Series Reactor
Series Reactor
Pradeep.P
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
SERIES REACTOR
Reactors are coils with a high reactance value compared to their resistance, which lowers
the short circuit to a healthy level to protect the equipment or installation. Series reactors reduce
the short circuit kVA of the equipment protection circuit breaker installed.
The short circuit current and the short circuit kVA of the system having the percentage
reactance of X% are respectively given by,
𝐼𝑆𝐶= 1
𝑋(𝑝.𝑢)
The above formula indicates that the short circuit current and short circuit kVA will be smaller
if the % of Reactance is larger.
Advantages:
• The system's efficiency is not much affected because the reactor's Reactance is more
significant than its resistance.
• The fault current is reduced.
• It is used to protect the circuit breakers of the inadequate rating.
• It reduces the short circuit kVA requirement of the circuit breaker.
Reactors are placed across a power system to reduce short circuit current. These reactors can
be connected in series with the generators, feeders, or bus bars.
Generator reactors:
1
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
Feeder reactors:
Disadvantages:
The drawback of such reactors is that they do not protect the generators from short circuit
faults across the bus bars. Reactors also have a constant voltage drop and power loss during normal
operation.
Bus Bar reactors are connected via bus bars. Bus bar reactors divide the bus bar into smaller
Sections. If the voltage level remains constant, no current flows through these reactors, and each
section acts as a separate bus bar. If a fault occurs on a section of the bus bar, the reactor prevents
the fault from reaching other sections, and only the fault section is affected. Hence, a bus bar should
be large enough to protect the system but should not disturb its synchronism.
The following methods describe how to decrease the continuous voltage drop and power
losses in the case of feeder and generator reactors:
1) Ring system:
A small amount of power goes through the reactors under normal operating conditions. As a
result, the reactor's voltage drop and power loss are minimal, and the bus bar reactor is made from a
high ohmic resistance to minimize the voltage drop across it.
2
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
2) Tie-Bar system:
This method offers greater flexibility. By increasing the number of sections, the switch gears
perform more effectively without requiring system changes. However, this technique is complicated
and requires an extra bus, i.e., a tie bar.
Note: Since the series reactors used should not have a saturation problem, the core of the reactors is
replaced with circular coils or bars of normal copper set in a number of specially shaped
concentrate slabs.
In this scenario, a simple network is modelled with a grid short circuit current of 40 kA, and table
1 shows the grid and cable parameters.
Figure 5 shows that the fault current is 35.07 kA without a series reactor. As a result, cable
impedance comes into the picture. So, because the fault current is higher, it can determine the
reactor's value and plan to reduce it from 35 kA to 20 kA.
Using manual calculation, the value of the reactor is determined. Using the value of grid
impedance, the cable impedance and series reactor are assumed to be unknown values (X), and the
fault current is limited to 20 kA. The values need to be in p.u, so the p.u calculation is done on the
following page.
3
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
Therefore, we consider that the voltage base is 33 kV, and the base MVA is 100.
(33)2 (33)2
𝑍𝑏𝑎𝑠𝑒 = = = 𝟏𝟎. 𝟖𝟗 𝒐𝒉𝒎𝒔
𝑀𝑉𝐴𝑏 100
𝒁𝒂𝒄𝒕𝒖𝒂𝒍 0.00697
𝒁𝒑.𝒖 𝑪𝒂𝒃𝒍𝒆 = = = 𝟎. 𝟎𝟎𝟔𝟒 𝒑. 𝒖
𝒁𝒃𝒂𝒔𝒆 10.89
𝑀𝑉𝐴𝑆𝐶 = √3 ∗ 40 ∗ 33 = 2268.30 𝑘𝐴
(𝒌𝑽)𝟐 (33)2
𝒁𝒂𝒄𝒕𝒖𝒂𝒍 𝑮𝒓𝒊𝒅 = = = 𝟎. 𝟒𝟕𝟔𝟑 𝒐𝒉𝒎𝒔
𝑴𝑽𝑨𝑺𝑪 2268.30
4
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
𝑽𝒐𝒍𝒕𝒂𝒈𝒆 𝒓𝒂𝒕𝒊𝒏𝒈
𝑰𝒇 =
√𝟑 ∗ (𝒁𝒂𝒄𝒕𝒖𝒂𝒍 𝑮𝒓𝒊𝒅 + 𝒁𝒂𝒄𝒕𝒖𝒂𝒍 𝑪𝒂𝒃𝒍𝒆 + 𝒁𝒂𝒄𝒕𝒖𝒂𝒍 𝑹𝒆𝒂𝒄𝒕𝒐𝒓)
33
20 𝑘𝐴 =
√3 ∗ (0.4763 + 0.0697 + 𝑍𝑎𝑐𝑡𝑢𝑎𝑙 𝑅𝑒𝑎𝑐𝑡𝑜𝑟)
33
√3 ∗ (0.4763 + 0.0697 + 𝑍𝑎𝑐𝑡𝑢𝑎𝑙 𝑅𝑒𝑎𝑐𝑡𝑜𝑟) =
20 𝑘𝐴
√3 ∗ (0.4763 + 0.0697) + √3 ∗ (𝑍𝑎𝑐𝑡𝑢𝑎𝑙 𝑅𝑒𝑎𝑐𝑡𝑜𝑟) = 1.65
(0.945) + √3 ∗ (𝑍𝑎𝑐𝑡𝑢𝑎𝑙 𝑅𝑒𝑎𝑐𝑡𝑜𝑟) = 1.65
1.65 − 0.945
𝑍𝑎𝑐𝑡𝑢𝑎𝑙 𝑅𝑒𝑎𝑐𝑡𝑜𝑟 = = 𝟎. 𝟒𝟎𝟕𝟎 𝒐𝒉𝒎𝒔
√3
The resistance value is calculated and used in modelling in the series reactor. The calculated
resistance Limits the fault current to 20 kA, as shown in figure 6.
Case 1:
In this case, the rated power of the Series reactor is 10 MVA with a resistance of 0.4070 ohms.
Since the fault current depends on the voltage and impedance, it does not vary even if the
reactor's rated power is Changed.
5
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
Case 2:
In this case, the rated power of the Series reactor is 50 MVA with a resistance of 0.4070 ohms.
Figures 7 & 8 show the simulation results after changing it to 50 MVA since the fault current
remains constant.
6
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
Case 3: In this case, the rated power of the Series reactor is 10 MVA, and the short circuit voltage
uk input (Impedance) is used. The impedance is 3 %, and as a result, the fault current changes,
as shown in Figure 11.
Figure 11: With Series Reactor (Rated power of 10 MVA & SC Voltage 3%) - Simulation results
7
SERIES REACTOR & MODELLING OF SERIES REACTOR IN DIGSILENT
POWERFACTORY
Pradeep P
Case 4: In this case, the rated power of the Series reactor is 50 MVA, and the short circuit voltage
uk input (Impedance) is used. The impedance is 3 %, and as a result, the fault current changes,
as shown in Figure 12.
Figure 12: With Series Reactor (Rated power of 50 MVA & SC Voltage 3%)- Simulation results
Comparing the case 3 and 4 simulation results, the series reactor rated power is changed, and the
reactor impedance is kept constant. As a result, the fault current also changed accordingly.
Reference:
• Industrial Power System Analysis Digsilent power factory Training at Power Projects.
• Principles of power system V.K Metha- Rohit Metha,4th Edition.