0% found this document useful (0 votes)
177 views15 pages

Tank 44M3

This document provides a structural analysis report for an above ground storage tank with a capacity of 44 cubic meters. It includes a 3D model and analysis of the tank under operating conditions. The analysis was conducted using STAAD Pro software to check the steel structure according to codes. Loads such as self-weight, fluid weight, atmospheric pressure, and wind were considered in the load combinations analyzed. Output from the STAAD model under operating conditions is provided.

Uploaded by

Tech Design
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
177 views15 pages

Tank 44M3

This document provides a structural analysis report for an above ground storage tank with a capacity of 44 cubic meters. It includes a 3D model and analysis of the tank under operating conditions. The analysis was conducted using STAAD Pro software to check the steel structure according to codes. Loads such as self-weight, fluid weight, atmospheric pressure, and wind were considered in the load combinations analyzed. Output from the STAAD model under operating conditions is provided.

Uploaded by

Tech Design
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 15

CALCULATION REPORT ABOVE GROUND UL-142 STORAGE

TANK, CAPACITY= 44 M3(TAG NO.: - 191-ASI-TK3)

STAAD 3D MODEL

06 15.07.17 ISSUED FOR APPROVAL NP AMH KMA


Rev. Date Description Prepared By Checked By Approved By

CONTENT:

1
S/ DESCRIPTION PAGE NOS.
NO
1 INTRODUCTION 3
2 CODES, SPECIFICATIONS AND REFERENCE DOCUMENTS 4
2.1 CODES 4
2.2 SPECIFICATIONS AND REFERENCE DOCUMENTS 4
3 MATERIAL 4
4 GENERAL DESCRIPTION 5-13
5 LOAD DESCRIPTION 9
5.1 WIND LOAD DATA 9
6 SEISMIC LOAD DATA 9
7 LOAD ANALYSIS 9
7.1 OPERATING CONDITION ANALYSIS 9
8 LOAD COMBINATION FOR OPERATING CONDITION 10
9 LOAD APPLICATION ON STAAD PRO 11
9.1 OPERATING CONDITON 11-12
10 STAAD OUTPUT 13
10.1 OPERATING CONDITION ANALYSIS 14-74
10.2 INPUT FILE FOR OPERATING CONDITION 75-80

2
1. INTRODUCTION

The objective of this report is the structural check for The Above Ground Ul-142
Storage Tank, Capacity= 44 M3(TAG No.: - 191-ASI-TK3) under the following
condition :

1. While in operation at site

FEM analysis has been carried out using STAAD Pro V8i SS 4 , a certified structural
computer program, licensed worldwide through Bentley .

The structure is checked according to AISC 360-05 ( ASD method ) Design .

3
2. CODES, SPECIFICATIONS AND REFERENCE DOCUMENTS

2.1 CODES
 ANSI/AISC 360-05: "Specification for Structural Steel Buildings”

2.2 SPECIFICATIONS AND REFERENCE DOCUMENTS


 UL142 – “Steel Above ground tanks for flammable and combustible liquids ”
 General arrangement drawing for TAG No.: - 191-ASI-TK3

3. MATERIALS

- STRUCTURAL STEEL:
1. A36 FOR OTHER STRUCTURE ITEMS
Yield Stress :-
ASTM A36 / Fy ¿ 250 MPa

- BOLTS: type ASTM A307

DIMENSION OF TANK

2
4-Skid member size considered :

PLATE FOR TANK

BOTTOM PLATE STIFFENER (UPN100)

2
VERTICAL AND HORIZONTAL STIFFENER FOR SHELL PLATE ( SD 75X75X6 THK)

TOP PLATE STIFFENER (UPN100)

2
Staad Input Pics
NODE NUMBER

2
BEAM NUMBER

2
SUPPORT

2
5) LOAD DISCRIPTION :-
5.1) Wind Load Data :- ASCE-7 -05

Basic Wind speed (V) 45 m/s 162Km/hr


Exposure coefficient (Kz) 0.85 ( from table 6-3 / ASCE-7 )
Topographic factor (Kzt) 1 ( Cl-6.5.7.2 / ASCE-7)
wind directional factor (Kd) 0.95 ( from table 6-4 / ASCE-7 )
Structure category IV
Exposure category C
Gust Factor (G) 0.85 (CL-6.5.8.1 ( ASCE-7 )
Importance factor (I) 1.15 [ from table 6-1 / ASCE-7 ][ CL-4.13]
Height above ground level (z) 2.1m
load diameter multiplier (Wm) 2.1 ( for additional piping and left over area )

Wind velocity pressure (qz) 1.152 kN/m2 ( qz= 0.613 x Kz x Kzt x Kd x V2 x I)


(Wind Velocity pressure is inserted in Staad Pro Software )

6) Seismic Load Data:- (NA)

7) LOAD ANALYSIS
7.1). OPERATING CONDITION ANALYSIS:-

A) Operating condition load

1) Selfweight Of Tank with stiffener


2) Fluide Weight = h = 1000 kg/m3 x 2.100m
= 2100 kg/m2

3) Atm load on top plate = 102 Kg/m2

4) Wind Load Data :- ASCE-7 -05

Basic Wind speed (V) 45 m/s 162Km/hr


Exposure coefficient (Kz) 0.85 ( from table 6-3 / ASCE-7 )
Topographic factor (Kzt) 1 ( Cl-6.5.7.2 / ASCE-7)
wind directional factor (Kd) 0.95 ( from table 6-4 / ASCE-7 )
Structure category IV
Exposure category C
Gust Factor (G) 0.85 (CL-6.5.8.1 ( ASCE-7 )
Importance factor (I) 1.15 [ from table 6-1 / ASCE-7 ][ CL-4.13]
Height above ground level (z) 2.1m
load diameter multiplier (Wm) 2.1 ( for additional piping and left over area )

Wind velocity pressure (qz) 1.152 kN/m2 ( qz= 0.613 x Kz x Kzt x Kd x V2 x I)

2
(Wind Velocity pressure is inserted in Staad Pro Software )

8) Load Combination As Per ASCE 7-05 ASD

8.1) Operating Load Combination:

Staad CombinationLoad
1.0DL Combination Load 1
1.0DL+0.7WL (+X DIRECTION) Combination Load 2A
1.0DL+0.7WL (-X DIRECTION) Combination Load 2B
1.0DL+0.7WL (+Z DIRECTION) Combination Load 2C
1.0DL+0.7WL (-Z DIRECTION) Combination Load 2D
Abbreviations:-
DL- DAED LOAD
WL- WIND LOAD

2
9) LOAD APPLICATION IN STAAD PRO:

9.1) IN OPERATING CONDITION:


SELFWEIGHT

FLUID AND Atm LOAD

2
WIND LOAD

COMBINATION LOAD

2
10) STAAD OUTPUT:-