5846585-YTG-A-1119

Sun™ Core
TECHNICAL GUIDE
ZZ Series
6 - 12.5 TON
60 HERTZ (EXPORT ONLY)

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE


5846585-YTG-A-1119

Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Field Installed Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Cooling Performance Rating Table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
AHRI 270 Outdoor Sound Power Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Power Exhaust Blower Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Product Highlights
• Assembled in Norman, OK • Evaporator coils utilize copper tube/aluminum fin design
• ASHRAE 90.1 Compliant for proven reliability and performance.
• R-410A Refrigerant • TXV (Thermostatic Expansion Valve) Standard on:
(ASHRAE 90.1 Compliant Standard Efficiency Level 6 -
• Cooling Only and Gas/Electric configurations available
12.5 ton models)
• Scroll Compressors
• Single-stage Cooling (6 - 7.5 ton models)
• State of the art Microprocessor Controls with specific
• Two-stage Cooling (8.5 - 12.5 ton models)
programming for product applications
• Alternate Motor and Drives
• MicroChannel Condenser Coils

Options and Accessories


• Economizers with Barometric Relief • Smoke Detectors
• Louvered Hail Guards • Manual and Motorized Dampers
• Non-fused Disconnect (Verify on the unit nameplate that • Hinged Cabinet Doors
the disconnect is properly sized for the application. Units • Low Ambient Head Pressure Control Kit.
with field installed electric heat may exceed the factory
• Optional Stainless Steel Heat Exchanger
installed disconnect amperage rating.)
• Thru-The-Base Connections for power, gas and control
• Power Exhaust
wiring.
• Propane Conversion Kits
• Field Installed Electric Heat Kit, Installation Instructions for
• High Altitude Heating Conversion Kits the Electric Heat Kits may be found in the Electric Heat
• Flue Exhaust Extension Kit Kits.
• Flue Heat Shield

2 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Component Location
Cooling With Gas Heat

B
E

D H

G J

Click on the letters to see a description of the features.

E B

G
C

Johnson Controls Ducted Systems 3


5846585-YTG-A-1119

Features and Benefits


better performance and reliability. The direct drive fan design
mounted to the fan grill allows for quick and easy service.
Where other's components might fail at extreme temperatures
Our units are tested and rated up to 125°F ambient cooling
operation.

A All models utilize a scroll compressor that are


environmentally friendly by utilizing R-410A refrigerant. Use of
the scroll compressor technology means a simple internal
design, fewer moving parts, equating to a quiet, reliable, easy to
service and efficient system. Internal compressor protection is
standard and compressors include protection to prevent liquid C Convertible Filter Rack - No tools required for easy field
damage. conversion of the filter rack to accommodate either 2” or 4”
filters. Units will ship with MERV 4 throwaway filters standard;
Total system design - A TXV is used for precise metering on however MERV 8 and MERV 13 filters can be easily added
the 6-12.5 Ton products. Two independent refrigerant circuits through the tool-free filter access panel to meet LEED
and compressors are used on the 8.5 - 12.5ton units for requirements. Refer to physical data tables for filter size details.
economical and precise control. A single circuit, single
compressor design is used on the 6 - 7.5 ton units for cost
effectiveness and reliability without compromising quality.

System Protection - Liquid line filter-driers, high and low


pressure safeties are standard on each independent refrigerant
circuit. Suction line sensors monitor temperature to prevent
possible liquid flood back to the compressors and also protect
against loss of charge and coil frosting.

D Units will come with the new state of the art Smart
Equipment™ control system. The new unit control
incorporates the best of the already proven Smart Equipment™
controls and creates a more robust, intelligent control. The goal
of this control is to utilize cutting edge technology making the
equipment easier to install, operate, and service. All units are
Factory commissioned, configured, and run tested.

Versatile - The Smart Equipment™ control can be configured


to use with a standard thermostat (easy to connect screw
terminals), a zone sensor, or can be setup to communicate with
B Balanced outdoor fan design makes for a quieter unit -
The outdoor condenser fans are dynamically balanced for

4 Johnson Controls Ducted Systems


5846585-YTG-A-1119

multiple BAS communication protocols to integrate with building


automation systems.

Reduce field installed complexity - Each unit will come


equipped with factory installed supply air, return air, and
outdoor air temperature sensors providing key temperature
readings thus reduce field installed complexity.

On-board USB Port - The new control comes with a long list of
features including data logging, current and previous system
faults and software update capabilities using the on board USB
port and common flash drive. Energy use monitoring
capabilities allow custom tailoring to allow a system to work
more efficiently at all times and occupancy levels. Self test and
start-up reports also available from the board VIA the USB port.

Embedded LCD Display - The board has a easy to read, built-


in LCD display and easy to use navigation joystick and buttons
allowing the user to quickly navigate the menus displaying unit E Robust design - Each unit is designed with an embossed
status, options, current function, supply, return and outdoor top to increase structural support and ensure rigidity. The unit
temperatures, fault codes and other information. has a powder paint exterior finish including a industry leading
750-hour salt spray rating. All units are painted with a long
Safety Monitoring - The control monitors the outdoor, supply, lasting, powder paint that stands up over the life of the unit.
and return air temperatures and the high and low pressure
switch status on the independent refrigerant circuits. On units
with heating the gas valve and high temperature limit switches
are monitored on gas and electric heating units. The control
also monitors the voltage supplied to the unit and will protect
the unit if low voltage due to a brown out, or other electrical
issue occurs.

Low Ambient - An integrated low-ambient control allows units


to operate in the cooling mode down to 0°F outdoor ambient
without additional components or intervention. Optionally, the
F Full Perimeter base rail that fits on many existing curbs -
This product was designed with the replacement market in mind
control board can be programmed to lockout the compressors
which is why it will fit on many existing curbs in the field but it
when the outdoor air temperature is low or when free cooling is
also takes into account the new construction market by being
available.
versatile and sturdy. This unit is equipped with heavier gauge
Anti-Short Cycle Protection - To aid compressor life, an anti- and innovatively designed base rails to prevent damage from
short cycle delay is incorporated into the standard control. transporting and rigging.
Compressor reliability is further ensured by programmable
minimum run times. For testing, the anti-short cycle delay can
be temporarily overridden with the push of a button.

Fan Delays - Fan on and fan off delays are fully programmable.
Furthermore, the heating and cooling fan delay times are
independent of one another. All units are programmed with
default values based upon their configuration of cooling and/or
heating capacity.

Nuisance Trip Protection and Three Strikes - To prevent


nuisance calls, the control board uses a three times, you're out
philosophy. The high, low-pressure switch, anti-freeze
protection, low voltage or heating high limit must trip three times
within two hours before the unit control board will lock out the
associated compressor. The same safety must trip three times
before a hard lockout will occur.

G Coils - All units utilize Micro-Channel "all-aluminum"


condenser coils that provides improved heat transfer
capabilities and reduced refrigerant charge volumes. This

Johnson Controls Ducted Systems 5


5846585-YTG-A-1119

equates to all units meeting LEED EA Credit 4 Requirements Aluminized steel heat exchangers carry a 10-year warranty and
for Enhanced Refrigerant Management. MicroChannel coils are stainless steel heat exchangers carry a 15- year warranty.
also much easier to clean than your typical fin/tube designs.

All evaporator coils utilize copper tube with aluminum fin design
Factory Installed Options
for proven reliability and performance.
(Nomenclature Digit Position)

Airflow Options (6)


Alternate Indoor Blower Motor - For applications with high
static restrictions, units are offered with optional indoor motors
providing higher external static capability and/or higher airflow,
depending upon the installer's needs.

• A=Standard Static (Belt Drive for 6-12.5 Ton)


• B=Medium Static (Belt Drive for 6-12.5 Ton)
• C=High Static (Belt Drive for 6-12.5 Ton; 3 Phase
Models Only)

Coil Options (8)


E-Coat Coils – Coils are coated with an epoxy polymer
coating to protect against corrosion. A 3-year warranty is
H Rigid Mounted Blower Assembly - Dynamically balanced added when this option is selected.
indoor fans ensure better performance and reliability. Large
access panels for easier access, service, and maintenance. • A=Standard Indoor & Outdoor Coils (fin/tube design on
The belt drive option is standard on 6-12.5 ton products. Low, indoor coil and MicroChannel design used on outdoor
Medium, and High Static drive options for airflow versatility up coil with no E-Coat coating added).
to 2" ESP with no field installed drive packages necessary. The • B=Standard Indoor Coil & E-Coat Coil Outdoor Coil (fin/
blower section includes a dual density insulation for indoor air tube design on indoor coil and MicroChannel design
quality. used on outdoor coil. E-Coat coating added to outdoor
coil)
• C= E-Coat Indoor Coil & Standard Outdoor Coil (fin/tube
design on indoor coil and MicroChannel design used on
outdoor coil. E-Coat coating added to indoor coil)
• D= E-Coat Indoor Coil & Outdoor Coil (fin/tube design
on indoor coil and MicroChannel design used on
outdoor coil. E-Coat coating added to indoor and
outdoor coil)

Controls (9)
Smart Equipment™ - This is the Standard microprocessor
control with capabilities to work with a sensor or thermostat
only. Smart Equipment™ with BAS includes communication
board with BACnet open-protocol system.

Verasys - Verasys provides a simple user experience with


configurable self-recognizing controllers without the need for
J Balanced Heating - The two stage gas heating offers any additional tools. Verasys creates enhanced integration of
ultimate heating comfort with a balance between 1st and 2nd HVACR equipment, zoning, and controls. Contractors are
stage gas heating. The first stage of a two stage gas heat able to offer a complete bundled solution of equipment and
option provides approximately 70% of the heating capacity in all controls to serve the light commercial market.
3-12.5 tons two stage gas heat models. Balanced heating
allows the unit to better maintain desired temperatures and • A=Smart Equipment™
helps saves energy. The heat exchanger section includes foil • B=Smart Equipment™ + BACnet MSTP, Mdbs, N2
faced insulation that is not only environmentally friendly but COM Card
meets all NFPA codes.
• J=Verasys Single Zone
Warranty - All models include a 1-year limited warranty on the • K=Verasys Change Over Bypass
complete unit. Compressors carry a 5-year warranty.

6 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Sensor Options (10) Electrical Options (13)


• 1=None (Units come standard with factory installed Disconnect Switch - For units with field installed electric
supply air, return air, and outdoor air temperature heat kits, two factory installed disconnect sizes are available
sensors) (60A or 100A non-fused disconnect). Depending on the field
• 2=RA1 Smoke Detector installed heater kit selected, the factory installed disconnect
may not be sufficient. Always refer to the unit nameplate or
• 3=SA Smoke Detector
unit electrical data for the proper disconnect size. If the heater
• 4=RA1 & SA Smoke Detector application requires a disconnect above 100 Amps, the
1. Return Air Smoke Detector Sensor Must Be Relocated in the factory installed disconnect should be removed and an
Field. (See Unit Installation Manual.) appropriately sized external disconnect should be installed.

• 1=None
Economizer/Damper (11)
• 2=Non-fused Disconnect1
Down flow Economizers (with barometric relief) - All units
offer a variety of optional factory installed economizers that are 1. Verify on the unit nameplate that the disconnect is properly
shipped, installed and wired with AMCA 511 Licensed Class sized for the application. Units with field installed electric heat
1A low leak dampers designed to exceed ASHRAE 90.1 and may exceed the factory installed disconnect amperage rating.
the International Energy Conservation Code (IECC)
certification requirements by achieving leakage rates of 3 cfm/ Cabinet Options (14)
sq. ft. at 1" of static pressure. Each economizer goes through a Louvered Hail Guard - This kit includes a decorative
rigorous 60,000 cycle test. Dry bulb, single enthalpy, and dual louvered panel which installs over the outside condenser coil
enthalpy (with field installed kit) can be selected. All and prevents damage to the coil fins from hail strikes.
economizer options are fully integrated into the Smart
Equipment™ controls. The economizer has spring return, fully Hinged Cabinet Doors - The factory installed hinged panel
modulating damper actuators and is capable of introducing up option will save time, money and labor while allowing easy
to 100% outdoor air. As the outdoor air intake dampers open, servicing of blower components, filters and controls. With this
the return air dampers close. The changeover from option there is no longer a need to remove panels to access
mechanical refrigeration to economizer operation is regulated these critical sections and running the risk of losing panels or
by the outdoor air dry bulb temperature or the outdoor air roof damage from loose panels and materials. Extra care was
enthalpy input. The dual enthalpy kit provides a second input taken to design a durable hinged panel with leak tight seal.
used to monitor the return air (field installed). The installer
• 1=None
needs only to assemble the outdoor air hood, attach the
enthalpy control the hood and mount the hood to the unit • 2=Louvered Panels
(Hood and control are provided). • 3=Hinged Cabinet Doors

Dry Bulb Economizer - Economizer operation is enabled by • 4=Hinged Cabinet Doors And Louvered Panels
the outdoor air temperature being less than the setpoint of the FDD (Fault Detection and Diagnostics) - Refrigerant side A
economizer module. Modification Shop offering for an additional installed control
system for commercial equipment that constantly monitors
Enthalpy Economizer - The added outdoor air enthalpy refrigerant circuit pressures, refrigerant circuit temperatures, as
sensor enables economizer operation if the outdoor enthalpy well as the environmental temperatures and humidity via
is less than the setpoint of the economizer logic module. multiple sensor inputs.
• A=None
• B=Dry Bulb Economizer
Field Installed Accessories
• C=Enthalpy Economizer • Down flow Economizers/Horizontal Economizers
(with barometric relief) - All units offer a variety of field
Convenience Outlet (12)
installed economizers that are installed and wired with
Convenience Outlet - (Powered and Non-Powered) - This AMCA 511 Licensed Class 1A low leak dampers designed
option locates a 120V single-phase GFCI outlet with cover, on to exceed ASHRAE 90.1 and the International Energy
the corner of the unit housing adjacent to the compressors. Conservation Code (IECC) certification requirements by
The Non-powered option requires the installer to provide the achieving leakage rates of 3 cfm/sq. ft. at 1" of static
120V single-phase power source and wiring. Factory installed pressure. Each economizer goes through a rigorous
option only. 60,000 cycle test. Dry bulb, single enthalpy, and dual
• 1=None enthalpy (with field installed kit) can be selected. All
economizer options are fully integrated into the Smart
• 2=Non-powered Convenience Outlet Equipment™ controls. The economizer has spring return,
• 3=Powered Convenience Outlet fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The

Johnson Controls Ducted Systems 7


5846585-YTG-A-1119

changeover from mechanical refrigeration to economizer • Gas Heat High Altitude Kit - This kit converts a gas heat
operation is regulated by the outdoor air dry bulb unit to operate at high altitudes, 2,000 to 10,000 feet.
temperature or the outdoor air enthalpy input. The dual Conversion kits are available for natural gas and propane.
enthalpy kit provides a second input used to monitor the • Roof Curbs - The roof curbs have insulated decks and
return air (field installed). The installer needs only to are shipped disassembled The roof curbs are available in
assemble the outdoor air hood, attach the enthalpy control 14 and 24 heights.
the hood and mount the hood to the unit (Hood and
• Thermostat - The units are designed to operate with 24-
control are provided).
volt electronic and electro-mechanical thermostats. All 7.5
• Dry Bulb Economizer - Economizer operation is enabled thru 12.5 ton units operate with two-stage heat/two-stage
by the outdoor air temperature being less than the cool or two-stage cooling only thermostats, depending
setpoint of the economizer module. upon unit configuration.
• Single Enthalpy Control, Accessory for Economizer - • Smoke detectors - The smoke detectors stop operation
All field installed economizers will come standard as a dry of the unit by interrupting power and providing a fault
bulb economizer. This kit adds an outdoor air enthalpy message to the control board if smoke is detected within
sensor which enables economizer operation if the outdoor the air compartment. Smoke detectors are available for
enthalpy is less than the setpoint of the economizer logic both the supply and/or return air configurations.
module.
• Hinged Filter Access Panel For Use With Horizontal
• Dual Enthalpy Control, Accessory for Economizer - All Flow Economizer - Allows hinged access to the filter
field installed economizers will come standard as a dry section when used with a horizontal economizer.
bulb economizer. This kit adds an outdoor air enthalpy
• Low Ambient Head Pressure Control Kit - The
sensor and return air enthalpy sensor which enables
Electronic Low Ambient Controller is designed to regulate
economizer operation if the outdoor enthalpy is less than
condenser head pressure at low ambient temperatures by
the setpoint of the economizer logic module.
varying the amount of airflow through the condenser.
• Power Exhaust - This accessory installs in the unit with a
• Manual Outdoor Air Damper - Like the motorized
down flow economizer or in the ductwork for a horizontal
outdoor air damper, each manual outdoor air damper
application.
includes a slide-in damper assembly with an outdoor air
• Louvered Hail Guard - This kit includes a decorative hood and filters. Customers have a choice of dampers
louvered panel which installs over the outside condenser with ranges of 0% to 100% or 0% to 35% outdoor air
coil and prevents damage to the coil fins from hail strikes. entry.
• Flue Exhaust Extension Kit - In locations where wind or • Thru The Base Connection - Kits are available to
weather conditions may interfere with proper exhausting provide a way to route wiring to the unit through the base
of furnace combustion products, this kit can be installed to of the unit and gas supplied to the unit through the base or
prevent the flue exhaust from entering nearby fresh air through the curb. These kits provide a seal tight way to
intakes. bring power and gas to the unit without additional roof
• Propane Conversion Kit - This kit converts a gas heat penetrations.
unit to operate with propane gas at altitudes up to 2,000 • Electric Heat (Field installed option Only) - Select
feet. heater sizes for 3-12.5 ton units available. Necessary
hardware and connectors are included with the heaters.

8 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Nomenclature

Nomenclature for ZZ07-14 (6-12.5) Ton Units


Z Z E 07 A 2 A 1 A A
1 1 A 1 1 1 L 1

Product Category Product Generation

1 = First Generation
ZZ = Pkg AC Constant Volume (Export Only)

Special Options - Country


Heat Type
L = Latin America
E = No Heat, Cooling Only
G = Gas Heat
Cabinet Options

Nominal Cooling Capacity 1 = None


2 = Louvered Panels Installed
07 = 6 Ton 3 = Hinged Cabinet Doors
08 = 7.5 Ton 4 = Hinged Cabinet Doors & Louvered Panels
09 = 8.5 Ton
12 = 10 Ton
14 = 12.5 Ton Electrical Options

1 = None
Heat Capacity 2 = Non-Fused Disconnect
5 = Phase Monitor
A = Cooling only (no heat)

Gas Heat
Convenience Outlet
D = Low Heat
E = Medium Heat 1 = None
F = High Heat 2 = Non-powered
R = Low Heat - Stainless Steel 3 = Powered
S = Medium Heat - Stainless Steel
T = High Heat - Stainless Steel
Economizer / Damper

Voltage A = None
B = Dry Bulb Economizer
C = Enthalpy Economizer
2 = 208/230-3-60
4 = 460-3-60
Sensor Options

Airflow 1 = None (units come standard with


factory-installed supply air, return air, and
A = Standard Static (CV) outdoor air temperature sensors)
B = Medium Static (CV) 2 = RA1 Smoke Detector
C = High Static (CV) 3 = SA Smoke Detector
4 = RA1 & SA Smoke Detector

Options 1) Return air smoke detector sensor must be


relocated in the field. (See unit installation manaul).
1 = No service options
Controls

Coil Options A = Smart Equipment™


B = Smart Equipment + BACnet MSTP, Modbus, N2 COM Card
J = Verasys Single Zone
A = Standard Indoor & Outdoor Coils
K = Verasys Change Over Bypass
B = Standard Indoor Coil & Electrofin Outdoor Coils
C = E-Coat Indoor Coil & Standard Outdoor Coils
D = E-Coat Indoor & Outdoor Coils

Johnson Controls Ducted Systems 9


5846585-YTG-A-1119

Accessories
Accessory Kit
Description Where Used Voltage
Number
2EE04706724 Econ, DB, Vertical Flow, Small Footprint ZZ07, ZZ08 All
2EE04706824 Econ, DB, Vertical Flow, Large Footprint ZZ09, ZZ12, ZZ14 All
2EE04707124 Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet ZZ07, ZZ08 All
2EE04707324 Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet ZZ09, ZZ12, ZZ14 All
1FA0415 Manual Outside Air Damper 0-35% ZZ07, ZZ08 All
1FA0416 Manual Outside Air Damper 0-35% ZZ09, ZZ12, ZZ14 All
1FA0417 Manual Outside Air Damper 0-100% ZZ07, ZZ08 All
1FA0418 Manual Outside Air Damper 0-100% ZZ0, ZZ12, ZZ14 All
2MD04704224 Motorized Outside Air Damper 0-100% ZZ07, ZZ08 All
2MD04704324 Motorized Outside Air Damper 0-100% ZZ09, ZZ12, ZZ14 All
2EC0401 Kit, Single Enthalpy Field Installed All All
2EC0402 Kit, Dual Enthalpy Field Installed All All
Hinged Filter Access Panel For Units With A Horizontal
1HD0402 ZZ07, ZZ08 All
Economizer
Hinged Filter Access Panel For Units With A Horizontal
1HD0404 ZZ09, ZZ12, ZZ14 All
Economizer
1HG0420 Hail Guard Kit Small Footprint, Tall Cabinet ZZ07, ZZ08 All
1HG0424 Hail Guard Kit Large Footprint, Tall Cabinet ZZ09, ZZ12, ZZ14 All
1RC0456 Curb Rigid 14" Small Footprint ZZ07, ZZ08 All
1RC0457 Curb Rigid 14" Large Footprint ZZ09, ZZ12, ZZ14 All
1RC0458 Curb Rigid 24" Small Footprint ZZ07, ZZ08 All
1RC0459 Curb Rigid 24" Large Footprint ZZ09, ZZ12, ZZ14 All
2PE04704225 Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph ZZ07, ZZ08 208/230-3-60
2PE04704246 Power Exhaust Vert Flow Small Footprint 460V 3-ph ZZ07, ZZ08 460-3-60
2PE04704325 Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph ZZ09, ZZ12, ZZ14 208/230-3-60
2PE04704346 Power Exhaust Vert Flow Large Footprint 460V 3-ph ZZ09, ZZ12, ZZ14 460-3-60
2PE04704425 Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph ZZ07, ZZ08 208/230-3-60
2PE04704446 Power Exhaust Horiz Flow Small Footprint 460V 3-ph ZZ07, ZZ08 460-3-60
2PE04704525 Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph ZZ09, ZZ12, ZZ14 208/230-3-60
2PE04704546 Power Exhaust Horiz Flow Large Footprint 460V 3-ph ZZ09, ZZ12, ZZ14 460-3-60
1HA0454 High Altitude Kit for Natural Gas (2,000-10,000 ft) ZZ07, ZZ08 - Low, Med, High Heat All
1HA0455 High Altitude Kit for Natural Gas (2,000-10,000 ft) ZZ09, ZZ12, ZZ14 All
1NP0456 Propane Conversion Kit Note: Not for use with Low NOx ZZ07, ZZ08 - Low, Med, High Heat All
1NP0457 Propane Conversion Kit ZZ09, ZZ12, ZZ14 All
High Altitude Kit for Propane (2,000-10,000 ft) Note: Not for use
1HA0458 ZZ07, ZZ08 - Low, Med, High Heat All
with Low NOx
1HA0459 High Altitude Kit for Propane (2,000-10,000 ft) ZZ09, ZZ12, ZZ14 All
1FE0415 Flue Exhaust Kit ZZG07, ZZG08 All
1FE0416 Flue Exhaust Kit ZZG09, ZZG12, ZZG14 All
1HS0401 Flue Heat Shield Accessory ZZ07, ZZ08, ZZ09, ZZ12, ZZ14 All
2EK04510625 6.5 KW Electric Heat ZZ07, ZZ08 208/230-30-60
2EK04510646 6.0 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511125 10.5 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04511146 11.5 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511446 14 KW Electric Heat ZZ07, ZZ08 460-3-60
2EK04511625 16 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04511725 16 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04511746 16.5 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60

10 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Accessories (Continued)
Accessory Kit
Description Where Used Voltage
Number
2EK04510625 6.5 KW Electric Heat ZZ07, ZZ08 208/230-3-60
2EK04512525 24.8 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04512846 27.8 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2EK04513225 32 KW Electric Heat ZZ09,ZZ12, ZZ14 208/230-3-60
2EK04513346 33 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2EK04514225 42.4 KW Electric Heat ZZ09, ZZ12, ZZ14 208/230-3-60
2EK04514246 41.7 KW Electric Heat ZZ09, ZZ12, ZZ14 460-3-60
2LA04704725 Low Ambient Accessory Kit ZZ07, ZZ08 208/230-3-60
2LA04704746 Low Ambient Accessory Kit ZZ07, ZZ08 460V-3-60
2LA04704825 Low Ambient Accessory Kit ZZ09, ZZ12, ZZ14 208/230-3-60
2LA04704846 Low Ambient Accessory Kit ZZ09, ZZ12, ZZ14 460V-3-60
2LA04704925 Low Ambient Accessory Kit ZZ14 208V/230V-3-60
2LA04704946 Low Ambient Accessory Kit ZZ14 460V-3-60
2SD04701224 Supply Air Stream Smoke Detector ZZ07, ZZ08, ZZ09, ZZ12, ZZ14 All
2SD04701124 Return Air Stream Smoke Detector ZZ07, ZZ08 All
2SD04701424 Return Air Stream Smoke Detector ZZ09, ZZ12, ZZ14 All
2SD04701324 Combination Supply & Return Air Stream Smoke Detector ZZ07, ZZ08 All
2SD04701624 Combination Supply & Return Air Stream Smoke Detector ZZ09, ZZ12, ZZ14 All
1TB0401 Small Footprint Thru The Base Electrical & Thru The Curb Gas ZZ07, ZZ08 All
1TB0402 Large Footprint Thru The Base Electrical & Thru The Curb Gas ZZ09, ZZ12, ZZ14 All
1TB0403 Small Footprint Thru The Base Electrical & Gas ZZ07, ZZ08 All
1TB0404 Large Footprint Thru The Base Electrical & Gas ZZ09, ZZ12, ZZ14 All

Johnson Controls Ducted Systems 11


5846585-YTG-A-1119

Cooling Performance Rating Table

NOM. COOLING EER EER (A/C IEER IEER (A/C


COOLING NET COOLING TOTAL
UNIT CAPACITY SEER (COOLING WITH GAS (COOLING WITH GAS
STAGES CAPACITY (MBH) POWER (kW)
(TONS) ONLY) HEAT) ONLY) HEAT)

ZZ07 1 6.0 67.0 6.0 --- 11.2 11.0 N/A N/A


ZZ08 1 7.5 85.0 8.4 --- 10.6 10.4 N/A N/A
ZZ09 2 8.5 99.0 7.7 --- 11.2 11.0 N/A N/A
ZZ12 2 10.0 116.0 9.2 --- 11.2 11.0 N/A N/A
ZZ14 2 12.5 135.0 10.8 --- 11.0 10.8 N/A N/A

AHRI 270 Outdoor Sound Power Levels

Octave Bands (Hz)


Unit (Tons) Sound Rating1(dB-A)
63 125 250 500 1000 2000 4000 8000
ZZ07 (6) 79 85.0 85.0 77.0 75.0 74.0 70.0 66.0 62.0
ZZ08 (7.5) 78.5 84.0 82.5 79.0 74.5 73.5 69.0 66.5 59.5
ZZ09 (8.5) 83 91.0 86.0 79.0 79.5 78.0 74.0 70.5 69.0
ZZ12 (10) 84 87.5 85.0 81.0 80.0 80.0 74.5 70.5 69.0
ZZ14 (12.5) 90 87.5 88.5 85.0 86.0 85.0 81.0 78.5 73.0

1. Rated in accordance with AHRI 270 standard.

12 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Physical Data

ZZ07 Physical Data


Models
Component
ZZG07 ZZE07
Nominal Tonnage 6 6

Gross Capacity @ AHRI A point (Btu) 70000 70000


AHRI net capacity (Btu) 67000 67000
EER 11.0 11.2
Nominal CFM 2200 2200
AHRI COOLING
System power (KW) 6.0 6.0
PERFORMANCE
Refrigerant type R-410A R-410A
Refrigerant charge (lb-oz)
System 1 7-4 7-4
System 2

Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) - - 100 -
2nd. Stage Heat input (K Btu) 70 114 145 -
1st. Stage Heat output (K Btu) - - 80 -
2nd. Stage Heat output (K Btu) 56 91 116 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 2 3 3 -
No. stages 1 1 2 -
Temperature Rise Range (ºF) 17-29 28-47 36-60 -
Gas Limit Setting (ºF) 150 140 140 -
Gas piping connection (in.) 1/2 1/2 1/2 -

Length 74.1 74.1


DIMENSIONS (inches) Width 48.9 48.9
Height 40.6 40.6

OPERATING WT. (lbs.) 668 614

Type Scroll Scroll


COMPRESSORS Quantity 1 1
Unit Capacity Steps (%) 100 100

Face area (Sq. Ft.) 21.1 21.1


Rows 1 1
CONDENSER
Fins per inch 23 23
COIL DATA
Tube diameter (in./MM) .79/20 .79/20
Circuitry Type 2-pass Microchannel 2-pass Microchannel

Face area (Sq. Ft.) 7.3 7.3


Rows 4 4
EVAPORATOR Fins per inch 15 15
COIL DATA Tube diameter 0.375 0.375
Circuitry Type Intertwined Intertwined
Refrigerant control TXV TXV

Johnson Controls Ducted Systems 13


5846585-YTG-A-1119

ZZ07 Physical Data (Continued)


Models
Component
ZZG07 ZZE07
Nominal Tonnage 6 6

Quantity of fans 1 1
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1/2 1/2
No. speeds 2 2
RPM 900 / 1150 900 / 1150
Nominal total CFM 3600 / 4600 3600 / 4600

Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
BELT DRIVE Blower Sheave AK51 AK51 AK51 AK51 AK51 AK51
Belt A39 A40 A41 A39 A40 A41
Motor Max Bhp, 3 Phase 2.4 2.9 3.7 2.4 2.9 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ

FILTERS Quantity - Size 4 - (16 x 16 x 2)1 4 - (16 x 16 x 2)1

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

14 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ08 Physical Data


Models
Component
ZZG08 ZZE08
Nominal Tonnage 7.5 7.5

Gross Capacity @ AHRI A Point (BTU) 88420 88420


AHRI net Capacity (Btu) 85241 85241
EER 10.4 10.6
Nominal CFM 2309 2309
AHRI COOLING
System Power (KW) 8.43 8.43
PERFORMANCE
Refrigerant type R-410A R-410A
Refrigerant charge (lb-oz)
System 1 6-12 6-12
System 2 - -

Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) - - 100 -
2nd. Stage Heat input (K Btu) 70 114 145 -
1st. Stage Heat output (K Btu) - - 80 -
2nd. Stage Heat output (K Btu) 56 91 116 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady State Efficiency (%) 80 80 80 -
No. burners 2 3 3 -
No. stages 1 1 2 -
Temperature Rise Range ( ͦF) 17-29 28-47 36-60 -
Gas Limit Setting ( ͦF) 150 140 140 -
Gas piping connection (in.) 1/2 1/2 1/2 -

Length 74.1 74.1


Dimensions (inches) Width 48.9 48.9
Height 40.6 40.6

OPERATING WT. (lbs.) 666 612

Type Scroll Scroll


COMPRESSORS Quantity 1 1
Unit Capacity Step (%) 100 100

Face area (Sq. Ft.) 21.1 21.1


Rows 1 1
CONDENSER
Fins per inch 23 23
COIL DATA
Tube diameter (in./MM) .79/20 .79/20
Circuit Type 2-pass Microchannel 2-pass Microchannel

Face area (Sq. Ft.) 7.3 7.3


Rows 4 4
EVAPORATOR COIL Fins per inch 15 15
DATA Tube diameter 0.375 0.375
Circuit Type Intertwined Intertwined
Refrigerant control TXV TXV

Johnson Controls Ducted Systems 15


5846585-YTG-A-1119

ZZ08 Physical Data


Models
Component
ZZG08 ZZE08
Nominal Tonnage 7.5 7.5

Quantity of fans 1 1
fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1150 1150
Nominal total CFM 4600 4600

Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan size (inch) 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10 11 x 10
Type Centrifugal Centrifugal
EVAPORATOR DAN Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
DATA BELT DRIVE Blower Sheave AK51 AK51 AK51 AK51 AK51 AK51
Belt A39 A40 A41 A39 A40 A41
Motor Max Bhp, 3 Phase 2.4 2.9 3.7 2.4 2.9 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ

FILTERS Quantity-Size 4 - (16 x 16 x 12)1 4 - (16 x 16 x 12)¹

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

16 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ09 Physical Data


Models
Component
ZZG09 ZZE09
Nominal Tonnage 8.5 8.5

Gross Capacity @ AHRI A point (Btu) 105600 105600


AHRI net capacity (Btu) 99000 99000
EER 11 11.2
Nominal CFM 3300 3300
AHRI COOLING
System power (KW) 7.70 7.70
PERFORMANCE
Refrigerant type R-410A R-410A
Refrigerant charge (lb-oz)
System 1 5-4 5-4
System 2 5-4 5-4

Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 90 125 176 -
2nd. Stage Heat input (K Btu) 125 180 220 -
1st. Stage Heat output (K Btu) 72 100 141 -
2nd. Stage Heat output (K Btu) 100 144 176 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 3 4 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 22-36 31-52 38-64 -
Gas Limit Setting (ºF) 140 150 140 -
Gas piping connection (in.) 3/4 3/4 3/4 -

Length 87.2 87.2


DIMENSIONS (inches) Width 61.7 61.7
Height 48.6 48.6

OPERATING WT. (lbs.) 954 852

Type Scroll Scroll


COMPRESSORS Quantity 2 2
Unit Capacity Steps (%) 50/100 50/100

Face area (Sq. Ft.) 25.5 25.5


Rows 1 1
CONDENSER
Fins per inch 23 23
COIL DATA
Tube diameter (in./MM) 1/25 1/25
Circuitry Type 2-pass Microchannel 2-pass Microchannel

Face area (Sq. Ft.) 11.1 11.1


Rows 3 3
EVAPORATOR Fins per inch 15 15
COIL DATA Tube diameter 0.375 0.375
Circuitry Type Intertwined Intertwined
Refrigerant control Orifice Orifice

Johnson Controls Ducted Systems 17


5846585-YTG-A-1119

ZZ09 Physical Data (Continued)


Models
Component
ZZG09 ZZE09
Nominal Tonnage 8.5 8.5

Quantity of fans 2 2
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 2 2
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1085 1085
Nominal total CFM 8600 8600

Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL34 1VL44 1VP50 1VL34 1VL44 1VP50
BELT DRIVE Blower Sheave AK74 AK74 AK74 AK74 AK74 AK74
Belt A47 A48 A50 A47 A48 A50
Motor Max Bhp, 3 Phase 2.4 2.4 3.7 2.4 2.4 3.7
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56Y 56HZ 56Y 56Y 56HZ

FILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

18 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ12 Physical Data


Models
Component
ZZG12 ZZE12
Nominal Tonnage 10 10

Gross Capacity @ AHRI A point (Btu) 125600 125600


AHRI net capacity (Btu) 116000 116000
EER 11 11.2
Nominal CFM 3400 3400
AHRI COOLING
System power (KW) 9.2 9.2
PERFORMANCE
Refrigerant type R-410A R-410A
Refrigerant charge (lb-oz)
System 1 5-12 5-12
System 2 5-12 5-12

Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 125 176 200 -
2nd. Stage Heat input (K Btu) 180 220 250 -
1st. Stage Heat output (K Btu) 100 141 160 -
2nd. Stage Heat output (K Btu) 144 176 200 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 4 5 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 27-44 33-54 37-62 -
Gas Limit Setting (ºF) 150 140 160 -
Gas piping connection (in.) 3/4 3/4 3/4 -

Length 87.2 87.2


DIMENSIONS (inches) Width 61.7 61.7
Height 48.6 48.6

OPERATING WT. (lbs.) 985 879

Type Scroll Scroll


COMPRESSORS Quantity 2 2
Unit Capacity Steps (%) 50/100 50/100

Face area (Sq. Ft.) 25.5 25.5


Rows 1 1
CONDENSER
Fins per inch 23 23
COIL DATA
Tube diameter (in./MM) 1/25 1/25
Circuitry Type 2-pass Microchannel 2-pass Microchannel

Face area (Sq. Ft.) 11.1 11.1


Rows 4 4
EVAPORATOR Fins per inch 15 15
COIL DATA Tube diameter 0.375 0.375
Circuitry Type Intertwined Intertwined
Refrigerant control Orifice Orifice

Johnson Controls Ducted Systems 19


5846585-YTG-A-1119

ZZ12 Physical Data (Continued)


Models
Component
ZZG12 ZZE12
Nominal Tonnage 10 10

Quantity of fans 2 2
Fan diameter (Inch) 22 22
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 2 2
FAN DATA
Motor HP each 1/2 1/2
No. speeds 1 1
RPM 1085 1085
Nominal total CFM 8600 8600

Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56
BELT DRIVE Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85
Belt A50 A50 BX52 A50 A50 BX52
Motor Max Bhp, 3 Phase 2.4 3.7 5.25 2.4 3.7 5.25
RPM 1725 1725 1725 1725 1725 1725
Frame size 56Y 56HZ 145TY 56Y 56HZ 145TY

FILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

20 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ14 Physical Data


Models
Component
ZZG14 ZZE14
Nominal Tonnage 12.5 12.5

Gross Capacity @ AHRI A point (Btu) 145000 145000


AHRI net capacity (Btu) 135000 135000
EER 10.8 11.0
Nominal CFM 4000 4000
AHRI COOLING
System power (KW) 10.8 10.8
PERFORMANCE
Refrigerant type R-410A R-410A
Refrigerant charge (lb-oz)
System 1 6-8 6-8
System 2 6-12 6-12

Heating Option D E F -
Heating model Low Med High -
1st. Stage Heat input (K Btu) 125 176 200 -
2nd. Stage Heat input (K Btu) 180 220 250 -
1st. Stage Heat output (K Btu) 100 141 160 -
2nd. Stage Heat output (K Btu) 144 176 200 -
AHRI HEATING
AFUE % -
PERFORMANCE
Steady state efficiency (%) 80 80 80 -
No. burners 4 5 5 -
No. stages 2 2 2 -
Temperature Rise Range (ºF) 21-36 26-43 30-49 -
Gas Limit Setting (ºF) 150 140 160 -
Gas piping connection (in.) 3/4 3/4 3/4 -

Length 87.2 87.2


DIMENSIONS (inches) Width 61.7 61.7
Height 55.26 55.26

OPERATING WT. (lbs.) 1047 941

Type Scroll Scroll


COMPRESSORS Quantity 2 2
Unit Capacity Steps (%) 50/100 50/100

Face area (Sq. Ft.) 24.9 24.9


Rows 1 1
CONDENSER
Fins per inch 21 21
COIL DATA
Tube diameter (in./MM) 1.26/32 1.26/32
Circuitry Type 2-pass Microchannel 2-pass Microchannel

Face area (Sq. Ft.) 11.1 11.1


Rows 4 4
EVAPORATOR Fins per inch 15 15
COIL DATA Tube diameter 0.375 0.375
Circuitry Type Intertwined Intertwined
Refrigerant control TXV TXV

Johnson Controls Ducted Systems 21


5846585-YTG-A-1119

ZZ14 Physical Data (Continued)


Models
Component
ZZG14 ZZE14
Nominal Tonnage 12.5 12.5

Quantity of fans 1 1
Fan diameter (Inch) 30 30
Type Prop Prop
Drive type Direct Direct
CONDENSER
Quantity of motors 1 1
FAN DATA
Motor HP each 1 1/2 1 1/2
No. speeds 1 1
RPM 1140 1140
Nominal total CFM 10600 10600

Airflow Option A B C A B C
Quantity 1 1 1 1 1 1
Fan Size (Inch) 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15 15 x 15
Type Centrifugal Centrifugal
EVAP FAN DATA Motor Sheave 1VL44 1VP50 1VP56 1VL44 1VP50 1VP56
BELT DRIVE Blower Sheave AK79 AK79 BK85 AK79 AK79 BK85
Belt A50 A52 BX54 A50 A52 BX54
Motor Max Bhp, 3 Phase 2.9 3.7 5.25 2.9 3.7 5.25
RPM 1750 1750 1750 1750 1750 1750
Frame size 56Z 184TZ 184TZ 56Z 184TZ 184TZ

FILTERS Quantity - Size 4 - (20 x 20 x 2)1 4 - (20 x 20 x 2)1

1. 2 in. Throwaway, Standard, MERV 4 (Minimum Efficiency Reporting Value).

ZZ 07-14 Unit Limitations


Unit Limitations
Size
Model Unit Voltage SCCR (kVA) Applied Voltage Outdoor DB Temp
(Tons)
Min Max Max (°F)
208/230-3-60 5 187 252 125
ZZ 07 (6)
460-3-60 5 432 504 125
208/230-3-60 5 187 252 125
ZZ 08 (7.5)
460-3-60 5 432 504 125
208/230-3-60 5 187 252 125
ZZ 09 (8.5)
460-3-60 5 432 504 125
208/230-3-60 5 187 252 125
ZZ 12 (10)
460-3-60 5 432 504 125
208/230-3-60 5 187 252 125
ZZ 14 (12.5)
460-3-60 5 432 504 125

22 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Capacity Performance
ZZ07-14 Cooling Capacities

ZZ07 (6 Ton)
Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 89.8 4.1 45.1 37.4 29.8 - - - 84.7 4.6 41.2 34.3 27.5 - - -
72 82.1 4.0 55.6 47.1 38.5 30.0 - - 76.7 4.5 52.7 44.4 36.1 27.9 - -
1500
67 74.3 3.9 66.1 56.7 47.3 38.1 30.4 - 68.8 4.4 64.2 54.5 44.8 36.2 28.4 -
62 74.4 3.9 72.9 63.5 56.0 45.6 39.4 31.1 70.8 4.4 68.1 60.3 53.5 44.3 37.2 29.0
77 91.0 4.1 51.6 40.8 29.9 - - - 85.5 4.6 48.6 38.0 27.4 - - -
72 84.1 4.0 59.7 50.0 40.3 30.5 - - 78.8 4.5 57.1 47.5 37.8 28.2 - -
1800 67 77.2 4.0 67.8 59.2 50.6 40.3 31.1 - 72.1 4.5 65.5 56.9 48.3 38.3 28.9 -
62 74.7 4.0 73.8 67.4 60.9 49.4 41.3 31.5 71.2 4.5 69.9 64.3 58.7 48.0 39.1 29.3
57 60.7 3.9 60.7 60.7 60.7 60.7 51.6 41.7 59.4 4.5 59.4 59.4 59.4 59.2 49.3 39.5
77 92.2 4.1 58.1 44.1 30.1 - - - 86.4 4.6 56.0 41.7 27.4 - - -
72 86.2 4.1 63.9 52.9 42.0 31.1 - - 80.9 4.6 61.5 50.5 39.5 28.6 - -
2100 67 80.1 4.0 69.6 61.8 54.0 42.4 31.7 - 75.4 4.5 66.9 59.3 51.7 40.3 29.3 -
62 75.1 4.0 74.6 71.2 65.9 53.3 43.2 31.9 71.6 4.5 71.6 68.3 63.8 51.8 41.1 29.7
57 61.4 4.0 61.4 61.4 61.4 61.4 54.7 43.2 59.6 4.5 59.6 59.6 59.6 59.6 52.8 41.2
77 93.4 4.1 64.7 47.5 30.3 - - - 87.2 4.6 63.5 45.4 27.4 - - -
72 88.2 4.1 68.0 55.9 43.8 31.7 - - 83.0 4.6 65.9 53.5 41.2 28.9 - -
2400 67 83.0 4.0 71.3 64.3 57.3 44.5 32.3 - 78.7 4.5 68.2 61.7 55.1 42.3 29.8 -
62 75.4 4.0 75.4 75.1 70.8 57.1 45.1 32.3 72.0 4.5 72.0 72.0 69.0 55.6 43.0 30.0
57 62.1 4.0 62.1 62.1 62.1 62.1 57.9 44.7 59.7 4.5 59.7 59.7 59.7 59.7 56.2 42.8
72 90.2 4.1 72.1 58.8 45.5 32.3 - - 85.1 4.6 70.3 56.6 42.9 29.3 - -
67 85.9 4.0 73.1 66.8 60.6 46.7 33.0 - 82.1 4.6 69.6 64.1 58.6 44.4 30.3 -
2700
62 75.8 4.0 75.8 75.8 75.7 61.0 47.0 32.7 72.3 4.6 72.3 72.3 72.3 59.4 45.0 30.4
57 62.8 4.1 62.8 62.8 62.8 62.8 61.0 46.1 59.9 4.6 59.9 59.9 59.9 59.9 59.6 44.5
72 92.3 4.1 76.2 61.8 47.3 32.8 - - 87.2 4.6 74.7 59.6 44.6 29.6 - -
67 88.8 4.1 74.8 69.4 64.0 48.8 33.6 - 85.4 4.6 71.0 66.5 62.0 46.4 30.8 -
3000
62 76.2 4.1 76.2 76.2 76.2 64.8 48.9 33.0 72.7 4.6 72.7 72.7 72.7 63.1 46.9 30.7
57 63.5 4.1 63.5 63.5 63.5 63.5 63.5 47.6 60.0 4.6 60.0 60.0 60.0 60.0 60.0 46.2
95°F 105°F
77 79.5 5.1 37.2 31.2 25.1 - - - 76.5 5.8 35.3 29.1 23.0 - - -
72 71.4 5.0 49.7 41.7 33.8 25.8 - - 67.1 5.7 47.4 39.5 31.6 23.6 - -
1500
67 63.2 4.9 62.2 52.3 42.4 34.4 26.4 - 57.7 5.7 57.7 49.9 40.2 32.1 24.1 -
62 67.3 4.9 63.3 57.2 51.0 43.0 34.9 26.8 63.8 5.7 59.9 54.3 48.7 40.6 32.4 24.3
77 80.0 5.1 45.6 35.2 24.9 - - - 75.3 5.8 43.6 33.2 22.7 - - -
72 73.5 5.0 54.4 44.9 35.4 25.9 - - 68.5 5.8 52.0 42.5 33.1 23.7 - -
1800 67 67.0 5.0 63.2 54.6 45.9 36.3 26.7 - 61.6 5.7 60.3 51.9 43.5 33.9 24.4 -
62 67.7 5.0 66.1 61.3 56.4 46.7 36.9 27.1 64.0 5.7 62.4 58.2 53.9 44.2 34.5 24.7
57 58.2 5.0 58.2 58.2 58.2 57.0 47.1 37.2 59.6 5.7 59.6 59.6 59.6 54.4 44.5 34.6
77 80.5 5.1 53.9 39.3 24.7 - - - 74.2 5.8 52.0 37.2 22.5 - - -
72 75.6 5.1 59.1 48.1 37.1 26.1 - - 69.8 5.8 56.5 45.6 34.7 23.8 - -
2100 67 70.7 5.0 64.2 56.8 49.4 38.2 27.0 - 65.4 5.7 61.0 54.0 46.9 35.8 24.7 -
62 68.1 5.0 68.1 65.4 61.8 50.4 38.9 27.4 64.3 5.7 64.3 62.0 59.1 47.8 36.5 25.1
57 57.8 5.0 57.8 57.8 57.8 57.8 50.8 39.1 58.0 5.7 58.0 58.0 58.0 58.0 47.6 35.7
77 81.1 5.1 62.3 43.4 24.4 - - - 73.0 5.8 60.3 41.3 22.2 - - -
72 77.8 5.1 63.7 51.2 38.7 26.2 - - 71.2 5.8 61.0 48.6 36.2 23.9 - -
2400 67 74.5 5.0 65.2 59.1 53.0 40.1 27.3 - 69.3 5.8 61.7 56.0 50.3 37.6 25.0 -
62 68.5 5.0 68.5 68.5 67.2 54.1 40.9 27.7 64.5 5.7 64.5 64.5 64.3 51.4 38.5 25.6
57 57.4 5.0 57.4 57.4 57.4 57.4 54.5 41.0 56.4 5.7 56.4 56.4 56.4 56.4 50.6 36.7
72 79.9 5.1 68.4 54.4 40.3 26.3 - - 72.5 5.8 65.5 51.7 37.8 23.9 - -
67 78.2 5.1 66.1 61.3 56.5 42.0 27.6 - 73.2 5.8 62.4 58.0 53.6 39.5 25.3 -
2700
62 68.9 5.1 68.9 68.9 68.9 57.8 42.9 28.0 64.8 5.8 64.8 64.8 64.8 55.0 40.5 26.0
57 57.0 5.1 57.0 57.0 57.0 57.0 57.0 42.9 54.7 5.8 54.7 54.7 54.7 54.7 53.6 37.8
72 82.0 5.1 73.1 57.5 42.0 26.4 - - 73.8 5.8 70.1 54.7 39.4 24.0 - -
67 81.9 5.1 67.1 63.5 60.0 43.9 27.9 - 77.0 5.8 63.1 60.1 57.0 41.3 25.6 -
3000
62 69.3 5.1 69.3 69.3 69.3 61.5 44.9 28.4 65.0 5.8 65.0 65.0 65.0 58.6 42.5 26.5
57 56.6 5.1 56.6 56.6 56.6 56.6 56.6 44.9 53.1 5.8 53.1 53.1 53.1 53.1 53.1 38.8

Johnson Controls Ducted Systems 23


5846585-YTG-A-1119

ZZ07 (6 Ton) (Continued)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 73.4 6.5 33.3 27.1 20.8 - - - 70.4 7.2 31.4 25.0 18.6 - - -
72 62.9 6.5 45.2 37.3 29.4 21.5 - - 58.6 7.2 42.9 35.0 27.2 19.3 - -
1500
67 52.3 6.4 52.3 47.4 37.9 29.8 21.8 - 46.8 7.2 46.8 45.0 35.7 27.6 19.5 -
62 60.3 6.4 56.4 51.5 46.5 38.2 30.0 21.7 56.8 7.1 53.0 48.6 44.2 35.9 27.5 19.2
77 70.6 6.5 41.7 31.1 20.6 - - - 65.9 7.2 39.7 29.0 18.4 - - -
72 63.4 6.5 49.5 40.2 30.8 21.5 - - 58.4 7.2 47.1 37.8 28.6 19.3 - -
1800 67 56.2 6.5 56.2 49.3 41.1 31.6 22.1 - 50.9 7.2 50.9 46.6 38.7 29.3 19.8 -
62 60.4 6.4 58.7 55.0 51.4 41.7 32.0 22.3 56.7 7.1 54.9 51.9 48.9 39.2 29.6 19.9
57 61.1 6.4 59.9 59.9 59.9 51.8 41.9 32.0 62.6 7.1 55.3 55.3 55.3 49.2 39.3 29.5
77 67.8 6.5 50.0 35.1 20.3 - - - 61.4 7.2 48.0 33.0 18.1 - - -
72 64.0 6.5 53.9 43.1 32.3 21.5 - - 58.2 7.2 51.3 40.6 30.0 19.3 - -
2100 67 60.2 6.5 57.9 51.1 44.3 33.4 22.4 - 54.9 7.2 54.7 48.2 41.8 30.9 20.1 -
62 60.5 6.4 60.5 58.6 56.4 45.2 34.0 22.9 56.7 7.2 56.7 55.2 53.6 42.6 31.6 20.6
57 58.2 6.4 58.2 58.2 58.2 56.3 44.3 32.2 58.5 7.1 58.5 58.5 58.5 53.3 41.0 28.8
77 64.9 6.5 58.3 39.2 20.0 - - - 56.9 7.2 56.3 37.0 17.8 - - -
72 64.5 6.5 58.3 46.0 33.8 21.6 - - 57.9 7.2 55.6 43.5 31.4 19.2 - -
2400 67 64.1 6.5 58.3 52.9 47.6 35.1 22.7 - 59.0 7.2 54.9 49.9 44.9 32.6 20.4 -
62 60.6 6.5 60.6 60.6 60.6 48.7 36.1 23.4 56.7 7.2 56.7 56.7 56.7 46.0 33.6 21.3
57 55.3 6.4 55.3 55.3 55.3 55.3 46.6 32.4 54.3 7.1 54.3 54.3 54.3 54.3 42.7 28.1
72 65.1 6.5 62.7 49.0 35.3 21.6 - - 57.7 7.2 57.7 46.3 32.8 19.2 - -
67 68.1 6.5 58.7 54.8 50.8 36.9 23.0 - 63.1 7.2 55.1 51.5 47.9 34.3 20.7 -
2700
62 60.7 6.5 60.7 60.7 60.7 52.2 38.1 24.0 56.6 7.2 56.6 56.6 56.6 49.4 35.7 22.0
57 52.5 6.5 52.5 52.5 52.5 52.5 49.0 32.6 50.2 7.2 50.2 50.2 50.2 50.2 44.4 27.4
72 65.7 6.5 65.7 51.9 36.8 21.6 - - 57.5 7.2 57.5 49.1 34.1 19.2 - -
67 72.1 6.5 59.2 56.6 54.0 38.6 23.3 - 67.1 7.2 55.2 53.1 51.0 36.0 21.0 -
3000
62 60.8 6.5 60.8 60.8 60.8 55.7 40.1 24.6 56.6 7.2 56.6 56.6 56.6 52.8 37.7 22.7
57 49.6 6.5 49.6 49.6 49.6 49.6 49.6 32.8 46.1 7.2 46.1 46.1 46.1 46.1 46.1 26.8

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

24 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ08 (7.5 Ton)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 116.5 6.4 60.6 53.3 46.0 - - - 110.6 7.2 62.1 51.7 44.0 - - -
72 108.2 6.2 71.7 63.8 55.8 47.9 - - 102.5 7.0 69.8 61.6 53.4 45.3 - -
2250 67 99.9 6.1 82.8 74.2 65.6 57.1 40.8 - 94.4 6.8 77.5 71.6 62.9 54.2 38.2 -
62 92.9 5.9 84.2 84.2 74.7 65.1 53.4 46.0 87.7 6.6 80.0 79.9 70.3 60.6 50.7 41.4
57 85.9 5.7 85.6 85.6 83.7 73.2 66.0 47.4 81.0 6.5 80.8 80.8 77.7 67.1 63.1 42.3
77 119.0 6.5 64.1 56.3 48.5 - - - 112.9 7.3 66.8 55.5 46.0 - - -
72 110.7 6.3 76.0 67.5 59.0 50.5 - - 104.7 7.1 74.0 64.9 56.1 47.4 - -
2625 67 102.3 6.1 88.0 78.8 69.6 60.4 41.2 - 96.4 6.9 81.3 74.4 66.3 56.2 38.4 -
62 96.7 6.0 89.7 89.4 79.2 68.9 56.1 48.4 90.0 6.7 83.2 82.3 73.3 63.0 53.3 40.7
57 91.0 5.8 90.8 90.8 88.7 77.4 70.9 49.7 84.1 6.6 83.9 83.2 80.4 69.7 65.6 41.6
77 121.6 6.6 67.5 59.2 50.9 - - - 115.2 7.3 71.5 59.2 48.1 - - -
72 113.2 6.4 80.4 71.3 62.2 53.2 - - 106.8 7.1 78.1 68.2 58.9 49.5 - -
3000 67 104.7 6.2 93.2 83.4 73.6 63.7 41.6 - 98.4 6.9 85.0 77.2 69.6 58.3 38.7 -
62 100.4 6.1 95.2 94.6 83.7 72.7 58.7 50.7 92.2 6.8 86.4 84.6 76.4 65.3 56.0 40.1
57 96.2 6.0 96.0 96.0 93.8 81.6 75.8 52.1 87.2 6.8 87.1 85.5 83.1 72.3 68.1 41.0
72 115.6 6.4 84.7 75.1 65.4 55.8 - - 109.0 7.2 80.2 71.5 61.6 51.6 - -
67 107.2 6.3 98.4 87.9 77.5 67.1 42.0 - 100.5 7.0 87.9 80.0 73.0 60.4 38.9 -
3375
62 104.2 6.2 100.6 99.9 88.2 76.5 61.4 53.1 94.5 6.9 89.6 87.0 79.4 67.6 58.6 39.5
57 101.3 6.1 101.3 101.3 96.2 85.9 80.7 54.4 90.3 6.9 90.3 87.9 84.4 74.8 70.7 40.4
72 118.1 6.5 89.0 78.8 68.7 58.5 - - 111.2 7.2 82.3 74.8 64.3 53.7 - -
67 109.6 6.3 103.6 92.5 81.5 70.4 42.4 - 102.5 7.0 90.9 82.9 76.4 62.5 39.1 -
3750
62 108.0 6.3 106.1 105.1 92.7 80.3 64.0 55.5 96.8 7.0 92.8 89.3 82.4 69.9 61.3 38.9
57 106.4 6.2 106.4 106.4 103.9 90.1 85.6 56.7 93.4 7.0 93.4 90.2 88.5 77.4 73.2 39.8
95°F 105°F
77 104.7 8.1 63.6 50.1 42.1 - - - 98.0 9.0 59.9 47.6 39.5 - - -
72 96.8 7.8 67.9 59.5 51.1 42.7 - - 90.1 8.7 65.2 56.7 48.3 39.8 - -
2250 67 88.8 7.5 72.2 68.9 60.1 51.3 35.6 - 82.1 8.4 70.4 65.8 57.1 48.3 32.6 -
62 82.4 7.4 75.8 75.6 65.9 56.1 47.9 36.7 77.6 8.4 72.9 72.8 63.5 54.2 45.1 35.5
57 76.0 7.3 76.0 76.0 71.7 61.0 60.2 37.1 73.2 8.3 73.2 73.2 69.9 60.1 57.5 35.9
77 106.8 8.1 69.5 54.7 43.6 - - - 98.5 9.0 64.4 51.9 40.5 - - -
72 98.6 7.8 71.9 62.3 53.3 44.2 - - 91.6 8.8 67.9 59.2 50.0 40.8 - -
2625 67 90.5 7.6 74.5 70.0 62.9 52.1 35.6 - 83.7 8.5 71.5 66.5 59.6 49.2 32.3 -
62 83.2 7.5 76.7 75.1 67.5 57.0 50.6 33.1 78.1 8.4 73.2 71.9 64.6 54.5 45.5 31.2
57 77.1 7.4 77.1 75.5 72.0 61.9 60.3 33.5 73.7 8.4 73.7 72.3 69.6 59.9 55.2 31.6
77 108.9 8.1 75.4 59.2 45.2 - - - 98.9 8.9 68.9 56.3 41.4 - - -
72 100.5 7.9 75.9 65.1 55.5 45.8 - - 93.2 8.8 70.7 61.7 51.7 41.8 - -
3000 67 92.1 7.6 76.8 71.0 65.7 52.9 35.7 - 85.2 8.6 72.7 67.2 62.1 50.0 32.0 -
62 84.0 7.6 77.6 74.6 69.0 57.9 53.2 29.5 78.5 8.5 73.5 71.0 65.7 54.9 45.8 26.9
57 78.2 7.5 78.2 75.0 72.3 62.9 60.4 29.9 74.2 8.4 74.2 71.4 69.3 59.7 52.9 27.3
72 102.4 7.9 75.8 68.0 57.7 47.4 - - 94.8 8.9 70.7 64.3 53.5 42.7 - -
67 93.8 7.7 77.5 72.1 68.6 53.7 35.8 - 86.7 8.6 72.8 67.9 64.6 50.9 31.6 -
3375
62 84.8 7.7 78.5 74.1 70.6 58.7 55.9 25.9 79.0 8.5 73.8 70.0 66.8 55.2 46.2 22.5
57 79.3 7.7 79.3 74.6 72.7 63.8 60.6 26.4 74.7 8.5 74.7 70.6 69.0 59.6 50.6 23.1
72 104.2 8.0 75.6 70.8 59.9 48.9 - - 96.3 8.9 70.7 66.8 55.2 43.7 - -
67 95.4 7.8 78.2 73.2 71.4 54.5 35.9 - 88.2 8.7 72.9 68.6 67.1 51.8 31.3 -
3750
62 85.6 7.8 79.4 73.6 72.2 59.6 58.6 22.3 79.4 8.6 74.1 69.1 67.9 55.6 46.5 18.2
57 80.4 7.8 80.4 74.1 73.0 64.7 60.7 22.8 75.2 8.5 75.2 69.7 68.7 59.4 48.2 18.8

Johnson Controls Ducted Systems 25


5846585-YTG-A-1119

ZZ08 (7.5 Ton) (Continued)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 91.3 10.0 56.3 45.1 36.9 - - - 84.6 11.0 52.6 42.6 34.3 - - -
72 83.4 9.7 62.4 53.9 45.5 37.0 - - 76.6 10.7 59.6 51.1 42.7 34.2 - -
2250 67 75.4 9.4 68.5 62.7 54.0 45.3 29.7 - 68.7 10.3 66.7 59.7 51.0 42.3 26.8 -
62 72.9 9.3 70.1 70.0 61.1 52.2 42.3 34.4 68.1 10.3 67.2 67.2 58.7 50.2 39.5 33.2
57 70.3 9.3 70.3 70.3 68.2 59.1 54.9 34.7 67.5 10.3 67.5 67.5 66.4 58.1 52.3 33.5
77 90.1 9.9 59.4 49.2 37.3 - - - 81.8 10.7 54.3 46.5 34.1 - - -
72 84.6 9.7 63.9 56.1 46.7 37.4 - - 77.6 10.7 59.9 53.0 43.5 33.9 - -
2625 67 76.8 9.4 68.6 63.0 56.2 46.2 29.0 - 70.0 10.4 65.6 59.6 52.8 43.3 25.7 -
62 73.0 9.4 69.7 68.7 61.7 52.0 40.4 29.3 67.9 10.3 66.3 65.4 58.8 49.6 35.3 27.4
57 70.2 9.3 70.2 69.1 67.2 57.9 50.1 29.7 66.8 10.2 66.8 65.8 64.8 55.8 45.0 27.8
77 89.0 9.7 62.5 53.3 37.7 - - - 79.0 10.5 56.0 50.4 33.9 - - -
72 85.9 9.8 65.4 58.3 48.0 37.7 - - 78.6 10.7 60.2 54.9 44.3 33.7 - -
3000 67 78.2 9.5 68.6 63.3 58.4 47.2 28.2 - 71.3 10.4 64.5 59.5 54.7 44.3 24.5 -
62 73.1 9.4 69.4 67.3 62.3 51.9 38.4 24.2 67.6 10.3 65.3 63.7 59.0 48.9 31.0 21.6
57 70.1 9.3 70.1 67.8 66.3 56.6 45.3 24.7 66.1 10.1 66.1 64.2 63.2 53.5 37.8 22.1
72 87.2 9.8 65.6 60.5 49.3 38.1 - - 79.6 10.7 60.5 56.8 45.1 33.5 - -
67 79.6 9.5 68.1 63.6 60.6 48.1 27.5 - 72.5 10.5 63.3 59.4 56.5 45.3 23.4 -
3375
62 73.2 9.4 69.1 66.0 62.9 51.7 36.5 19.1 67.3 10.3 64.4 61.9 59.1 48.3 26.7 15.8
57 70.0 9.3 70.0 66.6 65.3 55.4 40.5 19.7 65.4 10.1 65.4 62.5 61.6 51.2 30.5 16.4
72 88.4 9.8 65.7 62.7 50.6 38.5 - - 80.5 10.7 60.8 58.7 46.0 33.2 - -
67 81.0 9.6 67.5 63.9 62.7 49.0 26.8 - 73.8 10.5 62.2 59.3 58.4 46.3 22.2 -
3750
62 73.3 9.4 68.7 64.6 63.5 51.6 34.5 14.1 67.1 10.3 63.4 60.1 59.2 47.6 22.5 9.9
57 69.9 9.3 69.9 65.3 64.3 54.2 35.7 14.8 64.7 10.0 64.7 60.9 60.0 48.9 23.3 10.7

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

26 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ09 (8.5 Ton)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 126.8 6.3 67.0 53.9 40.8 - - - 121.9 7.0 65.6 53.5 41.3 - - -
72 118.4 6.2 80.7 68.2 55.7 43.3 - - 113.1 6.9 78.8 66.5 54.3 42.0 - -
2125
67 109.9 6.1 94.4 82.5 70.7 56.6 44.6 - 104.2 6.8 91.9 79.6 67.3 54.3 42.4 -
62 104.0 6.0 103.0 94.3 85.6 67.8 58.4 44.7 97.7 6.7 97.3 88.7 80.2 65.6 55.0 42.4
77 126.8 6.4 71.8 56.6 41.4 - - - 121.5 7.1 70.8 55.9 41.1 - - -
72 119.2 6.2 85.4 71.5 57.6 43.7 - - 113.9 7.0 83.5 69.8 56.1 42.4 - -
2550 67 111.7 6.1 98.9 86.4 73.8 58.6 45.2 - 106.4 6.9 96.3 83.7 71.2 56.8 43.3 -
62 106.9 6.0 106.1 98.0 90.0 72.0 60.6 45.9 101.1 6.8 100.7 93.5 86.2 70.4 57.9 43.7
57 106.2 5.9 106.2 106.2 106.2 91.1 76.0 60.9 100.8 6.7 100.8 100.8 100.8 86.9 72.4 58.0
77 126.7 6.4 76.6 59.3 42.0 - - - 121.1 7.1 75.9 58.4 40.8 - - -
72 120.1 6.3 90.0 74.7 59.4 44.1 - - 114.8 7.0 88.3 73.1 58.0 42.8 - -
2975 67 113.4 6.2 103.5 90.2 76.9 60.7 45.9 - 108.5 6.9 100.6 87.9 75.1 59.3 44.2 -
62 109.8 6.1 109.2 101.8 94.4 76.1 62.9 47.1 104.6 6.8 104.2 98.2 92.3 75.2 60.7 44.9
57 109.3 6.0 109.3 109.3 109.3 95.9 79.9 63.9 104.3 6.8 104.3 104.3 104.3 93.3 77.2 61.1
77 126.7 6.5 81.3 61.9 42.5 - - - 120.6 7.2 81.1 60.8 40.6 - - -
72 120.9 6.3 94.7 78.0 61.3 44.6 - - 115.6 7.1 93.0 76.4 59.8 43.2 - -
3400 67 115.1 6.2 108.0 94.0 80.0 62.8 46.5 - 110.6 7.0 104.9 92.0 79.0 61.8 45.0 -
62 112.7 6.2 112.3 105.5 98.7 80.3 65.1 48.4 108.0 6.9 107.6 102.9 98.3 80.1 63.5 46.2
57 112.3 6.1 112.3 112.3 112.3 100.6 83.8 66.9 107.8 6.9 107.8 107.8 107.8 99.8 82.0 64.3
72 121.7 6.4 99.3 81.2 63.1 45.0 - - 116.5 7.1 97.8 79.7 61.6 43.6 - -
67 116.8 6.2 112.5 97.8 83.1 64.9 47.2 - 112.8 7.0 109.3 96.1 83.0 64.3 45.9 -
3825
62 115.6 6.2 115.4 109.2 103.1 84.4 67.4 49.6 111.4 7.0 111.1 107.7 104.3 84.9 66.4 47.4
57 115.4 6.2 115.4 115.4 115.4 105.4 87.6 69.9 111.3 7.0 111.3 111.3 111.3 106.2 86.8 67.4
72 122.6 6.4 104.0 84.5 65.0 45.5 - - 117.4 7.2 102.5 83.0 63.5 43.9 - -
67 118.5 6.3 117.0 101.6 86.2 67.0 47.8 - 114.9 7.1 113.6 100.3 86.9 66.8 46.8 -
4250
62 118.5 6.3 118.5 113.0 107.5 88.6 69.7 50.8 114.8 7.1 114.5 112.4 110.3 89.7 69.2 48.6
57 118.5 6.3 118.5 118.5 118.5 110.1 91.5 72.9 114.8 7.1 114.8 114.8 114.8 112.7 91.6 70.5
95°F 105°F
77 117.0 7.7 64.2 53.0 41.8 - - - 108.3 8.8 63.8 51.9 39.9 - - -
72 107.8 7.7 76.8 64.8 52.8 40.8 - - 100.1 8.7 74.7 62.6 50.5 38.3 - -
2125
67 98.5 7.6 89.4 76.6 63.8 52.0 40.3 - 92.0 8.6 85.6 73.3 61.0 49.2 37.3 -
62 91.4 7.5 91.4 83.2 74.8 63.3 51.7 40.2 87.1 8.5 87.1 79.4 71.5 60.0 48.5 36.9
77 116.2 7.8 69.8 55.3 40.7 - - - 109.4 8.8 68.6 53.4 38.2 - - -
72 108.6 7.7 81.7 68.2 54.7 41.1 - - 102.1 8.7 78.9 65.4 51.9 38.4 - -
2550 67 101.1 7.6 93.6 81.1 68.6 55.0 41.4 - 94.8 8.6 89.1 77.4 65.6 52.0 38.3 -
62 95.4 7.5 95.4 88.9 82.5 68.8 55.1 41.4 90.9 8.5 90.6 85.0 79.4 65.6 51.7 37.9
57 95.4 7.4 95.4 95.4 95.4 82.6 68.9 55.1 90.8 8.5 90.8 90.8 90.8 79.1 65.1 51.1
77 115.4 7.8 75.3 57.5 39.6 - - - 110.6 8.8 73.4 54.9 36.4 - - -
72 109.5 7.7 86.6 71.5 56.5 41.5 - - 104.1 8.8 83.1 68.2 53.3 38.5 - -
2975 67 103.6 7.7 97.8 85.5 73.3 57.9 42.5 - 97.6 8.7 92.7 81.5 70.3 54.8 39.3 -
62 99.3 7.6 99.2 94.7 90.2 74.3 58.5 42.7 94.5 8.6 93.9 90.6 87.2 71.1 55.0 38.9
57 99.3 7.5 99.3 99.3 99.3 90.8 74.6 58.4 94.3 8.6 94.3 94.3 94.3 87.5 70.7 54.0
77 114.6 7.9 80.9 59.7 38.6 - - - 111.7 8.9 78.2 56.4 34.6 - - -
72 110.4 7.8 91.4 74.9 58.3 41.8 - - 106.1 8.8 87.2 71.0 54.8 38.6 - -
3400 67 106.2 7.7 101.9 90.0 78.1 60.8 43.6 - 100.4 8.7 96.3 85.6 74.9 57.6 40.3 -
62 103.3 7.7 103.0 100.4 97.8 79.9 61.9 44.0 98.1 8.7 97.2 96.2 95.1 76.7 58.3 39.9
57 103.2 7.6 103.2 103.2 103.2 98.9 80.3 61.6 97.7 8.7 97.7 97.7 97.7 95.8 76.3 56.8
72 111.2 7.8 96.3 78.2 60.1 42.1 - - 108.0 8.8 91.4 73.8 56.2 38.6 - -
67 108.7 7.8 106.1 94.5 82.8 63.7 44.7 - 103.3 8.8 99.8 89.7 79.6 60.5 41.3 -
3825
62 107.2 7.7 106.7 106.1 105.5 85.4 65.3 45.2 101.7 8.8 100.5 100.5 100.5 82.3 61.6 40.9
57 107.2 7.7 107.2 107.2 107.2 107.1 86.0 64.8 101.2 8.8 101.2 101.2 101.2 101.2 81.8 59.6
72 112.1 7.9 101.1 81.6 62.0 42.4 - - 110.0 8.9 95.6 76.6 57.7 38.7 - -
67 111.3 7.8 110.2 98.9 87.6 66.7 45.8 - 106.1 8.9 103.4 93.8 84.2 63.3 42.3 -
4250
62 111.2 7.8 110.5 110.5 110.5 90.9 68.7 46.5 105.4 8.9 103.8 103.8 103.8 87.8 64.9 41.9
57 111.1 7.8 110.8 110.8 110.8 110.8 91.6 68.1 104.6 8.9 104.3 104.3 104.3 104.3 87.4 62.4

Johnson Controls Ducted Systems 27


5846585-YTG-A-1119

ZZ09 (8.5 Ton) (Continued)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 99.6 9.8 63.4 50.7 38.0 - - - 91.0 10.8 63.0 49.6 36.1 - - -
72 92.5 9.6 72.5 60.3 48.1 35.9 - - 84.9 10.6 70.4 58.1 45.7 33.4 - -
2125
67 85.4 9.5 81.7 69.9 58.2 46.3 34.4 - 78.9 10.5 77.8 66.6 55.3 43.4 31.5 -
62 82.9 9.5 82.9 75.6 68.2 56.7 45.2 33.7 78.6 10.5 78.6 71.9 65.0 53.4 41.9 30.4
77 102.7 9.8 67.4 51.5 35.6 - - - 95.9 10.8 66.3 49.6 33.0 - - -
72 95.6 9.7 76.1 62.6 49.2 35.7 - - 89.1 10.7 73.2 59.8 46.4 33.0 - -
2550 67 88.5 9.6 84.7 73.7 62.7 49.0 35.3 - 82.2 10.6 80.2 70.0 59.8 46.0 32.3 -
62 86.5 9.6 85.9 81.1 76.3 62.3 48.3 34.4 82.0 10.6 81.1 77.2 73.2 59.1 45.0 30.8
57 86.3 9.5 86.3 86.3 86.3 75.6 61.4 47.2 81.8 10.6 81.8 81.8 81.8 72.1 57.7 43.2
77 105.7 9.8 71.5 52.3 33.1 - - - 100.9 10.9 69.6 49.7 29.9 - - -
72 98.7 9.8 79.6 64.9 50.2 35.5 - - 93.3 10.8 76.1 61.6 47.1 32.6 - -
2975 67 91.6 9.7 87.6 77.5 67.3 51.7 36.2 - 85.6 10.7 82.6 73.4 64.3 48.6 33.0 -
62 89.7 9.7 88.7 86.5 84.3 67.9 51.5 35.1 84.9 10.7 83.5 82.4 81.4 64.7 48.0 31.3
57 89.2 9.7 89.2 89.2 89.2 84.1 66.8 49.6 84.2 10.7 84.2 84.2 84.2 80.8 63.0 45.2
77 108.8 9.9 75.5 53.1 30.7 - - - 105.9 10.9 72.8 49.8 26.8 - - -
72 101.8 9.8 83.1 67.2 51.3 35.4 - - 97.4 10.8 78.9 63.3 47.7 32.2 - -
3400 67 94.7 9.8 90.6 81.2 71.8 54.4 37.1 - 89.0 10.8 84.9 76.8 68.7 51.3 33.8 -
62 93.0 9.8 91.5 91.5 91.5 73.5 54.7 35.8 87.8 10.8 85.8 85.8 85.8 70.4 51.1 31.7
57 92.2 9.8 92.2 92.2 92.2 92.2 72.3 52.0 86.7 10.8 86.6 86.6 86.6 86.6 68.3 47.1
72 104.8 9.9 86.6 69.4 52.3 35.2 - - 101.6 10.9 81.7 65.1 48.4 31.7 - -
67 97.8 9.8 93.6 85.0 76.4 57.2 37.9 - 92.4 10.9 87.3 80.2 73.2 53.9 34.6 -
3825
62 96.2 9.9 94.3 94.3 94.3 79.1 57.8 36.5 90.8 10.9 88.1 88.1 88.1 76.0 54.1 32.2
57 95.1 9.9 95.1 95.1 95.1 95.1 77.7 54.3 89.1 11.0 89.0 89.0 89.0 89.0 73.6 49.1
72 107.9 9.9 90.1 71.7 53.4 35.0 - - 105.8 10.9 84.6 66.8 49.1 31.3 - -
67 100.9 9.9 96.5 88.7 80.9 59.9 38.8 - 95.8 11.0 89.7 83.7 77.6 56.5 35.4 -
4250
62 99.5 10.0 97.2 97.2 97.2 84.7 61.0 37.3 93.7 11.0 90.5 90.5 90.5 81.6 57.2 32.7
57 98.1 10.0 97.8 97.8 97.8 97.8 83.2 56.7 91.6 11.1 91.3 91.3 91.3 91.3 78.9 51.1

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

28 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ12 (10 Ton)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 154.9 7.6 76.9 65.4 53.8 - - - 145.4 8.9 73.5 62.1 50.6 - - -
72 142.2 7.3 94.0 80.5 67.0 53.5 - - 133.7 8.5 90.5 77.2 63.8 50.4 - -
2500
67 129.5 7.1 111.0 95.5 80.1 66.6 53.2 - 122.1 8.1 107.5 92.2 76.9 63.5 50.1 -
62 124.9 7.0 120.5 106.9 93.3 76.9 66.5 53.1 118.2 8.0 115.9 103.0 90.1 75.2 63.2 49.8
77 156.2 7.6 84.5 68.6 52.7 - - - 149.4 8.5 82.5 66.3 50.2 - - -
72 145.1 7.4 101.3 85.4 69.5 53.6 - - 138.4 8.3 98.6 82.6 66.7 50.8 - -
3000 67 134.1 7.2 118.1 102.2 86.3 70.1 54.1 - 127.4 8.2 114.6 98.9 83.2 67.1 51.1 -
62 130.3 7.1 126.1 114.6 103.0 84.5 70.6 54.3 124.1 8.1 121.5 110.7 99.8 82.4 67.3 51.0
57 126.6 7.1 126.6 126.6 119.8 103.4 87.0 70.6 121.8 8.0 121.8 121.8 116.3 99.9 83.5 67.1
77 157.6 7.6 92.1 71.9 51.6 - - - 153.3 8.1 91.6 70.6 49.7 - - -
72 148.1 7.5 108.7 90.3 72.0 53.7 - - 143.0 8.2 106.6 88.1 69.6 51.1 - -
3500 67 138.6 7.3 125.2 108.8 92.4 73.7 55.0 - 132.7 8.2 121.6 105.6 89.5 70.7 52.0 -
62 135.8 7.2 131.8 122.3 112.8 92.0 74.7 55.6 130.0 8.1 127.2 118.3 109.5 89.5 71.4 52.3
57 132.9 7.2 132.9 132.9 129.6 113.8 94.3 74.8 128.0 8.1 128.0 128.0 127.5 110.1 90.7 71.4
77 158.9 7.7 99.7 75.1 50.5 - - - 157.2 7.7 100.6 74.9 49.2 - - -
72 151.0 7.5 116.0 95.3 74.5 53.8 - - 147.7 8.0 114.6 93.6 72.5 51.4 - -
4000 67 143.2 7.4 132.4 115.5 98.6 77.2 55.9 - 138.1 8.3 128.7 112.2 95.8 74.3 52.9 -
62 141.2 7.3 137.5 130.1 122.6 99.5 78.8 56.8 135.9 8.2 132.9 126.0 119.1 96.7 75.4 53.5
57 139.3 7.3 139.3 139.3 139.3 124.1 101.6 79.1 134.2 8.2 134.2 134.2 134.2 120.2 97.9 75.7
72 154.0 7.6 123.4 100.2 77.1 53.9 - - 152.3 7.8 122.7 99.1 75.4 51.8 - -
67 147.7 7.4 139.5 122.1 104.7 80.8 56.8 - 143.4 8.3 135.7 118.9 102.1 77.9 53.8 -
4500
62 146.7 7.4 143.1 137.8 132.4 107.1 82.9 58.1 141.8 8.3 138.5 133.7 128.8 103.8 79.5 54.8
57 145.7 7.4 145.1 145.1 145.1 134.5 108.9 83.3 140.4 8.3 140.4 140.4 140.4 130.3 105.1 79.9
72 156.9 7.6 130.7 105.2 79.6 54.0 - - 156.9 7.6 130.7 104.5 78.3 52.1 - -
67 152.3 7.5 146.7 128.8 110.9 84.3 57.7 - 148.7 8.4 142.8 125.6 108.4 81.6 54.7 -
5000
62 152.2 7.5 148.8 145.5 142.2 114.6 86.9 59.3 147.7 8.4 144.2 141.3 138.5 111.0 83.5 56.0
57 152.0 7.5 150.9 150.9 150.9 144.9 116.2 87.5 146.6 8.5 145.6 145.6 145.6 140.4 112.3 84.2
95°F 105°F
77 135.9 10.3 70.0 58.7 47.4 - - - 125.3 11.2 67.5 55.9 44.3 - - -
72 125.3 9.7 87.1 73.8 60.6 47.3 - - 117.4 10.7 84.0 70.6 57.1 43.7 - -
2500
67 114.6 9.0 104.1 89.0 73.8 60.4 47.1 - 109.6 10.3 100.5 85.2 70.0 56.5 43.1 -
62 111.5 8.9 111.3 99.1 87.0 73.5 60.0 46.5 106.6 10.1 105.3 94.1 82.8 69.4 56.0 42.5
77 142.5 9.4 80.5 64.1 47.6 - - - 130.8 10.6 77.8 60.8 43.9 - - -
72 131.6 9.3 95.8 79.8 63.9 47.9 - - 122.7 10.5 92.0 76.1 60.1 44.1 - -
3000 67 120.7 9.1 111.1 95.6 80.2 64.1 48.0 - 114.7 10.3 106.3 91.3 76.3 60.2 44.0 -
62 117.9 9.0 116.9 106.7 96.5 80.3 64.0 47.8 112.0 10.2 110.3 101.4 92.6 76.2 59.9 43.6
57 117.0 8.8 117.0 117.0 112.8 96.4 80.1 63.7 110.6 10.1 110.6 110.6 108.8 92.3 75.8 59.3
77 149.0 8.5 91.1 69.4 47.7 - - - 136.3 10.0 88.0 65.7 43.5 - - -
72 137.9 8.9 104.5 85.9 67.2 48.5 - - 128.0 10.2 100.1 81.6 63.1 44.6 - -
3500 67 126.9 9.2 118.0 102.3 86.6 67.8 48.9 - 119.8 10.4 112.1 97.4 82.7 63.8 45.0 -
62 124.2 9.1 122.6 114.3 106.1 87.1 68.0 49.0 117.3 10.3 115.3 108.8 102.3 83.1 63.9 44.6
57 123.1 9.0 123.1 123.1 123.1 106.3 87.1 68.0 115.9 10.2 115.9 115.9 115.9 102.3 82.7 63.1
77 155.6 7.7 101.6 74.7 47.9 - - - 141.8 9.4 98.2 70.7 43.1 - - -
72 144.3 8.4 113.3 91.9 70.5 49.1 - - 133.3 10.0 108.1 87.1 66.1 45.1 - -
4000 67 133.0 9.2 125.0 109.0 93.0 71.5 49.9 - 124.9 10.5 118.0 103.5 89.1 67.5 45.9 -
62 130.5 9.2 128.3 121.9 115.6 93.8 72.1 50.3 122.7 10.4 120.2 116.1 112.0 89.9 67.8 45.7
57 129.1 9.1 129.1 129.1 129.1 116.2 94.2 72.3 121.2 10.4 121.2 121.2 121.2 112.4 89.7 67.0
72 150.6 8.0 122.0 97.9 73.8 49.7 - - 138.6 9.7 116.1 92.6 69.1 45.5 - -
67 139.1 9.3 131.9 115.7 99.5 75.1 50.8 - 130.0 10.5 123.8 109.6 95.4 71.1 46.9 -
4500
62 136.9 9.2 133.9 129.6 125.2 100.6 76.1 51.5 128.1 10.5 125.2 123.5 121.8 96.8 71.7 46.7
57 135.2 9.2 135.2 135.2 135.2 126.1 101.3 76.6 126.5 10.5 126.5 126.5 126.5 122.4 96.6 70.9
72 156.9 7.6 130.7 103.9 77.1 50.2 - - 143.9 9.5 124.2 98.1 72.0 46.0 - -
67 145.2 9.3 138.9 122.4 105.9 78.8 51.7 - 135.1 10.6 129.6 115.7 101.8 74.8 47.8 -
5000
62 143.2 9.3 139.6 137.2 134.7 107.4 80.1 52.8 133.4 10.6 130.2 130.2 130.2 103.6 75.7 47.8
57 141.2 9.4 140.3 140.3 140.3 136.0 108.4 80.9 131.8 10.6 130.8 130.8 130.8 130.8 103.6 74.7

Johnson Controls Ducted Systems 29


5846585-YTG-A-1119

ZZ12 (10 Ton) (Continued)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 114.7 12.0 65.0 53.1 41.1 - - - 104.1 12.9 62.6 50.3 38.0 - - -
72 109.6 11.8 80.9 67.3 53.6 40.0 - - 101.8 12.8 77.9 64.0 50.2 36.3 - -
2500
67 104.5 11.5 96.8 81.5 66.2 52.7 39.1 - 99.4 12.7 93.2 77.8 62.4 48.8 35.2 -
62 101.7 11.3 99.3 89.0 78.7 65.3 51.9 38.5 96.7 12.6 93.3 84.0 74.6 61.2 47.9 34.5
77 119.1 11.8 75.0 57.6 40.2 - - - 107.4 12.9 72.2 54.3 36.5 - - -
72 113.8 11.7 88.3 72.3 56.3 40.3 - - 105.0 12.9 84.5 68.5 52.5 36.6 - -
3000 67 108.6 11.5 101.5 87.0 72.5 56.3 40.1 - 102.5 12.8 96.8 82.7 68.6 52.4 36.1 -
62 106.1 11.4 103.6 96.1 88.6 72.2 55.8 39.4 100.2 12.7 97.0 90.8 84.7 68.2 51.7 35.2
57 104.2 11.3 104.2 104.2 104.2 88.2 71.5 54.9 97.8 12.6 97.2 97.2 97.2 84.0 67.2 50.5
77 123.5 11.5 85.0 62.1 39.2 - - - 110.8 13.0 81.9 58.4 35.0 - - -
72 118.1 11.6 95.6 77.3 59.0 40.7 - - 108.2 12.9 91.1 73.0 54.9 36.8 - -
3500 67 112.7 11.6 106.2 92.5 78.8 59.9 41.0 - 105.6 12.9 100.3 87.6 74.8 56.0 37.1 -
62 110.5 11.6 107.9 103.2 98.6 79.1 59.7 40.2 103.6 12.8 100.6 97.7 94.8 75.1 55.5 35.8
57 108.8 11.5 108.8 108.8 108.8 98.3 78.3 58.3 101.6 12.8 100.8 100.8 100.8 94.3 73.9 53.5
77 127.9 11.2 94.9 66.6 38.3 - - - 114.1 13.0 91.6 62.5 33.5 - - -
72 122.3 11.5 102.9 82.3 61.7 41.0 - - 111.4 13.0 97.7 77.5 57.3 37.0 - -
4000 67 116.8 11.7 110.9 98.0 85.1 63.5 42.0 - 108.7 12.9 103.9 92.5 81.1 59.6 38.0 -
62 114.9 11.7 112.2 110.3 108.5 86.0 63.5 41.1 107.0 12.9 104.2 104.2 104.2 82.1 59.3 36.5
57 113.3 11.6 113.3 113.3 113.3 108.5 85.1 61.7 105.4 12.9 104.4 104.4 104.4 104.4 80.5 56.4
72 126.6 11.4 110.2 87.3 64.4 41.4 - - 114.6 13.0 104.4 82.0 59.6 37.3 - -
67 120.8 11.8 115.6 103.5 91.4 67.1 42.9 - 111.7 13.0 107.5 97.4 87.3 63.2 39.0 -
4500
62 119.3 11.8 116.5 116.5 116.5 92.9 67.4 41.9 110.5 13.0 107.8 107.8 107.8 89.0 63.1 37.1
57 117.9 11.8 117.4 117.4 117.4 117.4 91.9 65.1 109.2 13.0 108.1 108.1 108.1 108.1 87.2 59.4
72 130.8 11.3 117.6 92.3 67.0 41.8 - - 117.8 13.1 111.0 86.5 62.0 37.5 - -
67 124.9 11.9 120.3 109.0 97.7 70.8 43.9 - 114.8 13.1 111.1 102.3 93.6 66.7 39.9 -
5000
62 123.7 11.9 120.8 120.8 120.8 99.8 71.3 42.8 113.9 13.2 111.4 111.4 111.4 96.0 66.9 37.8
57 122.4 11.9 121.3 121.3 121.3 121.3 98.7 68.6 113.0 13.2 111.7 111.7 111.7 111.7 93.8 62.4

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

30 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ14 (12.5 Ton)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
75°F 85°F
77 185.1 8.9 93.2 78.5 63.9 - - - 176.3 9.8 92.7 76.8 60.9 - - -
72 169.2 8.8 114.0 97.2 80.3 63.4 - - 161.1 9.7 111.3 94.2 77.0 59.9 - -
3200
67 153.2 8.6 134.9 115.8 96.7 79.2 63.2 - 145.8 9.7 129.9 111.5 93.1 76.0 59.6 -
62 142.2 8.6 137.1 125.1 113.1 89.8 79.8 63.1 140.0 9.6 135.4 122.3 109.2 89.5 76.5 60.1
77 185.7 9.0 103.6 82.7 61.8 - - - 176.6 9.9 103.1 81.0 59.0 - - -
72 171.6 8.8 122.7 102.8 82.8 62.8 - - 163.4 9.8 119.9 99.7 79.6 59.4 - -
3750 67 157.6 8.7 141.8 122.8 103.7 83.0 63.4 - 150.3 9.7 136.7 118.4 100.2 79.7 59.9 -
62 148.7 8.6 144.0 134.3 124.7 99.0 83.9 63.6 145.6 9.7 141.3 131.0 120.8 97.9 80.5 60.3
57 147.6 8.6 146.2 145.9 145.6 125.0 104.5 83.9 144.7 9.6 144.7 143.7 141.4 121.2 101.0 80.9
77 186.3 9.0 114.1 86.9 59.8 - - - 176.9 9.9 113.5 85.3 57.0 - - -
72 174.1 8.9 131.4 108.3 85.3 62.2 - - 165.8 9.8 128.5 105.3 82.1 59.0 - -
4300 67 161.9 8.7 148.7 129.7 110.7 86.8 63.6 - 154.8 9.8 143.4 125.3 107.3 83.5 60.1 -
62 155.2 8.7 150.9 143.5 136.2 108.1 88.1 64.0 151.2 9.7 147.2 139.8 132.4 106.4 84.4 60.4
57 154.3 8.7 153.0 153.0 153.0 137.1 112.5 88.0 150.5 9.7 150.5 150.5 150.5 133.1 108.8 84.4
77 186.9 9.1 124.5 91.2 57.8 - - - 177.2 10.0 124.0 89.5 55.0 - - -
72 176.6 8.9 140.1 113.9 87.8 61.6 - - 168.2 9.9 137.1 110.9 84.7 58.5 - -
4900 67 166.3 8.8 155.7 136.7 117.7 90.5 63.9 - 159.2 9.8 150.2 132.3 114.3 87.2 60.3 -
62 161.7 8.8 157.7 152.7 147.7 117.3 92.2 64.5 156.8 9.8 153.1 148.5 144.0 114.9 88.4 60.6
57 161.0 8.7 159.8 159.8 159.8 149.1 120.6 92.1 156.2 9.8 155.9 155.9 155.9 145.0 116.5 87.9
72 179.1 9.0 148.7 119.5 90.3 61.0 - - 170.6 9.9 145.7 116.5 87.2 58.0 - -
67 170.6 8.8 162.6 143.7 124.7 94.3 64.1 - 163.7 9.8 157.0 139.2 121.4 90.9 60.6 -
5400
62 168.2 8.8 164.6 161.9 159.2 126.5 96.4 64.9 162.3 9.8 158.9 157.3 155.6 123.3 92.4 60.8
57 167.7 8.8 166.5 166.5 166.5 161.2 128.7 96.1 161.9 9.8 160.9 160.9 160.9 157.0 124.2 91.4
72 181.6 9.0 157.4 125.1 92.8 60.4 - - 173.0 10.0 154.3 122.1 89.8 57.5 - -
67 175.0 8.8 169.5 150.6 131.8 98.0 64.3 - 168.2 9.9 163.8 146.2 128.5 94.7 60.8 -
6000
62 174.7 8.9 171.4 171.1 170.8 135.6 100.5 65.4 167.9 9.9 164.8 164.8 164.8 131.8 96.3 60.9
57 174.5 8.9 173.3 173.3 173.3 173.2 136.7 100.2 167.7 9.9 165.9 165.9 165.9 165.9 131.9 94.8
95°F 105°F
77 167.5 10.7 92.2 75.1 58.0 - - - 153.5 12.0 90.1 72.1 54.1 - - -
72 153.0 10.7 108.5 91.1 73.8 56.4 - - 141.4 12.1 104.7 87.2 69.6 52.0 - -
3200
67 138.4 10.8 124.9 107.2 89.5 72.8 56.1 - 129.4 12.2 119.4 102.2 85.0 68.2 51.4 -
62 137.8 10.7 133.7 119.4 105.2 89.2 73.2 57.2 128.7 12.1 125.5 113.0 100.5 84.4 68.3 52.2
77 167.5 10.7 102.6 79.4 56.1 - - - 154.3 12.1 100.0 75.8 51.6 - - -
72 155.2 10.8 117.1 96.7 76.4 56.0 - - 144.1 12.2 112.6 92.2 71.8 51.4 - -
3750 67 143.0 10.8 131.5 114.1 96.6 76.5 56.3 - 133.9 12.2 125.2 108.6 92.0 71.8 51.6 -
62 142.4 10.7 138.6 127.7 116.9 96.9 77.0 57.0 133.2 12.2 130.2 121.2 112.2 92.2 72.2 52.1
57 141.9 10.6 141.9 141.4 137.2 117.4 97.6 77.8 132.6 12.1 132.6 132.6 132.4 112.6 92.8 72.9
77 167.4 10.8 113.0 83.6 54.2 - - - 155.1 12.2 109.9 79.4 49.0 - - -
72 157.5 10.8 125.6 102.3 79.0 55.7 - - 146.8 12.2 120.5 97.2 74.0 50.7 - -
4300 67 147.6 10.8 138.2 121.0 103.8 80.2 56.6 - 138.4 12.2 131.0 115.0 98.9 75.3 51.7 -
62 147.1 10.8 143.5 136.0 128.6 104.7 80.8 56.9 137.8 12.2 134.8 129.3 123.9 99.9 76.0 52.1
57 146.6 10.7 146.6 146.6 146.6 129.2 105.0 80.7 137.2 12.1 137.2 137.2 137.2 124.6 100.3 76.0
77 167.4 10.9 123.5 87.9 52.3 - - - 155.9 12.3 119.8 83.1 46.5 - - -
72 159.8 10.9 134.1 107.9 81.6 55.3 - - 149.4 12.3 128.3 102.2 76.2 50.1 - -
4900 67 152.2 10.8 144.8 127.9 110.9 83.9 56.8 - 143.0 12.3 136.9 121.4 105.9 78.9 51.9 -
62 151.8 10.8 148.4 144.3 140.3 112.4 84.6 56.7 142.4 12.2 139.4 137.5 135.6 107.7 79.9 52.0
57 151.4 10.8 151.4 151.4 151.4 141.0 112.3 83.7 141.7 12.2 141.7 141.7 141.7 136.5 107.8 79.1
72 162.1 10.9 142.7 113.4 84.2 55.0 - - 152.1 12.3 136.2 107.3 78.3 49.4 - -
67 156.8 10.9 151.5 134.8 118.1 87.6 57.1 - 147.5 12.3 142.7 127.7 112.8 82.4 52.1 -
5400
62 156.5 10.9 153.3 152.7 152.0 120.2 88.4 56.6 146.9 12.3 144.1 144.1 144.1 115.5 83.7 51.9
57 156.1 10.8 155.2 155.2 155.2 152.8 119.7 86.6 146.3 12.2 145.4 145.4 145.4 145.4 115.3 82.1
72 164.3 11.0 151.2 119.0 86.8 54.6 - - 154.8 12.4 144.1 112.3 80.5 48.8 - -
67 161.4 10.9 158.1 141.7 125.2 91.3 57.3 - 152.1 12.3 148.5 134.1 119.7 86.0 52.3 -
6000
62 161.1 10.9 158.2 158.2 158.2 127.9 92.2 56.4 151.5 12.3 148.7 148.7 148.7 123.2 87.6 51.9
57 160.9 10.9 158.4 158.4 158.4 158.4 127.0 89.5 150.9 12.3 148.9 148.9 148.9 148.9 122.8 85.2

Johnson Controls Ducted Systems 31


5846585-YTG-A-1119

ZZ14 (12.5 Ton) (Continued)


Air on Temperature of Air on Condenser Coil
Evaporator Coil Total Total Sensible Capacity (MBh) Total Total Sensible Capacity (MBh)
WB Capacity1 Input Return Dry Bulb (°F) Capacity1 Input Return Dry Bulb (°F)
CFM (MBh) (kW)2 (MBh) (kW)2
(°F) 90 85 80 75 70 65 90 85 80 75 70 65
115°F 125°F
77 139.5 13.4 88.0 69.1 50.2 - - - 125.5 14.8 85.9 66.1 46.2 - - -
72 129.9 13.5 100.9 83.2 65.4 47.6 - - 118.4 14.9 97.1 79.2 61.2 43.2 - -
3200
67 120.3 13.6 113.9 97.2 80.6 63.6 46.6 - 111.3 15.0 108.4 92.3 76.2 59.0 41.9 -
62 119.6 13.6 117.4 106.6 95.8 79.6 63.4 47.3 110.5 15.0 109.2 100.2 91.1 74.9 58.6 42.3
77 141.1 13.5 97.4 72.2 47.0 - - - 128.0 14.9 94.8 68.6 42.4 - - -
72 133.0 13.6 108.1 87.6 67.2 46.7 - - 121.8 15.0 103.7 83.1 62.6 42.0 - -
3750 67 124.8 13.6 118.9 103.1 87.3 67.0 46.8 - 115.7 15.1 112.6 97.6 82.7 62.3 42.0 -
62 124.0 13.6 121.7 114.6 107.5 87.4 67.3 47.3 114.9 15.0 113.3 108.0 102.8 82.7 62.5 42.4
57 123.3 13.5 123.3 123.3 123.3 107.8 87.9 68.1 114.0 15.0 114.0 114.0 114.0 103.0 83.1 63.2
77 142.8 13.5 106.8 75.3 43.8 - - - 130.4 14.9 103.6 71.1 38.6 - - -
72 136.0 13.6 115.3 92.1 68.9 45.7 - - 125.3 15.0 110.2 87.1 63.9 40.8 - -
4300 67 129.3 13.7 123.9 109.0 94.0 70.5 46.9 - 120.1 15.1 116.8 103.0 89.2 65.6 42.1 -
62 128.5 13.6 126.1 122.6 119.2 95.2 71.2 47.3 119.2 15.1 117.4 115.9 114.4 90.5 66.5 42.5
57 127.7 13.6 127.7 127.7 127.7 119.9 95.6 71.3 118.2 15.0 118.0 118.0 118.0 115.3 90.9 66.5
77 144.4 13.6 116.1 78.4 40.7 - - - 132.9 14.9 112.5 73.7 34.8 - - -
72 139.1 13.6 122.5 96.6 70.7 44.8 - - 128.7 15.0 116.7 91.0 65.3 39.5 - -
4875 67 133.8 13.7 128.9 114.8 100.8 73.9 47.0 - 124.5 15.1 121.0 108.3 95.7 68.9 42.1 -
62 132.9 13.6 130.4 130.4 130.4 103.0 75.1 47.3 123.5 15.1 121.5 121.5 121.5 98.3 70.4 42.6
57 132.1 13.6 132.0 132.0 132.0 132.0 103.3 74.5 122.4 15.0 121.9 121.9 121.9 121.9 98.8 69.9
72 142.2 13.7 129.7 101.1 72.5 43.9 - - 132.2 15.1 123.3 94.9 66.6 38.3 - -
67 138.3 13.7 134.0 120.7 107.5 77.3 47.1 - 129.0 15.2 125.2 113.7 102.2 72.2 42.2 -
5400
62 137.4 13.7 134.8 134.8 134.8 110.8 79.0 47.3 127.8 15.1 125.5 125.5 125.5 106.1 74.4 42.7
57 136.5 13.6 135.6 135.6 135.6 135.6 110.9 77.7 126.6 15.0 125.9 125.9 125.9 125.9 106.6 73.2
72 145.2 13.7 136.9 105.6 74.3 42.9 - - 135.7 15.1 129.8 98.9 68.0 37.1 - -
67 142.7 13.8 139.0 126.6 114.2 80.7 47.3 - 133.4 15.2 129.4 119.1 108.7 75.5 42.2 -
6000
62 141.8 13.7 139.2 139.2 139.2 118.6 82.9 47.3 132.1 15.1 129.6 129.6 129.6 113.9 78.3 42.8
57 140.9 13.6 139.3 139.3 139.3 139.3 118.6 80.9 130.8 15.0 129.8 129.8 129.8 129.8 114.4 76.6

1. These capacities are gross ratings. For net capacity, deduct the supply air blower motor heat (MBh = 3.415 x kW). Refer to the appropriate
Blower Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

32 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Drive Selection

1. Determine side or bottom supply duct Application.


2. Determine desired airflow.
3. Calculate or measure the amount of external static pressure.
• Add or deduct any additional static resistance from “Additional Static Resistance Table”.
4. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5. Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8. Determine turns open to obtain the desired operation point.
Example

1. 3200 SCFM, Bottom Supply Duct application


2. 1.8 IWG
3. Using the airflow performance table below, the following data point was located: 1071 RPM & 2.52 BHP.
4. Using the RPM selection table below, Model ZY and Size 08 (7.5 Tons) is found.
5. 2.52 BHP exceeds the maximum continuous BHP rating of the 2.4 HP motor. The 3.7 HP motor is required.
6. 1071 RPM is within the range of the 3.7 HP motor.
7. Using the 3.7-HP motor and High-Static drive, 0.5 turns open will achieve the required 1071 RPM.

Airflow Performance
Example Supply Air Blower Performance
ZY08 (7.5 Ton) Bottom Duct
Available External Static, IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 556 0.45 621 0.65 683 0.83 742 1.00 798 1.18 852 1.34 904 1.51 954 1.69 1003 1.87 1050 2.06
2400 567 0.53 632 0.73 694 0.91 753 1.09 809 1.26 863 1.43 914 1.60 964 1.77 1013 1.95 1060 2.14
2600 580 0.65 646 0.85 707 1.03 766 1.21 823 1.38 876 1.55 928 1.72 978 1.89 1027 2.07 1074 2.27
2800 595 0.79 660 0.99 722 1.17 780 1.35 837 1.52 890 1.69 942 1.86 992 2.03 1041 2.21 1088 2.40
3000 609 0.94 674 1.14 736 1.32 795 1.50 851 1.67 905 1.83 957 2.00 1007 2.18 1056 2.36 1100 2.55
3200 625 1.10 690 1.30 752 1.48 810 1.66 867 1.83 921 2.00 972 2.17 1022 2.34 1071 2.52 -- --
3400 641 1.28 706 1.47 768 1.66 827 1.83 883 2.00 937 2.17 989 2.34 1039 2.52 1087 2.70 '-- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed

Example RPM Selection


Size Airflow Max Blower Motor 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Fully
Model Phase
(Tons) Option BHP Sheave Sheave Open Open Open Open Open Open Closed
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
08
ZY Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(7.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100

Johnson Controls Ducted Systems 33


5846585-YTG-A-1119

Example Additional Static Resistance

Size Cooling Electric Heat kW2


Model CFM Economizer 2 3 4" Filters2
(Tons) Only1 6/6.5 9.2/10.5/1113.8/14/1616/16.5/17 23 24.8/25.5/27.8 32/33/3441.7/42.4
2200 0.04 0.11 --- --- --- --- 0.07 --- 0.09 0.10 0.12
2600 0.06 0.13 --- --- --- --- 0.09 --- 0.11 0.12 0.15
3000 0.10 0.17 --- --- --- --- 0.12 --- 0.14 0.15 0.19
3400 0.13 0.20 --- --- --- --- 0.15 --- 0.18 0.19 0.23
08 (7.5), 3800 0.16 0.25 --- --- --- --- 0.19 --- 0.22 0.23 0.27
ZY 09 (8.5), 4000 0.17 0.28 --- --- --- --- 0.21 --- 0.24 0.25 0.30
12 (10.0) 4400 0.20 0.33 --- --- --- --- 0.25 --- 0.29 0.30 0.35
4800 0.22 0.38 --- --- --- --- 0.30 --- 0.34 0.35 0.41
5200 0.24 0.43 --- --- --- --- 0.35 --- 0.39 0.41 0.47
5600 0.26 0.46 --- --- --- --- 0.41 --- 0.45 0.47 0.54
6000 0.28 0.50 --- --- --- --- 0.48 --- 0.52 0.54 0.60

Altitude and Temperature Correction for CFM, Static use the indoor blower tables for high altitude applications,
Pressure and Power. certain corrections are necessary.
The information below should be used to assist in application of A centrifugal fan is a "constant volume" device. This means
product when being applied at altitudes at or exceeding 1000 that, if the RPM remains constant, the CFM delivered is the
feet above sea level. same regardless of the density of the air. However, since the air
at high altitude is less dense, less static pressure will be
The air flow rates listed in the standard blower performance
generated and less power will be required than a similar
tables are based on standard air at sea level. As the altitude or
application at sea level. Air density correction factors are shown
temperature increases, the density of air decreases. In order to
below.
Altitude/Temperature Correction Factors
Air Altitude (Ft.)
Temp. 0 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
40 1.060 1.022 0.986 0.950 0.916 0.882 0.849 0.818 0.788 0.758 0.729
50 1.039 1.002 0.966 0.931 0.898 0.864 0.832 0.802 0.772 0.743 0.715
60 1.019 0.982 0.948 0.913 0.880 0.848 0.816 0.787 0.757 0.729 0.701
70 1.000 0.964 0.930 0.896 0.864 0.832 0.801 0.772 0.743 0.715 0.688
80 0.982 0.947 0.913 0.880 0.848 0.817 0.787 0.758 0.730 0.702 0.676
90 0.964 0.929 0.897 0.864 0.833 0.802 0.772 0.744 0.716 0.689 0.663
100 0.946 0.912 0.880 0.848 0.817 0.787 0.758 0.730 0.703 0.676 0.651

1.100

1.050

1.000
Sea Level
0.950
Correction Factor

1000 ft
0.900 2000 ft
3000 ft
0.850
4000 ft
0.800 5000 ft
6000 ft
0.750 7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650

0.600
40 50 60 70 80 90 100
Air Temperature (ºF)

34 Johnson Controls Ducted Systems


5846585-YTG-A-1119

The examples below will assist in determining the airflow blower tables to select the blower speed and the BHP
performance of the product at altitude. requirement.
Example 1: What are the corrected CFM, static pressure, and Solution: As in the example above, no temperature
BHP at an elevation of 5,000 ft. if the airflow performance data information is given so 70°F is assumed.
is 3,000 CFM, 1.4 IWC and 2.0 BHP?
The 1.4" static pressure given is at an elevation of 5,000 ft. The
Solution: At an elevation of 5,000 ft. the indoor blower will still first step is to convert this static pressure to equivalent sea level
deliver 3,000 CFM if the rpm is unchanged. However, the Altitude conditions.
correction must be used to determine the static pressure and
Sea level static pressure = 1.4" / .832 = 1.68"
BHP. Since no temperature data is given, we will assume an Air
Temperature of 70°F. The Altitude/Temperature Factors show Enter the Supply Air Blower Performance Table at 3,000 CFM
the correction factor to be 0.832. and static pressure of 1.68". The rpm listed will be the same
rpm needed at 5,000 ft.
Corrected static pressure = 1.4 x 0.832 = 1.16 IWC
Corrected BHP = 2.0 x 0.832 = 1.66 Suppose that the corresponding BHP listed in the table is 2.0.
Example 2: A system, located at 5,000 feet of elevation, is to This value must be corrected for elevation.
deliver 3,000 CFM at a static pressure of 1.4". Use the unit BHP at 5,000 ft. = 2.0 x .832 = 1.66

Indoor Blower Specifications


Size Airflow Motor Motor Sheave Blower Sheave
Model Belt
(Tons) Option Phase HP RPM Eff. SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.7 3/4 AK51 A39
07
ZZ Med. 3 2.9 1725 0.81 1.15 56Y 2.8 - 3.8 7/8 1VL44 4.7 3/4 AK51 A40
(6)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 4.7 3/4 AK51 A41
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 4.7 3/4 AK51 A39
08
ZZ Med. 3 2.9 1725 0.81 1.15 56Y 2.8 - 3.8 7/8 1VL44 4.7 3/4 AK51 A40
(7.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 4.7 3/4 AK51 A41
Std. 3 2.4 1725 0.80 1.15 56Y 1.9 - 2.9 5/8 1VL34 7.0 1 AK74 A47
09
ZZ Med. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.0 1 AK74 A48
(8.5)
H. Static 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.0 1 AK74 A50
Std. 3 2.4 1725 0.80 1.15 56Y 2.8 - 3.8 5/8 1VL44 7.5 1 AK79 A50
12
ZZ Med. 3 3.7 1725 0.84 1.15 56HZ 3.4 - 4.4 7/8 1VP50 7.5 1 AK79 A50
(10)
H. Static 3 5.25 1725 0.84 1.15 145TY 4.3 - 5.3 7/8 1VP56 7.9 1 BK85 BX52
Std. 3 2.9 1750 0.87 1.15 56Z 2.8 - 3.8 7/8 1VL44 7.5 1 AK79 A50
14
ZZ Med. 3 3.7 1750 0.90 1.15 184TZ 3.4 - 4.4 7/8 1VP50 7.5 1 AK79 A52
(12.5)
H. Static 3 5.25 1750 0.90 1.15 184TZ 4.3 - 5.3 7/8 1VP56 7.9 1 BK85 BX54

RPM Selection
Size Airflow MAX Blower Motor 6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turns Fully
Model Phase
(Tons) Option BHP Sheave Sheave Open Open Open Open Open Open Closed
Std. 3 2.4 AK51 1VL34 N/A 707 782 856 931 1005 1080
07
ZZ Med. 3 2.9 AK51 1VL44 N/A 1043 1117 1191 1266 1340 1415
(6)
H. Static 3 3.7 AK51 1VP50 N/A 1266 1340 1415 1489 1564 1638
Std. 3 2.4 AK51 1VL34 N/A 707 782 856 931 1005 1080
08
ZZ Med. 3 2.9 AK51 1VL44 N/A 1043 1117 1191 1266 1340 1415
(7.5)
H. Static 3 3.7 AK51 1VP50 N/A 1266 1340 1415 1489 1564 1638
Std. 3 2.4 AK74 1VL34 N/A 475 525 575 625 675 725
09
ZZ Med. 3 2.4 AK74 1VL44 N/A 700 750 800 850 900 950
(8.5)
H. Static 3 3.7 AK74 1VP50 N/A 850 900 950 1000 1050 1100
Std. 3 2.4 AK79 1VL44 N/A 653 700 747 793 840 887
12
ZZ Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027
(10)
H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A
Std. 3 2.9 AK79 1VL44 N/A 653 700 747 793 840 887
14
ZZ Med. 3 3.7 AK79 1VP50 N/A 793 840 887 933 980 1027
(12)
H. Static 3 5.25 BK85 1VP56 953 997 1041 1085 1130 1174 N/A

Johnson Controls Ducted Systems 35


5846585-YTG-A-1119

Additional Static Resistance - ZZ07-14

Size Electric Heat kW2


Model CFM Cooling Only1 Economizer 2 3 4” Filter2
(Tons) 6/6.5 9.2/10.5/11 13.8/14/16 16/16.5/17 23 24.8/25.5/27.8 32/33/34 41.7/42.4
1800 0.23 0.66 --- 0.03 0.03 0.05 --- --- --- --- ---
2000 0.28 0.81 --- 0.04 0.04 0.06 --- --- --- --- ---
2200 0.32 0.95 --- 0.06 0.06 0.07 --- --- --- --- ---
07
ZZ 2400 0.37 1.10 --- 0.07 0.07 0.08 --- --- --- --- ---
(6)
2600 0.38 1.25 --- 0.08 0.08 0.09 --- --- --- --- ---
2800 0.41 1.39 --- 0.09 0.09 0.10 --- --- --- --- ---
3000 0.45 1.54 --- 0.11 0.11 0.12 --- --- --- --- ---
2200 0.04 0.18 --- --- --- --- 0.07 --- 0.09 0.10 0.12
08 2600 0.06 0.24 --- --- --- --- 0.09 --- 0.11 0.12 0.15
(7.5),
3000 0.10 0.35 --- --- --- --- 0.12 --- 0.14 0.15 0.19
09
(8.5), 3400 0.13 0.47 --- --- --- --- 0.15 --- 0.18 0.19 0.23
ZZ
12 4800 0.22 0.91 --- --- --- --- 0.30 --- 0.34 0.35 0.41
(10.0), 5200 0.24 1.04 --- --- --- --- 0.35 --- 0.39 0.41 0.47
14
(12.5) 5600 0.26 1.17 --- --- --- --- 0.41 --- 0.45 0.47 0.54
6000 0.28 1.30 --- --- --- --- 0.48 --- 0.52 0.54 0.60
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

36 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Airflow Performance
ZZ07-14 Side Duct Application (Belt Drive)

ZZ07 (6.0 Ton) Side Duct


Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 915 0.67 979 0.77 1041 0.89 1102 1.02 1162 1.16 1221 1.31 1278 1.45 1334 1.59 1389 1.72 1442 1.82
1900 939 0.78 1003 0.87 1065 0.99 1126 1.12 1186 1.27 1244 1.41 1302 1.56 1358 1.69 1412 1.82 1466 1.93
2000 964 0.89 1028 0.99 1090 1.11 1151 1.24 1211 1.38 1269 1.52 1327 1.67 1383 1.81 1437 1.93 1491 2.04
2100 990 1.01 1054 1.11 1116 1.23 1177 1.36 1237 1.50 1296 1.65 1353 1.79 1409 1.93 1464 2.05 1517 2.16
2200 1018 1.14 1081 1.24 1143 1.36 1204 1.49 1264 1.63 1323 1.78 1380 1.92 1436 2.06 1491 2.18 1544 2.29
2300 1046 1.28 1110 1.37 1172 1.49 1233 1.62 1293 1.77 1351 1.91 1409 2.05 1465 2.19 1519 2.32 1573 2.43
2400 1076 1.42 1139 1.52 1201 1.63 1262 1.76 1322 1.91 1381 2.05 1438 2.20 1494 2.33 1549 2.46 1602 2.57
2500 1106 1.56 1170 1.66 1232 1.78 1293 1.91 1353 2.05 1411 2.20 1469 2.34 1525 2.48 1579 2.60 1633 2.71
2600 1138 1.71 1201 1.81 1263 1.93 1324 2.06 1384 2.20 1443 2.35 1500 2.49 1556 2.63 1611 2.75 -- --
2700 1170 1.87 1234 1.96 1296 2.08 1357 2.21 1417 2.35 1475 2.50 1533 2.64 1589 2.78 1638 2.91 -- --
2800 1203 2.02 1267 2.12 1329 2.24 1390 2.37 1450 2.51 1509 2.66 1566 2.80 1622 2.94 -- -- -- --
2900 1238 2.18 1301 2.28 1364 2.40 1425 2.53 1484 2.67 1543 2.81 1600 2.96 -- -- -- -- -- --
3000 1273 2.34 1337 2.44 1399 2.56 1460 2.69 1520 2.83 1578 2.97 1635 3.12 -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended blower speed

ZZ08 (7.5 Ton) Side Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 928 0.83 989 0.95 1048 1.08 1105 1.21 1160 1.34 1214 1.47 1266 1.61 1317 1.74 1368 1.88 1417 2.01
2400 967 1.04 1029 1.17 1087 1.29 1144 1.42 1200 1.56 1253 1.69 1306 1.82 1357 1.96 1407 2.09 1457 2.22
2600 1015 1.29 1076 1.42 1135 1.55 1192 1.68 1247 1.81 1301 1.94 1353 2.07 1404 2.21 1455 2.34 1504 2.48
2800 1070 1.59 1131 1.71 1190 1.84 1247 1.97 1302 2.10 1356 2.23 1408 2.37 1460 2.50 1510 2.63 1560 2.77
3000 1133 1.91 1194 2.04 1253 2.17 1310 2.30 1365 2.43 1419 2.56 1471 2.70 1523 2.83 1573 2.96 1623 3.10
3200 1204 2.28 1265 2.41 1324 2.54 1381 2.67 1436 2.80 1490 2.93 1542 3.06 1593 3.20 1644 3.33 1693 3.47
3400 1282 2.69 1343 2.82 1401 2.94 1458 3.07 1514 3.20 1567 3.34 1620 3.47 1671 3.61 -- -- -- --
3600 1366 3.14 1427 3.26 1486 3.39 1543 3.52 1598 3.65 1652 3.78 -- -- -- -- -- -- -- --
3750 1457 3.62 1519 3.74 1577 3.87 1634 4.00 1690 4.13 1743 4.26 -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7 h-p
- Exceeds recommended Blower speed

Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP

Johnson Controls Ducted Systems 37


5846585-YTG-A-1119

ZZ09 (8.5 Ton) Side Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 549 0.45 609 0.69 668 0.91 727 1.11 784 1.31 840 1.49 893 1.68 944 1.87 991 2.06 1035 2.25
2600 552 0.48 611 0.72 671 0.94 729 1.14 787 1.34 842 1.53 896 1.71 946 1.90 994 2.09 1038 2.29
2800 562 0.62 621 0.86 681 1.07 739 1.28 796 1.47 852 1.66 905 1.85 956 2.03 1004 2.22 1048 2.42
3000 573 0.77 632 1.00 692 1.22 750 1.43 807 1.62 863 1.81 917 2.00 967 2.18 1015 2.37 1059 2.57
3200 585 0.93 644 1.16 704 1.38 762 1.59 820 1.78 875 1.97 929 2.16 979 2.34 1027 2.53 1071 2.73
3400 598 1.10 658 1.34 717 1.55 776 1.76 833 1.95 889 2.14 942 2.33 993 2.51 1040 2.70 1084 2.90
3600 613 1.28 672 1.52 732 1.74 790 1.94 848 2.14 903 2.32 957 2.51 1008 2.70 1055 2.89 1099 3.08
3800 629 1.47 688 1.71 748 1.93 806 2.13 864 2.33 919 2.52 973 2.70 1024 2.89 1071 3.08 -- --
4000 646 1.68 706 1.91 765 2.13 824 2.34 881 2.53 937 2.72 990 2.90 1041 3.09 1088 3.28 -- --
4200 665 1.89 724 2.12 784 2.34 842 2.55 900 2.74 955 2.93 1009 3.11 1059 3.30 -- -- -- --
4250 670 1.94 729 2.18 789 2.40 847 2.60 904 2.80 960 2.98 1014 3.17 1064 3.35 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended Blower speed
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP

ZZ12 (10 Ton) Side Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 689 0.94 740 1.19 790 1.44 841 1.70 891 1.94 941 2.19 990 2.43 1038 2.66 1085 2.89
3200 654 0.84 702 1.09 752 1.35 803 1.60 854 1.85 904 2.10 954 2.34 1003 2.58 1051 2.82 1098 3.04
3400 665 1.00 715 1.26 766 1.51 816 1.77 867 2.02 917 2.27 967 2.51 1016 2.75 1064 2.99 1111 3.21
3600 680 1.19 730 1.44 780 1.70 831 1.95 881 2.20 932 2.45 982 2.70 1031 2.94 1079 3.17 1125 3.40
3800 695 1.39 745 1.64 796 1.90 846 2.15 897 2.40 947 2.65 997 2.90 1046 3.14 1094 3.37 1141 3.60
4000 712 1.61 762 1.86 812 2.12 863 2.37 914 2.62 964 2.87 1014 3.12 1063 3.36 1111 3.59 1158 3.82
4200 729 1.85 779 2.10 830 2.36 881 2.61 931 2.86 982 3.11 1032 3.35 1081 3.59 1129 3.83 1174 4.06
4400 748 2.10 798 2.36 849 2.61 899 2.87 950 3.12 1000 3.37 1050 3.61 1099 3.85 1147 4.09 -- --
4600 768 2.38 818 2.64 869 2.89 919 3.15 970 3.40 1020 3.65 1070 3.89 1119 4.13 1167 4.36 -- --
4800 794 2.68 839 2.93 889 3.19 940 3.44 991 3.69 1041 3.94 1091 4.19 1140 4.43 -- -- -- --
5000 811 3.00 861 3.25 912 3.51 962 3.70 1013 4.01 1063 4.26 1113 4.50 1162 4.74 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp
-- Exceeds recommended Blower speed
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP

38 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ14 (12.5 Ton) Side Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3750 684 1.33 741 1.56 792 1.81 840 2.07 884 2.33 927 2.60 971 2.85 1017 3.09 1066 3.30 1121 3.49
3800 688 1.38 745 1.61 797 1.85 844 2.12 888 2.38 932 2.65 976 2.90 1021 3.14 1071 3.35 1125 3.54
4000 706 1.58 763 1.81 814 2.06 861 2.32 906 2.59 949 2.85 993 3.11 1039 3.35 1088 3.56 1142 3.74
4200 724 1.81 781 2.04 832 2.29 879 2.55 924 2.82 967 3.08 1011 3.34 1057 3.57 1106 3.79 1160 3.97
4400 742 2.06 799 2.29 850 2.54 897 2.80 942 3.06 985 3.33 1029 3.58 1075 3.82 1124 4.03 1178 4.22
4600 760 2.32 817 2.55 869 2.80 916 3.06 960 3.33 1004 3.59 1048 3.85 1093 4.08 1143 4.30 -- --
4800 779 2.60 836 2.83 888 3.08 935 3.34 979 3.61 1023 3.88 1067 4.13 1112 4.37 1162 4.58 -- --
5000 799 2.91 856 3.14 907 3.39 954 3.65 999 3.91 1042 4.18 1086 4.43 1132 4.67 -- -- -- --
5200 819 3.23 876 3.46 927 3.71 974 3.97 1019 4.23 1062 4.50 1106 4.75 1152 4.99 -- -- -- --
5400 839 3.57 896 3.80 953 4.04 995 4.31 1039 4.57 1083 4.84 1127 5.09 -- -- -- -- -- --
5600 860 3.92 917 4.15 969 4.40 1016 4.66 1060 4.93 1104 5.19 -- -- -- -- -- -- -- --
5800 882 4.30 939 4.53 990 4.77 1037 5.04 -- -- -- -- -- -- -- -- -- -- -- --
6000 904 4.69 961 4.92 1012 5.17 -- -- -- -- -- -- -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.9-hp


Medium Static Option with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp
Bold Field-supplied BK95 x 1 fixed pulley (p/n 1074787) with Motor rated at 5.25-hp
-- Exceeds recommended Blower speed
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.857 x BHP for Standard Static option, kW = 0.829 x BHP for Medium and High Static options

Johnson Controls Ducted Systems 39


5846585-YTG-A-1119

ZZ07-14 Bottom Duct Application (Belt Drive)

ZZ07 (6.0 Ton) Bottom Duct


Available External Static
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1800 933 0.64 1000 0.79 1064 0.94 1126 1.09 1185 1.24 1243 1.38 1300 1.52 1356 1.64 1411 1.76 1466 1.86
1900 961 0.74 1028 0.89 1092 1.04 1153 1.19 1213 1.34 1271 1.49 1328 1.62 1384 1.75 1439 1.86 1494 1.97
2000 989 0.85 1055 1.00 1119 1.15 1181 1.31 1241 1.45 1299 1.60 1356 1.73 1411 1.86 1467 1.98 1521 2.08
2100 1017 0.97 1083 1.12 1147 1.27 1209 1.42 1269 1.57 1327 1.72 1384 1.85 1439 1.98 1495 2.09 1549 2.20
2200 1045 1.10 1112 1.25 1176 1.40 1238 1.55 1297 1.70 1355 1.84 1412 1.98 1468 2.10 1523 2.22 1578 2.32
2300 1075 1.23 1141 1.38 1205 1.53 1267 1.68 1327 1.83 1385 1.97 1441 2.11 1497 2.24 1552 2.35 1607 2.45
2400 1105 1.37 1171 1.52 1235 1.67 1297 1.82 1357 1.97 1415 2.11 1472 2.25 1527 2.38 1583 2.49 1637 2.59
2500 1136 1.52 1202 1.67 1266 1.82 1328 1.97 1388 2.12 1446 2.26 1503 2.40 1559 2.53 1614 2.64 -- --
2600 1168 1.67 1234 1.82 1298 1.97 1360 2.13 1420 2.27 1478 2.42 1535 2.55 1591 2.68 1638 2.80 -- --
2700 1201 1.84 1268 1.99 1332 2.14 1393 2.29 1453 2.44 1511 2.58 1568 2.72 1624 2.84 -- -- -- --
2800 1235 2.01 1302 2.16 1366 2.31 1428 2.46 1488 2.61 1546 2.75 1602 2.89 -- -- -- -- -- --
2900 1271 2.18 1338 2.33 1402 2.49 1463 2.64 1523 2.79 1581 2.93 1638 3.07 -- -- -- -- -- --
3000 1308 2.37 1374 2.52 1438 2.67 1500 2.82 1560 2.97 1618 3.12 -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended Blower speed

ZZ08 (8.5 Ton) Bottom Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2250 958 0.91 1014 1.08 1072 1.23 1130 1.37 1188 1.50 1246 1.62 1302 1.75 1356 1.90 1408 2.06 1456 2.25
2400 1023 1.16 1080 1.33 1138 1.48 1196 1.61 1254 1.74 1311 1.87 1368 2.00 1422 2.14 1473 2.30 1522 2.49
2600 1080 1.41 1137 1.58 1194 1.73 1253 1.87 1311 1.99 1368 2.12 1424 2.25 1479 2.39 1530 2.56 1579 2.75
2800 1137 1.70 1194 1.87 1251 2.02 1310 2.15 1368 2.28 1425 2.40 1481 2.54 1536 2.68 1587 2.84 1635 3.03
3000 1200 2.03 1257 2.20 1315 2.35 1373 2.48 1431 2.61 1488 2.74 1545 2.87 1599 3.01 1650 3.17 1699 3.36
3200 1274 2.42 1331 2.59 1388 2.74 1447 2.87 1505 3.00 1562 3.13 1618 3.26 1673 3.40 1724 3.56 1772 3.75
3400 1362 2.87 1419 3.04 1476 3.19 1535 3.33 1593 3.46 1650 3.58 1706 3.71 1760 3.86 -- -- -- --
3600 1466 3.40 1523 3.57 1580 3.72 1639 3.86 1697 3.98 1754 4.11 -- -- -- -- -- -- -- --
3750 1588 4.00 1644 4.17 1702 4.32 1760 4.46 -- -- -- -- -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.9-hp
High Static Option with Motor rated at 3.7-hp
-- Exceeds recommended Blower speed

40 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ09 (8.5 Ton) Bottom Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2550 570 0.59 630 0.77 687 0.94 744 1.13 799 1.31 852 1.49 903 1.67 953 1.85 1002 2.01 1049 2.16
2600 573 0.63 632 0.80 690 0.98 747 1.16 801 1.34 855 1.53 906 1.71 956 1.88 1005 2.04 1052 2.19
2800 585 0.77 645 0.94 703 1.12 759 1.30 814 1.49 867 1.67 918 1.85 968 2.02 1017 2.18 1064 2.33
3000 599 0.92 658 1.10 716 1.27 773 1.46 827 1.64 880 1.82 932 2.00 982 2.18 1030 2.34 1077 2.49
3200 614 1.09 673 1.27 731 1.44 787 1.63 842 1.81 895 1.99 947 2.17 997 2.35 1045 2.51 1092 2.66
3400 630 1.28 690 1.45 747 1.62 804 1.81 859 1.99 912 2.18 963 2.35 1013 2.53 1062 2.69 -- --
3600 648 1.47 708 1.64 765 1.82 822 2.00 877 2.19 930 2.37 981 2.55 1031 2.72 1080 2.88 -- --
3800 668 1.67 727 1.84 785 2.02 841 2.20 896 2.39 949 2.57 1001 2.75 1051 2.92 1099 3.09 -- --
4000 689 1.89 748 2.06 806 2.23 863 2.42 917 2.60 971 2.79 1022 2.96 1072 3.14 -- -- -- --
4200 712 2.11 771 2.28 829 2.46 886 2.64 940 2.83 994 3.01 1045 3.19 1095 3.36 -- -- -- --
4250 718 2.17 777 2.34 842 2.52 892 2.70 946 2.88 1000 3.07 1051 3.24 1100 3.42 -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 2.4-hp
High Static Option with Motor rated at 3.7-hp
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP

ZZ12 (10 Ton) Bottom Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3000 653 0.79 706 1.02 758 1.25 808 1.49 858 1.72 907 1.95 955 2.18 1003 2.40 1049 2.62 1095 2.82
3200 667 0.94 720 1.17 771 1.40 822 1.64 872 1.88 921 2.11 969 2.34 1016 2.56 1063 2.77 1109 2.97
3400 682 1.11 734 1.34 786 1.57 837 1.81 887 2.04 936 2.28 984 2.50 1031 2.73 1078 2.94 1124 3.14
3600 697 1.29 750 1.52 802 1.76 853 1.99 903 2.23 952 2.46 1000 2.69 1047 2.91 1094 3.12 1140 3.32
3800 714 1.50 767 1.73 819 1.96 870 2.20 920 2.43 969 2.67 1017 2.90 1064 3.12 1111 3.33 1157 3.53
4000 733 1.73 786 1.96 837 2.19 888 2.43 938 2.66 987 2.90 1035 3.12 1083 3.34 1129 3.56 1174 3.76
4200 753 1.98 806 2.21 857 2.44 908 2.68 958 2.91 1007 3.15 1055 3.37 1102 3.60 1149 3.81 -- --
4400 774 2.25 827 2.48 879 2.72 930 2.95 979 3.19 1028 3.42 1076 3.65 1124 3.87 1170 4.08 -- --
4600 797 2.55 850 2.78 902 3.02 952 3.25 1002 3.49 1051 3.72 1099 3.95 1147 4.17 -- -- -- --
4800 822 2.88 874 3.11 926 3.34 977 3.58 1027 3.81 1076 4.05 1124 4.27 1171 4.50 -- -- -- --
5000 848 3.23 901 3.46 952 3.69 1003 3.93 1053 4.16 1102 4.40 1150 4.62 -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.929 x BHP

Johnson Controls Ducted Systems 41


5846585-YTG-A-1119

ZZ14 (12.5 Ton) Bottom Duct


AVAILABLE EXTERNAL STATIC PRESSURE - IWG1
CFM 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3750 715 1.46 762 1.68 810 1.91 858 2.13 907 2.36 957 2.58 1008 2.80 1060 3.02 1113 3.24 1167 3.46
3800 720 1.51 766 1.73 814 1.96 862 2.18 911 2.41 961 2.63 1012 2.85 1064 3.07 1117 3.29 1171 3.51
4000 737 1.72 784 1.94 832 2.17 880 2.39 929 2.62 979 2.84 1030 3.07 1082 3.29 1135 3.51 -- --
4200 756 1.95 803 2.17 851 2.40 899 2.63 948 2.85 998 3.07 1049 3.30 1101 3.52 1154 3.74 -- --
4400 777 2.20 824 2.42 871 2.65 920 2.87 969 3.10 1019 3.32 1069 3.55 1121 3.77 1174 3.98 -- --
4600 799 2.47 846 2.69 893 2.92 941 3.14 990 3.37 1040 3.59 1091 3.81 1143 4.04 -- -- -- --
4800 822 2.75 869 2.98 916 3.20 965 3.43 1014 3.65 1064 3.88 1114 4.10 1166 4.32 -- -- -- --
5000 846 3.06 893 3.28 941 3.51 989 3.73 1038 3.96 1088 4.18 1139 4.41 -- -- -- -- -- --
5200 872 3.39 919 3.61 966 3.83 1015 4.06 1064 4.28 1114 4.51 1164 4.73 -- -- -- -- -- --
5400 899 3.73 946 3.95 993 4.18 1042 4.40 1091 4.63 1141 4.85 -- -- -- -- -- -- -- --
5600 927 4.09 974 4.32 1021 4.54 1070 4.77 1119 4.99 1169 5.22 -- -- -- -- -- -- -- --
5800 956 4.47 1003 4.70 1051 4.92 1099 5.15 -- -- -- -- -- -- -- -- -- -- -- --
6000 987 4.87 1034 5.10 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --

Standard Static Option with Motor rated at 2.4-hp


Medium Static Option with Motor rated at 3.7-hp
High Static Option with Motor rated at 5.25-hp

1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
Note: See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = 0.857 x BHP for Standard Static option, kW = 0.829 x BHP for Medium and High Static options

Power Exhaust Blower Curves

cfm cfm
0 500 1000 1500 2000 2500 0 500 1000 1500 2000 2500
250 1.00 250 1.00

200 0.80 200 0.80

460V 230V
150 0.60 150 0.60
In. In.
Pa Pa
WG WG

100 0.40 100 0.40


Forbidden area
Forbidden area

50 0.20 50 0.20

0 0 0 0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 0 500 1000 1500 2000 2500 3000 3500 4000 4500
Air volume[CMH] Air volume[CMH]

460-3-60 Power Exhaust Fan Curve 208/280-3-60 Power Exhaust Fan Curve

42 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Electrical Data
ZZ07-14 Standard Static Indoor Blower - Without Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size Rating4/
(Tons) Motors 2EK045* (Amps) 4 Exh
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 31.6 35 45 31 158 32.7 35 50 33 161
10625 4.9 1 13.6 31.6 35 45 31 158 32.7 35 50 33 161
208-3-60 17.6 136 27 4.4 5.2 1.1
11125 7.9 1 21.9 33.9 35 45 31 158 35.3 40 50 33 161
11625 12 1 33.3 48.1 50 50 44 158 49.5 50 50 46 161
None - - - 31.6 35 45 31 161 32.6 35 50 32 163
07 10625 6.5 1 15.6 31.6 35 45 31 161 32.6 35 50 32 163
230-3-60 17.6 136 27 4.4 5.2 1
(6) 11125 10.5 1 25.3 38.1 40 45 35 161 39.4 40 50 36 163
11625 16 1 38.5 54.6 60 60 50 161 55.9 60 60 51 163
None - - - 15.7 20 20 16 79 16.2 20 20 16 80
10646 6 1 7.2 15.7 20 20 11 79 16.2 20 20 12 80
460-3-60 8.5 66.1 13 2.5 2.6 0.5
11146 11.5 1 13.8 20.5 25 25 19 79 21.1 25 25 19 80
11446 14 1 16.8 24.3 25 25 22 79 24.9 25 25 23 80
None - - - 40.9 50 50 44 158 42.0 45 50 47 256
10625 4.9 1 13.6 40.9 50 50 44 158 42.0 45 50 47 256
208-3-60 25.0 164 39 4.4 5.2 1.1
11125 7.9 1 21.9 40.9 50 50 44 158 42.0 45 50 47 256
11625 12 1 33.3 46.8 50 50 44 158 47.9 50 50 46 161
None - - - 40.9 50 50 44 158 41.9 45 50 47 256
08 10625 6.5 1 15.6 40.9 50 50 44 158 41.9 45 50 47 256
230-3-60 25.0 164 39 4.4 5.2 1
(7.50) 11125 10.5 1 25.3 36.8 40 45 35 161 37.8 40 50 36 163
11625 16 1 38.5 53.3 60 60 50 161 54.3 60 60 51 163
None - - - 20.3 25 25 19 79 20.8 25 25 19 80
10646 6 1 7.2 20.3 25 25 19 79 20.8 25 25 19 80
460-3-60 12.2 100 19 2.5 2.6 0.5
11146 11.5 1 13.8 19.9 20 20 11 79 20.4 25 25 19 80
11446 14 1 16.8 23.6 25 25 22 79 24.1 25 25 19 80
None - - - 44.2 45 50 47 275 46.4 50 50 49 285
11725 12 1 33.3 50.4 60 60 47 275 53.1 60 60 49 285
208-3-60 14.5 98 23 14.5 98 23 2.3 7 1.1 12525 18.6 1 51.6 73.3 80 80 67 275 76 80 80 70 285
13225 24 1 66.6 92 100 100 85 275 94.8 100 100 87 285
14225 31.8 2 88.3 119.1 125 125 110 275 121.9 125 125 112 285
None - - - 44.4 45 50 47 278 46.4 50 60 49 272
11725 16 1 38.5 57.1 60 60 53 278 59.6 60 60 55 272
09
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 12525 24.8 1 59.7 83.6 90 90 77 278 86.1 90 90 79 272
(8.5)
13225 32 1 77 105.3 110 110 97 278 107.8 110 110 99 272
14225 42.4 2 102 136.5 150 150 126 278 139 150 150 128 272
None - - - 20.4 25 25 22 153 21.4 25 25 23 149
11746 16.5 1 19.8 29.3 30 30 27 153 30.5 35 35 28 149
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 12846 27.8 1 33.4 46.3 50 50 43 153 47.5 50 50 44 149
13346 33 1 39.7 54.1 60 60 50 153 55.4 60 60 51 149
14246 41.7 2 50.2 67.3 70 70 62 153 68.5 70 70 63 149
None - - - 47.2 50 60 50 299 49.4 50 60 52 309
11725 12 1 33.3 50.4 60 60 50 299 53.1 60 60 52 309
208-3-60 16 110 25 15.6 110 24 2.3 7 1.1 12525 18.6 1 51.6 73.3 80 80 67 299 76 80 80 70 309
13225 24 1 66.6 92 100 100 85 299 94.8 100 100 87 309
14225 31.8 2 88.3 119.1 125 125 110 299 121.9 125 125 112 309
None - - - 47.4 50 60 50 302 49.4 50 60 52 296
11725 16 1 38.5 57.1 60 60 53 302 59.6 60 60 55 296
12
230-3-60 16 110 25 15.6 110 24 2.3 7.2 1 12525 24.8 1 59.7 83.6 90 90 77 302 86.1 90 90 79 296
(10)
13225 32 1 77 105.3 110 110 97 302 107.8 110 110 99 296
14225 42.4 2 102 136.5 150 150 126 302 139 150 150 128 296
None - - - 23.8 25 30 25 147 24.8 25 30 26 143
11746 16.5 1 19.8 29.3 30 30 27 147 30.5 35 35 28 143
460-3-60 7.8 52 12 7.8 52 12 1.3 3.6 0.5 12846 27.8 1 33.4 46.3 50 50 43 147 47.5 50 50 44 143
13346 33 1 39.7 54.1 60 60 50 147 55.4 60 60 51 143
14246 41.7 2 50.2 67.3 70 70 62 147 68.5 70 70 63 143

Johnson Controls Ducted Systems 43


5846585-YTG-A-1119

ZZ07-14 Standard Static Indoor Blower - Without Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size Rating4/
(Tons) Motors 2EK045* (Amps) 4 Exh
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 58.8 60 70 62 371 61 70 70 65 381
11725 12 1 33.3 58.8 60 70 62 371 61 70 70 65 381
208-3-60 19.6 136 31 19.6 136 31 5.8 8.9 1.1 12525 18.6 1 51.6 75.6 80 80 70 371 78.4 80 80 72 381
13225 24 1 66.6 94.4 100 100 87 371 97.1 100 100 89 381
14225 31.8 2 88.3 121.5 125 125 112 371 124.3 125 125 114 381
None - - - 57.5 60 70 60 370 59.5 60 70 63 375
11725 16 1 38.5 58.4 60 70 60 370 60.9 70 70 63 375
14
230-3-60 19.6 136 31 19.6 136 31 5.2 8.2 1 12525 24.8 1 59.7 84.9 90 90 78 370 87.4 90 90 80 375
(12.5)
13225 32 1 77 106.5 110 110 98 370 109 110 110 100 375
14225 42.4 2 102 137.8 150 150 127 370 140.3 150 150 129 375
None - - - 25.5 30 30 27 178 26.5 30 30 28 180
11746 16.5 1 19.8 29.9 30 30 27 178 31.1 35 35 29 180
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 4.1 0.5 12846 27.8 1 33.4 46.9 50 50 43 178 48.1 50 50 44 180
13346 33 1 39.7 54.8 60 60 50 178 56 60 60 52 180
14246 41.7 2 50.2 67.9 70 70 62 178 69.1 70 70 64 180

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

44 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-14 Standard Static Indoor Blower - With Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr Fuse 2/ Fuse 2/ Discon- Breaker 3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 35.9 40 50 36 163 37 40 50 37 165
10625 4.9 1 13.6 35.9 40 50 36 163 37 40 50 37 165
208-3-60 17.6 136 27 4.4 5.2 1.1 8.6
11125 7.9 1 21.9 39.3 40 50 36 163 40.6 45 50 37 165
11625 12 1 33.3 53.5 60 60 49 163 54.9 60 60 50 165
None - - - 35.9 40 50 36 165 36.9 40 50 37 168
07 10625 6.5 1 15.6 35.9 40 50 36 165 36.9 40 50 37 168
230-3-60 17.6 136 27 4.4 5.2 1 8.6
(6) 11125 10.5 1 25.3 43.5 45 50 40 165 44.8 45 50 41 168
11625 16 1 38.5 60 60 60 55 165 61.3 70 70 56 168
None - - - 17.9 20 25 18 81 18.4 20 25 19 82
10646 6 1 7.2 17.9 20 25 14 81 18.4 20 25 14 82
460-3-60 8.5 66.1 13 2.5 2.6 0.5 8.6
11146 11.5 1 13.8 23.2 25 25 21 81 23.8 25 25 22 82
11446 14 1 16.8 26.9 30 30 25 81 27.6 30 30 25 82
None - - - 43.2 45 50 39 205 44.3 45 50 47 243
10625 4.9 1 13.6 43.2 45 50 39 205 44.3 45 50 47 243
208-3-60 25.0 164 39 4.4 5.2 1.1 8.6
11125 7.9 1 21.9 43.2 45 50 39 205 44.3 45 50 47 243
11625 12 1 33.3 55.4 60 60 53 191 56.5 60 60 55 243
None - - - 43.2 45 50 39 205 44.2 45 50 47 243
08 10625 6.5 1 15.6 43.2 45 50 39 205 44.2 45 50 47 243
230-3-60 25.0 164 39 4.4 5.2 1 8.6
(7.50) 11125 10.5 1 25.3 45.4 50 50 43 128 46.4 50 50 47 243
11625 16 1 38.5 61.9 70 70 62 128 62.9 70 70 63 121
None - - - 25.9 30 30 27 128 26.4 30 30 27 153
10646 6 1 7.2 25.9 30 30 27 128 26.4 30 30 27 153
460-3-60 12.2 100 19 2.5 2.6 0.5 8.6
11146 11.5 1 13.8 28.5 30 30 27 128 29.0 30 30 27 153
11446 14 1 16.8 32.2 35 50 31 158 32.7 35 50 32 163
None - - - 48.5 50 60 52 280 50.7 60 60 54 290
11725 12 1 33.3 55.8 60 60 52 280 58.5 60 60 54 290
208-3-60 14.5 98 23 14.5 98 23 2.3 7 1.1 8.6 12525 18.6 1 51.6 78.6 80 80 72 280 81.4 90 90 75 290
13225 24 1 66.6 97.4 100 100 90 280 100.1 110 110 92 290
14225 31.8 2 88.3 124.5 125 125 115 280 127.3 150 150 117 290
None - - - 48.7 50 60 52 282 50.7 60 60 54 277
11725 16 1 38.5 62.5 70 70 58 282 65 70 70 60 277
09
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 8.6 12525 24.8 1 59.7 89 90 90 82 282 91.5 100 100 84 277
(8.5)
13225 32 1 77 110.6 125 125 102 282 113.1 125 125 104 277
14225 42.4 2 102 141.9 150 150 131 282 144.4 150 150 133 277
None - - - 22.6 25 25 24 155 23.6 25 25 25 151
11746 16.5 1 19.8 31.9 35 35 29 155 33.2 35 35 31 151
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 48.9 50 50 45 155 50.2 60 60 46 151
13346 33 1 39.7 56.8 60 60 52 155 58.1 60 60 53 151
14246 41.7 2 50.2 69.9 70 70 64 155 71.2 80 80 65 151
None - - - 51.5 60 60 55 304 53.7 60 60 57 314
11725 12 1 33.3 55.8 60 60 55 304 58.5 60 60 57 314
208-3-60 16 110 25 15.6 110 24 2.3 7 1.1 8.6 12525 18.6 1 51.6 78.6 80 80 72 304 81.4 90 90 75 314
13225 24 1 66.6 97.4 100 100 90 304 100.1 110 110 92 314
14225 31.8 2 88.3 124.5 125 125 115 304 127.3 150 150 117 314
None - - - 51.7 60 60 55 306 53.7 60 60 57 301
11725 16 1 38.5 62.5 70 70 58 306 65 70 70 60 301
12
230-3-60 16 110 25 15.6 110 24 2.3 7.2 1 8.6 12525 24.8 1 59.7 89 90 90 82 306 91.5 100 100 84 301
(10)
13225 32 1 77 110.6 125 125 102 306 113.1 125 125 104 301
14225 42.4 2 102 141.9 150 150 131 306 144.4 150 150 133 301
None - - - 26 30 30 28 149 27 30 30 29 145
11746 16.5 1 19.8 31.9 35 35 29 149 33.2 35 35 31 145
460-3-60 7.8 52 12 7.8 52 12 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 48.9 50 50 45 149 50.2 60 60 46 145
13346 33 1 39.7 56.8 60 60 52 149 58.1 60 60 53 145
14246 41.7 2 50.2 69.9 70 70 64 149 71.2 80 80 65 145

Johnson Controls Ducted Systems 45


5846585-YTG-A-1119

ZZ07-14 Standard Static Indoor Blower - With Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 63.1 70 80 67 375 65.3 70 80 69 385
11725 12 1 33.3 63.1 70 80 67 375 65.3 70 80 69 385
208-3-60 19.6 136 31 19.6 136 31 5.8 8.9 1.1 8.6 12525 18.6 1 51.6 81 90 90 75 375 83.8 90 90 77 385
13225 24 1 66.6 99.8 100 100 92 375 102.5 110 110 94 385
14225 31.8 2 88.3 126.9 150 150 117 375 129.6 150 150 119 385
None - - - 61.8 70 80 65 374 63.8 70 80 68 379
11725 16 1 38.5 63.8 70 80 65 374 66.3 70 80 68 379
14
230-3-60 19.6 136 31 19.6 136 31 5.2 8.2 1 8.6 12525 24.8 1 59.7 90.3 100 100 83 374 92.8 100 100 85 379
(12.5)
13225 32 1 77 111.9 125 125 103 374 114.4 125 125 105 379
14225 42.4 2 102 143.1 150 150 132 374 145.6 150 150 134 379
None - - - 27.7 30 35 29 180 28.7 30 35 31 182
11746 16.5 1 19.8 32.6 35 35 30 180 33.8 35 35 31 182
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 4.1 0.5 8.6 12846 27.8 1 33.4 49.6 50 50 46 180 50.8 60 60 47 182
13346 33 1 39.7 57.4 60 60 53 180 58.7 60 60 54 182
14246 41.7 2 50.2 70.6 80 80 65 180 71.8 80 80 66 182

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

46 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-14 Medium Static Indoor Blower - Without Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 33.9 35 50 34 185 35 35 50 35 187
10625 4.9 1 13.6 33.9 35 50 34 185 35 35 50 35 187
208-3-60 17.6 136 27 4.4 7.5 1.1
11125 7.9 1 21.9 36.8 40 50 34 185 38.1 40 50 35 187
11625 12 1 33.3 51 60 60 47 185 52.4 60 60 48 187
None - - - 33.9 35 50 34 191 34.9 35 50 35 193
07 10625 6.5 1 15.6 33.9 35 50 34 191 34.9 35 50 35 193
230-3-60 17.6 136 27 4.4 7.5 1
(6) 11125 10.5 1 25.3 41 45 50 38 191 42.3 45 50 39 193
11625 16 1 38.5 57.5 60 60 53 191 58.8 60 60 54 193
None - - - 16.5 20 25 17 94 17 20 25 17 95
10646 6 1 7.2 16.5 20 25 12 94 17 20 25 13 95
460-3-60 8.5 66.1 13 2.5 3.4 0.5
11146 11.5 1 13.8 21.5 25 25 20 94 22.1 25 25 20 95
11446 14 1 16.8 25.3 30 30 23 94 25.9 30 30 24 95
None - - - 43.2 45 50 38 191 44.3 45 50 39 193
10625 4.9 1 13.6 43.2 45 50 38 191 44.3 45 50 39 193
208-3-60 25.0 164 39 4.4 7.5 1.1
11125 7.9 1 21.9 43.2 45 50 38 191 44.3 45 50 39 193
11625 12 1 33.3 49.1 50 50 49 272 50.2 60 60 55 207
None - - - 43.2 45 50 38 191 44.2 45 50 39 193
08 10625 6.5 1 15.6 43.2 45 50 38 191 44.2 45 50 39 193
230-3-60 25.0 164 39 4.4 7.5 1
(7.50) 11125 10.5 1 25.3 39.1 40 50 34 185 40.1 50 50 44 198
11625 16 1 38.5 55.6 60 60 53 191 56.6 60 60 53 191
None - - - 21.1 25 25 20 94 21.6 25 25 23 97
10646 6 1 7.2 21.1 25 25 20 94 21.6 25 25 23 97
460-3-60 12.2 100 19 2.5 3.4 0.5
11146 11.5 1 13.8 20.7 25 25 20 94 21.2 25 25 23 97
11446 14 1 16.8 24.4 25 25 20 94 24.9 25 25 23 97
None - - - 44.2 45 50 47 275 46.4 50 50 49 285
11725 12 1 33.3 50.4 60 60 47 275 53.1 60 60 49 285
208-3-60 14.5 98 23 14.5 98 23 2.3 7 1.1 12525 18.6 1 51.6 73.3 80 80 67 275 76 80 80 70 285
13225 24 1 66.6 92 100 100 85 275 94.8 100 100 87 285
14225 31.8 2 88.3 119.1 125 125 110 275 121.9 125 125 112 285
None - - - 44.4 45 50 47 278 46.4 50 60 49 272
11725 16 1 38.5 57.1 60 60 53 278 59.6 60 60 55 272
09
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 12525 24.8 1 59.7 83.6 90 90 77 278 86.1 90 90 79 272
(8.5)
13225 32 1 77 105.3 110 110 97 278 107.8 110 110 99 272
14225 42.4 2 102 136.5 150 150 126 278 139 150 150 128 272
None - - - 20.4 25 25 22 153 21.4 25 25 23 149
11746 16.5 1 19.8 29.3 30 30 27 153 30.5 35 35 28 149
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 12846 27.8 1 33.4 46.3 50 50 43 153 47.5 50 50 44 149
13346 33 1 39.7 54.1 60 60 50 153 55.4 60 60 51 149
14246 41.7 2 50.2 67.3 70 70 62 153 68.5 70 70 63 149
None - - - 50.1 60 60 53 312 52.3 60 60 56 322
11725 12 1 33.3 54 60 60 53 312 56.8 60 60 56 322
208-3-60 16 110 25 15.6 110 24 2.3 9.9 1.1 12525 18.6 1 51.6 76.9 80 80 71 312 79.6 80 80 73 322
13225 24 1 66.6 95.6 100 100 88 312 98.4 100 100 91 322
14225 31.8 2 88.3 122.8 125 125 113 312 125.5 150 150 115 322
None - - - 49.6 50 60 52 321 51.6 60 60 55 315
11725 16 1 38.5 59.9 60 60 55 321 62.4 70 70 57 315
12
230-3-60 16 110 25 15.6 110 24 2.3 9.4 1 12525 24.8 1 59.7 86.4 90 90 79 321 88.9 90 90 82 315
(10)
13225 32 1 77 108 110 110 99 321 110.5 125 125 102 315
14225 42.4 2 102 139.3 150 150 128 321 141.8 150 150 130 315
None - - - 24.9 25 30 26 156 25.9 30 30 27 152
11746 16.5 1 19.8 30.6 35 35 28 156 31.9 35 35 29 152
460-3-60 7.8 52 12 7.8 52 12 1.3 4.7 0.5 12846 27.8 1 33.4 47.6 50 50 44 156 48.9 50 50 45 152
13346 33 1 39.7 55.5 60 60 51 156 56.8 60 60 52 152
14246 41.7 2 50.2 68.6 70 70 63 156 69.9 70 70 64 152

Johnson Controls Ducted Systems 47


5846585-YTG-A-1119

ZZ07-14 Medium Static Indoor Blower - Without Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 59.8 60 70 63 367 62 70 80 66 377
11725 12 1 33.3 59.8 60 70 63 367 62 70 80 66 377
208-3-60 19.6 136 31 19.6 136 31 5.8 9.9 1.1 12525 18.6 1 51.6 76.9 80 80 71 367 79.6 80 80 73 377
13225 24 1 66.6 95.6 100 100 88 367 98.4 100 100 91 377
14225 31.8 2 88.3 122.8 125 125 113 367 125.5 150 150 115 377
None - - - 58.7 60 70 62 372 60.7 70 80 64 376
11725 16 1 38.5 59.9 60 70 62 372 62.4 70 80 64 376
14
230-3-60 19.6 136 31 19.6 136 31 5.2 9.4 1 12525 24.8 1 59.7 86.4 90 90 79 372 88.9 90 90 82 376
(12.5)
13225 32 1 77 108 110 110 99 372 110.5 125 125 102 376
14225 42.4 2 102 139.3 150 150 128 372 141.8 150 150 130 376
None - - - 26.1 30 30 28 184 27.1 30 30 29 186
11746 16.5 1 19.8 30.6 35 35 28 184 31.9 35 35 29 186
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 4.7 0.5 12846 27.8 1 33.4 47.6 50 50 44 184 48.9 50 50 45 186
13346 33 1 39.7 55.5 60 60 51 184 56.8 60 60 52 186
14246 41.7 2 50.2 68.6 70 70 63 184 69.9 70 70 64 186

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

48 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-14 Medium Static Indoor Blower - With Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 38.2 40 50 39 189 39.3 40 50 40 191
10625 4.9 1 13.6 38.2 40 50 39 189 39.3 40 50 40 191
208-3-60 17.6 136 27 4.4 7.5 1.1 8.6
11125 7.9 1 21.9 42.1 45 50 39 189 43.5 45 50 40 191
11625 12 1 33.3 56.4 60 60 52 189 57.8 60 60 53 191
None - - - 38.2 40 50 39 195 39.2 40 50 40 198
07 10625 6.5 1 15.6 38.2 40 50 39 195 39.2 40 50 40 198
230-3-60 17.6 136 27 4.4 7.5 1 8.6
(6) 11125 10.5 1 25.3 46.4 50 50 43 195 47.6 50 50 44 198
11625 16 1 38.5 62.9 70 70 58 195 64.1 70 70 59 198
None - - - 18.7 20 25 19 96 19.2 20 25 20 97
10646 6 1 7.2 18.7 20 25 15 96 19.2 20 25 15 97
460-3-60 8.5 66.1 13 2.5 3.4 0.5 8.6
11146 11.5 1 13.8 24.2 25 25 22 96 24.8 25 25 23 97
11446 14 1 16.8 27.9 30 30 26 96 28.6 30 30 26 97
None - - - 45.5 50 50 43 195 46.6 50 50 44 198
10625 4.9 1 13.6 45.5 50 50 43 195 46.6 50 50 44 198
208-3-60 25.0 164 39 4.4 7.5 1.1 8.6
11125 7.9 1 21.9 45.5 50 50 43 195 46.6 50 50 44 198
11625 12 1 33.3 57.7 60 60 52 189 58.8 60 60 53 191
None - - - 45.5 50 50 43 195 46.5 50 50 44 198
08 10625 6.5 1 15.6 43.2 45 50 39 189 44.2 45 50 40 191
230-3-60 25.0 164 39 4.4 7.5 1 8.6
(7.50) 11125 10.5 1 25.3 47.7 50 50 43 195 48.7 50 50 44 198
11625 16 1 38.5 64.2 70 70 58 195 65.2 70 70 59 198
None - - - 26.7 30 30 26 96 27.2 30 30 26 97
10646 6 1 7.2 26.7 30 30 26 96 27.2 30 30 26 97
460-3-60 12.2 100 19 2.5 3.4 0.5 8.6
11146 11.5 1 13.8 29.3 30 30 26 96 29.8 30 30 26 97
11446 14 1 16.8 33.0 35 35 31 127 33.5 35 35 31 127
None - - - 48.5 50 60 52 280 50.7 60 60 54 290
11725 12 1 33.3 55.8 60 60 52 280 58.5 60 60 54 290
208-3-60 14.5 98 23 14.5 98 23 2.3 7 1.1 8.6 12525 18.6 1 51.6 78.6 80 80 72 280 81.4 90 90 75 290
13225 24 1 66.6 97.4 100 100 90 280 100.1 110 110 92 290
14225 31.8 2 88.3 124.5 125 125 115 280 127.3 150 150 117 290
None - - - 48.7 50 60 52 282 50.7 60 60 54 277
11725 16 1 38.5 62.5 70 70 58 282 65 70 70 60 277
09
230-3-60 14.5 98 23 14.5 98 23 2.3 7.2 1 8.6 12525 24.8 1 59.7 89 90 90 82 282 91.5 100 100 84 277
(8.5)
13225 32 1 77 110.6 125 125 102 282 113.1 125 125 104 277
14225 42.4 2 102 141.9 150 150 131 282 144.4 150 150 133 277
None - - - 22.6 25 25 24 155 23.6 25 25 25 151
11746 16.5 1 19.8 31.9 35 35 29 155 33.2 35 35 31 151
460-3-60 6.3 55 10 6.3 55 10 1.3 3.6 0.5 8.6 12846 27.8 1 33.4 48.9 50 50 45 155 50.2 60 60 46 151
13346 33 1 39.7 56.8 60 60 52 155 58.1 60 60 53 151
14246 41.7 2 50.2 69.9 70 70 64 155 71.2 80 80 65 151
None - - - 54.4 60 70 58 316 56.6 60 70 60 326
11725 12 1 33.3 59.4 60 70 58 316 62.1 70 70 60 326
208-3-60 16 110 25 15.6 110 24 2.3 9.9 1.1 8.6 12525 18.6 1 51.6 82.3 90 90 76 316 85 90 90 78 326
13225 24 1 66.6 101 110 110 93 316 103.8 110 110 95 326
14225 31.8 2 88.3 128.1 150 150 118 316 130.9 150 150 120 326
None - - - 53.9 60 60 57 325 55.9 60 70 60 320
11725 16 1 38.5 65.3 70 70 60 325 67.8 70 70 62 320
12
230-3-60 16 110 25 15.6 110 24 2.3 9.4 1 8.6 12525 24.8 1 59.7 91.8 100 100 84 325 94.3 100 100 87 320
(10)
13225 32 1 77 113.4 125 125 104 325 115.9 125 125 107 320
14225 42.4 2 102 144.6 150 150 133 325 147.1 150 150 135 320
None - - - 27.1 30 30 29 158 28.1 30 30 30 154
11746 16.5 1 19.8 33.3 35 35 31 158 34.6 35 35 32 154
460-3-60 7.8 52 12 7.8 52 12 1.3 4.7 0.5 8.6 12846 27.8 1 33.4 50.3 60 60 46 158 51.6 60 60 47 154
13346 33 1 39.7 58.2 60 60 54 158 59.4 60 60 55 154
14246 41.7 2 50.2 71.3 80 80 66 158 72.6 80 80 67 154

Johnson Controls Ducted Systems 49


5846585-YTG-A-1119

ZZ07-14 Medium Static Indoor Blower - With Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 64.1 70 80 68 371 66.3 70 80 71 381
11725 12 1 33.3 64.1 70 80 68 371 66.3 70 80 71 381
208-3-60 19.6 136 31 19.6 136 31 5.8 9.9 1.1 8.6 12525 18.6 1 51.6 82.3 90 90 76 371 85 90 90 78 381
13225 24 1 66.6 101 110 110 93 371 103.8 110 110 95 381
14225 31.8 2 88.3 128.1 150 150 118 371 130.9 150 150 120 381
None - - - 63 70 80 67 376 65 70 80 69 381
11725 16 1 38.5 65.3 70 80 67 376 67.8 70 80 69 381
14
230-3-60 19.6 136 31 19.6 136 31 5.2 9.4 1 8.6 12525 24.8 1 59.7 91.8 100 100 84 376 94.3 100 100 87 381
(12.5)
13225 32 1 77 113.4 125 125 104 376 115.9 125 125 107 381
14225 42.4 2 102 144.6 150 150 133 376 147.1 150 150 135 381
None - - - 28.3 30 35 30 186 29.3 30 35 31 188
11746 16.5 1 19.8 33.3 35 35 31 186 34.6 35 35 32 188
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 4.7 0.5 8.6 12846 27.8 1 33.4 50.3 60 60 46 186 51.6 60 60 47 188
13346 33 1 39.7 58.2 60 60 54 186 59.4 60 60 55 188
14246 41.7 2 50.2 71.3 80 80 66 186 72.6 80 80 67 188

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

50 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-14 Hi Static Indoor Blower - Without Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 36.6 40 50 37 199 37.7 40 50 38 202
10625 4.9 1 13.6 36.6 40 50 37 199 37.7 40 50 38 202
208-3-60 17.6 136 27 4.4 10.2 1.1
11125 7.9 1 21.9 40.1 45 50 37 199 41.5 45 50 38 202
11625 12 1 33.3 54.4 60 60 50 199 55.8 60 60 51 202
None - - - 36.6 40 50 37 205 37.6 40 50 38 207
07 10625 6.5 1 15.6 36.6 40 50 37 205 37.6 40 50 38 207
230-3-60 17.6 136 27 4.4 10.2 1
(6) 11125 10.5 1 25.3 44.4 45 50 41 205 45.6 50 50 42 207
11625 16 1 38.5 60.9 70 70 56 205 62.1 70 70 57 207
None - - - 17.9 20 25 18 101 18.4 20 25 19 102
10646 6 1 7.2 17.9 20 25 14 101 18.4 20 25 14 102
460-3-60 8.5 66.1 13 2.5 4.8 0.5
11146 11.5 1 13.8 23.3 25 25 21 101 23.9 25 25 22 102
11446 14 1 16.8 27 30 30 25 101 27.6 30 30 25 102
None - - - 45.9 50 50 42 207 47.0 50 50 42 207
10625 4.9 1 13.6 45.9 50 50 42 207 47.0 50 50 42 207
208-3-60 25.0 164 39 4.4 10.2 1.1
11125 7.9 1 21.9 45.9 50 50 42 207 47.0 50 50 42 207
11625 12 1 33.3 51.8 60 60 50 199 52.9 60 60 51 202
None - - - 45.9 50 50 42 207 46.9 50 50 42 207
08 10625 6.5 1 15.6 45.9 50 50 42 207 46.9 50 50 42 207
230-3-60 25.0 164 39 4.4 10.2 1
(7.50) 11125 10.5 1 25.3 41.8 45 50 41 205 42.8 50 50 42 507
11625 16 1 38.5 58.3 60 60 50 199 59.3 60 60 51 202
None - - - 22.5 25 25 21 101 23.0 25 25 22 102
10646 6 1 7.2 22.5 25 25 21 101 23.0 25 25 22 102
460-3-60 12.2 100 19 2.5 4.8 0.5
11146 11.5 1 13.8 22.1 25 25 21 101 22.6 25 25 22 102
11446 14 1 16.8 25.8 30 30 25 101 26.3 30 30 25 102
None - - - 47.1 50 60 50 288 49.3 50 60 53 298
11725 12 1 33.3 54 60 60 50 288 56.8 60 60 53 298
208-3-60 14.5 98 23 14.5 98 23 2.3 9.9 1.1 12525 18.6 1 51.6 76.9 80 80 71 288 79.6 80 80 73 298
13225 24 1 66.6 95.6 100 100 88 288 98.4 100 100 91 298
14225 31.8 2 88.3 122.8 125 125 113 288 125.5 150 150 115 298
None - - - 46.6 50 60 49 297 48.6 50 60 52 291
11725 16 1 38.5 59.9 60 60 55 297 62.4 70 70 57 291
09
230-3-60 14.5 98 23 14.5 98 23 2.3 9.4 1 12525 24.8 1 59.7 86.4 90 90 79 297 88.9 90 90 82 291
(8.5)
13225 32 1 77 108 110 110 99 297 110.5 125 125 102 291
14225 42.4 2 102 139.3 150 150 128 297 141.8 150 150 130 291
None - - - 21.5 25 25 23 162 22.5 25 25 24 158
11746 16.5 1 19.8 30.6 35 35 28 162 31.9 35 35 29 158
460-3-60 6.3 55 10 6.3 55 10 1.3 4.7 0.5 12846 27.8 1 33.4 47.6 50 50 44 162 48.9 50 50 45 158
13346 33 1 39.7 55.5 60 60 51 162 56.8 60 60 52 158
14246 41.7 2 50.2 68.6 70 70 63 162 69.9 70 70 64 158
None - - - 53.7 60 60 57 342 55.9 60 70 60 352
11725 12 1 33.3 58.5 60 60 57 342 61.3 70 70 60 352
208-3-60 16 110 25 15.6 110 24 2.3 13.5 1.1 12525 18.6 1 51.6 81.4 90 90 75 342 84.1 90 90 77 352
13225 24 1 66.6 100.1 110 110 92 342 102.9 110 110 95 352
14225 31.8 2 88.3 127.3 150 150 117 342 130 150 150 120 352
None - - - 53.6 60 60 57 342 55.6 60 70 59 337
11725 16 1 38.5 64.9 70 70 60 342 67.4 70 70 62 337
12
230-3-60 16 110 25 15.6 110 24 2.3 13.4 1 12525 24.8 1 59.7 91.4 100 100 84 342 93.9 100 100 86 337
(10)
13225 32 1 77 113 125 125 104 342 115.5 125 125 106 337
14225 42.4 2 102 144.3 150 150 133 342 146.8 150 150 135 337
None - - - 26.9 30 30 29 167 27.9 30 30 30 163
11746 16.5 1 19.8 33.1 35 35 30 167 34.4 35 35 32 163
460-3-60 7.8 52 12 7.8 52 12 1.3 6.7 0.5 12846 27.8 1 33.4 50.1 60 60 46 167 51.4 60 60 47 163
13346 33 1 39.7 58 60 60 53 167 59.3 60 60 55 163
14246 41.7 2 50.2 71.1 80 80 65 167 72.4 80 80 67 163

Johnson Controls Ducted Systems 51


5846585-YTG-A-1119

ZZ07-14 Hi Static Indoor Blower - Without Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 63.4 70 80 67 397 65.6 70 80 70 407
11725 12 1 33.3 63.4 70 80 67 397 65.6 70 80 70 407
208-3-60 19.6 136 31 19.6 136 31 5.8 13.5 1.1 12525 18.6 1 51.6 81.4 90 90 75 397 84.1 90 90 77 407
13225 24 1 66.6 100.1 110 110 92 397 102.9 110 110 95 407
14225 31.8 2 88.3 127.3 150 150 117 397 130 150 150 120 407
None - - - 62.7 70 80 66 393 64.7 70 80 69 398
11725 16 1 38.5 64.9 70 80 66 393 67.4 70 80 69 398
14
230-3-60 19.6 136 31 19.6 136 31 5.2 13.4 1 12525 24.8 1 59.7 91.4 100 100 84 393 93.9 100 100 86 398
(12.5)
13225 32 1 77 113 125 125 104 393 115.5 125 125 106 398
14225 42.4 2 102 144.3 150 150 133 393 146.8 150 150 135 398
None - - - 28.1 30 35 30 194 29.1 30 35 31 196
11746 16.5 1 19.8 33.1 35 35 30 194 34.4 35 35 32 196
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 6.7 0.5 12846 27.8 1 33.4 50.1 60 60 46 194 51.4 60 60 47 196
13346 33 1 39.7 58 60 60 53 194 59.3 60 60 55 196
14246 41.7 2 50.2 71.1 80 80 65 194 72.4 80 80 67 196

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

52 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-14 Hi Static Indoor Blower - With Powered Convenience Outlet

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 40.9 45 50 42 204 42 45 50 43 206
10625 4.9 1 13.6 40.9 45 50 42 204 42 45 50 43 206
208-3-60 17.6 136 27 4.4 10.2 1.1 8.6
11125 7.9 1 21.9 45.5 50 50 42 204 46.9 50 50 43 206
11625 12 1 33.3 59.8 60 60 55 204 61.1 70 70 56 206
None - - - 40.9 45 50 42 209 41.9 45 50 43 212
07 10625 6.5 1 15.6 40.9 45 50 42 209 41.9 45 50 43 212
230-3-60 17.6 136 27 4.4 10.2 1 8.6
(6) 11125 10.5 1 25.3 49.8 50 50 46 209 51 60 60 47 212
11625 16 1 38.5 66.3 70 70 61 209 67.5 70 70 62 212
None - - - 20.1 25 25 21 103 20.6 25 25 21 104
10646 6 1 7.2 20.1 25 25 16 103 20.6 25 25 17 104
460-3-60 8.5 66.1 13 2.5 4.8 0.5 8.6
11146 11.5 1 13.8 25.9 30 30 24 103 26.6 30 30 24 104
11446 14 1 16.8 29.7 30 30 27 103 30.3 35 35 28 104
None - - - 48.2 50 50 42 204 49.3 50 50 43 206
10625 4.9 1 13.6 48.2 50 50 42 204 49.3 50 50 43 206
208-3-60 25.0 164 39 4.4 10.2 1.1 8.6
11125 7.9 1 21.9 48.2 50 50 42 204 49.3 50 50 43 206
11625 12 1 33.3 60.4 70 70 61 209 61.5 70 70 56 206
None - - - 48.2 50 50 42 204 49.2 50 50 43 206
08 10625 6.5 1 15.6 43.2 50 50 42 204 44.2 45 50 43 212
230-3-60 25.0 164 39 4.4 10.2 1 8.6
(7.50) 11125 10.5 1 25.3 50.4 60 60 55 204 51.4 60 60 47 212
11625 16 1 38.5 66.9 70 70 61 209 67.9 70 70 62 212
None - - - 28.1 30 30 24 103 28.6 30 30 24 104
10646 6 1 7.2 28.1 30 30 27 103 28.6 30 30 24 104
460-3-60 12.2 100 19 2.5 4.8 0.5 8.6
11146 11.5 1 13.8 30.7 35 35 28 104 31.2 35 35 28 104
11446 14 1 16.8 34.4 35 35 28 104 34.9 35 35 28 104
None - - - 51.4 60 60 55 292 53.6 60 60 58 302
11725 12 1 33.3 59.4 60 60 55 292 62.1 70 70 58 302
208-3-60 14.5 98 23 14.5 98 23 2.3 9.9 1.1 8.6 12525 18.6 1 51.6 82.3 90 90 76 292 85 90 90 78 302
13225 24 1 66.6 101 110 110 93 292 103.8 110 110 95 302
14225 31.8 2 88.3 128.1 150 150 118 292 130.9 150 150 120 302
None - - - 50.9 60 60 54 301 52.9 60 60 57 296
11725 16 1 38.5 65.3 70 70 60 301 67.8 70 70 62 296
09
230-3-60 14.5 98 23 14.5 98 23 2.3 9.4 1 8.6 12525 24.8 1 59.7 91.8 100 100 84 301 94.3 100 100 87 296
(8.5)
13225 32 1 77 113.4 125 125 104 301 115.9 125 125 107 296
14225 42.4 2 102 144.6 150 150 133 301 147.1 150 150 135 296
None - - - 23.7 25 25 25 164 24.7 25 25 27 160
11746 16.5 1 19.8 33.3 35 35 31 164 34.6 35 35 32 160
460-3-60 6.3 55 10 6.3 55 10 1.3 4.7 0.5 8.6 12846 27.8 1 33.4 50.3 60 60 46 164 51.6 60 60 47 160
13346 33 1 39.7 58.2 60 60 54 164 59.4 60 60 55 160
14246 41.7 2 50.2 71.3 80 80 66 164 72.6 80 80 67 160
None - - - 58 60 70 62 346 60.2 70 70 65 356
11725 12 1 33.3 63.9 70 70 62 346 66.6 70 70 65 356
208-3-60 16 110 25 15.6 110 24 2.3 13.5 1.1 8.6 12525 18.6 1 51.6 86.8 90 90 80 346 89.5 90 90 82 356
13225 24 1 66.6 105.5 110 110 97 346 108.3 110 110 100 356
14225 31.8 2 88.3 132.6 150 150 122 346 135.4 150 150 125 356
None - - - 57.9 60 70 62 346 59.9 60 70 64 341
11725 16 1 38.5 70.3 80 80 65 346 72.8 80 80 67 341
12
230-3-60 16 110 25 15.6 110 24 2.3 13.4 1 8.6 12525 24.8 1 59.7 96.8 100 100 89 346 99.3 100 100 91 341
(10)
13225 32 1 77 118.4 125 125 109 346 120.9 125 125 111 341
14225 42.4 2 102 149.6 150 150 138 346 152.1 175 175 140 341
None - - - 29.1 30 35 31 169 30.1 35 35 32 165
11746 16.5 1 19.8 35.8 40 40 33 169 37.1 40 40 34 165
460-3-60 7.8 52 12 7.8 52 12 1.3 6.7 0.5 8.6 12846 27.8 1 33.4 52.8 60 60 49 169 54.1 60 60 50 165
13346 33 1 39.7 60.7 70 70 56 169 61.9 70 70 57 165
14246 41.7 2 50.2 73.8 80 80 68 169 75.1 80 80 69 165

Johnson Controls Ducted Systems 53


5846585-YTG-A-1119

ZZ07-14 Hi Static Indoor Blower - With Powered Convenience Outlet (Continued)

Min Max Min


Min Max Min Fuse2/ Fuse2/ Discon-
OD Electric Heat MCA1
Nominal Supply Pwr Pwr 2
Fuse / 2
Fuse / Discon- Breaker3 Breaker3 nect
Size Compressor 1 Compressor 2 Fan Field Installed KitMCA1 w/Pwr
Unit Blower Exh Conv Breaker3 Breaker3 nect Size Size
(Tons) Motors 2EK045* (Amps) 4 Exh Rating4/
Voltage Motor Motor Outlet Size Size Rating w/ w/
(each) (Amps) Pwr Exh
(Amps) (Amps) Pwr Exh Pwr Exh
(Amps) (Amps)
RLA LRA MCC RLA LRA MCC Model kW Stages Amps FLA LRA FLA LRA
None - - - 67.7 70 80 72 401 69.9 70 80 75 411
11725 12 1 33.3 67.7 70 80 72 401 69.9 70 80 75 411
208-3-60 19.6 136 31 19.6 136 31 5.8 13.5 1.1 8.6 12525 18.6 1 51.6 86.8 90 90 80 401 89.5 90 90 82 411
13225 24 1 66.6 105.5 110 110 97 401 108.3 110 110 100 411
14225 31.8 2 88.3 132.6 150 150 122 401 135.4 150 150 125 411
None - - - 67 70 80 71 397 69 70 80 74 402
11725 16 1 38.5 70.3 80 80 71 397 72.8 80 80 74 402
14
230-3-60 19.6 136 31 19.6 136 31 5.2 13.4 1 8.6 12525 24.8 1 59.7 96.8 100 100 89 397 99.3 100 100 91 402
(12.5)
13225 32 1 77 118.4 125 125 109 397 120.9 125 125 111 402
14225 42.4 2 102 149.6 150 150 138 397 152.1 175 175 140 402
None - - - 30.3 35 35 32 196 31.3 35 35 34 199
11746 16.5 1 19.8 35.8 40 40 33 196 37.1 40 40 34 199
460-3-60 8.2 66.1 13 8.2 66.1 13 2.9 6.7 0.5 8.6 12846 27.8 1 33.4 52.8 60 60 49 196 54.1 60 60 50 199
13346 33 1 39.7 60.7 70 70 56 196 61.9 70 70 57 199
14246 41.7 2 50.2 73.8 80 80 68 196 75.1 80 80 69 199

1. Minimum Circuit Ampacity.


2. Dual Element, Time Delay Type.
3. HACR type per NEC.
4. Non-fused Disconnect, Verify on the unit nameplate that the disconnect is properly sized for the application. Units with field installed
electric heat kits may exceed the factory installed disconnect amperage rating.

54 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical Wiring Diagrams


ZZ07-14 Typical Wiring Diagrams

Typical ZZ07/08 Cooling Unit w/wo Electric Heat 208/230-3-60 Belt Drive - Elementary Diagram Power Circuit

Johnson Controls Ducted Systems 55


5846585-YTG-A-1119

Typical ZZ07/08 Cooling Unit w/wo Electric Heat 460-3-60 Belt Drive - Elementary Diagram Power Circuit

56 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical ZZ09, ZZ12 Cooling Unit w/wo Gas Heat 208/230-3-60 Belt Drive Elementary Diagram Power Circuit

Johnson Controls Ducted Systems 57


5846585-YTG-A-1119

Typical ZZ14 Cooling Unit w/wo Gas Heat 208/230-3-60 Belt Drive Elementary Diagram Power Circuit

58 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical ZZ09, ZZ12 Cooling Unit w/wo Gas Heat 460-3-60 Belt Drive Elementary Diagram Power Circuit

Johnson Controls Ducted Systems 59


5846585-YTG-A-1119

Typical ZZ14 Cooling Unit w/wo Gas Heat 460-3-60 Belt Drive Elementary Diagram Power Circuit

60 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical ZZ07/08 Cooling Unit w/wo Electric Heat Belt Drive - Elementary Diagram Control Circuit

Johnson Controls Ducted Systems 61


5846585-YTG-A-1119

Typical ZZ07-08 Cooling Unit with Gas Heat Belt Drive - Elementary Diagram Control Circuit

62 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical ZZ09 Cooling Unit Belt Drive Elementary Diagram Control Circuit

Johnson Controls Ducted Systems 63


5846585-YTG-A-1119

Typical ZZ09 Cooling Unit with Gas Heat Belt Drive Elementary Diagram Control Circuit

64 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical ZZ12/14 Cooling Unit Belt Drive Elementary Diagram Control Circuit

Johnson Controls Ducted Systems 65


5846585-YTG-A-1119

Typical ZZ12/14 Cooling Unit with Gas Heat Belt Drive Elementary Diagram Control Circuit

66 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Typical FDD Elementary Wiring Diagram

Johnson Controls Ducted Systems 67


5846585-YTG-A-1119

Weights and Dimensions


ZZ07-14 Unit Weights
Unit 4 Point Load Weight Unit 6 Point Load Weight

Unit Center Of Gravity

X
Y

FRONT
LEFT

68 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZE07-14 Corner Weights

Size Weight (lbs.) Center of Gravity 4 point Load Location (lbs.) 6 point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
07
ZZE 634 614 34 25 168 146 139 160 115 104 95 91 99 109
(6)
08
ZZE 617 612 33.6 24.8 170 141 137 165 117 103 91 88 100 113
(7.5)
09
ZZE 857 852 46 36 230 262 192 168 150 163 178 131 120 110
(8.5)
12
ZZE 884 879 46 36 242 271 193 172 158 171 184 131 122 113
(10)
14
ZZE 946 941 45 36 265 284 203 189 175 183 192 137 130 125
(12.5)

ZZG07-14 Corner Weights

Size Weight (lbs.) Center of Gravity 4 point Load Location (lbs.) 6 point Load Location (lbs.)
Model
(Tons) Shipping Operating X Y A B C D A B C D E F
07
ZZG 688 668 34 25 183 159 152 174 125 114 104 99 108 119
(6)
08
ZZG 671 666 33.6 24.8 185 153 149 179 127 112 99 96 109 123
(7.5)
09
ZZG 959 954 45 36 269 291 205 189 177 186 197 138 131 125
(8.5)
12
ZZG 990 985 45 37 284 301 206 194 187 195 203 139 133 128
(10)
14
ZZG 1052 1047 44 37 304 312 218 212 202 205 209 146 144 141
(12.5)

ZZ07-14 Unit Accessory Weights


Unit Accessory Weights (lbs.)
Powered Convenience Outlet Factory installed 35
Non-Powered Convenience Outlet Factory Installed 10
Vertical Flow Dry Bulb Economizer Small Footprint 63
Vertical Flow Dry Bulb Economizer Large Footprint 96
Horizontal Flow Dry Bulb Economizer Small Footprint Short 75
Horizontal Flow Dry Bulb Economizer Small Footprint Tall 81
Horizontal Flow Dry Bulb Economizer Large Footprint Short 105
Horizontal Flow Dry Bulb Economizer Large Footprint Tall 102
Power Exhaust Vert Flow Small Footprint 39
Power Exhaust Vert Flow Large Footprint 39
Power Exhaust Horiz Flow Small Footprint 39
Power Exhaust Horiz Flow Large Footprint 39
Hail Guard Kit Small Short Factory Installed 19
Hail Guard Kit Small Tall Factory Installed 24
Hail Guard Kit Large Short Factory Installed 50
Hail Guard Kit Large Tall Factory Installed 50
Flue Extension Kit (1FE0414) 15
Flue Extension Kit (1FE0415) 17
Flue Extension Kit (1FE0416) 19
Curb Rigid 14" Small Footprint 145
Curb Rigid 14" Large Footprint 135
Curb Rigid 24" Small Footprint 135
Curb Rigid 24" Large Footprint 135

Johnson Controls Ducted Systems 69


5846585-YTG-A-1119
ZZ07-14 Unit Dimensions
ZZ07 and ZZ08

70 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ09 and ZZ12

Johnson Controls Ducted Systems 71


5846585-YTG-A-1119

ZZ14

72 Johnson Controls Ducted Systems


5846585-YTG-A-1119

ZZ07-08 Unit Clearances ZZ09-14 Unit Clearances


Direction Distance (in.) Direction Distance (in.) Direction Distance (in.) Direction Distance (in.)
Top 1
72 Right 18 Top1 72 Right 18
Front 36 Left 12 Front 48 Left 12
Rear 2
18 /36 3
Bottom 4
1 Rear 182/363 Bottom4 1

1. Units must be installed outdoors. Over hanging structure or 1. Units must be installed outdoors. Over hanging structure or
shrubs should not obscure condenser air discharge outlet. shrubs should not obscure condenser air discharge outlet.
2. Units without economizer or power exhaust. 2. Units without economizer or power exhaust.
3. Units equipped with an Economizer or Power Exhaust. Flue 3. Units equipped with an Economizer or Power Exhaust. Flue
products must not be discharged within 10 Feet of the rear of products must not be discharged within 10 Feet of the rear of
the unit. the unit.
4. Units may be installed on combustible floors made from 4. Units may be installed on combustible floors made from wood
wood or class A, B or C roof covering materials. or class A, B or C roof covering materials.

ZZ07-14 Unit Roof Curb Dimensions


1RC0456, 1RC0458 Roof Curb Dimensions

70.875 O.D.

67.375 I.D.

RN
32.188

RETU
RN
TU
RE

13.781

3.000

LY
37.188

PP
I.D.

SU
RIGHT
LY

23.591 11.961 20.406


PP

FRONT
SU

RIGHT
4.961 14.000
5.422 FRONT
17.781

40.688 O.D.

70.871 40.684

1RC0456 X= 14" Height


1RC0458 X= 24" Height

Notes:
1. Sides, ends and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.
2. Full perimeter wood nailer.
3. Insulated deck pans.

NOTE: If utilities are required thru the base of the unit or thru
Unit Models used with 1RC0456, 1RC0458 Roof Curb the roof curb the following field installed accessories
ZZ07 can be purchased thru your dealer or contractor:
ZZ08 1TB0401 - Thru the base electrical and thru the curb gas
1TB0403 - Thru the base electrical and gas

Johnson Controls Ducted Systems 73


5846585-YTG-A-1119

1RC0457, 1RC0459 Roof Curb Dimensions

81.750 O.D.

78.250 I.D.

40.188

RN

RN
TU

RETU
RE
15.469

3.000

50.000
I.D. RIGHT

LY

LY
PP

PP
34.313 31.531

SU

SU
11.417
15.813
FRONT
6.043 RIGHT
4.173

26.000
FRONT 24.813

84.000 O.D. 53.500 O.D.

81.746 53.496

1RC0457 X= 14" Height


1RC0459 X= 24" Height
Notes:
1. Sides, ends, unit locator and cross support are 18-G90. Deck pans, R/A & S/A supports are 20-G90.
2. Full perimeter wood nailer.
3. Insulated deck pans.

NOTE: If utilities are required thru the base of the unit or thru
Unit Models used with 1RC0457, 1RC0459 Roof Curb the roof curb the following field installed accessories
ZZ09 can be purchased thru your dealer or contractor:
ZZ12 1TB0402 - Thru the base electrical and thru the curb gas
ZZ14 1TB0404 - Thru the base electrical and gas

74 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Economizer Options
Economizer Usage
Application Description Accessory Kit Number
Econ, DB, Vertical Flow, Small Footprint 2EE04706724
Economizer Vertical Flow
Econ, DB, Vertical Flow, Large Footprint 2EE04706824
Econ, DB, Horizontal Flow, Small Footprint, Short Cabinet 2EE04707024
Econ, DB, Horizontal Flow, Small Footprint, Tall Cabinet 2EE04707124
Economizer Horizontal Flow
Econ, DB, Horizontal Flow, Large Footprint, Short Cabinet 2EE04707224
Econ, DB, Horizontal Flow, Large Footprint, Tall Cabinet 2EE04707324
Power Exhaust Vert Flow Small Footprint 208V-230V 3-ph 2PE04704225
Power Exhaust Vert Flow Small Footprint 460V 3-ph 2PE04704246
Power Exhaust Vertical Flow Power Exhaust Vert Flow Large Footprint 208V-230V 1-ph 2PE04704306
Power Exhaust Vert Flow Large Footprint 208V-230V 3-ph 2PE04704325
Power Exhaust Vert Flow Large Footprint 460V 3-ph 2PE04704346
Power Exhaust Horiz Flow Small Footprint 208V-230V 3-ph 2PE04704425
Power Exhaust Horiz Flow Small Footprint 460V 3-ph 2PE04704446
Power Exhaust Horizontal Flow
Power Exhaust Horiz Flow Large Footprint 208V-230V 3-ph 2PE04704525
Power Exhaust Horiz Flow Large Footprint 460V 3-ph 2PE04704546
Field Installed Vertical Flow Economizer

Johnson Controls Ducted Systems 75


5846585-YTG-A-1119

Field Installed Vertical Flow Economizer W/Power Exhaust

Field Installed Horizontal Flow Economizer

76 Johnson Controls Ducted Systems


5846585-YTG-A-1119

Field Installed Horizontal Flow Economizer W/Power Exhaust

Johnson Controls Ducted Systems 77


5846585-YTG-A-1119

Guide Specifications

YORK® GUIDE MECHANICAL SPECIFICATIONS


SINGLE PACKAGE AIR CONDITIONERS

7 THRU 12-1/2 NOMINAL TONS

Sun™ Core SERIES

Size Range: 7 to 12 1/2 Tons Nominal Cooling

70,000 to 200000 BTUH Nominal Gas Heating Output

Model Series: ZZ

DIVISION 23 – HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

Number Title

23 00 00 HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)


23 06 00 Schedules for HVAC
23 06 80 Schedules for Decentralized HVAC Equipment

23 06 80.13 Decentralized Unitary HVAC Equipment Schedule


23 06 80.13.A. Rooftop unit schedule
23 07 00 HVAC Insulation
23 07 16 HVAC Equipment Insulation

23 07 16.13 Decentralized, Rooftop Units:


23 07 16.13.A. Evaporator fan compartment:
1. Interior cabinet surfaces shall be insulated with a minimum 1/2- in. thick, minimum 1 1/2 lb density, flexible
fiberglass insulation coated on the air side.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 07 16.13.B. Gas heat compartment:
1. Aluminum foil- faced fiberglass insulation shall be used.
2. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
23 09 00 Instrumentation and Control for HVAC
23 09 13 Instrumentation and Control Devices for HVAC

23 09 13.23 Sensors and Transmitters


23 09 13.23.A. Thermostats

78 Johnson Controls Ducted Systems


5846585-YTG-A-1119

1. Thermostat must

48HC
a. energize “G” when calling for fan only or continuous fan.
b. have capability to energize 2 different stages of cooling, and 2 different stages of heating.
c. include capability for occupancy scheduling.
23 09 23 Direct- digital Control system for HVAC

23 09 23.13 Decentralized, Rooftop Units:


23 09 23.13.A. Smart Equipment™ (Unit based microprocessor control)
1. Shall be ASHRAE 62 compliant.
2. Shall include an integrated economizer controller to support an economizer with 2 to 10 v DC actuator input.
3. Controller shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature,
indoor air quality, outdoor air quality, indoor relative humidity, compressor lockout, fire shutdown, enthalpy,
fan status, remote time clock/door switch.
4. Shall accept a CO2 sensor in the conditioned space, and be Demand Control Ventilation ready.
5. Unit shall provide surge protection for the controller through a circuit breaker.
6. Shall have an LED display independently showing the status of activity on the communication bus, and
processor operation.
7. Software upgrades will be accomplished by local download. Software upgrades through chip replacements
are not allowed.
A. Unit shall be complete with self-contained low-voltage control circuit protected by a resettable circuit breaker
on the 24-volt transformer side.
B. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit
should any of the following standard safety devices trip and shut off compressor:
C. Loss-of-charge/Low-pressure switch.
D. High-pressure switch.
E. Freeze-protection temperature sensor, evaporator coil. If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped.
F. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection.
G. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up.
H. Unit control board shall have on-board diagnostics and fault code display.
I. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down
to 0 ºF.
J. Control board shall monitor each refrigerant safety switch independently.
K. Control board shall retain last 5 fault codes in non-volatile memory, which will not be lost in the event of a
power loss.

23 09 23.13.B. RTU Open - multi- protocol, direct digital controller:


1. Shall be ASHRAE 62 compliant.
2. Shall include built- in protocol for BACNET , Modbus , and Johnson N2.
3. Shall allow access of up to 62 network variables (SNVT). Shall be compatible with all open controllers
4. Baud rate Controller shall be selectable using a dip switch.
5. Shall have an LED display independently showing the status of serial communication, running, errors, power,
all digital outputs, and all analog inputs.
6. Shall accept the following inputs: space temperature, setpoint adjustment, outdoor air temperature, indoor air
quality, outdoor air quality, compressor lock- out, fire shutdown, enthalpy switch, and fan status/filter status/
humidity/ remote occupancy.

Johnson Controls Ducted Systems 79


5846585-YTG-A-1119

7. Software upgrades will be accomplished by either local or remote download. No software upgrades through
chip replacements are allowed.
23 09 33 Electric and Electronic Control System for HVAC

23 09 33.13 Decentralized, Rooftop Units:


23 09 33.13.A. General:
1. Shall be complete with self- contained low- voltage control circuit protected by a resettable circuit breaker on
the 24- v transformer side. Transformer shall have 75VA capability.
2. Shall utilize color- coded wiring.
3. Shall include a central control terminal board to conveniently and safely provide connection points for vital
control functions such as: smoke detectors, phase monitor, gas controller, economizer, thermostat, DDC
control options, and low and high pressure switches.
4. The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor. See heat
exchanger section of this specification.
23 09 33.23.B. Safeties:
1. Compressor over- temperature, over- current. High internal pressure differential.
2. Low- pressure switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross- wiring of the safety switches between circuits
1 and 2.
b. Low pressure switch shall use different color wire than the high pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
3. High- pressure switch.
a. Units with 2 compressors shall have different sized connectors for the circuit 1 and circuit 2 low and high
pressure switches. They shall physically prevent the cross- wiring of the safety switches between circuits
1 and 2.
b. High pressure switch shall use different color wire than the low pressure switch. The purpose is to assist
the installer and service technician to correctly wire and or troubleshoot the rooftop unit.
4. Automatic reset, motor thermal overload protector.
5. Heating section shall be provided with the following minimum protections:
a. High- temperature limit switches.
b. Induced draft motor speed sensor.
c. Flame roll-out switch.
d. Flame proving controls
23 09 93 Sequence of Operations for HVAC Controls

23 09 93.13 Decentralized, Rooftop Units:


23 09 93.13 INSERT SEQUENCE OF OPERATION
23 40 13 Panel Air Filters

23 40 13.13 Decentralized, Rooftop Units:


23 40 13.13.A. Standard filter section
1. Shall consist of factory- installed, low velocity, disposable 2” or 4” thick fiberglass filters of commercially
available sizes.
2. Units can accept 2” or 4” filters and have a field convertible toolless

80 Johnson Controls Ducted Systems


5846585-YTG-A-1119

3. Filters shall be accessible through an access panel with toolless removal as described in the unit cabinet
section of this specification (23 81 19.13.H).
23 81 19 Self- Contained Air Conditioners

23 81 19.13 Small- Capacity Self- Contained Air Conditioners


23 81 19.13.A. General
1. Outdoor, rooftop mounted, electrically controlled, heating and cooling unit utilizing a fully hermetic scroll
compressor(s) for cooling duty and gas combustion for heating duty.
2. Factory assembled, single- piece heating and cooling rooftop unit. Contained within the unit enclosure shall
be all factory wiring, piping, controls, and special features required prior to field start- up.
3. Unit shall use environmentally sound, R-410A refrigerant.
4. Unit shall be installed in accordance with the manufacturer’s instructions.
5. Unit must be selected and installed in compliance with local, state, and federal codes.
23 81 19.13.B. Quality Assurance
1. Unit meets ASHRAE 90.1 minimum efficiency requirements.
2. Unit shall be rated in accordance with AHRI Standards 210/240 or 340/360.
3. Unit shall be designed to conform to ASHRAE 15.
4. Unit shall be UL- tested and certified in accordance with ANSI Z21.47 -2012/CSA 2.3-2012, CSA C22.2 No.
236-11 (UL 1995) 4th edition and CSA C22.2 No. 3 - M 1988.
5. Insulation and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
6. Unit casing shall be capable of withstanding 750-hour salt spray exposure per ASTM B117 (scribed
specimen).
7. Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered by ISO
9001.
8. Roof curb shall be designed to conform to NRCA Standards.
9. Unit shall be subjected to a completely automated run test on the assembly line. The data for each unit will be
stored at the factory, and must be available upon request.
10. Unit shall be designed in accordance with UL Standard 1995, including tested to withstand rain.
11. Unit shake tested to assurance level 1, ASTM D4169 to ensure shipping reliability.
12. High Efficient Motors listed shall meet section 313 of the Energy Independence and Security Act of 2007
(EISA 2007).
23 81 19.13.C. Delivery, Storage, and Handling
1. Unit shall be stored and handled per manufacturer’s recommendations.
23 81 19.13.E. Project Conditions
1. As specified in the contract.
23 81 19.13.F. Operating Characteristics
1. Unit shall be capable of starting and running at 125°_F (52°_C) ambient outdoor temperature, meeting
maximum load criteria of AHRI Standard 210/240 or 340/360 at ± 10% voltage.
2. Compressor with standard controls shall be capable of operation down to 0°_F (2°_C), ambient outdoor
temperatures. See below for head pressure control package or winter start kit.
3. Unit shall discharge supply air vertically or horizontally as shown on contract drawings.
4. Unit shall be factory configured for vertical supply & return configurations.
5. Unit shall be field convertible from vertical to horizontal airflow on all models.
6. Unit shall be capable of mixed operation: vertical supply with horizontal return or horizontal supply with vertical
return.
23 81 19.13.G. Electrical Requirements
1. Main power supply voltage, phase, and frequency must match those required by the manufacturer.
23 81 19.13.H. Unit Cabinet

Johnson Controls Ducted Systems 81


5846585-YTG-A-1119

1. Unit cabinet shall be constructed of galvanized steel with exterior surfaces coated with a non-chalking,
powder paint finish, certified at 750-hour salt spray test per ASTM-B117 standards.
2. Evaporator fan compartment interior cabinet insulation shall conform to AHRI Standards 210/240 or 340/360
minimum exterior sweat criteria. Interior surfaces shall be insulated with a minimum 1/2- in. thick, 1 1/2 lb
density, flexible fiberglass insulation, neoprene coated on the air side. Aluminum foil- faced fiberglass
insulation shall be used in the gas heat compartment. Fan shall be a belt drive assembly and include an
adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate
horsepower rating plus the service factor (Only premium efficiency motors have hp rating on the nameplate).
Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with forward
curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no
maintenance.
Condenser Fan Assembly: The outdoor fans shall be of the direct drive type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected
against overload conditions and staged independently.
3. Base of unit shall have a minimum of four locations for thru- the- base gas and electrical connections (factory
installed or field installed), standard.
4. Base Rail
a. Unit shall have base rails on a minimum of 4 sides.
b. Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead
rigging.
c. Holes shall be provided in the base rail for moving the rooftop by fork truck.
d. Base rail shall be a minimum of 16 gauge thickness.
5. Condensate pan and connections:
a. Shall be an internally sloped condensate drain pan made of a non- corrosive material. b. Shall comply with
ASHRAE Standard 62.
c. Shall use a 3/4” - 14 NPT drain connection, possible either through the bottom or side of the drain pan.
Connection shall be made per manufacturer’s recommendations.
6. Top panel:
a. Shall be a single piece top panel.
7. Gas Connections:
a. All gas piping connecting to unit gas valve shall enter the unit cabinet at a single location on side of unit
b. Thru- the- base capability
(1.) Standard unit shall have a thru- the- base gas- line location using a raised, embossed portion of the
unit base-pan.
(2.) Optional, factory- approved, water- tight connection method must be used for thru- the- base gas
connections.
(3.) No base-pan penetration, other than those authorized by the manufacturer, is permitted.
8. Electrical Connections
a. All unit power wiring shall enter unit cabinet at a single, factory- prepared, knockout location. b. Thru- the-
base capability.
(1.) Standard unit shall have a thru- the- base electrical location (s) using a raised, embossed portion of the
unit base-pan.
(2.) Optional, factory- approved, water- tight connection method must be used for thru- the- base electrical
connections.
(3.) No base-pan penetration, other than those authorized by the manufacturer, is permitted.

82 Johnson Controls Ducted Systems


5846585-YTG-A-1119

9. Component access panels (standard)


a. Cabinet panels shall be easily removable for servicing.
b. Unit shall have one factory installed, toolless, removable, filter access panel.
c. Panels covering control box, indoor fan, indoor fan motor, gas components (where applicable), and
compressors shall have a molded composite handles.
d. Handles shall be UV modified, composite. They shall be permanently attached, and recessed into the
panel.
e. Screws on the vertical portion of all removable access panel shall engage into heat resistant, molded
composite collars.
f. Collars shall be removable and easily replaceable using manufacturer recommended parts.
23 81 19.13.I. Gas Heat
1. General
a. Heat exchanger shall be an induced draft design. Positive pressure heat exchanger designs shall not be
allowed.
b. Shall incorporate a direct- spark ignition system and redundant main gas valve.
c. Gas supply pressure at the inlet to the rooftop unit gas valve must match that required by the manufacturer.
2. The heat exchanger shall be controlled by an integrated gas controller (IGC) microprocessor.
a. IGC board shall notify users of fault using an LED (light- emitting diode).
b. The LED shall be visible without removing the control box access panel.
c. IGC board shall contain algorithms that modify evaporator- fan operation to prevent future cycling on high
temperature limit switch.
d. Unit shall be equipped with anti- cycle protection with one short cycle on unit flame roll-out switch or 4
continuous short cycles on the high temperature limit switch. Fault indication shall be made using an LED.
3. Standard Heat Exchanger construction
a. Heat exchanger shall be of the tubular- section type constructed of a minimum of 20- gauge steel coated
with a nominal 1.2 mil aluminum- silicone alloy for corrosion resistance.
b. Burners shall be of the in- shot type constructed of aluminum- coated steel.
c. Burners shall incorporate orifices for rated heat output up to 2000 ft (610m) elevation. Additional accessory
kits may be required for applications above 2000 ft (610m) elevation, depending on local gas supply
conditions.
d. Each heat exchanger tube shall contain multiple dimples for increased heating effectiveness.
4. Optional Stainless Steel Heat Exchanger construction a. Use energy saving, direct- spark ignition system. b.
Use a redundant main gas valve.
c. Burners shall be of the in- shot type constructed of aluminum- coated steel.
d. All gas piping shall enter the unit cabinet at a single location on side of unit (horizontal plane).
e. The optional stainless steel heat exchanger shall be of the tubular- section type, constructed of a minimum
of 20- gauge type 409 stainless steel.
f. Type 409 stainless steel shall be used in heat exchanger tubes and vestibule plate
g. Complete stainless steel heat exchanger allows for greater application flexibility.
23 81 19.13.J. Coils
1. Standard Aluminum Fin/Copper Tube Coils:
a. Standard evaporator and condenser coils shall have aluminum lanced plate fins mechanically bonded to
seamless internally grooved copper tubes with all joints brazed.
b. Evaporator coils shall be leak tested to 150 psig, pressure tested to 450 psig, and qualified to CSA C22.2
No. 236-11 (UL 1995) 4th edition burst test at 1775 psig.
c. Condenser coils shall be leak tested to 150 psig, pressure tested to 650 psig, and qualified to CSA C22.2
No. 236-11 (UL 1995) 4th edition burst test at 1980 psig.
2. Optional EFIN- coated aluminum- fin evaporator and condenser coils:

Johnson Controls Ducted Systems 83


5846585-YTG-A-1119

a. Shall have a durable epoxy- phenolic coating to provide protection in mildly corrosive coastal
environments.
b. Coating shall be applied to the aluminum fin stock prior to the fin stamping process to create an inert barrier
between the aluminum fin and copper tube.
c. Epoxy- phenolic barrier shall minimize galvanic action between dissimilar metals.
23 81 19.13.K. Refrigerant Components
1. Refrigerant circuit shall include the following control, safety, and maintenance features:
a. Thermostatic Expansion Valve (TXV) shall help provide optimum performance across the entire operating
range. Shall contain removable power element to allow change out of power element and bulb without
removing the valve body. (Orifice on ZZ09, ZZ12)
b. Refrigerant filter drier - Solid core design.
c. Service gauge connections on suction and discharge lines.
d. Pressure gauge access through a specially designed access port in the top panel of the unit.
2. There shall be gauge line access port in the skin of the rooftop, covered by a black, removable plug.
a. The plug shall be easy to remove and replace.
b. When the plug is removed, the gauge access port shall enable maintenance personnel to route their
pressure gauge lines.
c. This gauge access port shall facilitate correct and accurate condenser pressure readings by enabling the
reading with the compressor access panel on.
d. The plug shall be made of a leak proof, UV- resistant, composite material.
3. Compressors
a. Unit shall use fully hermetic, scroll compressor for each independent refrigeration circuit.
b. Compressor motors shall be cooled by refrigerant gas passing through motor windings.
c. Compressors shall be internally protected from high discharge temperature conditions.
d. Compressors shall be protected from an over- temperature and over- amperage conditions by an internal,
motor overload device.
e. Compressor shall be factory mounted on rubber grommets.
f. Compressor motors shall have internal line break thermal, current overload and high pressure differential
protection.
g. Crankcase heaters shall not be required for normal operating range, unless provided by the factory.
23 81 19.13.L. Filter Section
1. Filters access is specified in the unit cabinet section of this specification.
3. Shall consist of factory- installed, low velocity, throw- away 2” or 4” thick fiberglass filters.
3. Units can accept 2” or 4” filters and have a field convertible toolless
23 81 19.13.M. Evaporator Fan and Motor
1. Evaporator fan motor:
a. Shall have permanently lubricated bearings.
b. Shall have inherent automatic reset thermal protection (Only on single-phase, belt-drive motors, three -
phase, belt-drive motors have internal thermostat used for external line-break control.).
2. Belt- driven Evaporator Fan:
a. Belt drive shall include an adjustable- pitch motor pulley.
b. Shall use sealed, permanently lubricated ball- bearing type.
c. Blower fan shall be double- inlet type with forward- curved blades.
d. Shall be constructed from steel with a corrosion resistant finish and dynamically balanced.
23 81 19.13.N. Condenser Fans and Motors
The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically balanced for smooth operation. The outdoor fan motors shall

84 Johnson Controls Ducted Systems


5846585-YTG-A-1119

have permanently lubricated 60°C ball bearings internally protected against overload conditions and staged
independently. A cleaning window shall be provided on two sides of the units for coil cleaning.
1. Condenser fan motors:
a. Shall be a totally enclosed motor.
b. Shall use permanently lubricated bearings.
c. Shall have inherent thermal overload protection with an automatic reset feature.
d. All models Shall use a shaft- down design except shaft- up on ZZ14 size with rain shield.
2. Condenser Fans:
a. Shall be a direct- driven propeller type fan.
b. Shall have galvanized steel blades riveted to corrosion- resistant steel spiders and shall be dynamically
balanced.
3. Standard Integrated Economizers:
a. Integrated, gear- driven opposing modulating blade design type capable of simultaneous economizer and
compressor operation.
b. Independent modules for vertical or horizontal return configurations shall be available. Vertical return
modules shall be available as a factory installed option.
c. Damper blades shall be galvanized steel with composite gears. Plastic or composite blades on intake or
return shall not be acceptable.
d. Shall include all hardware and controls to provide free cooling with outdoor air when temperature and/or
humidity are below set-points.
e. Shall be equipped with gear driven dampers for both the outdoor ventilation air and the return air for
positive air stream control.
f. Standard models shall be equipped with low- leakage dampers, not to exceed 2% leakage at 1 in. wg pres-
sure differential. Economizers will come with Actuator and module that is tied to Smart Equipment™:
(1.) Combined minimum and DCV maximum damper position potentiometers with compressor staging re-
lay.
(2.) Functions with solid state analog enthalpy or dry bulb changeover control sensing.
(3.) Contain LED indicates for: when free cooling is available when module is in DCV mode when exhaust
fan contact is closed
4. Two- Position Damper
a. Damper shall be a Two- Position Damper. Damper travel shall be from the full closed position to the field
adjustable %- open setpoint.
b. Damper shall include adjustable damper travel from 25% to 100% (full open).
c. Damper shall include single or dual blade, gear driven dampers and actuator motor.
d. Actuator shall be direct coupled to damper gear. No linkage arms or control rods shall be acceptable. e.
Damper will admit up to 100% outdoor air for applicable rooftop units.
f. Damper shall close upon indoor (evaporator) fan shutoff and/or loss of power.
g. The damper actuator shall plug into the rooftop unit’s wiring harness plug. No hard wiring shall be required.
h. Outside air hood shall include aluminum water entrainment filter.
5. Manual damper
a. Manual damper package shall consist of damper, air inlet screen, and rain hood which can be preset to admit
up to 25 or 50% outdoor air for year round ventilation.
6. Condenser Coil Hail Guard Assembly (Factory and Field installed on all models):
a. Shall protect against damage from hail.
b. Shall be of louvered style.
7. Unit- Mounted, Non- Fused Disconnect Switch: (Verify on the unit nameplate that the disconnect is properly sized
for the application. Units with field installed electric heat may exceed the factory installed disconnect amperage
rating.)

Johnson Controls Ducted Systems 85


a. Switch shall be factory- installed, internally mounted.
b. National Electric Code (NEC) and UL approved non- fused switch shall provide unit power shutoff.
c. Shall be accessible from outside the unit.
d. Shall provide local shutdown and lockout capability.
8. Thru- the- Base Connectors:
a. Kits shall provide connectors to permit gas and electrical connections to be brought to the unit through the unit
base-pan.
b. Minimum of four connection locations per unit.
9. Propeller Power Exhaust:
a. Power exhaust shall be used in conjunction with an integrated economizer.
b. Independent modules for vertical or horizontal return configurations shall be available. c. Horizontal power
exhaust is shall be mounted in return ductwork.
d. Power exhaust shall be controlled by economizer controller operation. Exhaust fans shall be energized when
dampers open past the 0- 100% adjustable setpoint on the economizer control.
10. Roof Curbs (Vertical):
a. Full perimeter roof curb with exhaust capability providing separate air streams for energy recovery from the
exhaust air without supply air contamination.
b. Formed galvanized steel with wood nailer strip and shall be capable of supporting entire unit weight. c.
Permits installation and securing of ductwork to curb prior to mounting unit on the curb.
11. High Altitude Gas Conversion Kit:
a. Package shall contain all the necessary hardware and instructions to convert a standard natural gas.
12. Outdoor Air Enthalpy Sensor:
a. The outdoor air enthalpy sensor shall be used to provide single enthalpy control. When used in conjunction
with a return air enthalpy sensor, the unit will provide differential enthalpy control. The sensor allows the unit
to determine if outside air is suitable for free cooling.
13. Return Air Enthalpy Sensor:
a. The return air enthalpy sensor shall be used in conjunction with an outdoor air enthalpy sensor to provide
differential enthalpy control.
14. Indoor Air Quality (CO2) Sensor:
a. Shall be able to provide demand ventilation indoor air quality (IAQ) control.
b. The IAQ sensor shall be available in duct mount, wall mount, or wall mount with LED display. The set- point
shall have adjustment capability.
b. Shall be environmental compensated with differential sensing for reliable, stable, and drift- free sensitivity.
c. Shall use magnet- activated test/reset sensor switches.
d. Shall have tool- less connection terminal access.

Subject to change without notice. Printed in U.S.A. 5846585-YTG-A-1119


Copyright © 2019 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing