30KAV Screw VSD Chiller (Katalog)

This document provides information about the 30KAV variable speed air-cooled screw chiller. It describes the unit's operating range, low energy consumption capabilities, environmental friendliness, and reliability features such as its screw compressors with Greenspeed Intelligence technology.

Uploaded by

ridho
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
227 views16 pages

30KAV Screw VSD Chiller (Katalog)

This document provides information about the 30KAV variable speed air-cooled screw chiller. It describes the unit's operating range, low energy consumption capabilities, environmental friendliness, and reliability features such as its screw compressors with Greenspeed Intelligence technology.

Uploaded by

ridho
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

30KAV

Variable Speed
Air-cooled Screw Chiller
4USOTGRIUUROTMIGVGIOZ_ dQ=
Turn To The Experts
Founded by the inventor of modern air conditioning, Carrier is the world’s

leader in high-technology heating, air-conditioning and refrigeration solutions.

Carrier experts provide sustainable solutions, integrating energy-efficient

products, building controls and energy services for residential, commercial,

retail, transport and food service customers. Carrier is a part of UTC Build

ing & Industrial Systems, a unit of United Technologies Corp., a leading

provider to the aerospace and building systems industries worldwide.

With a broad portfolio of advanced technical patent awards, our global R&D

center in Shanghai develops innovative heat, ventilation and air-conditioning

(HVAC) solutions.

In 1998, Time magazine named


Dr. Carrier oneof its 20 most
influential builders and titans of
the 20 th century.
Nomenclature
30KAV1100 A PT002B

Unit option
PT002B Blygold PoluAL
PT003A Gold Fin
PT303 Blue fin
PT020A IP54
PT041A Evaporator anti-freeze
PT301 Lead/lag control
PT148B J-Bus gateway
PT148C BacNet/Modbus RS485 gateway
PT148D LonTalk gateway
PT149 BacNet IP gateway
PT156 Energy Management Module (EMM)
PT158A 7" touch pilot
PT093A Discharge valve
PT107 Reversed water connections
PT312A Australian request
PT104 1.6MPa evaporator
PT254 Cu/Al condenser coils
PT282 EMC Classification C2 
PT299 38mm cooler insulation

Design Series

Unit Model Air-cooled Variable Speed Screw chiller 30KAV0550-1100

Operating Range
Evaporator Min. temperature Max. temperature
Entering water temperature (at start) °C - 45
Entering water temperature (operating) °C 6.8 26
Leaving water temperature (operating) °C 3.3 20
Condenser Min. temperature Max. temperature
Outdoor air temperature °C -20 50

50
+TZKXOTMGOXZKSVKXGZ[XK ȭ

40
30
20
10
0
-10
-20

3.3 7 20
Evaporator leaving water temperature ȭ

(KRU]ȭGOXZKSVGZ[XKZNK[TOZS[YZKOZNKXHKKW[OVVKJ]OZNK\GVUXGZUXLXUYZVXUZKIZOUTUVZOUT6:'
UXZNK]GZKXRUUVS[YZHKVXUZKIZKJGMGOTYZLXUYZH_[YOTMGLXUYZVXUZKIZOUTYUR[ZOUTH_ZNKOTYZGRRKX
6GXZRUGJG\KXGMK

2
Introduction

The Aquaforce chillers with Greenspeed® Intelligence are the premium solution for
commercial and industrial applications where installers, consultants and building owners
require superior reliability and optimal performances, especially at part load.

30KAV are designed to meet current and future requirements in terms of energy efficien-
cy, versatility and operating sound levels. Through the optimised combination of proven
best-in-class technologies that include:
- Exclusive new screw compressors with Greenspeed® Intelligence.
- The new Touch Pilot control.
- 6th flying bird Condenser fans with Greenspeed® Intelligence.

Furthermore, with 30KAV, Carrier offers its unique expertise and know-how to take care
of the machine long after the sale. With the new “CARRIER CONNECT” system in fact,
energy and facility managers and end-users in general can rely on the most qualified
remote monitoring services.

Low Energy Consumption

The air conditioning system could use 30%~40% of anual buidling engery consumption,
30KAV helps customer involved in green building certification with Greenspeed ® inveter
- driven technology.

With advanced unit mounted inverter-driven technolgy, the 30KAV is designed for high
performance both at full load and at part load. Exceptional efficiency performance at part
load which is up to 5.7.

Cooperating with primary viarable flow system, the system efficiency would be further
enhanced by synchronized control of chillers and pumps.

The high energy efficiency is reached thanks to:


- Inverter driven twin-rotor screw compressors allowing precise capacity matching of
buliding load and reducing unit power input, especially at part-load.
- Inverter driven fan motors minimizing power consumption while granting optimum air
flow.
- Electronic expansion device permitting operation at a lower condensing pressure and
improved utilization of the evaporator heat exchange surface.
- Economizer system with electronic expansion device increases cooling capacity by
10% and efficiency by 4%.
Efficlency (kW/kW)

Start-up (A)

100% 75% 50% 25%

Chiller load Time (s)

30KAV0852 30KAV0862A Fixed speed 30KAV

3
Environmental Friendly

HFC-134a refrigerant
Refrigerant of the HFC group with zero ozone depletion potential.

Leak-tight refrigerant circuit.


Reduction of leaks as no capillary tubes and flare connections are used.
Verification of pressure transducers and temperature sensors without transferring refrig-
erant charge.

Absolute reliability

Screw compressors with Greenspeed® Intelligence:


- Industrial-type screw compressors with oversized bearings and motor cooled by
suction gas.
- Specifically sized inverter for each compressor motor ensures reliable operation and
easy maintenance.
- All compressor components assembly are easily accessible on site minimising
down-time.

Fans with Greenspeed® Intelligence.


- 6th generation of Flying Bird fans equipped with inverter-driven asynchronous motors.
- Specifically sized inverter optimize air flow management reducing cost.
- Easily accessible inverter of fan speed control for easy service.

Exceptional endurance tests.


- Partnerships with specialised laboratories and use of limit simulation tools (finite
element calculation) for the design of critical components.
- Transport simulation test equivalent to 2000 km by truck under harsh conditions.
- Salt mist corrosion resistance test in the laboratory for increased corrosion resistance.

Minimised Operating Sound Levels

The inverter technology used for the compressor and fan motors minimises noise levels
at part load operation. When the unit is delivering 25% for example, compressors and
fans are running at minimum speed which implies lower noise.

Standard unit features include:


- Discharge dampers integrated in the oil separator (Carrier patent).
- Condenser coils in W-shape with an open angle, allowing quieter air flow across the coil.
- Low-noise 6th generation Flying Bird fans, made of a composite material (Carrier
patent) which do not generate intrusive low frequency noise.

4
General Features

New innovative smart control features:


- An intuitive and user-friendly, 5" colored interface (7" as option).
- Screen-shots with concise and clear information in local languages.
- Complete menu, customized for different users (end user, service personnel
and Carrier-factory technicians).
- Easy access to the controller box with touch screen mounting to ensure legibil-
ity under any lighting conditions.
- Safe operation and unit setting: password protection ensures that unautho-
rized people cannot modify any advanced parameters.
- Simple and “smart” intelligence uses data collection from the constant monitor-
ing of all machine parameters to optimise unit operation.
- Night-mode: Cooling capacity management for reduced noise level.

Economical operation

Energy management:
- Internal time schedule clock controls chiller on/off times and opera tion at a
second set-point.
- The DCT (Data Collection Tool) records the alarms history to simplify and
facilitate service operations.
Large colored

Remote Management (Standard)

- Units with Touch Pilot control can be easily accessed from the internet, using
a PC with an Ethernet connection. This makes remote control quick and easy
and offers significant advantages for service operations.
- Equipped with an RS485 serial port that offers multiple remote control, moni-
toring and diagnostic possibilities. When networked with other Carrier equip-
ment through the CCN (Carrier Comfort Network - proprietary protocol), all
components form a HVAC system fully-integrated and balanced through one
of the Carrier’s network system products, like the Chiller System Manager or
the Plant System Manager (optional). also communicates with other building
management systems viaoptional communication gateways.

5
Quiet operation

The following commands/visualizations are possible from remote


- Start/Stop of the machine.
- Dual set-point management: Through a dedicated contact is possible to
activate a second set-point (example: unoccupied mode).
- Demand limit setting: To limit the maximum chiller capacity to a predefined
value.
- Water pump control: These outputs control the contactors of one/two evapora-
tor water pumps.
- Operation visualization: Indication if the unit is operating or if it’s in stand-by
(no cooling load).
- Alarm visualization.

Absolute reliability

The Energy Management Module (EMM) offers extended remote control possi-
bilities:
- Room temperature: Permits set-point reset based on the building indoor air
temperature (if Carrier thermostat are installed).
- Set-point reset: Ensures reset of the cooling set-point based on a 4-20 mA or
0-10 V signal.
- Demand limit: Permits limitation of the maximum chiller power or current
touch display
based on 0-10 V signal.
- Demand limit 1 and 2: Closing of these contacts limits the maximum chiller
power or current to two predefined values.
- User safety: This contact can be used for any customer safety loop; opening
the contact generates a specific alarm.
- Ice storage end: When ice storage has finished, this input permits return to the
second set-point (unoccupied mode).
- Time schedule override: Closing of this contact cancels the time schedule
effects.
- Out of service: This signal indicates that the chiller is completely out of service.
- Chiller capacity: This analogue output (0-10 V) gives an immediate indication
of the chiller capacity.
- Alert indication: This volt-free contact indicates the necessity to carry out a
maintenance operation or the presence of a minor fau.
- Compressors running status : Set of outputs (as many as the compressors
number) indicating which compressors are running.

6
Performance data

Model 30KAV 0550A 0660A 0700A 0800A 0900A 1000A 1100A

Nominal cooling capacity* kW 546.3 664.8 712.9 798.3 887.9 986.2 1068

Compressor power input kW 158.1 202.6 211.5 244.0 274.7 298.3 333.6

Total power input kW 170.7 215.8 226.1 260.0 292 317.1 354

Compressor VFD Semi-hermetic screw compressor

CircuitA 1 1 1 1 1 1 1

CircuitB 1 1 1 1 1 1 1

Minimum capacity % 10% 10% 10% 10% 10% 10% 10%

Refrigerant R134a

CircuitA kg 70 85 85 95 95 125 125

CircuitB kg 70 70 85 85 95 95 125

Control Touch pilot system

Condenser Cu/AI heat exchanger

Fans VI generation FlyingBird axial fan

Quantity 8 9 10 11 12 13 14

Total air flow l/s 40080 45100 50110 55120 60126 65140 70150

Fan speed rpm 950

Evaporator Flooded multi-pipe

Water content l 79 93 93 127 127 146 157

Nominal water flow l/s 26.04 31.69 33.98 38.05 42.32 47.01 50.92

Nominal water pressure drop kPa 43.1 37.4 38.6 31.1 38.4 43.4 44.4
Max. water-side pressure
kPa 1000
(without hydronic module)
Water connection Victaulic

Nominal Diameter DN 150 150 150 150 150 200 200

Electrical data

Nominal power supply 400V-3Ph-50Hz

Control power supply VFD start

Start-up method 24V via internal transformer

Fan and control power kW 12.6 13.2 14.6 16.0 17.4 18.8 20.2

Nominal unit current draw Circuit A+B A 267 339 356 404 452 497 550

Maximum uint current draw Circuit A+B A 343 425 450 517 585 610 682

Maximum start-up current Circuit A+B A 343 425 450 517 585 610 682

Max operation power Circuit A+B kW 221 274 290 333 377 393 439

Unit length mm 5399 6475 6475 7555 7555 8635 8635

Unit width mm 2253

Unit height mm 2379

Shipping weight kg 5368 5825 5981 6800 7284 7624 7812

Operating weight (Standard) kg 5235 5626 5796 6620 7104 7428 7627

Notes: * Nominal conditoins - evaporator entering/leaving water temperature=12/7˚C, outdoor air temperature = 35˚C Evaporator fouling factor = 0.018m2K/kW

7
Dimension Drawing

30KAV0550A
2379

DN125

272
357
2337 1124
5008
DN125
5399

3
1500
1500

1
4

1 2

5 1 819
1500

1
892 1108 407
1500
Power supply
2253 connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

8
Dimension Drawing

30KAV0660A
2379

DN150

242
372
2983 1124
6120
DN150
6475

1500
1500

1 2

841
1
1500

1 1158 407
1587
1500 Power supply
2253
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

9
Dimension Drawing

30KAV0700A
2379

DN150

242
372
2977 1124
6120
DN150
6475

1500
1500

1 2

5 1 857
1500

1 1136 407

1500 1565 Power supply


2253
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

10
Dimension Drawing

30KAV0800A
2379

DN150

284
3585 1124

325
7200 DN150
7555

3
1500

1500
1

4 2

1 1

855
1500

1
1500 1190 407
2141
2253 Power supply
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

11
Dimension Drawing

30KAV0900A
2379

DN150

284
3496 1124

325
DN150
7200
7555

3
1500

1500
1

2
4

1 1

864
5
1500

1
1500 1138 407
2143
Power supply
2253
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

12
Dimension Drawing

30KAV1000A
2379

DN200

290
4356 1124

297
DN200
8280
8635

1500
1500

4 2

1 1

906
5
1500

1
1500 1143 407

2187 Power supply


2253
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

13
Dimension Drawing

30KAV1100A
2379

DN200

290
4325 1124

297
DN200
8280
8635

1500
1500

4 2

1 1

909
5
1500

1
1161 407
1500
2187
Power supply
2253
connection

1 Required clearances for maintenance Water inlet

2 Recommended space for evaparator tube removal Water outlet

3 Safety valve Air outlet

4 Fan drive cabinet Power supply connection

5 Comp drive cabinet Center gravity

14
The Manufacturer reserves the right to change any produt specifications without prior notices CAT_30KAV_E-1711-02
Version:

Supersede: -

Effective date: Oct, 2017