Paquetes ZZ de 7.5 A 12.5 Ton
Paquetes ZZ de 7.5 A 12.5 Ton
Sun™ Core
TECHNICAL GUIDE
ZZ Series
6 - 12.5 TON
60 HERTZ (EXPORT ONLY)
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Field Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling Performance Rating Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
AHRI 270 Outdoor Sound Power Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Power Exhaust Blower Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Product Highlights
• Assembled in Norman, OK • Evaporator coils utilize copper tube/aluminum fin design
• ASHRAE 90.1 Compliant for proven reliability and performance.
• R-410A Refrigerant • TXV (Thermostatic Expansion Valve) Standard on:
(ASHRAE 90.1 Compliant Standard Efficiency Level 6 -
• Cooling Only and Gas/Electric configurations available
12.5 ton models)
• Scroll Compressors
• Single-stage Cooling (6 - 7.5 ton models)
• State of the art Microprocessor Controls with specific
• Two-stage Cooling (8.5 - 12.5 ton models)
programming for product applications
• Alternate Motor and Drives
• MicroChannel Condenser Coils
Component Location
Cooling With Gas Heat
B
E
D H
G J
E B
G
C
D Units will come with the new state of the art Smart
Equipment™ control system. The new unit control
incorporates the best of the already proven Smart Equipment™
controls and creates a more robust, intelligent control. The goal
of this control is to utilize cutting edge technology making the
equipment easier to install, operate, and service. All units are
Factory commissioned, configured, and run tested.
On-board USB Port - The new control comes with a long list of
features including data logging, current and previous system
faults and software update capabilities using the on board USB
port and common flash drive. Energy use monitoring
capabilities allow custom tailoring to allow a system to work
more efficiently at all times and occupancy levels. Self test and
start-up reports also available from the board VIA the USB port.
Fan Delays - Fan on and fan off delays are fully programmable.
Furthermore, the heating and cooling fan delay times are
independent of one another. All units are programmed with
default values based upon their configuration of cooling and/or
heating capacity.
equates to all units meeting LEED EA Credit 4 Requirements Aluminized steel heat exchangers carry a 10-year warranty and
for Enhanced Refrigerant Management. MicroChannel coils are stainless steel heat exchangers carry a 15- year warranty.
also much easier to clean than your typical fin/tube designs.
All evaporator coils utilize copper tube with aluminum fin design
Factory Installed Options
for proven reliability and performance.
(Nomenclature Digit Position)
Controls (9)
Smart Equipment™ - This is the Standard microprocessor
control with capabilities to work with a sensor or thermostat
only. Smart Equipment™ with BAS includes communication
board with BACnet open-protocol system.
• 1=None
Economizer/Damper (11)
• 2=Non-fused Disconnect1
Down flow Economizers (with barometric relief) - All units
offer a variety of optional factory installed economizers that are 1. Verify on the unit nameplate that the disconnect is properly
shipped, installed and wired with AMCA 511 Licensed Class sized for the application. Units with field installed electric heat
1A low leak dampers designed to exceed ASHRAE 90.1 and may exceed the factory installed disconnect amperage rating.
the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3 cfm/ Cabinet Options (14)
sq. ft. at 1" of static pressure. Each economizer goes through a Louvered Hail Guard - This kit includes a decorative
rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual louvered panel which installs over the outside condenser coil
enthalpy (with field installed kit) can be selected. All and prevents damage to the coil fins from hail strikes.
economizer options are fully integrated into the Smart
Equipment™ controls. The economizer has spring return, fully Hinged Cabinet Doors - The factory installed hinged panel
modulating damper actuators and is capable of introducing up option will save time, money and labor while allowing easy
to 100% outdoor air. As the outdoor air intake dampers open, servicing of blower components, filters and controls. With this
the return air dampers close. The changeover from option there is no longer a need to remove panels to access
mechanical refrigeration to economizer operation is regulated these critical sections and running the risk of losing panels or
by the outdoor air dry bulb temperature or the outdoor air roof damage from loose panels and materials. Extra care was
enthalpy input. The dual enthalpy kit provides a second input taken to design a durable hinged panel with leak tight seal.
used to monitor the return air (field installed). The installer
• 1=None
needs only to assemble the outdoor air hood, attach the
enthalpy control the hood and mount the hood to the unit • 2=Louvered Panels
(Hood and control are provided). • 3=Hinged Cabinet Doors
Dry Bulb Economizer - Economizer operation is enabled by • 4=Hinged Cabinet Doors And Louvered Panels
the outdoor air temperature being less than the setpoint of the FDD (Fault Detection and Diagnostics) - Refrigerant side A
economizer module. Modification Shop offering for an additional installed control
system for commercial equipment that constantly monitors
Enthalpy Economizer - The added outdoor air enthalpy refrigerant circuit pressures, refrigerant circuit temperatures, as
sensor enables economizer operation if the outdoor enthalpy well as the environmental temperatures and humidity via
is less than the setpoint of the economizer logic module. multiple sensor inputs.
• A=None
• B=Dry Bulb Economizer
Field Installed Accessories
• C=Enthalpy Economizer • Down flow Economizers/Horizontal Economizers
(with barometric relief) - All units offer a variety of field
Convenience Outlet (12)
installed economizers that are installed and wired with
Convenience Outlet - (Powered and Non-Powered) - This AMCA 511 Licensed Class 1A low leak dampers designed
option locates a 120V single-phase GFCI outlet with cover, on to exceed ASHRAE 90.1 and the International Energy
the corner of the unit housing adjacent to the compressors. Conservation Code (IECC) certification requirements by
The Non-powered option requires the installer to provide the achieving leakage rates of 3 cfm/sq. ft. at 1" of static
120V single-phase power source and wiring. Factory installed pressure. Each economizer goes through a rigorous
option only. 60,000 cycle test. Dry bulb, single enthalpy, and dual
• 1=None enthalpy (with field installed kit) can be selected. All
economizer options are fully integrated into the Smart
• 2=Non-powered Convenience Outlet Equipment™ controls. The economizer has spring return,
• 3=Powered Convenience Outlet fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer • Gas Heat High Altitude Kit - This kit converts a gas heat
operation is regulated by the outdoor air dry bulb unit to operate at high altitudes, 2,000 to 10,000 feet.
temperature or the outdoor air enthalpy input. The dual Conversion kits are available for natural gas and propane.
enthalpy kit provides a second input used to monitor the • Roof Curbs - The roof curbs have insulated decks and
return air (field installed). The installer needs only to are shipped disassembled The roof curbs are available in
assemble the outdoor air hood, attach the enthalpy control 14 and 24 heights.
the hood and mount the hood to the unit (Hood and
• Thermostat - The units are designed to operate with 24-
control are provided).
volt electronic and electro-mechanical thermostats. All 7.5
• Dry Bulb Economizer - Economizer operation is enabled thru 12.5 ton units operate with two-stage heat/two-stage
by the outdoor air temperature being less than the cool or two-stage cooling only thermostats, depending
setpoint of the economizer module. upon unit configuration.
• Single Enthalpy Control, Accessory for Economizer - • Smoke detectors - The smoke detectors stop operation
All field installed economizers will come standard as a dry of the unit by interrupting power and providing a fault
bulb economizer. This kit adds an outdoor air enthalpy message to the control board if smoke is detected within
sensor which enables economizer operation if the outdoor the air compartment. Smoke detectors are available for
enthalpy is less than the setpoint of the economizer logic both the supply and/or return air configurations.
module.
• Hinged Filter Access Panel For Use With Horizontal
• Dual Enthalpy Control, Accessory for Economizer - All Flow Economizer - Allows hinged access to the filter
field installed economizers will come standard as a dry section when used with a horizontal economizer.
bulb economizer. This kit adds an outdoor air enthalpy
• Low Ambient Head Pressure Control Kit - The
sensor and return air enthalpy sensor which enables
Electronic Low Ambient Controller is designed to regulate
economizer operation if the outdoor enthalpy is less than
condenser head pressure at low ambient temperatures by
the setpoint of the economizer logic module.
varying the amount of airflow through the condenser.
• Power Exhaust - This accessory installs in the unit with a
• Manual Outdoor Air Damper - Like the motorized
down flow economizer or in the ductwork for a horizontal
outdoor air damper, each manual outdoor air damper
application.
includes a slide-in damper assembly with an outdoor air
• Louvered Hail Guard - This kit includes a decorative hood and filters. Customers have a choice of dampers
louvered panel which installs over the outside condenser with ranges of 0% to 100% or 0% to 35% outdoor air
coil and prevents damage to the coil fins from hail strikes. entry.
• Flue Exhaust Extension Kit - In locations where wind or • Thru The Base Connection - Kits are available to
weather conditions may interfere with proper exhausting provide a way to route wiring to the unit through the base
of furnace combustion products, this kit can be installed to of the unit and gas supplied to the unit through the base or
prevent the flue exhaust from entering nearby fresh air through the curb. These kits provide a seal tight way to
intakes. bring power and gas to the unit without additional roof
• Propane Conversion Kit - This kit converts a gas heat penetrations.
unit to operate with propane gas at altitudes up to 2,000 • Electric Heat (Field installed option Only) - Select
feet. heater sizes for 3-12.5 ton units available. Necessary
hardware and connectors are included with the heaters.
Nomenclature
1 = First Generation
ZZ = Pkg AC Constant Volume (Export Only)
1 = None
Heat Capacity 2 = Non-Fused Disconnect
5 = Phase Monitor
A = Cooling only (no heat)
Gas Heat
Convenience Outlet
D = Low Heat
E = Medium Heat 1 = None
F = High Heat 2 = Non-powered
R = Low Heat - Stainless Steel 3 = Powered
S = Medium Heat - Stainless Steel
T = High Heat - Stainless Steel
Economizer / Damper
Voltage A = None
B = Dry Bulb Economizer
C = Enthalpy Economizer
2 = 208/230-3-60
4 = 460-3-60
Sensor Options
Accessories
Accessory Kit
Description Where Used Voltage
Number
2EE04706724 Econ, DB, Vertical Flow, Small Footprint ZZ07, ZZ08 All
2EE04706824 Econ, DB, Vertical Flow, Large Footprint ZZ09, ZZ12, ZZ14 All
2EE04707124 Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet ZZ07, ZZ08 All
2EE04707324 Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet ZZ09, ZZ12, ZZ14 All
1FA0415 Manual Outside Air Damper 0-35% ZZ07, ZZ08 All
1FA0416 Manual Outside Air Damper 0-35% ZZ09, ZZ12, ZZ14 All
1FA0417 Manual Outside Air Damper 0-100% ZZ07, ZZ08 All
1FA0418 Manual Outside Air Damper 0-100% ZZ0, ZZ12, ZZ14 All
2MD04704224 Motorized Outside Air Damper 0-100% ZZ07, ZZ08 All
2MD04704324 Motorized Outside Air Damper 0-100% ZZ09, ZZ12, ZZ14 All
2EC0401 Kit, Single Enthalpy Field Installed All All
2EC0402 Kit, Dual Enthalpy Field Installed All All
Hinged Filter Access Panel For Units With A Horizontal
1HD0402 ZZ07, ZZ08 All
Economizer
Hinged Filter Access Panel For Units With A Horizontal
1HD0404 ZZ09, ZZ12, ZZ14 All
Economizer
1HG0420 Hail Guard Kit Small Footprint, Tall Cabinet ZZ07, ZZ08 All
1HG0424 Hail Guard Kit Large Footprint, Tall Cabinet ZZ09, ZZ12, ZZ14 All
1RC0456 Curb Rigid 14" Small Footprint ZZ07, ZZ08 All
1RC0457 Curb Rigid 14" Large Footprint ZZ09, ZZ12, ZZ14 All
1RC0458 Curb Rigid 24" Small Footprint ZZ07, ZZ08 All
1RC0459 Curb Rigid 24" Large Footprint ZZ09, ZZ12, ZZ14 All
2PE04704225 Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph ZZ07, ZZ08 208/230-3-60
2PE04704246 Power Exhaust Vert Flow Small Footprint 460V 3-ph ZZ07, ZZ08 460-3-60
2PE04704325 Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph ZZ09, ZZ12, ZZ14 208/230-3-60
2PE04704346 Power Exhaust Vert Flow Large Footprint 460V 3-ph ZZ09, ZZ12, ZZ14 460-3-60
2PE04704425 Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph ZZ07, ZZ08 208/230-3-60
2PE04704446 Power Exhaust Horiz Flow Small Footprint 460V 3-ph ZZ07, ZZ08 460-3-60
2PE04704525 Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph ZZ09, ZZ12, ZZ14 208/230-3-60
2PE04704546 Power Exhaust Horiz Flow Large Footprint 460V 3-ph ZZ09, ZZ12, ZZ14 460-3-60
1HA0454 High Altitude Kit for Natural Gas (2,000-10,000 ft) ZZ07, ZZ08 - Low, Med, High Heat All
1HA0455 High Altitude Kit for Natural Gas (2,000-10,000 ft) ZZ09, ZZ12, ZZ14 All
1NP0456 Propane Conversion Kit Note: Not for use with Low NOx ZZ07, ZZ08 - Low, Med, High Heat All
1NP0457 Propane Conversion Kit ZZ09, ZZ12, ZZ14 All
High Altitude Kit for Propane (2,000-10,000 ft) Note: Not for use
1HA0458 ZZ07, ZZ08 - Low, Med, High Heat All
with Low NOx
1HA0459 High Altitude Kit for Propane (2,000-10,000 ft) ZZ09, ZZ12, ZZ14 All
1FE0415 Flue Exhaust Kit ZZG07, ZZG08 All
1FE0416 Flue Exhaust Kit ZZG09, ZZG12, ZZG14 All
1HS0401 Flue Heat Shield Accessory ZZ07, ZZ08, ZZ09, ZZ12, ZZ14 All
2EK04510625 6.5 KW Electric Heat ZZ07, ZZ08 208/230-30-60
2EK04510646 6.0 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511125 10.5 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04511146 11.5 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511446 14 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511625 16 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04511725 16 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04511746 16.5 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
Accessories (Continued)
Accessory Kit
Description Where Used Voltage
Number
2EK04510625 6.5 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04512525 24.8 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04512846 27.8 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2EK04513225 32 KW Electric Heat ZZ09,ZZ12, ZZ14 208/230-3-60
2EK04513346 33 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2EK04514225 42.4 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04514246 41.7 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2LA04704725 Low Ambient Accessory Kit ZZ07, ZZ08 208/230-3-60
2LA04704746 Low Ambient Accessory Kit ZZ07, ZZ08 460V-3-60
2LA04704825 Low Ambient Accessory Kit ZZ09, ZZ12, ZZ14 208/230-3-60
2LA04704846 Low Ambient Accessory Kit ZZ09, ZZ12, ZZ14 460V-3-60
2LA04704925 Low Ambient Accessory Kit ZZ14 208V/230V-3-60
2LA04704946 Low Ambient Accessory Kit ZZ14 460V-3-60
2SD04701224 Supply Air Stream Smoke Detector ZZ07, ZZ08, ZZ09, ZZ12, ZZ14 All
2SD04701124 Return Air Stream Smoke Detector ZZ07, ZZ08 All
2SD04701424 Return Air Stream Smoke Detector ZZ09, ZZ12, ZZ14 All
2SD04701324 Combination Supply & Return Air Stream Smoke Detector ZZ07, ZZ08 All
2SD04701624 Combination Supply & Return Air Stream Smoke Detector ZZ09, ZZ12, ZZ14 All
1TB0401 Small Footprint Thru The Base Electrical & Thru The Curb Gas ZZ07, ZZ08 All
1TB0402 Large Footprint Thru The Base Electrical & Thru The Curb Gas ZZ09, ZZ12, ZZ14 All
1TB0403 Small Footprint Thru The Base Electrical & Gas ZZ07, ZZ08 All
1TB0404 Large Footprint Thru The Base Electrical & Gas ZZ09, ZZ12, ZZ14 All
Physical Data
Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) - - 100 -
2nd. Stage Heat input (K Btu) 70 114 145 -
1st. Stage Heat output (K Btu) - - 80 -
2nd. Stage Heat output (K Btu) 56 91 116 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 2 3 3 -
No. stages 1 1 2 -
Temperature Rise Range (ºF) 17-29 28-47 36-60 -
Gas Limit Setting (ºF) 150 140 140 -
Gas piping connection (in.) 1/2 1/2 1/2 -
Quantity of fans 1 1
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1/2 1/2
No. speeds 2 2
RPM 900 / 1150 900 / 1150
Nominal total CFM 3600 / 4600 3600 / 4600
Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
BELT DRIVE Blower Sheave AK51 AK51 AK51 AK51 AK51 AK51
Belt A39 A40 A41 A39 A40 A41
Motor Max Bhp, 3 Phase 2.4 2.9 3.7 2.4 2.9 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ
Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) - - 100 -
2nd. Stage Heat input (K Btu) 70 114 145 -
1st. Stage Heat output (K Btu) - - 80 -
2nd. Stage Heat output (K Btu) 56 91 116 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady State Efficiency (%) 80 80 80 -
No. burners 2 3 3 -
No. stages 1 1 2 -
Temperature Rise Range ( ͦF) 17-29 28-47 36-60 -
Gas Limit Setting ( ͦF) 150 140 140 -
Gas piping connection (in.) 1/2 1/2 1/2 -
Quantity of fans 1 1
fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1150 1150
Nominal total CFM 4600 4600
Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan size (inch) 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal
EVAPORATOR DAN Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
DATA BELT DRIVE Blower Sheave AK51 AK51 AK51 AK51 AK51 AK51
Belt A39 A40 A41 A39 A40 A41
Motor Max Bhp, 3 Phase 2.4 2.9 3.7 2.4 2.9 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ
Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 90 125 176 -
2nd. Stage Heat input (K Btu) 125 180 220 -
1st. Stage Heat output (K Btu) 72 100 141 -
2nd. Stage Heat output (K Btu) 100 144 176 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 3 4 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 22-36 31-52 38-64 -
Gas Limit Setting (ºF) 140 150 140 -
Gas piping connection (in.) 3/4 3/4 3/4 -
Quantity of fans 2 2
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 2 2
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1085 1085
Nominal total CFM 8600 8600
Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
BELT DRIVE Blower Sheave AK74 AK74 AK74 AK74 AK74 AK74
Belt A47 A48 A50 A47 A48 A50
Motor Max Bhp, 3 Phase 2.4 2.4 3.7 2.4 2.4 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ
Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 125 176 200 -
2nd. Stage Heat input (K Btu) 180 220 250 -
1st. Stage Heat output (K Btu) 100 141 160 -
2nd. Stage Heat output (K Btu) 144 176 200 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 4 5 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 27-44 33-54 37-62 -
Gas Limit Setting (ºF) 150 140 160 -
Gas piping connection (in.) 3/4 3/4 3/4 -
Quantity of fans 2 2
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 2 2
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1085 1085
Nominal total CFM 8600 8600
Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56
BELT DRIVE Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85
Belt A50 A50 BX52 A50 A50 BX52
Motor Max Bhp, 3 Phase 2.4 3.7 5.25 2.4 3.7 5.25
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56HZ 145TY 56Y 56HZ 145TY
Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 125 176 200 -
2nd. Stage Heat input (K Btu) 180 220 250 -
1st. Stage Heat output (K Btu) 100 141 160 -
2nd. Stage Heat output (K Btu) 144 176 200 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 4 5 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 21-36 26-43 30-49 -
Gas Limit Setting (ºF) 150 140 160 -
Gas piping connection (in.) 3/4 3/4 3/4 -
Quantity of fans 1 1
Fan diameter (Inch) 30 30
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1 1/2 1 1/2
No. speeds 1 1
RPM 1140 1140
Nominal total CFM 10600 10600
Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56
BELT DRIVE Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85
Belt A50 A52 BX54 A50 A52 BX54
Motor Max Bhp, 3 Phase 2.9 3.7 5.25 2.9 3.7 5.25
RPM 1750 1750 1750 1750 1750 1750
Frame size 56Z 184TZ 184TZ 56Z 184TZ 184TZ
Capacity Performance
ZZ07-14 Cooling Capacities
ZZ07 (6 Ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 89.8 4.1 45.1 37.4 29.8 - - - 84.7 4.6 41.2 34.3 27.5 - - -
72 82.1 4.0 55.6 47.1 38.5 30.0 - - 76.7 4.5 52.7 44.4 36.1 27.9 - -
1500
67 74.3 3.9 66.1 56.7 47.3 38.1 30.4 - 68.8 4.4 64.2 54.5 44.8 36.2 28.4 -
62 74.4 3.9 72.9 63.5 56.0 45.6 39.4 31.1 70.8 4.4 68.1 60.3 53.5 44.3 37.2 29.0
77 91.0 4.1 51.6 40.8 29.9 - - - 85.5 4.6 48.6 38.0 27.4 - - -
72 84.1 4.0 59.7 50.0 40.3 30.5 - - 78.8 4.5 57.1 47.5 37.8 28.2 - -
1800 67 77.2 4.0 67.8 59.2 50.6 40.3 31.1 - 72.1 4.5 65.5 56.9 48.3 38.3 28.9 -
62 74.7 4.0 73.8 67.4 60.9 49.4 41.3 31.5 71.2 4.5 69.9 64.3 58.7 48.0 39.1 29.3
57 60.7 3.9 60.7 60.7 60.7 60.7 51.6 41.7 59.4 4.5 59.4 59.4 59.4 59.2 49.3 39.5
77 92.2 4.1 58.1 44.1 30.1 - - - 86.4 4.6 56.0 41.7 27.4 - - -
72 86.2 4.1 63.9 52.9 42.0 31.1 - - 80.9 4.6 61.5 50.5 39.5 28.6 - -
2100 67 80.1 4.0 69.6 61.8 54.0 42.4 31.7 - 75.4 4.5 66.9 59.3 51.7 40.3 29.3 -
62 75.1 4.0 74.6 71.2 65.9 53.3 43.2 31.9 71.6 4.5 71.6 68.3 63.8 51.8 41.1 29.7
57 61.4 4.0 61.4 61.4 61.4 61.4 54.7 43.2 59.6 4.5 59.6 59.6 59.6 59.6 52.8 41.2
77 93.4 4.1 64.7 47.5 30.3 - - - 87.2 4.6 63.5 45.4 27.4 - - -
72 88.2 4.1 68.0 55.9 43.8 31.7 - - 83.0 4.6 65.9 53.5 41.2 28.9 - -
2400 67 83.0 4.0 71.3 64.3 57.3 44.5 32.3 - 78.7 4.5 68.2 61.7 55.1 42.3 29.8 -
62 75.4 4.0 75.4 75.1 70.8 57.1 45.1 32.3 72.0 4.5 72.0 72.0 69.0 55.6 43.0 30.0
57 62.1 4.0 62.1 62.1 62.1 62.1 57.9 44.7 59.7 4.5 59.7 59.7 59.7 59.7 56.2 42.8
72 90.2 4.1 72.1 58.8 45.5 32.3 - - 85.1 4.6 70.3 56.6 42.9 29.3 - -
67 85.9 4.0 73.1 66.8 60.6 46.7 33.0 - 82.1 4.6 69.6 64.1 58.6 44.4 30.3 -
2700
62 75.8 4.0 75.8 75.8 75.7 61.0 47.0 32.7 72.3 4.6 72.3 72.3 72.3 59.4 45.0 30.4
57 62.8 4.1 62.8 62.8 62.8 62.8 61.0 46.1 59.9 4.6 59.9 59.9 59.9 59.9 59.6 44.5
72 92.3 4.1 76.2 61.8 47.3 32.8 - - 87.2 4.6 74.7 59.6 44.6 29.6 - -
67 88.8 4.1 74.8 69.4 64.0 48.8 33.6 - 85.4 4.6 71.0 66.5 62.0 46.4 30.8 -
3000
62 76.2 4.1 76.2 76.2 76.2 64.8 48.9 33.0 72.7 4.6 72.7 72.7 72.7 63.1 46.9 30.7
57 63.5 4.1 63.5 63.5 63.5 63.5 63.5 47.6 60.0 4.6 60.0 60.0 60.0 60.0 60.0 46.2
95°F 105°F
77 79.5 5.1 37.2 31.2 25.1 - - - 76.5 5.8 35.3 29.1 23.0 - - -
72 71.4 5.0 49.7 41.7 33.8 25.8 - - 67.1 5.7 47.4 39.5 31.6 23.6 - -
1500
67 63.2 4.9 62.2 52.3 42.4 34.4 26.4 - 57.7 5.7 57.7 49.9 40.2 32.1 24.1 -
62 67.3 4.9 63.3 57.2 51.0 43.0 34.9 26.8 63.8 5.7 59.9 54.3 48.7 40.6 32.4 24.3
77 80.0 5.1 45.6 35.2 24.9 - - - 75.3 5.8 43.6 33.2 22.7 - - -
72 73.5 5.0 54.4 44.9 35.4 25.9 - - 68.5 5.8 52.0 42.5 33.1 23.7 - -
1800 67 67.0 5.0 63.2 54.6 45.9 36.3 26.7 - 61.6 5.7 60.3 51.9 43.5 33.9 24.4 -
62 67.7 5.0 66.1 61.3 56.4 46.7 36.9 27.1 64.0 5.7 62.4 58.2 53.9 44.2 34.5 24.7
57 58.2 5.0 58.2 58.2 58.2 57.0 47.1 37.2 59.6 5.7 59.6 59.6 59.6 54.4 44.5 34.6
77 80.5 5.1 53.9 39.3 24.7 - - - 74.2 5.8 52.0 37.2 22.5 - - -
72 75.6 5.1 59.1 48.1 37.1 26.1 - - 69.8 5.8 56.5 45.6 34.7 23.8 - -
2100 67 70.7 5.0 64.2 56.8 49.4 38.2 27.0 - 65.4 5.7 61.0 54.0 46.9 35.8 24.7 -
62 68.1 5.0 68.1 65.4 61.8 50.4 38.9 27.4 64.3 5.7 64.3 62.0 59.1 47.8 36.5 25.1
57 57.8 5.0 57.8 57.8 57.8 57.8 50.8 39.1 58.0 5.7 58.0 58.0 58.0 58.0 47.6 35.7
77 81.1 5.1 62.3 43.4 24.4 - - - 73.0 5.8 60.3 41.3 22.2 - - -
72 77.8 5.1 63.7 51.2 38.7 26.2 - - 71.2 5.8 61.0 48.6 36.2 23.9 - -
2400 67 74.5 5.0 65.2 59.1 53.0 40.1 27.3 - 69.3 5.8 61.7 56.0 50.3 37.6 25.0 -
62 68.5 5.0 68.5 68.5 67.2 54.1 40.9 27.7 64.5 5.7 64.5 64.5 64.3 51.4 38.5 25.6
57 57.4 5.0 57.4 57.4 57.4 57.4 54.5 41.0 56.4 5.7 56.4 56.4 56.4 56.4 50.6 36.7
72 79.9 5.1 68.4 54.4 40.3 26.3 - - 72.5 5.8 65.5 51.7 37.8 23.9 - -
67 78.2 5.1 66.1 61.3 56.5 42.0 27.6 - 73.2 5.8 62.4 58.0 53.6 39.5 25.3 -
2700
62 68.9 5.1 68.9 68.9 68.9 57.8 42.9 28.0 64.8 5.8 64.8 64.8 64.8 55.0 40.5 26.0
57 57.0 5.1 57.0 57.0 57.0 57.0 57.0 42.9 54.7 5.8 54.7 54.7 54.7 54.7 53.6 37.8
72 82.0 5.1 73.1 57.5 42.0 26.4 - - 73.8 5.8 70.1 54.7 39.4 24.0 - -
67 81.9 5.1 67.1 63.5 60.0 43.9 27.9 - 77.0 5.8 63.1 60.1 57.0 41.3 25.6 -
3000
62 69.3 5.1 69.3 69.3 69.3 61.5 44.9 28.4 65.0 5.8 65.0 65.0 65.0 58.6 42.5 26.5
57 56.6 5.1 56.6 56.6 56.6 56.6 56.6 44.9 53.1 5.8 53.1 53.1 53.1 53.1 53.1 38.8
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Drive Selection
Airflow Performance
Example Supply Air Blower Performance
ZY08 (7.5 Ton) Bottom Duct
Available External Static, IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 556 0.45 621 0.65 683 0.83 742 1.00 798 1.18 852 1.34 904 1.51 954 1.69 1003 1.87 1050 2.06
2400 567 0.53 632 0.73 694 0.91 753 1.09 809 1.26 863 1.43 914 1.60 964 1.77 1013 1.95 1060 2.14
2600 580 0.65 646 0.85 707 1.03 766 1.21 823 1.38 876 1.55 928 1.72 978 1.89 1027 2.07 1074 2.27
2800 595 0.79 660 0.99 722 1.17 780 1.35 837 1.52 890 1.69 942 1.86 992 2.03 1041 2.21 1088 2.40
3000 609 0.94 674 1.14 736 1.32 795 1.50 851 1.67 905 1.83 957 2.00 1007 2.18 1056 2.36 1100 2.55
3200 625 1.10 690 1.30 752 1.48 810 1.66 867 1.83 921 2.00 972 2.17 1022 2.34 1071 2.52 -- --
3400 641 1.28 706 1.47 768 1.66 827 1.83 883 2.00 937 2.17 989 2.34 1039 2.52 1087 2.70 '-- --
Altitude and Temperature Correction for CFM, Static use the indoor blower tables for high altitude applications,
Pressure and Power. certain corrections are necessary.
The information below should be used to assist in application of A centrifugal fan is a "constant volume" device. This means
product when being applied at altitudes at or exceeding 1000 that, if the RPM remains constant, the CFM delivered is the
feet above sea level. same regardless of the density of the air. However, since the air
at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance
generated and less power will be required than a similar
tables are based on standard air at sea level. As the altitude or
application at sea level. Air density correction factors are shown
temperature increases, the density of air decreases. In order to
below.
Altitude/Temperature Correction Factors
Air Altitude (Ft.)
Temp. 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729
50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715
60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701
70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676
90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651
1.100
1.050
1.000
Sea Level
0.950
Correction Factor
1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40 50 60 70 80 90 100
Air Temperature (ºF)
The examples below will assist in determining the airflow blower tables to select the blower speed and the BHP
performance of the product at altitude. requirement.
Example 1: What are the corrected CFM, static pressure, and Solution: As in the example above, no temperature
BHP at an elevation of 5,000 ft. if the airflow performance data information is given so 70°F is assumed.
is 3,000 CFM, 1.4 IWC and 2.0 BHP?
The 1.4" static pressure given is at an elevation of 5,000 ft. The
Solution: At an elevation of 5,000 ft. the indoor blower will still first step is to convert this static pressure to equivalent sea level
deliver 3,000 CFM if the rpm is unchanged. However, the Altitude conditions.
correction must be used to determine the static pressure and
Sea level static pressure = 1.4" / .832 = 1.68"
BHP. Since no temperature data is given, we will assume an Air
Temperature of 70°F. The Altitude/Temperature Factors show Enter the Supply Air Blower Performance Table at 3,000 CFM
the correction factor to be 0.832. and static pressure of 1.68". The rpm listed will be the same
rpm needed at 5,000 ft.
Corrected static pressure = 1.4 x 0.832 = 1.16 IWC
Corrected BHP = 2.0 x 0.832 = 1.66 Suppose that the corresponding BHP listed in the table is 2.0.
Example 2: A system, located at 5,000 feet of elevation, is to This value must be corrected for elevation.
deliver 3,000 CFM at a static pressure of 1.4". Use the unit BHP at 5,000 ft. = 2.0 x .832 = 1.66
RPM Selection
Size Airflow MAX Blower Motor 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Fully
Model Phase
(Tons) Option BHP Sheave Sheave Open Open Open Open Open Open Closed
Std. 3 2.4 AK51 1VL34 N/A 707 782 856 931 1005 1080
07
ZZ Med. 3 2.9 AK51 1VL44 N/A 1043 1117 1191 1266 1340 1415
(6)
H. Static 3 3.7 AK51 1VP50 N/A 1266 1340 1415 1489 1564 1638
Std. 3 2.4 AK51 1VL34 N/A 707 782 856 931 1005 1080
08
ZZ Med. 3 2.9 AK51 1VL44 N/A 1043 1117 1191 1266 1340 1415
(7.5)
H. Static 3 3.7 AK51 1VP50 N/A 1266 1340 1415 1489 1564 1638
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
09
ZZ Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(8.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK79 1VL44 N/A 653 700 747 793 840 887
12
ZZ Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027
(10)
H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A
Std. 3 2.9 AK79 1VL44 N/A 653 700 747 793 840 887
14
ZZ Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027
(12)
H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A
Airflow Performance
ZZ07-14 Side Duct Application (Belt Drive)
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.857 x BHP for Standard Static option, kW = 0.829 x BHP for Medium and High Static options
cfm cfm
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
250 1.00 250 1.00
460V 230V
150 0.60 150 0.60
In. In.
Pa Pa
WG WG
50 0.20 50 0.20
0 0 0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air volume[CMH] Air volume[CMH]
460-3-60 Power Exhaust Fan Curve 208/280-3-60 Power Exhaust Fan Curve
Electrical Data
ZZ07-14 Standard Static Indoor Blower - Without Powered Convenience Outlet
ZZ07-14 Standard Static Indoor Blower - Without Powered Convenience Outlet (Continued)
ZZ07-14 Standard Static Indoor Blower - With Powered Convenience Outlet (Continued)
ZZ07-14 Medium Static Indoor Blower - Without Powered Convenience Outlet (Continued)
ZZ07-14 Medium Static Indoor Blower - With Powered Convenience Outlet (Continued)
Typical ZZ07/08 Cooling Unit w/wo Electric Heat 208/230-3-60 Belt Drive - Elementary Diagram Power Circuit
Typical ZZ07/08 Cooling Unit w/wo Electric Heat 460-3-60 Belt Drive - Elementary Diagram Power Circuit
Typical ZZ09, ZZ12 Cooling Unit w/wo Gas Heat 208/230-3-60 Belt Drive Elementary Diagram Power Circuit
Typical ZZ14 Cooling Unit w/wo Gas Heat 208/230-3-60 Belt Drive Elementary Diagram Power Circuit
Typical ZZ09, ZZ12 Cooling Unit w/wo Gas Heat 460-3-60 Belt Drive Elementary Diagram Power Circuit
Typical ZZ14 Cooling Unit w/wo Gas Heat 460-3-60 Belt Drive Elementary Diagram Power Circuit
Typical ZZ07/08 Cooling Unit w/wo Electric Heat Belt Drive - Elementary Diagram Control Circuit
Typical ZZ07-08 Cooling Unit with Gas Heat Belt Drive - Elementary Diagram Control Circuit
Typical ZZ09 Cooling Unit Belt Drive Elementary Diagram Control Circuit
Typical ZZ09 Cooling Unit with Gas Heat Belt Drive Elementary Diagram Control Circuit
Typical ZZ12/14 Cooling Unit Belt Drive Elementary Diagram Control Circuit
Typical ZZ12/14 Cooling Unit with Gas Heat Belt Drive Elementary Diagram Control Circuit
X
Y
FRONT
LEFT
Size Weight (lbs.) Center of Gravity 4 point Load Location (lbs.) 6 point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
07
ZZE 634 614 34 25 168 146 139 160 115 104 95 91 99 109
(6)
08
ZZE 617 612 33.6 24.8 170 141 137 165 117 103 91 88 100 113
(7.5)
09
ZZE 857 852 46 36 230 262 192 168 150 163 178 131 120 110
(8.5)
12
ZZE 884 879 46 36 242 271 193 172 158 171 184 131 122 113
(10)
14
ZZE 946 941 45 36 265 284 203 189 175 183 192 137 130 125
(12.5)
Size Weight (lbs.) Center of Gravity 4 point Load Location (lbs.) 6 point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
07
ZZG 688 668 34 25 183 159 152 174 125 114 104 99 108 119
(6)
08
ZZG 671 666 33.6 24.8 185 153 149 179 127 112 99 96 109 123
(7.5)
09
ZZG 959 954 45 36 269 291 205 189 177 186 197 138 131 125
(8.5)
12
ZZG 990 985 45 37 284 301 206 194 187 195 203 139 133 128
(10)
14
ZZG 1052 1047 44 37 304 312 218 212 202 205 209 146 144 141
(12.5)
ZZ14
1. Units must be installed outdoors. Over hanging structure or 1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet. shrubs should not obscure condenser air discharge outlet.
2. Units without economizer or power exhaust. 2. Units without economizer or power exhaust.
3. Units equipped with an Economizer or Power Exhaust. Flue 3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of products must not be discharged within 10 Feet of the rear of
the unit. the unit.
4. Units may be installed on combustible floors made from 4. Units may be installed on combustible floors made from wood
wood or class A, B or C roof covering materials. or class A, B or C roof covering materials.
70.875 O.D.
67.375 I.D.
RN
32.188
RETU
RN
TU
RE
13.781
3.000
LY
37.188
PP
I.D.
SU
RIGHT
LY
FRONT
SU
RIGHT
4.961 14.000
5.422 FRONT
17.781
40.688 O.D.
70.871 40.684
Notes:
1. Sides, ends and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.
2. Full perimeter wood nailer.
3. Insulated deck pans.
NOTE: If utilities are required thru the base of the unit or thru
Unit Models used with 1RC0456, 1RC0458 Roof Curb the roof curb the following field installed accessories
ZZ07 can be purchased thru your dealer or contractor:
ZZ08 1TB0401 - Thru the base electrical and thru the curb gas
1TB0403 - Thru the base electrical and gas
81.750 O.D.
78.250 I.D.
40.188
RN
RN
TU
RETU
RE
15.469
3.000
50.000
I.D. RIGHT
LY
LY
PP
PP
34.313 31.531
SU
SU
11.417
15.813
FRONT
6.043 RIGHT
4.173
26.000
FRONT 24.813
81.746 53.496
NOTE: If utilities are required thru the base of the unit or thru
Unit Models used with 1RC0457, 1RC0459 Roof Curb the roof curb the following field installed accessories
ZZ09 can be purchased thru your dealer or contractor:
ZZ12 1TB0402 - Thru the base electrical and thru the curb gas
ZZ14 1TB0404 - Thru the base electrical and gas
Economizer Options
Economizer Usage
Application Description Accessory Kit Number
Econ, DB, Vertical Flow, Small Footprint 2EE04706724
Economizer Vertical Flow
Econ, DB, Vertical Flow, Large Footprint 2EE04706824
Econ, DB, Horizontal Flow, Small Footprint, Short Cabinet 2EE04707024
Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet 2EE04707124
Economizer Horizontal Flow
Econ, DB, Horizontal Flow, Large Footprint, Short Cabinet 2EE04707224
Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet 2EE04707324
Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph 2PE04704225
Power Exhaust Vert Flow Small Footprint 460V 3-ph 2PE04704246
Power Exhaust Vertical Flow Power Exhaust Vert Flow Large Footprint 208V-230V 1-ph 2PE04704306
Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph 2PE04704325
Power Exhaust Vert Flow Large Footprint 460V 3-ph 2PE04704346
Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph 2PE04704425
Power Exhaust Horiz Flow Small Footprint 460V 3-ph 2PE04704446
Power Exhaust Horizontal Flow
Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph 2PE04704525
Power Exhaust Horiz Flow Large Footprint 460V 3-ph 2PE04704546
Field Installed Vertical Flow Economizer
Guide Specifications
Model Series: ZZ
Number Title
1. Thermostat must
48HC
a. energize “G” when calling for fan only or continuous fan.
b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.
c. include capability for occupancy scheduling.
23 09 23 Direct- digital Control system for HVAC
7. Software upgrades will be accomplished by either local or remote download. No software upgrades through
chip replacements are allowed.
23 09 33 Electric and Electronic Control System for HVAC
3. Filters shall be accessible through an access panel with toolless removal as described in the unit cabinet
section of this specification (23 81 19.13.H).
23 81 19 Self- Contained Air Conditioners
1. Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking,
powder paint finish, certified at 750-hour salt spray test per ASTM-B117 standards.
2. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360
minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2- in. thick, 1 1/2 lb
density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil- faced fiberglass
insulation shall be used in the gas heat compartment. Fan shall be a belt drive assembly and include an
adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate
horsepower rating plus the service factor (Only premium efficiency motors have hp rating on the nameplate).
Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with forward
curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no
maintenance.
Condenser Fan Assembly: The outdoor fans shall be of the direct drive type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected
against overload conditions and staged independently.
3. Base of unit shall have a minimum of four locations for thru- the- base gas and electrical connections (factory
installed or field installed), standard.
4. Base Rail
a. Unit shall have base rails on a minimum of 4 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead
rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gauge thickness.
5. Condensate pan and connections:
a. Shall be an internally sloped condensate drain pan made of a non- corrosive material. b. Shall comply with
ASHRAE Standard 62.
c. Shall use a 3/4” - 14 NPT drain connection, possible either through the bottom or side of the drain pan.
Connection shall be made per manufacturer’s recommendations.
6. Top panel:
a. Shall be a single piece top panel.
7. Gas Connections:
a. All gas piping connecting to unit gas valve shall enter the unit cabinet at a single location on side of unit
b. Thru- the- base capability
(1.) Standard unit shall have a thru- the- base gas- line location using a raised, embossed portion of the
unit base-pan.
(2.) Optional, factory- approved, water- tight connection method must be used for thru- the- base gas
connections.
(3.) No base-pan penetration, other than those authorized by the manufacturer, is permitted.
8. Electrical Connections
a. All unit power wiring shall enter unit cabinet at a single, factory- prepared, knockout location. b. Thru- the-
base capability.
(1.) Standard unit shall have a thru- the- base electrical location (s) using a raised, embossed portion of the
unit base-pan.
(2.) Optional, factory- approved, water- tight connection method must be used for thru- the- base electrical
connections.
(3.) No base-pan penetration, other than those authorized by the manufacturer, is permitted.
a. Shall have a durable epoxy- phenolic coating to provide protection in mildly corrosive coastal
environments.
b. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
c. Epoxy- phenolic barrier shall minimize galvanic action between dissimilar metals.
23 81 19.13.K. Refrigerant Components
1. Refrigerant circuit shall include the following control, safety, and maintenance features:
a. Thermostatic Expansion Valve (TXV) shall help provide optimum performance across the entire operating
range. Shall contain removable power element to allow change out of power element and bulb without
removing the valve body. (Orifice on ZZ09, ZZ12)
b. Refrigerant filter drier - Solid core design.
c. Service gauge connections on suction and discharge lines.
d. Pressure gauge access through a specially designed access port in the top panel of the unit.
2. There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug.
a. The plug shall be easy to remove and replace.
b. When the plug is removed, the gauge access port shall enable maintenance personnel to route their
pressure gauge lines.
c. This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d. The plug shall be made of a leak proof, UV- resistant, composite material.
3. Compressors
a. Unit shall use fully hermetic, scroll compressor for each independent refrigeration circuit.
b. Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c. Compressors shall be internally protected from high discharge temperature conditions.
d. Compressors shall be protected from an over- temperature and over- amperage conditions by an internal,
motor overload device.
e. Compressor shall be factory mounted on rubber grommets.
f. Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g. Crankcase heaters shall not be required for normal operating range, unless provided by the factory.
23 81 19.13.L. Filter Section
1. Filters access is specified in the unit cabinet section of this specification.
3. Shall consist of factory- installed, low velocity, throw- away 2” or 4” thick fiberglass filters.
3. Units can accept 2” or 4” filters and have a field convertible toolless
23 81 19.13.M. Evaporator Fan and Motor
1. Evaporator fan motor:
a. Shall have permanently lubricated bearings.
b. Shall have inherent automatic reset thermal protection (Only on single-phase, belt-drive motors, three -
phase, belt-drive motors have internal thermostat used for external line-break control.).
2. Belt- driven Evaporator Fan:
a. Belt drive shall include an adjustable- pitch motor pulley.
b. Shall use sealed, permanently lubricated ball- bearing type.
c. Blower fan shall be double- inlet type with forward- curved blades.
d. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.
23 81 19.13.N. Condenser Fans and Motors
The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall
have permanently lubricated 60°C ball bearings internally protected against overload conditions and staged
independently. A cleaning window shall be provided on two sides of the units for coil cleaning.
1. Condenser fan motors:
a. Shall be a totally enclosed motor.
b. Shall use permanently lubricated bearings.
c. Shall have inherent thermal overload protection with an automatic reset feature.
d. All models Shall use a shaft- down design except shaft- up on ZZ14 size with rain shield.
2. Condenser Fans:
a. Shall be a direct- driven propeller type fan.
b. Shall have galvanized steel blades riveted to corrosion- resistant steel spiders and shall be dynamically
balanced.
3. Standard Integrated Economizers:
a. Integrated, gear- driven opposing modulating blade design type capable of simultaneous economizer and
compressor operation.
b. Independent modules for vertical or horizontal return configurations shall be available. Vertical return
modules shall be available as a factory installed option.
c. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or
return shall not be acceptable.
d. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or
humidity are below set-points.
e. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for
positive air stream control.
f. Standard models shall be equipped with low- leakage dampers, not to exceed 2% leakage at 1 in. wg pres-
sure differential. Economizers will come with Actuator and module that is tied to Smart Equipment™:
(1.) Combined minimum and DCV maximum damper position potentiometers with compressor staging re-
lay.
(2.) Functions with solid state analog enthalpy or dry bulb changeover control sensing.
(3.) Contain LED indicates for: when free cooling is available when module is in DCV mode when exhaust
fan contact is closed
4. Two- Position Damper
a. Damper shall be a Two- Position Damper. Damper travel shall be from the full closed position to the field
adjustable %- open setpoint.
b. Damper shall include adjustable damper travel from 25% to 100% (full open).
c. Damper shall include single or dual blade, gear driven dampers and actuator motor.
d. Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable. e.
Damper will admit up to 100% outdoor air for applicable rooftop units.
f. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.
g. The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.
h. Outside air hood shall include aluminum water entrainment filter.
5. Manual damper
a. Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit
up to 25 or 50% outdoor air for year round ventilation.
6. Condenser Coil Hail Guard Assembly (Factory and Field installed on all models):
a. Shall protect against damage from hail.
b. Shall be of louvered style.
7. Unit- Mounted, Non- Fused Disconnect Switch: (Verify on the unit nameplate that the disconnect is properly sized
for the application. Units with field installed electric heat may exceed the factory installed disconnect amperage
rating.)