This document summarizes the load capacity and deflection calculations for a glass combination of 6mm fully tempered outer glass, 16mm air space, and 9.52mm fully tempered inner glass. The calculations determine the load shared by each glass layer, load resistance, and deflection. The load resistance of 4.55KPa exceeds the actual wind load of 1.09KPa. Deflection for the outer glass is 8mm and inner glass is 9.5mm, which are below the allowable deflection limits. Therefore, the glass combination is determined to be safe for the given wind load conditions.

Uploaded by

Muraleedharan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
100 views

Glass Check

This document summarizes the load capacity and deflection calculations for a glass combination of 6mm fully tempered outer glass, 16mm air space, and 9.52mm fully tempered inner glass. The calculations determine the load shared by each glass layer, load resistance, and deflection. The load resistance of 4.55KPa exceeds the actual wind load of 1.09KPa. Deflection for the outer glass is 8mm and inner glass is 9.5mm, which are below the allowable deflection limits. Therefore, the glass combination is determined to be safe for the given wind load conditions.

Uploaded by

Muraleedharan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

1.0 Glass load capacity and deflection- (Glass Combination 6mm FT +16mmAS+9.

52 mm
FT glass)

 Aspect ratio of glass = L/B = 3.85/1.22 = 3.15


 Glass area in Sq.M = LxB = 3.85x122= 4.7 sqM
 Wind Load considered = 1.09 Kpa
 From table,5-ASTM E1300, Load share factor LS1 = 3.37
( for outer lite glass-6mm thick)
 Load share factor for Inner lite glass ( 6mm Thick)LS2=1.42
 Load shared outer lite = Windload in Kpa/Load share factor = 1.09/3.37= 0.32KN
 Load shared by Inner lite = 1.09/1.42 =0.76 KN
2
 Load x Area for outer lite = 0.32Kpa x 4.72 = 7.06 KN-m2
 Load x Area 2 for Inner lite = 0.76x4.7 2 = 16.78
Load capacity of glass arrangement is found out according to ASTM E 1300-03
As per ASTM E1300-03, the glass arrangement is
 Insulating glass(IG) with one monolithic lite under short duration load.

NFL1 NFL2 GTF1 GTF2 LS1 LS2 LR1 KPa LR2 KPa Final Load
( NON ( NON ( GLASS (GLASS (LOAD (LOAD (LOAD LOAD resistance
FACTORED FACTORED TYPE TYPE SHARING SHARING CAPACITY- CAPACITY- (LR) Value-
LOAD FOR LOAD FOR FACTOR- FACTOR- FACTOR- FACTOR- LITE01) LITE02) KPa
LITE 01) LITE 02) LITE01) LITE 02) LITE 01) LITE02) =NFL1xGTF1xLS1 NFL2xGTF2xLS2

.875 1.125 2.85 2.85 3.37 1.42 8.07 Kpa 4.55Kpa 4.55Kpa

From From Ref Ref Ref Ref


graph Graph Table Table 3- Table-5, Table-
attached attached 3- ASTM ASTM 5,
ASTM E1300 E1300 ASTM
E1300 E1300

Load resistance is = 4.55Kpa

Actual Wind load =1.09 Kpa < 4.55 Kpa, hence safe
Load factor for outer glass

Check for deflection for outer lite- 6mm Glass

Deflection corresponding to Load x Area2 -7.06 , from Fig- A-17, ASTM E-1300
Deflection for the outr lite glass = 8mm
Maximum allowable deflection( ref- AS 1288) = Length of shorter span/60 = 1221/60= 20 mm > actual
deflection. Hence safe
Deflection calculation for outer glass
Load factor for inner glass

Check for deflection of glass- Inner lite-8mm Glass

 Deflection corresponding to Load x Area2(16.78) and Aspect ratio 3.17 , from Fig- A-17, ASTM E-
1300 =9.5 mm
 Maximum allowable deflection( ref- AS 1288) = Length of shorter span/60 = 1221/60= 20.35 mm
Actual deflection < allowable deflection, hence Safe
Recommended to use 8mm Fully tempered +16mm Airspace +8mm Fully Tempered glass