TAN DELTA Application Notes
TAN DELTA Application Notes
APPLICATIONS NOTES
APPLICATION NOTES
1. INTRODUCTION
1.1. GENERAL
1.2. Principle of Operation
1.3. I, C, Tan d relations
1.4. Conversion formulas
1.5. Mode UST, GST & GST g connections
2. INTERPRETATION OF MEASUREMENTS
3. TYPES OF APPARATUS
3.1. Transformers
3.2. Bushings
3.3. Rotating M/C
3.4. Cables
3.5. Surge arresters
3.6. Liquids
3.7. Solids
3.8. Miscellaneous Assemblies & components
1
Sivananda Electronics
SECTION 1
Fig. 1
In physical world the bushing with central conductor & mounting flange is an
example of two terminal capacitor where as bushing with central conductor,
Tan d tap & mounting flange is a three terminal capacitance.
2
Sivananda Electronics
SIVA Bridges are based on Transformer arm ratio principle as shown in fig.2
Fig. 2
The null is obtained when ampere-turn due to Ix passing through Cx & ampere-
turn due to Is passing though Cs are equal, both in magnitude & phase.
Ix Nx = INs
Cx Nx = V WCs Ns
Cx = Cs x Ns/Nx
dielectric loss angle where d = 90 - F. For low loss insulation system Ic & I are
0
3
Sivananda Electronics
SIVA bridges are calibrated in terms of capacitance & Tan d. The important
characteristic of capacitance is it Tan d which is represented vectorially in fig.4
Incase where d is small sin d & Tan d are numerically almost equal. For power
factor less than 10% the difference is less than 0.5% & for power factor values
less than 20%, the difference is less than 2%. For this reason some times the
terms power factor & dissipation factors are used interchangeably, which is not
right.
The capacitor current at certain voltage & frequency is given by
I = Vwc
4
Sivananda Electronics
The capacitors normally have both series & parallel losses. The frequency of
operation determines whether series or parallel losses will be dominant. At power
frequency only parallel losses are important and at higher frequency the series
losses. See fig.5 for equivalent circuit.
Fig : 5.
For a particular frequency either series or parallel equivalent circuit can represent
any loss. Depending on the convenience of analyzing a particular circuit either
series of parallel equivalent circuit can be used for a practical capacitor.
5
Sivananda Electronics
Tan ds = Rs wCs
Tandp = 1/RpWCp
6
Sivananda Electronics
-6
mA = KV w Cpf x 10
-6
mA = KV X Cpf X 314 X 10 at 5Hz
% DF = W LOSS X 100
KV X mA
Df
PF =
Ö (1 + DF )
2
DF = PF
Ö (1- PF )
2
7
Sivananda Electronics
Fig. 8
1.5 UST, GST & GSTg MODES OF OPERATIONS: In the following, various
modes of operations possible for measurement with SIVA Test Sets are
explained. Basic three modes are explained. However in set with two LV Leads 7-
modes of operations are possible, which enables to measure complex objects
with minimum changes of connections.
UST: fig. 9 shows the basic ungrounded specimen testing mode & how
guarding is
Fig. 9
achieved in this mode. In this mode only CHL is measured as current through CHL
only passes through Nx. CHG& internal stray capacitor shunt the power supply
which effects only loading but does not effect measurement all stray
capacitances between L & guard (in this case ground) shunts the Nx winding.
8
Sivananda Electronics
Ix current flowing through CHL & CHG passes through Nx winding hence
capacitance measured is CHL + CHG. All internal stray capacitances shunt power
supply & external capacitances between GUARD & GROUND shunts Nx winding
which are not measured & also does not effect results as explained in UST mode.
GSTg-Mode: Fig.11 shows simplified circuit set up for GST g mode &
shows how guarding is achieved.
9
Sivananda Electronics
Only Current passing through CHG also passes through Nx so capacitance being
measured CHG. All internal & external capacitance between High Voltage point H
& GUARD shunts the power supply & between GUARD & GROUND SHUNTS
Nx, which are neither measured nor effect measurement as explained.
USING SET WITH TWO MEASURING LEADS: Following chart shows various
modes of measurements.
10
Sivananda Electronics
Typical connections for testing 3 & 4 terminal capacitor are shown in figures
12, 13, 14 &15 using test set with two leads.
11
Sivananda Electronics
12
Sivananda Electronics
13
Sivananda Electronics
14
Sivananda Electronics
GSTg Mode Measures between H & Ground with LV1 & LV2 Guarded
GSTg Mode Measures between H and LV1 + Ground with LV2 Guarded.
15
Sivananda Electronics
GSTg Mode Measures Between H & LV2 + Ground & LV1 Guarded.
16
Sivananda Electronics
SECTION 2
INTERPRETING TEST RESULTS
* Insulating system's chemical change due to time & temperature and other
service conditions
17
Sivananda Electronics
18
Sivananda Electronics
This shows that Tan d results will be abnormally affected; if measured at freezing
temperature because of 100:1 ratios. Tan d should not be measured at freezing
temperature.
The bushing, insulator, air or gases filled circuit breakers are assumed to have
same temperature as ambient temperature. While transformers, oil circuit
breakers are assumed to have same temperature as oil. Bushings installed on
transformer will have temp some where between oil & ambient. Any sudden
change in ambient condition will have adverse effect, as due to thermal inertia of
equipment the true temp of equipment will lag behind ambient temp.
19
Sivananda Electronics
Therefore, test should be conducted during sunny & clear days during late
morning or early afternoon. Moisture deposited by rain or fog should also avoid
just prior to test.
2.6 SURFACE LEAKAGE: Losses due to surface leakages influence the
bulk losses of insulating system. Tan d measurement will give false information
regarding the condition of bulk insulation. Even bushing with much higher voltage
rating than the test voltage will show appreciable effect of surface leakage.
Therefore surfaces of such insulations should be cleaned & dried prior to
measurement.
On bushings with Tan d tap, testing in UST mode can eliminate the effect of
surface leakage.
When testing Bushings with out Tan d tap. Under high humidity, effect of
surface leakage can be minimized by clean & drying the surface & use of
insulating grease.
Due consideration is to be given to test conditions while interpreting results.
20
Sivananda Electronics
21
Sivananda Electronics
The errors are usually increased when there is strong interfering field or
unfavorable weather conditions.
22
Sivananda Electronics
SECTION 3
TYPES OF EQUIPMENTS
Test procedures & methods should be designed after studying & identifying
various capacitances involved in complex insulating systems. All capacitance,
involved & terminals available for making measurements & their voltage
capability should be defined. So that while testing, these voltages are not
exceeded. Methods for recording data should also be designed & formats
prepared for recording these.
Following are the general guidelines for conducting test on various equipments.
23
Sivananda Electronics
Fig.16
While testing each winding it should be shorted on itself & protective ground
jumper should be provided when test leads are being connected which can than
be removed.
Above figure shows the typical set up for two winding Tx and table 3 shows
connections between test set & two winding transformer in UST / GST mode. It is
good to cross check calculated & measured capacitance values to validate
measurements. The calculated values should tally with measured values with in
limits.
Increased Tan d values, relative to previous measured values indicates
some general conditions like contaminated oil and degradation of insulation
system. Increase in both capacitance & Tan d indicates contamination by
moisture. When insulating liquid is being filtered, a repeated test on winding &
insulating liquid indicates whether desired results are ob tained & healthy
conditions are restored.
24
Sivananda Electronics
T A B L E : 3 . T W O W IN D IN G T R A N S F O R M E R S
T E S T C O N N E C T IO N
25
Sivananda Electronics
EQUIVALENT CIRCUIT:
Capacitance Watt loss
C1 = C2 C3 = CHLW1 = W2 W3
C4 =C5 C6 = CHLW4 = W5 W6
Here subscript denotes test Sr. No
H = High Voltage Winging G = Ground
L = Low Voltage Winging
26
Sivananda Electronics
Calculated Interchecks:
Capacitance
C1 = C2 C3 = CHL W1 = W2 W3
C4 = C5 C6 = CLT W4 = W5 W6
C7 = C8 C9 = CHT W7 = W8 W9
27
Sivananda Electronics
BUSHINGS:
Now a day all high voltage bushings come with Tan d test tap, which enables to test
bushing capacitance & Tan d in-site. Tan d measurement is made in UST mode,
which eliminates effects of all other insulating systems. The effect of stray
capacitance between Bushing terminal and ground as well as effects of surface
leakage of porcelains are also eliminated. UST mode essentially measures
Bushing only.
SIVA
TEST SET
28
Sivananda Electronics
Bushing, with flange isolation provision, can also be tested in UST mode. Just
remove the flange-grounding bolt; now bushing flange is completely isolated.
Connect HV to central conductor & LV1 to flange & take measurements in UST
mode.
Bushings with completely grounded flange cannot be tested in-site. Bushing has
to be removed and test performed.
INSULATION SYSTEM OF TAN d TAP: Insulation between Tan d tap & flanged
can be tested by connecting HV lead to Tan d tap & LV1 to central conductor &
flange is grounded a measurement done in GSTg mode.
Tand tap are generally designed to with stand 500V to 2.5KV voltage only.
Before conducting test, ascertain the testing voltage limit & in no case exceed this
limit as larger stress may puncture the insulation system.
29
Sivananda Electronics
Temperature correction graph should be established with care and the same
should be applied to record the values at some base value of temp. Temperature
on the surface of bushing should be measured.
While testing bushings in modes where surface leakages present problem, the
temp of surface should be above ambient to avoid condensation of moisture.
30
Sivananda Electronics
CABLES:
High voltage cables are generally armored. In a single conductor cable the
insulation between conductor & earth (armor), the test is done in GST mode.
When three-phase cable is tested then following measurements are made.
1. The tests give results for average Tan d of cables. In a cable, with some
small section having high Tan d the problem can be completely over
shadowed & have no effect on average value. The problem will be
more severe if the cable length is large.
31
Sivananda Electronics
SURGE ARRESTERS:
The complete test on surge arrestors is not possible in field since it involves
impulse, over voltage & Tan d measurements. Only Tan d test can be performed in
field. Power loss measurement in field is an effective method of monitoring the
health of arresters & predicting potential problem.
Normally individual units of arresters are tested for Tan d & power loss and
results compared with previous recorded data. Tests are performed at highest
possible test voltage. Surfaces of insulations must be cleaned & dried except
when testing for surface leakage effects. Use previously established temp Vs Tan
d graph to record Tan d results corrected same base value each time. The temp
on surface of arresters is taken as temp. of arrestors and ambient temp should
also be recorded. The surface temp should be more than ambient to avoid
condensation of moisture.
In the shop floor individual unit can be tested in UST mod but in the field when
these are mounted on supporting structures, GST or GST g modes are also used.
Surge arresters are rated on the basis of watt loss. What loss measured
should be recorded at a fixed voltage for ease of comparing with previous data.
Use conversion formulas to calculate watt loss at base value if measurements
are done at different voltage.
Use extreme caution while testing suspected damaged arrester units as high
gas pressures can build up in sealed units.
Referring fig.19, unit A, B & C can be tested in UST while D should tested in
GST mode while using set with two measuring leads multiple units (two) at a time
can be tested selecting appropriate mode. Table 5 shows the recommended test
mode & connections. Remove high voltage bus bar before starting test.
While using conversion formula make sure that arresters have linear
response in the voltage range.
An increase in Tan d indicates contamination by moisture, salt deposit,
cracked porcelain etc. While decrease in Tan d indicates open shunt resistor &
defective pre ionizing elements.
32
Sivananda Electronics
LIQUID:
SIVA three terminal cell can be used for testing insulation liquids. The cell has
guard third terminal to reduce fringe effects & effect of insulation used for
insulating electrodes & providing support.
The dielectric constant can also be measured by this method. The ratio of empty
cell capacitance to capacitance with liquid filled gives dielectric constant.
The temperature & Tan d graph also can be established using temperature
controlled heating chamber & raising the temperature & measuring Tan d values
while liquid is cooling.
Fig.
(Three Terminal Oil Cell & Heating Chamber)
33
Sivananda Electronics
SOLIDS:
Capacitance & Tan d of solids insulating system when available in this sheet
of appropriate thick can also be measured using SIVA cell for solids. Fig.22
shows the SIVA jig for solids.
Bulk losses can be separated from surface leakages by using third electrode
as guard. An example for insulated rod with central conductor is shown in fig.23 to
illustrate this.
The results of components & assemblies are compared with that of similar
components, which are known to be healthy.
34