Materials System Specification

16-SAMSS-510 22 May 2012


Manually Operated Pad Mounted
SF6 Switchgear: 1 kV to 36 kV
Document Responsibility: Electrical Substations Equipment Standards
Committee

Saudi Aramco DeskTop Standards


Table of Contents

1 Scope............................................................ 2
2 Conflicts and Deviations............................... 2
3 References.................................................... 2
4 Vendor Experience....................................... 3
5 Information Required with Quotation............ 4
6 Service Conditions........................................ 4
7 General Requirements.................................. 4
8 Weatherproof Outer Enclosure..................... 6
9 Switch Way Configuration............................. 8

Data Schedule................................................... 10
Appendix A......................................................... 11

Previous Issue: 14 October 2008 Next Planned Update: 22 May 2017 Page 1 of 11
Primary contact: Ghamdi, Mohammed Ahmed on 966-3-8809667

Copyright©Saudi Aramco 2012. All rights reserved.


Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

1 Scope

1.1 This specification defines the mandatory requirements for outdoor, manually
operated, dead-front, pad-mounted SF6 switchgear assemblies designed,
manufactured and tested to International Electrotechnical Commission (IEC)
Standards or North American (NA) Standards. This equipment is used in
primary distribution loops to provide radial feeds on distribution systems with
nominal voltages up to 36 kV.

1.2 Switchgear in compliance with this specification is housed in metal-enclosed,


free-standing, weatherproof enclosure(s) for outdoor use and contains all
necessary switching, current carrying, control and protection equipment.

1.3 This specification defines switchgear that utilizes fully rated equipment. SF6 gas
is used as the insulating medium. SF6 gas or vacuum is used for interruption.
The bus maybe contained within an SF6 insulted compartment or be insulated
with a solid insulating material. Tape insulation of bus and or bus joints is
unacceptable. The switchgear cable terminations are designed for use with
fully-shielded, dead-front, separable cable connectors.

1.4 This specification defines the basic features of the equipment required and shall
take precedence over all standards and codes as referenced. The equipment
manufacturer shall ensure that the applicable standards are adhered to in
addition to this specification.

2 Conflicts and Deviations

2.1 If there are any conflicts between this Specification and associated purchasing,
project or engineering documents, this specification shall take precedence.

2.2 Direct all requests to deviate from this Specification in writing to the Company
or Buyer Representative, who shall follow internal company waiver procedure.

2.3 The designation "Commentary" is used to label a sub-paragraph that contains


comments that are explanatory or advisory. These comments are not mandatory,
except to the extent that they explain mandatory requirements contained in this
SAMSS.

3 References

The following is a summary of all the documents which have been mentioned within
this Specification. The specific part(s) of these documents which are applicable have
been identified throughout this Specification.

Page 2 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

3.1 Saudi Aramco References

Saudi Aramco Engineering Standard


SAES-P-100 Basic Power System Design Criteria

Saudi Aramco Inspection Requirements


Form 175-162600 Manually-Operated Pad Mounted SF6
Switchgear: 1 kV to 36 kV

Saudi Aramco Forms and Data Sheets


Form NMR-7920 Non-Material Requirements for Disconnect
Switches

Saudi Aramco Materials System Specifications

3.2 Industry Codes and Standards

National Fire Protection Association


NFPA 70 National Electrical Code (NEC)

American National Standards Institute


ANSI/IEEE C37.72 Manually-Operated, Dead-Front Padmounted
Switchgear with Load-Interrupting Switches
and Separable Connectors for AC Systems
ANSI/IEEE C57.12.28 Switchgear and Transformers Pad-Mounted
Equipment - Enclosure Integrity

National Electrical Manufacturers Association


NEMA ICS 6 Enclosures for Industrial Control and Systems

International Electrotechnical Commission


IEC 62271 AC Metal-Enclosed Switchgear up to and
including 52 kV
IEC 60529 Degrees of Protection Provided by Enclosures
IEC 60227 Polyvinyl Chloride Insulated Cables of Rated
Voltages up to and Including 450 / 750 V

4 Vendor Experience

Designs and materials used shall have a minimum of two (2) years of verifiable, proven
field experience.

Page 3 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

5 Information Required with Quotation

The following is a list of the information which shall be supplied with the Quotation:

5.1 A detailed listing of all deviations from this standard with an explanation against
each item. In addition, written certification shall be provided that the proposed
equipment shall fully comply with all other items within this Standard.

5.2 Completed Data Schedule 2.

6 Service Conditions

6.1 The pad-mounted switchgear assembly shall be for outdoor application, and
shall be designed for mounting on a precast concrete pad/foundation.

6.2 Unless otherwise specified it shall be suitable for continuous operation at


locations up to an altitude of 1000 meters.

6.3 Unless otherwise specified this equipment shall be suitable for use in locations
that are subject to sand and dust storms, fog, and airborne contaminants,
including NaCl (Sodium Chloride) to 300 ppm and MgCl (Magnesium Chloride)
to 50 ppm.

6.4 Unless otherwise specified, equipment shall be suitable for use in locations with
the following ambient temperatures: Average monthly normal maximum
(hottest month), 45°C; Average daily temperature (hottest month), 40°C;
Maximum daily peak 50°C.

7 General Requirements

7.1 This specification shall take precedence over any referenced third party
document(s).

7.2 Refer to Section 2 for direction on conflict resolution between documents. For
example, if there are any conflicts between this Specification and associated
project or engineering documents, this specification shall take precedence.

7.3 Whenever this specification requires compliance to a third party document (e.g.,
ANSI, IEC, etc.), that document shall be the edition which was in effect on the
date of the Quotation Request.

7.4 All documentation shall be in the English language.

7.5 The Buyer's inspection requirements are presented within Saudi Aramco Form
175-162600. This form is included with the Quotation Request or the Purchase
Order documents.

Page 4 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

7.6 The Buyer's nonmaterial requirements are presented within Saudi Aramco Form
NMR-7920. This form is included with the Quotation Request or the Purchase
Order documents.

7.7 The switchgear supplied under this specification shall be furnished with
appropriate bushings suitable for use with fully-shielded, dead-front, non-load-
break, 600 amp minimum separable connectors. Bushings must be supplied
with removable fixing studs, with SAE 5/8-11 UNC threads for fastening the
connector in position. (SAE-Society of Automotive Engineers; UNC-Unified
National Coarse).

Space shall be provided within the enclosure/cable covers for the termination of
two cables per phase on the loop feed switches.

All cables shall be horizontally isolatable.

7.8 The switchgear assembly shall have a specifically designed pressure-relief


feature. It shall not rely on fortuitous relief by burn-through or overpressure
induced failure of the basic switchgear structure.

7.8.1 The manufacturer shall provide evidence of pressure-relief operation


which ensures consistent performance at design overpressure and ensures
physical integrity of the basic switchgear enclosure during and
immediately after internal arcing at the rated short circuit current,
voltage and duration.

7.8.2 Tests to establish internal arc performance shall be performed at, or


endorsed by, an independent laboratory in general compliance with the
internal arcing criteria of IEC 62271-Annex AA. Test evidence must be
approved by the Electrical Standards Committee Chairman before
purchase.

7.8.3 Vent ducting is required to direct internal arc products from the
switchgear tank(s) through the rear, side wall, or bottom of the outer,
weatherproof enclosure.

7.9 For grounding purposes, a minimum 6 mm x 50 mm copper ground bus shall be


provided which runs the full length of the switchgear assembly, suitably
positioned to allow grounding of the switchgear frame and cable shields. The
ground bus shall be bonded to the base frame. Provisions shall be made on the
ground bus for connecting cable shields and armors, grounding conductors, and
ground rods.

Page 5 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

7.10 Operating handles shall be provided and be located in a proper storage mounting
arrangement. The operating mechanism shall be pad-lockable in the OFF and
GROUND positions.

7.11 Each Way shall be provided with three (3) positions: ON-OFF-GROUND. The
"ON" and "GROUND" positions shall be rated for momentary (close & latch)
and short time current withstand. The switch mechanism shall be constructed in
such a way that only one action at a time can be taken, so that switching from
"ON" directly to "GROUND" will be prevented. Switching shall be from "ON"
to "OFF" then from "OFF" to "GROUND". Separate interlocked switches and
selectors may be provided to meet the above requirements.

7.12 The circuit breaker, load-break and ground switch functions shall be stored-
energy, spring-operated, to provide fast and reliable operation. The speed of
operation of the switch shall be independent of the operator. When a separate
selector is provided the switching device must be mechanically interlocked so
that it can only be operated (Closed) when the selector is in a determinate
position (ON/OFF/Ready to Earth).

7.13 Springs and moving parts of the switch operating mechanism(s) shall be located
inside the weatherproof enclosure protected from environmental conditions.

7.14 Viewing windows and/or indicators positively driven by direct linkage, clearly
delineating the "CLOSED", "OPEN" and "GROUND" positions are required.

7.15 A permanent mimic bus diagram shall be provided to represent the equipment
single-line configuration. This shall be mounted on the operating face of the
equipment.

7.16 Low voltage wiring shall be ANSI/NFPA 70; Type SIS, XHHW or
THHN/THWN or 85° rated meeting the requirements of IEC 60227.

7.17 Cable potential detection system shall be provided.

8 Weatherproof Outer Enclosure

8.1 The enclosures for outdoor use shall be NEMA ICS 6 Type 3 or IEC 60529
Type IP54, fabricated from a minimum of 2 mm (14 gage) sheet steel. The
enclosure door(s) shall be provided with pad-lockable handles.

Commentary Note:

This enclosure shall be used for the protection of switchgear not inherently
designed for use outdoor which includes equipment intended for subsurface use.

Page 6 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

8.2 The base frame of the enclosure shall be made of hot-dipped galvanized steel.
The switchgear shall be fixed to this base. The assembly shall be adequately
braced to provide strength and rigidity under normal operating conditions and
during transportation.

8.3 Bolts, hinges, and associated hardware shall be Type 300 Series stainless steel.
Gasketing materials and adhesives shall be suitable for the environmental
conditions specified in Section 5.

8.4 The enclosure/switchgear assembly shall be suitable for mounting on a concrete


pad or foundation by means of anchor bolts.

8.5 The enclosure assembly structure shall be provided with adequate lifting or
jacking means and shall be capable of being lifted or slid into position.

8.6 All exterior and interior surfaces of the equipment shall be painted and shall
meet the requirements of ANSI/IEEE C57.12.28 -Pad Mounted Equipment-
Enclosure Integrity, Section 5 -Enclosure Coating System, except the paint color
shall be white, or light gray unless otherwise specified. A wet paint process is
described in the paint system requirements of ANSI/IEEE C57.12.28. However,
an equivalent coating system utilizing an electrostatic powder coating process is
acceptable.

8.7 The weatherproof enclosure shall be suitable for severe corrosive environment
locations as noted below when specified in the Data Schedule and shall be
manufactured of 300 series stainless steel.
Commentary Note:

The following locations are deemed as "severe corrosive environments" for the
purposes of selection of electrical equipment:

 Outdoor offshore locations

 Outdoor onshore locations within one kilometer from the shoreline of the
Arabian Gulf

 Outdoor onshore locations within three kilometers from the shoreline of the
Red Sea.

 All of the Ras Tanura Refinery and Terminal.

8.8 A nameplate shall be permanently attached on the front of the switchgear


assembly, not the inside of the weatherproof enclosure.

8.8.1 The nameplates shall be stainless steel and attached with stainless steel
hardware. Entries shall be marked by etching, engraving or other
permanent marking method.

Page 7 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

8.8.2 The nameplates shall be in the English language according to American


usage.

8.8.3 Danger and warning labels shall be written in both Arabic and English,
utilizing white characters on a red background. If specifically noted
Arabic warning indicators will be supplied by others.

8.9 In addition to the standard switchgear data the nameplate information shall
include the following, which may be on a separate plate:

a) Buyer's Purchase Order number


b) Manufacturer's location
c) Manufacturer's order reference number
d) Equipment Serial Number
e) Date of Manufacture

9 Switch Way Configuration

9.1 Switching Device Variations

Switching Devices as specified in the DATA SCHEDULE shall include the


option of:

 Load-break Switches, and/or;


 Circuit Breakers (including control and protection equipment).

9.2 Load-break Switches

Load-break switches shall comply with the requirements of this specification as


described in Sections 6 and 7.

9.3 Circuit Breakers

9.3.1 Circuit breakers shall be provided in combination with three (3) position
disconnect switch as specified in Sections 6 and 7.

9.3.2 When compliance to Appendix A is specified, requests for alterative


manufacturers, models or functional application requires concurrence of
the Standards Chairman. Refer to SAES-P-100 for the factors that will
be considered when evaluating the request for alternatives to Appendix
A.

9.3.3 A solid-state protection package shall be as specified in Appendix A or


equipment manufacture's equivalent. This protection package shall be
suitable for service in environmental conditions as described in Section

Page 8 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

5. The protection shall be self-powered from the current provided by the


protection Current Transformers (CT's).

9.4 Cable Fault Detectors

When specified in the Data Schedule cable fault detectors shall be provided for
loop feed applications. As a minimum, two (2) sets shall be supplied, each set
shall comprise two (2) short circuit elements and one (1) ground fault element
together with all necessary controls and indication (NORTROLL-
CABLETROLL 2000 or equivalent). Cable fault detection shall be indicated by
red color LEDs.

Revision Summary
16 May 2007 Major revision.
14 October 2008 Editorial revision to replace Electrical Substations Equipment Standards Committee
Chairman and Vice Chairman.
22 May 2012 Editorial revision to update the next planned update and change primary contact.

Page 9 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

Data Schedule
Attachment to Specification 16-SAMSS-510
Manually-Operated Pad Mounted SF6 Switchgear: 1 kV to 36 kV
Minimum Ratings Vendor's
Description
(Select Value) Proposed Values
Rated Voltage 15 kV 15 kV 15 kV 36 kV

Rated Continuous Current 600 A 600 A 1200 A 1200 A

Rated Load Break Current 600 A 600 A 1200 A 1200 A

Short Time Withstand Current 1


sec. 21 kA 25 kA 31.5 kA 25 kA

Short Time Making Current 52.5 kA 62.5 kA 79 kA 62.5 kA

Interrupting Current Rating


(Circuit Breaker only) 21 kA 25 kA 31.5 kA 25 kA

Impulse Withstand BIL(min) 95 kV 95 kV 95 kV 150 kV

Power Frequency Withstand


Voltage AC (1 min) 35 kV 35 kV 35 kV 80 kV

Manufacturer -------- -------- -------- --------


Model/Type -------- -------- -------- --------
Manufacturing Location -------- -------- -------- --------

Switchgear Location Standard Environment


Severe Corrosive environment

Cable Termination Compartment Required Yes ______ No ______

____________________________________________________________________________________________

Required Switch Way Configuration

Position Load-Break Circuit Cable Fault


(From Front Left) Switch Breaker Detectors

1 _________ _________ _________


2 _________ _________ _________
3 _________ _________ _________
4 _________ _________ _________
5 _________ _________ _________
6 _________ _________ _________

Page 10 of 11
Document Responsibility: Electrical Substations Equipment 16-SAMSS-510
Issue Date: 22 May 2012 Manually Operated Pad Mounted
Next Planned Update: 22 May 2017 SF6 Switchgear: 1 kV to 36 kV

Appendix A
Acceptable Protective Devices
Packaged Switchgear Relays
Manufacturer's
Type Protection Manufacturer ANSI Function #
Number
HV Phase Overcurrent for ABB or 7SJ45 with 4MC63 or
Siemens Packaged Switchgear Siemens 4MC703 current 50/51
only. transformers
Ground Overcurrent for ABB or 7SJ457SJ45 with
Siemens Packaged Switchgear Siemens 4MC63 or 4MC703 50/51N
only. current transformers
Feeder protection for Merlin Gerin
Merlin Gerin VIP300 50/51/50N/51N
packaged switchgear only.

Page 11 of 11