RD10DSR2
RD10DSR2
2
175 kW, Tier 2, Chilled Water, 319 m
Facility Power
The facility power system supplies power to all of the critical and non-critical
components within the data center. The architecture used in this electrical
design is a single path with N+1 UPS and a generator. Switching between
generator power and utility is achieved using a programmable logic controller
(PLC). A 1600 amp bus feeds Prisma P electrical and mechanical
switchboards. In the electrical room, UPSs are configured down-stream of the
switchboards. A Symmetra PX configured to N+1 redundancy provides 225 kW
of critical power to the IT room with 6 minutes of runtime. Valve regulated lead
acid (VRLA) batteries are housed in an isolated battery room. A Galaxy 300
UPS provides 9 kW of power to the pumps in the facility cooling system.
DESIGN OPTIONS
Additional low-voltage transformers can be included in the design to support
This reference design can be modified as
lighting and other building loads. The power distribution architecture from the
follows without a significant effect on the electrical room to the IT space utilizes a combination of LV panels and Modular
design’s performance attributes: Power Distribution. The facility power system is designed to support additional
peripheral devices like fire panels, access control systems, and environmental
Add StruxureWare Power Monitoring monitoring and control devices. Power meters in the electrical path monitor
Expert power quality and allow for predictive maintenance & diagnostics of the system.
Provision for load bank These meters also integrate with StruxureWare Power Monitoring Expert.
Change UPS batteries Every component in this design is built and tested to the applicable IEC
Add/change standby generator options: standards.
Location
Further design details and schematics are available in the engineering package.
Tank size
Fuel type
Packaged Packaged
CRAH CRAH Humidifier AHU
Chiller Chiller
Facility Cooling
The mechanical design utilizes chilled water as the primary medium for heat
dissipation. The architecture consists of a single chilled water loop. The cooling
system contains two 245 kW air-cooled, packaged chillers in an N+1 redundant
configuration. Economization is achieved with a dry cooler to save energy
during favorable outdoor conditions.
In order to extend availability of chilled water during a power outage, a 1 cubic
meter water storage tank provides 2 minutes of continuous cooling.
The piping architecture of the mechanical system feeds room-based Uniflair
Chilled Water CRAHs in the IT space. It also feeds room-based CRAHs in the
electrical and battery rooms. More information on the cooling configuration is
provided in the IT space section of this document.
DESIGN OPTIONS This design is instrumented to work with StruxureWare Cooling Monitoring
Expert.
This reference design can be modified as
Further design details such as dimensions, equipment placement, temperature
follows without a significant effect on the
set points, pipe sizing, flow rates, and pressure drops are available in the
design’s performance attributes:
engineering package.
Add StruxureWare Cooling
Monitoring Expert
VFD
Thermal Storage
VFD CW supply
to IT space
System
bypass
Dirt/air
separator Strainers
CW return
from IT space
Expansion
tank
City Water
IT Space
The IT capacity of this design is 175 kW. The design is highly scalable and
adaptable; it can be configured to support IT loads within a range. Smaller
starting loads as low as 50 kW can be supported by making adjustments such
as reducing the number of IT pods or decreasing the quantity of UPS modules.
Likewise, this design can be used as a baseline for larger loads as high as 525
kW by using a step and repeat approach to the design. This flexibility drives
efficiency and defers capital expenditure until needed.
The IT space design specifies all of the physical infrastructure systems, as well
as their physical arrangement/spacing, required to meet the overall design’s
performance attributes. This includes racks, PDUs, rack power distribution,
DESIGN OPTIONS cooling units, and airflow management systems.
This reference design can be modified as Each pair of rows (pod) within the IT space can be “stepped and repeated” in a
follows without a significant effect on the standardized and predictable manner. This enables right-sizing of power and
design’s performance attributes: cooling that scales with IT growth. Each pod supports an average power
density of 2.8 kW per rack. All the pods are outfitted with integrated power
Add environmental and security distribution.
management Each pod is powered by floor-mount Modular Power Distribution. Every rack is
Change rack options (tall, configured with a metered rack-mount PDU to enable remote monitoring of the
wide, deep)
units for efficiency and capacity management.
Change power distribution options
Rack PDU type (basic, The space is cooled by N+1 redundant Uniflair Chilled Water CRAHs that
switched) control the supply of cool air by monitoring the temperature in the space.
Add StruxureWare Data Center
The security of the room is maintained at multiple points. At the rack level,
Expert
access is controlled by a door lock and sensor. At the room level, security
cameras are utilized for monitoring.
R R R R R R R D R R R R R R R
IT ROOM ATTRIBUTES
R/A-2/Z1 R/A-3/Z1 R/A-4/Z1 R/A-5/Z1 R/A-6/Z1 R/A-7/Z1 R/A-8/Z1 D/ R/A-10/Z1 R/A-11/Z1 R/A-12/Z1 R/A-13/Z1 R/A-14/Z1 R/A-15/Z1 R/A-16/Z1
A-9/
Z1
R R R R R R R D R R R R R R R
R/B-2/Z2 R/B-3/Z2 R/B-4/Z2 R/B-5/Z2 R/B-6/Z2 R/B-7/Z2 R/B-8/Z2 D/
B-9/
Z2
R/B-10/Z2 R/B-11/Z2 R/B-12/Z2 R/B-13/Z2 R/B-14/Z2 R/B-15/Z2 R/B-16/Z2
IT load 175 kW
Input voltage 400 V
R
R/C-2/Z3
R
R/C-3/Z3
R
R/C-4/Z3
R
R/C-5/Z3
R
R/C-6/Z3
R
R/C-7/Z3
R
R/C-8/Z3
D
D/
C-9/
R
R/C-10/Z3
R
R/C-11/Z3
R
R/C-12/Z3
R
R/C-13/Z3
R
R/C-14/Z3
R
R/C-15/Z3
R
R/C-16/Z3
Supply voltage to IT 230 V
Z3
R
R/D-2/Z4
R
R/D-3/Z4
R
R/D-4/Z4
R
R/D-5/Z4
R
R/D-6/Z4
R
R/D-7/Z4
R
R/D-8/Z4
D
D/
D-9/
R
R/D-10/Z4
R
R/D-11/Z4
R
R/D-12/Z4
R
R/D-13/Z4
R
R/D-14/Z4
R
R/D-15/Z4
R
R/D-16/Z4
Number of racks 62 racks
Z4
2
IT floor space 158 m © 2013 Schneider Electric. All rights reserved.
Design Attributes
OVERVIEW Value Unit
Target availability Tier 2 Tier
Annualized PUE at 100% load 1.63 / 1.62 / 1.78
Data center IT capacity 175 kW
2
IT & facility floor space 319 m
Average density 2.8 kW/rack
FACILITY POWER Value Unit
Total amps (main bus) 1600 A
Input voltage (main bus) 400 V
Switchboard kAIC 65 kA
Power path Single
Generator redundancy N
IT space UPS capacity 225 kW
IT space UPS redundancy N+1
IT space UPS runtime @ rated load 6 minutes
IT space UPS output voltage 400 V
Facility cooling UPS capacity 9 kW
Facility cooling UPS redundancy N
Facility cooling UPS runtime @ rated load 9 minutes
FACILITY COOLING Value Unit
Total cooling capacity 245 kW
Input voltage 400 V
Heat rejection medium Chilled water
Mechanical redundancy N+1
Outdoor heat exchange Air-cooled, packaged chiller
Coolant supply temperature 16 C
Coolant return temperature 22 C
3
Storage tank size 1 m
Ride-through time 2 minutes
Economizer type Water-side
IT SPACE Value Unit
IT load 175 kW
Input voltage 400 V
Supply voltage to IT 230 V © 2013 Schneider Electric. All rights reserved.
Good design and quality construction alone do not ensure a highly available &
efficient data center. Data centers require on-going monitoring and management to
ensure the facility lives up to its design intent. StruxureWare for Data Centers is a
software management suite designed to collect and manage data about a data
center’s assets, resource use, and operational status throughout the life cycle of the
facility. This information is then distributed, integrated, and applied in ways that help
managers optimize the data center’s performance and meet IT, business, and
service-oriented goals. From IT assets to racks, rows, rooms and buildings,
StruxureWare for Data Centers delivers the right information to the right users at the
right time.
Control level: Experts, on site or remotely, can control process performance and
ensure business continuity in real time, while tracking energy consumption in a highly
critical and secure environment.
Operations level: Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.
Enterprise level: C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to conserve
enterprise-wide resources.
StruxureWare for Data Centers allows for flexibility when requirements and
implementation strategies change over time. StruxureWare software applications
and suites simplify integration time, improve reliability, enhance visibility to energy
information, and streamline operational efficiency.
>
© 2013 Schneider Electric. All rights reserved.