOAD
The actual MW drawn by a LOAD from the POWER SYSTEM. The actual load will be different from
the rated or NOMINAL LOAD if the LOAD’s VOLTAGE or FREQUENCY vary from their NOMINAL
values.
ADEQUACY
The ability of the electric SYSTEM to supply the aggregate electrical DEMAND and ENERGY
requirements of the end-use customers at all times, taking into account SCHEDULED and reasonably
expected unSCHEDULEd OUTAGEs of SYSTEM ELEMENTS.
A-1
12422963
Glossary
AGC PULSES
The AGC SYSTEM sends signals to selected (regulating) GENERATORS to adjust their set-points.
These signals are sent via telecommunication EQUIPMENT. The signals are often called AGC
pulses.
AIR-GAP
The air space between the ROTOR and STATOR of a motor or GENERATOR.
ALTERNATOR
A rotating machine whose output is alternating VOLTAGE and CURRENT.
AMORTISSEUR WINDING
A machine winding consisting of a number of conducting bars attached between the magnetic
POLES of the machine’s ROTOR. Amortisseur windings may be used as starter windings or to help
dampen POWER OSCILLATIONS.
AMPERE
The unit of measurement for CURRENT flow, often stated as “amp”.
AMPLITUDE
The value or magnitude that a waveform has at a specific point in time.
ANALOG ELECTRONICS
Electronic circuitry in which the magnitudes of quantities are used in a continuous manner to
perform functions. For example, input CURRENT values may be amplified and used to perform
work in an analog CIRCUIT. Analog is different than digital in the sense that analog CIRCUITS use
VOLTAGE and CURRENT magnitudes continuously while digital CIRCUITS use VOLTAGE and
CURRENT to determine the state (on or off) of ELEMENTS.
A-2
12422963
Glossary
ANGLE INSTABILITY
The opposite of ANGLE STABILITY. When a POWER SYSTEM loses ANGLE STABILITY it enters a
PERIOD of angle instability. An angle unstable SYSTEM has lost some portion of the magnetic
bound that holds sections of the POWER SYSTEM in synchronism with one another.
ANGLE STABILITY
An angle stable POWER SYSTEM is one in which all ELEMENTS of the POWER SYSTEM are bound
together via magnetic forces. For example, an angle stable GENERATOR’s internal MAGNETIC
FIELD rotates in synchronism (in-step) with the MAGNETIC FIELD of the 3Φ POWER SYSTEM to
which it connects.
APPARENT POWER
The product of VOLTAGE and CURRENT PHASORS. Apparent power comprises both active and
REACTIVE POWER, usually expressed in KILOVOLTAMPEREs (kVA) or megavoltamperes (MVA).
Another term for apparent power is COMPLEX POWER.
ARC
The discharge of CURRENT through the air or in a gas.
ARCING HORNS
An enhancement to a DISCONNECT SWITCH to increase the switch’s CURRENT interrupting
capability.
ARMATURE
The component of a machine in which the VOLTAGE is induced. In a SYNCHRONOUS GENERATOR
the armature is usually the STATOR. The armature winding is wrapped about the armature.
ASYNCHRONOUS
To be OUT-OF-STEP with a reference. An induction GENERATOR is an asynchronous GENERATOR
as its ROTOR does not rotate in synchronism with the POWER SYSTEM.
AUTO-LOAD
A feature on some GENERATORs that automatically moves the GENERATOR to a TARGET LOAD
(MW) level.
A-3
12422963
Glossary
AUTO-TRANSFORMER
A POWER TRANSFORMER with a single coil. The entire coil acts as the PRIMARY WINDING while a
portion of the same coil acts as the SECONDARY WINDING.
AUXILIARY RELAY
A RELAY whose function is to supplement the actions of other types of RELAYS. For example, a
LOCKOUT RELAY is an auxiliary relay with numerous contacts that each can perform an action.
The IEEE has numbers assigned to two types of auxiliary relays; 86 (lock-out) and 94 (tripping).
AVAILABILITY
A measure of time a generating unit, TRANSMISSION line, or other FACILITY is capable of providing
service, whether or not it actually is in service. Typically, this measure is expressed as a percent
available for the PERIOD under consideration.
AVERAGE DEMAND
The electric ENERGY delivered over any interval of time as determined by dividing the total
ENERGY by the units of time in the interval.
A-4
12422963
Glossary
AVOIDED COST
The cost the utility would incur but for the existence of an independent GENERATOR or other
ENERGY service option. Avoided cost rates have been used as the POWER purchase price utilities
offer independent suppliers.
BACK EMF
When AC CURRENT flows through a CONDUCTOR an alternating MAGNETIC FIELD is created. This
alternating MAGNETIC FIELD induces a VOLTAGE in the CONDUCTOR. The induced VOLTAGE is
called the CONDUCTOR’S back EMF.
BACK-TO-BACK HVDC
An HVDC SYSTEM in which AC is converted to DC and then immediately back to AC. The
HVDC TRANSMISSION path is very short, normally consisting of a short section of buswork.
BACKUP POWER
POWER provided by contract to a customer when that customer’s normal SOURCE of POWER is not
available.
BALANCING AUTHORITY
The responsible ENTITY that integrates resource plans ahead of time, maintains LOAD-
INTERCHANGE-GENERATION balance within a BALANCING AUTHORITY AREA, and supports
INTERCONNECTION FREQUENCY in real time.
BANDWIDTH
The acceptable range of a quantity. For example, if it is desired to hold the VOLTAGE at a 345 kV
BUS between 355 and 360 kV then the bandwidth is 355 - 360 kV or 5 kV.
BANKING
ENERGY delivered or received by a utility with the intent that it will be returned in kind (as
ENERGY) in the future.
BASE LOAD
The minimum amount of electric POWER delivered or required over a given period at a constant
rate.
A-5
12422963
Glossary
BILATERAL PAYBACK
INADVERTENT INTERCHANGE accumulations paid back via an INTERCHANGE SCHEDULE with
another BALANCING AUTHORITY.
BIPOLAR HVDC
An HVDC SYSTEM that uses two CONDUCTORS. One CONDUCTOR is energized with a positive
VOLTAGE and the other a negative VOLTAGE.
BLADE
The component of a steam TURBINE upon which the steam impacts. Blades are also called
“buckets”.
BLOCKED GOVERNOR
A GOVERNOR CONTROL SYSTEM that has somehow been blocked or prevented from responding to
a FREQUENCY DEVIATION. There are many ways to block a governor.
BOILER
The component of a steam POWER plant in which the steam is created.
BOILER FOLLOW
A MODE of operation of a fossil unit’s TURBINE/BOILER CONTROL SYSTEM in which the unit’s
TURBINE is allowed to immediately respond to a LOAD (MW) change request while the BOILER
response “follows” with the resulting temperature and pressure swings.
BRAKING RESISTOR
A device used to enhance the angle stability of a power system that uses hydro-electric generation.
A Braking Resistor is a large resistive load that is inserted to absorb excess energy when an
accelerating condition is detected in the power system.
BROKER
A third party who establishes a TRANSACTION between a seller and a purchaser. A Broker does
not take title to CAPACITY or ENERGY.
A-6
12422963
Glossary
BRUSH
A sliding contact, usually made of carbon, located between the excitation CURRENT SOURCE and
the ROTOR FIELD WINDING leads of a SYNCHRONOUS GENERATOR.
BULK TRANSMISSION
A functional or VOLTAGE classification relating to the higher VOLTAGE portion of the
TRANSMISSION SYSTEM, specifically, lines at or above a VOLTAGE level of 115 kV.
BURDEN
Operation of the BULK ELECTRIC SYSTEM that violates or is expected to violate a SYSTEM
OPERATING LIMIT or INTERCONNECTION RELIABILITY OPERATING LIMIT in the INTERCONNECTION,
or that violates any other NERC, REGIONAL RELIABILITY ORGANIZATION, or local operating
RELIABILITY standards or criteria.
BUS
An abbreviation of the word busbar. A bus is a location in an electrical network where one or
more ELEMENTS are connected together.
CAPACITANCE (C)
The property of an ELECTRICAL CIRCUIT that opposes VOLTAGE changes by storing ENERGY in its
ELECTRIC FIELD. The symbol for capacitance is “C” and the unit is the FARAD. All energized
EQUIPMENT has a natural capacitance.
CAPACITIVE LOAD
A LOAD that supplies LAGGING REACTIVE POWER to the SYSTEM.
1
XC =
2π fC
A-7
12422963
Glossary
CAPACITOR
A device intentionally designed to act as a capacitor and store ENERGY in its ELECTRIC FIELD. A
shunt capacitor acts as a SOURCE of REACTIVE POWER to the SYSTEM. Series capacitors are seldom
seen devices that are used to reduce the INDUCTIVE REACTANCE of a TRANSMISSION path.
CAPACITOR BANK
A CAPACITOR is an electrical device that provides REACTIVE POWER to the SYSTEM and is often
used to compensate for reactive LOAD and help support SYSTEM VOLTAGE. A bank is a collection
of one or more CAPACITORS at a single location.
CAPACITY
The rated continuous LOAD-carrying ability, expressed in megawatts (MW) or megavolt-amperes
(MVA) of GENERATION, TRANSMISSION, or other electrical EQUIPMENT.
CAPACITY EMERGENCY
A capacity emergency exists when a BALANCING AUTHORITY AREA’s operating CAPACITY, plus
firm purchases from other systems, to the extent available or limited by TRANSFER CAPABILITY, is
inadequate to meet its DEMAND plus its regulating requirements.
CAPACITY FACTOR
The ratio of the total ENERGY generated by a generating unit for a specified period to the
maximum possible ENERGY it could have generated if operated at the maximum CAPACITY RATING
for the same specified period, expressed as a percent.
CASCADING
The uncontrolled successive loss of SYSTEM ELEMENTS triggered by an incident at any location.
Cascading results in widespread electric service INTERRUPTION that cannot be restrained from
sequentially spreading beyond an area predetermined by studies.
CASCADING OUTAGES
The uncontrolled successive LOSS of BULK ELECTRIC SYSTEM FACILITIES triggered by an incident
(or condition) at any location resulting in the INTERRUPTION of ELECTRIC SERVICE that cannot be
restrained from spreading beyond a pre-determined area.
CAVITATION
Noise or vibration causing damage to a hydro unit’s TURBINE BLADEs as a result of bubbles that
form in the water as it goes through the TURBINE which causes a loss in CAPACITY, HEAD loss,
efficiency loss, and the cavity or bubble collapses when they pass into higher regions of pressure.
A-8
12422963
Glossary
CHARGE
An atomic force. An electron has a negative charge. A proton has a positive charge. Like
charges repel one another while opposite charges attract one another. CURRENT is the flow of
charge.
CHARGING
The Mvar production of a TRANSMISSION line. For example, a 100 mile long 345 kV line has
approximately 75 Mvar of charging.
CHARGING CURRENT
The LEADING CURRENT that flows into the natural CAPACITANCE of a TRANSMISSION line when it
is first energized.
CHECKOUT PROCESS
The method by which any two ENTITIES in the utility industry routinely perform a confirmation of
SCHEDULES for a period of time.
CIRCUIT
A CONDUCTOR or a SYSTEM of CONDUCTORS through which electric CURRENT flows.
CLOCK HOUR
The 60-minute PERIOD ending at :00. All surveys, measurements, and reports are based on clock
hour PERIODS unless specifically noted.
COGENERATION
Production of ELECTRICITY from steam, heat, or other forms of ENERGY produced as a by-product
of another process.
A-9
12422963
Glossary
COMBINED CYCLE
An electric generating technology in which electricity and process steam are produced from
otherwise lost waste heat exiting from one or more combustion TURBINES. The exiting heat is
routed to a conventional BOILER or to a heat recovery steam GENERATOR for use by a steam
TURBINE in the production of electricity. This process increases the overall efficiency of the
electric generating unit.
COMMUTATION
The process of turning off one VALVE and turning on another in an HVDC CONVERTER. In a
twelve-pulse converter there are twelve commutations per CYCLE of the AC supply VOLTAGE.
COMPLIANCE MONITOR
The entity that monitors, reviews, and ensures compliance of responsible entities with
RELIABILITY standards.
COMPLIMENTARY CURRENTS
When a SUBSYNCHRONOUS CURRENT flows in the STATOR winding of a SYNCHRONOUS MACHINE it
will induce two complimentary currents in the ROTOR of the machine. These complimentary
currents will have frequencies of 60 ± the FREQUENCY of the SUBSYNCHRONOUS STATOR
CURRENT.
COMPRESSOR
A machine that increases the pressure of a gas (typically air) or vapor.
CONDENSER
The component of a steam POWER plant in which the steam is cooled to water after exiting the
TURBINE.
CONDUCTOR
A material with a low RESISTANCE to CURRENT flow. A conductor is the opposite of an
INSULATOR.
A-10
12422963
Glossary
CONGESTION
The condition that exists when MARKET PARTICIPANTS seek to dispatch GENERATION in a pattern
which would result in POWER flows that cannot be physically accommodated by the
TRANSMISSION SYSTEM. Although the TRANSMISSION SYSTEM will not normally be operated in an
overload condition, it may be described as congested based on requested/desired SCHEDULES.
CONSTRAINED FACILITY
A TRANSMISSION FACILITY (line, TRANSFORMER, breaker, etc.) that is approaching, is at, or is
beyond its SYSTEM OPERATING LIMIT or INTERCONNECTION RELIABILITY OPERATING LIMIT.
CONSTRAINT
A limitation placed on INTERCHANGE TRANSACTIONS that flow over a CONSTRAINED FACILITY.
CONTIGUOUS
To belong to a common area. Adjoining. A contiguous BALANCING AUTHORITY is self-
contained. A non-contiguous BALANCING AUTHORITY may have pieces spread over an entire
INTERCONNECTION.
CONTINGENCY
The unexpected failure or OUTAGE of a system component, such as a GENERATOR, TRANSMISSION
LINE, CIRCUIT BREAKER, SWITCH or other electrical ELEMENT.
CONTINGENCY RESERVE
The provision of CAPACITY deployed by the BALANCING AUTHORITY to meet the DISTURBANCE
CONTROL STANDARD (DCS) and other NERC and REGIONAL RELIABILITY ORGANIZATION
contingency requirements.
CONTINUOUS RATING
The RATING as defined by the EQUIPMENT owner that specifies the level of electrical loading,
usually expressed in megawatts (MW) or other appropriate units that a SYSTEM, FACILITY, or
ELEMENT can support or withstand indefinitely without loss of EQUIPMENT life.
A-11
12422963
Glossary
CONTRACT PATH
An agreed upon electrical path for the continuous FLOW of ELECTRICAL POWER between the parties
of an INTERCHANGE TRANSACTION.
CONTROL CENTER
The physical location from which an operating entity operates.
CONTROL SYSTEM
A collection of electrical and mechanical components designed to produce a series of outputs
based on a series of measured inputs. Common control systems related to POWER are excitation
control and GOVERNOR CONTROL SYSTEMS.
COORDINATED CONTROL
A MODE of operation of a fossil unit’s TURBINE/BOILER CONTROL SYSTEM in which the operation
of the BOILER and the TURBINE SYSTEMS are coordinated. The coordination balances the pressure
and temperature limits of the BOILER SYSTEM with the desire for a TURBINE to immediately
respond to LOAD (MW) change requests.
CORE
The material used within a TRANSFORMER. A TRANSFORMER’s core is formed of a magnetic
material such as iron. The purpose of the core is to confine the MAGNETIC FIELD to a TARGET area.
CORONA
A condition that occurs on energized EQUIPMENT when the surface potential (VOLTAGE) is so large
that the DIELECTRIC strength of the surrounding air breaks down (IONIZATION occurs). Symptoms
of corona are a visible ring of light and a hissing sound. Corona is undesirable as ENERGY LOSSES
and electrical interference are a consequence. Corona rings are used to reduce the gradient of the
ELECTRIC FIELD and reduce the likelihood of corona occurring.
COSINE
The cosine of either of the unknown angles of a RIGHT TRIANGLE is the ratio of the side adjacent to
the unknown angle to the HYPOTENUSE.
CRANKING PATH
A portion of the electric SYSTEM that can be ISOLATED and then energized to deliver ELECTRIC
POWER from a GENERATION SOURCE to enable the startup of one or more other GENERATING UNITS.
A-12
12422963
Glossary
CRANKING POWER
CURRENT (I)
The rate of flow of electrons in an electrical CONDUCTOR. Symbol is “I” and unit is the AMPERE,
or amp.
CURTAILMENT
A reduction in the SCHEDULED CAPACITY or ENERGY delivery.
CUT-OUT
A switching device typically found in the DISTRIBUTION SYSTEM. Cut-outs often include a fuse so
the device serves the dual purpose of providing electrical isolation and protection.
CYBER ASSETS
Programmable electronic devices and communication networks including hardware, software, and
data.
CYCLE
A complete sequence of a repeating waveform. For example, the magnitude of a SINE wave
changes as the degrees progress from 0° to 360°. After 360° the SINE wave begins to repeat itself.
One cycle of a SINEWAVE is therefore 360°.
DAMPING
Forces or CONTROL SYSTEM actions that reduce the magnitude of OSCILLATIONS. Damping is
provided by various natural phenomena and by various electrical EQUIPMENT. Damping can either
be positive (reduce OSCILLATIONS) or negative (amplify OSCILLATIONS).
DEADBAND
The distance about a TARGET value within which a CONTROL SYSTEM will not respond. For
example, a GOVERNOR CONTROL SYSTEM may have a deadband of ±0.036 HZ. Unless the
FREQUENCY DEVIATION exceeds 0.036 HZ, the governor will not respond.
DELIVERING PARTY
The entity supplying the CAPACITY and ENERGY to be transmitted at the POINT OF RECEIPT.
A-13
12422963
Glossary
DELTA CONNECTION
A 3Φ electrical connection in which the three PHASES are connected in series with one another.
The three PHASES form a closed triangle. TRANSFORMER windings are often connected in a Delta
configuration.
DEMAND
1. The rate at which electric ENERGY is delivered to or by a SYSTEM or part of a SYSTEM,
generally expressed in kilowatts or megawatts, at a given instant or averaged over any designated
interval of time. 2. The rate at which ENERGY is being used by the customer.
DEMAND INTERVAL
The time period during which a DEMAND is measured, usually in 15-, 30-, or 60-minute
increments.
DERATING (GENERATOR)
A reduction in a generating unit’s NET DEPENDABLE CAPACITY.
DEVIATION
The variance from the SCHEDULED value. For example, if the SCHEDULED value of VOLTAGE is
142 kV and the actual value is 138 kV then the VOLTAGE deviation is -4 kV.
DEVICE NUMBERS
The IEEE has adopted a numbering SYSTEM for labeling various types of protective EQUIPMENT.
Important numbers are:
A-14
12422963
Glossary
DIELECTRIC
Insulating material used to separate and insulate. CAPACITORs use a dielectric between its two
conducting plates.
DIGITAL ELECTRONICS
Electronic circuitry that operates on data in the form of digits. Most digital CIRCUITS use the
binary SYSTEM in which digital components are either turned on (a data value of “1”) or off (a data
value of “0”) based on CIRCUIT VOLTAGE magnitudes. Digital electronics have replaced ANALOG
ELECTRONICS in most, but not all, applications.
DISCONNECT SWITCH
A mechanical device that is used to isolate EQUIPMENT from energized parts of the POWER
SYSTEM. Disconnect switches are not rated for interrupting CURRENT unless additional ARC
interrupting components are added to the disconnect.
DISPATCHABLE GENERATION
GENERATION available physically or contractually to respond to changes in SYSTEM DEMAND or to
respond to TRANSMISSION security CONSTRAINTS.
A-15
12422963
Glossary
DISTRIBUTION
For electricity, the function of distributing electric POWER using low VOLTAGE lines to retail
customers.
DISTRIBUTION FACILITIES
The facilities owned or controlled by a TRANSMISSION Owner and used to provide Wholesale
DISTRIBUTION Service.
DISTRIBUTION LINES
CONDUCTORS used to distribute POWER to the utilities customers. Distribution lines may be 3Φ or
1Φ.
DISTRIBUTION NETWORK
The portion of an electric SYSTEM that is dedicated to delivering electric ENERGY to an end user.
The distribution network consists primarily of low VOLTAGE lines and TRANSFORMERS that
“transport” electricity from the bulk POWER SYSTEM to retail customers.
DISTRIBUTION PROVIDER
Provides and operates the “wires” between the TRANSMISSION system and the end-use customer.
For those end-use customers who are served at TRANSMISSION VOLTAGEs, the TRANSMISSION
OWNER also serves as the Distribution Provider. Thus, the Distribution Provider is not defined by
a specific VOLTAGE, but rather as performing the DISTRIBUTION function at any VOLTAGE.
DISTURBANCE
1. An unplanned event that produces an abnormal SYSTEM condition. 2. Any perturbation to the
electric system. 3. The unexpected change in ACE that is caused by the sudden failure of
GENERATION or INTERRUPTION of LOAD.
1
Phasor Measurement Units and any other equipment that meets the functional requirements of DMEs may qualify as
DMEs.
A-16
12422963
Glossary
• DYNAMIC DISTURBANCE RECORDERS (DDRs), which record incidents that portray POWER
SYSTEM behavior during dynamic events such as low-FREQUENCY (0.1 Hz – 3 Hz)
OSCILLATIONS and abnormal FREQUENCY or VOLTAGE excursions.
DIVERSITY FACTOR
The ratio of the sum of the coincident maximum DEMANDS of two or more LOADS to their
noncoincident maximum DEMAND for the same period.
DROOP
A characteristic of a GOVERNOR CONTROL SYSTEM that requires a decrease in GENERATOR shaft
speed to produce an increase in the GENERATOR’s MW output. There are two types of droop;
permanent and TRANSIENT:
Permanent Droop
Permanent droop is the droop used to enable all GENERATORs (with active governors) to share in
FREQUENCY REGULATION and to ensure a MW response in proportion to unit size. Desired values
of permanent droop are in the neighborhood of 5%. The 5% droop means that a 5% FREQUENCY
change will result in the unit’s governor moving the fuel (steam, water, gas, etc.) VALVES across
their full range.
Transient Droop
A feature implemented in some GOVERNOR CONTROL SYSTEMS to ensure GENERATORS do not
enter into POWER OSCILLATIONS following LOAD changes. POWER OSCILLATIONS may occur due
to the inherent time delay between a request for a LOAD change by the governor and the ability of
a GENERATOR to actually deliver the LOAD change. This natural time delay could lead to excessive
control action by the governor. A condition of oscillation called “hunting” could result. If a
GENERATOR is on isochronous control, TRANSIENT droop is a necessity. The TRANSIENT droop
function or “compensation” dampens a governor’s initial response following a speed change. The
effect is temporary as opposed to a permanent droop function which is permanent.
DROOP CURVE
A graphical method of representing the performance of a governor. The horizontal axis is
typically GENERATOR output while the vertical axis is SYSTEM FREQUENCY. When a governor
with a % DROOP is plotted on such a curve the plot DROOPS from left to right with increasing
GENERATOR output.
DYNAMIC RATING
The process that allows a SYSTEM ELEMENT RATING to vary with the changing environmental
conditions in which the ELEMENT is located.
A-17
12422963
Glossary
accounting purposes. Commonly used for scheduling jointly owned GENERATION to or from
another BALANCING AUTHORITY AREA.
DYNAMIC TRANSFER
The provision of the real-time monitoring, TELEMETERING, computer SOFTWARE, hardware,
communications, engineering, ENERGY accounting (including INADVERTENT INTERCHANGE), and
administration required to electronically move all or a portion of the real ENERGY services
associated with a GENERATOR or LOAD out of one BALANCING AUTHORITY AREA into another.
ECONOMIC DISPATCH
The allocation of DEMAND to individual generating units on line to effect the most economical
production of electricity.
ECONOMY ENERGY
ELECTRICAL ENERGY produced and supplied from a more economical SOURCE in one SYSTEM and
substituted for that being produced or capable of being produced by a less economical SOURCE in
another SYSTEM.
ELECTRIC FIELD
The invisible lines of force that surround an energized piece of EQUIPMENT. An electric field is
created when a CONDUCTOR is energized by a VOLTAGE. ENERGY is stored in an electric field.
ELECTRIC UTILITY
Person, agency, authority, or other legal entity that owns or operates facilities for the
GENERATION, TRANSMISSION, DISTRIBUTION, or sale of electric ENERGY primarily for use by the
public, and is defined as a utility under the statutes and rules by which it is regulated. An electric
utility can be investor owned, cooperatively owned, or government owned (by a federal agency,
crown corporation, state, provincial government, municipal government, and public POWER
district).
ELECTRICAL CIRCUIT
An electrical circuit consists of a VOLTAGE SOURCE, a conducting path to a LOAD, a LOAD, and a
return path from the LOAD to the VOLTAGE SOURCE. All four of these ingredients are necessary for
CURRENT to flow in the electrical circuit.
ELECTRICAL DISTANCE
The IMPEDANCE of a TRANSMISSION line is a measure of the electrical distance. For example, if a
line has a 100 Ω IMPEDANCE then 50 Ω is ½ the line’s electrical length. IMPEDANCE RELAYS are
A-18
12422963
Glossary
often called DISTANCE RELAYS in reference to the use of IMPEDANCE as a measure of electrical
distance.
ELECTRICAL ENERGY
The GENERATION or use of electric POWER by a device over a period of time, expressed in
KILOWATTHOURs (kWh), or MEGAWATTHOURs (MWh), or gigaWATTHOURs (GWh).
ELECTRODES
The connection to GROUND of an HVDC CONVERTER. The grounding electrode provides a
VOLTAGE reference and may be part of the CURRENT return path.
ELECTROJET
A CURRENT flow path in the shape of a donut that situates itself above the north and south
magnetic POLES of the earth. Electrojets are the result of solar DISTURBANCES.
ELECTROMAGNET
Temporary magnet created by passing electric CURRENT through a coil. The coil is typically
wound about a magnetic CORE.
ELECTROMAGNETIC INDUCTION
The creation of a VOLTAGE in a CONDUCTOR due to a relative movement between the CONDUCTOR
and a MAGNETIC FIELD. Electromagnetic induction is the basic principle of operation of
TRANSFORMERS and GENERATORS.
ELEMENT
Any electric device with terminals that may be connected to other electrical devices, such as a
GENERATOR, TRANSFORMER, CIRCUIT BREAKER, BUS section, or TRANSMISSION LINE. An element
may be comprised of one or more components.
EMERGENCY ENERGY
ELECTRICAL ENERGY purchased by a member SYSTEM whenever an event on that SYSTEM causes
insufficient Operating Capability to cover its own DEMAND requirement.
A-19
12422963
Glossary
EMERGENCY RATING
The RATING as defined by the EQUIPMENT owner that specifies the level of electrical loading or
output, usually expressed in megawatts (MW) or Mvar or other appropriate units, that a SYSTEM,
FACILITY, or ELEMENT can support, produce, or withstand for a finite PERIOD. The RATING
assumes acceptable loss of EQUIPMENT life or other physical or safety limitations for the
EQUIPMENT involved.
ENERGY
The POWER used over a period of time. Electrical energy is measured in watt-hours, kilowatt-
hours (kWh), or Megawatt-hours (MWh).
ENERGY CONVERSION
The conversion of ENERGY from one form to another. For example, a coal fired steam
TURBINE/GENERATOR converts the coal’s chemical ENERGY to thermal ENERGY by burning the
coal. The thermal ENERGY is then converted to MECHANICAL ENERGY by heating water and
turning the TURBINE with steam. The MECHANICAL ENERGY of the TURBINE is then converted to
ELECTRICAL ENERGY via ELECTROMAGNETIC INDUCTION.
ENERGY EMERGENCY
A condition when a LOAD Serving Entity has exhausted all other options and can no longer
provide its customers’ expected ENERGY requirements.
ENVELOPE
The imaginary boundary that surrounds the FUNDAMENTAL FREQUENCY OSCILLATIONS waveshape.
The FREQUENCY of lower FREQUENCY OSCILLATIONS can be determined by noting the FREQUENCY
of the oscillation envelope.
A-20
12422963
Glossary
EQUIPMENT
An electrical device with terminals that may be connected to other electrical devices.
EQUIPMENT RATING
The maximum and minimum permissible VOLTAGE, CURRENT, FREQUENCY, or active and
REACTIVE POWER flows on individual EQUIPMENT under steady state, short-circuit, and TRANSIENT
conditions, as specified by the EQUIPMENT owner.
ERCOT
Acronym for the Electrical Reliability Council of Texas.
EXCITATION SYSTEM
A GENERATOR CONTROL SYSTEM used to control the production of REACTIVE POWER. The
excitation system’S main components are the VOLTAGE REGULATOR and the EXCITER.
EXCITER
The DC POWER SOURCE for an EXCITATION SYSTEM.
EXCITING CURRENT
The CURRENT drawn by a TRANSFORMER to magnetize its CORE and supply the CORE LOSSES. The
exciting current is typically 1-2% of the TRANSFORMER’S full LOAD CURRENT.
FACILITY
A set of electrical EQUIPMENT that operate as a single bulk electrical SYSTEM ELEMENT (for
example, a line, a generating unit, a shunt CAPACITOR).
FACILITY RATING
The maximum or minimum VOLTAGE, CURRENT, FREQUENCY, or active and REACTIVE POWER
flows through a FACILITY that would not violate the applicable RATINGs of any EQUIPMENT
comprising the FACILITY. Facility ratings are based upon EQUIPMENT RATINGS and other limits as
applicable to the EQUIPMENT.
FARAD (F)
The unit of CAPACITANCE. Symbol is “F”.
A-21
12422963
Glossary
FAST VALVING
A method of reducing the accelerating ENERGY in a steam TURBINE/GENERATOR. Fast valving
involves the rapid adjustment of TURBINE VALVES when a GENERATOR starts to accelerate. Fast
valving may assist in maintaining the ANGLE STABILITY of a POWER SYSTEM.
FAULT
An event occurring on an ELECTRIC SYSTEM such as a SHORT CIRCUIT, a broken wire, or an
intermittent connection.
FEEDBACK LOOP
A control loop in which CURRENT control actions are influenced by the responses to previous
control actions. In a feedback loop (such as in a GENERATOR’s EXCITATION SYSTEM) the response
of the controlled variable is constantly monitored to determine what new control actions should be
taken.
FERRORESONANCE
A RESONANCE condition in which a portion of the INDUCTANCE is provided by an iron-core
INDUCTANCE (Ferro is Latin for iron.). Iron-core INDUCTANCES change magnitude when the iron
is saturated. Ferroresonance is possible in the TRANSMISSION or DISTRIBUTION SYSTEM but is
much more common in the DISTRIBUTION SYSTEM.
FIELD WINDING
The winding wrapped about the ROTOR of a SYNCHRONOUS MACHINE. DC excitation CURRENT is
fed to the field winding to produce the ROTOR’s MAGNETIC FIELD.
FILTER
A combination of CAPACITORS, inductors, and resistors used to encourage or block the flow of a
specific FREQUENCY or band of frequencies of ENERGY.
FIRM CAPACITY
CAPACITY that is as firm as the seller’s NATIVE LOAD unless modified by contract. Associated
ENERGY may or may not be taken at option of purchaser. Supporting reserve is carried by the
seller.
FIRM DEMAND
That portion of the DEMAND that a POWER supplier is obligated to provide except when SYSTEM
RELIABILITY is threatened or during EMERGENCY conditions.
A-22
12422963
Glossary
FLARE
A sudden eruption of ENERGY on the solar disk lasting minutes to hours, from which radiation and
particles are emitted.
FLASHOVER
An ELECTRICAL discharge through air around or over the surface of insulation, between objects of
different potential, caused by placing a VOLTAGE across the air space that results in the ionization
of the air space.
FLOWGATE
A designated point on the TRANSMISSION SYSTEM through which the INTERCHANGE DISTRIBUTION
CALCULATOR calculates the POWER flow from INTERCHANGE TRANSACTIONS.
FLYWEIGHTS
The portion of a CENTRIFUGAL BALLHEAD GOVERNOR that rotates.
FORCED OUTAGE
1. The removal from service AVAILABILITY of a GENERATING UNIT, TRANSMISSION LINE, or other
FACILITY for EMERGENCY reasons. 2. The condition in which the EQUIPMENT is unavailable due
to unanticipated failure.
FORECAST
Predicted DEMAND for electric POWER. A forecast may be short term (for example, 15 minutes)
for SYSTEM operation purposes, long-term (five to 20 years) for GENERATION PLANNING purposes,
or for any range in between. A forecast may include PEAK DEMAND, ENERGY, REACTIVE POWER,
or DEMAND profile. A forecast may be made for total SYSTEM DEMAND, TRANSMISSION LOADING,
SUBSTATION/feeder LOADING, individual customer DEMAND, or appliance DEMAND.
A-23
12422963
Glossary
FORECAST UNCERTAINTY
Probable DEVIATIONS from the expected values of factors considered in a FORECAST.
FOURIER ANALYSIS
A scientific process in which the various FREQUENCY components (HARMONICS) of a waveform
are identified. For example, a waveform may have a FUNDAMENTAL FREQUENCY of 60 HZ but
also contain 3rd and 5th harmonic components. Fourier Analysis is used to identify the order of the
harmonic components.
FRCC
Acronym for the Florida Reliability Coordinating Council. FRCC is one of the eight NERC
REGIONAL RELIABILITY ORGANIZATIONS.
FREQUENCY (F)
The rate at which a repeating waveform repeats itself. Frequency is measured in CYCLES per
second or in HERTZ (HZ). The symbol if “F”.
FREQUENCY BIAS
A value, usually expressed in megawatts per 0.1 HERTZ (MW/0.1 HZ), associated with a
BALANCING AUTHORITY AREA that approximates the BALANCING AUTHORITY AREA’s response to
INTERCONNECTION FREQUENCY ERROR.
FREQUENCY DEVIATION
A change in INTERCONNECTION FREQUENCY.
FREQUENCY REGULATION
The ability of a BALANCING AUTHORITY to help the INTERCONNECTION maintain SCHEDULED
FREQUENCY. This assistance can include both TURBINE governor response and AUTOMATIC
GENERATION CONTROL.
A-24
12422963
Glossary
FREQUENCY SWINGS
Constant changes in FREQUENCY from its NOMINAL or steady-state value.
FUNDAMENTAL FREQUENCY
The base FREQUENCY for a SYSTEM. For example, the fundamental frequency of North American
POWER SYSTEMS is 60 HZ while a large portion of the world uses 50 HZ as the fundamental
frequency.
GALLERY
A passageway within a water dam created to allow inspection of the dam’s structure.
GATE/GRID CONTROL
The means of controlling a MERCURY ARC VALVE (MAV) or a THYRISTER VALVE. A pulse of
CURRENT or VOLTAGE is applied to the GRID of a MAV or the gate of a THYRISTER. The pulse will
turn the VALVE on if it is forward biased. Gate/grid control is typically only used to turn a VALVE
on.
GENERATION
The process of producing ELECTRICAL ENERGY from other forms of ENERGY; also, the amount of
electric POWER produced, usually expressed in kilowatt hours (kW) or megawatt hours (MW).
GENERATION CONTROL
The process by which the GENERATION supply is adjusted to both maintain SYSTEM FREQUENCY
and keep a close match between the actual TIE-LINE flows and the SCHEDULED TIE-LINE flows.
GENERATOR
Generally, an electromechanical device used to convert mechanical POWER to electrical POWER.
GENERATOR OPERATOR
The entity that operates GENERATING unit(s) and performs the functions of supplying ENERGY and
INTERCONNECTED OPERATIONS SERVICES.
GENERATOR OWNER
Entity that owns and maintains GENERATING units.
A-25
12422963
Glossary
GEOMAGNETIC STORM
A worldwide disturbance of the earth’s magnetic field, distinct from regular diurnal variations.
GREEK ALPHABET
Upper and Lower case letters from the Greek alphabet are typically used by electrical engineers to
designate angles and represent variables. The following Greek letters are used in this text:
A-26
12422963
Glossary
GRID
An electrical TRANSMISSION and/or DISTRIBUTION NETWORK.
GROSS GENERATION
The output POWER (in MW) at the STATOR terminals of a GENERATOR.
GROUND
A conducting connection between an ELECTRICAL CIRCUIT or device and the earth. A ground may
be intentional, as in the case of a safety ground, or accidental, which may result in high
overcurrents.
HALF-CYCLE SATURATION
A magnetic SATURATION of a TRANSFORMER’s CORE due to the presence of a DC CURRENT in the
TRANSFORMER windings. The operating point of the TRANSFORMER on its SATURATION curve is
shifted such that for a portion of ½ of each CYCLE the TRANSFORMER saturates.
HARMONICS
Integer multiples of the FUNDAMENTAL FREQUENCY. If the FUNDAMENTAL FREQUENCY is 60 HZ
then the 2nd Harmonic has a FREQUENCY of 120 HZ, 3rd Harmonic 180 HZ, etc.
HEAD
Vertical change in elevation, expressed in either feet or meters, between the head water level and
the tailwater level of a hydro-electric FACILITY.
HEAT RATE
An expression for the efficiency of a thermal POWER plant. The heat rate is the amount of heat
(measured in British Thermal Units or BTU) that is required to produce a kWh or electrical
output. The lower the heat rate, the more efficient the POWER plant.
HENRY (H)
The unit of INDUCTANCE. The symbol for a Henry is “H”.
HERTZ (HZ)
Hertz is the unit of FREQUENCY equal to one CYCLE per second.
A-27
12422963
Glossary
HOURLY VALUE
Data measured on a clock-hour basis.
HVDC
Acronym for High VOLTAGE DIRECT CURRENT. The term HVDC is commonly used when the DC
VOLTAGE is above 100 kV.
HVDC CONVERTER
An arrangement of EQUIPMENT designed and operated to convert between AC and DC POWER. A
converter can be operated as an INVERTER (DC to AC) or a RECTIFIER (AC to DC).
HVDC MODULATION
A feature added to the controls of an HVDC SYSTEM. HVDC modulation modulates (adjusts) the
POWER flow into an HVDC CONVERTER in order to dampen POWER OSCILLATIONS in the AC
supply SYSTEM. HVDC modulation assists with DAMPING AC SYSTEM POWER OSCILLATIONS.
HYDRAULICS
The use of fluid forces to perform work. For example, hydraulics are often used in GOVERNOR
CONTROL SYSTEMS to develop the large forces required to move steam or water VALVES.
HYPOTENUSE
The side of a RIGHT TRIANGLE which is opposite the 90° angle.
IEEE
Acronym for the Institute of Electrical and Electronic Engineers. The IEEE is an international
standards organization that publishes guidelines for, among other areas, POWER SYSTEMS.
IGNEOUS ROCK
Rock that was created by volcanic activity.
IMBALANCE
A condition where the GENERATION and INTERCHANGE SCHEDULEs do not match DEMAND.
IMPEDANCE (Z)
The total opposition to the CURRENT flow in an ELECTRICAL CIRCUIT. The symbol for the
impedance is “Z”. The impedance includes the RESISTANCE (R), CAPACITANCE (C), and the
INDUCTANCE (L).
A-28
12422963
Glossary
IMPEDANCE RELAY
A PROTECTIVE RELAY that activates if the ratio of the measured VOLTAGE divided by the CURRENT
(the IMPEDANCE) falls below a pickup point. An impedance relay is also commonly called a
DISTANCE RELAY.
IMPULSE TURBINE
A water TURBINE in which high velocity water is directed through nozzles at the TURBINE buckets.
A Pelton Wheel is an example of an impulse turbine.
INADVERTENT ENERGY
When INADVERTENT INTERCHANGE exists for a period of time, inadvertent energy will be
accumulated.
INADVERTENT INTERCHANGE
The difference between the BALANCING AUTHORITY’s NET ACTUAL INTERCHANGE and NET
SCHEDULED INTERCHANGE. (IA – IS)
INCREMENTAL COST
The cost associated with producing an additional MWh of ENERGY from a generating unit.
Incremental cost is typically stated in $/MWh or MILLs/kWh.
INCREMENTAL LOSSES
The increase in LOSSES due to an increase in POWER flow. For example, assume the POWER flow
on a TRANSMISSION line is initially 100 MW. If the POWER flow is increased to 101 MW there
will be incremental ENERGY LOSSES associated with the 1 MW increase in POWER flow. The
percentage of the Incremental Loss increases with increasing levels of POWER flow.
A-29
12422963
Glossary
INDUCTANCE (L)
The property of an ELECTRICAL CIRCUIT that opposes a change in CURRENT flow. The symbol for
inductance is the letter “L” and the unit is the HENRY (symbol “H”).
INDUCTION MACHINE
An AC machine that can be operated as a GENERATOR or as a motor. When operated as a
GENERATOR the induction machine’s ROTOR is driven at a speed greater than SYNCHRONOUS
SPEED. When operated as a motor the induction machine’s ROTOR is driven at a speed less than
SYNCHRONOUS SPEED. Induction GENERATORs are rarely used by large scale POWER GENERATORs.
Induction motors are the most common type of AC motor. Induction machines absorb REACTIVE
POWER (always a LAGGING LOAD) and cannot be used to produce REACTIVE POWER as a
SYNCHRONOUS MACHINE can.
INDUCTIVE LOAD
A LOAD that absorbs LAGGING REACTIVE POWER from the SYSTEM.
X L = 2π fL
INERTIA
The property of an object that resists changes to the motion of the object. For example, the inertia
of a rotating object resists changes to the object’s speed of rotation. The inertia of a rotating
object is a function of its mass, diameter, and speed of rotation.
A-30
12422963
Glossary
INERTIAL ENERGY
ENERGY stored within a rotating mass. For example, a spinning GENERATOR contains inertial
energy. The terms inertial energy, STORED ENERGY, and ROTATIONAL ENERGY are often used
interchangeably to refer to the ENERGY stored in the rotating ELEMENTS (motors and GENERATORS)
of the POWER SYSTEM.
IN-RUSH CURRENT
The sudden rush of CURRENT when a TRANSFORMER or a motor is first energized. The peak
magnitudes of the in-rush current last only a few CYCLES but can reach levels more than 10 times
the device’s full LOAD CURRENT.
INSTALLED RESERVE
The difference between a utility’s expected annual peak MW GENERATION capability and their
annual peak MW LOAD. Installed reserves are a rough approximation of a utility's spare or reserve
GENERATION.
INSTANTANEOUS DEMAND
The rate of ENERGY delivered at a given instant.
INSULATOR
A material with a high IMPEDANCE to CURRENT flow. An insulator is the opposite of a
CONDUCTOR.
INTEGRATED DEMAND
The average of the INSTANTANEOUS DEMANDS (MW) over the DEMAND INTERVAL (usually hours).
INTER-AREA MODE
A POWER oscillation MODE (FREQUENCY) in which a large section of an interconnected POWER
SYSTEM oscillates with respect to another large section of the same INTERCONNECTION. The Inter-
area mode ranges from 0.05 to 0.5 HZ.
INTERCHANGE
ENERGY transfers that cross BALANCING AUTHORITY boundaries.
INTERCHANGE AUTHORITY
The responsible entity that authorizes implementation of valid and balanced INTERCHANGE
SCHEDULES between BALANCING AUTHORITY AREAS, and ensures communication of
INTERCHANGE information for reliability assessment purposes.
A-31
12422963
Glossary
INTERCHANGE SCHEDULE
An agreed-upon INTERCHANGE TRANSACTION size (megawatts), start and end time, beginning and
ending ramp times and rate, and type required for delivery and receipt of POWER and energy
between the SOURCE and SINK BALANCING AUTHORITIES involved in the TRANSACTION.
INTERCHANGE TRANSACTION
An AGREEMENT to transfer ENERGY from a seller to a buyer that crosses one or more BALANCING
AUTHORITY AREA boundaries.
INTERCONNECT
When two POWER SYSTEMs tie together with AC TRANSMISSION, it is referred to as an
interconnect.
INTERCONNECTED SYSTEM
A SYSTEM consisting of two or more individual electric SYSTEMS that normally operate in
synchronism and have connecting tie lines.
INTERCONNECTION
When capitalized, any one of the three BULK ELECTRIC SYSTEM networks in North America:
Eastern, Western, and ERCOT. When not capitalized, the facilities that connect two SYSTEMS or
BALANCING AUTHORITIES.
A-32
12422963
Glossary
INTERFACE
The specific set of TRANSMISSION ELEMENTS between two areas or between two areas comprising
one or more electrical SYSTEMS.
INTERRUPTION
A reduction in NON-FIRM TRANSMISSION SERVICE due to economic reasons.
INTRA-AREA MODE
A POWER oscillation MODE (FREQUENCY) in which a pocket of GENERATION in a POWER SYSTEM
oscillates with respect to another pocket of GENERATION in the same POWER SYSTEM. The intra-
area mode ranges from 0.4 to 1 HZ.
INTRA-PLANT MODE
A POWER oscillation MODE (FREQUENCY) in which several GENERATORs in a multi-unit POWER
STATION oscillate with respect to one another. The intra-plant mode ranges from 1.5 to 3 HZ.
INVERTER
An HVDC CONVERTER operated to convert DC POWER to AC POWER.
A-33
12422963
Glossary
IONIZATION
Ionization occurs when an atom (or group of atoms) receives enough ENERGY to split into one or
more free electrons and a positive ion. Ionization is a special case of CHARGING. The visible
CORONA effect that often surrounds energized EQUIPMENT is due to ionization of the air by the
strong ELECTRIC FIELD surrounding the energized CONDUCTOR.
ISLAND
An electrically ISOLATED portion of an INTERCONNECTION. An islanded SYSTEM maintains its
own FREQUENCY. Islands are frequently formed after major DISTURBANCES or during
RESTORATION following a major DISTURBANCE.
ISOLATED
To be electrically separated from the remainder of the INTERCONNECTION. An isolated system
does not have TRANSMISSION ties to the rest of the INTERCONNECTION. An isolated system is an
electrical ISLAND.
JOINT CONTROL
AUTOMATIC GENERATION CONTROL of JOINTLY OWNED UNITS by two or more BALANCING
AUTHORITIES.
JOURNAL BEARING
The bearing that supports the actual weight of a GENERATOR.
K-INDEX
A 3-hourly quasi-logarithmic local index of GEOMAGNETIC activity relative to an assumed quiet-
day curve for the recording site. Range is from 0 to 9. The K-index measures the deviation of the
most disturbed horizontal component.
K-INDEX WARNING
K-index Warnings are issued and/or extended for any period with expected values of K equal to or
greater than 4. Higher K-index warnings supersede lower ones.
KILOVAR (kVAr)
Unit of REACTIVE POWER equal to 1,000 Var.
KILOVOLT (kV)
Unit of electrical potential equal to 1,000 Volts.
A-34
12422963
Glossary
KILOVOLT-AMPERES (kVA)
Unit of COMPLEX POWER equal to 1,000 volt AMPEREs. Here, COMPLEX POWER is in contrast to
ACTIVE POWER. On AC SYSTEMS the VOLTAGE and CURRENT will not be in PHASE if REACTIVE
POWER is being transmitted.
KILOWATTHOUR (kWh)
Unit of ENERGY equaling one thousand WATTHOURs, or one kilowatt used over one hour. This is
the normal quantity used for METERING and billing electricity customers. The retail price for a
kWh varies from approximately 4 cents to 20 cents. At a 100% conversion efficiency, one kWh is
equivalent to about 4 fluid ounces of gasoline, 3/16 pound of liquid petroleum, 3 cubic feet of
natural gas, or ¼ pound of coal.
L SUB-TEN (L10)
The BANDWIDTH that ACE is bounded in order to comply with CPS2. An ACE value (±) whose
width is proportional to a BALANCING AUTHORITY’s size.
LAGGING
Term used when comparing VOLTAGE and CURRENT waves. The wave that is heading positive and
crosses zero last is the lagging wave. In a lagging LOAD the CURRENT wave lags the VOLTAGE
wave.
LAMBDA (λ)
The INCREMENTAL COST of GENERATION. Lambda is commonly expressed in $/MWh or
Mils/kWh. The symbol for lambda is “λ” (the Greek letter lambda).
LEADING
Term used when comparing VOLTAGE and CURRENT waves. The wave that is heading positive and
crosses zero first is the leading wave. In a leading LOAD the CURRENT wave leads the VOLTAGE
wave.
LIGHTNING ARRESTER
A piece of EQUIPMENT that is designed to protect the POWER SYSTEM from high VOLTAGES.
Lightning arresters activate when TRANSIENT over VOLTAGEs (TOVs) occur and harmlessly shunt
the VOLTAGE SURGE to GROUND.
A-35
12422963
Glossary
LIMIT VIOLATION
The operating state during which one or more facilities are outside SYSTEM OPERATING LIMITS or
INTERCONNECTED RELIABILITY LIMITS. A violation occurs at the instant the established limit is
exceeded. This could be a result of a change in one or more operating parameters.
LINE TRIP
Refers to the automatic opening of a TRANSMISSION line by its CIRCUIT BREAKERS. These
openings or “TRIPS” are controlled by PROTECTIVE RELAYS and are designed to protect the POWER
SYSTEM during faulted conditions.
LOAD
An end-use device or customer that receives POWER from the ELECTRIC SYSTEM.
LOAD FACTOR
A measure of the degree of uniformity of DEMAND over a period of time, usually one year,
equivalent to the ratio of AVERAGE DEMAND to PEAK DEMAND expressed as a percentage. Load
factor is calculated by dividing the total ENERGY provided by a SYSTEM during the PERIOD by the
product of the PEAK DEMAND during the PERIOD and the number of hours in the PERIOD.
LOAD FOLLOWING
An ENERGY based ancillary service that is provided via a linear change in a SCHEDULE through a
PERIOD (typically one hour).
LOAD OVERSHOOT
A short term increase in LOAD magnitude due to an increase in the customer’s VOLTAGE. Load
overshoot results from downstream tap changers boosting the customer’s VOLTAGE prior to the
upstream tap changer responding.
LOAD REJECTION
The rejection of LOAD by a GENERATOR. If a GENERATOR suddenly loses its TRANSMISSION path,
it has undergone a load rejection. The GENERATOR will speed up until its mechanical POWER input
can be removed or the unit tripped.
LOAD/FREQUENCY RELATIONSHIP
The relationship between FREQUENCY DEVIATIONS and the LOAD magnitude. In general, the LOAD
magnitude varies with the FREQUENCY. If the FREQUENCY rises the LOAD magnitude rises and
vice versa.
A-36
12422963
Glossary
LOAD SHEDDING
The process of deliberately removing (either manually or automatically) pre-selected customer
DEMAND from a POWER SYSTEM in response to an abnormal condition, to maintain the integrity of
the SYSTEM and minimize overall customer OUTAGES.
LOCAL MODE
A POWER oscillation MODE (FREQUENCY) in which a GENERATOR oscillates with respect to the
remainder of the POWER SYSTEM. The local mode ranges from 0.8 to 2 HZ.
LOCKOUT
A state of a TRANSMISSION line following CIRCUIT BREAKERS operations where the condition
detected by the PROTECTIVE RELAYING was not eliminated by temporarily opening and reclosing
the line. In this state, the CIRCUIT BREAKERS cannot generally be reclosed without resetting a
lockout device.
LOGISTICS
The handling of the details of an operation.
LOOP FLOW
See UNSCHEDULED POWER FLOW.
LOSS OF SYNCHRONISM
The loss of the magnetic bond between ELEMENTS of a POWER SYSTEM. Loss of synchronism and
OUT-OF-STEP refer to the same concept.
LOSSES
The ENERGY losses in the POWER SYSTEM. The total SYSTEM losses consist of the TRANSMISSION,
transformation, and DISTRIBUTION SYSTEM losses.
MAGNETIC FIELD
The invisible lines of force between the north and south POLES of a magnet. A magnetic field is
created when CURRENT flows through a CONDUCTOR. ENERGY is stored in a magnetic field.
A-37
12422963
Glossary
MAGNETISM
A property of matter associated with moving CHARGEs. A material may be a permanent magnet or
it may acquire magnetic characteristics due to CURRENT flow through the material.
MARKET OPERATOR
An ENTITY that administers a market that integrates CAPACITY, ENERGY, BALANCING RESOURCES,
and TRANSMISSION RESOURCES to achieve an economic, reliability-constrained dispatch of
RESOURCES.
MARKET PARTICIPANT
An entity participating in the ENERGY marketplace by buying/selling TRANSMISSION rights,
ENERGY, or ANCILLARY SERVICES into, out of, or through an ISO-controlled GRID.
MARKETER
An entity that has the authority to take title to electrical POWER generated by itself or another
entity and remarket that POWER at market-based rates.
MECHANICAL ENERGY
ENERGY of a mechanical nature. For example, a rotating mass possesses mechanical energy.
MEGAWATTHOUR (MWh)
One million WATTHOURS.
METERED VALUE
A measured electrical quantity that may be collected by TELEMETERING, SCADA, or other means.
METERING
A device for measuring a quantity. For example, meters are used to measure POWER flows,
VOLTAGES, CURRENT, FREQUENCY, etc.
A-38
12422963
Glossary
MICROPROCESSOR
An arithmetic, logic, and control unit all contained on one integrated CIRCUIT chip. One
microprocessor will contain thousands of transistors.
MILL
A unit of currency equal to 1/10 of a cent.
MISOPERATION
• Any failure of a PROTECTION SYSTEM ELEMENT to operate within the specified time
when a FAULT or abnormal condition occurs within a ZONE OF PROTECTION.
• Any operation for a FAULT not within a ZONE OF PROTECTION (other than operation as
backup protection for a FAULT in an adjacent zone that is not cleared within a specified
time for the protection for that zone).
• Any unintentional PROTECTION SYSTEM operation when no FAULT or other abnormal
condition has occurred unrelated to on-site maintenance and testing activity.
MODE
A specific oscillation FREQUENCY. For example, a steam/TURBINE GENERATOR’s shaft has
specific frequencies at which it is susceptible to SSR. These frequencies are called modes.
MONOPOLAR HVDC
An HVDC SYSTEM that uses one CONDUCTOR energized with either a positive or negative
VOLTAGE and a CURRENT return path.
MOTOR LOAD
A simplified grouping of all spinning type LOAD. Motor load includes air conditioner
COMPRESSORS, motor drives, etc. TOTAL LOAD is composed of motor load plus NON-MOTOR
LOAD.
MRO
Acronym for the Midwest Reliability Organization. MRO is one of the eight NERC REGIONAL
RELIABILITY ORGANIZATIONs.
MUST-RUN GENERATION
GENERATION designated to operate at a specific level and not available for dispatch.
NAESB
The acronym for the North American Energy Standards Board. NAESB is responsible for
business practice standards in the wholesale electric ENERGY industry.
A-39
12422963
Glossary
NATURAL FREQUENCY
Every mechanical device has a natural frequency of oscillation. For example, when a force is
applied to a bridge the bridge will oscillate at its natural frequency. ELECTRICAL CIRCUITS also
have a natural frequency of oscillation. An ELECTRICAL CIRCUIT’s natural frequency is determined
by its RESISTANCE, INDUCTANCE, and CAPACITANCE.
NERC
An acronym for the North American Electric Reliability Corporation. The purpose of NERC is to
enhance the RELIABILITY of the interconnected POWER SYSTEMS of North America. NERC
publishes RELIABILITY Standards that provide requirements as to how to reliably operate the
POWER SYSTEM.
NET GENERATION
The net POWER available from a GENERATOR to be fed to the POWER SYSTEM. Net generation is
equal to GROSS GENERATION minus the GENERATOR’s internal POWER usage (STATION SERVICE).
NETWORK CUSTOMER
An entity receiving TRANSMISSION SERVICE pursuant to the terms of the TRANSMISSION SERVICE
PROVIDER’s NETWORK INTEGRATION TRANSMISSION SERVICE.
NETWORK RESOURCE
Any designated generating resource owned, or purchased or leased by a NETWORK CUSTOMER
under the NETWORK INTEGRATION TRANSMISSION SERVICE Tariff. Network RESOURCES do not
include any resource, or any portion thereof, that is committed for sale to third PARTIES or
otherwise cannot be called upon to meet the NETWORK CUSTOMER’s Network LOAD on a non-
interruptible basis.
A-40
12422963
Glossary
NOAA
The acronym for the National Oceanic and Atmospheric Administration of the U.S. Government.
NOMINAL
The design or rated value. Not necessarily the value that is intended or that occurs. For example,
the nominal VOLTAGE for a piece of EQUIPMENT would be the design or rated VOLTAGE but in
operation the EQUIPMENT may be operated at a different value of VOLTAGE.
NOMINAL LOAD
The rated or nameplate LOAD. For example, 100 MW of customer LOAD may be fed from a utility
BUS. This LOAD will draw 100 MW if the VOLTAGE and FREQUENCY at the BUS are at NOMINAL
values. If VOLTAGE or FREQUENCY should vary then the ACTUAL LOAD will be different than the
nominal load.
NON-FIRM ENERGY
ELECTRICAL ENERGY that may be interrupted by either the provider or the receiver of the ENERGY
by giving advance notice to the other party to the TRANSACTION. This advance notice PERIOD is
equal to or greater than the minimum PERIOD agreed to in the contract. Non-firm energy may also
be interrupted to maintain SYSTEM RELIABILITY of third-party TRANSMISSION SERVICE
PROVIDERS. Non-firm energy must be backed up by reserves.
NON-MOTOR LOAD
A simplified grouping of all non-spinning type LOAD. Non-motor load includes resistive heaters,
lighting, etc. TOTAL LOAD is composed of MOTOR LOAD plus non-motor type LOAD.
NON-SPINNING RESERVE
1. That generating reserve not connected to the system but capable of serving DEMAND within a
specified time. 2. INTERRUPTIBLE LOAD that can be removed from the system in a specified time.
NORMAL CLEARING
A PROTECTION SYSTEM operates as designed and the FAULT is cleared in the time normally
expected with proper functioning of the installed PROTECTION SYSTEMS.
NORMAL EXCITATION
A condition in which the GENERATOR’s EXCITATION SYSTEM is supplying exactly the excitation
CURRENT needed to maintain the MAGNETIC FIELD of the GENERATOR. A normally excited
GENERATOR is neither supplying or absorbing REACTIVE POWER from the SYSTEM.
A-41
12422963
Glossary
NORMAL RATING
The RATING as defined by the EQUIPMENT owner that specifies the level of electrical loading,
usually expressed in megawatts (MW) or other appropriate units that a SYSTEM, FACILITY, or
ELEMENT can support or withstand through the daily DEMAND CYCLES without loss of EQUIPMENT
life.
NPCC
Acronym for the Northeast Power Coordinating Council. NPCC is one of the eight NERC
REGIONAL RELIABILITY ORGANIZATIONS.
OFF-PEAK
Those hours or other PERIODs defined by NAESB business practices, contract, AGREEMENTs, or
guides as PERIODs of lower electrical DEMAND.
ON-PEAK
Those hours or other PERIODs defined by NAESB business practices, contract, AGREEMENTs, or
guides as PERIODs of higher electrical DEMAND.
OHM’S LAW
A basic electrical law that relates the VOLTAGE (V), CURRENT (I), and IMPEDANCE (Z). Ohm’s law
is commonly stated as:
V =I×Z
A-42
12422963
Glossary
OPERATING AUTHORITY
An entity that:
1. Has ultimate accountability for a defined portion of the BULK ELECTRIC SYSTEM to meet
one or more of three RELIABILITY objectives – GENERATION/DEMAND balance,
TRANSMISSION security, and/or EMERGENCY preparedness; and
2. Is accountable to NERC and its REGIONAL RELIABILITY ORGANIZATIONS for complying
with NERC and Regional Policies; and
3. Has the authority to control or direct the operation of generating RESOURCES,
TRANSMISSION facilities, or LOADS, to meet these Policies.
OPERATING PROCEDURE
A document that identifies specific steps or tasks that should be taken by one or more specific
operating positions to achieve specific operating goal(s). The steps in an Operating Procedure
should be followed in the order in which they are presented, and should be performed by the
position(s) identified. A document that lists the specific steps for a SYSTEM OPERATOR to take in
removing a specific TRANSMISSION LINE from service is an example of an Operating Procedure.
OPERATING RESERVE
That capability above firm SYSTEM DEMAND required to provide for REGULATION, LOAD
forecasting error, EQUIPMENT forced and SCHEDULED OUTAGES and local area protection. It
consists of SPINNING and NON-SPINNING RESERVE.
• LOAD fully removable from the SYSTEM within the DISTURBANCE RECOVERY PERIOD
following the CONTINGENCY event.
OSCILLATIONS
Cyclic variations in VOLTAGE, CURRENT, FREQUENCY, or POWER flows. The VOLTAGE and
CURRENT of the POWER SYSTEM naturally oscillates at 60 HZ. The term oscillations is typically
used to refer to low FREQUENCY (a few HZ) oscillations that may occur.
A-43
12422963
Glossary
OUT-OF-STEP (OOS)
To lose synchronism. Out-of-step is best viewed in terms of rotating MAGNETIC FIELDs. When a
GENERATOR is out-of-step with the POWER SYSTEM it connects to, the GENERATOR’s rotating
MAGNETIC FIELD is no longer in-step or in synchronism with the rotating MAGNETIC FIELD of the
SYSTEM.
OUTAGE
The PERIOD during which a generating unit, TRANSMISSION line, or other FACILITY is out of
service.
OVERCURRENT RELAY
A PROTECTIVE RELAY that activates in response to a high CURRENT magnitude. Overcurrent relays
can be either timed or instantaneous and directional or non-directional.
OVEREXCITE
A GENERATOR is overexcited when the applied excitation is greater than that needed to support the
GENERATOR’s MAGNETIC FIELD. The excess REACTIVE POWER produced by the overexcitation
condition flows to the SYSTEM. An overexcited GENERATOR supplies REACTIVE POWER to the
SYSTEM. The terms “LAGGING” and “boosting” are also used to refer to an overexcited
GENERATOR. A TRANSFORMER may also overexcite. Overexcitation of a TRANSFORMER results
from either applying to high a VOLTAGE magnitude or operating at to low of a FREQUENCY.
A-44
12422963
Glossary
PARALLEL CIRCUIT
An ELECTRICAL CIRCUIT in which all the positive terminals are connected to a common point. All
the negative terminals are connected to a second point. The VOLTAGE drop is the same across
each full ELEMENT of the parallel circuit.
PARALLEL RESONANCE
A RESONANCE condition in a CIRCUIT with a parallel combination of INDUCTANCE and a
CAPACITANCE. At RESONANCE a PARALLEL CIRCUIT REACHes its maximum IMPEDANCE equal to a
multiple of the CIRCUIT’s RESISTANCE value.
PARKING
Parking is a commercial term that defines ENERGY or TRANSMISSION that is not complete. The
TRANSACTION SINK, SOURCE, and path are identified when tagged – prior to TRANSACTION
implementation. The priority of the TRANSACTION is also identified when tagged. The merchant
buys a “link” of the final TRANSMISSION path and “parks” the GENERATION without identifying
SOURCE or SINK (but must show POR and POD). The merchant can also buy a “link” of ENERGY
and park it. The ATC for a parked TRANSACTION should be decremented – there is an impact on a
FLOWGATE, but it is not calculated until the SOURCE and SINK are known. Parking applies to both
firm and NON-FIRM ENERGY and TRANSMISSION.
PARTICIPATION FACTOR
Typically used to refer to generator participation in a facilities loading
• For example, assume a transmission line is overloaded
• Further assume Generator “A” has a 0.3 participation factor
• This means that Generator “A” is responsible for 0.3 or 30% of the overloaded line’s
flow
PARTIES
The TRANSMISSION SERVICE PROVIDER and TRANSMISSION CUSTOMER receiving service under the
Tariff.
A-45
12422963
Glossary
PEAK DEMAND
1. The highest hourly integrated NET ENERGY FOR LOAD within a BALANCING AUTHORITY
occurring within a given PERIOD (e.g., day, month, season, or year). 2. The highest
INSTANTANEOUS DEMAND within the BALANCING AUTHORITY.
PEAKING CAPACITY
CAPACITY used to serve PEAK DEMAND. PEAKING GENERATING UNITS operate a limited number of
hours per year, and their CAPACITY FACTOR is normally less than 20%.
PENSTOCK
A water pipe or conduit that carries water from the upper water reservoir to the TURBINE at a
hydroelectric unit.
PERIOD
The time for one complete CYCLE of a repeating wave. For example, a 60 HZ CURRENT steps
through 60 CYCLES per second. The period of one complete CYCLE is therefore 1/60th of a second.
PER-UNIT (P.U.)
A SYSTEM for reporting quantity magnitudes. A per-unit number is stated in terms of a base
quantity. For example if the base VOLTAGE is 345 kV then a VOLTAGE of 359 kV is 1.04 per-unit
(359/345=1.04).
PHASE
AC POWER SYSTEMs use three CONDUCTORS to efficiently generate and transmit large amounts of
POWER. Each of the CONDUCTORS is called a phase. The phases are each assigned a letter
designation; “A”, “B”, and “C”. Customer LOAD can be connected as single-phase (1Φ), two-
phase (2Φ), or three-phase (3Φ).
PHASE ANGLE
The angle by which one waveform leads or lags another waveform. A phase angle can exist
between two VOLTAGEs, two CURRENTS, or between a CURRENT and a VOLTAGE.
A-46
12422963
Glossary
PHASORS
Similar to a vector but also includes information about the FREQUENCY of the quantity. A phasor
diagram is a collection of lines that, like VECTORS, illustrate a quantities magnitude and direction.
However, phasor diagrams must also specify the FREQUENCY of the quantity. AC VOLTAGES and
CURRENTS can be represented by phasors.
PICK-UP POINT
An operating setting for a PROTECTIVE RELAY that determines at what point the RELAY will
activate.
PILOT RELAY
A PROTECTIVE RELAY SYSTEM typically used to protect high VOLTAGE TRANSMISSION LINES. Pilot
relays use telecommunication SYSTEMS to communicate between the terminals of the
TRANSMISSION line.
PLANNED OUTAGE
An OUTAGE that is planned well in advance.
PLANNING
The process by which the performance of the electric SYSTEM is evaluated and future changes and
additions to the BULK ELECTRIC SYSTEMS are determined.
PLANNING AUTHORITY
The responsible entity that coordinates and integrates TRANSMISSION FACILITY and service plans,
resource plans, and protection systems.
PLANNING RESERVE
The difference between an entity’s expected annual peak capability and its expected annual PEAK
DEMAND expressed as a percentage of the annual PEAK DEMAND.
A-47
12422963
Glossary
POLES
The ELECTRICAL CIRCUITS formed by the FIELD WINDING on the ROTOR of a SYNCHRONOUS
GENERATOR. When DC CURRENT is passed through the FIELD WINDING the poles become
magnetic north or south poles.
POTENTIAL DIFFERENCE
A difference in VOLTAGE magnitudes between two locations. CURRENT can flow along a closed
path if a potential difference exists across the path.
POWER (P)
The rate at which ENERGY is expended to do work. Power is measured in watts (W), kilowatts
(kW), Megawatts (MW), or Gigawatts (GW).
POWER CONVERTER
A mechanical or solid state device for converting AC POWER to DC POWER or vice versa. Modern
power converters are THYRISTER based devices that are typically strong sources of HARMONICS.
POWER POOL
Two or more interconnected electric SYSTEMs planned and operated to supply POWER for their
combined DEMAND requirements.
POWER SYSTEM
The collective name given to the ELEMENTS of the electrical SYSTEM. The power system includes
the GENERATION, TRANSMISSION, DISTRIBUTION, SUBSTATIONS, etc. The term power system may
refer to one section of a large INTERCONNECTED SYSTEM or to the entire INTERCONNECTED
SYSTEM.
A-48
12422963
Glossary
POWER-ANGLE CURVE
A graphical representation of the ACTIVE POWER transfer equation. The power-angle curve is a
plot of the ACTIVE POWER transfer as the POWER ANGLE is varied between 0° and 180°. The
power-angle curve is a good tool for analyzing the ANGLE STABILITY of a simple (two BUS) POWER
SYSTEM.
POWER-CIRCLE DIAGRAM
A graphical method of illustrating how MW and Mvar flows change as the POWER ANGLE
changes. Power-circle diagrams are composed of circular characteristics of the POWER flow out of
the sending end and into the receiving end of a two BUS SYSTEM.
PRIMARY WINDING
The winding of a TRANSFORMER that is connected to the POWER input or SOURCE end of the
TRANSFORMER.
PRIME MOVER
A mechanism that converts thermal or hydraulic ENERGY into mechanical POWER. For example, a
coal fired BOILER with a steam TURBINE is a prime mover as it converts the thermal ENERGY of
coal into the mechanical POWER to turn the TURBINE.
PRODUCTION COST
The costs associated with starting, operating, and stopping generating units.
PROTECTION SYSTEM
PROTECTIVE RELAYS, associated communication systems, VOLTAGE and CURRENT sending
devices, station batteries and DC control circuitry.
PROTECTIVE RELAY
A mechanical or electronic device used to sense POWER SYSTEM DISTURBANCES and respond to
limit the possible damage.
A-49
12422963
Glossary
PSEUDO-TIE
A telemetered reading or value that is updated in real time and used as a “virtual” tie line flow in
the AGC/ACE equation but for which no physical tie or energy METERING actually exists. The
integrated value is used as a metered MWh value for INTERCHANGE accounting purposes.
P-V CURVE
A POWER versus VOLTAGE curve. A plot of the POWER transferred to a BUS versus the VOLTAGE at
that BUS. P-V curveS are a graphical tool used to analyze a POWER SYSTEM’s VOLTAGE STABILITY.
PYTHAGOREAN THEOREM
A mathematical relationship which states that in a RIGHT TRIANGLE the square of the HYPOTENUSE
length is equal to the sum of the squares of the lengths of the remaining two sides.
QUADRATURE (Q)
At an angle of 90°. When two VECTORS are in quadrature they are perpendicular to one another.
The symbol “Q” for REACTIVE POWER is derived from the word Quadrature.
QUALITY (Q)
A factor for measuring the FREQUENCY RESPONSE of an ELECTRICAL CIRCUIT. A CIRCUIT’s quality
is dependent upon the relative magnitudes of its reactive and resistive ELEMENTS.
RAMP PERIOD
The time between GENERATION ramp start and end times usually expressed in minutes.
RAMP RATE
(SCHEDULE) The rate, expressed in megawatts per minute, at which the INTERCHANGE SCHEDULE
is attained during the RAMP PERIOD.
(GENERATOR) The rate, expressed in megawatts per minute, that a GENERATOR changes its output.
RAMP WINDOW
The time PERIOD that occurs each hour for adjusting a BALANCING AUTHORITY’s GENERATION. A
typical ramp window is from 10 minutes to the hour till 10 minutes after the hour. If all
BALANCING AUTHORITIES use the same ramp windows, FREQUENCY DEVIATIONS will be reduced.
RATE BASE
The value of property upon which a utility is permitted to earn a specified rate of return as
established by a regulatory authority. The rate base generally represents the value of property
used by the utility in providing service and may be calculated by any one or a combination of the
following accounting methods: fair value, prudent investment, reproduction cost, or original cost.
Depending on which method is used, the rate base includes cash, working capital, materials and
supplies, and deductions for accumulated provisions for depreciation, contributions in aid of
A-50
12422963
Glossary
construction, customer advances for construction, accumulated deferred income taxes, and
accumulated deferred investment tax credits.
RATING
The operational limits of a TRANSMISSION SYSTEM ELEMENT under a set of specified conditions.
REACH
The extent of protection that an IMPEDANCE RELAY provides to a TRANSMISSION line. The reach is
typically defined in terms of the IMPEDANCE of the line. For example, a zone #1 IMPEDANCE
RELAY may reach 85% into the protected line.
REACTION TURBINE
A water TURBINE in which the pressure difference across the TURBINE BLADEs causes the BLADEs
to turn. A Francis TURBINE is an example of a reaction turbine.
REACTOR
A device intentionally designed to act as an inductor and store ENERGY in its MAGNETIC FIELD. A
shunt reactor acts as a SINK (absorber) of REACTIVE POWER from the SYSTEM. Series reactors are
devices that are used to increase the INDUCTIVE REACTANCE (XL) of a TRANSMISSION path.
REAL POWER
The portion of electricity that supplies ENERGY to the LOAD. Real Power is sometimes called
ACTIVE POWER.
REAL-TIME
Present time as opposed to future time. (From INTERCONNECTION RELIABILITY OPERATING
LIMITS standard.)
A-51
12422963
Glossary
REAL-TIME OPERATIONS
The instantaneous operations of a POWER SYSTEM as opposed to those operations that are
simulated.
RECLOSING RELAY
A RELAY that automatically (after a few CYCLES or a few seconds) recloses a TRANSMISSION line
following a FAULT.
RECTIFIER
An HVDC CONVERTER operated to convert AC POWER to DC POWER.
REGION
One of the NERC REGIONAL RELIABILITY ORGANIZATIONS.
REGULATING RESERVE
An amount of reserve responsive to AUTOMATIC GENERATION CONTROL, which is sufficient to
provide normal regulating MARGIN.
A-52
12422963
Glossary
REGULATING TRANSFORMER
A TRANSFORMER used to regulate VOLTAGE or PHASE ANGLE. Conventional tap changing (ULTC)
TRANSFORMERS and PHASE SHIFTING TRANSFORMERS (PSTs) are regulating transformers.
REGULATING UNIT
A GENERATOR used for the REGULATION of SYSTEM FREQUENCY. To serve as a regulating unit the
GENERATOR must have available SPINNING RESERVE.
REGULATION
The ability to maintain a quantity within acceptable limits. For example, FREQUENCY
REGULATION is the control or regulation of the SYSTEM FREQUENCY to within a tight BANDWIDTH
of 60 HZ. VOLTAGE regulation is the control of a VOLTAGE level within a set BANDWIDTH.
REGULATION SERVICE
The process whereby one BALANCING AUTHORITY contracts to provide corrective response to all
or a portion of the ACE of another BALANCING AUTHORITY. The BALANCING AUTHORITY
providing the response assumes the obligation of meeting all applicable control criteria as
specified by NERC for itself and the BALANCING AUTHORITY for which it is providing the
Regulation Service.
RELATIVE ACCELERATION
For TORQUE and POWER ANGLEs to change, a relative acceleration must exist for a PERIOD of time.
One part of the SYSTEM must accelerate with respect to another part. Once relative acceleration
occurs, any speed difference that has developed will continue the increase or decrease in TORQUE
or POWER ANGLES. TORQUE and POWER ANGLES will not stop changing until all sections of the
SYSTEM are running at the same FREQUENCY.
RELAY
A electrical or mechanical device that responds to a measured input with a user determined output.
Types of RELAYS include AUXILIARY RELAYS, monitoring RELAYS, regulating RELAYS, and
PROTECTIVE RELAYS.
RELIABILITY
The degree of performance of the ELEMENTS of the BULK ELECTRIC SYSTEM that results in
electricity being delivered to customers within accepted standards and in the amount desired.
Reliability may be measured by the FREQUENCY, duration, and magnitude of adverse effects on the
electric supply.
A-53
12422963
Glossary
REPORTABLE DISTURBANCE
Any event that causes an ACE change greater than or equal to 80% of a BALANCING AUTHORITY’s
or RESERVE SHARING GROUP’s most severe CONTINGENCY. The definition of a reportable
disturbance is specified by each REGIONAL RELIABILITY ORGANIZATION. This definition may not
be retroactively adjusted in response to observed performance.
RERATING
A change in the capability of a GENERATOR due to a change in conditions such as age, upgrades,
auxiliary EQUIPMENT, cooling, etc.
RESISTANCE (R)
The property of a material that opposes or resists CURRENT flow by converting electric ENERGY to
heat. The symbol for resistance is the letter “R”.
RESISTIVITY
A measure of the ability of a material to conduct electricity. The greater the resistivity, the greater
the opposition to CURRENT flow. An INSULATOR has a high resistivity.
A-54
12422963
Glossary
RESONANCE
In an ELECTRICAL CIRCUIT, resonance is achieved when the magnitudes of the inductive and
capacitive ELEMENTS match. Resonance may be achieved by inputting ENERGY at the CIRCUIT’s
RESONANT FREQUENCY or by varying the size of the inductive or capacitive ELEMENTS. A radio
receiver is tuned to resonance at the channel the operator wants to receive.
RESONANT
To achieve RESONANCE.
1
FR =
2π LC
RESOURCE PLANNER
The entity that develops a long-term (generally one year and beyond) plan for the resource
ADEQUACY of specific LOADs (customer DEMAND and energy requirements) within a PLANNING
AUTHORITY Area.
RESOURCES
Resources is typically used to refer to available GENERATION. For example, LOAD must match
resources to maintain FREQUENCY.
RESPONSE RATE
The RAMP RATE that a generating unit can achieve under normal operating conditions expressed
in megawatts per minute (MW/Min.).
RESPONSIVE RESERVES
Reserve CAPACITY that is available to respond to SYSTEM FREQUENCY DISTURBANCES.
RESTORATION
The process of returning GENERATORs and TRANSMISSION SYSTEM ELEMENTS and restoring LOAD
FOLLOWING an OUTAGE on the electric SYSTEM.
RESTRIKE
The re-ignition of an electric ARC.
RFC
Acronym for the Reliability First Corporation. RFC is one of the eight NERC RROs.
A-55
12422963
Glossary
RIGHT-OF-WAY (ROW)
A corridor of land on which electric lines may be located. The TRANSMISSION OWNER may own
the land in fee, own an easement, or have certain franchise, prescription, or license rights to
construct and maintain lines.
RIGHT TRIANGLE
A triangle in which one of the three internal angles is equal to 90°.
ROTATIONAL ENERGY
ENERGY stored within a rotating mass. For example, a spinning GENERATOR contains rotational
energy. The terms INERTIAL ENERGY, STORED ENERGY, and rotational energy are often used
interchangeably to refer to the ENERGY stored in the rotating ELEMENTS (motors and GENERATORS)
of the POWER SYSTEM.
ROTOR
The rotating component of a motor or GENERATOR.
RUNNER
The rotating ELEMENT of a hydro TURBINE.
SATURATION
After a MAGNETIC FIELD REACHes a certain strength, any further increase in the CURRENT that
caused the MAGNETIC FIELD will not result in any increase in the strength of the MAGNETIC FIELD.
The magnetic material is saturated at this point. When a TRANSFORMER becomes saturated, the
CORE’s MAGNETIC FIELD will expand and link portions of the TRANSFORMER not designed for
exposure to an alternating MAGNETIC FIELD. TRANSFORMER thermal problems may result.
SCENARIO
Possible event.
SCHEDULE (noun)
An INTERCHANGE schedule.
SCHEDULE (verb)
To set up a plan or arrangement for an INTERCHANGE TRANSACTION.
SCHEDULE PERIOD
The length of time between the NOMINAL starting and ending time of each SCHEDULE.
A-56
12422963
Glossary
SCHEDULED
The desired or TARGET value. For example, for a 345 kV BUS, the Scheduled value of VOLTAGE
may be 358 kV. SYSTEM OPERATORs would try to hold this BUS VOLTAGE at 358 kV.
SCHEDULED FREQUENCY
60.0 HERTZ, except during a time correction.
SCHEDULED INTERCHANGE
Electric POWER SCHEDULED to flow between entities, usually the net of all sales, purchases, and
WHEELING TRANSACTIONs between those areas at a given time.
SCHEDULING PATH
The TRANSMISSION SERVICE arrangements reserved by the PURCHASING-SELLING ENTITY for a
TRANSACTION.
SCROLL CASE
A spiral-shaped steel intake guiding the flow of water into the WICKET GATES located just prior to
the TURBINE of a hydro-electric FACILITY.
SCRUBBER
A pollution CONTROL SYSTEM used in fossil fuel units for removing sulfur from the exhaust gases.
SEAMS
The boundaries between adjacent electricity-related organizations. Differences in regulatory
requirements or operating practices may create “seams problems”.
SECONDARY WINDING
The winding of a TRANSFORMER that is connected to the POWER output or LOAD end of the
TRANSFORMER.
SECTIONALIZING
The process of reducing the LOAD on a DISTRIBUTION feeder using switching actions.
SELF-EXCITATION
A possible operating condition for a GENERATOR in which the CHARGING CURRENT from a high
VOLTAGE TRANSMISSION SYSTEM takes over as the excitation CURRENT SOURCE of the
GENERATOR. Self-excitation is a dangerous condition as high VOLTAGES can develop in the
GENERATOR and in the GENERATOR auxiliaries.
A-57
12422963
Glossary
SERC
Acronym for the Southeastern Electric Regional Reliability Council. SERC is one of the eight
NERC REGIONAL RELIABILITY ORGANIZATIONS.
SERIES CIRCUIT
ELECTRICAL CIRCUIT in which ELEMENTS are connected end to end. The same CURRENT flows
through each ELEMENT of a series circuit.
SERIES RESONANCE
A RESONANCE condition in a CIRCUIT with a series combination of INDUCTANCE and
CAPACITANCE. At RESONANCE a SERIES CIRCUIT REACHes its minimum IMPEDANCE equal to the
CIRCUIT’s RESISTANCE value.
SERVOMOTOR
A device used to create a force based on a control signal input. For example, in a GOVERNOR
CONTROL SYSTEM a control signal is first developed using a control VALVE. The control signal is
input to a servomotor. The servomotor then drives steam VALVES, WICKET GATES, etc. The
servomotor may be an electric motor, an hydraulic piston, or any other means of developing a
force.
SHIELD WIRES
CONDUCTORS strung across the top of TRANSMISSION LINES that are designed to protect the
TRANSMISSION line from lightning strikes.
SHORT CIRCUIT
The introduction of a low IMPEDANCE path between CONDUCTORS energized at different
VOLTAGES. A short circuit is the same as a FAULT.
SINE
The sine of either of the unknown angles of a RIGHT TRIANGLE is the ratio of the side directly
opposite the unknown angle to the HYPOTENUSE.
A-58
12422963
Glossary
SINEWAVE
A quantity that continually repeats itself. For example, AC VOLTAGE and CURRENT are sinewaves.
The wave shape for the COSINE function is the same as the SINE function but with a 90° PHASE
ANGLE difference.
SINGLE CONTINGENCY
The sudden, unexpected failure or OUTAGE of a SYSTEM FACILITY(ies) or ELEMENTS(s) (generating
unit, TRANSMISSION line, TRANSFORMER, etc.). ELEMENTS removed from service as part of the
operation of a REMEDIAL ACTION SCHEME are considered part of a single CONTINGENCY.
SINK
Final POINT OF DELIVERY for the TRANSACTION: the ACTUAL LOAD.
SIX-PULSE CONVERTER
An HVDC CONVERTER that has six pulses to the DC output VOLTAGE for each CYCLE of the AC
supply VOLTAGE.
SLIDING PRESSURE
A method of operation available in some thermal units. Normally a unit’s steam VALVES are
adjusted to control the amount of steam sent to the TURBINE stages. In a sliding pressure MODE of
operation, the steam VALVES are operated wide open to minimize VALVE throttling LOSSES. The
BOILER pressure is then varied to adjust the MW output of the unit.
SLIP
The difference between the SYNCHRONOUS SPEED of an induction motor and the speed at which its
ROTOR actually rotates.
SLIP-RINGS
Metal rings attached to the shaft of a SYNCHRONOUS MACHINE. The ROTOR’s FIELD WINDING
terminates on the inner surface of the slip-rings while the BRUSHes ride on the smooth outer
surface of the slip-rings.
SMOOTHING REACTOR
A series REACTOR attached to an HVDC TRANSMISSION line that smoothes the ripple of an HVDC
CONVERTER’s DC output VOLTAGE and assists with the POWER conversion process.
SOFTWARE
A series of instructions written to enable computer hardware to perform useful tasks.
A-59
12422963
Glossary
SOLENOID
An electro-magnet that, when energized, is used to perform a mechanical function such as opening
a switch.
SOLID-STATE RELAY
A RELAY that uses semiconductor components.
SOURCE
The INITIAL POINT OF RECEIPT for the TRANSACTION: the actual GENERATION FACILITY.
SPINNING RESERVE
Unloaded GENERATION that is SYNCHRONIZEd and ready to serve additional DEMAND.
SPP
Acronym for the Southwest Power pool. SPP is one of the eight NERC REGIONAL RELIABILITY
ORGANIZATIONS.
STABILITY
The ability of an electric SYSTEM to maintain a state of equilibrium during normal and abnormal
SYSTEM conditions or DISTURBANCES.
STABILITY LIMIT
The maximum POWER flow possible through some particular point in the SYSTEM while
maintaining STABILITY in the entire SYSTEM or the part of the SYSTEM to which the stability limit
refers.
A-60
12422963
Glossary
STATION
A location in an electrical network where one or more ELEMENTS are connected. Examples
include generating stations and SUBSTATIONS.
STATION SERVICE
The electric supply for the ancillary EQUIPMENT used to operate a generating STATION or
SUBSTATION.
STATOR
The stationary component of a motor or GENERATOR.
STORAGE
ENERGY transferred from one entity to another entity that has the ability to conserve the ENERGY
(that is, stored as water in a reservoir, coal in a pile, etc.) with the intent that the ENERGY will be
returned at a time when such ENERGY is more useable to the original supplying entity.
STORED ENERGY
ENERGY stored within a rotating mass. For example, a spinning GENERATOR contains stored
energy. The terms INERTIAL ENERGY, stored energy, and ROTATIONAL ENERGY are often used
interchangeably to refer to the ENERGY stored in the rotating ELEMENTS (motors and GENERATORs)
of the POWER SYSTEM.
A-61
12422963
Glossary
SUBREGION
A portion of a REGIONAL RELIABILITY ORGANIZATION.
SUBSTATION
An ELEMENT of the POWER SYSTEM that contains CIRCUIT BREAKERS, DISCONNECT SWITCHES,
TRANSFORMERS, REACTORS, CAPACITORS, and other EQUIPMENT. A central control house is often
provided to house control and protective EQUIPMENT.
SUBSYNCHRONOUS
A FREQUENCY below SYNCHRONOUS SPEED.
SUBTRANSMISSION
A functional or VOLTAGE classification relating to lines at VOLTAGE levels between the
DISTRIBUTION and TRANSMISSION levels.
SUNSPOTS
Large dark colored patches on the surface of the sun. Sunspots are a consequence of ENERGY
DISTURBANCES on the surface of the sun.
SUPERCRITICAL BOILER
A BOILER SYSTEM that is operated at a much higher temperature and pressure than a conventional
drum type BOILER. Supercritical BOILERs are also called “once through” type BOILERs. A
supercritical BOILER does not have any significant steam STORAGE, which affects its response to
governor commands.
SUPERSYNCHRONOUS
A FREQUENCY above SYNCHRONOUS SPEED.
SUPERVISORY CONTROL
A form of remote control comprising an arrangement for the selective control of remotely located
facilities by an electrical means over one or more communication media.
A-62
12422963
Glossary
SURGE
A TRANSIENT variation of CURRENT, VOLTAGE, or POWER flow in an electric CIRCUIT or across an
electric SYSTEM.
SWITCHING ORDER
A sequence of steps to accomplish a desired switching action.
SWITCHING PROCESS
The process by which the status (open, closed, etc.) of POWER SYSTEM EQUIPMENT (switches,
CIRCUIT BREAKERS, etc.) is adjusted to perform maintenance or enhance operations.
SWITCHING STATION
POWER SYSTEM EQUIPMENT used to tie together two or more electric CIRCUITS through switches.
The switches are selectively arranged to permit a CIRCUIT to be disconnected, or to change the
electric connection between the CIRCUITS.
SWITCHING SURGE
The sudden changes to VOLTAGE and CURRENT waveforms that accompany TRANSMISSION
SYSTEM switching events.
SYNCHRONIZE
The process to bring two electrical SYSTEMS together by closing a CIRCUIT BREAKER.
SYNCHRONOUS
To be in-step with a reference. A synchronous GENERATOR rotates in synchronism with the
POWER SYSTEM.
SYNCHRONOUS CONDENSER
A SYNCHRONOUS MACHINE that operates as a SYNCHRONOUS motor. The MW to turn the
machine’s shaft is drawn from the POWER SYSTEM. The full capabilities of the machines
EXCITATION SYSTEM (to absorb and supply MVAR) are then available for VOLTAGE CONTROL
purposes. Hydroelectric GENERATORS can often be operated in synchronous condenser MODE.
The unit’s water TURBINE is typically de-watered and the unit’s ROTOR turned as if it were a
motor.
A-63
12422963
Glossary
SYNCHRONOUS MACHINE
An AC machine whose ROTOR rotates in synchronism with the POWER SYSTEM to which it is
attached. Synchronous machines can be either GENERATORS or motors. A synchronous machine
also includes a SOURCE of DC excitation CURRENT (the EXCITATION SYSTEM).
SYNCHRONOUS SPEED
The speed at which a SYNCHRONOUS GENERATOR must rotate in order to stay in synchronism with
the rotating MAGNETIC FIELD of the SYSTEM. The synchronous speed is determined by the
FREQUENCY of the POWER SYSTEM and the number of ROTOR magnetic POLES.
SYNCHROSCOPE
A device for comparing the FREQUENCY difference and VOLTAGE ANGLE across an open CIRCUIT
BREAKER.
SYSTEM
A combination of GENERATION, TRANSMISSION, and DISTRIBUTION components comprising an
ELECTRIC UTILITY, or group of utilities.
SYSTEM OPERATOR
An individual at a CONTROL CENTER (BALANCING AUTHORITY, TRANSMISSION OPERATOR,
GENERATOR OPERATOR, RELIABILITY COORDINATOR) whose responsibility it is to monitor and
control that electric system in real time.
SYSTEM PERSONNEL
Those people who have the capability to affect SYSTEM operations and who must abide by the
authority vested in the SYSTEM OPERATOR. May include POWER plant operators, SYSTEM
maintenance personnel, POWER schedulers, POWER MARKETERS, etc.
TAG
Refers to the collection of information in the electronic request for an ENERGY SCHEDULE and
subsequent responses utilized in the electronic Transaction Information System (TIS)
implemented by NERC.
A-64
12422963
Glossary
TAPS
Fixed electrical contacts at different positions on a TRANSFORMER’s winding. Taps are adjusted to
change the VOLTAGE RATIO of a TRANSFORMER.
TARGET
An indicator on a RELAY that is displayed when the RELAY operates. The term “flag” is often used
to refer to a target.
TELEMETERING
The process by which measurable electrical quantities from SUBSTATIONS and generating
STATIONs are instantaneously transmitted to the CONTROL CENTER, and by which operating
commands from the CONTROL CENTER are transmitted to the SUBSTATIONS and generating
STATIONs.
TELEMETRY
EQUIPMENT for measuring a quantity (amps, volts, MW, etc.) and transmitting the result via a
telecommunication SYSTEM (radio, microwave, etc.) to a remote location for indication or
recording.
TERTIARY WINDING
An additional winding added to a POWER TRANSFORMER. The tertiary winding may be used to
connect a REACTOR, CAPACITOR, or to provide STATION SERVICE.
THERMAL LIMIT
A POWER flow limit based on the possibility of damage by heat. Heating is caused by the
electrical LOSSES which are equal to I2R.
THERMAL RATING
The maximum amount of electrical CURRENT that a TRANSMISSION line or electrical FACILITY can
conduct over a specified time PERIOD before it sustains permanent damage by overheating or
before it sags to the point that it violates public safety requirements.
THETA (q)
A Greek symbol used to indicate an angular measurement.
THRUST BEARING
The bearing that opposes axial forces in the GENERATOR shaft.
THYRISTER
A solid state electronic component whose ability to conduct CURRENT is controlled via its
VOLTAGE polarity or a gate signal. Thyristers are also called silicon controlled RECTIFIERS (SCR).
Thyristers are combined in series/parallel arrangements to perform rapid switching actions.
Thyristers are used in modern STATIC VAR COMPENSATORS (SVC), adjustable speed drives (ASD),
and high VOLTAGE DIRECT CURRENT (HVDC) SYSTEMS.
A-65
12422963
Glossary
TIE FACILITY
The transmission facility interconnecting BALANCING AUTHORITY AREAS.
TIE-LINE
A TRANSMISSION LINE connecting two BALANCING AUTHORITY AREAs.
TIE-LINE TELEMETRY
TELEMETRY EQUIPMENT used to measure POWER flow data on a TIE-LINE connecting BALANCING
AUTHORITIES. The POWER flow data is then transmitted to both BALANCING AUTHORITIES.
TIME ERROR
The difference between the INTERCONNECTION time measured at the BALANCING AUTHORITY(ies)
and the time specified by the National Institute of Standards and Technology. Time error is
caused by the accumulation of FREQUENCY ERROR over a given PERIOD.
TORQUE
The torque is a force that produces a rotating or twisting action.
TORQUE-SPEED CURVES
A graphical means of illustrating the relationship between the TORQUE developed by a motor and
the speed of rotation of the motor shaft.
TORSIONAL
A twisting force.
A-66
12422963
Glossary
TOTAL LOAD
The summation of motor and NON-MOTOR LOAD.
TRANSACTION
Sale of bulk POWER via the TRANSMISSION GRID.
TRANSFER CAPABILITY
The measure of the ability of interconnected electric SYSTEMS to move or transfer POWER in a
reliable manner from one area to another over all TRANSMISSION LINES (or paths) between those
areas under specified SYSTEM conditions. The units of transfer capability are in terms of electric
POWER, generally expressed in megawatts (MW). In this context, “area” may be an individual
electric SYSTEM, POWER POOL, BALANCING AUTHORITY, SUBREGION, or NERC REGION, or a
portion of any of these. Transfer capability is directional in nature. That is, the transfer capability
from “Area A” to “Area B” is not generally equal to the transfer capability from “Area B” to
“Area A”.
TRANSFER LIMIT
The maximum amount of POWER that can be transferred in a reliable manner from one area to
another over all TRANSMISSION LINES (or paths) between those areas under specified SYSTEM
conditions.
TRANSFORMER
A device that operates on magnetic principles to increase (step up) or decrease (step down)
VOLTAGE.
A-67
12422963
Glossary
TRANSIENT
A short term phenomena.
TRANSIENT STABILITY
The ability of an electric SYSTEM to maintain synchronism between its parts when subjected to a
DISTURBANCE and to regain a state of equilibrium following that DISTURBANCE.
TRANSMISSION
An interconnected group of lines and associated EQUIPMENT for the movement or transfer of
electric ENERGY between points of supply and points at which it is transformed for delivery to
customers or is delivered to other electric SYSTEMS.
TRANSMISSION CONSTRAINT
A limitation on one or more TRANSMISSION ELEMENTS that may be reached during normal or
CONTINGENCY SYSTEM operations.
TRANSMISSION LINE
A system of structures, wires, insulators and associated hardware that carry electric energy from
one point to another in an electric power system. Lines are operated at relatively high voltages
varying from 69 kV up to 765 kV, and are capable of transmitting large quantities of electricity
over long distances.
TRANSMISSION OPERATOR
The entity responsible for the RELIABILITY of its “local” TRANSMISSION SYSTEM, and that operates
or directs the operations of the TRANSMISSION FACILITIES.
TRANSMISSION OWNER
The entity that owns and maintains TRANSMISSION FACILITIES.
TRANSMISSION OVERLOAD
A state where a TRANSMISSION line has exceeded either a normal or EMERGENCY RATING of the
electric CONDUCTOR.
TRANSMISSION PLANNER
The entity that develops a long-term (generally one year and beyond) plan for the RELIABILITY
(ADEQUACY) of the interconnected BULK ELECTRIC TRANSMISSION SYSTEMS within its portion of
the PLANNING AUTHORITY AREA.
A-68
12422963
Glossary
TRANSMISSION SERVICE
Services provided to the TRANSMISSION CUSTOMER by the TRANSMISSION SERVICE PROVIDER to
move ENERGY from a POINT OF RECEIPT to a POINT OF DELIVERY.
TRAVELING WAVE
ENERGY can be viewed as a wave traveling through space. When a DISTURBANCE occurs in the
POWER SYSTEM the DISTURBANCE can be viewed as a wavefront of CURRENT and VOLTAGE
propagating out from the DISTURBANCE point. A FREQUENCY DISTURBANCE can also be viewed in
terms of a FREQUENCY DEVIATION propagating out from the DISTURBANCE point in the shape of a
wave.
TRE
Acronym for the Texas Reliability Entity. TRE is one of the eight Regional Reliability
Organizations.
TRIP
The opening of a CIRCUIT BREAKER or breakers on an electric SYSTEM, normally to electrically
isolate a particular ELEMENT of the SYSTEM to prevent it from being damaged by FAULT CURRENT
or other potentially damaging conditions.
TRIGONOMETRY
A branch of mathematics that deals with the relationships between the lengths of sides and the
angles between the sides of triangles.
TRIPLEN HARMONICS
The odd harmonic orders which are evenly divisible by the number three. For example, the 3rd,
9th, 15th, etc. are Triplen Harmonics.
TURBINE
A rotating mechanical device. A turbine is rotated by the force of a working fluid. The working
fluid is typically steam, water, or combustion gas.
A-69
12422963
Glossary
TURBINE FOLLOW
A MODE of operation of a fossil unit’s TURBINE/BOILER CONTROL SYSTEM in which the unit’s
response to a LOAD (MW) change request is delayed if the BOILER’s temperature and/or pressure
moves outside set boundaries. The MW response of the unit’s TURBINE “follows” the response of
the BOILER.
TURNING GEAR
A method of rotating the shaft of a horizontally mounted TURBINE/GENERATOR. The turning gear
may rotate the shaft at 2 RPM to prevent shaft warpage.
TURNS RATIO
The ratio of the number of turns in the PRIMARY WINDING of a TRANSFORMER to the number of
turns in the SECONDARY WINDING.
UNBUNDLING
Separating ELECTRIC UTILITY service into its basic components and offering each component
separately for sale with separate rates for each component.
UNDEREXCITE
A GENERATOR is underexcited when the applied excitation is less than that needed to support the
GENERATOR’s MAGNETIC FIELD. The deficiency in the REACTIVE POWER needs of the GENERATOR
is supplied by the SYSTEM. An underexcited GENERATOR absorbs REACTIVE POWER from the
SYSTEM. The terms “LEADING” and “bucking” are also used to refer to an underexcited
GENERATOR.
A-70
12422963
Glossary
UNILATERAL PAYBACK
INADVERTENT INTERCHANGE accumulations paid back unilaterally controlling to a target of non-
zero ACE. Controlling to a non-zero ACE ensures that the unilateral payback is accounted for in
the CPS calculations. The unilateral payback control offset is limited to BALANCING
AUTHORITY’S L10 limit and shall not burden the INTERCONNECTION.
UNIT COMMITMENT
The process of selecting which generating units will be placed on line to serve the LOAD and
reserve requirements.
VALVE
General name given to a mercury-ARC or THYRISTER based device that is used to conduct
CURRENT when a control signal is applied. A valve is turned on by a gate or GRID pulse. When
turned on a valve conducts CURRENT. When turned off a valve blocks the flow of CURRENT. A
valve is turned off by removing the forward biased VOLTAGE and stopping the CURRENT flow.
POWER CONVERTERS are composed of several valves connected in different arrangements
depending on the converter design.
VECTORS
Line segments that are used to represent the magnitude and direction of physical quantities. DC
VOLTAGES and CURRENTS can be represented by vectors.
VEGETATION
All plant material, growing or not, living or dead.
VISCOSITY
A property of a fluid that tends to prevent the fluid from flowing when subjected to an applied
force. High-viscosity fluids resist flow; low-viscosity fluids flow easily.
VOLTAGE (V)
The electrical force (a separation of CHARGE) that causes CURRENT to flow. Symbol is “V” and
units are volts.
A-71
12422963
Glossary
VOLTAGE ANGLE
The PHASE ANGLE between two VOLTAGES. The VOLTAGE angle is the same as the POWER ANGLE.
(In a GENERATOR the VOLTAGE angle between the internal GENERATOR VOLTAGE and the STATOR
terminal VOLTAGE is the equivalent of the TORQUE ANGLE.)
VOLTAGE COLLAPSE
A process in which a VOLTAGE unstable SYSTEM experiences an uncontrollable reduction in
SYSTEM VOLTAGE.
VOLTAGE CONTROL
The control of TRANSMISSION VOLTAGE through adjustments in GENERATOR reactive output and
TRANSFORMER TAPS, and by switching CAPACITORs and inductors on the TRANSMISSION and
DISTRIBUTION SYSTEMS.
VOLTAGE LIMITS
A hard limit above or below which is an undesirable operating condition. Normal limits are
between 95 and 105 percent of the NOMINAL VOLTAGE at the BUS under discussion.
VOLTAGE RATIO
The ratio between the primary and secondary VOLTAGES of a TRANSFORMER. There is a strong
(but not identical) relationship between a TRANSFORMER’s voltage ratio and its TURNS RATIO.
VOLTAGE REDUCTION
A procedure designed to deliberately lower the VOLTAGE at a BUS. It is often used as a means to
reduce DEMAND by lowering the customer’s VOLTAGE.
VOLTAGE REGULATOR
A component of an EXCITATION SYSTEM. The voltage regulator monitors the GENERATOR’s output
VOLTAGE and causes an adjustment in excitation CURRENT when required. Voltage regulators can
be operated in either a manual or automatic MODE.
VOLTAGE SOURCE
A device capable of producing a VOLTAGE. GENERATORS and batteries are voltage sources.
VOLTAGE STABILITY
The ability of a POWER SYSTEM to maintain VOLTAGE so that when the SYSTEM NOMINAL LOAD is
increased the actual POWER transferred to that LOAD will increase. In a VOLTAGE stable POWER
SYSTEM the POWER transfer and the SYSTEM VOLTAGES are controllable by the SYSTEM
OPERATORS.
A-72
12422963
Glossary
V-Q CURVE
A VOLTAGE versus REACTIVE POWER curve. A plot of the VOLTAGE at a BUS versus the REACTIVE
POWER injected into that BUS. V-Q curves are a graphical tool used to analyze a POWER SYSTEM’s
VOLTAGE STABILITY.
WATTHOUR (Wh)
A unit of measure of ELECTRICAL ENERGY equal to 1 watt of POWER supplied to, or taken from, an
electric CIRCUIT steadily for 1 hour.
WECC
Acronym for the Western Electricity Coordinating Council. WECC is one of the eight NERC
REGIONAL RELIABILITY ORGANIZATIONS.
WHEELING
TRANSMISSION line usage which a TRANSMISSION line owner agrees to provide to permit the
transfer of CAPACITY and ENERGY by another party.
WHEELING CHARGES
Payments required for providing WHEELING services.
WICKET GATE
Adjustable ELEMENTs that control the flow of water to the TURBINE of a hydro-electric FACILITY.
WIDE AREA
The entire RELIABILITY COORDINATOR AREA as well as the critical flow and status information
from adjacent RELIABILITY COORDINATOR AREAS as determined by detailed SYSTEM studies to
allow the calculation of Interconnected RELIABILITY OPERATING LIMITS.
WYE CONNECTION
A 3Φ electrical connection in which one end of each of the three PHASES is connected to a
common point. The common point is often GROUNDED. TRANSFORMER windings are often
connected in a Wye configuration.
ZONES OF PROTECTION
The zone or area within which a PROTECTIVE RELAY can sense abnormal conditions.
A-73
12422963
12422963
B
ABBREVIATIONS AND ACRONYM EXPANSION
12422963
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
A Symbol for Ampere
ABA Adjacent Balancing Authority
AC Alternating Current
ACB Air Circuit Breaker
ACE Area Control Error
ACSR Aluminum Conductor Steel Reinforced
AFC Available Flowgate Capability
AGC Automatic Generation Control
AIE Area Interchange Error
ANSI American National Standards Institute
AS Ancillary Services
ASD Adjustable Speed Drive
ATC Available Transfer Capability
ATF After the Fact
AVR Automatic Voltage Regulator
B Symbol for frequency Bias
β Symbol for frequency response characteristic
BA Balancing Authority
BAL Balancing
BES Bulk Electric System
BPD Bushing Potential Device
BSU Black-Start Unit
B-1
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
BTU British Thermal Unit
CA Contingency Analysis
CB Circuit Breaker
CF Compliance Factor
COM Communications
CS Circuit Switcher
CT Combustion Turbine
CT Current Transformer
DC Direct Current
B-2
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
DCU Directional Comparison Unblocking
DF Distribution Factor
EA Emergency Assistance
ED Economic Dispatch
EM Electromechanical
B-3
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
F Symbol for Frequency
FA Frequency Actual
FAC Facilities
FR Frequency Resonance
FS Frequency Scheduled
GO Generation Owner
GW Giga Watt
B-4
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
HIR High Initial Response
HP High Pass
HP High Pressure
HS High Side
HV High Voltage
HZ Hertz
IA Interchange Authority
INT Interchange
IP Intermediate Pressure
IR Inertia Ratio
IS Interchange Schedule
B-5
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
ISO Independent System Operator
IT Interchange Transaction
IT Instrument Transformer
kV kilo Volt
kW kilo Watt
LF Load Forecast
LP Low Pressure
LS Low Side
LV Low Voltage
B-6
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
MAV Mercury Arc Valve
MOD Modeling
MW Mega Watt
B-7
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
NRC Nuclear Regulatory Commission
P.U. Per-unit
PA Planning Authority
PF Power Factor
PS Personnel Subcommittee
B-8
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
PSI Pounds per Square Inch
PT Potential Transformer
PX Power Exchange
Q Quality
RC Reliability Coordinator
RF Reactive Factor
ROW Right-of-Way
RP Resource Planner
B-9
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
RRO Regional Reliability Organization
SE State Estimator
SO SystemOperator
B-10
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
SVS Static Var System
TO Transmission Owner
TP Transmission Planner
UC Unit Commitment
UF Under Frequency
B-11
12422963
Abbreviations and Acronym Expansion
Acronym Expansion
UPS Uninterruptible Power Supply
VA Volt-Ampere
VT Voltage Transformer
B-12
12422963
C
REVIEW QUESTIONS ANSWER KEY
12422963
12422963
Review Questions Answer Key
A. Leading
B. Lagging
C. Underexcited
D. Dropping
A. 87
B. 86
C. 67
D. 50
C-1
12422963
Review Questions Answer Key
6. The actual voltage is 362 kV on a 345 kV bus. What is the p.u. voltage?
A. 1.0
B. 1.05
C. 1.5
D. .95
7. A load has a power factor of 0.9 lagging. If the load draws 100 MVA,
what is the MW draw?
A. 100
B. 90
C. 111
D. 44
A. Phase angle
B. Frequency difference
C. Voltage magnitude difference
D. MW flow differential
C-2
12422963
Review Questions Answer Key
A. 199 kV
B. 230 kV
C. 345 kV
D. 500 kV
C-3
12422963
Review Questions Answer Key
A. True
B. False
3. At what line power angle does the MW transfer across a transmission path
equal ½ of the path’s PMAX?
A. 15 degrees
B. 20 degrees
C. 30 degrees
D. 45 degrees
A. Yes
B. No
C. Impossible to determine
D. The line has no load
5. The TTC limit has been determine to be 1000 MW from east to west for a
particular transmission path. The transmission path operator sells 500
MW of this TTC. What is the path’s ATC?
A. 1000 MW
B. 1500 MW
C. 0 MW
D. 500 MW
A. True
B. False
C-4
12422963
Review Questions Answer Key
A. 0 degrees
B. 45 degrees
C. 90 degrees
D. 180 degrees
A. 0 degrees
B. 45 degrees
C. 90 degrees
D. 180 degrees
10. 200 MW is scheduled to flow from Bus “X” to Bus “Y”. Transmission
line “A-B” has a 10% distribution factor for this schedule. How much of
the 200 MW schedule will flow on transmission line “A-B”?
A. 20 MW
B. 40 MW
C. 180 MW
D. 200 MW
C-5
12422963
Review Questions Answer Key
A. 500 MW
B. 1000 MW
C. 200 MW
D. 50 MW
A. True
B. False
C-6
12422963
Review Questions Answer Key
A. 2.0 seconds
B. 2.4 seconds
C. 1.0 second
D. 1.2 seconds
A. -75
B. +75
C. -150
D. +150
A. 5%
B. 0%
C. 10%
D. 8%
10. What element of the power system is typically most susceptible to damage
from prolonged operation at frequencies above or below 60 HZ?
C-7
12422963
Review Questions Answer Key
A. 75%
B. 100%
C. 0%
D. 25%
13. What magnitude of frequency change would cause a 10% droop governor
to move its generator from zero to full output in a 60 HZ system?
A. 6 HZ
B. 10 HZ
C. 3 HZ
D. 5 HZ
A. DCS 1
B. DCS 2
C. CPS1
D. CPS2
A. 50%
B. 100%
C. 200%
D. No limit
C-8
12422963
Review Questions Answer Key
A. 40.5
B. 45
C. 55.6
D. 61.7
2. A 5% change in voltage will typically lead to what change in the total load
magnitude?
A. 2%
B. 3%
C. 5%
D. 10%
A. High voltage
B. Low frequency
C. High voltage and low frequency
D. All of the above
A. 1/3
B. 3/4
C. 2.0
D. 5.0
A. 345 kV
B. 340 kV
C. 350 kV
D. 360 kV
C-9
12422963
Review Questions Answer Key
A. 25%
B. 40%
C. 50%
D. 80%
A. 1/3
B. 3/4
C. 2.0
D. 5.0
9. Given a purely inductive load, what can be said about the MVA this load
draws from the power system?
A. True
B. False
C-10
12422963
Review Questions Answer Key
A. True
B. False
A. Induction motors
B. Motor type load
C. Nominal load
D. Non-motor type load
5. P-V curves indicate the __________ margin from voltage instability while
V-Q curves indicate the __________ margin from voltage instability.
A. Mvar / MW
B. MW/ Mvar
C. MW / current
D. Power / Mvar
C-11
12422963
Review Questions Answer Key
7. In which type of voltage instability does a key element outage trigger the
instability?
C-12
12422963
Review Questions Answer Key
A. Angle stability
B. Loss of synchronism
C. Out-of-step
D. All of the above
A. Relative power
B. Synchronizing power
C. Stability power
D. Accelerating power
Match a type of angle instability from the left column with a unique
definition from the right column:
C-13
12422963
Review Questions Answer Key
A. True
B. False
10. The primary difference between an out-of-step event and a fault is:
C-14
12422963
Review Questions Answer Key
A. 0.001 HZ to .0001 HZ
B. 100 HZ to 80 HZ
C. 60 HZ to 30 HZ
D. 0.05 HZ to 3.0 HZ
A. Intra-area mode
B. Inter-area mode
C. Intra-plant mode
D. Local mode
5. High speed excitation systems tend to extend _____ stability limits but
may lead to _____ instability.
C-15
12422963
Review Questions Answer Key
A. HVDC modulation
B. Amortisseur windings
C. PSS
D. All of the above
A. Negatively damped
B. Damped
C. Undamped
D. Positively damped
A. 2 and 4
B. 1 and 2
C. 4
D. 1, 2, and 3
A. Intra-plant mode
B. Inter-area mode
C. Intra-area mode
D. Local mode
10. On August 10, 1996, large 0.224 HZ power oscillations were measured in
the Pacific AC Intertie 500 kV lines. These oscillations were:
A. Intra-area mode
B. Local mode
C. Inter-plant mode
D. Inter-area mode
C-16
12422963
Review Questions Answer Key
A. Odd harmonics
B. Even harmonics
C. High order harmonics
D. Triplen harmonics
2. If the inductance is 0.001 henry and the capacitance is .000782 farad, what
is the resonance frequency?
A. 300 HZ
B. 60 HZ
C. 180 HZ
D. 240 HZ
4. SSR is more of a concern with hydroelectric units than with thermal units.
A. True
B. False
6. The currents that flow in the earth’s surface as a result of solar magnetic
disturbances are called:
A. Electrojets
B. Geomagnetic induced currents
C. Earth surface potentials
D. Sunspot currents
C-17
12422963
Review Questions Answer Key
A. Series capacitors
B. Shunt capacitors
C. Transformer delta windings
D. Transformer grounded neutrals
A. 480 HZ
B. 100 HZ
C. 200 HZ
D. 300 HZ
10. Assume a transmission line has a series inductive reactance of 100 ohms
and a series capacitive reactance of 50 ohms. What amount of series
capacitance (in ohms) must be added to create a series resonance
condition?
A. 100
B. 50
C. 25
D. 150
C-18
12422963
Review Questions Answer Key
A. Semipolar
B. Bipolar
C. Unipolar
D. Monopolar
A. Transformers
B. Electrodes
C. Valves
D. Filters
A. Delay inversion
B. Delay commutation
C. Delay conversion
D. Delay rectification
C-19
12422963
Review Questions Answer Key
A. series / quadrature
B. series / series
C. quadrature / quadrature
D. quadrature / series
7. Several HVDC systems are used to electrically connect the Eastern and
Western Interconnections of North America. Since both Interconnections
are 60 HZ systems, why would HVDC be used?
A. True
B. False
A. Reducing DC ripple
B. Reducing DC fault duty
C. Assisting with the commutation process
D. Filtering the AC harmonics
C-20
12422963
Review Questions Answer Key
A. 67-100
B. 101-201
C. 400-600
D. 1000 or greater
C-21
12422963
Review Questions Answer Key
A. True
B. False
3. Generators and large motors are often equipped with negative sequence
relays. The negative sequence relay is designed to:
4. During which phase of the restoration process is the voltage and frequency
of the generators that survived the initial disturbance adjusted to optimum
values:
A. Phase 4: Billing
B. Phase 2: Preparation of Subsystems
C. Phase 1: Assessment
D. Phase 3: Establishment of Target Systems
C-22
12422963
Review Questions Answer Key
6. A 200 mile long 500 kV line is transposed at two locations along the line.
The purpose of transposition is to:
9. Which of the following types of units could most likely operate, without
damage, as a motor?
A. Hydro turbine
B. Nuclear drive steam turbine
C. Combustion turbine
D. Coal driven steam turbine
C-23
12422963
Review Questions Answer Key
10. Given the following types of turbine/generators, which typically has the
highest frequency response rate?
11. The high probability of switching surge induced TOVs and the potential
for ferroresonance may necessitate operation at reduced steady-state
voltage levels during the early stages of restoration. These reduced
steady-state voltage levels are typically in the __________ range.
A. 105 to 110%
B. 90 to 95%
C. 70 to 80%
D. 80 to 90%
12. When a switching surge occurs, the power system is exposed to a wave
like effect as the switching surge voltage propagates through the area
power system. The propagating surge voltage can add to the power
system steady-state voltage, producing a __________.
A. LOF
B. TOV
C. AGC
D. URAL
A. 150 MW
B. 10 MW
C. 25 MW
D. 50 MW
C-24
12422963
Review Questions Answer Key
C-25
12422963
12422963
12422963
Export Control Restrictions The Electric Power Research Institute, Inc.
Access to and use of EPRI Intellectual Property is granted with the (EPRI, www.epri.com) conducts research and development relating
specific understanding and requirement that responsibility for ensur- to the generation, delivery and use of electricity for the benefit of
ing full compliance with all applicable U.S. and foreign export laws the public. An independent, nonprofit organization, EPRI brings
and regulations is being undertaken by you and your company. This together its scientists and engineers as well as experts from academia
includes an obligation to ensure that any individual receiving access and industry to help address challenges in electricity, including
hereunder who is not a U.S. citizen or permanent U.S. resident is reliability, efficiency, health, safety and the environment. EPRI also
permitted access under applicable U.S. and foreign export laws and provides technology, policy and economic analyses to drive long-
regulations. In the event you are uncertain whether you or your com- range research and development planning, and supports research
pany may lawfully obtain access to this EPRI Intellectual Property, you in emerging technologies. EPRI’s members represent more than 90
acknowledge that it is your obligation to consult with your company’s percent of the electricity generated and delivered in the United
legal counsel to determine whether this access is lawful. Although States, and international participation extends to 40 countries.
EPRI may make available on a case-by-case basis an informal as- EPRI’s principal offices and laboratories are located in Palo
sessment of the applicable U.S. export classification for specific EPRI Alto, Calif.; Charlotte, N.C.; Knoxville, Tenn.; and Lenox, Mass.
Intellectual Property, you and your company acknowledge that this
Together…Shaping the Future of Electricity
assessment is solely for informational purposes and not for reliance
purposes. You and your company acknowledge that it is still the ob-
ligation of you and your company to make your own assessment
of the applicable U.S. export classification and ensure compliance
accordingly. You and your company understand and acknowledge
your obligations to make a prompt report to EPRI and the appropriate
authorities regarding any access to or use of EPRI Intellectual Prop-
erty hereunder that may be in violation of applicable U.S. or foreign
export laws or regulations.
© 2009 Electric Power Research Institute (EPRI), Inc. All rights reserved. Electric Power
Research Institute, EPRI, and TOGETHER...SHAPING THE FUTURE OF ELECTRICITY are
registered service marks of the Electric Power Research Institute, Inc.
1016042