DeltaV Distributed Control System Product Data Sheet

August 2018

CTO CHARM Field Enclosure

Configure to Order (CTO) CHARM Field Enclosures.

„„Delivers Electronic Marshalling enabled by Introduction


CHARacterization Modules (CHARM) technology
The DeltaV™ CTO CHARM Field Enclosures provide an off-
„„Reduce system footprint the-shelf solution for faster project execution and reduced
installation costs. Field Enclosures are factory tested products
„„Eliminate I/O home run cables and ready for installation in the field. Electronic Marshalling
eliminates traditional I/O design tasks and allows field wiring
„„Significantly reduce cabinet design engineering
to start long before control strategies are finalized.
„„Fully documented package The field enclosures are designed for hazardous areas and harsh
environments, from extreme temperatures to corrosive gases.
CTO CHARM Field Enclosure August 2018

Benefits Before delivery, each field enclosure undergoes a full in-house


inspection and test, to assure that it is fully operational before
Delivers Electronic Marshalling enabled by CHARMs leaving the factory. Electronic Marshalling eliminates the need
technology: The CHARM Field Enclosures offer the full benefits for custom designs. These enclosures can be ordered, together
of Electronic Marshalling. The individual channels can be with the DeltaV Electronic Marshalling equipment and CHARM
defined for any combination of field signal type, as required I/O and delivered directly to site to begin field wiring (Factory
by the process equipment. This allows for 100 % utilization Acceptance Test (FAT) with client may be optional).
of channels, regardless of the I/O signal mix. Late changes
are easily accommodated with minimal re-engineering and The CTO CHARM Field Enclosures are ordered by selecting a
no rewiring. base enclosure model and required options to meet specific
project needs.
Reduce system footprint: Equipment room footprint is greatly
reduced by replacing traditional marshalling cabinets with field A range of base enclosure models are available:
mounted I/O cards. „„ For different I/O quantities: 48 or 96 I/O’s.
Eliminate I/O home run cables: Field instrumentation wiring „„ For different power distribution needs: DC-Powered or
is reduced to the signal pair that connects the field device to AC- Powered.
the Field Enclosure. Save on home run multi-core cables, cable
„„ For different environmental requirements: Safe Area or
trays, associated engineering, and documentations.
Hazardous Area.
Significantly reduce cabinet design engineering: The
„„ For different electrical codes/regulations (world areas):
CHARM Field Enclosures are pre-engineered and factory tested.
Europe and US/Canada.
The I/O flexibility allows the same design to serve a wide variety
of I/O signals, conditioned individually by the CHARM. Field Each base model is further explained in the coming sections.
wiring design is complete at the terminal block.
Configurable options include the type of CHARMS (I.S. or non
Fully documented package: Each Field Enclosure is supplied I.S.), network (Fiberoptic or Copper), enclosure material, cable
with full documentation and engineering drawings showing entry, nameplate engraving, injected power, heater, etc.
internal lay-out, bill of materials, and internal wiring. They
are designed to meet local building code and industry best System planning
practices in order to deliver proven functionality with Electronic Marshalling changes the game with respect to
minimal costs. control system I/O planning. The field I/O wiring can be
designed independently from the control strategy design,
Description allowing E&I engineers to determine the number and type of
I/O based on the process design.
The CTO CHARM Field Enclosures offering comprises a range
of pre-engineered solutions based on industry standard, wall „„ Count the I/O requirements and determine the number of
mounting enclosures that are available in AC-powered and DC- CHARM Field Enclosures you need.
powered version with space for 48 or 96 CHARM I/O depending „„ Determine whether the enclosure is for a safe area or
on the model chosen. hazardous area.
The designs have considered specific requirements related „„ Plan the power distribution and install the enclosures.
to outdoor installation in the field, including environmental
protection, heat dissipation, power and grounding „„ Wire the field devices and commission them.
requirements, and installation in hazardous areas. „„ When control strategies and associated controller hardware
All components are prewired and tested at the factory. Simply is finalized, simply assign the I/O signals to the controllers as
select the required DeltaV Electronic Marshalling equipment needed, no wiring changes. You can change controller I/O
and the enclosure is ready to install, connect the field wiring, assignments with the click of a mouse, without touching a
power and network cables. Install needed CHARMs to wired connection.
commission your loops and autosense the hardware into
your DeltaV system.

www.emerson.com/deltav 2
CTO CHARM Field Enclosure August 2018

CHARM Field Enclosures „„ Pre-drilled bottom entry with Nickel Plated Brass wire
glands for I/O, power, communications and grounding cables.
All CHARM Field Enclosures come with the following
With standard drill pattern (with stop plugs). Or
equipment installed:
cable transit system with flexible cable gland blocks that
„„ Power distribution and isolation components for primary are installed in a cable entry frame.
and secondary 24V DC Power to CHARM I/O Cards.
„„ Name plate engraved with custom supplied cabinet
„„ AC power feeds with redundant AC/DC 24V DC bulk identification information.
power supplies.
„„ 24V DC power distribution for injected power or 4-wire
- or - transmitter power: 8 or 12 fused circuits, prewired to
all base plates. (Selecting this option, upgrades the
24V DC power distribution from remote.
power supplies and includes a redundancy diode to
„„ Halogen-Free wire ducts. bring primary and secondary power feeds to a common
injected power distribution).
„„ Grounding bars for CG (Chassis Ground) and DC
Reference Ground. „„ Heaters, for extreme low temperature installations.

„„ Reference. „„ Blue marking for wire ducts.

„„ Name Plate. „„ Breather: Brass Ni plated / SS316L.

„„ Removable Gland Plate (5mm). „„ Ethernet: Fiberoptic / Copper.

Enclosures are designed for bottom entry for all cables „„ Warning label languages other than standard English,
(power, network, and I/O signals) French, Spanish, and German.

The CTO CHARM Field Enclosures support all available low All CTO options are implemented, tested and shipped to site as
voltage CHARM I/O types with 24V DC bussed field power. one package, significantly reducing the required upfront design
and certification effort.
CHARM I/O Cards (CIOC), Non-standard CHARM terminal blocks,
and CHARMs are not included and are to be ordered separately. The following sections provide a more detailed specification for
the CTO CHARM Field Enclosures and available options.
CTO Options
For a particular base enclosure model, a number
of pre-engineered CTO options can be specified.
These options include:

„„ Type of CHARMs:
48IO (Non-IS)/ 48IO (IS)/ 48IO with 24 (IS)+24(Non-IS)
96IO (Non-IS)/ 96IO (IS)/ 96IO with 60(IS)+36 (Non-IS)
Actual CHARMs to be ordered separately.

„„ Enclosure material: stainless steel SS304 or SS316L. Stainless


steel provides protection for corrosive environments
(category CSA TYPE 4X). SS316L provides superior corrosive
protection and is typically applied in off-shore applications
(salt resistant).

www.emerson.com/deltav 3
CTO CHARM Field Enclosure August 2018

Overview of CHARM Field Enclosures – Base Models:

No. Power
Permitted Location /
Base Model No. Description CHARM Requirements
World Area
IO (Prim and Sec)
EU-FE-48-DC-CIOC-SA DC Powered Field Enclosure for 48 CHARM 48 24V DC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-48-DC-CIOC-SA DC Powered Field Enclosure for 48 CHARM 48 24V DC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-48-DC-CIOC-HA DC Powered Field Enclosure for 48 CHARM 48 24V DC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-48-DC-CIOC-HA DC Powered Field Enclosure for 48 48 24V DC Hazardous Area
CHARM I/O; NEC/CEC Hazardous Locations; (US/Canada)
Class I, Division 2; Class I, Zone 2.
EU-FE-48-AC-CIOC-SA AC Powered Field Enclosure for 48 CHARM 48 120/230V AC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-48-AC-CIOC-SA AC Powered Field Enclosure for 48 CHARM 48 115V AC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-48-AC-CIOC-HA AC Powered Field Enclosure for 48 CHARM 48 120/230V AC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-48-AC-CIOC-HA AC Powered Field Enclosure for 48 48 115V AC Hazardous Area
CHARM I/O; NEC/CEC Hazardous Locations; (US/Canada)
Class I, Division 2; Class I, Zone 2.
EU-FE-96-AC-CIOC-SA AC Powered Field Enclosure for 96 CHARM 96 120/230V AC Safe Area
I/O; CE; Safe Area Locations. CE (Europe)
NA-FE-96-AC-CIOC-SA AC Powered Field Enclosure for 96 CHARM 96 115V AC Safe Area
I/O; NEC/CEC Ordinary Locations. (US/Canada)
EU-FE-96-AC-CIOC-HA AC Powered Field Enclosure for 96 CHARM 96 120/230V AC Hazardous Area
I/O; CE; ATEX; IECEx, Zone 2 Locations. ATEX/IECEx Zone 2
NA-FE-96-AC-CIOC-HA AC Powered Field Enclosure for 96 CHARM 96 115V AC Hazardous Area
I/O; NEC/CEC Hazardous Locations; Class I, (US/Canada)
Division 2; Class I, Zone 2.
EU-FE-96-AC-VLV-SA AC Powered Indoor Field Enclosure with 60 60 24V DC Safe Area
CHARM I/O and ASCO Valve Island; CE; Safe CE (Europe)
Area Locations
EU-FE-96-DC-VLV-SA DC Powered Indoor Field Enclosure with 60 60 120/230V AC Safe Area
CHARM I/O and ASCO Valve Island; CE; Safe CE (Europe)
Area Locations
Overview of CHARM Field Enclosures.
The CTO base model reference for field enclosures uses the following naming convention:
“EU or NA-FE-XX-YY-CIOC-ZZ”, where
• EU = Europe Design Standards and Regulations or NA = US/Canada Design Standards and Regulations.
• XX = maximum I/O’s count in this CTO model.
• YY = Incoming Power, DC: 24V DC or AC: 120/230V AC/115V AC.
• CIOC = short description of content and purpose.
• ZZ = SA: for use in Safe Area, HA: for use in Hazardous Area (Class 1 Div 2 or Class 1 Zone 2)

www.emerson.com/deltav 4
CTO CHARM Field Enclosure August 2018

Overview of CHARM Field Enclosures base models and options for EUROPE World Area

EU-FE-48-DC-CIOC-HA

EU-FE-48-AC-CIOC-HA

EU-FE-96-AC-CIOC-HA
EU-FE-48-DC-CIOC-SA

EU-FE-48-AC-CIOC-SA

EU-FE-96-AC-CIOC-SA

EU-FE-96-DC-VLV-SA

EU-FE-96-AC-VLV-SA
Base Model
•: Default option setting

o : Configure to option setting. (Different


#CHARM I/O 48IO 48IO 48IO 48IO 96IO 96IO 96IO 96IO
from Default)
: Intentionally left blank to fill in your Power Input (230V AC / 24V DC) DC DC AC AC AC AC DC AC
configuration choices Location (Safe Area -SA, Hazardous Area - HA) SA HA SA HA SA HA SA SA

Certification as per World Area CE ATEX CE ATEX CE ATEX CE CE

Enclosure Options Enclosure Options Options Selection

1 Stainless Steel SS304 with single gland plate ● ● ● ● ● ● ● ●

Enclosure Material A 2 Stainless Steel SS316L with single gland plate ○ ○ ○ ○ ○ ○ ○ ○

3 Hygienic Design enclosure NA ○ ○

1 Undrilled Gland Plate ● ● ● ● ● ● ● ●

Cable Entry B 2 Gland Plate with Standard Drill Pattern ○ ○ ○ ○ ○ ○ ○ ○

3 Gland Plate with Roxtec Glands ○ ○ ○ ○ ○ ○ NA

1 48IO - NONIS ● ● ● ●

C1 2 48IO - IS ○ ○ ○ ○ NA

3 24IO (IS) + 24IO (NONIS) ○ ○ ○ ○

1 96IO - NONIS ● ● NA
Type of CHARMs
C2 2 96IO - IS ○ ○

3 60IO (IS) + 36IO (NONIS) NA ○ ○

1 60IO - NONIS ● ●
C3 NA
2 60IO - IS ○ ○

1 No (5A Power Supply) ● ● ● ●


D1 NA
2 Yes (8 Circuit - 10Amp Power Supply + Diode) ○ ○ ○ ○
24V DC Injected power
1 No (10A Power Supply) ● ● ● ●
D2 NA
2 Yes (12 Circuits - 20Amp Power Supply + Diode) ○ ○ ○ ○

1 Multimode Fibre Optic w / Adapter ● ● ● ● ● ●

2 Multimode Fibre Optic w / Splice Cassettes ○ ○ ○ ○ ○ ○


NA
3 Single-mode Fibre Optic w / Adapter ○ ○ ○ ○ ○ ○
Ethernet - Safety Network E
4 Single-mode Fibre Optic w / Splice Cassettes ○ ○ ○ ○ ○ ○

5 Copper ○ ○ ○ ○ ○ ○ ● ●

6 Fiber Optic (Singe Mode IOP) NA ○ ○

1 No ● ● ● ●

2 Single Heater ○ ○ ○ ○
Heater F NA NA
3 Two Heaters ○ ○ NA

4 Three Heaters NA ○ ○

1 English + French + German + Spanish ● ● ● ● ● ● ● ●

2 English + French + German + User Specific Language ○ ○ ○ ○ ○ ○ ○ ○


Warning Label Languages G
English + French + Spanish + User
3 ○ ○ ○ ○ ○ ○ ○ ○
Specific Language

1 12 Coil Standard Configuration Valve Island ● ●

2 12 Coil Custom Configuration Valve Island ○ ○

3 24 Coil Standard Configuration Valve Island ○ ○


Type of Valve Island H NA
4 24 Coil Custom Configuration Valve Island ○ ○

5 32 Coil Custom Configuration Valve Island ○ ○

6 32 Coil Standard Configuration Valve Island ○ ○

1 No ● ●
WIOC I NA NA
2 Yes (reduces qty of CHARM baseplates by 2) ○ ○

www.emerson.com/deltav 5
CTO CHARM Field Enclosure August 2018

Overview of CHARM Field Enclosures base models and options for US/Canada World Area

NA-FE-48-DC-CIOC-HA

NA-FE-48-AC-CIOC-HA

NA-FE-96-AC-CIOC-HA
NA-FE-48-DC-CIOC-SA

NA-FE-48-AC-CIOC-SA

NA-FE-96-AC-CIOC-SA
Base Model

•: Default option setting

o : Configure to option setting. (Different


#CHARM I/O 48IO 48IO 48IO 48IO 96IO 96IO
from Default)
: Intentionally left blank to fill in your Power Input (110 VAC / 24 VDC) DC DC AC AC AC AC
configuration choices Location (Safe Area -SA, Hazardous Area - HA) SA HA SA HA SA HA

Certification as per World Area cCSAus cCSAus cCSAus cCSAus cCSAus cCSAus

Enclosure Options Enclosure Options Options Selection

1 Stainless Steel SS304 with single gland plate ● ● ● ● ● ●


Enclosure Material A
2 Stainless Steel SS316L with single gland plate ○ ○ ○ ○ ○ ○

1 Undrilled Gland Plate ● ● ● ● ● ●

Cable Entry B 2 Gland Plate with Standard Drill Pattern ○ ○ ○ ○ ○ ○

3 Gland Plate with Roxtec Glands ○ ○ ○ ○ ○ ○

1 48IO - NONIS ● ● ● ●

C1 2 48IO - IS ○ ○ ○ ○ NA

3 24IO (IS) + 24IO (NONIS) ○ ○ ○ ○

1 96IO - NONIS ● ●
Type of CHARMs
C2 2 96IO - IS ○ ○

3 60IO (IS) + 36IO (NONIS) NA ○ ○

1 60IO - NONIS
C3 NA
2 60IO - IS

1 No (5A Power Supply) ● ● ● ●


D1 NA
2 Yes (8 Circuit - 10Amp Power Supply + Diode) ○ ○ ○ ○
24V DC Injected power
1 No (10A Power Supply) ● ●
D2 NA
2 Yes (12 Circuits - 20Amp Power Supply + Diode) ○ ○

1 Multimode Fibre Optic w / Adapter ● ● ● ● ● ●

2 Multimode Fibre Optic w / Splice Cassettes ○ ○ ○ ○ ○ ○

3 Single-mode Fibre Optic w / Adapter ○ ○ ○ ○ ○ ○


Ethernet - Safety Network E
4 Single-mode Fibre Optic w / Splice Cassettes ○ ○ ○ ○ ○ ○

5 Copper ○ ○ ○ ○ ○ ○

6 Fiber Optic (Singe Mode IOP) NA

1 No ● ● ● ●

2 Single Heater ○ ○ ○ ○
Heater F NA
3 Two Heaters ○ ○ NA

4 Three Heaters NA ○ ○

1 English + French + German + Spanish ● ● ● ● ● ●

English + French + German + User


2 ○ ○ ○ ○ ○ ○
Warning Label Language G Specific Language

English + French + Spanish + User


3 ○ ○ ○ ○ ○ ○
Specific Language

Surge Protection Device 1 No ● ● ● ●


H NA
(for non-CSLS Field Enclosures) 2 Yes ○ ○ ○ ○

www.emerson.com/deltav 6
CTO CHARM Field Enclosure August 2018

Enclosure Options Enclosure Options Options Selection

1 12 Coil Standard Configuration Valve Island

2 12 Coil Custom Configuration Valve Island

3 24 Coil Standard Configuration Valve Island


Type of Valve Island I NA
4 24 Coil Custom Configuration Valve Island

5 32 Coil Custom Configuration Valve Island

6 32 Coil Standard Configuration Valve Island

1 No ● ●
WIOC J NA
2 Yes (Reduces qty of CHARM baseplates by 2) ○ ○

www.emerson.com/deltav 7
CTO CHARM Field Enclosure August 2018

EU-FE-48-DC-CIOC-SA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution. Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default option settings. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-48-DC-CIOC-SA.

www.emerson.com/deltav 8
CTO CHARM Field Enclosure August 2018

NA-FE-48-DC-CIOC-SA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution. Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2)
or Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default option settings. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-48-DC-CIOC-SA.

www.emerson.com/deltav 9
CTO CHARM Field Enclosure August 2018

EU-FE-48-DC-CIOC-HA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~135 kg
Certifications ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc
for NON-IS CHARMS
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default option settings. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-48-DC-CIOC-HA.

www.emerson.com/deltav 10
CTO CHARM Field Enclosure August 2018

NA-FE-48-DC-CIOC-HA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~135 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution Primary and secondary 24 VDC power to be supplied from
outside the Field Enclosure.
Includes full redundant (primary and secondary) 24 VDC
distribution through power terminals and circuit breakers.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.

Other Mounting plate, Halogen-Free wire ducts, external wall


mounting brackets, door clamps, ground bars, drip edge,
breather-drain.
(*)Specifications given for the base model with default options. WIOC is optional. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-48-DC-CIOC-HA.

www.emerson.com/deltav 11
CTO CHARM Field Enclosure August 2018

EU-FE-48-AC-CIOC-SA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals,
and circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-48-AC-CIOC-SA

www.emerson.com/deltav 12
CTO CHARM Field Enclosure August 2018

NA-FE-48-AC-CIOC-SA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, drip edge,
breather-drain.
(*) Specifications given for the base model with default options. WIOC is optional. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-48-AC-CIOC-SA .

www.emerson.com/deltav 13
CTO CHARM Field Enclosure August 2018

EU-FE-48-AC-CIOC-HA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~135 kg
Certifications ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc
for NON-IS CHARMS
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. WIOC is optional. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-48-AC-CIOC-HA.

www.emerson.com/deltav 14
CTO CHARM Field Enclosure August 2018

NA-FE-48-AC-CIOC-HA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915mm (W) x 1070mm (H) x 325mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~135 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 5A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 48 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 48 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, drip edge,
breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-48-AC-CIOC-HA.

www.emerson.com/deltav 15
CTO CHARM Field Enclosure August 2018

EU-FE-96-AC-CIOC-SA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915 mm (W) x 1220mm (H) x 475 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~165 kg
Certifications CE, installation in Safe Area Locations
Power Requirements – Internal Power Distribution Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 10A and
full redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 4 x CHARM Base Plates and address plugs.
„„ 96 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x WIOC (Optional) with 72 CHARM IO

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-96-AC-CIOC-SA.

www.emerson.com/deltav 16
CTO CHARM Field Enclosure August 2018

NA-FE-96-AC-CIOC-SA

Material (*) Stainless Steel SS304 1.5 mm

Dimensions 915 mm (W) x 1220mm (H) x 475 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 – Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~165 kg
Certifications cCSAus for Ordinary Locations
Power Requirements – Internal Power Distribution (*) Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 8 x CHARM Base Plates and address plugs.
„„ 96 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x WIOC (Optional) with 72 CHARM IO

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with example options. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-96-AC-CIOC-SA.

www.emerson.com/deltav 17
CTO CHARM Field Enclosure August 2018

EU-FE-96-AC-CIOC-HA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915 mm (W) x 1220mm (H) x 475 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~175 kg
ATEX, IECEx; Ex d e ic nA nC [op is Ga] IIC T4 Gc for
NON-IS CHARMS
Certifications
ATEX, IECEx; Ex d e [ia Ga] [ic] nA nC [op is Ga] IIC T4 Gc
for IS CHARMS
Power Requirements – Internal Power Distribution (*) Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24 VDC bulk power supplies: 2 x 10A and
full redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper
Converter (MM or SM), SC adaptors, SC-LC FO patch cables,
Multimode 50/125-micron core/cladding diameters (OM2) or
Single mode 9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 8 x CHARM Base Plates and address plugs.
„„ 96 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x WIOC (Optional) with 72 CHARM IO

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.

Other Mounting plate, Halogen-Free wire ducts, external wall


mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-96-AC-CIOC-HA.

www.emerson.com/deltav 18
CTO CHARM Field Enclosure August 2018

NA-FE-96-AC-CIOC-HA

Material (*) Stainless Steel SS304, 1.5 mm

Dimensions 915 mm (W) x 1220mm (H) x 475 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 66 –Type 4X (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~175 kg
Certifications cCSAus for Hazardous Locations;
Non-IS CHARMS:
Class I, Division 2, Groups B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC IIB+H2 T4 Gc
IS CHARMS:
Class I, Division 2, Groups A, B, C and D;
Class I, Zone 2, A/Ex e d ic nA nC [ia IIC Ga] [ic IIC Gc] IIB+H2
T4 Gc
Power Requirements – Internal Power Distribution (*) Primary and secondary 115 VAC power supply supplied from
outside the Field Enclosure.
Redundant 115 VAC distribution through power terminals and
circuit breakers. 24 VDC bulk power supplies: 2 x 10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 96 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 8 x CHARM Base Plates and address plugs.
„„ 96 x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x WIOC (Optional) with 72 CHARM IO

No DeltaV equipment is included in the base model. All DeltaV


equipment is to be specified separately through the Emerson
quoting tools.

Other Mounting plate, Halogen-Free wire ducts, external wall


mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for NA-FE-96-AC-CIOC-HA.

www.emerson.com/deltav 19
CTO CHARM Field Enclosure August 2018

EU-FE-96-DC-VLV-SA

Material (*) Stainless Steel SS304, 1.5 mm (Clean Room Enclosure optional)

Dimensions 915 mm (W) x 1070mm (H) x 325 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 65 (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications CE, installation in Safe Area Locations

Power Requirements – Internal Power Distribution (*) Primary and secondary 24 VDC power supply supplied from
outside the Field Enclosure.
Redundant 24 VDC distribution through power terminals; full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable.
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 60 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 5 x CHARM Base Plates and address plugs.
„„ 60x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x ASCO valve (12 Channel Valve by default)
No DeltaV equipment is included in the base model. All DeltaV
equipment is to be specified separately through the Emerson
quoting tools.

Other Mounting plate, Halogen-Free wire ducts, external wall


mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-96-DC-VLV-SA.

www.emerson.com/deltav 20
CTO CHARM Field Enclosure August 2018

EU-FE-96-AC-VLV-SA

Material (*) Stainless Steel SS304, 1.5 mm (Clean Room Enclosure optional)

Dimensions 915 mm (W) x 1070mm (H) x 325 mm (D)

Access Single door, left hand hinged

Protection Category (*) IP 65 (Corrosive Environment)

Cable Entry (*) Bottom, single gland plate

Name Plate (*) Outside Door: laser engraved plastic

Weight ~125 kg
Certifications CE, installation in Safe Area Locations

Power Requirements – Internal Power Distribution (*) Primary and secondary 120/230 VAC power supply supplied
from outside the Field Enclosure.
Redundant 120/230 VAC distribution through power terminals
and circuit breakers. 24VDC Power Supplies: 2x10A and full
redundant (primary and secondary) 24 VDC distribution.
Control Network (*) Redundant Single Mode or Multi-Mode FO Converter:
One 100 BASE-FX, Single Mode or Multi-mode port with
LC Connector.
Fiber Optic control network Includes: FO to Copper Converter
(MM or SM), SC adaptors, SC-LC FO patch cables, Multimode
50/125-micron core/cladding diameters (OM2) or Single mode
9/125-micron cable
Example Layout and Installed DeltaV CHARM Equipment (*) This field enclosure has space for 60 CHARM I/O
channels, including:
„„ 1 x CHARM I/O Carrier with redundant copper
Ethernet connectors.
„„ 5 x CHARM Base Plates and address plugs.
„„ 60x CHARM standard terminal blocks - Screw type.
„„ Base Plate and Channel Identifier Labels.
„„ 1 x ASCO valve (12 Channel Valve by default)
No DeltaV equipment is included in the base model. All DeltaV
equipment is to be specified separately through the Emerson
quoting tools.
Other Mounting plate, Halogen-Free wire ducts, external wall
mounting brackets, door clamps, ground bars, external
grounding bolt, drip edge, breather-drain.
(*) Specifications given for the base model with default options. For other available configurations: see Overview of CTO Options.

Specifications for EU-FE-96-AC-VLV-SA.

www.emerson.com/deltav 21
CTO CHARM Field Enclosure August 2018

Design Considerations
Environmental Specifications
The CTO CHARM Field Enclosures are certified for an ambient temperature range of -20 to +50 degrees °C. With the two and
three heaters options this can be extended to -40 to +50 degree C. Caution: Operating any electronics at the higher end of its
temperature range for long periods of time will shorten its expected lifetime, see Effects of Heat and Airflow Inside an Enclosure
White Paper for more information.

The humidity specification for the CTO field enclosures is 5-95% relative humidity, none condensing.

The table below specifies the impact of CTO configurable options on the heat dissipation within the CTO enclosures: assuming
wall-mount installation (back side not used for heat dissipation), installation in shaded area (no direct sunlight) and an internal heat
dissipation not greater than the value specified in the column “Maximum allowed heat dissipation inside the enclosure.”

It is advised to calculate the heat dissipation and power consumption for each individual enclosure with the actual quantity and mix
of CHARM types. In high ambient temperatures the CHARM capacity of the enclosure may have to be reduced depending on the
mix of CHARM types.
User Configurable Heart contributing options Maximum allowable
Maximum allowed Total Dissipation CIOC Heat
CTO Enclosure Model A B C heat load for CHARM
heat dissipation (A+B+C) Dissipation (W)
Ethernet InJ. Power Power Supply HW
FO NO - 16,4 90,6
FO YES - 24 ,2 82 ,8
EU-FE-48-DC-CIOC-SA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99 ,2
FO NO - 16,4 90,6
FO YES - 24,2 82,8
NA-FE-48-DC-CIOC-SA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99,2
FO NO - 16,4 90,6
FO YES - 24 ,2 82 ,8
EU-FE-48-DC-CIOC-HA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99 .2
FO NO - 16,4 90,6
FO YES - 24,2 82,8
NA-FE-48-DC-CIOC-HA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
EU-FE-48-AC-CIOC-SA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
NA-FE-48-AC-CIOC-SA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75,2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
EU-FE-48-AC-CIOC-HA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31,8 75.2
FO NO 5amp 28,4 78,6
FO YES 10amp 48,2 58,8
NA-FE-48-AC-CIOC-HA 115 8
COPPER NO 5amp 12 95
COPPER YES 10amp 31 ,8 75,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62 ,2 89,8
EU-FE-96-AC-CIOC-SA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62,2 89,8
NA-FE-96-AC-CIOC-SA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2
FO NO 10amp 40,4 111 ,6
FO YES 20amp 62 ,2 89,8
EU-FE-96-AC-CIOC-HA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2

www.emerson.com/deltav 22
CTO CHARM Field Enclosure August 2018

FO NO 10amp 40,4 111 ,6


FO YES 20amp 62 ,2 89,8
NA-FE-96-AC-CIOC-HA 160 8
COPPER NO 10amp 24 128
COPPER YES 20amp 45,8 106,2

User Configurable Heart contributing options Maximum allowable


Maximum allowed Total Dissipation CIOC Heat
CTO Enclosure Model A B C heat load for CHARM
heat dissipation (A+B+C) Dissipation (W)
Ethernet InJ. Power Power Supply HW
FO NO - 16,4 90.6
FO YES - 24 ,2 82.8
EU-FE-96-DC-VLV-SA 115 8
COPPER NO - 0 107
COPPER YES - 7,8 99 ,2
FO NO 10amp 40,4 66.6
FO YES 20amp 62 ,2 44.8
EU-FE-96-AC-VLV-SA 115 8
COPPER NO 10amp 24 83
COPPER YES 20amp 45.8 61.2

Power Calculations „„ ATEX


It is advised to calculate power requirements for each individual • EN 60079-0, EN 60079-1, EN 60079-7
enclosure with the actual quantity and mix of CHARM types.
• EN 60079-11, EN 60079-15, EN 60079-28
Enclosure Location „„ IECEx
The ambient temperature specification provided assumes the • IEC 60079-0, IEC 60079-1
enclosure is not exposed to direct sunlight. It is recommended
• IEC 60079-7, IEC 60079-11
to mount the field enclosures in a permanently shaded area.
• IEC 60079-15, IEC 60079-28

Project Customizations „„ cCSAus Ordinary Locations


• CAN/CSA C22.2 No. 61010-1
“…What if a CTO Field Enclosure is 90% what I need, but I
really need my Field Enclosure to have…” • UL 61010-1

Minor customizations as a variation or addition to the standard „„ cCSAus Hazardous Locations


CTO offering can often be developed in such a way that the • CAN/CSA C22.2 No. 60079-0
additional effort is incremental. • CAN/CSA C22.2 No. 60079-1
In case your project would require a customer witnessed FAT, • CAN/CSA C22.2 No. 60079-7
this can also be accommodated.
• CAN/CSA C22.2 No. 60079-15
Please work with your local Emerson Sales office or regional • CAN/CSA C22.2 No. 60079-11
Emerson assembly center to evaluate any impacts of requested
• C22.2 No. 213-M1987
customizations to cost, delivery time and certifications.
• UL 60079-0
System Compatibility • UL 60079-1

CTO Field Enclosures are compatible with DeltaV v11.3.1 • UL 60079-7


and above. • UL 60079-11
CHARM I/O cards require S-series Controllers. • UL 60079-15
• ANSI/ISA 12.12.01
Certifications Refer to the DeltaV S-series Electronic Marshalling or to the
The CTO CHARM Field Enclosures are designed with DeltaV S-series IS Electronic Marshalling Product Data Sheet
components that meet or exceed the following certifications. for certification information on the DeltaV system components.
Depending on the enclosure type (see specs):

„„ CE
• EN 61326-1 , EN 61010-1

www.emerson.com/deltav 23
CTO CHARM Field Enclosure August 2018

Related Products 3. Based on the specification, you will then receive:

„„ CHARM I/O Card Carrier must be ordered separately • A quotation for the fully assembled Field Enclosure.

„„ CHARM I/O Cards must be ordered separately • The detailed specification (drawing package) matching
your configuration, including the Bill of Materials.
„„ CHARM Baseplates must be ordered separately
4. Approve the drawing package for construction.
„„ CHARMs and terminal blocks must be ordered separately
5. Order the CHARM Field Enclosure as per provided quotation
and approved drawings.
How to order a CTO CHARM
6. The CHARM Field Enclosure is assembled, factory tested and
Field Enclosure? delivered to site. The delivery includes the as-built drawing
CTO CHARM Field Enclosures are pre-engineered solutions package (AutoCAD).
developed by Emerson’s Project Management Office (PMO)
For questions related to specific project quotations or order
and made available from Emerson Supply Chain. Basically, the
processing, please contact your local Emerson Sales office or
following steps are followed to obtain a CHARM Field enclosure:
your regional Emerson assembly center:
1. Specify the CHARM Field Enclosure by selecting the
For US/Canada (NASAD):
base model and the options required for the project.
[email protected]
A Configuration tool is available to aid in the selection of the
right combination of options for your CTO field enclosure. For Europe iCenter Cluj:
[email protected]
2. Generate the specification sheet from the configuration tool
and send this to your world area contact. For Asia Pacific Singapore iCenter:
[email protected]

Emerson
North America, Latin America:
©2018, Emerson. All rights reserved.
+1 800 833 8314 or
+1 512 832 3774 The Emerson logo is a trademark and service mark of Emerson Electric Co. The DeltaV logo is
a mark of one of the Emerson family of companies. All other marks are the property of their
Asia Pacific: respective owners.
+65 6777 8211 The contents of this publication are presented for informational purposes only, and while
diligent efforts were made to ensure their accuracy, they are not to be construed as warranties
Europe, Middle East: or guarantees, express or implied, regarding the products or services described herein or their
+41 41 768 6111 use or applicability. All sales are governed by our terms and conditions, which are available on
request. We reserve the right to modify or improve the designs or specifications of our products
www.emerson.com/deltav at any time without notice.