Cto Charm Field Enclosures en 57582
Cto Charm Field Enclosures en 57582
August 2018
www.emerson.com/deltav 2
CTO CHARM Field Enclosure August 2018
CHARM Field Enclosures Pre-drilled bottom entry with Nickel Plated Brass wire
glands for I/O, power, communications and grounding cables.
All CHARM Field Enclosures come with the following
With standard drill pattern (with stop plugs). Or
equipment installed:
cable transit system with flexible cable gland blocks that
Power distribution and isolation components for primary are installed in a cable entry frame.
and secondary 24V DC Power to CHARM I/O Cards.
Name plate engraved with custom supplied cabinet
AC power feeds with redundant AC/DC 24V DC bulk identification information.
power supplies.
24V DC power distribution for injected power or 4-wire
- or - transmitter power: 8 or 12 fused circuits, prewired to
all base plates. (Selecting this option, upgrades the
24V DC power distribution from remote.
power supplies and includes a redundancy diode to
Halogen-Free wire ducts. bring primary and secondary power feeds to a common
injected power distribution).
Grounding bars for CG (Chassis Ground) and DC
Reference Ground. Heaters, for extreme low temperature installations.
Enclosures are designed for bottom entry for all cables Warning label languages other than standard English,
(power, network, and I/O signals) French, Spanish, and German.
The CTO CHARM Field Enclosures support all available low All CTO options are implemented, tested and shipped to site as
voltage CHARM I/O types with 24V DC bussed field power. one package, significantly reducing the required upfront design
and certification effort.
CHARM I/O Cards (CIOC), Non-standard CHARM terminal blocks,
and CHARMs are not included and are to be ordered separately. The following sections provide a more detailed specification for
the CTO CHARM Field Enclosures and available options.
CTO Options
For a particular base enclosure model, a number
of pre-engineered CTO options can be specified.
These options include:
Type of CHARMs:
48IO (Non-IS)/ 48IO (IS)/ 48IO with 24 (IS)+24(Non-IS)
96IO (Non-IS)/ 96IO (IS)/ 96IO with 60(IS)+36 (Non-IS)
Actual CHARMs to be ordered separately.
www.emerson.com/deltav 3
CTO CHARM Field Enclosure August 2018
No. Power
Permitted Location /
Base Model No. Description CHARM Requirements
World Area
IO (Prim and Sec)
EU-FE-48-DC-CIOC-SA DC Powered Field Enclosure for 48 CHARM 48 24V DC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-48-DC-CIOC-SA DC Powered Field Enclosure for 48 CHARM 48 24V DC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-48-DC-CIOC-HA DC Powered Field Enclosure for 48 CHARM 48 24V DC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-48-DC-CIOC-HA DC Powered Field Enclosure for 48 48 24V DC Hazardous Area
CHARM I/O; NEC/CEC Hazardous Locations; (US/Canada)
Class I, Division 2; Class I, Zone 2.
EU-FE-48-AC-CIOC-SA AC Powered Field Enclosure for 48 CHARM 48 120/230V AC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-48-AC-CIOC-SA AC Powered Field Enclosure for 48 CHARM 48 115V AC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-48-AC-CIOC-HA AC Powered Field Enclosure for 48 CHARM 48 120/230V AC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-48-AC-CIOC-HA AC Powered Field Enclosure for 48 48 115V AC Hazardous Area
CHARM I/O; NEC/CEC Hazardous Locations; (US/Canada)
Class I, Division 2; Class I, Zone 2.
EU-FE-96-AC-CIOC-SA AC Powered Field Enclosure for 96 CHARM 96 120/230V AC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-96-AC-CIOC-SA AC Powered Field Enclosure for 96 CHARM 96 115V AC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-96-AC-CIOC-HA AC Powered Field Enclosure for 96 CHARM 96 120/230V AC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-96-AC-CIOC-HA AC Powered Field Enclosure for 96 CHARM 96 115V AC Hazardous Area
I/O; NEC/CEC Hazardous Locations; Class I, (US/Canada)
Division 2; Class I, Zone 2.
EU-FE-96-AC-VLV-SA AC Powered Indoor Field Enclosure with 60 60 24V DC Safe Area
CHARM I/O and ASCO Valve Island; CE; Safe CE (Europe)
Area Locations
EU-FE-96-DC-VLV-SA DC Powered Indoor Field Enclosure with 60 60 120/230V AC Safe Area
CHARM I/O and ASCO Valve Island; CE; Safe CE (Europe)
Area Locations
Overview of CHARM Field Enclosures.
The CTO base model reference for field enclosures uses the following naming convention:
“EU or NA-FE-XX-YY-CIOC-ZZ”, where
• EU = Europe Design Standards and Regulations or NA = US/Canada Design Standards and Regulations.
• XX = maximum I/O’s count in this CTO model.
• YY = Incoming Power, DC: 24V DC or AC: 120/230V AC/115V AC.
• CIOC = short description of content and purpose.
• ZZ = SA: for use in Safe Area, HA: for use in Hazardous Area (Class 1 Div 2 or Class 1 Zone 2)
www.emerson.com/deltav 4
CTO CHARM Field Enclosure August 2018
Overview of CHARM Field Enclosures base models and options for EUROPE World Area
EU-FE-48-DC-CIOC-HA
EU-FE-48-AC-CIOC-HA
EU-FE-96-AC-CIOC-HA
EU-FE-48-DC-CIOC-SA
EU-FE-48-AC-CIOC-SA
EU-FE-96-AC-CIOC-SA
EU-FE-96-DC-VLV-SA
EU-FE-96-AC-VLV-SA
Base Model
•: Default option setting
1 48IO - NONIS ● ● ● ●
C1 2 48IO - IS ○ ○ ○ ○ NA
1 96IO - NONIS ● ● NA
Type of CHARMs
C2 2 96IO - IS ○ ○
1 60IO - NONIS ● ●
C3 NA
2 60IO - IS ○ ○
5 Copper ○ ○ ○ ○ ○ ○ ● ●
1 No ● ● ● ●
2 Single Heater ○ ○ ○ ○
Heater F NA NA
3 Two Heaters ○ ○ NA
4 Three Heaters NA ○ ○
1 No ● ●
WIOC I NA NA
2 Yes (reduces qty of CHARM baseplates by 2) ○ ○
www.emerson.com/deltav 5
CTO CHARM Field Enclosure August 2018
Overview of CHARM Field Enclosures base models and options for US/Canada World Area
NA-FE-48-DC-CIOC-HA
NA-FE-48-AC-CIOC-HA
NA-FE-96-AC-CIOC-HA
NA-FE-48-DC-CIOC-SA
NA-FE-48-AC-CIOC-SA
NA-FE-96-AC-CIOC-SA
Base Model
Certification as per World Area cCSAus cCSAus cCSAus cCSAus cCSAus cCSAus
1 48IO - NONIS ● ● ● ●
C1 2 48IO - IS ○ ○ ○ ○ NA
1 96IO - NONIS ● ●
Type of CHARMs
C2 2 96IO - IS ○ ○
1 60IO - NONIS
C3 NA
2 60IO - IS
5 Copper ○ ○ ○ ○ ○ ○
1 No ● ● ● ●
2 Single Heater ○ ○ ○ ○
Heater F NA
3 Two Heaters ○ ○ NA
4 Three Heaters NA ○ ○
www.emerson.com/deltav 6
CTO CHARM Field Enclosure August 2018
1 No ● ●
WIOC J NA
2 Yes (Reduces qty of CHARM baseplates by 2) ○ ○
www.emerson.com/deltav 7
CTO CHARM Field Enclosure August 2018
EU-FE-48-DC-CIOC-SA
Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution. Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 8
CTO CHARM Field Enclosure August 2018
NA-FE-48-DC-CIOC-SA
Weight ~125 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution. Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2)
or Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 9
CTO CHARM Field Enclosure August 2018
EU-FE-48-DC-CIOC-HA
Weight ~135 kg
Certifications ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc
for NON-IS CHARMS
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 10
CTO CHARM Field Enclosure August 2018
NA-FE-48-DC-CIOC-HA
Weight ~135 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 11
CTO CHARM Field Enclosure August 2018
EU-FE-48-AC-CIOC-SA
Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals,
and circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 12
CTO CHARM Field Enclosure August 2018
NA-FE-48-AC-CIOC-SA
Weight ~125 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 13
CTO CHARM Field Enclosure August 2018
EU-FE-48-AC-CIOC-HA
Weight ~135 kg
Certifications ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc
for NON-IS CHARMS
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 14
CTO CHARM Field Enclosure August 2018
NA-FE-48-AC-CIOC-HA
Weight ~135 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
48 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
www.emerson.com/deltav 15
CTO CHARM Field Enclosure August 2018
EU-FE-96-AC-CIOC-SA
Weight ~165 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 10A and
full redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
4 x CHARM Base Plates and address plugs.
96 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x WIOC (Optional) with 72 CHARM IO
www.emerson.com/deltav 16
CTO CHARM Field Enclosure August 2018
NA-FE-96-AC-CIOC-SA
Weight ~165 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution (*) Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
8 x CHARM Base Plates and address plugs.
96 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x WIOC (Optional) with 72 CHARM IO
www.emerson.com/deltav 17
CTO CHARM Field Enclosure August 2018
EU-FE-96-AC-CIOC-HA
Weight ~175 kg
ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc for
NON-IS CHARMS
Certifications
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution (*) Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 10A and
full redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
8 x CHARM Base Plates and address plugs.
96 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x WIOC (Optional) with 72 CHARM IO
www.emerson.com/deltav 18
CTO CHARM Field Enclosure August 2018
NA-FE-96-AC-CIOC-HA
Weight ~175 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution (*) Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
8 x CHARM Base Plates and address plugs.
96 x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x WIOC (Optional) with 72 CHARM IO
www.emerson.com/deltav 19
CTO CHARM Field Enclosure August 2018
EU-FE-96-DC-VLV-SA
Material (*) Stainless Steel SS304, 1.5 mm (Clean Room Enclosure optional)
Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution (*) Primary and secondary 24 VDC power supply supplied from
outside the Field Enclosure.
Redundant 24 VDC distribution through power terminals; full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 60 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
5 x CHARM Base Plates and address plugs.
60x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x ASCO valve (12 Channel Valve by default)
No DeltaV equipment is included in the base model. All DeltaV
equipment is to be specified separately through the Emerson
quoting tools.
www.emerson.com/deltav 20
CTO CHARM Field Enclosure August 2018
EU-FE-96-AC-VLV-SA
Material (*) Stainless Steel SS304, 1.5 mm (Clean Room Enclosure optional)
Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution (*) Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24VDC Power Supplies: 2x10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 60 CHARM I/O
channels, including:
1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
5 x CHARM Base Plates and address plugs.
60x CHARM standard terminal blocks - Screw type.
Base Plate and Channel Identifier Labels.
1 x ASCO valve (12 Channel Valve by default)
No DeltaV equipment is included in the base model. All DeltaV
equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.
www.emerson.com/deltav 21
CTO CHARM Field Enclosure August 2018
Design Considerations
Environmental Specifications
The CTO CHARM Field Enclosures are certified for an ambient temperature range of -20 to +50 degrees °C. With the two and
three heaters options this can be extended to -40 to +50 degree C. Caution: Operating any electronics at the higher end of its
temperature range for long periods of time will shorten its expected lifetime, see Effects of Heat and Airflow Inside an Enclosure
White Paper for more information.
The humidity specification for the CTO field enclosures is 5-95% relative humidity, none condensing.
The table below specifies the impact of CTO configurable options on the heat dissipation within the CTO enclosures: assuming
wall-mount installation (back side not used for heat dissipation), installation in shaded area (no direct sunlight) and an internal heat
dissipation not greater than the value specified in the column “Maximum allowed heat dissipation inside the enclosure.”
It is advised to calculate the heat dissipation and power consumption for each individual enclosure with the actual quantity and mix
of CHARM types. In high ambient temperatures the CHARM capacity of the enclosure may have to be reduced depending on the
mix of CHARM types.
User Configurable Heart contributing options Maximum allowable
Maximum allowed Total Dissipation CIOC Heat
CTO Enclosure Model A B C heat load for CHARM
heat dissipation (A+B+C) Dissipation (W)
Ethernet InJ. Power Power Supply HW
FO NO - 16,4 90,6
FO YES - 24 ,2 82 ,8
EU-FE-48-DC-CIOC-SA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99 ,2
FO NO - 16,4 90,6
FO YES - 24,2 82,8
NA-FE-48-DC-CIOC-SA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99,2
FO NO - 16,4 90,6
FO YES - 24 ,2 82 ,8
EU-FE-48-DC-CIOC-HA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99 .2
FO NO - 16,4 90,6
FO YES - 24,2 82,8
NA-FE-48-DC-CIOC-HA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
EU-FE-48-AC-CIOC-SA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
NA-FE-48-AC-CIOC-SA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
EU-FE-48-AC-CIOC-HA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75.2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
NA-FE-48-AC-CIOC-HA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31 ,8 75,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62 ,2 89,8
EU-FE-96-AC-CIOC-SA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62,2 89,8
NA-FE-96-AC-CIOC-SA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62 ,2 89,8
EU-FE-96-AC-CIOC-HA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2
www.emerson.com/deltav 22
CTO CHARM Field Enclosure August 2018
CE
• EN 61326-1 , EN 61010-1
www.emerson.com/deltav 23
CTO CHARM Field Enclosure August 2018
CHARM I/O Card Carrier must be ordered separately • A quotation for the fully assembled Field Enclosure.
CHARM I/O Cards must be ordered separately • The detailed specification (drawing package) matching
your configuration, including the Bill of Materials.
CHARM Baseplates must be ordered separately
4. Approve the drawing package for construction.
CHARMs and terminal blocks must be ordered separately
5. Order the CHARM Field Enclosure as per provided quotation
and approved drawings.
How to order a CTO CHARM
6. The CHARM Field Enclosure is assembled, factory tested and
Field Enclosure? delivered to site. The delivery includes the as-built drawing
CTO CHARM Field Enclosures are pre-engineered solutions package (AutoCAD).
developed by Emerson’s Project Management Office (PMO)
For questions related to specific project quotations or order
and made available from Emerson Supply Chain. Basically, the
processing, please contact your local Emerson Sales office or
following steps are followed to obtain a CHARM Field enclosure:
your regional Emerson assembly center:
1. Specify the CHARM Field Enclosure by selecting the
For US/Canada (NASAD):
base model and the options required for the project.
[email protected]
A Configuration tool is available to aid in the selection of the
right combination of options for your CTO field enclosure. For Europe iCenter Cluj:
[email protected]
2. Generate the specification sheet from the configuration tool
and send this to your world area contact. For Asia Pacific Singapore iCenter:
[email protected]
Emerson
North America, Latin America:
©2018, Emerson. All rights reserved.
+1 800 833 8314 or
+1 512 832 3774 The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
Asia Pacific: respective owners.
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while
diligent efforts were made to ensure their accuracy, they are not to be construed as warranties
Europe, Middle East: or guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.